Merlin Gerin Varlogic NR6, Varlogic NR12 User Manual

Page 1
Varlogic NR6, NR12
Power factor controller
User manual
Page 2
Table of Contents
1. General...................................................................................................3
2. Installation ..............................................................................................5
3. Display....................................................................................................6
4. Start-up Procedure.................................................................................6
5. Menu Operations....................................................................................7
5.2 Main Menu .......................................................................................9
5.3 Bank Pre-Configuration .................................................................11
5.4 Commissioning ..............................................................................13
5.5 Auto Setup of Parameters .............................................................14
5.6 Manual Setup of Parameters .........................................................15
5.7 Measurement Menu.......................................................................17
5.8 Parameter Update..........................................................................18
5.9 Alarms Menu..................................................................................19
5.10 Maintenance Menu ......................................................................20
6. Miscellaneous.......................................................................................23
6.1 Stepping Programs........................................................................23
6.2 Manual calculation of response value............................................26
6.3 High Voltage use of NR6/NR12......................................................27
7. Glossary ...............................................................................................29
8. Technical specifications .......................................................................31
2
USER´S MANUAL
Power Factor Controller NR6 / NR12
USER’S MANUAL
Page 3
3
USER´S MANUAL
1. General
1.1 Safety
The following precautions must be taken into account when installing and operating the controller
The installation of the controller must be performed by a qualified electrician
Do not touch the connectors when the controller is energized, make sure that the operating voltage is disconnected before touching any parts located on the rear side of the controller
Do not open a live current circuit, this may cause dangerous overvoltages. Always short circuit the current transformer (CT) before replacing or removing the controller installed in a bank.
Do not open the controller casing, there are no user serviceable parts inside
For better understanding of the terminology used, please refer to the Glossary (chapter 7) at the end of this manual.
1.2 Description
Front view:
Legend
A Display B Keys C Opening of door D Door E Alarm information F Mounting bracket for panel mounting installation
Page 4
Rear view:
Legend
Side view:
Legend
See Chapter 8 for technical specifications.
4
USER´S MANUAL
G Step output connectors H Specification label
I Mounting bracket for panel mounting installation J Fixing spring for DIN-rail mounting K Current/voltage connection inputs L Fan and alarm outputs M DIN-rail mounting installation area
N Screwdriver guide
Page 5
5
USER´S MANUAL
2. Installation
The controller is designed for either panel (cut-out 138 x 138 mm) or DIN-rail installation. It is locked to the rail by a screwdriver-operated fixing spring and to a panel by a side fitting spring.
There are two ways of connecting the controller to the network.
Voltage LN (Line – Neutral) (CT on the same line phase) Voltage LL (Line – Line) (CT on the third phase)
Incorrect connections can be automatically corrected by the controller when Auto Setup is selected from the main menu.
Caution: For use in HV network, look first at chapter 6.3
Figure 1: Controller connections
Page 6
6
USER´S MANUAL
3. Display
The controller is equipped with a backlighted LCD-display.
Figure 2 : Display layout and symbols
4. Start-up Procedure
Before connecting power, check the wiring of all controller terminals. Check carefully for correct operating voltage. Selection of wrong voltage input can permanently damage the controller.
After the first power switch-on, the controller will automatically ask for the language setting of the menu.
Page 7
7
USER´S MANUAL
Figure 3: Language setting dialog
5. Menu Operations
5.1 General
Navigation between different menu levels
As a precaution against accidental use, the access of certain menus has been protected by a keylock, which is a special sequence of keystrokes enabling the use the particular menu item.
Page 8
Figure 4: General way of entering the menu with a keylock
Adjusting a value
Figure 5: Adjusting a value
Special case: The wiring editor
Figure 6: The wiring editor
8
USER´S MANUAL
Page 9
5.2 Main Menu
The main menu contains all basic submenus required to set up and operate the controller.
Which menu to choose?
Figure 7: Required skills and menu selection
If bank preconfiguration is properly done, commissioning does not require any special skill.
9
USER´S MANUAL
Page 10
10
USER´S MANUAL
Figure 8: Main menu
(1) Bank pre-configuration
When factory settings have not been changed, this menu provides the bank builder the means of pre­configuring the bank at the workshop. After pre­configuration, this menu topic is replaced by (2) Commissioning, by which the controller is taken into service.
(3) Automatic setup of parameters
In the event that the controller has not been pre­configured, an inexperienced user can automatically set up all the characteristics of the bank and bring it into service.
(4) Manual setup of parameters
In the event that the controller has not been pre­configured, an experienced user can manually set up all the characteristics of the bank and bring it into service.
(5) Measurement
The measurement menu contains the most common measurements taken from the network and provides some information about the bank. This is a read-only menu.
(7) Alarm settings
To adjust status and parameters of alarms.
(8) Maintenance
The maintenance menu provides some useful information about the usage of the bank, capacitors and contactors. Some auxiliary settings and action have also been provided. This menu is basically intended for use by the manufacturer’s maintenance team.
(6) Parameter update
At any time, an experienced user can access the most common operating parameters from this menu. Unlike the configuration and setup sequences, this is a menu allowing a free and unrestricted entry into all its items and should be used when an occasional parameter access is needed.
Page 11
11
USER´S MANUAL
5.3 Bank Pre-Configuration
This menu item is a forced sequence, meaning that all items must be accessed before the pre­configuration takes place.
NOTE: Do not use of the Bank Pre-Configuration menu for HV network applications
The sequence can be interrupted by pressing key.
See Glossary (chapter 7) for parameters definitions.
Page 12
12
USER´S MANUAL
Figure 9: Bank pre-configuration
Page 13
5.4 Commissioning
A pre-configured controller is put into service by this menu. The sequence contains an automatic parameter verification to check that the manually entered parameters agree with the network used.
See Glossary (chapter 7) for parameter definitions.
NOTE: Do not use of the Commissioning menu for HV network applications
What to do in case of error ?
Error codes can help you to identify a problem and make corrections.
13
USER´S MANUAL
Figure 10: Commissioning
Page 14
Code Meaning
Unstable network: The controller is unable to operate due to excessive load variations on the network. CT oversized.
Step size too small: The effect of the 1
st
step
cannot be measured. CT oversized, wrong wiring, inoperative steps.
Sequence not found: Step ratio does not match available step sequences.
Step size too large: The ratio of measured step compared with the 1
st
step is too large. Step
sequence cannot be resolved.
Non-relevant autosetup process with this bank configuration
Reserved
Wiring verify error: Controller wiring not correct.
Step count error: The Number of Steps setting is incorrect.
Step sequence error: The step size ratios differ from the selected step sequence.
C/K value error.
14
USER´S MANUAL
5.5 Auto Setup of Parameters
The auto setup sequence is intended for inexperienced users so they can commission the bank with minimal prior knowledge. The user need only input three of the most common parameters and then launch an automatic search for the other parameters.
NOTE: The use of Auto Setup of Parameters menu is forbidden on HV network applications
In the event of error, see the Commissioning Menu (chapter 5.4).
Action to do
Enter the parameter settings
manually using Parameter Update menu.
Rerun the commissioning sequence
Check wiring, CT, condition of capacitor steps (1
st
step)
Check the condition and sizes of steps and contactors
Check the condition and sizes of steps and contactors
Use manual setup to confirm or correct the information obtained by autosetup
Check the wiring of voltage­and current inputs
Check the Wiring setting from Parameter Update menu
Check the Number of Steps setting
Check the number of steps in the bank and the condition of steps
Check Step Sequence setting
Check step sizes used in the
bank
Check the response value used
Check the size of 1
st
step in the
bank
to
Page 15
15
USER´S MANUAL
Figure 11: Auto setup of parameters
5.6 Manual Setup of Parameters
The manual setup sequence is intended for experienced users. There are nine important parameters to input before the controller can be taken into service. This sequence is completed by an automatic verification of the parameters entered earlier in this sequence.
This menu item is a forced sequence, meaning that all items must be accessed before the validation of the setup takes place.
The sequence can be interrupted by pressing key.
See Glossary (chapter 7), for parameter definitions.
In case of error, refer to the Commissioning Menu, chapter 5.4.
Page 16
16
USER´S MANUAL
Figure 12: Manual setup of parameters
Page 17
17
USER´S MANUAL
5.7 Measurement Menu
The measurement menu contains the most common measurements taken from the network. This is a read-only menu sequence.
Figure 13: Measurement menu
Page 18
18
USER´S MANUAL
5.8 Parameter Update
The most common operating parameters can be accessed from this menu.
Unlike the configuration and setup sequences presented earlier in this text, this is a menu allowing a free and unrestricted entry into all of its items and should be used when occasional parameter access is needed.
See Glossary (chapter 7), for parameter definitions.
In case of error, refer to the Commissioning Menu, chapter 5.4.
Figure 14: Parameter update
Page 19
5.9 Alarms Menu
In Alarms menu, each individual alarm can be enabled or disabled.
Once an alarm condition is detected, the corresponding alarm number is shown at the upper part of the display, and the alarm symbol is on. The alarm relay is also activated.
List of alarms:
Alarm contacts are
closed when the controller is not energized
opened when the controller is energized without alarm
closed when the controller is energized with alarm
ALRM.SET
informs on the status of each alarm : enabled or disabled
allows enabling or disabling of each individual alarm by setting it ON or OFF. If an alarm
is set to OFF, it cannot cause an alarm under any condition. To allow a normal alarm response, the appropriate alarm must be enabled, i.e. set ON.
Some alarm triggering levels can be adjusted
Alarm No 9 (overtemperature ), with temperature limit setting Alarm No 10 (voltage distortion ), with THD(U) limit setting
An alarm can be reset by an extended pressure of key, this clears all passive alarms.
If alarm condition is still active, the alarm cannot be reset.
19
USER´S MANUAL
Alarm
No
.
1
2
3
4
5
6
7
8
9
10
Alarm Possible cause Controller action
Low power factor
Hunting
Abnormal Cos Phi
Low voltage
Overcapacitive
Wrong frequency
Overcurrent
Overvoltage
Overtemperature
Voltage distortion
Wiring or LL/LN definition error
Undersized bank
Too small C/K value
Wrong program choice
Defective capacitors
(optimal program)
Wiring mistake
overcapacitive network
(welded contactors)
Too low current
Wiring or LL/LN definition error
Improper use of
fixed steps
Wrong or unstable network frequency detected at startup
Undersized CT
Ambient temperature too high
Defective coolingsystem
Harmonic pollution
Resonance
Pauses regulation for 10 minutes
Disconnection till voltage returns
Stop regulation. No automatic restart
Temporary disconnection of steps
Temporary disconnection of steps
Temporary disconnection of steps
Page 20
20
USER´S MANUAL
Figure 15: Alarms menu
5.10 Maintenance menu
The maintenance menu provides useful information about the usage of the bank, capacitors and contactors. Also, some auxiliary settings have been provided.
CAUTION: This menu access is dedicated to specialists.
CAUTION: In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger value (e.g. 600 secs) to prevent destruction of capacitors.
Page 21
21
USER´S MANUAL
Figure 16/1: Maintenance menu
Page 22
22
USER´S MANUAL
Figure 16/2: Maintenance menu
Page 23
23
USER´S MANUAL
6. Miscellaneous
6.1 Stepping programs
The controller's algorithm will try to reach the target cos inside a tolerance area dependant upon the C/K value. It reaches the value by switching on or off available relevant steps.
The regulation step program choice is as follows:
a) Stack Program (linear) : All capacitor steps are of equal size (ex :1.1.1.1). The operation sequence obeys to a last-in- first-out (LIFO) principle. The first step connected will be the last one to be disconnected and vice versa. See Fig. 17
b)
Normal program (2+ linear) Normal program can be used on bank whose step ratio is 1.2.4.4.. The linear sequence starts with the 3rd step. The two first steps are used as fine-tuning. The controller always start by switching the first step then the second. Other steps are used successively See Fig. 18.
c)
Circular A program All capacitor steps are of equal size (ex :1.1.1.1). The operation sequence obeys the first-in-first­out (FIFO) principle. The first step connected will be the first one to be disconnected and vice versa. Then a circular sequence is followed. In order to operate correctly, the number of steps programmed into the controller must strictly comply with the number of physical steps See Fig. 19.
d) Circular B program (1+Circular) Circular B program can be used on a bank whose step ratio is 1.2.2.2 The first step is used as tuning after the activating limit is exceeded. The circular sequence starts with the 2nd step.
Figure 17: Stack program - Operation sequence 1:1:1:1
Figure 18: Normal program - Operation sequence 1:2:4:4
Step Step number demand 1 2 3 4 5 6
+ X + X X + X X X + X X X X
+ X X X X X + X X X X X X
- X X X X X
- X X X X
- X X X
- X X + X X X + X X X X + X X X X X
- X X X X
- X X X
- X X
- X
Step Step number demand 1 2 3 4 5 6
+ X + X X + X X X + X X X X
- X X X
- X X + X X X
+ X X X X
+ X X X X X
- X X X X
- X X X
- X X
- X
Page 24
24
USER´S MANUAL
e) Optimal Program :
The optimal program operates with many step configurations:
1.1.1.1.1 1.2.2.2.2 1.2.4.4.4 1.2.4.8.8 1.1.2.2.2
1.1.2.3.3 1.1.2.4.4 1.2.3.3.3 1.2.3.4.4 1.2.3.6.6
The target cos
power is reached using the fewest number of steps in minimal time. Like the
circular program, this algorithm equalises the usage of steps.
This program uses optimally selected steps sizes when approaching the target power and at the same time the response delays are shortened, particularly if there is a large requirement for kvar or if the network suddenly becomes capacitive.
Comparison between normal and optimal program:
Normal program will reach the cos
target value by successive connection/disconnection of
kvar corresponding to the smallest step value.
Optimal program will reach the target cos
value by successive connection/disconnection of
kvar corresponding to the highest relevant and available step value
Figure 20: Circular B program ­Operation sequence 1:2:2
Figure 19: Circular A program - Operation sequence 1:1:1
Step Step number demand 1 2 3 4 5 6
+ X + X X + X X X + X X X X
- X X X
- X X + X X X + X X X X
- X X X
- X X + X X X + X X X X
- X X X
Step Step number demand 1 2 3 4 5 6
+ X + X X + X X X
- X X
+ X X X + X X X X
- X X X
- X X
- X + X X + X X X + X X X X + X X X X X
- X X X X
- X X X
- X X
Page 25
25
USER´S MANUAL
Figure 21: Regulation example - Optimal vs. Normal
Ind
Cap
+4
-4
-4
Steps on : 4
Steps on : 4+4+4+1
Steps on : 4+1
Compensated reactive power
Connection of steps
Disconnection of steps
+4
+1
t
Q
Uncompensated reactive power
Optimal Stepping Program
Step sizes : 1:2:4:4
+4
-4
Normal Stepping Program
Q
Ind
Cap
Step sizes : 1:2:4:4
+4
-4
Steps on : 4
Steps on : 4+4+4+4
Steps on : 4
-4
-1
+4
+1
+2
t
-4
+4
-2
Page 26
26
USER´S MANUAL
6.2 Manual calculation of response value
Normally the response value, more generally known as the C/K value, is set automatically as a part of the Auto Setup sequence, but there are cases when these values must be entered manually. The correct value can be calculated using an equation requiring the 1st step size (in vars), line-to-line voltage of the network used (in volts) and the CT ratio as follows
where Q
1st
= size of 1
st
step in vars
U
LL
= line-to-line voltage in volts
I1/5A = CT ratio
Alternatively, the C/K value can be taken from the table below (valid for 400 V networks)
Table 1: C/K-values for 400 V network
By successive connections (or disconnections) of steps we adjust the reactive power between two symmetrical limits corresponding to response value
n1/n
2
Smallest step (kvar)
12,5 20 25 30 40 50 60 100 100/5 0,91 1,44 150/5 0,60 0,96 1,20 1,44
200/5 0,45 0,72 0,90 1,08 1,44 250/5 0,36 0,58 0,72 0,87 1,16 1,44
300/5 0,30 0,48 0,60 0,72 0,96 1,20 1,44
400/5 0,36 0,45 0,54 0,72 0,90 1,08
500/5 0,29 0,36 0,43 0,58 0,72 0,87 1,44
600/5 0,30 0,36 0,4 0,60 0,72 1,20
800/5 0,27 0,36 0,45 0,54 0,90
1000/5 0,29 0,36 0,43 0,72
1500/5 0,24 0,29 0,48 2000/5 0,22 0,36
2500/5 0,29
3000/5 0,24
35
/
1
1
××
=
LL
st
UAI
Q
KC
Page 27
27
USER´S MANUAL
Figure 22: Compensation example and consequences
6.3 High Voltage use of NR6/NR12
This controller is primarily intended for LV network, but may be used in HV networks under the commissioner’s full responsibility, if the following points are taken into account. Connections must employ VT and CT with respect to the following figure.
In HV applications the power values displayed in Measurement Menu represent only the secondary side values of the VT. To avoid potential misunderstandings, set the CT ratio to percentage scale.
Safety (or reconnection) delay must be adapted to the value of the discharge resistors of the capacitors, the most usual value is 10 minutes (600 seconds). The controller’s default response delay is adapted for LV use. Using too short a response delay may damage the capacitors.
Important:
the whole commissioning process must be performed using the Manual setup menu and Parameter menu
the commissioner should not use Bank Pre-Configuration and Commissioning menus
the use of Auto Setup menu is strictly forbidden to prevent capacitor destruction
Page 28
28
USER´S MANUAL
Figure 23: HV use of the controller
Page 29
29
USER´S MANUAL
ALARMS Alarms Menu ALRM.SET Alarm Setup (Enable/Disable) AUTO Automatic search of C/K response value AUTO.SET Automatic Setup Sequence BANK.PRE Bank Pre-configuration Sequence Menu
BANK.TST Bank Test: each step is automatically connected
and disconnected in turn. This facilitates testing of the operation of each capacitor step contactor. See also Step Test.
CIRC.A Circular A stepping program CIRC.B Circular B stepping program
C/K Response value, normally set up automatically by
the controller
CLR.STAT Clear Statistics COMMISS Commissioning Sequence Menu COS PHI Target cos  value 0,8ind 1.00 0,9cap CT Current Transformer primary setting, xxx/5 A 25/5 % 6000/5
DELAY Safety Delay or reconnection delay. Response 10s 50s 600s
delay is fixed 20% of reconnection delay. The default value corresponds to capacitors with
internal discharge resistors 50V 1 min ENGLISH Language names: English, for instance ERR NN Error in parameter search or verify. NN= error number FACTOR.S Restore Factory Settings
IGNORED The controller does not require the information
about step sequence for any program outside
Optimal. The controller defines it automatically. I HIGH Current too high >115%
I
N
I LOW Current too low <2,5%
I
N
LANGUAG Language Selection for menus LL Line to Line connection LN Line to Neutral connection LV Low Voltage MAINTEN Maintenance Menu MAN.SET Manual Setup Sequence Menu MANUAL Manual setting of C/K response value. See further 0,01 0,50 1,99 MEASURE Measurements Menu
7. Glossary
Display information
Long form text Min
value
Default value
Max value
Page 30
30
USER´S MANUAL
N.CONNEC Number of Connections N.STEPS Number of used steps 1 6/12 12 NORMAL Normal, Standard stepping program OPTIM Optimal program PARAMET Parameters Menu PROGRAM Selection of suitable stepping program between
(see 6.1 Stepping programs) The controler’s algorithm will try to reach the target cos
inside a tolerance area dependant upon the C/K value. It reaches the value by switching on or off available relevant steps.
Stack Normal Circular A Circular B Optimal
SEARCH Search (response value, step sizes, wiring...) SERIAL.N Serial Number of the product (for internal
manufacturer use)
STACK Linear stepping program STEP.SEQ Setting of Step Size Sequence
1.1.1.1.1 - 1.1.2.2.2 - 1.1.2.3.3 - 1.1.2.4.4 - 1.2.2.2.2 -
1.2.4.4.4 - 1.2.4.8.8 -1.2.3.3.3 - 1.2.3.4.4 - 1.2.3.6.6 This concerns the Optimal program. Step sequence are predefined with other programs and modification request are not then taken into account
STEP.TST Step Test: each step can be manually connected and
disconnected. This facilitates testing of the operation of each capacitor step contactor. See also Bank Test.
TEMP.LIM Temperature Limit (adjustable) 20
°
C50°C60
°
C
Fan switch-on limit is 15°C lower than temperature limit.
THD.U Total Harmonic Distortion of Voltage THD.U.LIM Maximum Harmonic Distortion of Voltage (adjustable) 5% 7% 20% U LOW Voltage too low
<85%U
N
UPTIME Uptime (Power On Hours) VERIFY Automatic verification of parameters VERSION Software version number (for internal manufacturer use) VOLTAGE Input Voltage reference value for voltage alarms 80V 400V 460V WIRING Connections of voltage and current inputs.
Example: U.L2-L3 (Voltage connected between phase 2 and 3) Example: I.1.AUTO (Current connected to phase 1 with automatic polarity selection) Current polarity selections: DIR = direct connection INV = inverted connection AUTO = automatic polarity (defined by controller)
Display information
Long form text Min
value
Default value
Max value
Page 31
31
USER´S MANUAL
8. Technical specifications
Number of steps 6 or 12 Dimensions 155 x 155 x 70 mm Frequency 48...52 Hz, 58...62 Hz Measuring current 0...5 A Measuring and supply voltages 88...130 V
185...265 V
320...460 V
Relay outputs 120 Vac/5A, 250 Vac/2A, 400 Vac/1A
110 Vdc/0,3A, 60 Vdc/0,6A, 24 Vdc/2A
Display LCD glass with 160 symbols, backlighted
Protection class IP41 front panel, IP20 rear part Target cos
-range 0,85 ind...1,00...0,90 cap
Response limits, C/K 0,01...1,99 symmetrical Reconnection delay 10...600 s Response delay 20 % of reconnection delay, min. 10 s Displayed measurements cos
, P, Q, S, THD(U), temperature
Installation method Panel installation, DIN-rail installation Casing Impact resistant PC/ABS, UL94V-0 Operating temperature range 0...60°C Alarm log List of 5 last alarms Step counters Yes Fan control with dedicated relay Yes Accuracy (of FS) Is: 5%
Iq: 5% U/I-samples: 5% Phase: 5° Distortion: ±3 dB (up to 11
th
)
Temperature: ±3°C
CT setting range 25/5...6000/5 Power outage detection Reaction time > 15 ms Approvals IEC 61010-1
IEC 61000-6-2 IEC 61000-6-4 IEC 61326
Page 32
Schneider Electric Industries SAS
As characteristics and dimensions of our products are constantly changing, please contact our offices for confirmation.
10/2003Rec NM39EN
Loading...