“Bulletin illustrations cover the general appearance of McQuay International products at the time of publication
and we reserve the right to make changes in design and construction at any time without notice.”
Introduction
General Description
McQuay type SeasonPak® air cooled water chillers are complete, self-contained automatic refrigerating
units that include the latest in engineering components arranged to provide a compact and efficient
unit. Each unit is completely assembled, factory wired, evacuated, charged, tested and comes complete
and ready for installation. Each unit consists of multiple air cooled condensers with integral subcooler
sections, multiple accessible semi-hermetic single-screw compressors, replaceable tube multiple circuit
shell-and-tube evaporator, and complete refrigerant piping. Liquid line components included are
manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sightglass/
moisture indicators, and electronic expansion valves. Other features include compressor heaters, an
evaporator heater for low ambient water freeze protection, automatic one time pumpdown of refrigerant
circuit upon circuit shutdown, and an advanced fully integrated microprocessor control system.
The electrical control center includes all safety and operating controls necessary for dependable automatic
operation, (the high and low pressure controls and the chiller heater thermostat are external from the electricalcontrol center.) Thermal overload protected condenser fan motors are fused in all three conductor legs
and started by their own three-pole contactors. Compressors are protected by solid state overload
protection and over temperature protection. Field installed fused disconnect offers additional
protection.
When the equipment is received, all items should be carefully checked against the bill of lading to insure
a complete shipment. All units should be carefully inspected for damage upon arrival. All shipping
damage must be reported to the carrier and a claim must be filed with the carrier. The unit’s serial plate
should be checked before unloading the unit to be sure that it agrees with the power supply available.
Physical damage to unit after acceptance is not the responsibility of McQuay International.
Note: Unit shipping and operating weights are available in the physical data tables.
Installation and Start-up
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar
with local codes and regulations, and experienced with this type of equipment.
Sharp edges and coil surfaces are a potential injury
hazard. Avoid contact with them.
Start-up by McQuayService is included on all units sold for installation within the USA and Canada.
Two week prior notification of start-up is required. The contractor should obtain a copy of the Start-up
Scheduled Request Form from the sales representative or from the nearest office of McQuayService.
Handling
Care should be taken to avoid rough handling or shock due to impact or dropping the unit. Do not
push or pull the unit from anything other than the base, and block the pushing vehicle away from the
unit to prevent damage to the sheetmetal cabinet and end frame (see Figure 1).
Never allow any part of the unit to fall during unloading or moving as this may result in serious
damage.
IM 548 / Page 3
To lift the unit, 21/2" (64 mm) diameter lifting holes are provided in the base of the unit. Spreader bars
and cables should be arranged to prevent damage to the condenser coils or unit cabinet (see Figures 2, 3,
Locate bars above unit to
clear fan grilles. Minimum
distance across unit
between cables or chains
at bars is 90 inches.
Control box end
Note: Number of fans may vary from this diagram, but lifting method remains the same.
All (8) rigging holes must be used.
(Note control box locations)
Lift only from (8) base points as shown
Unit Models ALS360 thru 380
Unit weights:
22,100 lbs. with aluminum fin coils
22,506 lbs. with copper fin coils
Location
Care should be taken in the location of the unit to provide proper airflow to the condenser, minimizing
effects on condensing pressure.
Due to the vertical condenser design of the ALS125A thru ALS380A chillers, it is recommended that
the unit is oriented so that prevailing winds blow parallel to the unit length, thus minimizing the effects
of condensing pressure on performance. If the unit is installed with no protection against prevailing winds
it is recommended that wind baffles be installed.
Using less clearances than shown in Figures 6, 7 and 8 will cause discharge air recirculation to the
condenser and could have a significant and detrimental effect on unit performance.
Service Access
Each end of the unit must be accessible after installation for periodic service work. Compressors, filterdriers, and manual liquid line shutoff valves are accessible on each side of the unit adjacent to the
control box. High pressure and low pressure transducers are mounted on the compressor. The cooler
barrel heater thermostat is located on the cooler. Compressor overloads, microprocessor, and most other
operational, safety and starting controls are located in the unit control box.
On all ALS units the condenser fans and motors can be removed from the top of the unit. The complete
fan/motor assembly can be removed for service. The fan blade and fan motor rain shield must be
removed for access to wiring terminals at the top of the motor.
Disconnect all power to the unit while servicing
condenser fan motors. Failure to do so may cause
bodily injury or death.
Page 6 / IM 548
Figure 6. Clearance requirements (125 thru 204)
5'-0" if open fence
4'-0" working
clearance per
National Electric
Code Article
110-16
Field installed
disconnect switch,
locate so as not to
block service access
to unit components
3'-9"
door
swing
2'-0" min.
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
5'-0" if open fence
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
No obstructions allowed
above unit at any height
Top View
Air flow.
No obstructions.
Recommended area required
for unit operation, air flow
and maintenance
10'-0" clearance for
evaporator
service or removal
3'-0" gate
or opening
centered on
unit width
2'-0" min.
See notes 2 & 4
concerning wall height
Wall
or fence
See note 5
Elevation
See note 6
Notes:
1. Minimum side clearance between two units is 12 feet.
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit
unless extra clearance is provided per note 4.
3. Minimum clearance on each side is a 8 feet when installed in a pit no deeper than unit height.
4. Minimum side clearance to solid wall or building taller than unit height is 8 feet provided no solid
wall above 6 feet tall is closer than 12 feet to opposite side of unit.
5. Removable post for compressor service access must not be blocked at either side of unit.
6. Do not mount electrical conduits, etc. above the side rail on either side of unit.
7. There must be no obstruction of the fan discharge.
IM 548 / Page 7
Figure 7. Clearance requirements (205 thru 280)
4'-0" working
clearance per
National Electric
Code Article 110-16
Control
Center
5'-0" if open fence
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
No obstructions.
Recommended area
required for unit
operation, air flow
and maintenance
access
8'-0" gate or access
opening centered on
corner of unit for
evaporator removal
3'-9"
door
swing
Field installed
disconnect switch,
locate so as not to
block service access to
unit components
Wall
or fence
2'-0" min.
See notes 2 & 4
concerning wall
height at unit sides
See note 5
5'-0" if open fence
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
Top View
Air Flow.
No obstructions allowed
above unit at any height
d
Side View
2'-0" min. for unit
operation.
4'-0" min. for major
component removal.
10'-0" min. for evaporator
removal (see access
opening dimension above)
See note 6
Wall or
fence
Notes:
1. Minimum side clearance between two units is 12 feet.
2. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit
unless extra clearance is provided per note 4.
3. Minimum clearance on each side is a 8 feet when installed in a pit no deeper than unit height.
4. Minimum side clearance to solid wall or building taller than unit height is 8 feet provided no solid
wall above 6 feet tall is closer than 12 feet to opposite side of unit.
5. Removable post for compressor service access must not be blocked at either side of unit.
6. Do not mount electrical conduits, etc. above the side rail on either side of unit.
7. There must be no obstruction of the fan discharge.
Page 8 / IM 548
Figure 8. Clearance requirements (300 thru 380)
4'-0" working
clearance per
National Electric
Code Article 110-16
Control Center
3'-9"
door
swing
Field installed
disconnect switch, locate so
as not to block service access
to unit components
2'-0" min.
See notes 2 & 4
concerning wall
height at unit sides
5'-0" if open fence
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
5'-0" if open fence
or 50% open wall
6'-0" if solid wall
(see note 3 for pit)
Top View
Air Flow.
No obstructions allowed
above unit at any height
d
Alternate access
opening at side
opposite water
connections
No obstructions.
Recommended area
required for unit
operation, air flow
and maintenance
access
6'-0" gate or access
opening centered on
corner of unit for
evaporator removal
2'-0" min. for unit
operation.
4'-0" min. for major
component removal.
10'-0" min. for evaporator
removal (see access
opening dimension above)
Wall
or fence
See note 6
Wall or
fence
See note 5
Side View
See note 5
Notes:
1. Minimum side clearance between two units must be 12 feet.
2. Unit must not be installed in a pit that is deeper or enclosure higher than the height of the unit
unless extra clearance is provided per notes 3 and 4.
3. Minimum clearance on each side is a 8 feet when installed in a pit no deeper than unit height.
4. Minimum side clearance to solid wall or building higher than unit height is 8 feet. In addition, the
opposite side of the unit must be at least 12 feet away from a solid wall higher than 6 feet.
5. The removable posts for compressor or evaporator service access must not be blocked at either side of
unit.
6. Do not mount electrical conduits, etc. above the side rail on either side of unit.
IM 548 / Page 9
Vibration Isolators
Vibration isolators are recommended for all roof mounted installations or wherever vibration
transmission is a consideration. Figure 9 (125 thru 204), Figure 10 (205 thru 280), Figure 12 (300 thru
340) and Figure 13 (360 thru 380) show isolator locations in relation to the unit control center. Table 2
(125 thru 204), Table 3 (205 thru 280), Table 5 (300 thru 340) and Table 6 (360 thru 380) give the
isolator loads at each location shown in Figures 9, 10, 12 and 13. Figure 11 gives dimensions that are
required to secure each McQuay isolator section to the mounting surface.
Table 1. Vibration isolators (spring)
COLOR
ALS UNIT SIZETYPEOF
125-280CP2-32 White00477929322600 (1180)
STRIPE
MCQUAY PART
NUMBER
RECOMMENDED
MAXIMUM LOAD
LBS. (KG)
Note: The same isolators are used when the chiller is
supplied with the optional copper finned condenser coils.
The spring is fully compressed at approximately 3900 lbs
A = 13" (330 mm)
B = 95" (2413 mm)
C = 215" (5461 mm) ALS125A-155A
250" (6350 mm) ALS170A-204A
3
Figure 10. Isolator locations (205 thru 280)
67 89 10
12 34 5
Control Center
A
▼
▼
B
▼
▼▼▼
A = 13" (330 mm)
B = 95" (2413 mm)
C = 177" (4496 mm)
D = 259" (6579 mm)
E = 341" (8661 mm)
Figure 11. Spring flex isolator
3"
(76.2 mm)
3
⁄8"(15.8mm)
1
⁄2" (12.7 mm) dia.
positioning pin
6" free ht.
(152.4 mm)
9
⁄16" (14.1 mm)
++
++
▼
C
D
+++
+++
▼
E
73⁄4" (196.8 mm)
91⁄4" (234.9 mm) C-C FDTN. bolt
1
⁄2" (266.70 mm)
10
9
⁄16"(14.1mm)
▼
▼
5
⁄8" (15.8 mm)
Adjust mounting so that
upper housing clears
lower housing by at least
1
⁄4" (6.3 mm) and not
more than
1
⁄2" (12.7 mm)
1
⁄4" (6.3 mm)
acoustical non-skid
neoprene pad
Figure 12. Vibration isolator (300 thru 340)
•
1
Control Center
2
•
828282
•
3
4
•
Table 4. Vibration isolators (spring)
ALS UNIT SIZETYPEOF
300A-340ACP2-32 White0477929323000 (1360)
Note:
The same isolators are used when the chiller is supplied with the optional
copper finned condenser coils. The spring is fully compressed at
approximately 3900 lbs (1769 kgs).
COLOR
STRIPE
•
5
6
•
MCQUAY PART
NUMBER
•
7
8
•
RECOMMENDED
MAXIMUM LOAD
LBS (KG)
116.7
•
9
10
•
1413
IM 548 / Page 11
Table 5. Operating weight loads (300 thru 340)
ALS
UNITWEIGHT
SIZE
300A
315A
330A
340A
Note: 1. Unit to be supported at (5) isolator mounting locations per side, 10 total, as indicated.
2. Add approximately 370 lbs (168 kgs) at each isolator location for units with optional copper finned condenser coils.
3. Unit to be level in both directions within 1⁄8 inch (3 mm) per 10 feet (3 m).
4. See dimensional drawing 073124701 for exact location of isolator support holes in base frame.
OPERATING WEIGHT LOAD AT ISOLATOR LOCATIONS, LBS (KGS) FOR UNITS WITH ALUMINUM FINNED COILS
Note: 1. Unit to be supported at (6) isolator mounting locations per side, 12 total, as indicated.
2. Add approximately 370 lbs (168 kgs) at each isolator location for units with optional copper finned condenser coils.
3. Unit to be level in both directions within 1⁄8 inch (3 mm) per 10 feet (3 m).
4. See dimensional drawing 073124801 for exact location of isolator support holes in base frame.
OPERATING WEIGHT LOAD AT ISOLATOR LOCATIONS, LBS (KGS) FOR UNITS WITH ALUMINUM FINNED COILS
123 456 78 9101112
Page 12 / IM 548
Water Piping
Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities.
They can supply the installer with the proper building and safety codes required for a safe and proper
installation.
Basically, the piping should be designed with a minimum number of bends and changes in elevation to
keep system cost down and performance up. It should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Drains at the low parts in the
system.
4. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit to aid in unit servicing.
6. A strainer or some means of removing foreign matter from the water before it enters the pump. It
should be placed far enough upstream to prevent cavitation at the pump inlet (consult pumpmanufacturer for recommendations). The use of a strainer will prolong pump life and thus keep
system performance up.
7. A strainer should also be placed in the supply water line just prior to the inlet of the evaporator.
This will aid in preventing foreign material from entering and decreasing the performance of the
evaporator.
8. The shell-and-tube cooler has a thermostat and heating cable to prevent freeze-up, due to low
ambient, down to -20°F (-28.8°C). It is suggested that the heating cable be wired to a separate 110V
supply circuit. As shipped from the factory, it is factory wired to the control circuit. Any water
piping to the unit must also be protected to prevent freezing.
9. If the unit is used as a replacement chiller on a previously existing piping system, the system should
be thoroughly flushed prior to unit installation and then regular chilled water analysis and chemical
water treatment is recommended immediately at equipment start-up.
10. The total water quantity in the system should be sufficient to prevent frequent “on-off” cycling. A
reasonable minimum quantity would allow for a complete water system turnover in not less than 15
minutes.
11. In the event glycol is added to the water system, as an afterthought for freeze protection, recognize
that the refrigerant suction pressure will be lower, cooling performance less, and water side pressure
drop greater. If the percentage of glycol is large, or if propylene is employed in lieu of ethylene
glycol, the added pressure drop and loss of performance could be substantial.
12. For operations requiring the ice mode feature, logic in MicroTech will adjust the freezestat to a
pressure equivalent to 13.5°F (7.5°C) below the leaving evaporator water temperature. However, if a
different freezestat pressure value is desired, the freezestat can be manually changed through
MicroTech. Refer to IM549 for additional information.
If a separate disconnect is used for the 110V supply
to the cooler heating cable, it should be clearly
marked so that it is not accidentally shut off during
cold seasons.
Prior to insulating the piping and filling the system, a preliminary leak check should be made.
Piping insulation should include a vapor barrier to prevent moisture condensation and possible damage
to the building structure. It is important to have the vapor barrier on the outside of the insulation to
prevent condensation within the insulation on the cold surface of the pipe.
IM 548 / Page 13
Figure 14. Typical field water piping
Inlet
Refrigerant
Connections
this end
Vent
Outlet
Drain
Valved
Pressure
Gauge
Vibration
Eliminator
Flow
Switch
Vibration
Eliminator
Balancing
Valve
Water
Strainer
Gate
Valve
Gate
Valve
Flow Switch
A water flow switch must be mounted in either the entering or leaving water line to insure that there
will be adequate water flow to the evaporator before the unit can start. This will safeguard against
slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is
interrupted to guard against evaporator freeze-up.
A flow switch is available from McQuay under ordering number 0017503300. It is a “paddle” type switch
and adaptable to any pipe size from 1" (25mm) to 8" (203mm) nominal. Certain minimum flow rates are
required to close the switch and are listed in Table 9. Installation should be as shown in Figure 15.
Electrical connections in the unit control center should be made at terminals 62 and 63. The normally
open contacts of the flow switch should be wired between these two terminals. Flow switch contact quality
must be suitable for 24 VAC, low current (16ma). Flow switch wire must be in separate conduit from
any high voltage conductors (115 VAC and higher).
Note: Water pressure differential switches are not recommended for
outdoor applications.
Flow direction
marked on switch
Flow
5" pipe dia.–
minimum after switch
1.00" NPT flow
switch connection
Te e
5" pipe dia.–
minimum before switch
Water Connections
Water piping to the cooler can be brought up through the bottom of the unit or through the side
between the vertical supports. The dimensional data on pages 20-23 gives the necessary dimensions and
locations for all piping connections.
Note: On unit size 175A thru 204A there is a diagonal brace off of a vertical support which will
interfere with the water connection if brought in from the side. This brace can be removed, but only
after the unit is in place.
Refrigerant Charge
All units are designed for use with HCFC-22 and are compatible with HCFC alternatives and are
shipped with a full operating charge. The operating charge for each unit is shown in the Physical Data
Tables on pages 17-20.
Glycol Solutions
The system glycol capacity, glycol solution flow rate, and pressure drop through the cooler may be
calculated using the following formulas and tables.
Note: The procedure below does not specify the type of glycol. Use the derate factors found in Table 10
for corrections when using Ethylene glycol and those in Table 11 for Propylene glycol.
1. Capacity — Cooling capacity is reduced from that with plain water. To find the reduced value
multiply the chiller’s water system tonnage by the capacity correction factor to find the chiller’s
capacity in the glycol system.
2. Flow — To determine flow (or delta-T) knowing delta-T
(or flow) and cap:
Glycol flow = 24 x cap (glycol) x flow factor
delta-T
3. Pressure drop — To determine pressure drop through the cooler, when using glycol, enter the water
pressure drop graph on page 13 at the actual glycol flow. Multiply the water pressure drop found
there by the PD factor to obtain corrected glycol pressure drop.
4. To determine glycol system kW, multiply the water system kW by factor called Power.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service stations)
to determine the freezing point. Obtain percent glycol from the freezing point table below. On
glycol applications it is normally recommended by the supplier that a minimum of 25% solution by
weight be used for protection against corrosion.
Do not use an automotive grade antifreeze. Industrial
grade glycols must be used. Automotive antifreeze
contains inhibitors which will cause plating on the
copper tubes within the chiller evaporator. The type
and handling of glycol used must be consistent with
local codes.
Balance the chilled water flow through the evaporator. The flow rates must fall between the minimum and
maximum values shown in Table 12. Flow rates below the minimum values shown will result in laminar
flow which will reduce efficiency, cause erratic operation of the electronic expansion valve and could
cause low temperature cutouts. On the other hand flow rates exceeding the maximum values shown can
cause erosion on the evaporator water connections and tubes.
Measure the chilled water pressure drop through the evaporator at field installed pressure taps. It is
important not to include valves or strainers in these readings.
Variable chilled water flow through the evaporator while the compressor(s) are operating is not
recommended. MicroTech control set points are based upon a constant flow and variable temperature.
Unit Capacity @ ARI Conditions, tons68.781.993.298.7
Unit Operating Charge R-22, lbs.150160180190
Cabinet Dimensions, L x W x H, in.124.5 x 83.4 x 93.3124.5 x 83.4 x 93.3159.1 x 83.4 x 93.3159.1 x 83.4 x 93.3
Unit Operating Weight, lbs.5725617568257300
Unit Shipping Weight, lbs.5500590065006900
COMPRESSORS, SCREW, SEMI-HERMETIC
Nominal Capacity, tons65809595
CONDENSERS, HIGH EFFICIENCY FIN & TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil Face Area, ft.
2
115.6115.6154.1154.1
Finned Height x Finned Length, in.160 x 104161 x 104160 x 138.7160 x 138.7
Fins Per Inch x Rows Deep16 x 316 x 316 x 316 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of Fans — Fan Diameter, in.6 - 286 - 288 - 288 - 28
No. of Motors — hp6 - 1.56 - 1.58 - 1.58 - 1.5
Fan & Motor RPM1140114011401140
Fan Tip Speed, fpm8357835783578357
Total Unit Airflow, ft3/sec54120541207216072160
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
CONDENSERS, HIGH EFFICIENCY FIN & TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil face area, sq. ft. (m2)115.6 (10.7)115.6 (10.7)115.6 (10.7)115.6 (10.7)115.6 (10.7)115.6 (10.7)115.6 (10.7)115.6 (10.7)
Finned height x finned length, in. (mm)
Fins per inch x rows deep16 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans – fan diameter, in. (mm)10 – 28 (711)10 – 28 (711)12 – 28 (711)12 – 28 (711)
No. of motors – hp (kW)10 – 1.5 (1.1)10 – 1.5 (1.1)12 – 1.5 (1.1)12 – 1.5 (1.1)
Fan & motor rpm, 601140114011401140
60 Hz fan tip speed, fpm8357835783578357
60 Hz total unit airflow, cfm9020090200108240108240
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
228.7 x 83.4 x 92.5228.7 x 83.4 x 92.5228.7 x 83.4 x 92.5228.7 x 83.4 x 92.5
(5809 x 2118 x 2350)(5809 x 2118 x 2350)(5809 x 2118 x 2350)(5809 x 2118 x 2350)
80 x 20880 x 20880 x 20880 x 20880 x 20880 x 20880 x 20880 x 208
(2032 x 5283) (2032 x 5283) (2032 x 5283) (2032 x 5283) (2032 x 5283) (2032 x 5283) (2032 x 5283) (2032 x 5283)
ALS MODEL NUMBER
Table 15. Unit sizes 175 thru 204
DATA175A185A195A204A
BASIC DATA
Unit capacity @ ARI conditions, tons (kW)80.4 (282)90.6 (318)91.2 (320)91.2 (320)94.6 (332)94.6 (332)101 (355)101 (355)
Unit operating charge R-22, lbs. (kg)160 (72.6)160 (72.6)160 (72.6)160 (72.6)170 (77.1)170 (77.1)195 (88.4)195 (88.4)
Cabinet dimensions263.4 x 83.4 x 92.5263.4 x 83.4 x 92.5263.4 x 83.4 x 92.5263.4 x 83.4 x 92.5
L x W x H, in. (mm)(6690 x 2118 x 2350)(6690 x 2118 x 2350)(6690 x 2118 x 2350)(6690 x 2118 x 2350)
Unit operating weight, lbs. (kg)11250 (5100)11250 (5100)11500 (5218)12570 (5701)
Unit shipping weight, lbs. (kg)10850 (4920)10850 (4920)11100 (5036)11980 (5433)
CONDENSERS, HIGH EFFICIENCY FIN & TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil face area, sq. ft. (m2)135.0 (12.5)135.0 (12.5)135.0 (12.5)135.0 (12.5)135.0 (12.5)135.0 (12.5)135.0 (12.5)135.0 (12.5)
Finned height x finned length, in. (mm)
Fins per inch x rows deep16 x 316 x 316 x 316 x 316 x 316 x 312 x 412 x 4
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans – fan diameter, in. (mm)14 – 28 (711)14 – 28 (711)14 – 28 (711)14 – 28 (711)
No. of motors – hp (kW)14 – 1.5 (1.1)14 – 1.5 (1.1)14 – 1.5 (1.1)14 – 2.0 (1.5)
Fan & motor rpm, 601140114011401140
60 Hz fan tip speed, fpm8357835783578357
60 Hz total unit airflow, cfm126280126280126280138908
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
Fins per inch x rows deep16 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans – fan diameter, in. (mm)16 – 28 (711)16 – 28 (711)18 – 28 (711)
No. of motors – hp (kW)16 – 1.5 (1.1)16 – 1.5 (1.1)18 – 1.5 (1.1)
Fan & motor rpm, 60114011401140
60 Hz fan tip speed, fpm835783578357
60 Hz total unit airflow, cfm144320144320162360
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
Fins per inch x rows deep16 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 316 x 3
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans – fan diameter, in. (mm)18 – 28 (711)18 – 28 (711)18 – 28 (711)
No. of motors – hp (kW)18 – 1.5 (1.1)18 – 1.5 (1.1)18 – 1.5 (1.1)
Fan & motor rpm, 60114011401140
60 Hz fan tip speed, fpm835783578357
60 Hz total unit airflow, cfm162360162360162360
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
Cabinet dimensions389.7 x 83.4 x 94.5389.7 x 83.4 x 94.5389.7 x 83.4 x 94.5389.7 x 83.4 x 94.5
L x W x H, in. (mm) (9898 x 2118 x 2400) (9898 x 2118 x 2400) (9898 x 2118 x 2400) (9898 x 2118 x 2400)
Unit operating weight, lbs. (kg)21250 (9637)21250 (9637)21320 (9669) 21320 (9669)
Unit shipping weight, lbs. (kg)20300 (9206)20300 (9206)20400 (9252)20400 (9252)
Fins per inch x rows deep12 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4 12 x 4
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans – fan diameter, in. (mm)20 – 28 (711)20 – 28 (711)20 – 28 (711)20 – 28 (711)
No. of motors – hp (kW)20 – 2.0 (1.5)20 – 2.0 (1.5)20 – 2.0 (1.5)20 – 2.0 (1.5)
Fan & motor rpm, 601140114011401140
60 Hz fan tip speed, fpm8357835783578357
60 Hz total unit airflow, cfm198440198440198440198440
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE
Cabinet dimensions459 x 83.4 x 94.5459 x 83.4 x 94.5459 x 83.4 x 94.5
L x W x H, in. (mm)(11659 x 2118 x 2400)(11659 x 2118 x 2400)(11659 x 2118 x 2400)
Unit operating weight, lbs. (kg)22920 (10395)22970 (10417)23020 (10440)
Unit shipping weight, lbs. (kg)22000 (9977)22050 (10000)22100 (10023)
CONDENSERS, HIGH EFFICIENCY FIN & TUBE TYPE WITH INTEGRAL SUBCOOLER
Coil face area, sq. ft. (m2)
Finned height x finned length, in. (mm)
Fins per inch x rows deep12 x 4 12 x 4 12 x 412 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4 12 x 4 12 x 412 x 4
CONDENSER FANS, DIRECT DRIVE PROPELLER TYPE
No. of fans– fan diameter, in. (mm)24 – 28 (711)24 – 28 (711)24 – 28 (711)
No. of motors – hp (kW)24 – 2.0 (1.5)24 – 2.0 (1.5)24 – 2.0 (1.5)
Fan & motor rpm, 60114011401140
60 Hz fan tip speed, fpm835783578357
60 Hz total unit airflow, cfm238128238128238128
EVAPORATOR, DIRECT EXPANSION, BAFFLED SHELL & THRU TUBE