MGE UPS Systems 1500C User Manual

www.mgeups.com
MGE UPS SYSTEMS
Pulsar EXtreme CLA
1500C
Installation and user manual
51031998EN/AA - Page 1
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EXtreme a reference in environmental protection include:
the eco-design approach used in product development; recycling of Pulsar EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
Safety rules
Safety of persons
When the batteries are connected to the UPS, the outlets may be energised even if the UPS is disconnected from the AC input source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 mA.
Product safety
UPSs must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power source by removing the power cord.
Never install the UPS near liquids or in an excessively damp environment.Never let a foreign body penetrate inside the UPS.Never block the ventilation grates of the UPS.Never expose the UPS to direct sunlight or a source of heat.
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order. Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. If the UPS must be stored prior to installation, storage must be in a dry place. The admissible storage temperature range is -20° C to +45° C. If the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 48 hours, at least once every month. This charges the battery, thus avoiding possible irreversible damage. Prior to handling the battery:
remove all watches, rings, bracelets and any other metal objects;use tools with insulated handles.
Safety
51031998EN/AA - Page 3
Foreword
Using this document
Information may be found primarily by consulting:
the contents,the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Earth cables
Other cables
Contents
1. Presentation
1.1 Pulsar EXtreme range................................................................................................................. 7
Tower model.................................................................................................................................... 7
Rack model ..................................................................................................................................... 7
1.2 Back ............................................................................................................................................. 8
Tower model.................................................................................................................................... 8
Rack model ..................................................................................................................................... 9
1.3 Control panel ............................................................................................................................... 10
2. Installation
2.1 Unpacking and checks ............................................................................................................... 11
Tower model.................................................................................................................................. 11
Rack model ................................................................................................................................... 12
2.2 Installation of the rack version .................................................................................................. 13
2.3 Connection to the RS 232 or USB communications port (optional)........................................ 14
2.4 Installation of the communications-card option ...................................................................... 15
Tower model.................................................................................................................................. 15
Rack model ................................................................................................................................... 15
2.5 Battery connection ..................................................................................................................... 16
Warning......................................................................................................................................... 16
Interconnecting the batteries to obtain the required configuration ................................................ 16
Connecting the battery configuration to the UPS .......................................................................... 16
2.6 UPS connection and settings .................................................................................................... 19
Tower model.................................................................................................................................. 19
Rack model ................................................................................................................................... 19
3. Operation
3.1 Start-up ........................................................................................................................................ 20
3.2 Bargraph indications .................................................................................................................. 20
3.3 Operation on battery power (following failure of AC input power) ............................................. 21
Transfer to battery power .............................................................................................................. 21
Threshold for the low-battery warning...........................................................................................21
End of backup time ....................................................................................................................... 21
51031998EN/AA - Page 5
Contents
3.4 Personalisation (optional) ........................................................................................................... 22
Function ........................................................................................................................................ 22
"ON / OFF conditions" tab............................................................................................................. 22
"Battery" tab .................................................................................................................................. 22
"Output" tab ................................................................................................................................... 23
"Bypass" tab .................................................................................................................................. 23
3.5 Shutdown..................................................................................................................................... 23
4. Maintenance
4.1 Troubleshooting.......................................................................................................................... 24
5. Environment ............................................................................................................. 26
6. Appendices
6.1 Technical characteristics ........................................................................................................... 27
Simplified diagram ........................................................................................................................ 27
Operating conditions ..................................................................................................................... 27
6.2 Glossary....................................................................................................................................... 28
6.3 Index............................................................................................................................................. 29
1.1 Pulsar EXtreme range
Tower model
1. Presentation
Dimensions in mm
(H x W x D)
235.5 x 145 x 505
Weight in kg
9.5
Rack model
EX1000 Rack
Dimensions in mm
(H x W x D)
88 (2U) x 482.6 x 493
Weight in kg
12.5
51031998EN/AA - Page 7
1. Presentation
1.2 Back
Tower model
4 1 2
USB
RS232
1
2
3
9
10
8
11
6 7
1
slot for communications-card option.
2
RS232 communications port.
3
USB communications port.
four outlets for direct connection of
4
protected equipment.
6
input circuit breaker.
7
socket for connection to AC-power source.
connector for battery connection.
8
9
pushbutton to test phase/neutral inversion of AC-power source.
10
LED indicating phase/neutral inversion of AC-power source.
11
two programmable outlets (outlet 1 and
2).
Rack model
1. Presentation
1
USB
RS232
9210
slot for communications-card option.
1
2
RS232 communications port.
3
USB communications port.
four outlets for direct connection of
4
protected equipment.
6
input circuit breaker.
7
socket for connection to AC-power source.
83
2
1
8
connector for battery connection.
pushbutton to test phase/neutral inversion of
9
411
6
7
AC-power source.
10
LED indicating phase/neutral inversion of AC-power source.
11
two programmable outlets (outlet 1 and 2).
51031998EN/AA - Page 9
1. Presentation
1.3 Control panel
1
2
bypass
%
100%
80%
50%
20%
%
test
Alarms
12
UPS overload.
electronics fault.
13
battery fault.
14
15
hold down to display percent load:
16
- lamp test or buzzer OFF.
- forced transfer to bypass and back
17
by pressing button 3 times in less than 5 seconds.
18
status of programmable outlet 1:
19
status of programmable outlet 2:
operation on bypass
20
(no backup power available).
% battery ␣␣␣␣␣ remaining
100 %
80 %
50 %
20 %
% load
100 %
80 %
50 %
20 %
Supplied with power
Status change in progress.
Page 10 - 51031998EN/AA
operation in ON-LINE mode
21
(backup power available).
22
operation on battery power.
23
ON / OFF.
2.1 Unpacking and checks
Tower model
2. Installation
24
25
27 28
two cords for connection of the protected equipment.
24
RS 232 communications cable.
25
USB communications cable.
26
"UPS Driver" diskette for UPS personalisation.
27
28
"Solution Pac" CD ROM.
29
documentation.
box for battery connection.
30
26
29
30
51031998EN/AA - Page 11
2. Installation
Rack model
24
25
26
24
Rack
EX1000
31
27
28
29
␣24 two cords for connection of the protected equipment.
␣25 RS 232 communications cable.
␣26 USB communications cable.
␣27 "UPS Driver" diskette for UPS personalisation.
␣28 "Solution Pac" CD ROM.
␣29 documentation.
␣30 box for battery connection.
␣31 telescopic rails for mounting in 19" bay with mounting hardware.
30
Page 12 - 51031998EN/AA
2.2 Installation of the rack version
Rack mounting diagram with rails.
2. Installation
3
3
3
3
2
EX1000 Rack
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.
1
4
51031998EN/AA - Page 13
2. Installation
2.3 Connection to the RS 232 or USB communications port (optional)
1 - Connect the RS 232 25 or USB 26 communications cable to the serial port or
25
the USB port on the computer.
USB
RS232
26
USB
3
2
3
2
RS232
The RS 232 and USB communications ports cannot operate simultaneously.
2 - Connect the other end of the communications cable 25 or 26 to the RS 232 2 or USB 3 communications port on the UPS.
The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.
Page 14 - 51031998EN/AA
2.4 Installation of the communications-card option
Tower model
2. Installation
Rack model
USB
RS232
1
2
1
Slot for the communications­card option.
USB
1
Slot for the communications-card option.
2
It is not necessary to shut down the UPS to install the communications card:
1 - Remove the slot 1 cover secured by two screws.
2 - Insert the card in the slot.
3 - Secure the card with the two screws.
1
RS232
51031998EN/AA - Page 15
2. Installation
2.5 Battery connection
Warning
The batteries should be connected only by qualified electrical installation specialists. The work involved in connecting the batteries must be carried out in accordance with all applicable rules and regulations, respecting all safety measures for working on live equipment, i.e. qualified personnel using insulated gloves, protective eyeware, insulated tools, etc.
Interconnecting the batteries to obtain the required configuration
Wire the batteries as indicated in the table below to obtain the required backup time: 2, 4 or 8 hours. Use sealed lead-acid batteries only with ratings of 12 V / 45 Ah for 2-hour configurations and 12 V / 65 Ah for 4-hour and 8-hour backup times.
Typical backup times at
rated power
1500 VA, 1050 W
2 hours
4 hours
8 hours
Configuration
Batteries CSB, Panasonic, Sonnenschein, CEAC, ...
2 parallel strings each made up of 4 x 12 V / 40 Ah batteries connected in series for a total voltage (for the 8 batteries) of 48␣ V.
Connecting the battery configuration to the UPS
The cable and circuit breaker are not supplied.
Connect the battery configuration to terminal 8 of the UPS via a protective circuit breaker (40 A, C curve, short circuit 10␣ kA).
ON
OFF
The circuit breaker must remain open (OFF position). The connection is made using a cable no more than 6 m long made up of 3 x 6/8 mm2 conductors (Battery+, Battery- and earth) fitted with metal caps at both ends (we recommend using a shielded cable for equipment that is sensitive to disturbances).
2 parallel strings each made up of 4 x 12V / 65 Ah batteries connected in series for a total voltage (for the 8 batteries) of 48␣ V.
4 parallel strings each made up of 4 x 12 V / 65 Ah batteries connected in series for a total voltage (for the 16 batteries) of 48 V.
Page 16 - 51031998EN/AA
g
Tower model
2. Installation
8
b
40A
12V-65Ah
40A
40 A curve C
Cable and circuit-breaker not supplied
e
10
140
10
f
10
10
OFF
a
c
d
6 m max.
j
i
h
51031998EN/AA - Page 17
2. Installation
Rack model
40A
12V-65Ah
40A
OFF
40 A curve C
Cable and circuit-breaker not provided
e
10
f
10
140
10
10
1
2
USB
RS232
8
1
2
b
c
a
6 m max.
d
g
Page 18 - 51031998EN/AA
j
1
2
1
2
i
h
2.6 UPS connection and settings
Tower model
Rack model
1
2
11
24
24
2. Installation
Connecting the UPS to the AC-input source
1 - Remove the power cord supplying the
4
equipment. Check cord characteristics (> 250 V, 10 A, see the technical sheet). 2 - Connect the cord to the AC-power socket ␣␣7 on the UPS, then to the AC-power wall outlet.
Setting the UPS for the installed battery configuration
(For a 2-hour configuration, skip this step, this is the default setting for the UPS). The UPS is set using the “UPS Driver”
7
personalisation software that comes with the UPS. To use the software, use an RS232 cable to connect a PC to the UPS. Run the “UPS Driver” software on the
4
diskette, go to the “battery” menu and select the type of CLA charger (2, 4 or 8 hours of backup time). Once the type of CLA charger has been selected, click “save” and quit “UPS Driver”.
The installation is now configured.
Connecting the UPS to the equipment to be protected
7
1 - Close the battery circuit
11
breaker. 2 - Connect the protected equipment to the UPS using the cords 24 . It is advised to connect priority loads to the four outlets ␣ ␣ 4 and any non­priority loads to the two programmable outlets 11 .
51031998EN/AA - Page 19
ON
OFF
3. Operation
3.1 Start-up
The protected equipment connected to the UPS can be energised, whether AC input power is available or not.
3.2 Bargraph indications
Caution: the AC input power source must be present when energising for the first time. Press the ON / OFF button 23 . The buzzer beeps and all the LEDs go ON. The buzzer beeps twice, then:
- If AC input power is available, LED 21 goes ON, indicating operation
21
22 23
in ON-LINE mode.
- If AC input power is not available and the UPS is configured for automatic restart mode, the buzzer beeps three times and LED 22 goes ON, signalling operation on battery power.
All connected equipment is energised.
If LEDs 21 or 22 do not go ON or if LEDs 12 to 14 flash, there is a fault (see section 4.1).
Page 20 - 51031998EN/AA
1
2
bypass
100%
80%
50%
20%
test
%
%
12
13
14
15
16
18
19
1 - Remaining backup time in percent (during normal operation).
2 - Percent load drawn by the protected equipment, when button 16 is pressed.
3 - Operating faults (flashing LED and beeps):
␣ 12 Overload. ␣ 13 UPS fault. ␣ 14 Battery fault.
Status LEDs 18 and 19 for programmable outlets 1 and 2:
- LEDs OFF: the outlets are not supplied with power.
- LEDs flashing: status change in progress.
- LEDs ON: the outlets are supplied with power. Outlets 1 and 2 can be remotely programmed and controlled. They may be used for sequential start-up of the protected applications, shedding of non-priority applications during operation on battery power, and priority management at the end of battery backup time to reserve the longest possible backup time for the most sensitive applications. These outlets are programmed using Solution Pac software.
LEDs 12 to 15 provide three different indications:
3. Operation
3.3 Operation on battery power (following failure of AC input power)
Transfer to battery power
1
2
bypass
Threshold for the low-battery warning
1
2
bypass
End of backup time
The AC-power source is outside tolerances, LED 23 is ON, the buzzer beeps three times.
The equipment connected to the UPS is supplied by the battery.
22
The low-battery warning threshold can be set by the user, with the "UPS Driver" software (see section 3.4). LED 22 flashes. The buzzer beeps every three seconds.
There is very little remaining battery backup time. Close all
22
applications because UPS automatic shutdown is imminent.
%
test
1
2
bypass
The buzzer sounds continuously. Press button 17 to turn the buzzer OFF.
17
The equipment is no longer supplied with power.
The UPS goes to sleep mode at the end of the battery backup time until complete shutdown due to tripping of the battery­protection function against deep discharge.
Return of AC input power: If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.4).
51031998EN/AA - Page 21
3. Operation
3.4 Personalisation (optional)
Function
Personalisation parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 (or USB) communications port).
Check that the RS 232 25 or USB 26 cable is properly connected.
"UPS Driver" installation:
1 - Insert the "UPS Driver" diskette in the drive of a PC running Windows. 2 - Select the disk drive (A:\). 3 - Double-click "upsdriv.exe".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.
"ON / OFF conditions" tab
"Battery" tab
Page 22 - 51031998EN/AA
Personalisable function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
Personalisable function
Automatic "Battery test" intervals
"Low-battery warning" threshold
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled
Default setting
Every day
20% remaining battery backup time
Options
Disabled
Disabled
Disabled
Enabled
Disabled
Options
Once a week
Once a month
No test
40% remaining battery backup time
"Output" tab
3. Operation
"Bypass" tab
Personalisable function
Rated UPS voltage
Rated UPS frequency
UPS tolerance for AC-power
source frequency
Overload alarm threshold
UPS restart following short-circuit
Personalisable function
Transfer to bypass if overload
Transfer to bypass following a fault, whatever the
conditions on the AC-power source
bypass
Default setting
230 V
F = 50 Hz
F ± 5 %
110 %
Disabled
Default setting
Enabled
Disabled
Press button 23 (return to the OFF position).
The connected equipment is no longer supplied with power.
200 V - 210 V - 220 V - 240 V
F ± 1 % to ± 10 %, in 1 % steps
Enabled (click to add check)
Disabled (click to remove check)
Enabled (click to add check)
Options
60 Hz
0 to 110 %, in 10 % steps
Options
23
51031998EN/AA - Page 23
4. Maintenance
4.1 Troubleshooting
If any of LEDs 12 , 13 or 14 flash, there is a operating anomaly or an alarm.
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support
Indication
LED 12 flashes and the buzzer beeps.
LED 14 flashes.
The yellow LED ␣ 15. flashes, the red indicator light 10 behind the UPS comes on and the buzzer sounds continuously.
Signification
UPS overload. Overload is too long or too high.
If AC power is present and within tolerances, the UPS
goes to bypass mode (supply directly by the AC-power source). LED 20 flashes. The buzzer beeps every seconds.
If AC power is not present or not within tolerances,
the connected applications are no longer supplied. The buzzer sounds continuously.
A battery fault was detected during the automatic battery test.
The function for monitoring the phase and neutral position of your electrical network has detected a reversal.
Correction
Check the power drawn by the equipment and disconnect any non­priority devices.
Check that the battery connector is
fully pushed in.
Replace battery module (see the
Maintenance section).
Directly earthed neutral type networks: to correct cabling, unplug and turn the network socket, of the DIN-SCHUKO type, by 180 degrees or contact an electrician to modify your electrical network.
For all other network types, de­activate the detection function (this function is only operational for directly earthed neutral electrical networks):
Press for at least 5 seconds the pushbutton 9 behind the UPS (UPS stopped and connected to the network for less than 30 minutes).
Page 24 - 51031998EN/AA
Troubleshooting requiring MGE UPS SYSTEMS after-sales support
4. Maintenance
Indication
LED 13 flashes and the buzzer sounds continuously.
Signification
UPS electronics have detected a UPS fault. Depending on the UPS personalisation parameters (see section 3.4), there are two possibilities:
the equipment connected to the UPS continues to be
supplied, but directly from the AC-power source (via the automatic bypass (LED 20 ON);
the connected equipment is no longer supplied.
The equipment connected to the UPS is no
longer protected.
Correction
Call the after-sales support department.
51031998EN/AA - Page 25
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your MGE UPS SYSTEMS branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by specialised companies.
Page 26 - 51031998EN/AA
Web site: www.mgeups.com
6.1 Technical characteristics
Simplified diagram
Operating conditions
6. Appendices
Relative humidity: 20 to 90 % without condensation. Temperature: 0 to 40° C.
Input voltage and frequency
160 V to 276 V +/- 5 % (at rated power)
50 Hz or 60 Hz +/- 5 %
Output voltage and frequency
200* / 210 / 220 / 230 / 240 V
50 Hz or 60 Hz +/- 5 %
* Except TUV
51031998EN/AA - Page 27
6. Appendices
6.2 Glossary
Authorised voltage range for Upper and lower voltage thresholds within which the UPS can operate on the automatic transfer to bypass if fault or bypass in the event of a UPS fault or overload. overload
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment directly to the
Automatic start following This function automatically starts the UPS when AC input power returns following return of AC input power shutdown at the end of the battery backup time. It can be enabled or disabled.
Backup time Time that the connected equipment can operate on battery power.
Bargraph Device on the front panel indicating the percent remaining backup time or the percent
Battery test Internal UPS test on battery status.
Dialog box A window in a computer program displayed for selection by the user of various options
Double conversion The power supplied to the connected equipment is completely regenerated by
Equipment Devices or systems connected to the UPS output.
Forced shutdown Ten-second interruption in the supply of power to the connected equipment following a
Percent load Ratio between the power drawn by the connected equipment and the total power that
Personalisation A number of UPS functions can be modified using the «UPS Driver» software to better
Programmable outlets Outlets that can be automatically shed during operation on battery power (a shedding
Start on battery power This function makes it possible to energise the connected equipment even when AC
UPS Uninterruptible Power Supply
UPS ON / OFF via software It is possible to enable or disable use of UPS ON / OFF controls by the computer-
AC-power source in the event of a UPS failure or an overload.
load.
and parameter settings.
continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.
system shutdown, even if AC input power returns during the interruption period.
the UPS can supply.
meet the user’s needs.
time delay may be programmed using Solution-Pac software.
input power is not available (operation exclusively on battery power).
system protection software.
Page 28 - 51031998EN/AA
6.3 Index
6. Appendices
A
AC power
Failure .................................................................... 21
Frequency tolerance ............................................... 23
Return ..................................................................... 21
Automatic start ............................................................... 22
B
Bargraph ................................................................... 10-20
Battery
Battery test ............................................................. 22
End of backup time ................................................. 21
Fault .................................................................. 10-20
Handling precautions ................................................ 3
Low-battery warning ............................................... 22
Recycling ............................................................. 3-26
Transfer to battery power ....................................... 21
Buttons .....................................................................8-9-10
Buzzer ....................................................................... 20-21
Bypass
Automatic bypass ......................................... 10-23-25
C
Communication .................................................. 8-9-14-15
Connection
Additional battery module ......................................8-9
Communications card ............................................. 14
RS 232 communications port ................................. 14
USB communications port ...................................... 14
D
Dimensions ...................................................................... 7
E
Environnement .........................................................2-3-26
M
Mode
ON LINE mode .......................................................10
O
Overload ............................................................. 10-23-25
S
Safety ...............................................................................3
Shutdown
Buzzer .............................................................. 10-21
Forced shutdown ....................................................22
UPS ON / OFF via software ................................... 22
UPS shutdown .................................................. 10-23
Sleep mode ....................................................................22
Automatic restart .............................................. 20-23
Software
UPS Driver .............................................................22
Start-up .......................................................................... 20
T
Technical characteristics ................................................27
Temperature
Excessive ambient temp. .......................................27
Transfer (forced) ........................................................... 10
U
UPS Driver .................................................................... 22
UPS fault ............................................................. 10-20-23
UPS storage .................................................................... 3
W
Web site ...........................................................................2
Weight ..............................................................................7
F
Fault (UPS) .................................................... 10-20-24-25
L
LEDs ....................................................................... 8-9-10
Lamp test ................................................................10
51031998EN/AA - Page 29
MGE UPS SYSTEMS
140, Avenue Jean Kuntzmann ZIRST - Montbonnot St Martin 38334 - Saint Ismier Cedex - France www.mgeups.com
5103199800/AA
5103199800-AA
Nothing will stop you now
Loading...