This manual describes the sequences of operation for MicroTech
controlled AAF-HermanNelson Unit V entilators equipped with chilled
water cooling and electric hating, or chilled water cooling only. Unit
Ventilators with these heating and cooling configurations could be
AAF-HermanNelson models AVV, AVS, AHF or AHV. Regardless of
General Information
Software ID
The Unit Ventilator Controller software must be compatible with the Unit
V entilator heating and cooling configuration. The softw are is identified by
a program code and “software model” number printed on a small label
attached to the controller. Models AVV, AVS, AHF, or AHV with chilled
water cooling only or both chilled water cooling and electric heating use
program UV7***. The first wild card character defines the UVC
communication type as follows: S = stand-alone , M = master/slav e, and
N = network code. The last two wild card char acters denote the software
version (numeric) and revision lev el (alphabetical) respectiv ely . Progr am
UV7*** comprises four software models: MDL15 through MDL18. Each
software model is for a diff erent unit configuration. Refer to Table 1.
Table 1. Program UV7 Unit Ventilator Configurations
ProgramSoftware ModelConfiguration Description
MDL15Chilled Water Only, Valve Control
UV7***
MDL16Chilled Water Only, Damper Control
MDL17Chilled Water and Electric Heat, Valve Control
MDL18Chilled Water and Electric Heat, Damper Control
the AAF model type, the Unit Ventilator Controller (UVC) provided
with these units uses program UV7***.
For more information on the MicroTech Unit Ventilator Controller,
refer to Bulletin No. IM613, “MicroTech Unit Ventilator Controller.”
Setpoints
Most UVC setpoints are either “hardware” or “software” adjustable.
Hardware adjustable means there is an on-board potentiometer used
for adjustment. Software adjustable means a PC equipped with Monitor
software and proper cable connection is required to make an adjustment.
Default software adjustable v alues are shown on the sequence charts.
Hardware adjustable values sho wn on the charts are for example only.
Several UVC setpoints are defined b y offsets relative to other setpoints.
Table 2 summarizes these setpoints and offsets.
In order to maintain more stable room temperature control, the
MicroTech Unit Ventilator Controller (UVC) uses the concept of a
“Control Temperature.” During the occupied or tenant override
operating modes, the Control T emperature is a weighted v alue equal
to 19/20 room temperature and 1/20 discharge air temperature.
During the unoccupied operating mode, the Control Temperature is
set equal to the room temperature.
OM 107-1 / Page 2 (Rev. 7/99)
Setpoint Abbreviations
OCSOccupied cooling setpoint
VCSVentilation cooling setpoint
OHSOccupied heating setpoint
UHSUnoccupied heating setpoint
UCSUnoccupied cooling setpoint
VCLOVentilation cooling outdoor air lockout setpoint
VCLLVentilation cooling discharge air low limit setpoint
CWLLChilled water cooling discharge air low limit setpoint
OALOOutdoor air lockout setpoint
Software ID
Program: UV7***
Software Model: MDL15
Default
Value
Occupied or Tenant Override Operating Mode
The supply fan will run continually in the occupied or tenant override
operating modes.
When the UVC is first energized it will perform a self-calibration
procedure upon the OA damper and valv e actuators. The calibr ation
procedure will take approximately 5-minutes to perf orm during which
time the supply fan will not operate.
An outdoor air lockout setpoint has been provided to force the OA
damper closed when the OA temperature goes below the OALO
setpoint (software adjustable).The OALO setpoint must not be set
below the freeze point of the liquid being used within the building
water loop. In order to lower the OALO setpoint below the default
value glycol must be added to the building water loop in sufficient
concentration to ensure freezing will not occur. However, the O ALO
setpoint can be lowered if steam heat is used.
If provided, the optional exhaust fan output will energize when the
OA damper opens and de-energize when the OA damper closes.
If provided, the optional ventilation lock out feature can ov erride UVC
temperature control and keep the OA damper closed as required.
If provided, the optional auxiliary heat output will operate a normally
open device. The auxiliary output will energize (close the device)
when the Control Temperature is above the OHS. The auxiliary output
will de-energize (open the device) when the Control Temperature is
o
F below the OHS.
3
The same UVC output is used for both the auxiliary heat output
feature and the exhaust f an output f eature. Therefore, both features
cannot be used together.
Note: When switching from unoccupied-to-occupied mode the OA
damper will remain closed for the first 5-minutes of occupied operation.
Morning Start
If the space is cool and heating is required, the outdoor air (OA)
damper will remain closed and room air will be circulated until the
Control Temperature rises to within 3
will be opened to minimum position.
If the space is warm and cooling is required, the unit will operate as
described in “Cooling Operation” below. If the outdoor air is not
suitable for free cooling, the OA damper will remain closed until the
Control Temperature falls to within 3
will be opened to minimum position.
Cooling Operation
When the Control Temperature is greater than the OHS setpoint and
less than the VCS setpoint, the OA damper will be held at its minim um
position setpoint (hardware adjustable). As the Control Temperature
rises and cooling becomes necessary, the UVC will decide whether
the outdoor air is suitable for free cooling by comparing the outdoor
air temperature (dry bulb) to the VCLO setpoint.
If the OA temperature is less than or equal to the VCLO setpoint,
the economizer will modulate as required to maintain the VCS
setpoint (default = 2
o
F less than OCS). The Control Temperature will
rise if the outdoor air is too warm to satisfy the cooling load. If the
OA damper is more than 85% open, the chilled water valve will
modulate as required to maintain the OCS setpoint.
If the OA temperature is warmer than the VCLO setpoint, the chilled
water valve will modulate as required to maintain the OCS setpoint.
The OA damper will be held to the minimum position setpoint, except
when the Control Temperature is 3
unlikely situation, the OA damper will be closed.
As the Control Temperature falls, the chilled water valve will modulate
closed. If the v alve is less than 15% open when the Control T emperature
falls below the VCS setpoint, the OA damper will modulate closed.
Note: Regardless of the economizer state, its operation is subject
to discharge air low limit control.
o
F of the OHS setpoint. Then it
o
F of the OCS setpoint. Then it
o
F or more above the OCS. In this
Heating Operation
The OA damper will maintain its minimum position when the Control
Temperature is within 3
Temperature falls to 3
Certified Drawing
o
F of the OHS setpoint. If the Control
o
F or more below the OHS, the OA damper
will be closed and room air will be circulated.
Unoccupied Operating Mode
The outdoor air damper will always be closed when the unit is in the
unoccupied operating mode. The indoor fan will remain off when the
unit is in the unoccupied operating mode unless heating or cooling
are required (see note below).
Note: During the unoccupied mode, if the fan remains off continually
for 60-minutes, it will start and run for 5-minutes.
Cooling Operation
If the Control Temperature rises to the UCS setpoint, the chilled
water valve will be fully opened and the fan will be energized.
o
When the Control Temperature falls 1
the fan will be de-energized. When it f alls 2
F below the UCS setpoint,
o
F below the UCS setpoint,
the valve will be closed.
Heating Operation
If the Control Temperature falls below the UHS setpoint, the fan will
be energized and room air will be circulated.
The fan will be de-energized when the Control Temperature rises
above the UHS setpoint.
Discharge Air Low Limit Control
There are two discharge air low limit functions: the “CW cooling” low
limit and the “vent cooling” low limit. The vent cooling low limit function
prevents the discharge air (D A) temperature from falling below the VCLL
setpoint whenever chilled water cooling is not necessary; when chilled
water cooling is necessary , the vent cooling low limit function is disabled.
The CW cooling low limit function prevents the DA temperature from
falling below the lower CWLL setpoint whene ver the unit is in the chilled
water cooling mode (chilled water valv e > 15% open).
Vent Cooling Low Limit (CW Cooling Inactive)
If the DA temperature f alls below the VCLL setpoint, the OA damper
will modulate toward fully closed. When the DA temper ature rises to
the VCLL setpoint, normal operation will resume.
CW Low Limit (CW Cooling Active)
If the DA temperature falls below the CWLL setpoint, the chilled
water valve will be closed.
If the DA temperature rises abov e the CWLL setpoint before the actual
valve position is less than 15% open, normal operation will resume.
If the DA temperature remains below the CWLL setpoint until the
actual valve position is less than 15% open (unlikely), the O A damper
will be closed by the vent cooling low limit function (see above).
Safeties
Low Water Coil Leaving Air Temperature
A normally closed low temperature switch is provided to detect low
leaving air temperature conditions on the indoor air coil. The low
temperature switch cut out is 38
When the UVC detects the possibility of low leaving air temperatures
for longer then 5-seconds (fixed), the following will occur:
•The OA damper is closed
•The chilled water valv e is opened to 25% if the DA temperature
is above the VCLL setpoint
•The chilled water valve is opened to 100% if the D A temperature
is less than or equal to the VCLL setpoint
When the alarm conditions are gone, the fault will automatically reset.
o
F +/– 2 and the cut in is 45oF +/– 2.
OM 107-1 / Page 3 (Rev. 7/99)
Sequence Charts
12345678901234
4
12345678901234
5
5
123
123
123
123
The following charts graphically summarize the expected sequences
of operation for this Unit Ventilator configuration. The charts are all
based upon factory default setpoints. The output states indicated on
the charts will typically exist for a particular control temperature,
howev er, e xceptions will occur when other control features are active
or when alarm conditions exist or when factory defaults are changed.
Brief descriptions of the control feature exceptions are noted on the
Outdoor Air Temperature Dependent Functions
charts. Refer to bulletin No. IM613, “MicroTech Unit Ventilator
Controller” for more information.
Software ID
Program: UV7***
Software Model: MDL015
Outdoor Air Temperature (
o
F)
UVC
Function
Indicated
State
Notes
OALOVCLO
34 35 3663 64 65
Economizer CoolingAvailable1,3,4
Outdoor Air LockoutAvailable2
Indicated state
(default setpoints)
Indicated state dependent on
differential (default setpoints)
Outdoor Air Temperature Dependent Function Notes:
1.Economizer cooling will be unavailable when OA is above VCLO
2.OA lockout feature is enabled from the factory in UV Model 15, when enabled the O A damper will be forced closed if O A temperature is below OALO
3.In very humid locations VCLO can be lowered to limit the economizer function
4.In locations where humidity is of no concern, VCLO can be raised slightly to allow additional economizer cooling