Microprocessor Control Board........................................................................................................................5
Field Wiring Terminal Board.............................................................................................................................8
MicroTech Monitoring and Networking Options.............................................................................................9
PC Monitoring....................................................................................................................................................9
Panel Location and Mounting............................................................................................................................11
Field Wiring...........................................................................................................................................................12
Power .................................................................................................................................................................12
PC Connection..................................................................................................................................................14
Test Procedures....................................................................................................................................................21
LED Diagnostics ..............................................................................................................................................21
Troubleshooting Power Problems .................................................................................................................21
Parts List................................................................................................................................................................23
Figure 17. MCB Power Connector.....................................................................................................................22
Tables
Table 1. Maximum Output Ratings.......................................................................................................................7
2IM 657-1
Table 2. PC Specification.....................................................................................................................................10
This manual provides information about the MicroTech® Series 100 Application Specific Controller
(ASC-100). It describes the ASC-100’s components, field wiring requirements, and service procedures.
The versatile ASC-100 controller monitors and controls a variety of mechanical and electrical
environmental equipment in a MicroTech building automation system (BAS). The ASC-100 uses
custom configured software written for each application. This provides the customers with a wide
range of options for monitoring and controlling their HVAC equipment.
WARNING
Electric shock hazard. Can cause personal injury or equipment damage.
This equipment must be properly grounded. Connections and service to the MicroTech
control panel must be performed only by personnel that are knowledgeable in the operation
of the equipment being controlled.
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards
can cause damage to the components.
Discharge any static electrical charge by touching the bare metal inside the control panel
before performing any service work. Never unplug any cables, circuit board terminal blocks,
or power plugs while power is applied to the panel.
NOTICE
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with this instruction manual, may cause interference to
radio communications. It has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. Operation of this equipment in a residential area is likely to
cause harmful interference in which case users will be required to correct the interference
at their own expense. McQuay International disclaims any liability resulting from any
interference or for the correction thereof.
4IM 657-1
General Description
The MicroTech Series 100 Application Specific Controller (ASC-100) is a microprocessor-based
controller used to monitor and control pieces of hardware that do not have MicroTech controls
factory installed. Typical applications of the ASC-100 include control of lighting, boiler systems,
circulating pumps, and air handlers.
The ASC-100’s design offers input and output flexibility. The ASC-100 supports eight inputs (analog
or digital) and eight digital outputs.
Component Data
Figure 1 shows the control panel layout for the ASC-100. The main components of the control system
include the Microprocessor Control Board (MCB) and the Field Wiring Terminal Board (FWTB). The
MCB contains hex switches, power-in connector, relays, status LEDs, inputs switches, communication
ports, and a 1.5-amp fuse.
The FWTB contains terminal blocks with screw terminals for connecting analog/digital inputs, digital
outputs, and auxiliary power.
Transformers T1 and T2 provide power to the controller. A 0.5-amp circuit breaker protects the
controller against power surges and over-voltages. These major components are mounted inside a
NEMA 1 enclosure.
Figure 1. MicroTech ASC-100 Panel Layout
L1
GRD
L2
51
52
53
54
55
TB1
T2
T1
CB1
MCBFWTB
Microprocessor Control Board
Figure 2 shows the Microprocessor Control Board (MCB). It contains a microprocessor that has
custom software written to monitor and control the equipment connected to the ASC-100. This
custom software is normally loaded into the MCB at the job-site. The various MCB connections and
components are described below.
IM 657-15
Figure 2. Microprocessor Control Board (MCB)
Electromechanical
Relays
Hex Switches
Communications
Ports
Watchdog LED
Port A Select
Digital Input
Status LEDs
HI
LO
1 2 3321
Port APort B
Status LED
L1
a0191
Reset LED
Output Status
LEDs
Input Switches
Hex Switches
The MCB includes two hex (hexadecimal) switches that are used to set the ASC-100 controller’s
network address.
The HI and LO hex switches are shown in Figure 3(hex switch setting 01 shown). A “hex switch
setting” is defined as the HI switch digit followed by the LO switch digit. For example, a hex switch
setting of 2F would have the HI switch set to “2” and the LO switch set to “F.” In most cases, the
ASC-100’s hex switch setting is set between 01 and 40 (level-2).
Note: To change the setting of a hex switch, use a 3/32-inch tip, slotted-blade screwdriver. Insert the
screwdriver into the slot on the hex switch, then turn it to the position required. If a hex switch setting
is changed, cycle power to the MCB by opening and closing the circuit breaker located in the power
section of the control panel. By cycling power, the new switch setting is entered into memory.
Figure 3. Hex Switches
6IM 657-1
Power In Connector
The MCB receives 18 Vac, center-tapped power from transformer T2 through the Power In connector.
This power drives all logic and communications circuitry. Refer to the panel’s wiring diagram or Figure
16 for more information.
Electromechanical Relays
The single-pole double through (SPDT) electromechanical relays drive digital outputs connected to
the Field Wiring Terminal Board. Depending on the wiring setup, the relay can be normally open or
normally closed (see “Digital Outputs” below). See Table 1 for the relay’s output ratings.
Table 1. Maximum Output Ratings
VoltageOutput Rating
30 Vdc20 watts resistive,
10 watts inductive
30 Vac30 VA resistive,
20 VA inductive
LEDs
The MCB has the following LEDs: Digital Output Status, Digital Input Status, Watchdog, Reset, and
Status.
•The Digital Output Status LED is lit when a digital output is activated. There are eight Digital
Output Status LEDs, one for each electromechanical relay. When the relay is energized, the LED
illuminates.
•The Digital Input Status LED is lit when an input switch is set to “Contact” and a digital input
signal is present. There are eight Digital Input Status LEDs located below the input switches (see
“Input Switches” below).
•The Reset LED illuminates for 5 seconds when power is applied to the MCB. The LED’s location
is on the right side of the MCB mounting plate.
• The Status LED indicates when the MCB is operational and ready to communicate by flashing.
• The Watchdog LED operates the same as the Reset LED.
Input SwitchesThe input switches select the type of input signal connected to the Field Wiring Terminal Board (see
Figure 4). There are eight input switches with each switch having four positions (thermistor, 4-20 mA,
0–5 Vdc, or contact). For example, if the device connected to input 0 is a thermistor type input, input
switch SW0 is set to position 1. Switches SW1 through SW7 are set the same way depending on the
type of input that is field wired to the Field Wiring Terminal Board.
Figure 4. Input Switches
INPUT SWITCHES
SW0 SW1 SW2 SW3 SW4 SW5 SW6 SW7
THERMISTOR
4–20 mA
0–5 Vdc
CONTACT
(POS. 1)
(POS. 2)
(POS. 3)
(POS. 4)
IM 657-17
Communication PortsThe MCB contains two communication ports: port A and port B. Each port includes three terminals.
The Port A Select switch, located below the hex switches, enables the user to select RS-232 or RS-485
data transmission for port A. Moving the switch to the left position sets up RS-232 data transmission
while moving the switch to the right sets up RS-485 data transmission. The MCB uses Phoenix type
connectors for the ports. Following are brief descriptions of each port’s function.
Port A Port A (TS1) is usually used for communications with an IBM compatible PC using the RS-
232 interface standard. The PC can be directly connected, over a limited distance, with a
twisted, shielded pair cable. The default communications rate is 9600 bps. For more
information, see “PC Connection” in the “Field Wiring” section of this manual.
Port B Port B is for MicroTech network communications using the RS-485 interface standard. A
twisted, shielded pair cable should be connected to port B (TS2). The communications rate
is 9600 bps. For more information, see “Network Communications” in the “Field Wiring”
section of this manual.
Field Wiring Terminal BoardFigure 5 shows the Field Wiring Terminal Board. The Field Wiring Terminal Board has field wiring
terminals for analog/digital inputs, digital outputs, and auxiliary power.
Analog/Digital InputsScrew terminals on TB4 and TB5 enable the user to connect an analog input or a digital input (dry
contact ) to the ASC-100. Inputs are labeled IN 0 through IN 7. Each input has two screw terminals
associated with it. For example: IN 0 includes screw terminals TB5-28 and TB5-29 (see Figure 5). For
more information, see “Analog/Digital Inputs” in the “Field Wiring” section of this manual.
Digital OutputsScrew terminals on TB1, TB2, and TB3 enable the user to wire a digital output to the ASC-100. The
digital outputs are labeled Output 0 through Output 7. Each output consists of three screw terminals.
For example: Output 0 includes screw terminals TB1-1, TB1-2, and TB1-3. If the output is to be
normally open, screw terminals 1 and 2 are used. If the output is to be normally closed, screw terminals
2 and 3 are used. For more information, see “Digital Outputs” in the “Field Wiring” section of this
manual.
PowerAuxiliary power sources are available at screw terminals TB3-25 and TB3-26 (13 Vdc), and screw
terminals TB4-36 and TB5-37 (5 Vdc). These terminals can be used to power peripheral devices.
8IM 657-1
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.