AAF-HermanNelson Classroom Unit Ventilators 3
The Model AV Floor Unit 4
Features & Benefits 5
Quiet Operation With Our GentleFlo Delivery 5
The Right Amount of Fresh Air and Cooling 6
Precise Temperature and Dehumidification Control 7
Low Installation Costs 9
Low Operating Costs 10
Easy To Maintain 11
Built To Last 13
MicroTech II Controls 15
MicroTech II Controls For Superior Performance, Easy Integration 15
Control Modes and Functions 17
Advanced Control Options 19
System Components 21
Why Classrooms Overheat 29
Meeting IAQ Requirements 31
Following ASHRAE Control Cycle II 31
Meeting ARI 840 Requirements 32
Meeting IBC Seismic Requirements 33
Face & Bypass Temperature Control 34
Modulating Valve Temperature Control 36
Coil Selection 37
DX Split Systems 38
Window Downdraft Protection 40
Digital Ready Systems 43
Field-Installed Controls By
Others & Digital Ready Controls 43
Unit Installation 48
Unit Arrangements: 16-5/8" Deep 51
Unit Arrangements: 21-7/8" Deep 52
Coil Selection 55
Quick Selection Procedure 55
Coil Selection Procedure 56
Chilled Water Selection Example 58
Hot Water Heating Selection 60
Steam Heating Selection 63
Electric Heating Selection 64
Direct Expansion Cooling Coil Selection 65
New construction installations are easily accomplished
with AAF-HermanNelson unit ventilators because they
avoid the added cost and space required for expensive
ductwork. Retrofit installations are also economical
because new units fit the same space occupied by
existing ones. Multiple control options—including
MicroTech II controls with Protocol Selectability™, or
For more than 85 years, schools have relied on
AAF-HermanNelson unit ventilators to keep classrooms
comfortable. Students learn more readily in a quiet, wellventilated environment. That’s why Herman Nelson
invented the unit ventilator and why we remain
committed to meeting the changing requirements of
schools with the highest quality products available.
We realize that keeping expenditures down is a high
priority for school administrators and school boards.
AAF-HermanNelson unit ventilators are inexpensive to
install and operate, and they are designed and built to
provide decades of trouble-free service.
Quiet Operation
AAF-HermanNelson unit ventilators are engineered and
manufactured to deliver quiet, continuous comfort. We
developed our GentleFlo™ air moving system to minimize
operating sound levels—even as demands for more fresh
air require units to operate longer and work harder.
The Right Amount of Fresh Air and Cooling
AAF-HermanNelson unit ventilators deliver required
amounts of fresh air to meet ventilation requirements,
and added cooling capacity to maintain consistent
comfort for students and teachers. Our Economizer
Operation, Demand Control Ventilation (DCV) and Part
Load, Variable Air options allow you to closely match
comfort requirements and reduce operating costs.
Precise Temperature and Dehumidification
Control
AAF-HermanNelson unit ventilators feature precise
temperature and dehumidification control to keep
students and teachers comfortable while making
maximum use of “free” outdoor-air cooling to reduce
operating costs. They utilize a draw-thru air design that
contributes to even heat transfer and uniform discharge
air temperatures into the classroom. Coupled with face
and bypass air control and our MicroTech
passive dehumidification control strategies, they provide
precise control of temperature and humidity levels.
II™ active and
Digital Ready™ features—provide easy, low cost
integration into the building automation system of your
choice.
Low Operating Costs
When running, AAF-HermanNelson unit ventilators can
use as little electricity as two 100-watt light bulbs. They
take maximum advantage of “free” cooling opportunities
to reduce operating costs. During unoccupied periods
and at night, units operate sparingly to conserve energy.
Easy To Maintain, Modular Design
AAF-HermanNelson Unit Ventilators are designed to
provide easy access for maintenance and service
personnel to all serviceable components. Most tasks are
easily handled by a single person.
Built To Last
Our proven institutional design can withstand the rigors
of the classroom environment. It features an extra-sturdy
chassis and double-wall damper on the inside; scuffresistant finishes and tamper prevention features on the
outside. In fact, many units installed over 30 years ago
continue to provide quiet, reliable classroom comfort.
MicroTech II Control For Superior
Performance, Easy Integration
AAF-HermanNelson unit ventilators can be equipped
with MicroTech II™ unit controllers for superior
performance. Factory integrated and tested controller,
sensor, actuator and unit options promote quick, reliable
start-up and minimize costly field commissioning. Our
Protocol Selectability feature provides easy, low-cost
integration into most building automation systems. Select
BACnet
communications to communicate control and monitoring
information to your BAS, without the need for costly
gateways. Unit controllers are L
the optional L
®
, LonTalk® or Metasys® N2 Open
ONWORKS
®
communication module.
ONMARK
®
certified with
AAF-HermanNelson Model AV Unit Ventilators3
Introduction
The Model AV Floor Unit
Our Model AV is a vertical, floor-standing unit that utilizes
remotely-supplied chilled water or refrigerant for cooling,
and hot water, steam or electric heat for heating. The
Model AV also can be supplied as a heating/ventilating
unit only or as a cooling/ventilating unit only.
The Model AV is just right for new construction and for
retrofit applications. Older buildings with baseboard
Hinged Top Access Doors
Welded OnePiece Chassis
Sampling
Chamber
Draw-Thru
Air Flow
Quiet, Aerodynamic Fans
radiant heat or other hydronic heating systems can be
easily adapted to work efficiently with Model AV units.
Chilled-water or refrigerant cooling can be added to
provide year-round comfort. The major features of this
model are shown below and described in more detail on
the following pages.
Fan Motor Out
Of Airstream
MicroTech II Controls
Composite
Drain Pan
Sectionalized
Access Panels
Face And Bypass
Damper Design
• Welded One-Piece Chassis offers
superior strength, durability, and vibration reduction.
• Unique Draw-Thru Design provides
uniform air distribution across the coil
for even discharge air temperatures.
• Quiet, Aerodynamic Fans utilize
GentleFlo technology for exceptionally
quiet unit operation.
• Modular Fan Section improves
balance, alignment and simplifies
maintenance.
• Fan Motor Located Out Of Air
Stream and away from heating coil
reduces heat exposure to prolong life.
• Face And Bypass DamperDesign
provides superior dehumidification
and reduces chance of coil freeze-up
Advanced Heat
Transfer Coil
• Certified Ventilation Performance
per ARI-840.
• MicroTech II Controls provide supe-
rior comfort control and easy
integration into the building automation system of your choice.
• Advanced Heat Transfer Coil design
provides extra capacity.
• Sturdy Cabinet Construction
includes hidden reinforcement, a nonglare textured surface, and a tough,
scuff- and mar-resistant finish to make
the top sturdy enough to support
maintenance personnel.
• Sectionalized Front Access Panels
provide easy access to unit interior.
Panels are easily removed by a single
person. Front side panels can be
removed while unit is running.
Single Full-Length
Air Filter
Sturdy Cabinet
• Two Hinged Top Access Doors pro-
vide easy access to motor and end
bearing. Special tamper-resistant fasteners deter unauthorized access.
• Sampling Chamber for unit-mounted
sensor provides accurate sensing of
room temperature.
• Indoor Room Air Damper blocks
unwanted gusts of outdoor air on
windy days. Its nylon bearings are
quiet and maintenance free.
• Insulated Double-Wall Outdoor Air
Damper seals tightly without twisting.
• Single Full-length Air Filter is effi-
cient and easy to replace. All air
delivered to classroom is filtered.
• UL/cUL Listed
4McQuay Catalog 1600
Features & Benefits
Features & Benefits
Quiet Operation With Our GentleFlo Delivery
AAF-HermanNelson unit ventilators are engineered and
manufactured to deliver quiet, continuous comfort. We
developed our GentleFlo™ air moving system to
minimize operating sound levels—even as demands for
more fresh air require units to operate longer and work
harder. GentleFlo features include:
• Fan wheels are large, wide and rotate at a low speed
to reduce fan sound levels. They are impact-resistant
and carefully balanced to provide consistent
performance.
• Offset, aerodynamic fan wheel blades move air
efficiently (
• Precision tolerances help reduce flow and pressure
turbulence, resulting in lower sound levels.
• Fan housings incorporate the latest logarithmicexpansion technology for smoother, quieter air flow
(
Figure 2).
Figure 1. GentleFlo Fan Technology
Figure 1).
Expanded discharge air
opening
• A large, expanded discharge opening minimizes air
resistance, further lowering sound levels.
• Modular fan construction contributes to equal outlet
velocities and promotes quiet operation.
• Fan shafts are of ground and polished steel to
minimize deflections and provide consistent, long-term
operation.
• Fan assemblies are balanced before unit assembly,
then tested after assembly (and rebalanced if
necessary) to provide stable, quiet operation.
Figure 2. GentleFlo Reduces Turbulence
Minimal
Offset aerodynamic blades
Logarithmic expansion
housing
Precision Tolerances
AAF-HermanNelson Model AV Unit Ventilators5
GentleFlo fan blade design
turbulence
Typical fan blade design
High turbulence
Features & Benefits
The Right Amount of Fresh Air and Cooling
AAF-HermanNelson unit ventilators deliver required
amounts of fresh air to meet ventilation requirements and
added cooling capacity to maintain consistent comfort for
students and teachers. Our Economizer Operation,
Demand Control Ventilation (DCV) and Part Load,
Variable Air options allow you to match classroom
comfort requirements even more closely, and reduce
operating costs.
This means that you can be confident that your school is
meeting ventilation standards for Indoor Air Quality and
that your students are receiving adequate air to be
attentive to instruction. At the same time, you are saving
money in early morning hours, between classes or after
hours when classrooms are heated and cooled but not
always fully occupied.
Economizer Operation
It is well recognized that cooling, not heating, is the main
thermal challenge in school classrooms. The typical
classroom is cooled by outdoor air over half the time,
even in cold climates. It is therefore essential that unit
ventilators efficiently deliver outdoor air when classroom
conditions call for “free” or economizer cooling.
With AAF-HermanNelson unit ventilators, you can have
outdoor air whenever it is needed. Economizer operation
is facilitated by the outdoor air damper, which
automatically adjusts the above-minimum outside air
position to provide free cooling when the outdoor air
temperature is appropriate (
with MicroTech II controls, three levels of economizer
control are available (see
Figure 3. Full Economizer Mode
100% Outdoor Air Into Classroom
Figure 3). On units equipped
page 17).
Part-Load Variable Air Control
Part Load Variable Air control can be used in conjunction
with face and bypass damper temperature control to
automatically adjust the unit ventilator fan speed based
upon the room load and the room temperature. This
MicroTech II control option provides higher latent cooling
capabilities and quieter operation during non-peak load
periods by basing indoor fan speed upon room load.
Lower fan speeds in conjunction with our GentleFlo fan
technology (see page
page 5) contributes to a very quiet
classroom environment.
Room-temperature PI control loops determine the speed
of the fan, which varies according to the room load. It
also provides a built-in delay to prevent overshooting for
better comfort control. The outdoor air damper’s
minimum-air position is adjusted with the fan speed to
bring in a constant amount of fresh air.
Demand Control Ventilation
AAF-HermanNelson unit ventilators can be equipped to
use input from a CO
based on actual occupancy instead of a fixed design
occupancy. This Demand Controlled Ventilation (DCV)
system monitors the amount of CO
outdoor air is introduced to maintain good air quality. The
system is designed to achieve a target ventilation rate
(e.g., 15 cfm/person) based on actual occupancy.
By using DCV to monitor the actual occupancy pattern in
a room, the system can allow code-specific levels of
outdoor air to be delivered when needed. Unnecessary
over-ventilation is avoided during periods of low or
intermittent occupancy, leading to improved energy
efficiencies and cost savings.
controller to ventilate the space
2
so enough fresh
2
Face &
Bypass
Damper
Room Air
Damper
6McQuay Catalog 1600
Filter
Outdoor Air
Damper
Outdoor Air
Features & Benefits
Precise Temperature and Dehumidification Control
AAF-HermanNelson unit ventilators provide precise
temperature and dehumidification control to keep
students and teachers comfortable while making
maximum use of “free” outdoor-air cooling to reduce
operating costs. They utilize a draw-thru fan design that
contributes to even heat transfer and provides uniform
discharge air temperatures into the classroom. Coupled
with face and bypass damper air control and/or our
MicroTech
II active and passive dehumidification control
strategies, they provide precise control of temperature
and humidity levels under both part-load and full-load
conditions.
Draw-Thru Design For Even Discharge
Temperatures
The AAF-HermanNelson Draw-Thru design sets our unit
ventilators apart from most competitive models. With this
system, fans draw air through the entire heat transfer
element (
concentrated areas of the coil element. The result is
more uniform discharge air temperatures into the
classroom and more efficient unit ventilator operation.
Figure 4. Draw-Thru Design Provides Even Discharge Air
Figure 4) rather than blowing it through highly
Uniform Discharge Air (Shaded)
Motor
Fans
Condenser
Ta bl e s 1 and 2 below compare the composition of the air
streams through the coil and air streams bypassing the
coil at various bypass air percentages for draw-thru and
blow-thru unit ventilators using 450 cfm of outdoor air. At
both 0% bypass air and 100% bypass air, no difference
exists in the composition of the air streams. However, at
all other bypass air percentages (part load), significant
differences are evident.
For instance, compare the 1500 cfm draw-thru (Ta bl e 1)
and blow-thru (Tab le 2) units at 70% bypass air. At this
point, the draw-thru unit still has all of the outdoor air
going through the coil. Meanwhile, the blow-thru unit is
bypassing 70% (315 cfm) of the humid outdoor air
directly into the classroom.
Table 1: AAF-Herman Nelson 1500 CFM Draw-Thru Unit
Bypass Air Stream CFMCold Air Stream CFM
Tot al
% Bypass Air
0150000015001050450
10150015015001350900450
20150030030001200750450
30150045045001050600450
4015006006000900450450
5015007507500750300450
6015009009000600150450
7015001050105004500450
801500120010501503000300
901500135010503001500150
100150015001050450000
Bypass
Total Unit CFM
From
Room
From
Outdoors
Tot al
Coil
From
Room
From
Outdoors
Table 2: 1500 CFM Blow-Thru Unit
Face & Bypass Design For Better
Temperature and Humidity Control
When coupled with our draw-thru design, face and
bypass damper air control offers maximum
dehumidification and optimal temperature control. That’s
because indoor and outdoor air streams can be
separated until it is optimal to mix them.
During most part-load conditions, humid outdoor air is
directed through the cold coil (coil surface below the dew
point) where moisture is removed. Room air is bypassed
around the coil, since it has already been dehumidified.
This arrangement allows for maximum condensate
removal. Humid outdoor air is not bypassed around the
coil until the total amount of cooling air required is less
than the total amount of fresh outdoor air required in the
% Bypass Air
0150000015001050450
101500150105451350945405
201500300210901200840360
3015004503151351050735315
4015006006000900450450
501500750525225750525
601500900630270600420180
7015001050735315450315135
801500120084036030021090
901500135094540515010545
100150015001050450000
Bypass Air Stream CFMCold Air Stream CFM
Tot al
Bypass
Total Unit CFM
From
Room
From
Outdoors
Tot al
Coil
From
Room
From
Outdoors
225
room.
AAF-HermanNelson Model AV Unit Ventilators7
Features & Benefits
This illustrates that the most effective way to maintain an
acceptable humidity level with a chilled-water unit
ventilator system is to use a face and bypass damper,
draw-thru unit.
Why Blow-Thru Designs Don’t Measure Up
Blow-thru designs cannot provide comfort like this. With
blow-thru designs, the humid outside air is pre-mixed
with the room air before it can go through the coil
(
Figure 5). Dehumidification occurs only to the portion of
the air that is directed unevenly through the cooling coil.
The air that bypasses the coil is largely humid outdoor
air, resulting in unconditioned air being bypassed and
creating poor comfort conditions.
Figure 5. Draw-Thru Vs. Blow-Thru Design
Coil
Face &
Bypass
Damper
Room Air
Damper
Room Air
AAF-HermanNelson
Draw-Thru Design
Outdoor
Air Damper
Outdoor Air
With a blow-thru design the positive pressure of the fan
discharge can create areas across the coil of varying
temperatures and airflow. In addition, blow-thru face and
bypass damper construction picks up heat by wiping the
coil, creating overheating conditions. The sound level in
a blow-thru design also varies based upon the position of
the face and bypass damper.
Coil
Filter
RA/OA
Divider
Room Air
Outdoor Air
Blow-Thru Design
See “Active Dehumidification Control (Reheat)” on page
20 for more information.
Passive Dehumidification (Optional)
On units with face and bypass damper air control and
MicroTech II part-load variable air control, passive
dehumidification can be used under high humidity
conditions to keep classrooms comfortable. A unitmounted humidity sensor and fan speed changes are
utilized to improve latent cooling by keeping the air in
closer contact with the cold coil for passive
dehumidification.
This occurs in the unoccupied mode as the unit operates
to satisfy the unoccupied temperature and humidity set
points with the outside damper closed. The face and
bypass damper is placed in a minimum face position to
promote high latent cooling. The unit fan continues to
operate on low speed until the load is satisfied. This is
very helpful in high humidity areas where high night time
humidity can be absorbed in the building during off
hours.
Increased Coil Freeze Protection
AAF-HermanNelson units equipped with face and
bypass damper control provide extra protection from coil
freeze-up. That’s because there is a constant flow of hot
water through the coil, and water that is flowing typically
does not freeze. Additionally, all AAF-HermanNelson
units feature a double-walled, insulated outdoor air
damper with airtight mohair seals to prevent unwanted
coil air from entering the unit.
Furthermore, a low-temperature freezestat is factory
installed on all units with hydronic coils. Its serpentine
capillary tube senses temperatures across the leaving air
side of the coil, allowing the unit controller to react
quickly to low-temperature conditions.
Active Dehumidification (Reheat)
In high-humidity applications where valve-controlled,
Figure 6. Freezestat
Freezestat
reheat units are used, the Active Dehumidification
Control (ADC) sequence should be considered. During
excessive humidity conditions, a humidity sensor directs
the unit to continue cooling past the room setpoint to
remove excess moisture. Hydronic heat or electric heat
is then used to reheat the discharge air to maintain
acceptable room temperatures.
MicroTech II controls minimize the amount of reheat
needed to maintain relative humidity below a preset limit.
Capillary Tube
Reheat is used only when required and in the most
energy-efficient manner possible.
8McQuay Catalog 1600
Features & Benefits
Low Installation Costs
AAF-HermanNelson unit ventilators have many features
that make them economical to purchase and to install in
both new construction and retrofit applications. It is this
attention to detail and understanding of school
applications that make them the system of choice.
Perfect For Both New & Retrofit
Applications
New construction installations are easily accomplished
with AAF-HermanNelson unit ventilators because they
avoid the added cost and space required for expensive
ductwork. Further savings can be realized because
piping installations use less space than duct systems.
This is important in existing buildings and also in new
construction where floor-to-floor heights can be reduced,
saving on overall building costs.
Retrofit installations are also economical because new
units fit the same space occupied by existing ones. Using
AAF-HermanNelson unit ventilators, central equipment,
such as chillers, can be sized smaller using building
diversity. This results in a low capital-cost system.
Built In Flexibility
AAF-HermanNelson unit ventilators include features that
make them easy to set up and reconfigure as needed to
meet special requirements. These features include:
• Reversible Drain Connections All units come with a
composite drain pan that has drain connections on
either end (
connection is also provided. The drain-side connection
can be selected in the field. The direction in which the
drain pan slants can also be field-modified.
• Add Cooling At A Later Date Because we recognize
that some schools may wish to add cooling at a later
date, even heating-only units are shipped standard
with a composite drain pan.
Figure 7). A secondary, overflow drain
Secondary Overflow
Drain Connection
Primary Drain
Connection
Connect Drains On Either
End, Slant Pan To Either
End, Can Field-Modify
• Adjustable Leg Levelers Adjustable leg levelers are
furnished on the front legs of all floor units to
compensate for floor irregularities (
Figure 8. Adjustable Leg Levelers
Leg Leveler
Figure 8).
• Built-in Pipe Tunnel A built-in pipe tunnel allows field
crossover of hot-water or chilled-water piping,
electrical conduit or refrigeration tubing (see Unit
Arrangements beginning on page
51).
• Built-In Wire Race A built-in metal wire race runs from
one end of the unit to the other to provide extra
protection for wires and protect them from unit air.
Controls Flexibility
Multiple control options—including MicroTech II controls
with our Protocol Selectability feature—provide easy, low
cost integration of AAF-HermanNelson unit ventilators
into the building automation system of your choice (see
page 15). You can also operate these units individually or
in a master-slave control configuration.
With MicroTech II controls, you select BACnet, LonTalk
or Metasys
and monitoring information to your BAS, without the
need for costly gateways. Unit controllers are L
certified with the optional L
module.
Controls and communication modules can be factory
provided or field-installed by others. Factory integrated
and tested controller, sensor, actuator and unit options
promote quick, reliable start-up and minimize costly field
commissioning.
You can also use our Digital Ready option, where we
factory-install and pre-wire control sensors and actuators
and the controller is field-installed by others. See
Ready Systems” on page 43.
N2 communications to communicate control
ONMARK
ONWORKS communication
“Digital
AAF-HermanNelson Model AV Unit Ventilators9
Features & Benefits
Low Operating Costs
Schools consume more than 10% of the total energy
expended in the United States for comfort heating and
cooling of buildings. As energy costs increase, educators
are placed in a difficult position: caught between rising
costs, lower budgets and the requirements to raise
educational standards.
Fortunately, the technology and the system exists for
schools to take control of their energy expenditures while
providing a comfortable environment for learning. And
that system is the AAF-HermanNelson unit ventilator.
Consider these realities of school environments:
• Most heating energy in schools is expended to heat
unoccupied spaces. Because lights, computers and
students give off considerable heat, occupied spaces
require little supplemental heat.
• The removal of heat is usually required in occupied
classrooms, even when outside temperatures are
moderately cold (i.e., 35-40°F).
Then consider how AAF-HermanNelson unit ventilators,
located in each classroom, take advantage of these
realities to lower operating costs:
• They provide individual classroom control and comfort.
• They can be cycled on when the room is occupied and
cycled off when it is not.
• They bring in fresh air from directly outside the
classroom for high indoor air quality.
• During most of the school year, they use outdoor air to
keep classrooms comfortable without the expense of
mechanical cooling.
• They have their own air-moving device—a fan and 1/4
hp motor—which uses about as much energy as two
100-watt light bulbs. Compare this to the energy
consumed by the 20-plus-hp motors used in
centralized systems to cool both occupied and
unoccupied spaces (at about 1 hp of energy consumed
per room).
MicroTech II Control Options Further
Reduce Operating Costs
Many of the MicroTech II control options available with
AAF-HermanNelson unit ventilators can further reduce
operating costs. For example:
• Economizer Operation Economizer operation
automatically adjusts the above-minimum outside air
position to provide free cooling when the outdoor air
temperature is appropriate.
• Demand Control Ventilation By using CO2 levels to
monitor the actual occupancy pattern in a room, the
system can allow code-specific levels of outdoor air to
be delivered when needed without costly overventilation during periods of low or intermittent
occupancy (
Figure 9. Energy Savings with Demand Control Ventilation
100%
20%
• Occupancy Mode Operation Units can be
programmed to operate only sparingly during
unoccupied periods and at night to conserve energy.
Figure 9).
Energy Savings
with DCV
Unoccupied
After Hours
DCV's fresh air for indoor air quality
6:008:00 10:00 12:00 2:004:006:008:0010:00
School Hours
Cleaning
Unoccupied
10McQuay Catalog 1600
Features & Benefits
Easy To Maintain
AAF-HermanNelson Unit Ventilators are designed to
provide easy access for maintenance and service
personnel to all serviceable components. Most
maintenance tasks are easily handled by a single
person.
Modular Fan Deck
The entire fan deck is easily removed as a single unit.
This provides ready access to fan wheels, motors,
bearings and other components for service, cleaning or
repair.
The fan deck’s rotating element has one large, selfaligning, oilable end bearing and two oilable motor
bearings for smoother operation. The location of these
bearings at the ends of the shaft (out of the airstream)
enables easy access and long life.
Figure 10. Long-life bearings
Even “permanently” lubricated motors are supplied with
recommended lubrication charts calling for lubrication
every seven years. Maintenance instructions of the
motor manufacturer should be followed closely.
Heavy-Duty Discharge Grille
The discharge grille on the top of the unit is made from
extra-strength steel bar stock, promoting long life
(
Figure 11). It can be removed to facilitate cleaning of
fans and fan housings. A built-in 10-degree angle
provides proper air throw to blanket the room for proper
air circulation and comfort.
Figure 11. Heavy-Duty Steel Discharge Grille
Easy Motor Removal
Unlike with many competitive models, the motor in
AAF-HermanNelson unit ventilators is separate from the
fan assembly and is located out of the airstream at the
end of the fan shaft—away from the hot coil—for easier
maintenance and removal. Locating the motor away from
the coil (
motor life. Our direct-coupled motor and self-aligning
motor mount facilitate motor change-out. The motor
comes with a molex plug that fits all sizes and further
simplifies removal.
Figure 12) has the added benefit of extending
Figure 12. Modular Fan Deck
Heavy-Duty Discharge Grille
Modular Fan Deck
AAF-HermanNelson Model AV Unit Ventilators11
Motor & Bearings Located
Out Of Airstream
Features & Benefits
Tamper-Resistant Fasteners
Front panels and top access doors are held in place by
tamper-resistant, positive-positioning fasteners. They are
quickly removed or opened with the proper tool, but deter
unauthorized access to the unit’s interior (
Figure 13).
Sectionalized Access Panels And Doors
All floor units have three separate front panels and
hinged top access doors, sized for convenient handling
by a single person (
Figure 13). The result is easy,
targeted access to the component that needs servicing:
• Two 12 inch-wide end panels provide easy access to
piping, temperature control components and the fan
switch. Unlike units with full-length front panels, these
can be removed without disturbing the normal
operation of the unit.
• Hinged top access doors provide easy access into the
end compartments to facilitate convenient servicing of
the motor and shaft bearing.
• A short, center front panel provides easy access to the
filter and discharge grille.
Single-Filter Design
With AAF-HermanNelson’s single-filter design, filter
change-out takes only seconds. Uneven dust loading is
eliminated, which is common to units with separate filters
for room and outdoor air, or that use a metal partition to
separate filtering of indoor and outdoor air. The result
can be longer filter life, which means less maintenance
and fewer filters consumed.
Three filter types are offered:
• Single-use filters which feature Amerglas media and
are designed to be used once and discarded. These
are standard on all but electric heat units.
• Permanent metal filters which may be removed for
cleaning and reused numerous times. These are
standard on electric heat units.
• Renewable media filters, which consist of a heavyduty, painted-metal structural frame and renewable
Amerglas media.
Figure 13. Easy Access With Tamper-Resistant Fasteners
Discharge Grille
Doors
Right Front
Access Panel
Discharge Screen
Tamper-Resistant
Fasteners
Fan
Motor
Ta m pe r -
Resistant
Fasteners
Center Front Access
Panel
Tamper-Resistant
Fasteners
Top Access
Left Front
Access Panel
Renewable
Media Filter
12McQuay Catalog 1600
Features & Benefits
Built To Last
Our industrial-strength design provides the durability to
withstand the rigors of the classroom environment. Its
solid construction and rugged finish promotes continued
alignment, structural strength and long-lasting beauty
decades after the unit is installed. In fact, many units
installed over 30 years ago continue to provide quiet,
reliable classroom comfort.
Heavy Duty Frame Construction
AAF-HermanNelson’s exclusive, unitized frame
(
Figure 14) is far superior to the fastener-type
construction used by other manufacturers. Loosened
fasteners can cause vibration, rattles and sagging
panels. With unitized construction, there are no fasteners
(screws or bolts) to come loose.
Other design features that promote trouble-free
operation and long life include:
• A corrosion-resistant, galvanized-steel frame.
• Extra-strength, steel-bar discharge grille.
• Heavy-gauge-metal cabinet access panels and doors.
• An extra-strength pipe tunnel that stiffens the structure
while adding aerodynamic air flow within the unit.
• Hidden reinforcement that provides additional built-in
support for the top section as well as better support for
the fan deck assembly.
• A rigid exterior that is strong enough to support
maintenance personnel without fear of damaging the
unit.
Rugged Exterior Finish
The superior finish of the unit ventilator’s cabinets fosters
long-lasting beauty as well as resistance to abuse and
corrosion. We apply the very highest standards at every
step of the finishing process to provide lasting quality:
• High-quality furniture steel is carefully inspected before
painting. Scratches and marks that might show through
are removed.
• After fabrication, the metal undergoes a five-stage
cleaning and phosphatizing process to provide a good
bonding surface and reduce the possibility of peeling
or corrosion.
• A specially formulated, environmentally friendly,
thermosetting urethane powder is applied
electrostatically to the exterior panels. This film is
oven-cured to provide correct chemical cross-linking
and to obtain maximum scuff- and mar-resistance.
• The top of the unit is finished with a textured, non-glare
and scuff-resistant, charcoal bronze electrostatic paint.
End and front panels are available in a pleasing array
of architectural colors.
• The Oxford brown steel kickplate is coated and baked
with a thermosetting urethane powder paint to blend
with floor moldings and provide years of trouble-free
service.
• Each unit is painstakingly inspected before boxing,
then encapsulated in a clear plastic bag, surrounded
by an extra-heavy-duty cardboard box and secured to
a skid to help provide damage-free shipment.
Figure 14. Heavy-Duty, Welded Chassis
Unitized Frame
Welded
Construction
AAF-HermanNelson Model AV Unit Ventilators13
Energy-Efficient
Fan Motor
Features & Benefits
Durable, Energy Efficient Fan Motors
AAF-HermanNelson unit ventilators are equipped with
115/60/1 NEMA motors that feature low operating current
and wattage (
Figure 15. Energy-Efficient Fan Motor
Additional features of these motors include:
• Split-capacitor (PSC) design with automatic reset and
thermal-overload protection.
• No brushes, contacts or centrifugal starting switches—
the most common causes of motor failure.
• A built-in, decoupled isolation system to reduce
transmission of vibrations for quieter operation.
• A multi-tap, auto-transformer (Figure 16) provides
multiple fan motor speed control through the speed
switch. The motor is independent of supply voltage,
which allows stocking of one motor (school districtwide) for various voltage applications.
Figure 16. Multi-Tap Auto-Transformer
Figure 15).
Energy Efficient
NEMA Motor
Decoupled Isolation
System
Additional features include:
• Face and bypass dampers have a twist-free
reinforced aluminum construction for durability.
Aluminum is used because it is lightweight and
noncorrosive, resulting in low torque and easy
movement.
• Outdoor air dampers are made of galvanized steel to
inhibit corrosion, with double-wall welded construction
for rigidity and encapsulated insulation (
Figure 17).
Additional insulation is provided on the exterior of the
outdoor air damper blade and on the outdoor air entry
portion of the unit.
Figure 17. Outdoor Damper Seals Out Cold Weather
Turned Metal
Damper Blade
Turned Metal
Damper Stop
Wool Mohair
End Seal
Full-Length
Wool Mohair Damper
Additional
Insulation
Wool Mohair End
Seal
• Room air dampers are free-floating and designed to
prevent intermittent gusts of cold air from blowing
directly into the classroom on windy days (
Figure 18).
They are constructed of aluminum with built-in rigidity.
The metal forming technique that is employed resists
twisting and incorporates a full-length counter weight
for easy rotation. The simple principle of an area
exposed to a force is used to automatically close the
damper, rather than open it, when gusts of cold air
occur.
Figure 18. Room Air Damper Auto-Closed By Wind Gusts
Wind
Gust
Durable Damper Design
All dampers in AAF-HermanNelson Unit Ventilators use
the turned-metal principle on their long closing edges
(
Figure 17). Positive sealing is provided by embedding
the edge into wool mohair (no metal to metal contact).
There are no plastic gaskets to become brittle with time,
sag with heat or age, or require a difficult slot fit to seal.
Nylon damper bearings foster quiet, maintenance-free
operation.
14McQuay Catalog 1600
MicroTech II Controls
MicroTech II Controls
MicroTech II Controls For Superior Performance, Easy Integration
AAF-HermanNelson unit
ventilators equipped with
MicroTech
provide superior performance
and easy integration into your
building automation system of
choice. MicroTech II benefits
include:
• Factory integrated and tested
controller, sensor, actuator and unit options promote
quick, reliable start-up and minimize costly field
commissioning.
• High-performance features and advanced control
options can quickly pay for themselves in saved energy
costs and more comfortable classrooms.
• Select from three control levels: stand-alone, masterslave or network control.
• For network control applications, our Protocol
Selectability feature provides easy, low-cost integration
of AAF-HermanNelson unit ventilators into most
building automation systems.
• Flexible BAS network communication options guard
against controls obsolescence, keeping MicroTech II
controls viable for the life of your AAF-HermanNelson
equipment.
II unit controllers can
If a school has more than one zone, separate, remote
time clocks are used to regulate each zone. In this case,
the remote-mounted time clock energizes or deenergizes an external, 24-volt or 120-volt control circuit
which operates the unit-mounted day/night relays in that
zone.
Master-Slave Control
Designate the master and slave units and we will factory
configure and install the controllers so they are set up for
a local peer-to-peer network between units (leaving only
the network wiring between these units to be field
installed).
Slave units can be field-configured to be dependent or
independent as follows:
• Dependent slave units follow the master unit
completely. They are ideal for large spaces that have
even loads across the space (such as some libraries).
• Independent slave units (default) use master setpoints
and slave sensors. The slave follows the master unit
modes, such as heat or cool, but has the flexibility to
provide the conditioning required for its area within the
space. Independent slave units perform better in
spaces where loads vary from one area of the space to
the other (such as stairwells or cafeterias).
Three Control Levels
MicroTech II unit controllers provide the flexibility to
operate AAF-HermanNelson unit ventilators on any of
three levels:
• As stand-alone units, with control either at the unit or
from a wall sensor.
• In a master-slave relationship, where slave units follow
the master unit for some or all functions.
• Controlled as part of a network using a centralized
building automation system.
Stand-Alone Control
When operating in stand-alone mode, the MicroTech II
controller performs complete room temperature and
ventilation control. Units can be operated in occupied,
unoccupied, stand-by, or bypass (tenant override)
modes. Occupied/unoccupied changeover can be
accomplished:
• Manually by a unit-mounted day/night switch.
• Automatically by a unit-mounted day/night time clock.
• Automatically by a remote-mounted time clock that
operates unit-mounted day/night relays.
Network Control
MicroTech II unit controllers provide easy integration into
your building automation system of choice. All factoryinstalled options are handled by the unit controller. This
simplifies the transmission of monitoring and setpoint
data to the building automation system.
You select BACnet, LonTalk or Metasys N2 Open
communications to communicate control and monitoring
information to your BAS, without the need for costly
gateways (see
page 22). Unit controllers are LONMARK certified with the
optional LONWORKS communication module.
Flexible network communication options via our Protocol
Selectability feature help you avoid control obsolescence
over the life of your AAF-HermanNelson equipment.
“Optional Communication Modules” on
AAF-HermanNelson Model AV Unit Ventilators15
MicroTech II Controls
A Wide Variety of Input, Output & Alarm
Data Points Available
A wide variety of data is available from AAFHermanNelson unit ventilators when equipped with
MicroTech II unit controllers in a network situation. They
classroom and notify your building automation system of
alarm conditions regardless of the protocol you select.
See
"Table 3: Network Operation - Typical Data Points"
below for a list of inputs, outputs and alarm functions
available.
provide a clear picture of just what's happening in each
Table 3: Network Operation - Typical Data Points
Read/Write AttributesRead Only Attributes
• Application Mode
• Auxiliary Heat
Enable
• Compressor
Enable
• Emergency
Override
• Energy Hold Off
• Heat/Cool Mode
• Occupancy
Override
• Outdoor Air
Humidity
• Reset Alarm
• Reset Filter Alarm
• Setpoint Offset
• Source (Water In)
Temperature
• Space CO2
• Space Humidity
• Space
Temperature
• Binary Input 1 Status
• Binary Output 1 Status
• Binary Output 2 Status
• Compressor Run Time
• Chiller Water Valve
Position
• Discharge Air
Temperature
• Discharge Air
Temperature Setpoint
• Effective Setpoint
• Effective Space
Temperature
• Fan Speed
• F & BP Damper
Position
• Local Setpoint
• Outdoor Air Damper
Position
• Space Fan Runtime
• Unit Ventilator
Controller State
• Water-out Temperature
• WH or CW/HW Valve
Position
1.
Not all data points or alarms listed will be available in all unit ventilator configurations. Humidity and CO2 points require the use of optional sensors.
1
Read/Write
Setpoint Attributes
• Econ. IA/OA Enthalpy
Differential Setpoint
• Econ. IA/OA Temp.
Differential. Setpoint
• Econ. Outdoor Air
Enthalpy Setpoint
• OAD Min. Position
Low-Speed Setpoint
• OAD Min. Position
Med.-Speed Setpoint
• Occupied Cooling
Setpoint
• Occupied Heating
Setpoint
• Space CO2 Setpoint
• Space Humidity
Setpoint
• Standby Cooling
Setpoint
• Unoccupied Cooling
Setpoint
• Unoccupied Heating
Setpoint
• UV Software
Application Version
Typical Alarms
• Indoor Air Temperature Sensor
Failure
• DX Pressure Fault
• Compressor Envelope Fault
• Condensate Overflow Indication
• Indoor Air Coil DX Temperature
Sensor Failure
• Outdoor Air Temperature Sensor
Failure
• Discharge Air Temperature Sensor
Failure
• Outdoor Air Coil DX Temperature
Sensor Failure (or)
• Water Coil DX Temperature
Sensor Failure
• Water-out Temperature Sensor
Failure (or)
• Water-in Temperature Sensor
Failure
• Space Humidity Sensor Failure
• Outdoor Humidity Sensor Failure
• Space CO2 Sensor Failure
• Source Temperature (Water-in)
Inadequate Indication
• Change Filter Indication
16McQuay Catalog 1600
MicroTech II Controls
Control Modes and Functions
AAF-HermanNelson unit ventilators equipped with
MicroTech
operate in a variety of modes based on the current
situation in the room and the status of the unit ventilator.
Changes in mode can be triggered manually, via network
signals, by sensor readings, or by date and time.
External inputs and outputs can be used to change
modes, communicate data to network controls or change
the functional operation of the unit.
Occupancy Modes
MicroTech II unit controllers can be set up to change
modes based on room occupancy. Four different
occupancy modes are provided, as described below.
Occupied Mode
This is the normal daytime operation mode. The
controller maintains a room set point using the outside air
capability and other functions.
Note: For non-school applications, the unit can also be
Unoccupied Mode
This is the night setback operating mode, in which the
unit responds to a new room set point and cycles to
maintain the condition. The fan comes on when heating
or cooling is needed and runs until the load is satisfied.
The outdoor air damper is closed during this mode.
When a cooling load is satisfied by a refrigerant system,
the compressor is de-energized and the unit ventilator
indoor fan continues to run for a fixed period of time to
remove coldness from the evaporator coil. This reduces
the potential for low refrigerant temperatures to exist on
the evaporator coil.
II unit controllers can be programmed to
configured to cycle the fan in response to the room load.
In this case, the fan would normally be in the Off Mode
until heating or cooling is required. The outside air
damper is always closed when the fan is off. When the
fan starts, the outside air damper opens to the required
position, usually minimum position.
can be made in 1-minute increments from 1 minute to
240 minutes through ServiceTools™ (see
network.
page 24) or a
Economizer Modes
Economizer operation is facilitated by the outdoor air
damper, which automatically adjusts the above-minimum
outside air position to provide free cooling when the
outdoor air temperature is appropriate. Three levels of
economizer control are available:
Basic Economizer Operation: The MicroTech II
controller compares the inside and outside temperatures.
If the temperature comparison is satisfactory, then freeair economizer operation is used to cool the space.
Reheat units also come configured with an indoor
humidity sensor.
Expanded Economizer Operation: In addition to
comparing inside and outside temperatures, outdoor
relative humidity is measured to calculate outside air
enthalpy. If the enthalpy set point is not exceeded, and
the temperature comparison is satisfactory, then free
economizer operation is used to cool the space. This
helps to minimize the entrance of humid outside air.
Leading-Edge Economizer Operation: The MicroTech II
controller compares both indoor and outdoor
temperatures and indoor and outdoor relative humidities.
Then it calculates both inside and outside air enthalpy to
determine if free economizer operation can cool the
space with non-humid outside air. This is a true enthalpy
economizer—a first for unit ventilators.
Night Purge Mode
Under this mode, the unit is configured to purge the room
space for one hour for various reasons (odor or fume
removal, drying, etc.).During Night Purge the outside air
damper is open full and the fan is run on high speed. No
“normal” heating or cooling takes place (the emergency
heat set point is maintained) and the exhaust fan, if the
room is so equipped, is signaled to turn on.
Stand By Mode
In this mode, the unit maintains the occupied mode set
point temperature with the outdoor air damper closed.
The fan runs continuously unless it is configured to cycle
in response to the load.
Bypass Mode
This is a tenant override operating mode in which the unit
is placed back into the Occupied Mode for a
predetermined time. The default is 120 minutes. Settings
AAF-HermanNelson Model AV Unit Ventilators17
Freeze Prevention Mode
This mode helps protect the unit ventilator from freezing
air conditions. Control functions vary depending on the
type of temperature control used by the unit, as follows:
Face and bypass control units: Upon sensing a potential
freezing air temperature condition leaving the heating
coil, the unit will automatically protect itself by shutting
the outside air damper and opening the EOC valve. The
face and bypass damper is allowed to operate normally
to control the space. The fan continues to run to remove
the cold air. Once accomplished, the freezestat is reset,
MicroTech II Controls
the outside air damper opens to the minimum position
and the unit commences its normal mode of operation.
Valve control units: Upon sensing a potential freezing
air temperature condition leaving the heating coil, the
unit will automatically protect itself by shutting the outside
air damper and opening the hot water valve to a
minimum of 50% (more if required to heat the room). The
fan speed will be staged down to low speed and then
turned off. When the freezestat is reset, the outside air
damper opens to the minimum position and the fan runs
at low speed for a minimum of 10 minutes. It then will
stage up if needed to satisfy the room set point. This
reduces the potential to overheat a room recovering from
a potential freeze condition.
Note: Valve selection and coil sizing is critical for proper
operation. Face and bypass control is recommended for
proper humidity and freeze protection.
Emergency Heat Mode
If the unit is left in a mode that does not normally allow
heating (such as Off, Fan Only, Cool, or Night Purge)
and the room temperature falls below 55°F, the unit will
heat the space to above 55°F and then return to the
previously set mode of operation. This mode of operation
can be field configured and/or be disabled.
External Input Functions
The unit ventilator controller is provided with three (3)
binary inputs that allow a single set of dry contacts to be
used as a signal to it. Input signal choices are described
below. Multiple units can be connected to a single set of
dry contacts.
Note: Not all of the functions listed can be used at the same
time. The unit ventilator controller is provided with
configuration parameters that can be adjusted to select
which function will be used for these inputs where
multiple functions are indicated below. For wiring
examples see installation manual IM
Unit Ventilator Controller.
Unoccupied Input Signal
This input signals the unit ventilator controller to go into
unoccupied or occupied mode. When the contacts close,
the unit ventilator controller goes into unoccupied mode;
when the contacts open, it goes into occupied mode.
Additional variables can affect occupancy mode and
override this binary input. See
“Occupancy Modes” on
page 17.
Dewpoint/Humidity Input Signal (Optional)
This input signals the unit ventilator controller to go into
active dehumidification mode. When the contacts close
747: MicroTech II
(high humidity) the controller will go into active
dehumidification; when the contacts open (low humidity)
it will stop active dehumidification.
Remote Shutdown Input Signal
This input signals the unit ventilator controller to go into
shutdown mode. When the contacts close, the controller
goes into shutdown mode; when the contacts open, it
returns to normal operation.
Ventilation Lockout Input Signal
This input signals the unit ventilator controller to close
the outdoor air damper. When the contacts close
(ventilation lockout signal) the controller closes the
outdoor damper; when the contacts open, it returns to
normal outdoor damper operation.
Exhaust Interlock Input Signal
This input signals the unit ventilator controller that an
exhaust fan within the space has been energized. The
controller then repositions the outdoor air damper to a
user-adjustable minimum position. When the contacts
close (exhaust fan on signal) the controller uses the
value defined by the Exhaust Interlock OA Damper Min
Position Setpoint as the new minimum outdoor air
damper position regardless of the indoor air fan speed.
When the contacts open, it returns to normal outdoor
damper operation.
External Output Functions
The unit ventilator controller is provided with three (3)
binary outputs to perform the functions described below.
These are relay type outputs that are intended to be
used with signal level voltages only (24 VAC max).
Note: Not all of the functions listed can be used at the same
time. The unit ventilator controller is provided with
configuration parameters that can be adjusted to select
which function will be used for these outputs when
multiple functions are indicated below. For wiring
examples, see installation manual IM
Unit Ventilator Controller.
Lights On/Off Signal
This relay output provides one set of NO dry contacts
that can be used to signal the operation of the room
lights. When the unit ventilator controller is in occupied,
standby or bypass occupancy modes, the relay output
will signal the lights on (contacts closed); when the
controller is in unoccupied occupancy mode the relay
output will signal the lights off (contacts open).
747: MicroTech II
18McQuay Catalog 1600
MicroTech II Controls
Fault Signal
This relay output provides NO, NC, and Common
connections that can be used to signal a fault condition.
When a fault exists, the unit ventilator controller
energizes this relay output. When the fault or faults are
cleared, it de-energizes this relay output.
Exhaust Fan On/Off Signal
This relay output provides one set of NO dry contacts
that can be used to signal the operation of an exhaust
fan. When the outdoor air damper opens more than the
Energize Exhaust Fan OA Damper Setpoint, the relay
output will signal the exhaust fan on (contacts closed).
When the outdoor damper closes below this setpoint, the
relay output will signal the exhaust fan off (contacts
open).
Auxiliary Heat Signal
This relay output provides one set of NO dry contacts
that can be used to operate an auxiliary heat device. The
unit ventilator controller by default is configured to
operate a NO auxiliary heat device (de-energize when
heat is required) such as a wet heat valve actuator with a
spring setup to open upon power failure. However, the
Auxiliary Heat Configuration variable can be used to set
the controller to use an NC auxiliary heat device
(energize when heat is required) such as electric heat.
fan operation under normal operating conditions, in
conjunction with our GentleFlo fan technology (see
5page 5) contributes to a very quiet classroom
envionment.
page
Demand-Controlled Ventilation (Optional)
AAF-HermanNelson unit ventilators can be equipped to
use input from a CO
based on actual occupancy instead of a fixed design
occupancy. This Demand Controlled Ventilation (DCV)
system monitors the amount of CO
students and teachers so that enough fresh outdoor air is
introduced to maintain good air quality. The system is
designed to achieve a target ventilation rate (e.g., 15
cfm/person) based on actual occupancy.
By using DCV to monitor the actual occupancy pattern in
a room, the system can allow code-specific levels of
outdoor air to be delivered when needed. Unnecessary
over-ventilation is avoided during periods of low or
intermittent occupancy.
With DCV you can be confident that your school is
meeting ventilation standards for Indoor Air Quality and
that your students are receiving adequate air to be
attentive to instruction. At the same time, you are saving
money in early morning hours, in between classes, or
after hours when classrooms are heated and cooled but
not always fully occupied.
controller to ventilate the space
2
produced by
2
Advanced Control Options
MicroTech II controls make possible a number of
advanced control options that can quickly pay for
themselves in saved energy costs and more comfortable
classrooms, as described below.
Part Load Variable Air Control
Part Load Variable Air control can be used in conjunction
with face and bypass damper temperature control to
automatically adjust the unit ventilator fan speed based
upon the room load and the room-temperature PI control
loop. This MicroTech II control option provides higher
latent cooling capabilities and quieter operation during
non-peak load periods by basing indoor fan speed upon
room load.
During low-load or normal operation (about 60% of the
time) the fan will operate on low speed. When the load
increases to an intermediate demand, the fan will
automatically shift to the medium-speed setting. Under
near-design or design-load conditions, the fan will
operate on high speed. A built-in, 10-minute delay helps
minimize awareness of fan speed changes. Low-speed
As Simple as a Thermostat
Demand Controlled Ventilation is easy to apply. When
DCV is ordered, a CO
and configured for operation. The system does the rest.
If desired, the ventilation control setpoint can be adjusted
through the MicroTech II Controller.
sensor is mounted on the unit
2
Acceptance By Codes And Standards
ASHRAE Standard 62-2004 Ventilation for Indoor Air
Quality recognizes CO
controlling ventilation based on occupancy. The
ASHRAE standard has been referenced or adopted by
most regional and local building codes. This standard
references ventilation on a per-person basis.
Using CO2 control will sometimes lower the absolute
amount of outside air delivered into a room but will
maintain the per-person rate. For example, if a
classroom is designed for 30 students, the ventilation
rate is 450 cfm (30 students X 15 cfm/student). However,
when there are only ten students in the classroom, the
CO
control will adjust ventilation to 150 cfm (10 students
2
X 15 cfm/student). A minimum base ventilation rate
(typically 20% of design levels) is provided when in the
based DCV as a means of
2
AAF-HermanNelson Model AV Unit Ventilators19
MicroTech II Controls
occupied mode. This provides outdoor air to offset any
interior source contamination while allowing for proper
space pressurization.
Active Dehumidification Control (Reheat)
In high-humidity applications where valve-controlled,
reheat units are used, the Active Dehumidification
Control (ADC) sequence should be considered. During
excessive humidity conditions, a humidity sensor directs
the unit to continue cooling past the room setpoint to
remove excess moisture. Hydronic heat or electric heat
is then used to reheat the discharge air to maintain
acceptable room temperatures.
MicroTech II controls minimize the amount of reheat
needed to maintain relative humidity below a preset limit.
Reheat is used only when required and in the most
energy-efficient manner possible.
Active Dehumidification comes standard on units
equipped with MicroTech
configuration and valve-control temperature modulation.
The MicroTech ADC humidity sensor is unit-mounted. It
issues a signal proportional to the classroom’s humidity
level (unlike humidistats which issue an open-close
signal). This enables a control sequence that manages
both the temperature and the relative humidity.
When the relative humidity exceeds a preset value, the
modulating chilled-water valve opens fully to dehumidify
the mixture of outdoor and return air entering the cooling
coil. The reheat modulating water valve then opens, or
electric heat is engaged, to reheat the air leaving the
cooling coil, as required to maintain the classroom
setpoint.
Active dehumidification starts when the indoor relative
humidity exceeds the preset relative humidity upper
setpoint and continues until the room humidity falls 5%
below the endpoint. During active dehumidification,
economizer operation is disabled (and the outdoor air
damper is reset to its minimum position) unless the
outdoor air temperature is below 55°F. It is maintained
until dehumidification is completed. When the indoor
humidity level is satisfied, the MicroTech II controller
reverts to its normal sequences to satisfy the classroom
temperature setpoint.
II controls, a reheat
closer contact with the cold coil for passive
dehumidification.
This only occurs in the unoccupied mode as the unit
operates to satisfy the humidity set point with the outside
damper closed. The face and bypass damper is placed in
a minimum face position to promote high latent cooling.
The unit fan continues to operate on low speed until the
load is satisfied. This is very helpful in high humidity
areas where high night time humidity can be absorbed in
the building during off hours.
DX Split System Control
On unit ventilators equipped with direct-expansion (DX)
coils, the unit ventilator controller is configured to operate
the compressor as secondary (mechanical) cooling when
economizer cooling is available, and as primary cooling
when economizer cooling is not available. Addtiional DX
control features include:
Compressor Envelope: This helps protect the
compressor from adverse operating conditions that can
cause damage and or shortened compressor life. It ends
compressor operation if coil temperatures exceed the
defined operating envelope.
Compressor Cooling Lockout: The unit ventilator
controller is configured to lock out compressor cooling
when the outdoor air temperature falls below the
compressor cooling lock out setpoint. Below this
temperature setpoint only economizer cooling will be
available.
Minimum On And Off Time: The unit ventilator controller
is provided with minimum-on and minimum-off timers to
prevent adverse compressor cycling (3-minutes default).
Compressor Start Delay Variable: This variable is
intended to be adjusted as part of the start-up procedure
for each unit. It is used to prevent multiple unit
compressors from starting at the same time after a power
failure or after an unoccupied-to-occupied changeover.
Each unit should be configured at start-up with a slightly
different (random) delay, or groups of units should be
provided with different delays.
Passive Dehumidification Control
On units with face and bypass damper control, a chilledwater coil and MicroTech II part-load variable air control,
passive dehumidification can be used under high
humidity conditions to keep classrooms comfortable. A
unit-mounted humidity sensor and a low fan speed are
utilized to improve latent cooling by keeping the air in
20McQuay Catalog 1600
MicroTech II Controls
System Components
The main components of the MicroTech II system are:
• The Unit Ventilator Controller (UVC)
• The Local User Interface (LUI)
• Optional plug-in network communication modules
In addition, unit ventilators equipped with MicroTech II
controllers feature factory-mounted sensors and
actuators for system control and feedback.
Unit Ventilator Controller
The MicroTech II UVC is a DDC, microprocessor-based
controller designed to provide sophisticated comfort
control of an economizer-equipped AAF-HermanNelson
unit ventilator. In addition to normal operating control, it
provides alarm monitoring and alarm-specific component
shutdown if critical system conditions occur. Each UVC is
factory wired, factory programmed and factory run-tested
for the specific unit ventilator model and configuration
ordered by the customer.
Figure 19. MicroTech II Control Board
Terminal Connections
Plug-In Control Module
Figure 20. User Interface Touch Pad
The User Interface has individual touch-sensitive printed
circuit board mounted buttons, and comes with a built-in
menu structure (Hidden Key and Password Protected) to
change many of the common operating variables.
Four Operating Mode States
Four different user operating mode states can be chosen
on the LUI:
Heat: Heating and economizer operation only.
Cool: Cooling and economizer operation only.
Fan Only: Fan only operation.
Auto: The unit automatically switches between heating,
cooling and economizer operation to satisfy the room
load conditions. The current unit state is also displayed.
Local User Interface
A built-in LUI touch pad with digital LED Display is
located in the right hand compartment below the top right
access door. In addition to the Operating Mode States
and Fan Functions, the Touch Pad will digitally display:
• The room set point temperature.
• The current room temperature.
• Any fault code for quick diagnostics at the unit.
Four Fan States
Four fan states are provided on all units: high, medium
low and Auto speed modulation. The Auto speed
function (part load, variable air) varies the fan speed
automatically to meet the room load whether the unit is in
heating, cooling or economizer mode.
All this is accomplished with a standard, single-speed
NEMA frame motor. A built-in 10-minute delay helps
minimize awareness of speed changes. During low-load
or normal operation (about 60% of the time) the fan will
operate at low speed. The low speed operation, along
with GentleFlo fan technology, contributes to a very quiet
classroom environment.
When the load increases to an intermediate demand, the
fan automatically shifts to the medium speed setting. At
near-design or design-load conditions the fan will
operate on high speed.
With four fan states and GentleFlo fan technology, there
is no need to oversize units or worry about
uncomfortable conditions.
AAF-HermanNelson Model AV Unit Ventilators21
MicroTech II Controls
Optional Communication Modules
Optional communication modules provide control and
monitoring information to your building automation
system without the need for costly gateways. Available
communication protocols include BACnet, LonTalk and
Metasys N2 Open. The communication modules for each
are described below.
Figure 21. Typical 2" x 4" Communication Module
BACnet MS/TP Communication Module
This module allows the UVC to inter-operate with
systems that use the BACnet (MS/TP) protocol with a
conformance level of 3. It meets the requirements of the
ANSI/ASHRAE 135-1995 standard for BACnet systems.
LonWorks SCC Communication Module
This module supports the LonWorks SCC (Space
Comfort Communication) profile number 8500-10. Unit
controllers are LonMark certified with this optional
LonWorks communication module.
Metasys N2 Communication Module
This module provides N2 Open network communication
capability to the UVC for communication with Johnson
Metasys systems.
Figure 22. Wall-Mounted Temperature Sensors
StandardExpandedDeluxe
Standard Sensor: This sensor has no remote setpoint
adjustment capability.
Expanded Sensor: This sensor has a remote room
setpoint adjustment of ±3°F (±1.5°C) from the room
setpoint established on the unit ventilator’s local user
interface touch pad. Five temperature settings are
provided on each side of center.
Deluxe Sensor : This sensor has a remote room setpoint
adjustment of from 54°F (12°C) to 82°F (28°C) with a
midpoint setting of 68°F (20°C).
Note: McQuay does not recommend using the Deluxe Sensor
with DX systems due to its wide operating range and
potential problems with the refrigerant system.
Humidity Sensors
On units equipped with humidity sensors, the UVC is
configured to use a 0-100% RH, 0
VDC, capacitive
humidity sensor. Humidity sensors are available as unitmounted only. The humidity sensors are used with units
capable of passive or active dehumidification, or with
units using an outdoor enthalpy economizer or an indoor/
outdoor enthalpy economizer.
Sensors
The UVC is configured to use passive Positive
Temperature Coefficient (PTC) unit-mounted and wallmounted sensors. These sensors vary their input
resistance to the UVC as the sensed temperature
changes.
CO2 Sensor for Demand Controlled Ventilation
On units equipped for Demand Controlled Ventilation
(DCV) the UVC is configured to use a 0-2000 PPM, 0-10
VDC, single beam absorption infrared gas sensor. CO
2
sensors are available as unit mounted only. An air
collection probe (pitot tube and filter) is installed in the
return air of the unit.
Remote Wall-Mounted Temperature Sensors
MicroTech II unit ventilators offer three choices for
Figure 23. CO2 Sensor For Demand Control Ventilation
remote wall-mounted room sensors (
Figure 22). Each
has a tenant override capability and comes with an
international, quick-fastening connection capability.
22McQuay Catalog 1600
MicroTech II Controls
Figure 24. MicroTech II Sensor and Component Locations
Top V i ew
Room Humidity
Sensor (Optional)
Face & Bypass
Damper Actuator
RoomTemp
Outdoor/Return
Air Damper
Actuator
Sensor
Discharge Air
Temp S e n s o r
Interface (LUI)
External Signal
Connection Plugs
Freezestat
Low Refrig
Temp S n s r
Local User
Time Clock (Stand
Alone Unit Option)
Tenant Override
Switch
MicroTech II Unit
Ventilator Controller
Communication
Module (Optional)
Control Transformer
Fuse(s)
Electric
Connection Box
Outdoor Air
Temp S e n s o r
Outdoor
Humidity Sensor
Front View
Drainpan Condensate Overflow Sensor (Optional)
A sensor can be installed in the drain pan of the unit
ventilator to sense high water levels and force the unit to
discontinue cooling. This helps prevent the overflow of
condensate fwhen the drain is clogged.
Actuators
Face & Bypass Damper Actuator
On units equipped with face & bypass damper control,
the UVC is configured to operate a floating-point (tristate), direct-coupled, face & bypass damper actuator. To
determine the modulating damper position, the controller
uses a separate, factory-preset, configurable setting for
each actuator's stroke time. To increase accuracy, the
controller has an overdrive feature for the 0% and 100%
positions and a periodic (12-hour) auto-zero PI control
loop for each modulating actuator.
Figure 25. Face & Bypass Damper Actuator
CO2 Sensor
(Optional)
Main Power
On/Off Switch
Outdoor Air/Return Air Damper (OAD) Actuator
The UVC is configured to operate a floating-point (tristate) direct-coupled actuator for the outdoor air damper.
This actuator provides spring-return operation upon loss
of power for positive close-off of the outdoor air damper.
To determine damper position, the UVC uses a separate,
factory-preset, configurable setting for each actuator's
stroke time. To increase actuator positioning accuracy,
the UVC is provided with an overdrive feature for the 0%
and 100% positions and a periodic (12- hour) auto-zero
PI control loop for each modulating actuator.
On units equipped with 2-way or 3-way, end-of-cycle
(EOC) valves, the UVC is configured to operate 2position End-Of-Cycle (EOC) valve actuators
(
Figure 27). Spring return actuators are used for all End
of Cycle (EOC) valves. All wet heat and heat/ cool EOC
valves are normally open, and all cooling EOC valves
are normally closed.
AAF-HermanNelson Model AV Unit Ventilators23
MicroTech II Controls
Figure 27. End of Cycle Valve Actuator
Modulating Valve Actuators (Optional)
On units equipped with modulating valves, the UVC is
configured to operate floating-point (tri-state) actuators
for modulating 2- way and 3-way valves (
Figure 28. Modulating Valve Actuators
2-Way Valve3-Way Valve
Figure 28).
Spring return actuators are used for all modulating
valves. All wet heat and heat/ cool valves are normally
open, all cooling valves are normally closed.
To determine modulating valve position the UVC uses a
separate factory preset, configurable setting for each
actuator's stroke time. For accuracy of actuator
positioning, the UVC is provided with an overdrive
feature for the 0% and 100% positions and a periodic
(12-hour) auto-zero PI control loop for each modulating
actuator.
Optional Time Clock For Stand-Alone
Operation
As an option, stand-alone, non-slave unit ventilators can
be factory-equipped with a unit-mounted, digital, 24-hour/
7-day time clock with 20 programs (
is factory-wired to automatically place the unit into
occupied or unoccupied mode based upon its schedule.
Features of this clock include:
Figure 29). The clock
• Large keys with circular programming for easy
schedule setup
• An LCD display
• Manual 3-way override (On/Auto/Off)
• Capacitor backup to retain program memory during
power outages.
Figure 29. Optional Time Clock
ServiceTools™
ServiceTools for MicroTech II Unit Ventilators is a CD
containing software for operation on a personal
computer. This software provides a visual schematic of
the unit, a pictorial representation of the sequence of
operation and enables the service technician to:
• Monitor equipment operation.
• Configure network communications.
• Diagnose unit operating problems.
• Download application code and configure the unit.
This software is a purchased tool for service technicians
and will run on PCs with Windows
2000 (SP2), and NT4.0 (SP6) and XP (SP1) operating
systems. This tool provides more capabilities than the
unit’s user interface touch pad and is highly
recommended for startup and servicing. (It may be
required for startup and/or servicing, depending upon
unit integration and other requirements.) It has no BAS
functions, such as scheduling or trending, and it cannot
serve as a Work Station Monitoring package.
ServiceTools comes with a service cable having two
interface connections:
• A 12-pin connection to connect to the main control
board.
• A 3-pin connection to connect to the optional
communication modules.
®
98 (Second Edition),
24McQuay Catalog 1600
Accessories
Accessories
Wall Louvers & Grilles
AAF-HermanNelson wall louvers allow outdoor air to be
drawn in while blending with the building architecture.
They are sized to match the unit outside air opening and
provide maximum air intake. Heavy-gauge, all-aluminum
construction is standard, with a decorative grille optional.
Both louvers and grilles are available either painted or
unpainted. When painted, a specially formulated,
environmentally friendly thermosetting urethane powder
is applied electrostatically and baked for long lasting
beauty as well as resistance to corrosion. The paint is
then oven cured to provide correct chemical crosslinking, which can provide years of service. The alloy
used for louvers and grilles, AQ 5005, is suitable for color
anodizing by others.
Figure 30. Intake Louvers
Horizontal Blade Louver
Vertical Blade Louver
Weep Holes
Louver Details
Louvers are available in both horizontal and vertical
blade configurations (
Figure 30):
• Horizontal blade construction turns the incoming air
to keep moisture from entering. Bottom weep holes
drain moisture to the outside.
• Vertical-blade construction provides positive water
impingement and entrapment. The bottom lip drains
moisture to the outside.
Louvers can be supplied with or without flanges:
• Flanged louvers are typically used for a panel wall
finish (
Figure 31).
• Unflanged louvers are typically used for recessing
into a masonry wall.
A half-inch-square mesh bird screen (Figure 32) located
on the leaving air side of the louver prevents birds and
other small animals from entering. The screen’s strong
aluminum mesh is designed to minimize air pressure
drops, unlike expanded metal mesh.
Figure 32. Louver Assembly With Grille
Bird Screen
Louver
Grille
Grille Details
AAF-HermanNelson decorative intake grilles come in
either painted or unpainted AQ 5005 aluminum with
holes for mounting to building exteriors (
Figure 33). Their
square holes are designed to match the blades of the
AAF-HermanNelson louver, maximizing the air opening.
Figure 33. Decorative Intake Grille
Weep Holes
Figure 31. Flanged Louver (Indoor View)
Bird Screen
AAF-HermanNelson Model AV Unit Ventilators25
Accessories
Ventimatic™ Shutter Room Exhaust Ventilation
Outdoor air introduced by the unit ventilator must leave
the room in some way. In some states, exhaust vents are
required by law or code to accomplish this. The
Ventimatic shutter is a more economical solution to the
problem.
The Ventimatic shutter is a continuously variable, gravityactuated room exhaust vent (
Figure 34). It operates in
direct response to positive static air pressure created
when ventilation air is brought into the room by the unit
ventilator. It is a “one-way” shutter that opposes any flow
of air into the room.
Figure 34. Ventimatic Shutter
Front (Indoor Side)Back (Outdoor Side)
The Ventimatic Shutter’s ability to exhaust only the
amount of air required results in considerable energy
savings. In the heating mode, the unit ventilator will be
able to bring in only the required percent minimum
outdoor air. Unlike systems that rely on powered
exhaust, no energy will be wasted heating excess
outdoor air. In the cooling mode, the unit ventilator will be
able to bring in 100% outdoor air for full natural or free
cooling when it is energy effective.
Since it is not powered, Ventimatic Shutter’s operation is
inherently silent. Unlike other non-powered vents, it
opens at an extremely low positive pressure (0.005"). Its
shutter flaps are made of temperature-resistant glass
fabric impregnated with silicone rubber for flexibility and
long life. This fabric retains its original properties down to
-50°F.
Ventimatic Installation
The Ventimatic Shutter should be mounted on the same
wall as the unit ventilator. This neutralizes the effect of
wind pressure forcing excess air into the room through
the unit ventilator louver. That’s because the wind
pressure will also keep the Ventimatic Shutter closed and
prevent room air from escaping. Since the existing room
air cannot leave, excess air from the wind gust will not
enter. (In contrast, a powered exhauster would “assist”
the wind’s effect.) Same-wall mounting also minimizes
“short circuiting” of air flow that could occur with
opposite-wall mounting.
The Ventimatic Shutter is generally mounted on an AAFHermanNelson wall louver (ordered separately) which is
then used for exhaust (
Figure 35). For large unit
ventilators, two Ventimatic Shutters may be mounted
side by side on the same wall louver to promote
adequate exhaust air capacity. The size and appearance
of wall louvers and grilles used for unit ventilators and for
Ventimatic Shutters are identical and present an
architecturally coordinated and pleasing installation.
An ideal method of integrating the Ventimatic Shutter
with the unit ventilator is to locate the shutter behind a
matching open-shelf or closed-shelf storage cabinet
mounted next to the unit ventilator. For example, 48-inchlength wall louver can be accommodated behind a 4foot-high storage cabinet. The cabinet should be ordered
with a slotted-type kick plate to provide a concealed
exhaust air path to the shutter. This combination will
enable a complete, integrated, energy-efficient HVAC
and room exhaust system. For dimensional information,
see
“Ventimatic Shutter Assembly” on page 90.
Figure 35. Ventimatic Shutter Installation
Aluminum Exterior Grille (Optional)
Aluminum Louver
Ventimatic Shutter
Louver
Two Shutter Assemblies
Mounted On One Louver
Center Cover
Baffle Plate
Steel Interior
Grille (Optional)
26McQuay Catalog 1600
Accessories
Storage Cabinets, Sink & Bubbler
AAF-HermanNelson storage cabinets are designed to
complement our classroom unit ventilators. They are
made from heavy-gauge steel and finished with
environmentally friendly, thermosetting urethane powder
paint that is available in a pleasing array of matching
architectural colors.
Storage Cabinets
Shelving cabinet tops are furnished with a textured, nonglare and scuff-resistant charcoal bronze electrostatic
paint. Optional laminate tops are available for these
cabinets and for field-supplied and installed countertops.
Other features include:
• Adjustable kick plates with leg levelers are standard on
all units and functional accessories. European cabinet
design has adjustable leg levellers on each corner that
adjust to compensate for variations in the floor.
• Adjustable-height metal shelves for flexible storage
space (
tools by repositioning the four concealed shelf holding
clips.
• Optional easy sliding doors with bottom glide track for
good alignment (
prevents door bottom intrusion into the storage space.
Optional door locks.
• Door pulls added for convenience and finished
appearance.
Figure 36). Shelves can be adjusted without
Figure 37). Bottom glide track
Figure 37. Cabinet With Sliding Doors
Sink & Bubbler Cabinet
Sink & bubbler cabinets have a one-piece stainless steel
top with stainless steel bowls, a raised front lip, and
formed back and end splash boards (
have a choice of single or double bowls and optional
door locks to conceal storage and piping. The adapter
back top, when furnished, has a charcoal textured finish.
Figure 38. Cabinet With Sink And Bubbler
Figure 38). You
Figure 36. Cabinet With Shelves
AAF-HermanNelson Model AV Unit Ventilators27
Accessories
End Panels, Filler Sections & Sub-Bases
AAF-HermanNelson end panels, filler sections and subbases can be used to match up AAF-HermanNelson unit
ventilators with existing furniture or units, or with our
storage, sink and bubbler cabinet offerings
End Panels
One-inch end panels are typically used to finish off
stand-alone floor units. Six-inch end panels, with kick
plates, can be used to provide extra space needed for
piping (
wrapped in plastic and boxed to help prevent damage
during construction.
Figure 39. End Panels
Figure 39). All end panels are individually
End Panel
Sub-Bases
AAF-HermanNelson sub-bases are used to provide
additional height to floor unit ventilators so that they
match up with the window sill or with existing cabinets
(
Figure 40).
Note: Prior to 1968, unit ventilators came in 28, 30 and 34-inch
heights. The industry then standardized on the 30-inch
height of the current AAF-HermanNelson unit.
Sub-bases can also be used to raise the outside air
opening above floor level to reduce blockage of outside
louvers and reduce louver soiling from rain splash.
They are available in 1, 2, 4, 6 and 12-inch heights with a
depth of either 16-5/8" or 21-7/8". The unit ventilator’s
leg levelers can also be used to level the entire unit/subbase assembly, compensating for uneven floors.
Sub-bases have an Oxford brown, baked, thermalsetting urethane powder paint finish that matches the
unit’s bottom section and withstands cleaning of floors.
Figure 40. Sub-Base
Filler Sections
Filler sections can be used as spacing between cabinets,
walls and unit ventilators. They are available with either
laminate or painted metal tops and come in 18" and 24"
lengths. They may be cut to length, with a minimum
length after cutting of 3".
Each filler section includes a top, a front panel and a kick
plate. Corner sections are also available which include a
top, a corner post and a corner kickplate. For
dimensional information and illustrations, see
Sections & Utility Compartment” on page 92.
“Filler
Sub Base
28McQuay Catalog 1600
Application Considerations
Application Considerations
Why Classrooms Overheat
Overheated classrooms occur every day in schools in
every area of the country. The most serious result is their
detrimental effect on students’ ability to concentrate and
learn. Research has determined that the ability to learn
and retain knowledge decreases rapidly as the
temperature exceeds recommendations. Overheated
rooms also represent wasted fuel, resulting in excessive
operating costs.
Correcting an overheating problem in an existing building
is very difficult and expensive. It calls for redesign and
alteration of the heating and ventilating system,
necessitating considerable renovation. This potential
problem should be recognized, understood and planned
for when heating and ventilating systems are designed
for new and existing buildings.
Schools Have Special Needs
Schools have unique heating and ventilating needs, in
large part because of their variable occupancy and
usage patterns. Fewer cubic feet of space is provided
per student in a school building than in any other type of
commercial or public building. School classrooms are
typically occupied only six hours a day, five days a week,
for only three-fourths of the year, with time out for
vacations. All in all, this represents approximately 15% of
the hours in a year that a classroom is occupied.
To understand the overheating problem in schools, one
must first realize that the excess heat comes from what
is commonly termed “uncontrolled heat sources.” To gain
some perspective on how this affects heating and cooling
decisions, let’s take a look at a typical classroom in the
northern section of the midwestern United States.
Suppose we have a classroom that is 24 by 38 feet with
10-foot ceilings and 100 square feet of window area
along the outside wall. At an outside temperature of 0°F
and a desired room temperature of 72°F, let’s assume
the normal amount of heat loss from the room to the
outside is 55,000 BTUs per hour.
As the outside temperature changes, so does the
amount of heat that the room loses. This is represented
in
Figure 41 by Room Heat Loss Line A, which ranges
from 55,000 BTUs per hour at 0°F outside air
temperature to zero BTUs at 70°F. Obviously, if the
heating system were the only source of heat in the
classroom, the solution would be simple: The room
thermostat would cause the heating system to supply
exactly the amount of heat required to maintain the room
at the thermostat temperature setting. In reality, the
introduction of excess heat from a variety of uncontrolled
sources makes the challenge considerably more
complex.
Figure 41. Heat Gain vs. Heat Loss In Occupied Classrooms
A
60,000
50,000
40,000
30,000
20,000
Room Heat Loss, BTU/HR
10,000
-10010203040506070
As this chart illustrates, even in very cold weather an occupied
classroom is more likely to require cooling than heating.
ROOM HEAT LOSS LINES
B
C
D
Outside Air Temperature, °F
Temperature On Room
Heat Loss Line Above
Which Cooling Is
Always Required
10,000 BTU/HR
}
Possible Heat Gain From
Sun, Direct & Reflected
8,500 BTU/HR
}
Heat Gain From Lights
7,800 BTU/HR
}
Heat Gain From
Students
Heat From Students
Body heat generated by students in a classroom is one
of the three primary sources of uncontrolled heat. In a
typical classroom of 30 students, the amount of heat
given off at all times will vary according to factors such
as age, activity, gender, etc. A conservative estimate is
260 BTUs per hour per pupil. Multiply this by 30 and you
get a total of 7,800 BTUs per hour added to the room by
the students alone. This excess heat is noted in
Figure 41 as “Heat Gain from Students.”
Heat Gain From Lights
Heat emitted by the lighting system constitutes a second
uncontrolled heat source. Artificial lighting is needed in
most classrooms even during daylight hours to prevent
unbalanced lighting and eye strain. A typical classroom
requires approximately 2,500 watts of supplemental
lighting to provide properly balanced lighting. Fluorescent
lights add heat to the room at the rate of 3.4 BTU per
watt per hour, or a total of 8,500 BTU per hour. This extra
heat is represented in
Figure 41 as “Heat Gain from
Lights.”
Add the heat gain from lighting to the 7,800 BTUs
introduced by student body heat and we now have an
extra 16,300 BTU/HR being introduced into the
classroom by uncontrolled sources. This heat gain
remains constant regardless of the outdoor air
temperature.
AAF-HermanNelson Model AV Unit Ventilators29
Application Considerations
Solar Heat Gain
The sun is a third uncontrolled source of heat. And,
because it is neither positive nor constant, calculating its
contribution to the overall heat gain is difficult. Solar heat
gain can be the worst offender of the three in classrooms
with large windows. Indirect or reflected solar radiation is
substantial even on cloudy days, even in rooms with
north exposure, as a result of what is termed “skyshine.”
To get an idea of the potential effect of the sun, let’s
assume that the solar heat gain in our hypothetical
classroom will peak at 240 BTU/HR per square foot of
glass area. If we then assume a glass area of 100
square feet and at least 100 BTU/HR per square foot of
glass for solar heat gain, we can calculate a very
conservative estimate of 10,000 BTU/HR heat gain
through windows. If we add this to the heat from the
lights and body heat, total heat gain adds up to 26,300
BTU/HR from sources other than the heating and
ventilating system. This is indicated in
top horizontal line, which intersects Room Heat Loss
Line A at approximately 37°F. This is a reasonable
estimate of the maximum uncontrolled heat gain that can
be received in the typical classroom from these common
heat sources.
Figure 41 by the
The Analysis
From Figure 41 it is evident that, at an outside
temperature of 48°F or higher, the heat given off by 30
students and classroom lighting is sufficient to cause
overheating. This is true even if the classroom is occupied
at night when solar heat gain is not a factor. But, since
classrooms are occupied during the day, solar addition
provides heat in varying amounts even in classrooms with
north exposures. Consequently, the heating and
ventilating system in our typical classroom must provide
cooling at all times when the outdoor temperature is above
48°F and at any time during colder weather when the
solar heat gain exceeds room heat loss.
If we assume an average winter temperature of
approximately 33°F in the region where our typical
classroom is located, we know that, half of the time, both
night and day, the outside temperature will be above 33°F.
However, since it is generally warmer during the day, when
school is in session, the heating and ventilating system will
be required to provide cooling for this classroom during
much of the time that the room is occupied.
In this example, we’ve assumed that our classroom had
a room heat loss of 55,000 BTU/HR at a design outdoor
air temperature of 0°F (Room Heat Loss Line “A”). Bear
in mind, however, that the recent trend in “energy-saving”
building design often results in rooms with lower room
heat loss, as indicated by Room Heat Loss Lines “B”, “C”
and “D.” At 0°F design outdoor air temperature:
• Room “B” has a room heat loss of 45,000 BTU/HR,
• Room “C” has a room heat loss of 35,000 BTU/HR,
• Room “D” has a room heat loss of 25,000 BTU/HR.
Note the lowering of the temperature above which
cooling will always be required as the room heat loss
decreases.
We’ve noted that cooling is always required in Classroom
“A” when outdoor air temperatures exceed 48°F. In
Classroom “B,” “C,” and “D” cooling is always required
when outdoor temperatures exceed 44°, 36°and 23°F,
respectively (
Now that we understand the reason for classrooms
overheating, the solution is simple: The heating and
ventilating system must provide cooling to take care of
the heat given off in the classroom by uncontrolled heat
sources.
Figure 41).
Cooling The Classroom
The AAF-HermanNelson Unit Ventilator has become a
standard for heating and ventilating systems in schools
because it provides the solution for overheating
classrooms. The unit ventilator cools as well as heats.
During the heating season the outdoor air temperature is
nearly always below the desired room temperature. It
stands to reason then that the outside air should be used
to provide the cooling necessary to keep classrooms
down to thermostat temperature.
The classroom unit ventilator does just that. By
incorporating an automatically controlled outdoor air
damper, a variable quantity of outdoor air is introduced in
the classroom, metered exactly to counteract
overheating. Since our problem is more one of cooling
than of heating, it is evident that more than just the room
heat loss must be determined to design a good heating
and ventilating system. The cooling requirements should
be assessed as well, and the free-cooling capacity of the
equipment specified along with the heating capacity
required. If this is done, the optimum learning
temperature can be maintained in each classroom.
30McQuay Catalog 1600
Loading...
+ 76 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.