McQuay ALS 260C Installation Manual

Installation, Operation and Maintenance Manual
Air-Cooled Screw Compressor Chiller
ALS 141C through 420C
IOMM ALS-3
Group: Chiller Part Number: 330145707 Date: March 2001 Supersedes: IOMM ALS-2
Table Of Contents
Introduction.............................3
General Description........................................3
Nomenclature...................................................3
Inspection........................................................3
Installation and Start-up ............3
Handling...........................................................4
Location............................................................5
Service Access................................................5
Clearance Requirements.................................6
Vibration Isolators...........................................9
Lifting and Mounting Weights...................10
Water Piping..................................................12
System Water Volume...................................13
Variable Water Flow......................................13
Evaporator Freeze Protection......................14
Flow Switch....................................................14
Water Connections.......................................15
Refrigerant Charge........................................15
Glycol Solutions............................................15
Remote Evaporator................16
General............................................................16
Performance Derate Factors ........................16
Refrigerant Piping.........................................17
Startup Procedures .......................................22
Dimensions, Remote Evaporator................23
Water Flow and Pressure Drop26
Physical Data ......................... 28
Compressor Staging ..............32
Unit Layout and Principles of
Operation.............................. 67
Major Component Location.........................67
Control Center ................................................68
Sequence of Operation.................................71
Start-up and Shutdown.......... 73
Seasonal Start-up..........................................73
Temporary Shutdown ...................................73
Start-up After Temporary Shutdown..........74
Extended (Seasonal) Shutdown ..................74
Start-up After Extended (Seasonal)
Shutdown .......................................................75
System Maintenance.............. 76
General............................................................76
Compressor Maintenance............................76
Lubrication.....................................................76
Electrical Terminals........................................76
Condensers ....................................................76
Refrigerant Sightglass..................................77
Lead-Lag.........................................................77
Preventative Maintenance Schedule..........78
Service.................................. 79
Compressor Solenoids..................................79
Filter-Driers.....................................................79
Liquid Line Solenoid Valve..........................81
Electronic Expansion Valve..........................81
Electronic Expansion Valve Operation.......82
Evaporator......................................................82
Charging Refrigerant.....................................83
Charging Oil...................................................84
Dimensional Data...................34
Wind Baffles and Hail Guards 37
Electrical Data........................39
Field Wiring....................................................39
Wire Sizing Ampacities ................................40
Field Wiring Diagram .............59
In-Warranty Return Material
Procedure ............................. 85
Standard Controls ................. 86
Optional Controls ..........................................91
Controls, Settings and Functions...............92
Troubleshooting Chart.................................93
Periodic Maintenance Log...........................94
Solid State Starters ................60
Our facility is ISO Certified
"McQuay" is a registered trademarks of McQuay International
"Information covers the McQuay International products at the time of publication and we reserve the right to make changes in
design and construction at anytime without notice"
2 IOMM ALS-3
Initial Issue January 1998
2001 McQuay International
Introduction
Design Vintage
General Description
McQuay air-cooled water chillers are complete, self-contained automatic refrigerating units that include the latest in engineering components arranged to provide a compact and efficient unit. Each unit is completely assembled, factory wired, evacuated, charged, tested and comes complete and ready for installation, except for remote evaporator models. Each unit consists of multiple air-cooled condensers with integral subcooler sections, multiple accessible semi-hermetic single-screw compressors, solid-state starters, multiple circuit shell-and-tube evaporator, and complete refrigerant piping. Liquid line components included are manual liquid line shutoff valves, charging valves, filter­driers, liquid line solenoid valves, sightglass/moisture indicators, and electronic expansion valves. Compressor suction and discharge shutoff valves are included. Other features include compressor heaters, an evaporator heater for low ambient water freeze protection, automatic one time pumpdown of refrigerant circuit upon circuit shutdown, and an advanced fully integrated microprocessor control system.
Nomenclature
A L S - XXX C
Air-Cooled
Liquid Oil Injected
Rotary Screw Compressor
Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to insure a complete shipment. All units should be carefully inspected for damage upon arrival. All shipping damage must be reported to the carrier and a claim must be filed with the carrier. The unit’s serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available. Physical damage to unit after acceptance is not the responsibility of McQuay International. Note: Unit shipping and operating weights are available in the Physical Data Tables.
Installation and Start-up
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Start-up by McQuayService is included on all units sold for installation within the USA and Canada and must be performed by them. Two week prior notification of start-up is required. The contractor should obtain a copy of the Start-up Scheduled Request Form from the sales representative or from the nearest office of McQuayService.
Nominal Tons
CAUTION
IOMM ALS-3 3
Handling
Care should be taken to avoid rough handling or shock due to impact or dropping the unit. Do not push or pull the unit from anything other than the base, and block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet and end frame (see Figure 1).
Never allow any part of the unit to fall during unloading or moving as this may result in serious damage.
To lift the unit, 2½ “ (64 mm) diameter lifting holes are provided in the base of the unit. Spreader bars and cables should be arranged to prevent damage to the condenser coils or unit cabinet (see Figure 2).
Figure 1, Suggested Pushing Method
Figure 2, Required Lifting Method
NOTES:
1. All rigging points on a unit, either 4, 6, or 8 locations, must be used. See Figure 7 through Figure 10 for number, location, and weight at lifting points for a specific size unit. This diagram illustrates a unit with 4 mounting holes (ALS 141 - ALS 218).
2. Crosswise and lengthwise spreader bars must be used to avoid damage to unit. Lifting cables from the unit mounting holes up must be vertical.
3. The number of condenser sections, and fans can vary from this diagram.
4 IOMM ALS-3
Location
Care should be taken in the location of the unit to provide proper airflow to the condenser. (See Figure 3 through Figure 5 for required clearances).
Due to the vertical condenser coil design of the ALS chillers, it is recommended that the unit be oriented so that prevailing winds blow parallel to the unit length, thus minimizing the wind effect on condensing pressure and performance. It is recommended that wind baffles be installed if the unit is installed with no protection against prevailing winds.
Using less clearances than shown in Figure 3, Figure 4, and Figure 5 will cause discharge air recirculation to the condenser and could have a significant and detrimental effect on unit performance. See the current version of McQuay Product Manual PM ALS for more detailed information on the subject of air recirculation.
Service Access
Each end of the unit must be accessible after installation for periodic service work. Compressors, filter-driers, and manual liquid line shutoff valves are accessible on each side of the unit adjacent to the control box. High pressure and low pressure transducers are mounted on the compressor. The cooler barrel heater thermostat is located on the cooler. Compressor microprocessor and most other operational and equipment protection controls are located in the unit control box. The solid-state starters with their internal electrical protection features are mounted on the base side rails adjacent to the compressor they serve.
On all ALS units the condenser fans and motors can be removed from the top of the unit. The complete fan/motor assembly can be removed for service. The fan blade and fan motor rain shield must be removed for access to wiring terminals at the top of the motor.
WARNING
Disconnect all power to the unit while servicing condenser fan motors.
Failure to do so may cause bodily injury or death.
Do not block access to the sides or ends of the unit with piping or conduit. These areas must be open for service access. Do not block any access to the control panel with a field mounted disconnect switch.
IOMM ALS-3 5
Clearance Requirements
Figure 3, Clearance Requirements, ALS 141-218
Notes:
1. Minimum side clearance between two units is 12 feet.
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit
unless extra clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet when installed in a pit no deeper than the unit height.
4. Minimum side clearance to a side wall or building taller than the unit height is 8 feet provided no
solid wall above 6 feet is closer than 12 feet to the opposite side of the unit.
5. The evaporator can be removed from the side of the unit.
6. Do not mount electrical conduits, etc, above the side rail on either side if the unit.
7. There must be no obstruction of the fan discharge.
8. It is recommended that field supplied disconnect switches not be mounted on the unit.
6 IOMM ALS-3
Figure 4, Clearance Requirements, ALS 245-295
Notes:
1. Minimum side clearance between two units is 12 feet.
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit
unless extra clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet when installed in a pit no deeper than the unit height.
4. Minimum side clearance to a side wall or building taller than the unit height is 8 feet provided no
solid wall above 6 feet is closer than 12 feet to the opposite side of the unit.
5. The evaporator can be removed from the side of the unit.
6. Do not mount electrical conduits, etc, above the side rail on either side if the unit.
7. There must be no obstruction of the fan discharge.
8. It is recommended that field supplied disconnect switches not be mounted on the unit.
IOMM ALS-3 7
Figure 5, Clearance Requirements, ALS 325-420
Notes:
1. Minimum side clearance between two units is 12 feet.
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit
unless extra clearance is provided per note 4.
3. Minimum clearance on each side is 8 feet when installed in a pit no deeper than the unit height.
4. Minimum side clearance to a side wall or building taller than the unit height is 8 feet provided no
solid wall above 6 feet is closer than 12 feet to the opposite side of the unit.
5. The removable post for compressor service access must not be blocked at either side of the unit.
6. Do not mount electrical conduits, etc, above the side rail on either side if the unit.
7. There must be no obstruction of the fan discharge.
8. It is recommended that field supplied disconnect switches not be mounted on the unit.
8 IOMM ALS-3
Vibration Isolators
Vibration isolators are recommended for all roof mounted installations or wherever vibration transmission is a consideration. The following section "Lifting and Mounting Weights" contains the location of unit lifting holes and the load at each location. Mounting holes are also dimensioned and the bearing weight at each hole given.
Figure 6, Spring Flex Isolators
Table 1, Spring Vibration Isolators, Part Numbers
Mounting Location (See Footprint Drawings Figure 7 through Figure 10)
Model R1 R2 R3 R4 R5 R6 R7 R8 R9 R10
ALS 141-ALS 186 Isolator kit part number 350014880
Max Load 2200 2200 2600 2600 1800 1800
Spring P/N 022611901 022611901 022612000 02261200 022611800 022611800
Color Gray Gray White White Green Green
Housing P/N 022610300 022610300 022610300 022610300 022610300 022610300
ALS 190-ALS218 Isolator kit part number 350014881
Max Load 2600 2600 3000 3000 2200 2200
Spring P/N 022612000 022612000 330202101 330202101 022611901 022611901
Color White White Gold Gold Gray Gray
Housing P/N 022610300 022610300 022610300 022610300 022610300 022610300
ALS 245-ALS 295 Isolator kit part number 350014882
Max Load 2200 2200 3000 3000 2600 3000 1800 2200
Spring P/N 022611901 022611901 330202101 330202101 022612000 330202101 022611800 022611901
Color Gray Gray Gold Gold White Gold Green Gray
Housing P/N 022610300 022610300 022610300 022610300 022610300 022610300 022610300 022610300
ALS 325-ALS 420 Isolator kit part number 350014883
Max Load 2600 2600 3000 3000 2200 2200 3000 3000 2600 2600
Spring P/N 022612000 022612000 330202101 330202101 022611901 022611901 330202101 330202101 022612000 022612000
Color White White Gold Gold Gray Gray Gold Gold White White
Housing P/N 022610300 022610300 022610300 022610300 022610300 022610300 022610300 022610300 022610300 022610300
Notes:
1. The same isolators are used when the chiller is supplied with the optional copper finned condenser coils.
2. The spring is fully compressed at approximately 3900 lb. (1769 kg).
IOMM ALS-3 9
Lifting and Mounting Weights
Figure 7, ALS 141C – ALS 186C Lifting and Mounting Locations
NOTES:
1. 2 ½ in. (63.5 mm) lifting holes at location "L" on side of base rail.
2. 1 in. (25.4 mm) mounting holes at location "R" on bottom of base rail.
L2
R2
36 (914)
BOX
CONTROL
46 (1168)
ALS
Model
141 2585 (1171) 2125 (963) 1835 (831) 1785 (809) 1230 (557) 9700 (4394) 9420 (4267) 1370 (620) 150 2570 (1164) 2205 (999) 1830 (829) 1805 (818) 1305 (591) 9880 (4476) 9550 (4326) 1370 (620) 171 2570 (1164) 2210 (1001) 1830 (829) 1810 (820) 1305 (591) 9890 (4472) 9560 (4331) 1370 (620) 186 2575 (1166) 2210 (1001) 1830 (829) 1810 (820) 1310 (593) 9900 (4485) 9570 (4335) 1370 (620)
Lifting Weight for Each
Point lb (kg)
L1 & L2 L3 & L4 R1 & R2 R3 & R4 R5 & R6
102 (2591)
R1
L1
R4
192 (4877)
161 (4089)
R3
Mounting Loads for Each Point
lb. (kg)
L4
R6
83.4
(2118)
R5
L3
Operating Wt
lb. (kg)
2 (51) Typical Spacing for Isolator Mounting (6)
Shipping Wt.
lb. (kg)
Copper Fin
Figure 8, ALS 190C – ALS 218C Lifting and Mounting Locations
Add
L2 L4
R2
36 (914)
BOX
CONTROL
46 (1168)
ALS
Model
190 2915 (1320) 2230 (1010) 2010 (910) 2135 (967) 1165 (527) 10620 (4811) 10290 (4661) 1610 (730) 200 2920 (1323) 2230 (1010) 2015 (913) 2135 (967) 1165 (527) 10630 (4815) 10300 (4666) 1610 (730) 206 2940 (1332) 2310 (1046) 2000 (906) 2240 (1015) 1240 (562) 10960 (4965) 10500 (4756) 1610 (730) 218 2960 (1341) 2405 (1089) 1985 (899) 2425 (1098) 1365 (618) 11550 (5232) 10730 (4861) 1610 (730)
Lifting Weight for Each
Point lb (kg)
L1 & L2 L3 & L4 R1 & R2 R3 & R4 R5 & R6
123 (3124)
R1
L1
R4
195 (4953)
R3
Mounting Loads for Each Point
lb. (kg)
224 (5690)
R6
83.4
(2118)
R5
L3
Operating Wt
lb. (kg)
2 (51) Typical Spacing for Isolator Mounting (6)
Shipping Wt.
lb. (kg)
Copper Fin
Add
10 IOMM ALS-3
Figure 9, ALS 245C – ALS 295C Lifting and Mounting Locations
83.4
(2118)
2 (51) Typical Spacing for Isolator Mounting (8)
ALS
Model
Lifting Weight for Each Point lb (kg) Mounting Loads for Each Point lb. (kg)
L1 & L2 L3 & L4 L5 L6 R1 & R2 R3 & R4 R5 & R6 R7 R8
Operating Wt
lb. (kg)
Shipping Wt.
lb. (kg)
Copper Fin
Add
245 2845 (1289) 2445 (1108) 1420 (643) 2050 (928) 1745 (790) 2240 (1015) 2030 (920) 1150 (521) 1660 (752) 14840 (6722) 14030 (6356) 2020 (915) 260 2850 (1291) 2445 (1108) 1420 (643) 2050 (928) 1745 (790) 2245 (1017) 2030 (920) 1150 (521) 1660 (752) 14850 (6727) 14040 (6360) 2020 (915) 270 2845 (1289) 2455 (1112) 1430 (648) 2060 (933) 1750 (793) 2245 (1017) 2035 (922) 1155 (523) 1665 (528) 14880 (6741) 14090 (6383) 2020 (915) 275 2850 (1291) 2455 (1112) 1430 (648) 2060 (933) 1755 (793) 2245 (1017) 2035 (922) 1155 (523) 1665 (528) 14890 (6745) 14100 (6387) 2020 (915) 295 2865 (1298) 2455 (1112) 1430 (648) 2060 (933) 1755 (793) 2250 (1019) 2035 (922) 1155 (523) 1665(528) 14900 (6750) 14110 (6392) 2020 (915)
Figure 10, ALS 325C – ALS 420C Lifting and Mounting Locations
83.4
(2118)
2 (51) Typical Spacing for Isolator Mounting (10)
ALS
Model
Lifting Weight for Each Point lb (kg) Mounting Loads for Each Point lb. (kg)
L1 & L2 L3 & L4 L5 & L6 L7 & L8 R1 & R2 R3 & R4 R5 & R6 R7 & R8 R9 & R10
Operating Wt
lb. (kg)
Shipping Wt.
lb. (kg)
Copper Fin
Add
325 2625 (1189) 1895 (858) 2805 (1271) 1835 (831) 2060 (933) 1955 (886) 1485 (673) 2245 (1017) 1895 (858) 19280 (8734) 18320 (8299) 2750 (1246) 335 2625 (1189) 1895 (858) 2805 (1271) 1840 (833) 2065 (935)) 1955 (886) 1485 (673) 2245 (1017) 1895 (858) 19290 (8738) 18330 (8303) 2750 (1246) 350 2625 (1189) 1895 (858) 2805 (1271) 1840 (833) 2065 (935) 1955 (886) 1485 (673) 2245 (1017) 1895 (858) 19290 (8738) 18330 (8303) 2750 (1246) 365 2625 (1189) 1900 (861) 2805 (1271) 1840 (833) 2070 (938) 1955 (886) 1485 (673) 2245 (1017) 1895 (858) 19300 (8743) 18340 (8308) 2750 (1246) 375 2635 (1194) 1905 (863) 2815 (12750 1845 (836) 2075 (940) 1960 (888) 1490 (675) 2255 (1021) 1900 (861) 19360 (8770) 18400 (8335) 2750 (1246) 385 2640 (1196) 1905 (863) 2815 (12750 1845 (836) 2075 (940) 1965 (890) 1490 (675) 2255 (1021) 1900 (861) 19370 (8775) 18410 (8340) 2750 (1246) 400 2640 (1196) 1905 (863) 2815 (12750 1845 (836) 2075 (940) 1965 (890) 1490 (675) 2255 (1021) 1900 (861) 19370 (8775) 18410 (8340) 2750 (1246) 420 2640 (1196) 1905 (863) 2815 (12750 1845 (836) 2075 (940) 1965 (890) 1495 (677) 2260 (1024) 1920 (870) 19430 (8802) 18510 (8385) 2750 (1246)
IOMM ALS-3 11
Water Piping
Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities. They can supply the installer with the proper building and safety codes required for a safe and proper installation.
Basically, the piping should be designed with a minimum number of bends and changes in elevation to keep system cost down and performance up. It should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Drains at the low parts in
the system. The evaporator should not be the highest point in the piping system.
4. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulating
valve).
5. Water temperature and pressure indicators located at the unit to aid in unit servicing.
6. A strainer or some means of removing foreign matter from the water before it enters the pump.
The strainer should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). The use of a strainer will prolong pump life and help maintain high system performance levels.
WARNING
7. A strainer must also be placed in the supply water line just prior to the inlet of the evaporator.
This will aid in preventing foreign material from entering the evaporator and causing damage or decreasing its performance. Care must also be exercised if welding pipe to the evaporator connections to prevent any weld slag from entering the vessel.
8. The shell-and-tube evaporator has a thermostat and heating cable to prevent freeze-up down to ­20°F (-28.8°C). It is suggested that the heating cable be wired to a separate 110V supply circuit. As shipped from the factory, it is factory wired to the control circuit. Any water piping to the unit must also be protected to prevent freezing.
9. If the unit is used as a replacement chiller on a previously existing piping system, the system should be thoroughly flushed prior to unit installation and then regular chilled water analysis and chemical water treatment is recommended immediately at equipment start-up.
10. The total water quantity in the system should be sufficient to prevent frequent "on-off" cycling. For air-conditioning systems, system gallons equal to 7 time the flow rate is recommended.
11. In the event glycol is added to the water system, as an afterthought for freeze protection, recognize that the refrigerant suction pressure will be lower, cooling performance less, and water side pressure drop greater. If the percentage of glycol is large, or if propylene is employed in lieu of ethylene glycol, the added pressure drop and loss of performance could be substantial.
12. For operations requiring the ice mode feature, logic in MicroTech will adjust the freezestat to a pressure equivalent to 13.5°F (7.5°C) below the leaving evaporator water temperature. However, if a different freezestat pressure value is desired, the freezestat can be manually changed through MicroTech. Refer to the current OM ALSMICRO for additional information.
CAUTION
If a separate disconnect is used for the 110V supply to the cooler heating cable, it should be clearly marked so that it is not accidentally shut off during cold seasons.
Prior to insulating the piping and filling the system, a preliminary leak check should be made. Piping insulation should include a vapor barrier to prevent moisture condensation and possible
damage to the building structure. It is important to have the vapor barrier on the outside of the insulation to prevent condensation within the insulation on the cold surface of the pipe.
12 IOMM ALS-3
System Water Volume
It is important to have adequate water volume in the system to provide an opportunity for the chiller to sense a load change, adjust to the change and stabilize. As the expected load change becomes more rapid, a greater water volume is needed. The system water volume is the total amount of water in the evaporator, air handling products and associated piping. If the water volume is too low, operational problems can occur including rapid compressor cycling, rapid loading & unloading of compressors, erratic refrigerant flow in the chiller, improper motor cooling, shortened equipment life and other undesirable occurrences.
For normal comfort cooling applications where the cooling load changes relatively slowly, we recommend a minimum system volume of seven minutes times the flow rate (gpm). For example, if the design chiller flow rate is 400 gpm, we recommend a minimum system volume of 2800 gallons (400 gpm X 7 minutes).
For process applications where the cooling load can change rapidly, additional system water volume is needed. A process example would be the cooling of hot metal objects. The load would be very stable until the hot metal is dipped into the water tank. Then, the load would increase drastically. For this type of application, we recommend that the normal comfort cooling recommendation addressed above plus three minutes of ballast for every 10% quick change in load. For example, if the hot metal example load changes from a stable 50% load to an immediate 100% load for metal cooling, the recommended system volume would increase to 8800 gallons.
System volume = {400 gpm X 7 minutes} + {(5 increments of 10% increase) X (3 minutes) X 400 gpm} = 8800 gallons
Since there are many other factors that can influence performance, systems may successfully operate below these suggestions. However, as the water volume decreases below these suggestions, the possibility of problems increases.
Variable Water Flow
Variable water flow involves changing the water flow through the evaporator as the load changes. McQuay chillers are designed for this duty provided that the rate of change in water flow is slow and the minimum and maximum flow rates for the vessel are not exceeded.
The recommended change in water flow is listed in the table below. As the number of stages of control increase, the slower the permissible rate of change in flow rate becomes. The ALS control logic has timers that limit the rate of unloading or loading allowed. Slow changes allow the chiller the opportunity to sense a change, react to the change and stabilize preventing operational problems.
ALS Size
141 to 218 2 8 10.0 245 to 295 3 12 7.5 325 to 420 4 16 5.0
For example, assume that an ALS with two compressors has a design flow of 500 gpm and the minimum vessel flow rate of 300 gpm. The allowable amount of flow change is 200 gpm. An ALS with two compressors has an allowable change rate of 10% of change per minute. Therefore, the maximum rate of change recommended would be 20 gpm/minute (200 X .10).
The water flow through the vessel must remain between the minimum and maximum values listed on Figure 19. If flow drops below the minimum allowable, large reductions in heat transfer can occur. If the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.
Number of
Compressors
Unloading
Steps
Maximum allowable % per
minute of flow change
IOMM ALS-3 13
Evaporator Freeze Protection
All evaporators come equipped with thermostatically controlled resistive element heater. When power is applied to terminals 13 and 16, the heat tape will provide freeze protection down to -20°F (-28.8°C). However, this should not be the only method of freeze protection. Unless the evaporator is flushed and drained as is described below in note 4, two or more of the remaining three recommendations must be followed as part of the system design:
1. Continuous circulation of water through the piping and the heat exchanger.
2. The inclusion of glycol solution in the chilled water circuit.
3. The addition of insulation and heat to the exposed piping.
4. Draining and flushing the chiller vessel with glycol during subfreezing weather.
It is the responsibility of the installing contractor and/or on-site maintenance personnel to insure that this additional protection is provided. Routine checks should be made to insure adequate freeze protection is maintained.
Failure to do so may result in damage to unit components. Freeze damage is not considered a warranty failure.
Figure 11, Typical Field Water Piping
Vent
Outlet
Drain
Vibration
Eliminator
Valved
pressure
gauge
Water
strainer
Vibration
Eliminator
Gate valve
Flow
Balancing
Switch
Protect all field piping against freezing
valve
Gate valve
Flow Switch
A water flow switch must be mounted in the leaving water line to insure that there will be adequate water flow to the evaporator before the unit can start. This will safeguard against slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up.
A flow switch is available from McQuay under ordering number 017503300. It is a "paddle" type switch and adaptable to any pipe size from 1" (25mm) to 8" (203mm) nominal.
Certain minimum flow rates are required to close the switch and are listed in Table 2. Installation should be as shown in Figure 12.
Electrical connections in the unit control center should be made at terminals 62 and 63. The normally open contacts of the flow switch should be wired between these two terminals. Flow switch contact quality must be suitable for 24 VAC, low current (16ma). Flow switch wire must be in separate conduit from any high voltage conductors (115 VAC and higher).
14 IOMM ALS-3
Figure 12, Flow Switch
()()(
)
Flow direction marked
on switch
1" (25mm) NPT flow
switch connection
Tee
Table 2, Switch Minimum Flow Rates
NOMINAL PIPE SIZE
INCHES (MM)
5 (127) 58.7 (3.7) 6 (152) 79.2 (5.0) 8 (203) 140 (8.8)
Note: Water pressure differential switches are not recommended for outdoor applications.
MINIMUM REQUIRED FLOW TO ACTIVATE SWITCH - GPM (LPS)
1 1/4" (32mm) pipe dia.
min. after switch
1 1/4" (32mm) pipe
dia. min. before switch
Water Connections
Water piping to the cooler can be brought up through the bottom of the unit or through the side between the vertical supports. The dimensional drawings in Figure 20 through Figure 22 give the necessary dimensions and locations for all piping connections. Evaporator piping connections face toward the left side of the unit when looking at the control panel.
Refrigerant Charge
All units are designed for use with HCFC-22 (and are compatible with some HCFC alternatives) and are shipped with a full operating charge. The operating charge for each unit is shown in the Physical Data Tables. Units ordered with a remote evaporator are shipped with a unit operating charge of refrigerant pumped down in the unit condensers. The McQuay authorized startup technician will top off the system charge at startup.
Glycol Solutions
When using glycol anti-freeze solutions the chiller's capacity, glycol solution flow rate, and pressure drop through the cooler may be calculated using the following formulas and tables.
Note: The procedure below does not specify the type of glycol. Use the derate factors found in Table 3 for corrections when using propylene glycol and those in Table 4 for ethylene glycol.
1. Capacity - Cooling capacity is reduced from that with plain water. To find the reduced value,
multiply the chiller’s water system tonnage by the capacity correction factor to find the chiller’s capacity when using glycol.
2. Flow - To determine flow (or delta-T) knowing delta-T (or flow) and capacity:
GPM−=
24
factorflowtons
TDelta
3. Pressure drop - To determine pressure drop through the cooler, when using glycol, enter the
water pressure drop curve at the water flow rate. Multiply the water pressure drop found there by the PD factor to obtain corrected glycol pressure drop.
4. To determine glycol system kW, multiply the water system kW by factor called Power. Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service
stations) to determine the freezing point. Obtain percent glycol from the freezing point table below. On glycol applications the supplier normally recommends that a minimum of 25% solution by weight be used for protection against corrosion.
IOMM ALS-3 15
CAUTION
Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller evaporator. The type and handling of glycol used must be consistent with local codes.
Table 3, Propylene Glycol
FREEZE
%
POINT.
P.G.
oFo
C
10 26 -3 0.987 0.992 1.010 1.068 20 19 -7 0.975 0.985 1.028 1.147 30 9 -13 0.962 0.978 1.050 1.248 40 -5 -21 0.946 0.971 1.078 1.366 50 -27 -33 0.965 0.965 1.116 1.481
Remote Evaporator
General
The multiple compressor ALS air-cooled chillers are available with the evaporator shipped loose for remote mounting. This allows the main unit to be installed outdoors to save interior room and eliminates the need for anti-freeze solutions and heat tracing of chilled water lines since the chilled water system is indoors. There are some general guidelines to review before proceeding:
1. R-22 only.
2. Maximum line length of 50 ft (15 m) and Total Equivalent Length (TEL) of 120 ft (37 m).
3. Evaporator not more than 6 ft (1.8 m) above the compressor or 16 ft (5 m) below compressor.
4. No underground piping.
CAP POWER FLOW PD
Table 4, Ethylene Glycol
FREEZE
%
E.G.
POINT.
oFo
10 26 -3 0.991 0.996 1.013 1.070 20 18 -8 0.982 0.992 1.040 1.129 30 7 -14 0.972 0.986 1.074 1.181 40 -7 -22 0.961 0.976 1.121 1.263 50 -28 -33 0.946 0.966 1.178 1.308
CAP POWER FLOW PD
C
5. No hot gas bypass.
6. Units with remote evaporator are not included in the ARI Certification Program.
The remote evaporator is shipped separately, ready for quick and easy installation at the job site. All refrigerant accessories such as liquid-vapor line shut-off valves, replaceable core filter-driers, liquid line solenoid valves, electronic expansion valves, and sightglasses are already included on the ALS condensing unit. The evaporator is equipped with entering and leaving chilled water temperature sensor wells. The sensors are pre-wired to the ALS unit with 75 feet long sensor leads and must be field connected to the evaporator thermowells. Suction pressure transducers and temperature sensors must also be relocated to the evaporator. ALS units are factory charged with a full unit charge pumped down into the condensers. Field piping must be leak tested, evacuated and charged during installation. Do not exceed 150 psig test pressure unless the unit is blanked off from the piping.
Performance Derate Factors
All performance tables and adjustment factors found in the current version of the Air-Cooled Screw Chiller catalog (PM ALS-x) are applicable for remote evaporator installations. However, a performance derate must be applied to the R-22 performance data due to additional pressure drops in the suction and liquid lines which cause a loss of compressor performance. These derates are based on a suction line pressure drop equivalent of approximately 2°F (1°C) change in saturation temperature.
For R-22 applications:
Capacity = Tons (kW) x 0.97 Power = Compressor kW x 0.99
16 IOMM ALS-3
Refrigerant Piping
General
Careful design of the refrigerant piping is necessary for efficient system operation. The refrigerant piping should be designed for a low refrigerant pressure drop to obtain maximum capacity and efficiency while maintaining adequate velocity. Lines should slope in the direction of flow to assure good oil return to the compressors. Cost considerations favor keeping line sizes as small as possible while not exceeding acceptable pressure drops in order to maintain unit performance.
NOTE
All refrigerant piping must be reviewed and approved by McQuay Application
Engineers prior to order entry and will be verified by McQuay startup technicians.
Equivalent Line Lengths
Recommended refrigerant line sizes are based on equivalent line lengths of straight pipe, that is, a combination of straight pipe, fittings and valves. The pressure drop through valves and fittings is determined by establishing the equivalent straight length of pipe of the same size with the same friction loss. The "Total Equivalent Length" is the sum of the "Lineal Line Length" and the appropriate "Valve and Fitting Losses in Equivalent Feet of Pipe for Field Supplied Piping" given in Table 5
Table 5, Fitting Equivalent Feet of Pipe
Line Size (in.) Angle Valve Globe Valve 90° Std. Radius Elbow 90° Long Radius Elbow
1 1/8 12 29 2.6 1.7 1 3/8 15 38 3.3 2.3 1 5/8 18 43 4.0 2.6 2 1/8 24 55 5.0 3.3 2 5/8 29 69 6.0 4.1 3 1/8 35 84 7.5 5.0
Location and Arrangement
Refrigerant lines should be as short and direct as possible to minimize tubing and fittings. Long radius elbows must be used (except for traps) to minimize the pressure drops. Traps should be as short as possible to minimize oil accumulation. Refrigerant piping should be arranged so that normal inspection of the equipment is not hindered. Adequate clearance should be provided between refrigerant piping and adjacent walls for insulation. Piping should be run so that it does not interfere with compressor service access, passages or obstruct headroom, windows and doors. Suction line hangers must be sized and located to support the weight of the piping in accordance with good piping practice.
Horizontal portions of the suction lines must be downward sloping toward the compressors. Slope all piping in the direction of flow. Vertical portions of the suction lines must be sized for oil return at minimum compressor load.
Note: Double section risers must not be utilized on any circuit. Traps must be provided as shown on Figure 13 and Figure 14.
Suction Line Sizing
Pressure drop in the suction line reduces system capacity and efficiency because it forces the compressor to operate at lower suction pressure. The suction line should be sized for a pressure drop approximately equivalent of 2°F (1°C) change in saturation temperature. For suction line sizing see Table 7 and table 8. For applications with the evaporator below the ALS unit, the vertical section of the suction lines must be sized to return oil to the compressors at the minimum compressor capacity step.
IOMM ALS-3 17
Example of Suction Line Size Calculation
ALS150C condensing unit with refrigerant R-22 Evaporator located 5 feet below the ALS compressor Lineal length of horizontal suction line is 25 feet Suction line requires 7 long radius (90°) elbows; 3 in the horizontal, 4 in the riser
From Table 6, the nominal circuit capacities for circuit 1 and 2 are 65 and 80 tons respectively
Total lineal suction line length = 30 feet each circuit (25 feet horizontal plus 5 feet vertical riser). For the first try, assume that the total equivalent suction line length is twice the lineal suction line length.
Therefore the estimated total equivalent suction line length = 60 feet
From Table 7 and Table 8, For nominal circuit capacities of 65 & 80 tons and total equivalent line
length of 60 ft, the suction line size = 2 5/8" for horizontal lines and 2 1/8" for vertical lines.
From Table 5, Fitting loss for 2 5/8" long radius (90°) elbow = 4.1 ft, and 3.3 ft for the 2 1/8 elbows.
Therefore fitting loss in equivalent feet of pipe for (3) 2 5/8" long radius (90°) elbow = 12.3 ft, and
13.2 ft for (4) 2 1/8" elbows. Therefore the actual equivalent suction line length = 30 + 12.3 + 13.2 = 55.5 feet
From and Table 8, For nominal circuit capacities of 65 & 80 tons and equivalent line length of 55.5 ft the suction line size is correct.
Table 6, ALS 141C-420C Nominal Circuit Capacities
ALS Model
141 65 (229) 65 (229) - ­150 65 (229) 80 (262) - ­171 80 (262) 80 (262) - ­186 80 (262) 95 (334) - ­190 80 (262) 95 (334) - ­200 95 (334) 95 (334) - ­206 95 (334) 95 (334) - ­218 95 (334) 95 (334) - ­245 65 (229) 80 (262) 80 (262) ­260 80 (262) 80 (262) 80 (262) ­270 80 (262) 80 (262) 95 (334) ­275 80 (262) 95 (334) 95 (334) ­295 95 (334) 95 (334) 95 (334) ­325 65 (229) 65 (229) 80 (262) 80 (262) 335 65 (229) 80 (262) 80 (262) 80 (262) 350 80 (262) 80 (262) 80 (262) 80 (262) 365 80 (262) 80 (262) 80 (262) 95 (334) 375 80 (262) 80 (262) 95 (334) 95 (334) 385 80 (262) 95 (334) 95 (334) 95 (334) 400 95 (334) 95 (334) 95 (334) 95 (334) 420 95 (334) 95 (334) 95 (334) 95 (334)
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Tons (kW) Tons (kW) Tons (kW) Tons (kW)
Table 7, Vertical Upflow Suction Line Sizes
Nominal Circuit
Capacity
Tons (kW)
65 (229)
80 (262)
95 (334)
Equivalent Line Length Ft (m) Suction Line Size (in.)
Vertical Upflow Suction Lines
40 (12) 2 1/8 75 (23) 2 1/8 40 (12) 2 1/8 75 (23) 2 1/8 40 (12) 2 5/8 75 (23) 2 5/8
18 IOMM ALS-3
Table 8, Horizontal and Vertical Downflow Suction Line Sizes
Capacity
Tons (kW)
65 (229) 75 (23) 2 5/8
80 (262) 75 (23) 2 5/8
95 (334) 75 (23) 3 1/8
Vertical Downflow and Horizontal Suction LinesNominal Circuit
Equivalent Line Length Ft (m) Suction Line Size, in.
40 (12) 2 5/8
115 (35) 2 5/8
40 (12) 2 5/8
115 (35) 3 1/8
40 (12) 2 5/8
115 (35) 3 1/8
Liquid-Vapor Lines
The liquid-vapor line from the ALS condensing unit to the evaporator liquid connection is not a conventional liquid line since it carries both liquid and vapor. The compressors on the ALS units utilize a liquid cooled motor and an economizer. Therefore the expansion valve which feeds the full flow of liquid refrigerant into the compressor for motor cooling is mounted in the liquid line between the condenser sub-cooling coil and the compressor inlet, not at the evaporator inlet. The liquid-vapor line to the evaporator is a low pressure line downstream of the expansion valve and the size is slightly larger than a normal liquid line. For liquid line sizing see Table 9 and Table 10.
Table 9, Vertical Upflow Liquid-Vapor Line Sizes
Capacity
Tons (kW)
65 (229)
80 (262)
95 (334)
Equivalent Line Length
Vertical Upflow Liquid-Vapor LinesNominal Circuit
Ft (m) 40 (12) 1 3/8 75 (23) 1 3/8 40 (12) 1 3/8 75 (23) 1 3/8 40 (12) 1 5/8 75 (23) 1 5/8
Liquid-Vapor Line Size
o.d (in.)
Table 10, Horizontal and Vertical Downflow Liquid-Vapor Line Sizes
Capacity
Tons (kW)
65 (229) 75 (23) 1 3/8
80 (262) 75 (23) 1 5/8
95 (334) 75 (23) 1 5/8
Vertical Downflow and Horizontal Liquid-Vapor LinesNominal Circuit
Equivalent Line Length
Ft (m) 40 (12) 1 3/8
115 (35) 1 3/8
40 (12) 1 3/8
115 (35) 1 5/8
40 (12) 1 5/8
115 (35) 1 5/8
Liquid-Vapor Line Size
o.d (in.)
Figure 13, Evaporator Above ALS Unit
Evaporator
Trap
ALS Unit
Suction Line
IOMM ALS-3 19
Figure 14, Evaporator Below ALS Unit
ALS Unit
Suction Line
Evaporator
Trap
NOTE: Keep the trap width at a minimum to avoid trapping excessive oil.
Insulation
All piping joints and fittings must be thoroughly leak tested before insulation is applied. Suction lines must be insulated and should not be installed underground. Suction line insulation must be selected to prevent condensation under local ambient conditions with the lines at 40°F to 50°F (4.4°C to 10°C) operating temperatures. The liquid-vapor lines will operate at 40°F to 60°F (4.4°C to 15.6°C) and must also be insulated to prevent sweating and heat gain.
20 IOMM ALS-3
Startup Procedures
NOTE: McQuayService or a factory authorized McQuay service agent must do initial start-up and
commissioning.
Filter Driers
Following an initial 24 hour operation the pressure drop across the replaceable core filter-drier should be checked. If this pressure drop exceeds the values given in Table 11 at the various load conditions the filter drier cores must be replaced. Also if the moisture indicating sight glass shows a wet system condition after 24 hours of operation the filter cores must be changed. This should remove any contaminants introduced during field piping. The filter drier cores must also be changed anytime the system is opened for servicing.
Table 11, Filter Drier Pressure Drop
Percent Circuit
Loading (%)
100 7 (48.3)
75 5 (34.5) 50 3 (20.7) 25 3 (20.7)
Refrigerant and Oil Charge
The relative position of the ALS unit and the evaporator and the distance between them plays a critical role in determining suction and liquid line sizes and the field refrigerant and oil charges. ALS units with the remote evaporator option are shipped with a unit operating charge of refrigerant and oil. It will be necessary to evacuate the evaporator and field installed line and top off the charge See Table 12 for refrigerant charge for suction and liquid-vapor lines. McQuay Service will supply and add additional oil as required. The correct oil is Planetelf ACD68AW, McQuay Part No. 735030439 (5 gal.), 735030438 (1 gal.).
Maximum Recommended Pressure Drop Across Filter Drier
psig (kPa)
Charging Procedure
The calculated refrigerant charge must be added through the factory supplied charging valve located on the liquid-vapor line coming out of the compressor. Sufficient charge must be added to clear the liquid line sight glass located at the outlet of the condenser. Add an extra 10 lb. of refrigerant after the sight glass is clear.
Table 12, Refrigerant Charge for Suction and Liquid-Vapor Lines
Lineal Tubing
Length
ft (m)
10 (3) 2 5/8 0.51 (0.23) 1 5/8 5.0 (2.3)
20 (6) 2 5/8 1.02 (0.46) 1 5/8 10.0 (4.5)
30 (9) 2 5/8 1.53 (0.69) 1 5/8 15.0 (6.8)
40 (12) 2 5/8 2.04 (0.92) 1 5/8 20.0 (9.0)
Suction Line Refrigerant Charge
lb (kg)
Line (in.) R-22 Line (in.) R-22
2 1/8 0.33 (0.15) 1 3/8 3.6 (1.6)
3 1/8 0.71 (0.32) 2 1/8 0.66 (0.30) 1 3/8 7.2 (3.3)
3 1/8 1.42 (0.64) 2 1/8 0.99 (0.45) 1 3/8 10.8 (4.9)
3 1/8 2.13 (0.96) 2 1/8 1.32 (0.60) 1 3/8 14.4 (6.5)
3 1/8 2.84 (1.29)
Notes:
1. The only approved oil is that identified on the label attached to the compressors. All POE oils are
hygroscopic and care should be exercised in handling the oil to avoid absorption and retention of moisture.
2. Do not leave the oil container open for more than a minute while charging oil. Do not use oil that
has not been properly sealed and stored.
3. Charge must never be added through the compressor suction line
Liquid-Vapor Line Refrigerant Charge
lb (kg)
IOMM ALS-3 21
Dimensions
Use the ALS dimension drawings Figure 20 through Figure 22 for the ALS with remote evaporator. The refrigerant connections are located approximately where the refrigerant connections to the unit mounted evaporator are on a packaged chiller. The remote evaporator dimensions are Figure 15 through Figure 18.
Dimensions, Remote Evaporator
Figure 15, Evaporator for ALS 141 - ALS 200
ALS
Model
141 CDE350332801 34 (128) 1.4 (40.0) 934 (424) 635 (288) 34 (15.4) 34 (15.4)
150-200 CDE350332901 40 (150) 1.8 (52.4) 1127 (512) 758 (343) 45 (20.4) 45 (20.4)
Model
141 94.6 (2403) 17.8 (452) 11.0 (279) 10.2 (259) 12.8 (325) 6.4 (163) 85.2 (2164) 5 (152)
150-200 95.5 (2426) 18.4 (467) 12.0 (305) 10.2 (259) 14.0 (356) 6.8 (173) 84.0 (2134) 8 (203)
Evaporator
Model
Overall Dimensions in. (mm)ALS
Length "K" Height "A" "B" "C" "D" "H" "J"
Water
Volume
gal. (l)
Refrigerant
Volume
cu. ft. (L)
Unit Weights lb. (kg) R-22 Operating Charge lb. (kg)
Operating Shipping Circuit 1 Circuit 2
Conn.
"G"
22 IOMM ALS-3
Figure 16, Evaporator for ALS 206 - ALS 218
ALS
Model
206 CDE350281651 55 (208) 2.4 (67.9) 1464 (665) 943 (428) 57 (25.8) 57 (25.8) 218 CDE350282101 98 (373) 2.8 (79.2) 2028 (921) 1121 (509) 68 (30.9) 68 (30.9)
Model
206 21.3 (542) 12.1 (307) 16.0 (406) 6.9 (176) 84.5 (2149) 96.7 (2459) 218 23.6 (601) 12.4 (315) 20.0 (508) 9.2 (235) 86.6 (2202) 99.7 (2533)
Evaporator
Model
A C D H J K
Water Volume
gal. (l)
Refrig Volume
cu. ft. (l)
Dimensional DataALS
Weights lb. (kg)
Operating Shipping Circuit 1 Circuit 2
R-22 Opn Charge lb.
(kg)
IOMM ALS-3 23
Figure 17, Evaporator for ALS 245 - ALS 295
Evaporator
Model
245-260 CDE350282111 98 (371) 2.91 (82.3) 2035 (924) 1130 (513) 47 (21) 47 (21) 47 (21) 270-295 CDE350282121 94 (357) 3.3 (93.4) 2068 (939) 1174 (533) 53 (24) 53 (24) 53 (24)
Model
Water
Volume
gal. (l)
Refrig Volume cu. ft. (l)
Weights lb. (kg)
Operating Shipping
R-22 Operating Charge lb.
(kg)ALS
Circuit1Circuit
Circuit 3
2
24 IOMM ALS-3
Figure 18, Evaporator for ALS 325 - ALS 420
Evaporator
Model
325-400 CDE350283101 115 (435) 4.1 (116) 2529 (1148) 1423 (646) 49 (22) 49 (22) 49 (22) 49 (22)
420 CDE350283111 110 (416) 4.7 (133( 2575 (1169) 1484 (674) 56 (25) 56 (25) 56 (25) 56 (25)
Model
Water Vol.
gal. (l)
Refrig Vol.
cu. ft. (l)
Operating Shipping Circuit 1 Circuit 2 Circuit 3 Circuit 4
Water Flow and Pressure Drop
The chilled water flow through the evaporator should be adjusted to meet specified conditions. The flow rates must fall between the minimum and maximum values shown in. Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency, cause erratic operation of the electronic expansion valve and could cause low temperature cutouts. On the other hand flow rates exceeding the maximum values shown can cause erosion on the evaporator water connections and tubes.
Measure the chilled water pressure drop through the evaporator at field installed pressure taps. It is important not to include valve or strainer pressure drop in these readings.
Weights lb. (kg) R-22 Operating Charge lb. (kg)ALS
IOMM ALS-3 25
Figure 19, Evaporator Pressure Drops
ALS 420
ALS 141
ALS 150-200
ALS 206
ALS 218-260
ALS 270-295
ALS 325-400
Table 13, Minimum/Maximum Flow Rates
ALS
Minimum Unit Size
141 187 4.0 498 24.2 275 395 4.2 1052 37.8 150 210 4.2 559 28.5 295 413 4.6 1100 41.9 171 234 5.2 623 35.3 325 445 3.9 1186 34.8 186 255 6.1 680 41.9 335 463 4.2 1235 38.1 190 260 6.4 692 43.4 350 484 4.7 1291 42.1 200 276 7.2 737 49.0 365 498 5.0 1328 44.8 206 285 7.5 761 50.4 375 531 5.8 1417 51.9 218 307 5.0 818 36.8 385 546 6.0 1457 55.2 245 339 5.9 903 43.6 400 565 6.6 1506 59.4 260 360 6.7 960 49.4 420 609 8.8 1623 76.2 270 380 3.8 1012 34.7
Flow
gpm
Pressure
Drop ft.
Maximum
Flow gpm
Pressure
Drop ft.
ALS Unit Size
Minimum
Flow gpm
Pressure
Drop ft.
Maximum
Flow gpm
Pressure
Drop ft.
26 IOMM ALS-3
Physical Data
Table 14, Physical Data, ALS 141C – ALS 186C
DATA 141C 150C 171C 186C
BASIC DATA
Unit Cap. @ ARI Conditions, tons
(kW)
Unit Operating Charge R-22, lbs (kg) 140 (63.5) 140 (63.5) 140 (63.5) 150 (68.1) 150 (68.1) 150 (68.1) 150 (68.1) 160 (72.6)
Cabinet Dimensions L x W x H, in. (mm)
Unit Operating Weight, lbs. (kg) 9700 (4395) 9880 (4475) 9890 (4480) 9900 (4485)
Unit Shipping Weight, lbs (kg) 9420 (4270) 9550 (4325) 9560 (4330) 9570 (4335)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 65 (230) 65 (230) 65 (230) 80 (280) 80 (280) 80 (280) 80 (280) 95 (335)
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft2. (m2) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7)
Finned Height x Finned Length
ft. (mm)
Fins Per Inch x Rows Deep 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans -- Fan Diameter, in. (mm) 10 - 28 (711) 10 - 28 (711) 12 - 28 (711) 12 - 28 (711)
No. of Motors -- hp (kW) 10 - 1.5 (1.1) 10 - 1.5 (1.1) 12 - 1.5 (1.1) 12 - 1.5 (1.1) Fan & Motor RPM, 60Hz 1140 1140 1140 1140
60 Hz Fan Tip Speed, fpm 8357 8357 8357 8357
60 Hz Total Unit Airflow, ft3/min 90200 90200 108240 108240
EVAPORATOR, DIRECT EXPANSION
Shell Dia.- Length
in.(mm) - in. (mm)
Evaporator R-22 Charge lbs (kg) 34 (15.4) 34 (15.4) 45 (20.4) 45 (20.4) 45 (20.4) 45 (20.4) 45 (20.4) 45 (20.4)
Water Volume, gallons (liters) 34 (129) 40 (151) 40 (151) 40 (151)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Pressure, psi (kPa) 300 (2068) 300 (2068) 300 (2068) 300 (2068)
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
124.5 (436) 139.7 (489) 155.8 (545) 170 (595)
228.7 x 83.4 x 92.5
(5809 x 2118 x 2350)
80 x 208
(2032 x 5283)
(2032 x 5283)
12.75 – 94.6 (324 - 2403)
80 x 208
228.7 x 83.4 x 92.5
(5809 x 2118 x 2350)
80 x 208
(2032 x 5283)
Table 15, Physical Data, ALS 190C – ALS 218C
DATA 190C 200C 206C 218C
BASIC DATA
Unit Cap. @ ARI Conditions, tons
(kW)
Unit Operating Charge R-22, lbs (kg) 170 (77.0) 180 (81.5) 180 (81.5) 180 (81.5) 185 (83.8) 185 (83.8) 210 (95.1) 210 (95.1)
Cabinet Dimensions,
L x W x H, in. (mm)
Unit Operating Weight, lbs. (kg) 10620 (4810) 10630 (4815) 10960 (4965) 11550 (5230)
Unit Shipping Weight, lbs (kg) 10290 (4660) 10300 (4665) 10500 (4755) 10730 (4860)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 80 (280) 95 (335) 95 (335) 95 (335) 95 (335) 95 (335) 95 (335) 95 (335)
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft2. (m2) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5) 135.0 (12.5)
Finned Height x Finned Length
ft. (mm)
Fins Per Inch x Rows Deep 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans -- Fan Diameter, in. (mm) 14 - 28 (711) 14 - 28 (711) 14 - 28 (711) 14 - 28 (711)
No. of Motors -- hp (kW) 14 - 1.5 (1.1) 14 - 1.5 (1.1) 14 - 1.5 (1.1) 14 - 2.0 (1.5) Fan & Motor RPM, 60Hz 1140 1140 1140 1140
60 Hz Fan Tip Speed, fpm 8357 8357 8357 8357
60 Hz Total Unit Airflow, ft3/mon 126280 126280 126280 138908
EVAPORATOR, DIRECT EXPANSION
Shell Dia. -- Length
in.(mm) - in. (mm)
Evaporator R-22 Charge lbs (kg) 45 (20.4) 45 (20.4) 45 (20.4) 45 (20.4) 57 (25.8) 57 (25.8) 68 (30.8) 68 (30.8)
Water Volume, gallons (liters) 40 (151) 40 (151) 55 (208) 98 (371)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Pressure, psi (kPa) 300 (2068) 300 (2068) 300 (2068) 300 (2068)
Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2
173.1 (606) 184.2 (645) 190.3 (666) 204.4 (715)
263.4 x 83.4 x 92.5
(6690 x 2118 x 2350)
80 x 243
(2032 x 6172)
(2032 x 6172)
14.0 – 95.5
(356 - 2425)
80 x 243
263.4 x 83.4 x 92.5
(6690 x 2118 x 2350)
80 x 243
(2032 x 6172)
ALS MODEL NUMBER
80 x 208
(2032 x 5283)
14.0 – 95.5
(356 - 2425)
ALS MODEL NUMBER
80 x 243
(2032 x 6172)
14.0 – 95.5
(356 - 2425)
228.7 x 83.4 x 92.5
(5809 x 2118 x 2350)
80 x 208
(2032 x 5283)
263.4 x 83.4 x 92.5
(6690 x 2118 x 2350)
80 x 243
(2032 x 6172)
(2032 x 5283)
14.0 – 95.5
(356 - 2425)
(2032 x 6172)
16.0 – 96.8
(406 - 2459)
80 x 208
80 x 243
228.7 x 83.4 x 92.5
(5809 x 2118 x 2350)
80 x 208
(2032 x 5283)
263.4 x 83.4 x 92.5
(6690 x 2118 x 2350)
80 x 243
(2032 x 6172)
(2032 x 5283)
14.0 – 95.5
(356 - 2425)
(2032 x 6172)
20.0 – 99.7
(508 - 2532)
80 x 208
80 x 243
IOMM ALS-3 27
Table 16, Physical Data, ALS 245C – ALS 270C
DATA 245C 260C 270C
CKT. 1 CKT. 2 CKT. 3 CKT. 1 CKT. 2 CKT. 3 CKT. 1 CKT. 2 CKT. 3
BASIC DATA
Unit Cap. @ ARI Conditions, tons
225.7 (790) 239.8 (839) 253.0 (886)
(kW)
Unit Operating Charge R-22, lbs (kg) 140 (63.5) 150 (68.1) 150 (68.1) 150 (68.1) 150 (68.1) 150 (68.1) 150 (68.1) 150 (68.1) 160 (72.6)
Cabinet Dimensions, L x W x H, in.
(mm)
355 x 83.4 x 94.5
(9017 x 2118 x 2400)
Unit Operating Weight, lbs. (kg) 14840 (6725) 14850 (6730) 14880 (6740)
Unit Shipping Weight, lbs (kg) 14030 (6355) 14040 (6360) 14090 (6385)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 65 (230) 80 (280) 80 (280) 80 (280) 80 (280) 80 (280) 80 (280) 80 (280) 95 (335)
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft2. (m2) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7)
Finned Height x Finned Length
ft. (mm)
80 x 208
(2032 x 5283)
80 x 208
(2032 x 5283)
160 x 104
(4064 x 2642)
Fins Per Inch x Rows Deep 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans -- Fan Diameter, in. (mm) 16 - 28 (711) 18 - 28 (711) 18 - 28 (711)
No. of Motors -- hp (kW) 16 - 1.5 (1.1) 18 - 1.5 (1.1) 18 - 1.5 (1.1) Fan & Motor RPM, 60Hz 1140 1140 1140
60 Hz Fan Tip Speed, fpm 8357 8357 8357
60 Hz Total Unit Airflow, ft3/min 144320 162360 162360
EVAPORATOR, DIRECT EXPANSION
Shell Dia. -- Length
in.(mm) - in. (mm)
20.0 – 99.7
(508 - 2532)
Evaporator R-22 Charge lbs (kg) 47 (21.3) 47 (21.3) 47 (21.3) 47 (21.3) 47 (21.3) 47 (21.3) 52 (23.6) 52 (23.6) 52 (23.6)
Water Volume, gallons (liters) 98 (371) 98 (371) 94 (356)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048) 152 (1048)
Max. Refrigerant Pressure, psi (kPa) 300 (2068) 300 (2068) 300 (2068)
ALS MODEL NUMBER
355 x 83.4 x 94.5
(9017 x 2118 x 2400)
80 x 208
(2032 x 5283)
(2032 x 5283)
20.0 – 99.7
(508 - 2532)
80 x 208
160 x 104
(4064 x 2642)
355 x 83.4 x 94.5
(9017 x 2118 x 2400)
80 x 208
(2032 x 5283)
80 x 208
(2032 x 5283)
20.0 – 99.7
(508 - 2532)
160 x 104
(4064 x 2642)
Table 17, Physical Data, ALS 275C – ALS 295C
DATA 275C 295C
CKT. 1 CKT. 2 CKT. 3 CKT. 1 CKT. 2 CKT. 3
BASIC DATA
Unit Cap. @ ARI Conditions, tons
263.1 (921) 275.3 (964)
(kW)
Unit Operating Charge R-22, lbs (kg) 150 (68.1) 160 (72.6) 160 (72.6) 160 (72.6) 160 (72.6) 160 (72.6)
Cabinet Dimensions, L x W x H, in.
(mm)
355 x 83.4 x 94.5
(9017 x 2118 x 2400)
Unit Operating Weight, lbs. (kg) 14890 (6745) 14900 (6750)
Unit Shipping Weight, lbs (kg) 14100 (6390) 14110 (6390)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons (kW) 80 (280) 95 (335) 95 (335) 95 (335) 95 (335) 95 (335)
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft2. (m2) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7) 115.6 (10.7)
Finned Height x Finned Length
ft. (mm)
80 x 208
(2032 x 5283)
80 x 208
(2032 x 5283)
Fins Per Inch x Rows Deep 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans -- Fan Diameter, in. (mm) 18 - 28 (711) 18 - 28 (711)
No. of Motors -- hp (kW) 18 - 1.5 (1.1) 18 - 1.5 (1.1)
Fan & Motor RPM, 60Hz 1140 1140
60 Hz Fan Tip Speed, fpm 8357 8357
60 Hz Total Unit Airflow, ft3/min 162360 162360
EVAPORATOR, DIRECT EXPANSION
Shell Dia. -- Length
in.(mm) - in. (mm)
20.0 – 99.7
(508 - 2532)
Evaporator R-22 Charge lbs (kg) 52 (23.6) 52 (23.6) 52 (23.6) 52 (23.6) 52 (23.6) 52 (23.6)
Water Volume, gallons (liters) 94 (356) 94 (356)
Max. Water Pressure, psi (kPa) 152 (1048) 152 (1048)
Max. Refrigerant Pressure, psi (kPa) 300 (2068) 300 (2068)
ALS MODEL NUMBER
160 x 104
(4064 x 2642)
80 x 208
(2032 x 5283)
355 x 83.4 x 94.5
(9017 x 2118 x 2400)
80 x 208
(2032 x 5283)
(4064 x 2642)
20.0 – 99.7
(508 - 2532)
160 x 104
28 IOMM ALS-3
Table 18, Physical Date, ALS 325C – ALS 365C
DATA 325C 335C 350C 365C
BASIC DATA
Unit Capacity @ ARI
Conditions, tons (kW)
Unit Operating Charge
R-22, lbs (kg)
Cabinet Dimensions,
L x W x H, in. (mm)
Operating Wt., lbs
(kg)
Shipping Wt., lbs (kg) 18320 (8300) 18330 (8305) 18330 (8305) 18340 (8310)
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity,
tons (kW)
CONDENSERS, HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft2.
Fins Per Inch x Rows 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3 16 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
Fan Tip Speed, fpm 8357 8357 8357 8357
Unit Airflow, ft3/min 198440 198440 198440 198440
EVAPORATOR, DIRECT EXPANSION
in.(mm) - in. (mm)
Water Volume, gallons
Max. Water Pressure,
Pressure, psi (kPa)
2)
(m
Finned Height x
Finned Length ft.
(mm)
Fan Qty., Dia. in.
(mm)
No. of Motors, hp
(kW)
Fan & Motor RPM 1140 1140 1140 1140
Shell Dia. Length
Evaporator R-22
Charge lbs (kg)49(22.2)49(22.2)
(liters)
psi (kPa)
Max. Refrigerant
Ckt 1 Ckt 2 Ckt 3 Ckt 4 Ckt 1 Ckt 2 Ckt 3 Ckt 4 Ckt 1 Ckt 2 Ckt 3 Ckt 4 Ckt 1 Ckt 2 Ckt 3 Ckt 4
296.5 (1038) 308.7 (1080) 322.8 (1130) 331.9 (1162)
155
155
160
160
155
(70.3)
(70.3)
(72.6)
96.3
(8.9)
80x173
(2032x
4394)
49 (22.2)
(72.6)
96.3 (8.9)
80x173
80x173
(2032x
(2032x
4394)
49
(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)49(22.2)
458.5 x 83.4 x 94.5
(11646 x 2118 x 2400)
19280 (8735) 19290 (8740) 19290 (8740) 19300 (8740)
65
(230)65(230)80(280)80(280)65(230)80(280)80(280)80(280)80(280)80(280)80(280)80(280)80(280)80(280)80(280)95(335))
96.3
96.3
(8.9)
(8.9)
80x173
80x173
(2032x
(2032x
4394)
4394)
20 – 28 (711) 20 - 28 (711) 20 – 28 (711) 20 - 28 (711)
20 - 2.0 (1.5) 20 - 2.0 (1.5) 20 - 2.0 (1.5) 20 - 2.0 (1.5)
22.0 – 100.7 (559 - 2558)
115 (435) 115 (435) 115 (435) 115 (435)
152 (1048) 152 (1048) 152 (1048) 152 (1048)
300 (2068) 300 (2068) 300 (2068) 300 (2068)
160
(70.3)
(72.6)
458.5 x 83.4 x 94.5
(11646 x 2118 x 2400)
96.3
96.3
(8.9)
(8.9)
80x173
(2032x
4394)
4394)
22.0 – 100.7 (559 - 2558)
ALS MODEL NUMBER
160
160
(72.6)
(72.6)
96.3
96.3
(8.9)
(8.9)
80x173
80x173
(2032x
(2032x
4394)
4394)
160
160
(72.6)
(72.6)
458.5 x 83.4 x 94.5
(11646 x 2118 x 2400)
96.3
96.3
(8.9)
(8.9)
80x173
80x173
(2032x
(2032x
4394)
4394)
22.0 – 100.7 (559 - 2558)
160
(72.6)
96.3
(8.9)
80x173
(2032x
4394)
160
(72.6)
96.3 (8.9)
80x173
(2032x
4394)
160
160
(72.6)
(72.6)
458.5 x 83.4 x 94.5
(11646 x 2118 x 2400)
96.3
96.3
(8.9)
(8.9)
80x173
80x173
(2032x
(2032x
4394)
4394)
22.0 – 100.7 (559 - 2558)
160
(72.6)
96.3
(8.9)
80x173
(2032x
4394)
170
(77.1)
96.3
(8.9)
80x173
(2032x
4394)
IOMM ALS-3 29
Loading...
+ 67 hidden pages