MGE UPS Systems 250A User Manual

Page 1
www.mgeups.com
Galaxy 3000
10 - 30 kVA
MGE UPS SYSTEMS
Power Management Module
250A
Installation and user manual
M
M
P
R
E
D
I
V
O
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
E
T
N
I
N
U
E
H
T
34020201EN/AB - Page 1
Page 2
Page 2 - 34020201EN/AB
Page 3
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Power Management Module (PMM) has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your new equipment.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. The considerable resources put into developing the Power Management Module make it a reference in terms of environmental protection. Of particular importance are:
the eco-design approach during product development, recycling of the Power Management Module at the end of its service life.
MGE UPS SYSTEMS warrants this hardware product against defects in materials and workmanship for a period of one year.
Limitation of warranty: the above warranty shall not apply to defects resulting from: misure, non-MGE UPS SYSTEMS modification, operation or storage outside the environmental specifications for the product, improper maintenance, or defects resulting from use of non-MGE UPS SYSTEMS software, accessories, -media or such items not designed for use with the product. Moreover, the warranty does not include the consumable goods and the replacements or repairs which would result from the abnormal wear of the products, and deteriorations or accidents coming from an external cause such as fire, damage of water, damage caused by other equipment...
We invite you to discover the entire MGE UPS SYSTEMS range of products and services including the options for the Power Management Module by visiting our Web site at www.mgeups.com or by contacting your nearest sales representative.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by MGE UPS SYSTEMS.
This document may be copied only with the written consent of MGE UPS SYSTEMS. Authorized copies must be marked "Power Management Module User Manual nr 3402020100".
34020201EN/AB - Page 3
Page 4
Foreword
Structure of this document
Information may be found via:
the contents, the index.
Symbols
Mandatory instructions
General instructions, advice, help
Indication
Action
Earth cables
Other cables
Page 4 - 34020201EN/AB
Page 5
Contents
1. Presentation
1.1 250 A PMM modules .................................................................................................................... 6
1.2 Access to the circuit breakers ................................................................................................... 7
Version with 126 circuit breakers (doors open)............................................................................... 7
Version with 60 circuit breakers (doors open)................................................................................. 7
1.3 Access to connections ............................................................................................................... 8
1.4 Control panel ................................................................................................................................. 8
2. Installation
2.1 Setting up the module .................................................................................................................. 9
Module 825 mm deep ..................................................................................................................... 9
Module 425 mm deep ................................................................................................................... 10
2.2 Input power connections ........................................................................................................... 12
2.3 Output circuit connections ........................................................................................................ 14
2.4 Alarm and remote shutdown connections ............................................................................... 14
2.5 Communication connections..................................................................................................... 15
3. Operation
3.1 Turning on the PMM module ...................................................................................................... 16
3.2 Display ......................................................................................................................................... 16
3.3 Metering ....................................................................................................................................... 16
Output-circuit metering.................................................................................................................. 17
General metering .......................................................................................................................... 17
3.4 Alarms .......................................................................................................................................... 17
3.5 Setup ............................................................................................................................................ 18
Communication settings................................................................................................................ 18
Operation settings (display and alarms) ....................................................................................... 18
3.6 Turning off the PMM module ...................................................................................................... 18
4 Maintenance
4.1 Trouble-shooting and solutions ................................................................................................ 19
5 Environment .................................................................................................................................... 20
6. Appendices
6.1 Technical data sheets ................................................................................................................. 21
Electrical characteristics ............................................................................................................... 21
Thermal characteristics ................................................................................................................. 21
Noise level .................................................................................................................................... 21
Maximum wire sizes for terminal blocks ....................................................................................... 21
Recommended upstream protection devices................................................................................ 21
Standards...................................................................................................................................... 21
6.2 Simplified diagrams .................................................................................................................... 22
Version with isolation transformer ................................................................................................. 22
Version without isolation transformer ............................................................................................ 22
6.3 Auxiliary contact functions ........................................................................................................ 23
6.4 Modbus communication information ........................................................................................ 23
Access to communicated information ........................................................................................... 23
Cards BCM1, BCM2 and BCM3 (status and measurements for 42 or 21 output circuits) ............ 24
Card MCM (general status and measurements) ........................................................................... 31
6.5 Glossary....................................................................................................................................... 32
6.6 Index............................................................................................................................................. 33
34020201EN/AB - Page 5
Page 6
1. Presentation
1.1 250 A PMM modules
You can choose from 6 different modules depending on:
the number of output circuits required and the type of protection (126 standard circuit breakers or 60 circuit breakers with
earth-leakage protection),
the presence of an isolation transformer, the depth (825 with or without an isolation transformer and 425 without).
1
Control panel with display
M
M
P
Page 6 - 34020201EN/AB
Module characteristics
Number of circuits
126 126
126 60 (with EL protection) 60 (with EL protection) 60 (with EL protection)
Isolation
transformer
Yes
No No
Yes
No No
Depth
in mm
825 825 425 825 825 425
Width in mm
1215 1215 1215 1215 1215 1215
Height in mm
1900 1900 1900 1900 1900 1900
Weight
in kg
900 350 300 900 350 300
Page 7
1.2 Access to the circuit breakers
Version with 126 circuit breakers (doors open)
1. Presentation
I 0
A-01 A-03 A-05 A-07 A-09 A-11 A-13 A-15 A-17 A-19 A-21 A-23 A-25 A-27 A-29 A-31 A-33 A-35 A-37 A-39 A-41
I 0
A-02
I
Q2
0
I
Q1
0
A-04 A-06 A-08 A-10 A-12 A-14 A-16 A-18 A-20 A-22 A-24 A-26 A-28 A-30 A-32 A-34 A-36 A-38 A-40 A-42
I 0
I 0
B-01 B-03 B-05 B-07 B-09 B-11 B-13 B-15 B-17 B-19 B-21 B-23 B-25 B-27 B-29 B-31 B-33 B-35 B-37 B-39 B-41
B-02 B-04 B-06 B-08 B-10 B-12 B-14 B-16 B-18 B-20 B-22 B-24 B-26 B-28 B-30 B-32 B-34 B-36 B-38 B-40 B-42
I 0
I 0
C-01 C-03 C-05 C-07 C-09 C-11 C-13 C-15 C-17 C-19 C-21 C-23 C-25 C-27 C-29 C-31 C-33 C-35 C-37 C-39 C-41
C-02 C-04 C-06 C-08 C-10 C-12 C-14 C-16 C-18 C-20 C-22 C-24 C-26 C-28 C-30 C-32 C-34 C-36 C-38 C-40 C-42
2
F1 disconnector-fuse for protection of the control electronics
3
F2 disconnector-fuse for protection of the voltage measurement inputs
6
2 x 21 circuit breakers for phase A (A-1 to A­41 and A-2 to A-42)
2 x 21 circuit breakers for phase B (B-1 to B-
7
41 and B-2 to B-42)
8
2 x 21 circuit breakers for phase C (C-1 to C-41 and C-2 to C-42)
9 Eight connection cover panels
4
General protection circuit breaker for the 126 output circuits
5
Upstream general protection circuit breaker (only in modules with an isolation transformer)
Version with 60 circuit breakers (doors open)
I 0 I 0 I 0
A-01
A-03
A-05
A-07
A-09
A-11
A-13
A-15
A-17
A-19
I 0 I 0 I 0
I
Q2
0
I
Q1
0
A-02
A-04
A-06
A-08
A-10
A-12
A-14
A-16
A-18
A-20
B-01
B-03
B-05
B-07
B-09
B-11
B-13
B-15
B-17
B-19
B-02
B-04
B-06
B-08
B-10
B-12
B-14
B-16
B-18
B-20
C-01
C-03
C-05
C-07
C-09
C-11
C-13
C-15
C-17
C-19
C-02
C-04
C-06
C-08
C-10
C-12
C-14
C-16
C-18
C-20
2
F1 disconnector-fuse for protection of the control electronics
3
F2 disconnector-fuse for protection of the voltage measurement inputs
2 x 10 circuit breakers with earth-leakage
6
protection for phase A (A-1 to A-19 and A-2 to A-20)
2 x 10 circuit breakers with earth-leakage
7
protection for phase B (B-1 to B-19 and B-2 to B-20)
2 x 10 circuit breakers with earth-leakage
8
protection for phase C (C-1 to C-19 and C-2 to C-20)
Eight connection cover panels
9
4
General protection circuit breaker for the 60 output circuits
5
Upstream general protection circuit breaker (only in modules with an isolation transformer)
34020201EN/AB - Page 7
Page 8
1. Presentation
1.3 Access to connections
Remove the eight cover panels (each secured with two screws).
Example showing the version with 126 output circuits:
Q2
10
11
12
13
14
Phase connections for output-circuit cables
Metal trunking for passage and securing of output cables
Connection bars for earth wires of output cables
Terminal block for remote shutdown function and minor and major alarms
In modules without an isolation transformer, connection of the three input phases and the neutral to circuit breaker Q2
Q1
1.4 Control panel
CRITICAL POWER MONITORING SYSTEM
NEXT PARAMETER
MGE UPS SYSTEMS
Ph-A CH01 2.637 BCM CH02 4.215
SETUP MODE
DOWNUP SELECT METER
PREVIOUS PARAMETER
HOLD READING
ALARM MENU
SCROLL METERS
15
16
17
18
22
21
In modules with an isolation transformer, of the three input phases to circuit breaker Q1
Main earthing bar of the module
System status LED: see table on page 23
Alphanumeric display
Scroll through different types of measurements or return to display of measurements
Scroll through different system settings
Page 8 - 34020201EN/AB
20
19
Previous measurement or setting
Next measurement or setting
Page 9
2.1 Setting up the module
Module 825 mm deep
400 mm
2. Installation
1. Install the lower base panels 23 on the sides that will not be accessible (not mandatory).
2. Position the module.
3. Level the module using the adjustable feet 24 .
4. Install the lower base panels 23 on the
visible sides.
Connection cables run under the false floor or in a cable trough.
Rear of module
1076
4 feet, diameter 40 mm
M
M
P
720 mm
Important. At least 400 mm of free space is required above the module to ensure correct ventilation. At least 720 mm of free space is required in front to open the doors.
23 24 23
Footprint of module
69.569.5
6767
Weight exerted on the floor by the four feet:
28 kg/cm up to 72 kg/cm
2
(module without transformer),
2
(module with transformer).
676
8282
Front of module
34020201EN/AB - Page 9
Page 10
2. Installation
Module 425 mm deep
Installation against a wall
25
1685,5
Caution: during handling, make sure the module does not fall over.
1. Turn to horizontal position the two brackets 25 at the back used to secure the module (see figure).
2. Install the rear base panel 23 (not mandatory).
26
400 mm
3. Position the module.
4. Level the module using the adjustable feet 24 .
1250
5. Attach the module to the wall using the
two rear brackets.
6. Install the base panels 23 on the sides
and front.
7. Remove the bracket 26 on the top of the
module (used only for back-to-back assembly of two modules) and retighten the fixing screw.
276
Rear of module
1076
4 feet, diameter 40 mm
M
M
P
720 mm
Connection cables run under the false floor or in a trough.
Important: At least 400 mm of free space is required above the module to ensure correct ventilation. At least 720 mm of free space is required in front to open the doors.
23 24
23
24 23
Footprint of module
69.569.5
6767
Force exerted on the floor by the four feet:
28 kg/cm
2
.
Page 10 - 34020201EN/AB
8282
Front of module
Page 11
Back-to-back assembly
25
26
2. Installation
Caution: during handling, make sure the modules do not fall over.
1. Remove the brackets 25 on the back of the module (used only for securing the module to a wall) and retighten the fixing screws.
25
2. Position the modules and use the brackets 26 on the top to interconnect the two modules (see figure).
720 mm
860 mm
400 mm
M
M
P
720 mm
26
26
3. Level the modules using the adjustable feet 24 .
4. Install the base panels 23 on the sides and fronts.
Important: At least 400 mm of free space is required above the module to ensure correct ventilation. At least 720 mm of free space is required in front to open the doors.
23
23
24 23
34020201EN/AB - Page 11
Page 12
2. Installation
2
1
4
5
BCA
Q1
333
PE / PEN
4
1
BC
Q2
2
333
5
3
N
A
2.2 Input power connections
Specifications for protection devices and cables are provided in section 6 (Appendices, technical data sheet). To access the connections, see section 1.3. Connection cables are not supplied.
Q2
Module with isolation transformer
1. Connect the PE or PEN protection cable
to the earthing bar at the bottom of the module.
2. Remove the bottom cover on circuit
breaker Q1.
3. Connect the three phases of the input
power cable to the bottom terminals of circuit breaker Q1 (without removing the control wires that are already connected).
4. Ties the cables to the earthing bar.
5. Refit the bottom cover on circuit breaker
Q1.
Q1
Module without isolation transformer, separate earth and neutral (TNS system)
1. Connect the PE protection cable to the
earthing bar at the bottom of the module.
2. Remove the bottom cover on circuit
breaker Q2.
3. Connect the three phases and the neutral
of the input power cable to the bottom terminals of circuit breaker Q2 (without removing the control wires that are already connected).
4. Ties the cables to the earthing bar.
5. Refit the bottom cover on circuit breaker
Q2.
Q2
Page 12 - 34020201EN/AB
BCNA
PE
Page 13
Q2
5
BCA
14
N
PEN
BC
Q2
2
433
6
3
N
A
2. Installation
Module without isolation transformer, combined earth and neutral (TNC system)
1. Connect the PEN protection cable to the earthing bar at the bottom of the module.
2. Remove the bottom cover on circuit breaker Q2.
3. Connect the three phases of the input power cable to the bottom terminals of circuit breaker Q2 (without removing the control wires that are already connected).
4. Use a cable (not supplied) to connect the neutral connector on the lower part of circuit breaker Q2 to the earthing bar.
5. Ties the cables to the earthing bar.
6. Refit the bottom cover on circuit breaker Q2.
34020201EN/AB - Page 13
Page 14
1
2
345
6
2. Installation
1
2
2
3
Ph
N
2.3 Output circuit connections
Q2
It is advised to use crimped ferrules on the phase wires and lugs on the earth wires.
1. Connect the earth wire of each output
cable to the earth connection bar located to the left of the metal trunking.
2. Connect the phase and neutral wires to
each circuit breaker.
3. Tie the cables to the metal trunking.
Note: it is advised to make the connections from the top down.
Q1
2.4 Alarm and remote shutdown connections
13
1. Connect the NO remote shutdown contact
to terminals 1 and 2 on terminal block 13 .
2. The alarm signals are transmitted by dry
contacts (Umax = 250 V AC / 30 V DC, Imax = 7 A AC / 10 A DC) between terminals 3 and 4 for the type 1 alarm and between 5 and 6 for the type 2 alarm.
3. Tie the cable down to the module frame.
Page 14 - 34020201EN/AB
3
Q2
Q1
3
Remote shutdown
1
2
Type 2 alarm Type 1 alarm
Warning: the remote shutdown function is not implemented using a very low safety voltage. Consequently, the usual safety measures must be taken to avoid all risk of electrical shock when making connections for this function.
Page 15
2.5 Communication connections
2
Q2
3
RS-232
RS-485
1
2. Installation
1. Connect the communication cable to the RS232 or RS485 connector on the right­hand door of the module.
2. Run the cable as shown in the figure opposite.
3. Tie the cable down to the module frame.
Q1
Communication connector details
RS-232
9
12345
6
8
7
RS232 connector
Td (from the PMM display) Rd (to the PMM display)
GND
RS-485
54321
RS485 connector 2 wires
GND Not used Not used Tx+ / Rx+ Tx- / Rx-
RS485 connector 4 wires
GND Tx+ Tx­Rx+ Rx-
Example of an RS485 2-wire connection:
Tx- / Rx-
Tx+ / Rx+
GND
54321
Example of an RS485 4-wire connection:
Master SlaveMaster or slave
Rx-
Rx+
Tx-
Tx+
GND
Rx-
Rx+
54321
GND
Tx-
Tx+
54321
34020201EN/AB - Page 15
Page 16
3. Operation
3.1 Turning on the PMM module
1. Close the upstream switching device (external and not supplied) on the circuit supplying the PMM module.
2. In a module with an isolation transformer, close ("I" or ON position) circuit breaker Q1 5 (see page 7) .
3. Make sure disconnector-fuses F1 and F2 are closed and close ("I" or ON position) circuit breaker Q2 5 (see page 7) .
The system status LED 17 (see page 8) flashes yellow a few seconds, then green and should subsequently remain
green.
After a few seconds, the first page of measurements is displayed:
Ph-A CH01 0.000
BCM CH02 0.000
4. Close the circuit breakers on the output circuits to be powered.
3.2 Display
The display unit for the PMM module offers three operating modes: metering, alarm and setup.
Metering mode
DOWN
UP
This is the default mode.
Ph-A CH01 0.000
BCM CH02 0.000
UP
DOWN
Ph-B CH01 0.000
BCM CH02 0.000
UP
DOWN
BCM CH42 0.000
METER
BCM CH42 0.000
+
SELECT
+
Ph-B CH25 WARNING
Ph-C CH12 ALARM
METER
Alarm mode Setup mode
UP
UP
SELECT
SELECT
Enter Password : * * * * * *
DOWN
DOWN
View System Info
UP
SELECT
UP
UP
METER
Ph-C CH01 0.000
BCM CH02 0.000
UP
DOWN
METER
GENE KWH 0000.0
MCM KW 0000.0
UP
DOWN
BCM CH42 0.000
MCM MAX 0000.0
METER
METER
METER
GENE OVER
MCM VOLTAGE
UP
GENE OVER
MCM CURRENT
UP
AUX INPUT
ALARM
UP
SELECT
SELECT
Find Meters
UP
Review Meters
UP
Setup Communication
UP
Setup Operation
UP
Page 16 - 34020201EN/AB
Page 17
3.3 Metering
Output-circuit metering
3. Operation
Ph-A: measurements on phase A CH-01: measurements on output circuit 01
Ph-A CH01 0.000
BCM CH02 0.000
General metering
GENE KWH 0000.0
MCM KW 0000.0
KVA: apparent power drawn by the PMM module in kVA. PF: average power factor on the three phases of the PMM module. V-LL: average phase-to-phase voltage on the three phases of the PMM module in volts. V-LN: average phase-to-neutral voltage on the three phases of the PMM module in volts. AMPS: average current on the three phases of the PMM module in amperes. FREQ: frequency of the voltage supplied by the PMM module in Hertz. KW-A, KW-B, KW-C: active power drawn by phases A, B and C of the PMM module in kW. PF-A, PF-B, PF-C: power factor on phases A, B and C of the PMM module. V-AB, V-BC, V-AC: phase-to-phase voltages supplied by the PMM module in volts. V-AN, V-BN, V-CN: phase-to-neutral voltages supplied by the PMM module in volts. AMPA, AMPB, AMPC, AMPN: current on the three phases A, B, C and on the neutral of the PMM module in amperes. MIN: minimum power (stored in memory) supplied by the PMM module in kW since the last reset. MAX: maximum power (stored in memory) supplied by the PMM module in kW since the last reset.
The minimum, maximum and average power values are reset via the communication function.
Display of the current drawn by the output circuit in amperes
GENE: general measurements. Measurement units:
KWH: total energy consumed by the PMM module in kWh. This value can be reset via the communication function.
KW: total active power drawn by the PMM module in kW. KVAR: reactive power drawn by the PMM module in kVAR.
3.4 Alarms
SELECT
The
rotation). The display flashes and the measurement is not updated.
Access alarm mode by pressing simultaneously the
This mode displays the list of stored major and minor faults that have occurred in the PMM or on the output circuits. When an alarm is present in the memory, LED 17 goes on:
yellow for fault that does not hinder normal operation; ◗ red for a fault requiring intervention.
Ph-B CH25
WARNING
ALARM: indicates that the current on the indicated circuit is higher than 80% of the maximum value. OVER VOLTAGE: the voltage supplied by the PMM exceeds the permissible range by over 10%. OVER CURRENT: there is an overload on the PMM. AUX INPUT ALARM: this alarm signals either:
excessive temperature rise in the isolation transformer, or activation of the remote shutdown button.
button may be used to hold the display of a measurement if the module is set up for autoscrolling (parameter
SELECT
Ph-B: alarm on phase B. CH-25: alarm on output circuit 25.
Alarm text: WARNING: indicates that the current on the indicated circuit (number 25, phase B) is between 60 and 80% of the maximum value.
+
METER
buttons.
These alarms are stored in memory:
Press the
Press the
The display automatically returns to metering mode if buttons 19 to 22 are not used for ten seconds.
SELECT
button to clear the displayed alarm.
METER
button to return to metering mode.
34020201EN/AB - Page 17
Page 18
3. Operation
3.5 Setup
Access setup mode by pressing simultaneously the
SELECT
DOWN DOWN
SELECT
UP UP
This mode presents the functions listed below.
View System Info, Find Meters and Review Meters : these functions are reserved for MGE UPS SYSTEMS. Setup Communication : access to the communication settings. Setup Operation : access to the display settings (luminosity, autoscroll) and selection of the alarm operating mode (open
or closed contacts).
The display automatically returns to metering mode if buttons are not used for ten seconds.
Communication settings
Settings include:
Routing Address (ON, OFF): internal setting reserved for MGE UPS SYSTEMS, must not be modified (ON). Modbus Address (1 to 225): Modbus address, must be selected from 1 to 225 (by steps of 16). Upstream Type (RS-485, RS-232, INFRARED): type of serial link. Upstream Duplex (2-WIRE, 4-WIRE): 2 or 4-wire link. Upstream Baudrate (2400, 4800, 9600, 19200): speed of transmission in Bauds. Upstream Parity (NONE, ODD, EVEN): parity. Downstream Duplex: internal setting reserved for MGE UPS SYSTEMS, must not be modified (2-WIRE). Downstream Baudrate: internal setting reserved for MGE UPS SYSTEMS, must not be modified (9600). Downstream Parity: internal setting reserved for MGE UPS SYSTEMS, must not be modified (NONE).
Operation settings (display and alarms)
The user-settable parameters are listed below.
Blacklight Brightness (0 to 9): adjustment of the display luminosity. Auxiliary INPUT ALARM: internal setting reserved for MGE UPS SYSTEMS, must not be modified (CLOSED). Rotate parameters (NO, YES) : fixed display or autoscroll.
+
DOWN
buttons and then entering the password:
UP
.
3.6 Turning off the PMM module
1. Open ("O" or OFF position) all the circuit breakers on the output circuits.
2. Open ("O" or OFF position) circuit breaker Q2 4 .
3. In a module with an isolation transformer, open ("O" or OFF position) circuit breaker Q1 5 .
4. Open the upstream switching device of the installation on the circuit supplying the PMM. LED 17 and the display go off.
Caution: dangerous voltage levels are present inside the PMM, even if Q1 and Q2 are open.
Page 18 - 34020201EN/AB
Page 19
4.1 Trouble-shooting and solutions
4. Maintenance
Alarm
WARNING
ALARM
OVER VOLTAGE
OVER CURRENT
AUX INPUT ALARM
Fault
No display
Incoherent measurement values
LED 17 yellow
LED 17 red
Meaning
The current on the indicated output circuit is between 60 and 80% of the maximum value for the circuit.
The current on the indicated output circuit is higher than 80% of the maximum value for the circuit.
The voltage on the distribution system is high.
The load on the PMM module is higher than 250A.
Temperature rise in the isolation
transformer.
Activation of the remote shutdown function.
Possible Causes
Fuses F1 blown, Disconnector-fuse F1 open.
Fuses F2 blown, Disconnector-fuse F2 open.
The current on at least one output circuit is between 60 and 80% of the maximum value for the circuit.
One of the following:
The current on at least one output circuit is
higher than 80% of the maximum value for the circuit,
Overvoltage (>457V), Overcurrent (>250A), Transformer temperature too high, Actuation of remote shutdown function.
Action
Monitor the power drawn on the circuit and avoid adding other loads to the circuit.
Turn off certain loads connected to the circuit until the fault disappears (after alarm reset).
Monitor the voltage on the distribution system. The connected loads may suffer breakdowns.
Turn off certain connected loads until the fault disappears (after alarm reset).
Check the ventilation system in the room. Shut down the PMM module, then start it
up again when the remote shutdown signal has been cleared.
Action
Call the MGE after-sales technical support, Close disconnector-fuse F1.
Call the MGE after-sales technical support, Close disconnector-fuse F2.
Consult the list of alarms (alarm mode) and reset the alarm.
Consult the list of alarms (alarm mode) and reset the alarm.
34020201EN/AB - Page 19
Page 20
5. Environment
This product has been designed to respect the environment.
It does not contain CFCs or HCFCs.
Recycling at the end of service life
MGE UPS SYSTEMS undertakes to have all products recovered at the end of their service life recycled by certified companies in compliance with applicable regulations (contact your branch office).
Packing materials
Comply with all applicable regulations for recycling of packing materials.
Page 20 - 34020201EN/AB
Web Site: www.mgeups.com
Page 21
6.1 Technical data sheets
Electrical characteristics
Rated input current: 250 A per phase and 400 A for the neutral Rated output current: 16 A per phase Input voltages:
Rated voltage: 380 V / 400 V / 415 V Maximum voltage: 457 V (415 V +10%) Minimum voltage: 342 V (380 V -10%) Rated frequency: 50 or 60 Hz (47 Hz minimum, 63 Hz maximum)
Output voltages: 220 V / 230 V / 240 V F1 and F2 fuses: 0.5 A aM - 600 V - 100 kA
Thermal characteristics
Heat loss (with isolation transformer):
At full rated power: 5000 W At 50% rated power: 2000 W
Noise level
Acoustic noise as defined by standard ISO 3746: 62 dBa (with isolation transformer)
6. Appendices
Maximum wire sizes for terminal blocks
Input phases: 120 mm ◗ Input neutral: 2 x 120 mm ◗ PE: 120 mm ◗ PEN: 2 x 120 mm ◗ Output circuits: 2.5 mmAuxiliary wires (remote shutdown, remote alarms): 1.5 mm ◗ Communication wires: shielded cable (telephone type)
2
2
2
2
2
Recommended upstream protection devices
Upstream system
TNC
TNS
(1) I0 and IR are thermal settings, Ii and Im are magnetic settings.
Number of output
circuits on PMM module
126 output circuits
60 output circuits
126 output circuits
60 output circuits
2
Recommended upstream circuit breaker
Siemens 3VL3725-1DC36-0AA0
Merlin Gerin NS250 TM 250D 3/3 poles protected
Siemens 3VF52-1MH41-0AA0
Merlin Gerin NS400 STR23SE 400 3/4 poles protected
Settings
IR = 1.0 In Ii = 10 In
IR = 1.0 In Im = 10 In
IR = 1.0 In Ii = 10 In
I0 = 0.63 In IR = I
0
Im = 10 I
R
(1)
Standards
Selection of the protection devices must comply with applicable standards and regulations using the information presented above and taking into account discrimination requirements. The models in the table are only intended as a general indication and in no way engage the responsibility of MGE UPS SYSTEMS.
Protection level: IP 20C (standard CEI 529). Environment: 2 (standard EN 60439-1).
34020201EN/AB - Page 21
Page 22
6. Appendices
6.2 Simplified diagrams
Version with isolation transformer
MX
AC input power
Q1 Q2
F1
Remote shutdown
Type 1 alarm
(contact open or closed)
Version without isolation transformer
PMM Module
Control and display electronics
Type 2 alarm
(contact open or closed)
F2
Communication information
(RS232 or RS485)
Output circuits CH01
CH02
CH03
CH42
power
F1
Remote shutdown
MX
Q2
PMM Module
Control and display electronics
Type 1 alarm
(contact open or closed)
Type 2 alarm
(contact open or closed)
F2
Communication information
(RS232 or RS485)
Output circuits CH01AC input
CH02
CH03
CH42
Page 22 - 34020201EN/AB
Page 23
6.3 Auxiliary contact functions
6. Appendices
Normal operation
Downgraded operation
Overload or overvoltage
Other fault
Alarm LED
17
Green
Yellow
Red
Red
Type 1-alarm
contact
OFF
ON
ON
OFF
6.4 Modbus communication information
Access to communicated information
Each status indication or measurement displayed on the module is accessible via the RS232 or RS485 communication port.
Each PMM module uses a series of 16 addresses.
If the network communicates with a number of PMM modules, use an available series among the following series of 16 addresses for each module: 1 to 16 ,17 to 32, 33 to 48, 49 to 64, 65 to 80, 81 to 96, 97 to 112, 113 to 128, 129 to 144, 145 to 160, 161 to 176, 177 to 192, 193 to 208, 209 to 224 and 225 to 241.
The 16 addresses in each series are assigned the following functions: 1st address in the series: reserved for MGE UPS SYSTEMS,
2nd address in the series: access to card BCM1 (status and measurements for output circuits of phase A), 3rd address in the series: access to card BCM2 (status and measurements for output circuits of B), 4th address in the series: access to card BCM3 (status and measurements for output circuits of C),
5th to 8th address in the series: reserved for MGE UPS SYSTEMS, 9th address in the series: access to card MCM (general status and measurements), 10th to 16th address in the series: reserved for MGE UPS SYSTEMS.
As indicated above, four addresses in each series are used to access the information in the registers of four cards, corresponding to all the status and measurement information presented in the tables on the following pages.
Key for tables: # : register using 2 bytes, R/W : read only (R ) or read/write (R/W ) information, Bit : detail of each bit of the address, NV : non-volatile information, Description : description of the concerned information.
Additional explications are provided in the right-hand column if necessary.
Type 2-alarm
contact
OFF
OFF
OFF
ON
Cause
Current on at least one output circuit between 60% and 80% of max. value for the circuit.
Current on at least one output
circuit higher than 80% of max. value for the circuit,
or overvoltage (> 457 V), or overcurrent (> 250 A).
Temperature rise in the isolation
transformer,
or actuation of remote shutdown
function.
Warning: Do not modify the registers reserved for MGE UPS SYSTEMS. Changing these registers can cause the PMM module to malfunction.
34020201EN/AB - Page 23
Page 24
6. Appendices
Cards BCM1, BCM2 and BCM3 (status and measurements for 42 or 21 output circuits of one phase)
All the variables are whole numbers.
# Bit R/W NV Description
1 R Current in circuit 01 2 R Current in circuit 02
... ... ......
... ... ......
41 R Current in circuit 41 42 R Current in circuit 42
43 R NV Global alarm register
0 for the register with address 44 1 for the register with address 45 2 for the register with address 46 3 for the register with address 47 4 for the register with address 48 5 for the register with address 49 6 to 15 Unused bits
44 R/W NV Minor alarms on circuits 1 to 16
0 60% < Current in circuit 01 < 80% 1 60% < Current in circuit 02 < 80% 2 60% < Current in circuit 03 < 80% 3 60% < Current in circuit 04 < 80% 4 60% < Current in circuit 05 < 80% 5 60% < Current in circuit 06 < 80% 6 60% < Current in circuit 07 < 80% 7 60% < Current in circuit 08 < 80% 8 60% < Current in circuit 09 < 80% 9 60% < Current in circuit 10 < 80% 10 60% < Current in circuit 11 < 80% 11 60% < Current in circuit 12 < 80% 12 60% < Current in circuit 13 < 80% 13 60% < Current in circuit 14 < 80% 14 60% < Current in circuit 15 < 80% 15 60% < Current in circuit 16 < 80%
45 R/W NV Minor alarms on circuits 17 to 32
0 60% < Current in circuit 17 < 80% 1 60% < Current in circuit 18 < 80% 2 60% < Current in circuit 19 < 80% 3 60% < Current in circuit 20 < 80% 4 60% < Current in circuit 21 < 80% 5 60% < Current in circuit 22 < 80% 6 60% < Current in circuit 23 < 80% 7 60% < Current in circuit 24 < 80% 8 60% < Current in circuit 25 < 80% 9 60% < Current in circuit 26 < 80% 10 60% < Current in circuit 27 < 80% 11 60% < Current in circuit 28 < 80% 12 60% < Current in circuit 29 < 80% 13 60% < Current in circuit 30 < 80% 14 60% < Current in circuit 31 < 80% 15 60% < Current in circuit 32 < 80%
46 R/W NV Minor alarms on circuits 33 to 42
0 60% < Current in circuit 33 < 80% 1 60% < Current in circuit 34 < 80% 2 60% < Current in circuit 35 < 80% 3 60% < Current in circuit 36 < 80% 4 60% < Current in circuit 37 < 80% 5 60% < Current in circuit 38 < 80% 6 60% < Current in circuit 39 < 80% 7 60% < Current in circuit 40 < 80% 8 60% < Current in circuit 41 < 80% 9 60% < Current in circuit 42 < 80% 10 to 15 Unused bits (all set to 0)
Each element represents the value in mA of the current in the given output circuit.
This register provides a rapid overview of the status of the alarms on the card. The global alarm bit is 1 if any one of the 16 bits of the indicated register is 1.
These bits go to 1 when the current in a corresponding output circuit is greater than the minor alarm threshold (60% in the example opposite) and less than the major alarm threshold (80% in the example opposite). This state is stored in memory until the alarm is reset by setting the bit to 0.
Page 24 - 34020201EN/AB
Page 25
# Bit R/W NV Description
47 R/W NV Major alarms on circuits 1 to 16
0 Current in circuit 01 > 80% 1 Current in circuit 02 > 80% 2 Current in circuit 03 > 80% 3 Current in circuit 04 > 80% 4 Current in circuit 05 > 80% 5 Current in circuit 06 > 80% 6 Current in circuit 07 > 80% 7 Current in circuit 08 > 80% 8 Current in circuit 09 > 80% 9 Current in circuit 10 > 80% 10 Current in circuit 11 > 80% 11 Current in circuit 12 > 80% 12 Current in circuit 13 > 80% 13 Current in circuit 14 > 80% 14 Current in circuit 15 > 80% 15 Current in circuit 16 > 80%
48 R/W NV Major alarms on circuits 17 to 32
0 Current in circuit 17 > 80% 1 Current in circuit 18 > 80% 2 Current in circuit 19 > 80% 3 Current in circuit 20 > 80% 4 Current in circuit 21 > 80% 5 Current in circuit 22 > 80% 6 Current in circuit 23 > 80% 7 Current in circuit 24 > 80% 8 Current in circuit 25 > 80% 9 Current in circuit 26 > 80% 10 Current in circuit 27 > 80% 11 Current in circuit 28 > 80% 12 Current in circuit 29 > 80% 13 Current in circuit 30 > 80% 14 Current in circuit 31 > 80% 15 Current in circuit 32 > 80%
49 R/W NV Major alarms on circuits 33 to 42
0 Current in circuit 33 > 80% 1 Current in circuit 34 > 80% 2 Current in circuit 35 > 80% 3 Current in circuit 36 > 80% 4 Current in circuit 37 > 80% 5 Current in circuit 38 > 80% 6 Current in circuit 39 > 80% 7 Current in circuit 40 > 80% 8 Current in circuit 41 > 80% 9 Current in circuit 42 > 80% 10 to 15 Unused bits (all set to 0)
50 R NV Reserved for MGE UPS SYSTEMS 51 R NV Reserved for MGE UPS SYSTEMS
52 R/W NV Rating of breaker on circuit 01 53 R/W NV Rating of breaker on circuit 02 54 R/W NV Rating of breaker on circuit 03 55 R/W NV Rating of breaker on circuit 04 56 R/W NV Rating of breaker on circuit 05 57 R/W NV Rating of breaker on circuit 06 58 R/W NV Rating of breaker on circuit 07 59 R/W NV Rating of breaker on circuit 08 60 R/W NV Rating of breaker on circuit 09 61 R/W NV Rating of breaker on circuit 10 62 R/W NV Rating of breaker on circuit 11 63 R/W NV Rating of breaker on circuit 12 64 R/W NV Rating of breaker on circuit 13 65 R/W NV Rating of breaker on circuit 14 66 R/W NV Rating of breaker on circuit 15 67 R/W NV Rating of breaker on circuit 16 68 R/W NV Rating of breaker on circuit 17
6. Appendices
These bits go to 1 when the current in a corresponding output circuit is greater than the major alarm threshold (80% in the example opposite). This state is stored in memory until the alarm is reset by setting the bit to 0.
Circuit breaker ratings in amps (16). Must not be modified.
34020201EN/AB - Page 25
Page 26
6. Appendices
# Bit R/W NV Description
69 R/W NV Rating of breaker on circuit 18 70 R/W NV Rating of breaker on circuit 19 71 R/W NV Rating of breaker on circuit 20 72 R/W NV Rating of breaker on circuit 21 73 R/W NV Rating of breaker on circuit 22 74 R/W NV Rating of breaker on circuit 23 75 R/W NV Rating of breaker on circuit 24 76 R/W NV Rating of breaker on circuit 25 77 R/W NV Rating of breaker on circuit 26 78 R/W NV Rating of breaker on circuit 27 79 R/W NV Rating of breaker on circuit 28 80 R/W NV Rating of breaker on circuit 29 81 R/W NV Rating of breaker on circuit 30 82 R/W NV Rating of breaker on circuit 31 83 R/W NV Rating of breaker on circuit 32 84 R/W NV Rating of breaker on circuit 33 85 R/W NV Rating of breaker on circuit 34 86 R/W NV Rating of breaker on circuit 35 87 R/W NV Rating of breaker on circuit 36 88 R/W NV Rating of breaker on circuit 37 89 R/W NV Rating of breaker on circuit 38 90 R/W NV Rating of breaker on circuit 39 91 R/W NV Rating of breaker on circuit 40 92 R/W NV Rating of breaker on circuit 41 93 R/W NV Rating of breaker on circuit 42
94 R/W NV Minor alarm threshold (%) for circuit 01 95 R/W NV Minor alarm threshold (%) for circuit 02 96 R/W NV Minor alarm threshold (%) for circuit 03 97 R/W NV Minor alarm threshold (%) for circuit 04 98 R/W NV Minor alarm threshold (%) for circuit 05 99 R/W NV Minor alarm threshold (%) for circuit 06 100 R/W NV Minor alarm threshold (%) for circuit 07 101 R/W NV Minor alarm threshold (%) for circuit 08 102 R/W NV Minor alarm threshold (%) for circuit 09 103 R/W NV Minor alarm threshold (%) for circuit 10 104 R/W NV Minor alarm threshold (%) for circuit 11 105 R/W NV Minor alarm threshold (%) for circuit 12 106 R/W NV Minor alarm threshold (%) for circuit 13 107 R/W NV Minor alarm threshold (%) for circuit 14 108 R/W NV Minor alarm threshold (%) for circuit 15 109 R/W NV Minor alarm threshold (%) for circuit 16 110 R/W NV Minor alarm threshold (%) for circuit 17 111 R/W NV Minor alarm threshold (%) for circuit 18 112 R/W NV Minor alarm threshold (%) for circuit 19 113 R/W NV Minor alarm threshold (%) for circuit 20 114 R/W NV Minor alarm threshold (%) for circuit 21 115 R/W NV Minor alarm threshold (%) for circuit 22 116 R/W NV Minor alarm threshold (%) for circuit 23 117 R/W NV Minor alarm threshold (%) for circuit 24 118 R/W NV Minor alarm threshold (%) for circuit 25 119 R/W NV Minor alarm threshold (%) for circuit 26 120 R/W NV Minor alarm threshold (%) for circuit 27 121 R/W NV Minor alarm threshold (%) for circuit 28 122 R/W NV Minor alarm threshold (%) for circuit 29 123 R/W NV Minor alarm threshold (%) for circuit 30 124 R/W NV Minor alarm threshold (%) for circuit 31 125 R/W NV Minor alarm threshold (%) for circuit 32 126 R/W NV Minor alarm threshold (%) for circuit 33 127 R/W NV Minor alarm threshold (%) for circuit 34 128 R/W NV Minor alarm threshold (%) for circuit 35 129 R/W NV Minor alarm threshold (%) for circuit 36 130 R/W NV Minor alarm threshold (%) for circuit 37 131 R/W NV Minor alarm threshold (%) for circuit 38 132 R/W NV Minor alarm threshold (%) for circuit 39 133 R/W NV Minor alarm threshold (%) for circuit 40 134 R/W NV Minor alarm threshold (%) for circuit 41 135 R/W NV Minor alarm threshold (%) for circuit 42
Page 26 - 34020201EN/AB
These registers define the minor alarm thresholds. A minor alarm occurs when the current in a given output circuit is greater than the minor alarm threshold and less than the major alarm threshold for a duration exceeding the minor alarm time delay. The units are in % (60 = 60%). The setting range is from 0 to 100. The factory setting is 60. A minor alarm is not activated if the current goes instantaneously from one threshold to the other.
Page 27
# Bit R/W NV Description
136 R/W NV Major alarm threshold (%) for circuit 01 137 R/W NV Major alarm threshold (%) for circuit 02 138 R/W NV Major alarm threshold (%) for circuit 03 139 R/W NV Major alarm threshold (%) for circuit 04 140 R/W NV Major alarm threshold (%) for circuit 05 141 R/W NV Major alarm threshold (%) for circuit 06 142 R/W NV Major alarm threshold (%) for circuit 07 143 R/W NV Major alarm threshold (%) for circuit 08 144 R/W NV Major alarm threshold (%) for circuit 09 145 R/W NV Major alarm threshold (%) for circuit 10 146 R/W NV Major alarm threshold (%) for circuit 11 147 R/W NV Major alarm threshold (%) for circuit 12 148 R/W NV Major alarm threshold (%) for circuit 13 149 R/W NV Major alarm threshold (%) for circuit 14 150 R/W NV Major alarm threshold (%) for circuit 15 151 R/W NV Major alarm threshold (%) for circuit 16 152 R/W NV Major alarm threshold (%) for circuit 17 153 R/W NV Major alarm threshold (%) for circuit 18 154 R/W NV Major alarm threshold (%) for circuit 19 155 R/W NV Major alarm threshold (%) for circuit 20 156 R/W NV Major alarm threshold (%) for circuit 21 157 R/W NV Major alarm threshold (%) for circuit 22 158 R/W NV Major alarm threshold (%) for circuit 23 159 R/W NV Major alarm threshold (%) for circuit 24 160 R/W NV Major alarm threshold (%) for circuit 25 161 R/W NV Major alarm threshold (%) for circuit 26 162 R/W NV Major alarm threshold (%) for circuit 27 163 R/W NV Major alarm threshold (%) for circuit 28 164 R/W NV Major alarm threshold (%) for circuit 29 165 R/W NV Major alarm threshold (%) for circuit 30 166 R/W NV Major alarm threshold (%) for circuit 31 167 R/W NV Major alarm threshold (%) for circuit 32 168 R/W NV Major alarm threshold (%) for circuit 33 169 R/W NV Major alarm threshold (%) for circuit 34 170 R/W NV Major alarm threshold (%) for circuit 35 171 R/W NV Major alarm threshold (%) for circuit 36 172 R/W NV Major alarm threshold (%) for circuit 37 173 R/W NV Major alarm threshold (%) for circuit 38 174 R/W NV Major alarm threshold (%) for circuit 39 175 R/W NV Major alarm threshold (%) for circuit 40 176 R/W NV Major alarm threshold (%) for circuit 41 177 R/W NV Major alarm threshold (%) for circuit 42
178 R/W NV Minor alarm delay for circuit 01 179 R/W NV Minor alarm delay for circuit 02 180 R/W NV Minor alarm delay for circuit 03 181 R/W NV Minor alarm delay for circuit 04 182 R/W NV Minor alarm delay for circuit 05 183 R/W NV Minor alarm delay for circuit 06 184 R/W NV Minor alarm delay for circuit 07 185 R/W NV Minor alarm delay for circuit 08 186 R/W NV Minor alarm delay for circuit 09 187 R/W NV Minor alarm delay for circuit 10 188 R/W NV Minor alarm delay for circuit 11 189 R/W NV Minor alarm delay for circuit 12 190 R/W NV Minor alarm delay for circuit 13 191 R/W NV Minor alarm delay for circuit 14 192 R/W NV Minor alarm delay for circuit 15 193 R/W NV Minor alarm delay for circuit 16 194 R/W NV Minor alarm delay for circuit 17 195 R/W NV Minor alarm delay for circuit 18 196 R/W NV Minor alarm delay for circuit 19 197 R/W NV Minor alarm delay for circuit 20 198 R/W NV Minor alarm delay for circuit 21 199 R/W NV Minor alarm delay for circuit 22 200 R/W NV Minor alarm delay for circuit 23 201 R/W NV Minor alarm delay for circuit 24
6. Appendices
These registers define the major alarm thresholds. A major alarm occurs when the current in a given output circuit is greater than the major alarm threshold a duration exceeding the major alarm time delay. The units are in % (80 = 80%). The setting range is from 0 to 100. The factory setting is 80.
Minor alarm time delay for each output circuit. This delay is expressed in seconds (from 0 to 65535 seconds). The factory setting is 10 seconds.
34020201EN/AB - Page 27
Page 28
6. Appendices
# Bit R/W NV Description
202 R/W NV Minor alarm delay for circuit 25 203 R/W NV Minor alarm delay for circuit 26 204 R/W NV Minor alarm delay for circuit 27 205 R/W NV Minor alarm delay for circuit 28 206 R/W NV Minor alarm delay for circuit 29 207 R/W NV Minor alarm delay for circuit 30 208 R/W NV Minor alarm delay for circuit 31 209 R/W NV Minor alarm delay for circuit 32 210 R/W NV Minor alarm delay for circuit 33 211 R/W NV Minor alarm delay for circuit 34 212 R/W NV Minor alarm delay for circuit 35 213 R/W NV Minor alarm delay for circuit 36 214 R/W NV Minor alarm delay for circuit 37 215 R/W NV Minor alarm delay for circuit 38 216 R/W NV Minor alarm delay for circuit 39 217 R/W NV Minor alarm delay for circuit 40 218 R/W NV Minor alarm delay for circuit 41 219 R/W NV Minor alarm delay for circuit 42
220 R/W NV Major alarm delay for circuit 01 221 R/W NV Major alarm delay for circuit 02 222 R/W NV Major alarm delay for circuit 03 223 R/W NV Major alarm delay for circuit 04 224 R/W NV Major alarm delay for circuit 05 225 R/W NV Major alarm delay for circuit 06 226 R/W NV Major alarm delay for circuit 07 227 R/W NV Major alarm delay for circuit 08 228 R/W NV Major alarm delay for circuit 09 229 R/W NV Major alarm delay for circuit 10 230 R/W NV Major alarm delay for circuit 11 231 R/W NV Major alarm delay for circuit 12 232 R/W NV Major alarm delay for circuit 13 233 R/W NV Major alarm delay for circuit 14 234 R/W NV Major alarm delay for circuit 15 235 R/W NV Major alarm delay for circuit 16 236 R/W NV Major alarm delay for circuit 17 237 R/W NV Major alarm delay for circuit 18 238 R/W NV Major alarm delay for circuit 19 239 R/W NV Major alarm delay for circuit 20 240 R/W NV Major alarm delay for circuit 21 241 R/W NV Major alarm delay for circuit 22 242 R/W NV Major alarm delay for circuit 23 243 R/W NV Major alarm delay for circuit 24 244 R/W NV Major alarm delay for circuit 25 245 R/W NV Major alarm delay for circuit 26 246 R/W NV Major alarm delay for circuit 27 247 R/W NV Major alarm delay for circuit 28 248 R/W NV Major alarm delay for circuit 29 249 R/W NV Major alarm delay for circuit 30 250 R/W NV Major alarm delay for circuit 31 251 R/W NV Major alarm delay for circuit 32 252 R/W NV Major alarm delay for circuit 33 253 R/W NV Major alarm delay for circuit 34 254 R/W NV Major alarm delay for circuit 35 255 R/W NV Major alarm delay for circuit 36 256 R/W NV Major alarm delay for circuit 37 257 R/W NV Major alarm delay for circuit 38 258 R/W NV Major alarm delay for circuit 39 259 R/W NV Major alarm delay for circuit 40 260 R/W NV Major alarm delay for circuit 41 261 R/W NV Major alarm delay for circuit 42
262 to 267 Reserved for MGE UPS SYSTEMS
Major alarm time delay for each output circuit. This delay is expressed in seconds (from 0 to 65535 seconds). The factory setting is 10 seconds.
Page 28 - 34020201EN/AB
Page 29
# Bit R/W NV Description
268 W Global circuit breaker rating 269 W Global minor alarm threshold (%) 270 W Global major alarm threshold (%) 271 W Global minor alarm time delay 272 W Global major alarm time delay
273 to 280 Reserved for MGE UPS SYSTEMS
281 R Non-stored minor alarms
0 60% < Current in circuit 01 < 80% 1 60% < Current in circuit 02 < 80% 2 60% < Current in circuit 03 < 80% 3 60% < Current in circuit 04 < 80% 4 60% < Current in circuit 05 < 80% 5 60% < Current in circuit 06 < 80% 6 60% < Current in circuit 07 < 80% 7 60% < Current in circuit 08 < 80% 8 60% < Current in circuit 09 < 80% 9 60% < Current in circuit 10 < 80% 10 60% < Current in circuit 11 < 80% 11 60% < Current in circuit 12 < 80% 12 60% < Current in circuit 13 < 80% 13 60% < Current in circuit 14 < 80% 14 60% < Current in circuit 15 < 80% 15 60% < Current in circuit 16 < 80%
282 R Non-stored minor alarms
0 60% < Current in circuit 17 < 80% 1 60% < Current in circuit 18 < 80% 2 60% < Current in circuit 19 < 80% 3 60% < Current in circuit 20 < 80% 4 60% < Current in circuit 21 < 80% 5 60% < Current in circuit 22 < 80% 6 60% < Current in circuit 23 < 80% 7 60% < Current in circuit 24 < 80% 8 60% < Current in circuit 25 < 80% 9 60% < Current in circuit 26 < 80% 10 60% < Current in circuit 27 < 80% 11 60% < Current in circuit 28 < 80% 12 60% < Current in circuit 29 < 80% 13 60% < Current in circuit 30 < 80% 14 60% < Current in circuit 31 < 80% 15 60% < Current in circuit 32 < 80%
283 R Non-stored minor alarms
0 60% < Current in circuit 33 < 80% 1 60% < Current in circuit 34 < 80% 2 60% < Current in circuit 35 < 80% 3 60% < Current in circuit 36 < 80% 4 60% < Current in circuit 37 < 80% 5 60% < Current in circuit 38 < 80% 6 60% < Current in circuit 39 < 80% 7 60% < Current in circuit 40 < 80% 8 60% < Current in circuit 41 < 80% 9 60% < Current in circuit 42 < 80% 10 to 15 Unused bits (all set to 0)
284 R Non-stored major alarms
0 Current in circuit 01 > 80% 1 Current in circuit 02 > 80% 2 Current in circuit 03 > 80% 3 Current in circuit 04 > 80% 4 Current in circuit 05 > 80% 5 Current in circuit 06 > 80% 6 Current in circuit 07 > 80% 7 Current in circuit 08 > 80% 8 Current in circuit 09 > 80% 9 Current in circuit 10 > 80% 10 Current in circuit 11 > 80% 11 Current in circuit 12 > 80%
6. Appendices
A value entered in the global parameters to enable the 42 (or 21) output circuits to be set to that value at the same time.
These bits go to 1 when the current in a corresponding output circuit is greater than the minor alarm threshold (60% in the example opposite) and less than the major alarm threshold (80% in the example opposite). This state is not stored in memory.
These bits go to 1 when the current in a corresponding output circuit is greater than the major alarm threshold (80% in the example opposite). This state is not stored in memory.
34020201EN/AB - Page 29
Page 30
6. Appendices
# Bit R/W NV Description
12 Current in circuit 13 > 80% 13 Current in circuit 14 > 80% 14 Current in circuit 15 > 80% 15 Current in circuit 16 > 80%
285 R Non-stored major alarms
0 Current in circuit 17 > 80% 1 Current in circuit 18 > 80% 2 Current in circuit 19 > 80% 3 Current in circuit 20 > 80% 4 Current in circuit 21 > 80% 5 Current in circuit 22 > 80% 6 Current in circuit 23 > 80% 7 Current in circuit 24 > 80% 8 Current in circuit 25 > 80% 9 Current in circuit 26 > 80% 10 Current in circuit 27 > 80% 11 Current in circuit 28 > 80% 12 Current in circuit 29 > 80% 13 Current in circuit 30 > 80% 14 Current in circuit 31 > 80% 15 Current in circuit 32 > 80%
286 R Non-stored major alarms
0 Current in circuit 33 > 80% 1 Current in circuit 34 > 80% 2 Current in circuit 35 > 80% 3 Current in circuit 36 > 80% 4 Current in circuit 37 > 80% 5 Current in circuit 38 > 80% 6 Current in circuit 39 > 80% 7 Current in circuit 40 > 80% 8 Current in circuit 41 > 80% 9 Current in circuit 42 > 80% 10 to 15 Unused bits (all set to 0)
Page 30 - 34020201EN/AB
Page 31
Card MCM (general status and measurements)
The variables entered in registers 1 to 74 are whole numbers read on 16 bits. The variables entered in registers 1 to 29 are also accessible in “floating” format on 32 bits (registers 257 to 314 in the “Float.” column of the table). The “floating” variables are read only. Multiply each value in whole number format by the coefficient indicated in the “Coeff.” column of the table.
# Bit Float. R/W NV Coeff. Description
1 257/258 R/W NV 0.1 Energy consumed in kWh (least significant bit of the word)* 2 259/260 R/W NV 6553.6 Energy consumed in kWh (most significant bit of the word)* 3 261/262 R 0.1 Total active power in kW 4 263/264 R 0.1 Total reactive power in kVAR 5 265/266 R 0.1 Total apparent power in kVA 6 267/268 R 0.0001 Total power factor 7 269/270 R 0.01 Average of the phase-to-phase voltages in the 3 phases in V 8 271/272 R 0.01 Average of the phase-to-neutral voltages in the 3 phases in V 9 273/274 R 0.1 Average of the current in the 3 phases in A 10 275/276 R 0.01 Frequency in Hz 11 277/278 R 0.1 Active power for phase A in kW 12 279/280 R 0.1 Active power for phase B in kW 13 281/282 R 0.1 Active power for phase C in kW 14 283/284 R 0.0001 Power factor for phase A 15 285/286 R 0.0001 Power factor for phase B 16 287/288 R 0.0001 Power factor for phase C 17 289/290 R 0.01 Voltage between phase A and B in V 18 291/292 R 0.01 Voltage between phase B and C in V 19 293/294 R 0.01 Voltage between phase C and A in V 20 295/296 R 0.01 Voltage between phase A and the neutral in V 21 297/298 R 0.01 Voltage between phase B and the neutral in V 22 299/300 R 0.01 Voltage between phase C and the neutral in V 23 301/302 R 0.1 Current in phase A in A 24 303/304 R 0.1 Current in phase B in A 25 305/306 R 0.1 Current in phase C in A 26 307/308 R 0.1 Neutral current in A 27 309/310 R/W 0.1 Average total active power in kW* 28 311/312 R/W 0.1 Minimum total active power in kW* 29 313/314 R/W 0.1 Maximum total active power in kW* 30 to 36 R/W NV Reserved for MGE UPS SYSTEMS 37 R/W NV Alarms
0 Stored overload alarms (bit set to 1). Reset by setting bit to 0. 1 to 3 Unused bits (set to 0) 4 Stored overvoltage alarms (bit set to 1). Reset by setting bit to 0.
5 to 15 Unused bits (set to 0) 38 to 42 R/W NV Reserved for MGE UPS SYSTEMS 43 to 48 R Reserved for MGE UPS SYSTEMS 49 R NV Alarms
0 Non-stored overload alarms (bit set to 1).
1 to 3 Unused bits (set to 0)
4 Non-stored overvoltage alarms (bit set to 1).
5 to 15 Unused bits (set to 0) 50 to 74 Reserved for MGE UPS SYSTEMS
6. Appendices
*: Values valid since the last reset. Reset is carried out by writing a whole number value.
34020201EN/AB - Page 31
Page 32
6. Appendices
6.5 Glossary
ALARM Major alarm signalling that the current in the output circuit considered is higher than 80%
AUX ALARM INPUT Alarm indicating either:
DOWN Scroll button used to access previous measurement (metering mode) or setting (setup
Isolation transformer Optional transformer used to provide galvanic isolation between the distribution system
METER Function button for access to the next measurements (metering mode) or to return to
Output circuit Single-phase circuit (phase, neutral and earth) exiting the PMM module, protected by a
OVER CURRENT Alarm indicating an overload on the PMM module.
of its rated value.
excessive temperature rise in the isolation transformer, actuation of the remote shutdown function.
mode).
and the output circuits, to block reinjection of third-order harmonics upstream or to create a neutral if the distribution system does not have one.
MONITORING mode (alarm or setup mode).
single standard circuit breaker (PMM module with 126 output circuits) or by a circuit breaker with earth-leakage protection (PMM module with 60 output circuits).
OVER VOLTAGE Alarm indicating that the voltage of the distribution system is too high.
PMM Power Management Module (the device in question).
RS-232 Serial communication standard using a SUB-D 9-pin connector.
RS-485 Serial communication standard available via a screw-terminal block.
SELECT Function button used to obtain a fixed display if autoscroll (parameter rotation) is
activated, clear an alarm (alarm mode) or access the next parameter to be set (setup mode).
UP Scroll button used to access next measurement (metering mode) or setting (setup
mode).
WARNING Minor alarm signalling that the current in the output circuit considered is between 60 and
80% of its rated value.
Page 32 - 34020201EN/AB
Page 33
6.5 Index
6. Appendices
A
Alarms
Displayed .......................................................... 17, 19
Remote ............................................................. 19, 22
C
Cable sizes .................................................................... 21
Characteristics
Electrical ................................................................. 21
Mechanica ................................................................ 6
Thermal .................................................................. 21
Circuit breakers .......................................................... 7, 21
Communication connections .......................................... 15
Communication information ..................................... 15, 22
Connections
Access ...................................................................... 8
Communication information .................................... 15
Power cables ..................................................... 12-14
Remote alarms ....................................................... 14
Remote shutdown .................................................. 14
D
Dimensions ...................................................................... 6
Disconnector-fuses .................................................... 7, 19
Display .................................................................. 8, 16-19
Display modes
Alarms .............................................................. 16, 17
Metering ........................................................... 16, 17
Setup ................................................................ 16, 18
Display settings ................................................................ 8
Distribution system ................................................... 19, 22
E
Earthing bars .............................................................. 8, 14
Electrical diagrams ......................................................... 22
F
Footprint ..................................................................... 9, 10
Frequency ................................................................ 17, 21
Function buttons ................................................... 8, 16-18
Fuses ......................................................................... 7, 19
H
Heat losses .................................................................... 21
I
Isolation transformer .................................................. 6, 22
M
Metering ................................................................... 16, 17
Module layout ................................................................... 7
O
Output circuits ................................................. 7, 16-19, 22
R
Recommended protection devices ................................. 21
Recycling ....................................................................... 20
Remote shutdown .................................................... 14, 22
RS232 link ................................................................ 15, 22
RS485 link ................................................................ 15, 22
S
Safety instructions ............................................................ 3
Settings .......................................................................... 18
Special precautions .......................................................... 3
Symbols ........................................................................... 4
System-status LED ............................................... 8, 16-19
T
Terminal blocks .......................................................... 8, 14
V
Voltages ............................................................. 17, 19, 21
W
Weight .............................................................................. 6
34020201EN/AB - Page 33
Page 34
Page 34 - 34020201EN/AB
Loading...