Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Power Management Module (PMM) has been designed with the utmost care. We recommend that you take the time
to read this manual to take full advantage of the many features of your new equipment.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products.
The considerable resources put into developing the Power Management Module make it a reference in terms of
environmental protection. Of particular importance are:
◗ the eco-design approach during product development,
◗ recycling of the Power Management Module at the end of its service life.
MGE UPS SYSTEMS warrants this hardware product against defects in materials and workmanship for a period of one
year.
Limitation of warranty: the above warranty shall not apply to defects resulting from: misure, non-MGE UPS
SYSTEMS modification, operation or storage outside the environmental specifications for the product, improper
maintenance, or defects resulting from use of non-MGE UPS SYSTEMS software, accessories, -media or such
items not designed for use with the product.
Moreover, the warranty does not include the consumable goods and the replacements or repairs which would
result from the abnormal wear of the products, and deteriorations or accidents coming from an external cause
such as fire, damage of water, damage caused by other equipment...
We invite you to discover the entire MGE UPS SYSTEMS range of products and services including the options for the
Power Management Module by visiting our Web site at www.mgeups.com or by contacting your nearest sales
representative.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical
characteristics and dimensions are not binding unless confirmed by MGE UPS SYSTEMS.
This document may be copied only with the written consent of MGE UPS SYSTEMS. Authorized copies must be marked "PowerManagement Module User Manual nr 3402020100".
34020201EN/AB - Page 3
Page 4
Foreword
Structure of this document
Information may be found via:
◗ the contents,
◗ the index.
Symbols
Mandatory instructions
General instructions, advice, help
Indication
Action
Earth cables
Other cables
Page 4 - 34020201EN/AB
Page 5
Contents
1.Presentation
1.1250 A PMM modules .................................................................................................................... 6
1.2Access to the circuit breakers ................................................................................................... 7
Version with 126 circuit breakers (doors open)............................................................................... 7
Version with 60 circuit breakers (doors open)................................................................................. 7
1.3Access to connections ............................................................................................................... 8
F1 disconnector-fuse for protection of the
control electronics
3
F2 disconnector-fuse for protection of the
voltage measurement inputs
6
2 x 21 circuit breakers for phase A (A-1 to A41 and A-2 to A-42)
2 x 21 circuit breakers for phase B (B-1 to B-
7
41 and B-2 to B-42)
8
2 x 21 circuit breakers for phase C (C-1 to
C-41 and C-2 to C-42)
9Eight connection cover panels
4
General protection circuit breaker for the 126
output circuits
5
Upstream general protection circuit breaker
(only in modules with an isolation
transformer)
Version with 60 circuit breakers (doors open)
I 0I 0I 0
A-01
A-03
A-05
A-07
A-09
A-11
A-13
A-15
A-17
A-19
I 0I 0I 0
I
Q2
0
I
Q1
0
A-02
A-04
A-06
A-08
A-10
A-12
A-14
A-16
A-18
A-20
B-01
B-03
B-05
B-07
B-09
B-11
B-13
B-15
B-17
B-19
B-02
B-04
B-06
B-08
B-10
B-12
B-14
B-16
B-18
B-20
C-01
C-03
C-05
C-07
C-09
C-11
C-13
C-15
C-17
C-19
C-02
C-04
C-06
C-08
C-10
C-12
C-14
C-16
C-18
C-20
2
F1 disconnector-fuse for protection of the
control electronics
3
F2 disconnector-fuse for protection of the
voltage measurement inputs
2 x 10 circuit breakers with earth-leakage
6
protection for phase A (A-1 to A-19 and A-2
to A-20)
2 x 10 circuit breakers with earth-leakage
7
protection for phase B (B-1 to B-19 and B-2
to B-20)
2 x 10 circuit breakers with earth-leakage
8
protection for phase C (C-1 to C-19 and C-2
to C-20)
Eight connection cover panels
9
4
General protection circuit breaker for the 60
output circuits
5
Upstream general protection circuit breaker
(only in modules with an isolation
transformer)
34020201EN/AB - Page 7
Page 8
1. Presentation
1.3 Access to connections
Remove the eight cover panels (each secured with two screws).
Example showing the version with 126 output circuits:
Q2
10
11
12
13
14
Phase connections for output-circuit cables
Metal trunking for passage and securing of
output cables
Connection bars for earth wires of output
cables
Terminal block for remote shutdown function
and minor and major alarms
In modules without an isolation transformer,
connection of the three input phases and the
neutral to circuit breaker Q2
Q1
1.4 Control panel
CRITICAL POWER MONITORING SYSTEM
NEXT
PARAMETER
MGE UPS SYSTEMS
Ph-A CH01 2.637
BCM CH02 4.215
SETUP MODE
DOWNUPSELECTMETER
PREVIOUS
PARAMETER
HOLD
READING
ALARM MENU
SCROLL
METERS
15
16
17
18
22
21
In modules with an isolation transformer, of
the three input phases to circuit breaker Q1
Main earthing bar of the module
System status LED: see table on page 23
Alphanumeric display
Scroll through different types of
measurements or return to display of
measurements
Scroll through different system settings
Page 8 - 34020201EN/AB
20
19
Previous measurement or setting
Next measurement or setting
Page 9
2.1 Setting up the module
Module 825 mm deep
≥400 mm
2. Installation
1. Install the lower base panels 23 on the
sides that will not be accessible (not
mandatory).
2. Position the module.
3. Level the module using the adjustable feet
24 .
4. Install the lower base panels 23 on the
visible sides.
Connection cables run under the false floor
or in a cable trough.
Rear of module
1076
4 feet, diameter 40 mm
M
M
P
≥720 mm
Important.
At least 400 mm of free space is required
above the module to ensure correct
ventilation.
At least 720 mm of free space is required
in front to open the doors.
23
24
23
Footprint of module
69.569.5
6767
Weight exerted on the floor by the four feet:
◗ 28 kg/cm
◗ up to 72 kg/cm
2
(module without transformer),
2
(module with transformer).
676
8282
Front of module
34020201EN/AB - Page 9
Page 10
2. Installation
Module 425 mm deep
Installation against a wall
25
1685,5
Caution: during handling, make sure the module does not fall over.
1. Turn to horizontal position the two
brackets 25 at the back used to secure the
module (see figure).
2. Install the rear base panel 23 (not
mandatory).
26
≥ 400 mm
3. Position the module.
4. Level the module using the adjustable feet
24 .
1250
5. Attach the module to the wall using the
two rear brackets.
6. Install the base panels 23 on the sides
and front.
7. Remove the bracket 26 on the top of the
module (used only for back-to-back
assembly of two modules) and retighten the
fixing screw.
276
Rear of module
1076
4 feet, diameter 40 mm
M
M
P
≥720 mm
Connection cables run under the false floor
or in a trough.
Important:
At least 400 mm of free space is required
above the module to ensure correct
ventilation.
At least 720 mm of free space is required
in front to open the doors.
23
24
23
24
23
Footprint of module
69.569.5
6767
Force exerted on the floor by the four feet:
◗ 28 kg/cm
2
.
Page 10 - 34020201EN/AB
8282
Front of module
Page 11
Back-to-back assembly
25
26
2. Installation
Caution: during handling, make sure the modules do not fall over.
1. Remove the brackets 25 on the back of
the module (used only for securing the
module to a wall) and retighten the fixing
screws.
25
2. Position the modules and use the
brackets 26 on the top to interconnect thetwo modules (see figure).
≥720 mm
∼ 860 mm
≥ 400 mm
M
M
P
≥720 mm
26
26
3. Level the modules using the adjustable
feet 24 .
4. Install the base panels 23 on the sides
and fronts.
Important:
At least 400 mm of free space is required
above the module to ensure correct
ventilation.
At least 720 mm of free space is required
in front to open the doors.
23
23
24
23
34020201EN/AB - Page 11
Page 12
2. Installation
2
1
4
5
BCA
Q1
333
PE / PEN
4
1
BC
Q2
2
333
5
3
N
A
2.2 Input power connections
Specifications for protection devices and cables are provided in section 6 (Appendices, technical data sheet).
To access the connections, see section 1.3. Connection cables are not supplied.
Q2
Module with isolation transformer
1. Connect the PE or PEN protection cable
to the earthing bar at the bottom of the
module.
2. Remove the bottom cover on circuit
breaker Q1.
3. Connect the three phases of the input
power cable to the bottom terminals of circuit
breaker Q1 (without removing the control
wires that are already connected).
4. Ties the cables to the earthing bar.
5. Refit the bottom cover on circuit breaker
Q1.
Q1
Module without isolation
transformer, separate earth and
neutral (TNS system)
1. Connect the PE protection cable to the
earthing bar at the bottom of the module.
2. Remove the bottom cover on circuit
breaker Q2.
3. Connect the three phases and the neutral
of the input power cable to the bottom
terminals of circuit breaker Q2 (without
removing the control wires that are already
connected).
4. Ties the cables to the earthing bar.
5. Refit the bottom cover on circuit breaker
Q2.
Q2
Page 12 - 34020201EN/AB
BCNA
PE
Page 13
Q2
5
BCA
14
N
PEN
BC
Q2
2
433
6
3
N
A
2. Installation
Module without isolation
transformer, combined earth and
neutral (TNC system)
1. Connect the PEN protection cable to the
earthing bar at the bottom of the module.
2. Remove the bottom cover on circuit
breaker Q2.
3. Connect the three phases of the input
power cable to the bottom terminals of circuit
breaker Q2 (without removing the control
wires that are already connected).
4. Use a cable (not supplied) to connect the
neutral connector on the lower part of circuit
breaker Q2 to the earthing bar.
5. Ties the cables to the earthing bar.
6. Refit the bottom cover on circuit breaker
Q2.
34020201EN/AB - Page 13
Page 14
1
2
345
6
2. Installation
1
2
2
3
Ph
N
2.3 Output circuit connections
Q2
It is advised to use crimped ferrules on the
phase wires and lugs on the earth wires.
1. Connect the earth wire of each output
cable to the earth connection bar located to
the left of the metal trunking.
2. Connect the phase and neutral wires to
each circuit breaker.
3. Tie the cables to the metal trunking.
Note: it is advised to make the connections
from the top down.
Q1
2.4 Alarm and remote shutdown connections
13
1. Connect the NO remote shutdown contact
to terminals 1 and 2 on terminal block 13 .
2. The alarm signals are transmitted by dry
contacts (Umax = 250 V AC / 30 V DC, Imax
= 7 A AC / 10 A DC) between terminals 3
and 4 for the type 1 alarm and between 5
and 6 for the type 2 alarm.
3. Tie the cable down to the module frame.
Page 14 - 34020201EN/AB
3
Q2
Q1
3
Remote shutdown
1
2
Type 2 alarm
Type 1 alarm
Warning: the remote shutdown function
is not implemented using a very low
safety voltage.
Consequently, the usual safety
measures must be taken to avoid all risk
of electrical shock when making
connections for this function.
Page 15
2.5 Communication connections
2
Q2
3
RS-232
RS-485
1
2. Installation
1. Connect the communication cable to the
RS232 or RS485 connector on the righthand door of the module.
2. Run the cable as shown in the figure
opposite.
3. Tie the cable down to the module frame.
Q1
Communication connector details
RS-232
9
12345
6
8
7
RS232 connector
Td (from the PMM
display)
Rd (to the PMM display)
GND
RS-485
54321
RS485 connector
2 wires
GND
Not used
Not used
Tx+ / Rx+
Tx- / Rx-
RS485 connector
4 wires
GND
Tx+
TxRx+
Rx-
Example of an RS485 2-wire
connection:
Tx- / Rx-
Tx+ / Rx+
GND
54321
Example of an RS485 4-wire connection:
MasterSlaveMaster or slave
Rx-
Rx+
Tx-
Tx+
GND
Rx-
Rx+
54321
GND
Tx-
Tx+
54321
34020201EN/AB - Page 15
Page 16
3.Operation
3.1 Turning on the PMM module
1. Close the upstream switching device (external and not supplied) on the circuit supplying the PMM module.
2. In a module with an isolation transformer, close ("I" or ON position) circuit breaker Q1 5 (see page 7) .
3. Make sure disconnector-fuses F1 and F2 are closed and close ("I" or ON position) circuit breaker Q2 5 (see page 7) .
◗ The system status LED 17 (see page 8) flashes yellow a few seconds, then green and should subsequently remain
green.
◗ After a few seconds, the first page of measurements is displayed:
Ph-A CH01 0.000
BCM CH02 0.000
4. Close the circuit breakers on the output circuits to be powered.
3.2 Display
The display unit for the PMM module offers three operating modes: metering, alarm and setup.
Metering mode
DOWN
UP
This is the default mode.
Ph-A CH01 0.000
BCM CH02 0.000
UP
DOWN
Ph-B CH01 0.000
BCM CH02 0.000
UP
DOWN
BCM CH42 0.000
METER
BCM CH42 0.000
+
SELECT
+
Ph-B CH25
WARNING
Ph-C CH12
ALARM
METER
Alarm modeSetup mode
UP
UP
SELECT
SELECT
Enter Password :
* * * * * *
DOWN
DOWN
View System Info
UP
SELECT
UP
UP
METER
Ph-C CH01 0.000
BCM CH02 0.000
UP
DOWN
METER
GENE KWH 0000.0
MCM KW 0000.0
UP
DOWN
BCM CH42 0.000
MCM MAX 0000.0
METER
METER
METER
GENE OVER
MCM VOLTAGE
UP
GENE OVER
MCM CURRENT
UP
AUX INPUT
ALARM
UP
SELECT
SELECT
Find Meters
UP
Review Meters
UP
Setup
Communication
UP
Setup
Operation
UP
Page 16 - 34020201EN/AB
Page 17
3.3 Metering
Output-circuit metering
3. Operation
Ph-A: measurements on phase A
CH-01: measurements on output circuit 01
Ph-A CH01 0.000
BCM CH02 0.000
General metering
GENE KWH 0000.0
MCM KW 0000.0
KVA: apparent power drawn by the PMM module in kVA.
PF: average power factor on the three phases of the PMM module.
V-LL: average phase-to-phase voltage on the three phases of the PMM module in volts.
V-LN: average phase-to-neutral voltage on the three phases of the PMM module in volts.
AMPS: average current on the three phases of the PMM module in amperes.
FREQ: frequency of the voltage supplied by the PMM module in Hertz.
KW-A, KW-B, KW-C: active power drawn by phases A, B and C of the PMM module in kW.
PF-A, PF-B, PF-C: power factor on phases A, B and C of the PMM module.
V-AB, V-BC, V-AC: phase-to-phase voltages supplied by the PMM module in volts.
V-AN, V-BN, V-CN: phase-to-neutral voltages supplied by the PMM module in volts.
AMPA, AMPB, AMPC, AMPN: current on the three phases A, B, C and on the neutral of the PMM module in amperes.
MIN: minimum power (stored in memory) supplied by the PMM module in kW since the last reset.
MAX: maximum power (stored in memory) supplied by the PMM module in kW since the last reset.
The minimum, maximum and average power values are reset via the communication function.
Display of the current drawn by the output circuit in amperes
GENE: general measurements.
Measurement units:
KWH: total energy consumed by the PMM module in kWh.
This value can be reset via the communication function.
KW: total active power drawn by the PMM module in kW.
KVAR: reactive power drawn by the PMM module in kVAR.
3.4 Alarms
SELECT
The
rotation). The display flashes and the measurement is not updated.
Access alarm mode by pressing simultaneously the
This mode displays the list of stored major and minor faults that have occurred in the PMM or on the output circuits.
When an alarm is present in the memory, LED 17 goes on:
◗ yellow for fault that does not hinder normal operation;
◗ red for a fault requiring intervention.
Ph-B CH25
WARNING
ALARM: indicates that the current on the indicated circuit is higher than 80% of the maximum value.
OVER VOLTAGE: the voltage supplied by the PMM exceeds the permissible range by over 10%.
OVER CURRENT: there is an overload on the PMM.
AUX INPUT ALARM: this alarm signals either:
◗ excessive temperature rise in the isolation transformer,
◗ or activation of the remote shutdown button.
button may be used to hold the display of a measurement if the module is set up for autoscrolling (parameter
SELECT
Ph-B: alarm on phase B.
CH-25: alarm on output circuit 25.
Alarm text:
WARNING: indicates that the current on the indicated circuit (number
25, phase B) is between 60 and 80% of the maximum value.
+
METER
buttons.
These alarms are stored in memory:
◗ Press the
◗ Press the
The display automatically returns to metering mode if buttons 19 to 22 are not used for ten seconds.
SELECT
button to clear the displayed alarm.
METER
button to return to metering mode.
34020201EN/AB - Page 17
Page 18
3.Operation
3.5 Setup
Access setup mode by pressing simultaneously the
SELECT
DOWNDOWN
SELECT
UPUP
This mode presents the functions listed below.
View System Info, Find Meters and Review Meters : these functions are reserved for MGE UPS SYSTEMS.
Setup Communication : access to the communication settings.
Setup Operation : access to the display settings (luminosity, autoscroll) and selection of the alarm operating mode (open
or closed contacts).
The display automatically returns to metering mode if buttons are not used for ten seconds.
Communication settings
Settings include:
◗ Routing Address (ON, OFF): internal setting reserved for MGE UPS SYSTEMS, must not be modified (ON).
◗ Modbus Address (1 to 225): Modbus address, must be selected from 1 to 225 (by steps of 16).
◗ Upstream Type (RS-485, RS-232, INFRARED): type of serial link.
◗ Upstream Duplex (2-WIRE, 4-WIRE): 2 or 4-wire link.
◗ Upstream Baudrate (2400, 4800, 9600, 19200): speed of transmission in Bauds.
◗ Upstream Parity (NONE, ODD, EVEN): parity.
◗ Downstream Duplex: internal setting reserved for MGE UPS SYSTEMS, must not be modified (2-WIRE).
◗ Downstream Baudrate: internal setting reserved for MGE UPS SYSTEMS, must not be modified (9600).
◗ Downstream Parity: internal setting reserved for MGE UPS SYSTEMS, must not be modified (NONE).
Operation settings (display and alarms)
The user-settable parameters are listed below.
◗ Blacklight Brightness (0 to 9): adjustment of the display luminosity.
◗ Auxiliary INPUT ALARM: internal setting reserved for MGE UPS SYSTEMS, must not be modified (CLOSED).
◗ Rotate parameters (NO, YES) : fixed display or autoscroll.
+
DOWN
buttons and then entering the password:
UP
.
3.6 Turning off the PMM module
1. Open ("O" or OFF position) all the circuit breakers on the output circuits.
2. Open ("O" or OFF position) circuit breaker Q2 4 .
3. In a module with an isolation transformer, open ("O" or OFF position) circuit breaker Q1 5 .
4. Open the upstream switching device of the installation on the circuit supplying the PMM. LED 17 and the display go
off.
Caution: dangerous voltage levels are present inside the PMM, even if Q1 and Q2 are open.
Page 18 - 34020201EN/AB
Page 19
4.1 Trouble-shooting and solutions
4. Maintenance
Alarm
WARNING
ALARM
OVER VOLTAGE
OVER CURRENT
AUX INPUT ALARM
Fault
No display
Incoherent measurement
values
LED 17 yellow
LED 17 red
Meaning
The current on the indicated output circuit is
between 60 and 80% of the maximum value
for the circuit.
The current on the indicated output circuit is
higher than 80% of the maximum value for
the circuit.
The voltage on the distribution system is
high.
The load on the PMM module is higher than
250A.
◗ Temperature rise in the isolation
transformer.
◗ Activation of the remote shutdown function.
Possible Causes
◗ Fuses F1 blown,
◗ Disconnector-fuse F1 open.
◗ Fuses F2 blown,
◗ Disconnector-fuse F2 open.
The current on at least one output circuit is
between 60 and 80% of the maximum value
for the circuit.
One of the following:
◗ The current on at least one output circuit is
higher than 80% of the maximum value for
the circuit,
◗ Overvoltage (>457V),
◗ Overcurrent (>250A),
◗ Transformer temperature too high,
◗ Actuation of remote shutdown function.
Action
Monitor the power drawn on the circuit and
avoid adding other loads to the circuit.
Turn off certain loads connected to the
circuit until the fault disappears (after alarm
reset).
Monitor the voltage on the distribution
system. The connected loads may suffer
breakdowns.
Turn off certain connected loads until the
fault disappears (after alarm reset).
◗ Check the ventilation system in the room.
◗ Shut down the PMM module, then start it
up again when the remote shutdown signal
has been cleared.
Action
◗ Call the MGE after-sales technical support,
◗ Close disconnector-fuse F1.
◗ Call the MGE after-sales technical support,
◗ Close disconnector-fuse F2.
Consult the list of alarms (alarm mode) and
reset the alarm.
Consult the list of alarms (alarm mode) and
reset the alarm.
34020201EN/AB - Page 19
Page 20
5. Environment
This product has been designed to respect the environment.
It does not contain CFCs or HCFCs.
Recycling at the end of service life
MGE UPS SYSTEMS undertakes to have all products recovered at the end of their service life recycled by certified
companies in compliance with applicable regulations (contact your branch office).
Packing materials
Comply with all applicable regulations for recycling of packing materials.
Page 20 - 34020201EN/AB
Web Site: www.mgeups.com
Page 21
6.1 Technical data sheets
Electrical characteristics
Rated input current:250 A per phase and 400 A for the neutral
Rated output current:16 A per phase
Input voltages:
◗ Rated voltage:380 V / 400 V / 415 V
◗ Maximum voltage:457 V (415 V +10%)
◗ Minimum voltage:342 V (380 V -10%)
◗ Rated frequency:50 or 60 Hz (47 Hz minimum, 63 Hz maximum)
Output voltages:220 V / 230 V / 240 V
F1 and F2 fuses:0.5 A aM - 600 V - 100 kA
Thermal characteristics
Heat loss (with isolation transformer):
◗ At full rated power: 5000 W
◗ At 50% rated power: 2000 W
Noise level
Acoustic noise as defined by standard ISO 3746: 62 dBa (with isolation transformer)
6. Appendices
Maximum wire sizes for terminal blocks
◗ Input phases: 120 mm
◗ Input neutral: 2 x 120 mm
◗ PE: 120 mm
◗ PEN: 2 x 120 mm
◗ Output circuits: 2.5 mm
◗ Auxiliary wires (remote shutdown, remote alarms): 1.5 mm
◗ Communication wires: shielded cable (telephone type)
2
2
2
2
2
Recommended upstream protection devices
Upstream system
TNC
TNS
(1) I0 and IR are thermal settings, Ii and Im are magnetic settings.
Number of output
circuits on PMM module
126 output circuits
60 output circuits
126 output circuits
60 output circuits
2
Recommended upstream circuit breaker
Siemens 3VL3725-1DC36-0AA0
Merlin Gerin NS250 TM 250D
3/3 poles protected
Siemens 3VF52-1MH41-0AA0
Merlin Gerin NS400 STR23SE 400
3/4 poles protected
Settings
IR = 1.0 In
Ii = 10 In
IR = 1.0 In
Im = 10 In
IR = 1.0 In
Ii = 10 In
I0 = 0.63 In
IR = I
0
Im = 10 I
R
(1)
Standards
Selection of the protection devices must comply with applicable standards and regulations using the information
presented above and taking into account discrimination requirements.
The models in the table are only intended as a general indication and in no way engage the responsibility of MGE
UPS SYSTEMS.
Protection level: IP 20C (standard CEI 529).
Environment: 2 (standard EN 60439-1).
34020201EN/AB - Page 21
Page 22
6. Appendices
6.2 Simplified diagrams
Version with isolation transformer
MX
AC input
power
Q1Q2
F1
Remote
shutdown
Type 1 alarm
(contact open or
closed)
Version without isolation transformer
PMM Module
Control and display electronics
Type 2 alarm
(contact open or
closed)
F2
Communication
information
(RS232 or RS485)
Output
circuits
CH01
CH02
CH03
CH42
power
F1
Remote
shutdown
MX
Q2
PMM Module
Control and display electronics
Type 1 alarm
(contact open or
closed)
Type 2 alarm
(contact open or
closed)
F2
Communication
information
(RS232 or RS485)
Output
circuits
CH01AC input
CH02
CH03
CH42
Page 22 - 34020201EN/AB
Page 23
6.3 Auxiliary contact functions
6. Appendices
Normal operation
Downgraded operation
Overload or overvoltage
Other fault
Alarm LED
17
Green
Yellow
Red
Red
Type 1-alarm
contact
OFF
ON
ON
OFF
6.4 Modbus communication information
Access to communicated information
Each status indication or measurement displayed on the module is accessible via the RS232 or RS485 communication
port.
Each PMM module uses a series of 16 addresses.
If the network communicates with a number of PMM modules, use an available series among the following series of 16
addresses for each module: 1 to 16 ,17 to 32, 33 to 48, 49 to 64, 65 to 80, 81 to 96, 97 to 112, 113 to 128, 129 to 144, 145
to 160, 161 to 176, 177 to 192, 193 to 208, 209 to 224 and 225 to 241.
The 16 addresses in each series are assigned the following functions:
1st address in the series: reserved for MGE UPS SYSTEMS,
2nd address in the series: access to card BCM1 (status and measurements for output circuits of phase A),
3rd address in the series: access to card BCM2 (status and measurements for output circuits of B),
4th address in the series: access to card BCM3 (status and measurements for output circuits of C),
5th to 8th address in the series: reserved for MGE UPS SYSTEMS,
9th address in the series: access to card MCM (general status and measurements),
10th to 16th address in the series: reserved for MGE UPS SYSTEMS.
As indicated above, four addresses in each series are used to access the information in the registers of four cards,
corresponding to all the status and measurement information presented in the tables on the following pages.
Key for tables:
# :register using 2 bytes,
R/W :read only (R ) or read/write (R/W ) information,
Bit :detail of each bit of the address,
NV :non-volatile information,
Description : description of the concerned information.
Additional explications are provided in the right-hand column if necessary.
Type 2-alarm
contact
OFF
OFF
OFF
ON
Cause
Current on at least one output
circuit between 60% and 80% of
max. value for the circuit.
◗ Current on at least one output
circuit higher than 80% of max.
value for the circuit,
◗ or overvoltage (> 457 V),
◗ or overcurrent (> 250 A).
◗ Temperature rise in the isolation
transformer,
◗ or actuation of remote shutdown
function.
Warning: Do not modify the registers reserved for MGE UPS SYSTEMS. Changing these registers can cause the
PMM module to malfunction.
34020201EN/AB - Page 23
Page 24
6. Appendices
Cards BCM1, BCM2 and BCM3 (status and measurements for 42 or 21 output circuits
of one phase)
All the variables are whole numbers.
#BitR/WNV Description
1RCurrent in circuit 01
2RCurrent in circuit 02
............
............
41RCurrent in circuit 41
42RCurrent in circuit 42
43RNV Global alarm register
0for the register with address 44
1for the register with address 45
2for the register with address 46
3for the register with address 47
4for the register with address 48
5for the register with address 49
6 to 15Unused bits
44R/WNV Minor alarms on circuits 1 to 16
060% < Current in circuit 01 < 80%
160% < Current in circuit 02 < 80%
260% < Current in circuit 03 < 80%
360% < Current in circuit 04 < 80%
460% < Current in circuit 05 < 80%
560% < Current in circuit 06 < 80%
660% < Current in circuit 07 < 80%
760% < Current in circuit 08 < 80%
860% < Current in circuit 09 < 80%
960% < Current in circuit 10 < 80%
1060% < Current in circuit 11 < 80%
1160% < Current in circuit 12 < 80%
1260% < Current in circuit 13 < 80%
1360% < Current in circuit 14 < 80%
1460% < Current in circuit 15 < 80%
1560% < Current in circuit 16 < 80%
45R/WNV Minor alarms on circuits 17 to 32
060% < Current in circuit 17 < 80%
160% < Current in circuit 18 < 80%
260% < Current in circuit 19 < 80%
360% < Current in circuit 20 < 80%
460% < Current in circuit 21 < 80%
560% < Current in circuit 22 < 80%
660% < Current in circuit 23 < 80%
760% < Current in circuit 24 < 80%
860% < Current in circuit 25 < 80%
960% < Current in circuit 26 < 80%
1060% < Current in circuit 27 < 80%
1160% < Current in circuit 28 < 80%
1260% < Current in circuit 29 < 80%
1360% < Current in circuit 30 < 80%
1460% < Current in circuit 31 < 80%
1560% < Current in circuit 32 < 80%
46R/WNV Minor alarms on circuits 33 to 42
060% < Current in circuit 33 < 80%
160% < Current in circuit 34 < 80%
260% < Current in circuit 35 < 80%
360% < Current in circuit 36 < 80%
460% < Current in circuit 37 < 80%
560% < Current in circuit 38 < 80%
660% < Current in circuit 39 < 80%
760% < Current in circuit 40 < 80%
860% < Current in circuit 41 < 80%
960% < Current in circuit 42 < 80%
10 to 15Unused bits (all set to 0)
Each element represents the value in mA of
the current in the given output circuit.
This register provides a rapid overview of
the status of the alarms on the card.
The global alarm bit is 1 if any one of the 16
bits of the indicated register is 1.
These bits go to 1 when the current in a
corresponding output circuit is greater than
the minor alarm threshold (60% in the
example opposite) and less than the major
alarm threshold (80% in the example
opposite). This state is stored in memory
until the alarm is reset by setting the bit to 0.
Page 24 - 34020201EN/AB
Page 25
#BitR/WNV Description
47R/WNV Major alarms on circuits 1 to 16
0Current in circuit 01 > 80%
1Current in circuit 02 > 80%
2Current in circuit 03 > 80%
3Current in circuit 04 > 80%
4Current in circuit 05 > 80%
5Current in circuit 06 > 80%
6Current in circuit 07 > 80%
7Current in circuit 08 > 80%
8Current in circuit 09 > 80%
9Current in circuit 10 > 80%
10Current in circuit 11 > 80%
11Current in circuit 12 > 80%
12Current in circuit 13 > 80%
13Current in circuit 14 > 80%
14Current in circuit 15 > 80%
15Current in circuit 16 > 80%
48R/WNV Major alarms on circuits 17 to 32
0Current in circuit 17 > 80%
1Current in circuit 18 > 80%
2Current in circuit 19 > 80%
3Current in circuit 20 > 80%
4Current in circuit 21 > 80%
5Current in circuit 22 > 80%
6Current in circuit 23 > 80%
7Current in circuit 24 > 80%
8Current in circuit 25 > 80%
9Current in circuit 26 > 80%
10Current in circuit 27 > 80%
11Current in circuit 28 > 80%
12Current in circuit 29 > 80%
13Current in circuit 30 > 80%
14Current in circuit 31 > 80%
15Current in circuit 32 > 80%
49R/WNV Major alarms on circuits 33 to 42
0Current in circuit 33 > 80%
1Current in circuit 34 > 80%
2Current in circuit 35 > 80%
3Current in circuit 36 > 80%
4Current in circuit 37 > 80%
5Current in circuit 38 > 80%
6Current in circuit 39 > 80%
7Current in circuit 40 > 80%
8Current in circuit 41 > 80%
9Current in circuit 42 > 80%
10 to 15Unused bits (all set to 0)
50RNV Reserved for MGE UPS SYSTEMS
51RNV Reserved for MGE UPS SYSTEMS
52R/WNV Rating of breaker on circuit 01
53R/WNV Rating of breaker on circuit 02
54R/WNV Rating of breaker on circuit 03
55R/WNV Rating of breaker on circuit 04
56R/WNV Rating of breaker on circuit 05
57R/WNV Rating of breaker on circuit 06
58R/WNV Rating of breaker on circuit 07
59R/WNV Rating of breaker on circuit 08
60R/WNV Rating of breaker on circuit 09
61R/WNV Rating of breaker on circuit 10
62R/WNV Rating of breaker on circuit 11
63R/WNV Rating of breaker on circuit 12
64R/WNV Rating of breaker on circuit 13
65R/WNV Rating of breaker on circuit 14
66R/WNV Rating of breaker on circuit 15
67R/WNV Rating of breaker on circuit 16
68R/WNV Rating of breaker on circuit 17
6. Appendices
These bits go to 1 when the current in a
corresponding output circuit is greater than
the major alarm threshold (80% in the
example opposite). This state is stored in
memory until the alarm is reset by setting
the bit to 0.
Circuit breaker ratings in amps (16).
Must not be modified.
34020201EN/AB - Page 25
Page 26
6. Appendices
#BitR/WNV Description
69R/WNV Rating of breaker on circuit 18
70R/WNV Rating of breaker on circuit 19
71R/WNV Rating of breaker on circuit 20
72R/WNV Rating of breaker on circuit 21
73R/WNV Rating of breaker on circuit 22
74R/WNV Rating of breaker on circuit 23
75R/WNV Rating of breaker on circuit 24
76R/WNV Rating of breaker on circuit 25
77R/WNV Rating of breaker on circuit 26
78R/WNV Rating of breaker on circuit 27
79R/WNV Rating of breaker on circuit 28
80R/WNV Rating of breaker on circuit 29
81R/WNV Rating of breaker on circuit 30
82R/WNV Rating of breaker on circuit 31
83R/WNV Rating of breaker on circuit 32
84R/WNV Rating of breaker on circuit 33
85R/WNV Rating of breaker on circuit 34
86R/WNV Rating of breaker on circuit 35
87R/WNV Rating of breaker on circuit 36
88R/WNV Rating of breaker on circuit 37
89R/WNV Rating of breaker on circuit 38
90R/WNV Rating of breaker on circuit 39
91R/WNV Rating of breaker on circuit 40
92R/WNV Rating of breaker on circuit 41
93R/WNV Rating of breaker on circuit 42
94R/WNV Minor alarm threshold (%) for circuit 01
95R/WNV Minor alarm threshold (%) for circuit 02
96R/WNV Minor alarm threshold (%) for circuit 03
97R/WNV Minor alarm threshold (%) for circuit 04
98R/WNV Minor alarm threshold (%) for circuit 05
99R/WNV Minor alarm threshold (%) for circuit 06
100R/WNV Minor alarm threshold (%) for circuit 07
101R/WNV Minor alarm threshold (%) for circuit 08
102R/WNV Minor alarm threshold (%) for circuit 09
103R/WNV Minor alarm threshold (%) for circuit 10
104R/WNV Minor alarm threshold (%) for circuit 11
105R/WNV Minor alarm threshold (%) for circuit 12
106R/WNV Minor alarm threshold (%) for circuit 13
107R/WNV Minor alarm threshold (%) for circuit 14
108R/WNV Minor alarm threshold (%) for circuit 15
109R/WNV Minor alarm threshold (%) for circuit 16
110R/WNV Minor alarm threshold (%) for circuit 17
111R/WNV Minor alarm threshold (%) for circuit 18
112R/WNV Minor alarm threshold (%) for circuit 19
113R/WNV Minor alarm threshold (%) for circuit 20
114R/WNV Minor alarm threshold (%) for circuit 21
115R/WNV Minor alarm threshold (%) for circuit 22
116R/WNV Minor alarm threshold (%) for circuit 23
117R/WNV Minor alarm threshold (%) for circuit 24
118R/WNV Minor alarm threshold (%) for circuit 25
119R/WNV Minor alarm threshold (%) for circuit 26
120R/WNV Minor alarm threshold (%) for circuit 27
121R/WNV Minor alarm threshold (%) for circuit 28
122R/WNV Minor alarm threshold (%) for circuit 29
123R/WNV Minor alarm threshold (%) for circuit 30
124R/WNV Minor alarm threshold (%) for circuit 31
125R/WNV Minor alarm threshold (%) for circuit 32
126R/WNV Minor alarm threshold (%) for circuit 33
127R/WNV Minor alarm threshold (%) for circuit 34
128R/WNV Minor alarm threshold (%) for circuit 35
129R/WNV Minor alarm threshold (%) for circuit 36
130R/WNV Minor alarm threshold (%) for circuit 37
131R/WNV Minor alarm threshold (%) for circuit 38
132R/WNV Minor alarm threshold (%) for circuit 39
133R/WNV Minor alarm threshold (%) for circuit 40
134R/WNV Minor alarm threshold (%) for circuit 41
135R/WNV Minor alarm threshold (%) for circuit 42
Page 26 - 34020201EN/AB
These registers define the minor alarm
thresholds.
A minor alarm occurs when the current in a
given output circuit is greater than the minor
alarm threshold and less than the major
alarm threshold for a duration exceeding the
minor alarm time delay.
The units are in % (60 = 60%).
The setting range is from 0 to 100.
The factory setting is 60.
A minor alarm is not activated if the current
goes instantaneously from one threshold to
the other.
Page 27
#BitR/WNV Description
136R/WNV Major alarm threshold (%) for circuit 01
137R/WNV Major alarm threshold (%) for circuit 02
138R/WNV Major alarm threshold (%) for circuit 03
139R/WNV Major alarm threshold (%) for circuit 04
140R/WNV Major alarm threshold (%) for circuit 05
141R/WNV Major alarm threshold (%) for circuit 06
142R/WNV Major alarm threshold (%) for circuit 07
143R/WNV Major alarm threshold (%) for circuit 08
144R/WNV Major alarm threshold (%) for circuit 09
145R/WNV Major alarm threshold (%) for circuit 10
146R/WNV Major alarm threshold (%) for circuit 11
147R/WNV Major alarm threshold (%) for circuit 12
148R/WNV Major alarm threshold (%) for circuit 13
149R/WNV Major alarm threshold (%) for circuit 14
150R/WNV Major alarm threshold (%) for circuit 15
151R/WNV Major alarm threshold (%) for circuit 16
152R/WNV Major alarm threshold (%) for circuit 17
153R/WNV Major alarm threshold (%) for circuit 18
154R/WNV Major alarm threshold (%) for circuit 19
155R/WNV Major alarm threshold (%) for circuit 20
156R/WNV Major alarm threshold (%) for circuit 21
157R/WNV Major alarm threshold (%) for circuit 22
158R/WNV Major alarm threshold (%) for circuit 23
159R/WNV Major alarm threshold (%) for circuit 24
160R/WNV Major alarm threshold (%) for circuit 25
161R/WNV Major alarm threshold (%) for circuit 26
162R/WNV Major alarm threshold (%) for circuit 27
163R/WNV Major alarm threshold (%) for circuit 28
164R/WNV Major alarm threshold (%) for circuit 29
165R/WNV Major alarm threshold (%) for circuit 30
166R/WNV Major alarm threshold (%) for circuit 31
167R/WNV Major alarm threshold (%) for circuit 32
168R/WNV Major alarm threshold (%) for circuit 33
169R/WNV Major alarm threshold (%) for circuit 34
170R/WNV Major alarm threshold (%) for circuit 35
171R/WNV Major alarm threshold (%) for circuit 36
172R/WNV Major alarm threshold (%) for circuit 37
173R/WNV Major alarm threshold (%) for circuit 38
174R/WNV Major alarm threshold (%) for circuit 39
175R/WNV Major alarm threshold (%) for circuit 40
176R/WNV Major alarm threshold (%) for circuit 41
177R/WNV Major alarm threshold (%) for circuit 42
178R/WNV Minor alarm delay for circuit 01
179R/WNV Minor alarm delay for circuit 02
180R/WNV Minor alarm delay for circuit 03
181R/WNV Minor alarm delay for circuit 04
182R/WNV Minor alarm delay for circuit 05
183R/WNV Minor alarm delay for circuit 06
184R/WNV Minor alarm delay for circuit 07
185R/WNV Minor alarm delay for circuit 08
186R/WNV Minor alarm delay for circuit 09
187R/WNV Minor alarm delay for circuit 10
188R/WNV Minor alarm delay for circuit 11
189R/WNV Minor alarm delay for circuit 12
190R/WNV Minor alarm delay for circuit 13
191R/WNV Minor alarm delay for circuit 14
192R/WNV Minor alarm delay for circuit 15
193R/WNV Minor alarm delay for circuit 16
194R/WNV Minor alarm delay for circuit 17
195R/WNV Minor alarm delay for circuit 18
196R/WNV Minor alarm delay for circuit 19
197R/WNV Minor alarm delay for circuit 20
198R/WNV Minor alarm delay for circuit 21
199R/WNV Minor alarm delay for circuit 22
200R/WNV Minor alarm delay for circuit 23
201R/WNV Minor alarm delay for circuit 24
6. Appendices
These registers define the major alarm
thresholds.
A major alarm occurs when the current in a
given output circuit is greater than the major
alarm threshold a duration exceeding the
major alarm time delay.
The units are in % (80 = 80%).
The setting range is from 0 to 100.
The factory setting is 80.
Minor alarm time delay for each output
circuit.
This delay is expressed in seconds (from 0
to 65535 seconds).
The factory setting is 10 seconds.
34020201EN/AB - Page 27
Page 28
6. Appendices
#BitR/WNV Description
202R/WNV Minor alarm delay for circuit 25
203R/WNV Minor alarm delay for circuit 26
204R/WNV Minor alarm delay for circuit 27
205R/WNV Minor alarm delay for circuit 28
206R/WNV Minor alarm delay for circuit 29
207R/WNV Minor alarm delay for circuit 30
208R/WNV Minor alarm delay for circuit 31
209R/WNV Minor alarm delay for circuit 32
210R/WNV Minor alarm delay for circuit 33
211R/WNV Minor alarm delay for circuit 34
212R/WNV Minor alarm delay for circuit 35
213R/WNV Minor alarm delay for circuit 36
214R/WNV Minor alarm delay for circuit 37
215R/WNV Minor alarm delay for circuit 38
216R/WNV Minor alarm delay for circuit 39
217R/WNV Minor alarm delay for circuit 40
218R/WNV Minor alarm delay for circuit 41
219R/WNV Minor alarm delay for circuit 42
220R/WNV Major alarm delay for circuit 01
221R/WNV Major alarm delay for circuit 02
222R/WNV Major alarm delay for circuit 03
223R/WNV Major alarm delay for circuit 04
224R/WNV Major alarm delay for circuit 05
225R/WNV Major alarm delay for circuit 06
226R/WNV Major alarm delay for circuit 07
227R/WNV Major alarm delay for circuit 08
228R/WNV Major alarm delay for circuit 09
229R/WNV Major alarm delay for circuit 10
230R/WNV Major alarm delay for circuit 11
231R/WNV Major alarm delay for circuit 12
232R/WNV Major alarm delay for circuit 13
233R/WNV Major alarm delay for circuit 14
234R/WNV Major alarm delay for circuit 15
235R/WNV Major alarm delay for circuit 16
236R/WNV Major alarm delay for circuit 17
237R/WNV Major alarm delay for circuit 18
238R/WNV Major alarm delay for circuit 19
239R/WNV Major alarm delay for circuit 20
240R/WNV Major alarm delay for circuit 21
241R/WNV Major alarm delay for circuit 22
242R/WNV Major alarm delay for circuit 23
243R/WNV Major alarm delay for circuit 24
244R/WNV Major alarm delay for circuit 25
245R/WNV Major alarm delay for circuit 26
246R/WNV Major alarm delay for circuit 27
247R/WNV Major alarm delay for circuit 28
248R/WNV Major alarm delay for circuit 29
249R/WNV Major alarm delay for circuit 30
250R/WNV Major alarm delay for circuit 31
251R/WNV Major alarm delay for circuit 32
252R/WNV Major alarm delay for circuit 33
253R/WNV Major alarm delay for circuit 34
254R/WNV Major alarm delay for circuit 35
255R/WNV Major alarm delay for circuit 36
256R/WNV Major alarm delay for circuit 37
257R/WNV Major alarm delay for circuit 38
258R/WNV Major alarm delay for circuit 39
259R/WNV Major alarm delay for circuit 40
260R/WNV Major alarm delay for circuit 41
261R/WNV Major alarm delay for circuit 42
262 to 267Reserved for MGE UPS SYSTEMS
Major alarm time delay for each output
circuit.
This delay is expressed in seconds (from 0
to 65535 seconds).
The factory setting is 10 seconds.
Page 28 - 34020201EN/AB
Page 29
#BitR/WNV Description
268WGlobal circuit breaker rating
269WGlobal minor alarm threshold (%)
270WGlobal major alarm threshold (%)
271WGlobal minor alarm time delay
272WGlobal major alarm time delay
273 to 280Reserved for MGE UPS SYSTEMS
281RNon-stored minor alarms
060% < Current in circuit 01 < 80%
160% < Current in circuit 02 < 80%
260% < Current in circuit 03 < 80%
360% < Current in circuit 04 < 80%
460% < Current in circuit 05 < 80%
560% < Current in circuit 06 < 80%
660% < Current in circuit 07 < 80%
760% < Current in circuit 08 < 80%
860% < Current in circuit 09 < 80%
960% < Current in circuit 10 < 80%
1060% < Current in circuit 11 < 80%
1160% < Current in circuit 12 < 80%
1260% < Current in circuit 13 < 80%
1360% < Current in circuit 14 < 80%
1460% < Current in circuit 15 < 80%
1560% < Current in circuit 16 < 80%
282RNon-stored minor alarms
060% < Current in circuit 17 < 80%
160% < Current in circuit 18 < 80%
260% < Current in circuit 19 < 80%
360% < Current in circuit 20 < 80%
460% < Current in circuit 21 < 80%
560% < Current in circuit 22 < 80%
660% < Current in circuit 23 < 80%
760% < Current in circuit 24 < 80%
860% < Current in circuit 25 < 80%
960% < Current in circuit 26 < 80%
1060% < Current in circuit 27 < 80%
1160% < Current in circuit 28 < 80%
1260% < Current in circuit 29 < 80%
1360% < Current in circuit 30 < 80%
1460% < Current in circuit 31 < 80%
1560% < Current in circuit 32 < 80%
283RNon-stored minor alarms
060% < Current in circuit 33 < 80%
160% < Current in circuit 34 < 80%
260% < Current in circuit 35 < 80%
360% < Current in circuit 36 < 80%
460% < Current in circuit 37 < 80%
560% < Current in circuit 38 < 80%
660% < Current in circuit 39 < 80%
760% < Current in circuit 40 < 80%
860% < Current in circuit 41 < 80%
960% < Current in circuit 42 < 80%
10 to 15Unused bits (all set to 0)
284RNon-stored major alarms
0Current in circuit 01 > 80%
1Current in circuit 02 > 80%
2Current in circuit 03 > 80%
3Current in circuit 04 > 80%
4Current in circuit 05 > 80%
5Current in circuit 06 > 80%
6Current in circuit 07 > 80%
7Current in circuit 08 > 80%
8Current in circuit 09 > 80%
9Current in circuit 10 > 80%
10Current in circuit 11 > 80%
11Current in circuit 12 > 80%
6. Appendices
A value entered in the global parameters to
enable the 42 (or 21) output circuits to be set
to that value at the same time.
These bits go to 1 when the current in a
corresponding output circuit is greater than
the minor alarm threshold (60% in the
example opposite) and less than the major
alarm threshold (80% in the example
opposite).
This state is not stored in memory.
These bits go to 1 when the current in a
corresponding output circuit is greater than
the major alarm threshold (80% in the
example opposite).
This state is not stored in memory.
34020201EN/AB - Page 29
Page 30
6. Appendices
#BitR/WNV Description
12Current in circuit 13 > 80%
13Current in circuit 14 > 80%
14Current in circuit 15 > 80%
15Current in circuit 16 > 80%
285RNon-stored major alarms
0Current in circuit 17 > 80%
1Current in circuit 18 > 80%
2Current in circuit 19 > 80%
3Current in circuit 20 > 80%
4Current in circuit 21 > 80%
5Current in circuit 22 > 80%
6Current in circuit 23 > 80%
7Current in circuit 24 > 80%
8Current in circuit 25 > 80%
9Current in circuit 26 > 80%
10Current in circuit 27 > 80%
11Current in circuit 28 > 80%
12Current in circuit 29 > 80%
13Current in circuit 30 > 80%
14Current in circuit 31 > 80%
15Current in circuit 32 > 80%
286RNon-stored major alarms
0Current in circuit 33 > 80%
1Current in circuit 34 > 80%
2Current in circuit 35 > 80%
3Current in circuit 36 > 80%
4Current in circuit 37 > 80%
5Current in circuit 38 > 80%
6Current in circuit 39 > 80%
7Current in circuit 40 > 80%
8Current in circuit 41 > 80%
9Current in circuit 42 > 80%
10 to 15Unused bits (all set to 0)
Page 30 - 34020201EN/AB
Page 31
Card MCM (general status and measurements)
The variables entered in registers 1 to 74 are whole numbers read on 16 bits.
The variables entered in registers 1 to 29 are also accessible in “floating” format on 32 bits (registers 257 to 314 in the
“Float.” column of the table). The “floating” variables are read only.
Multiply each value in whole number format by the coefficient indicated in the “Coeff.” column of the table.
#BitFloat.R/WNVCoeff. Description
1257/258R/WNV0.1Energy consumed in kWh (least significant bit of the word)*
2259/260R/WNV6553.6 Energy consumed in kWh (most significant bit of the word)*
3261/262R0.1Total active power in kW
4263/264R0.1Total reactive power in kVAR
5265/266R0.1Total apparent power in kVA
6267/268R0.0001 Total power factor
7269/270R0.01Average of the phase-to-phase voltages in the 3 phases in V
8271/272R0.01Average of the phase-to-neutral voltages in the 3 phases in V
9273/274R0.1Average of the current in the 3 phases in A
10275/276R0.01Frequency in Hz
11277/278R0.1Active power for phase A in kW
12279/280R0.1Active power for phase B in kW
13281/282R0.1Active power for phase C in kW
14283/284R0.0001 Power factor for phase A
15285/286R0.0001 Power factor for phase B
16287/288R0.0001 Power factor for phase C
17289/290R0.01Voltage between phase A and B in V
18291/292R0.01Voltage between phase B and C in V
19293/294R0.01Voltage between phase C and A in V
20295/296R0.01Voltage between phase A and the neutral in V
21297/298R0.01Voltage between phase B and the neutral in V
22299/300R0.01Voltage between phase C and the neutral in V
23301/302R0.1Current in phase A in A
24303/304R0.1Current in phase B in A
25305/306R0.1Current in phase C in A
26307/308R0.1Neutral current in A
27309/310R/W0.1Average total active power in kW*
28311/312R/W0.1Minimum total active power in kW*
29313/314R/W0.1Maximum total active power in kW*
30 to 36R/WNVReserved for MGE UPS SYSTEMS
37R/WNVAlarms
0Stored overload alarms (bit set to 1). Reset by setting bit to 0.
1 to 3Unused bits (set to 0)
4Stored overvoltage alarms (bit set to 1). Reset by setting bit to 0.
5 to 15Unused bits (set to 0)
38 to 42R/WNVReserved for MGE UPS SYSTEMS
43 to 48RReserved for MGE UPS SYSTEMS
49RNVAlarms
0Non-stored overload alarms (bit set to 1).
1 to 3Unused bits (set to 0)
4Non-stored overvoltage alarms (bit set to 1).
5 to 15Unused bits (set to 0)
50 to 74Reserved for MGE UPS SYSTEMS
6. Appendices
*: Values valid since the last reset. Reset is carried out by writing a whole number value.
34020201EN/AB - Page 31
Page 32
6. Appendices
6.5 Glossary
ALARMMajor alarm signalling that the current in the output circuit considered is higher than 80%
AUX ALARM INPUTAlarm indicating either:
DOWNScroll button used to access previous measurement (metering mode) or setting (setup
Isolation transformerOptional transformer used to provide galvanic isolation between the distribution system
METERFunction button for access to the next measurements (metering mode) or to return to
Output circuitSingle-phase circuit (phase, neutral and earth) exiting the PMM module, protected by a
OVER CURRENTAlarm indicating an overload on the PMM module.
of its rated value.
◗ excessive temperature rise in the isolation transformer,
◗ actuation of the remote shutdown function.
mode).
and the output circuits, to block reinjection of third-order harmonics upstream or to create
a neutral if the distribution system does not have one.
MONITORING mode (alarm or setup mode).
single standard circuit breaker (PMM module with 126 output circuits) or by a circuit
breaker with earth-leakage protection (PMM module with 60 output circuits).
OVER VOLTAGEAlarm indicating that the voltage of the distribution system is too high.
PMMPower Management Module (the device in question).
RS-232Serial communication standard using a SUB-D 9-pin connector.
RS-485Serial communication standard available via a screw-terminal block.
SELECTFunction button used to obtain a fixed display if autoscroll (parameter rotation) is
activated, clear an alarm (alarm mode) or access the next parameter to be set (setup
mode).
UPScroll button used to access next measurement (metering mode) or setting (setup
mode).
WARNINGMinor alarm signalling that the current in the output circuit considered is between 60 and