McQuay" is a registered trademark of McQuay International
"Illustrations and data cover the McQuay International products at the time of publication and we reserve the right to make changes in design
1997 McQuay International
and construction at anytime without notice"
Keypad Key Functions..................49
Personal Computer Specification.51
MicroTech Menu Structure..........52
Menus for Two (2) Screw
Compressor Units..........................53
Menus for Three (3) Screw
Compressor Units..........................61
Menus for Four (4) Screw
Compressor Units..........................68
Schematics and Drawings.............77
2OM ALSMICRO
Introduction
This manual provides installation, setup and troubleshooting information for the MicroTech controller
provided on McQuay air-cooled screw compressor chillers. Please refer to the current version of
installation manual IOMM ALS for unit application information as well as water and refrigerant piping
details. All operating descriptions contained in this manual are based on the current MicroTech
controller software version at time of publication. Contact McQuay Technical Response Center at 1877-349-7782 for information on specific code versions. Chiller operating characteristics and menu
selections may vary depending on the actual software version installed.
This equipment generates, uses and can radiate radio frequency energy and if not
installed and used in accordance with the instructions manual, may cause
interference to radio communications. It has been tested and found to comply with
the limits for a class A digital device, pursuant to part 15 of the FCC rules. These
limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense. McQuay International disclaims any liability resulting from any
interference or for the correction thereof.
CAUTION
CAUTION
The McQuay MicroTech control panel contains static sensitive components. A static
discharge while handling electronic circuit boards may cause damage to the
components.
To prevent such damage during service involving board replacement, McQuay
recommends discharging any static electrical charge by touching the bare metal
inside the panel before performing any service work.
CAUTION
Excessive moisture in the control panel can cause hazardous working conditions and
improper equipment operation.
When servicing equipment during rainy weather conditions, the electrical devices
and MicroTech components housed in the main control panel must be protected.
The MicroTech controller is designed to operate within an ambient temperature range of minus 40 to
plus 185°F and a maximum relative humidity of 95% (non-condensing).
OM ALSMICRO3
General Description
The MicroTech Unit Control Panel, available on all McQuay ALS products, contains a Model 250 or
280 Microprocessor based controller, which provides all monitoring, and control functions required
for the safe, efficient operation of the unit. The operator can monitor all operating conditions by
using the panel's built in 2 line by 16 character display and keypad or by using an IBM compatible
computer running McQuay Monitor software. In addition to providing all normal operating controls,
the MicroTech controller monitors all safety devices on the unit and will shut the system down and
close a set of alarm contacts if an alarm condition develops.
Important operating conditions at the time an alarm occurs are retained in the controller's memory to
aid in troubleshooting and fault analysis. The system is protected by a password scheme, which only
allows access, by authorized personnel. The operator must enter a valid password into the panel
keypad before any setpoints may be altered.
Table 1, Unit Identification
ALSAir-Cooled Chiller with Screw Compressors
Control Panel Features
Ø Flexible control of leaving chilled water with convenient reset capability.
Ø Enhanced head pressure control on air-cooled units resulting in increased total unit SEER.
Ø Convenient, easy to read 2 line by 16-character display for plain English readout of operating
temperatures and pressures, operating modes or alarm messages.
Ø Keypad adjustment of unit safeties such as low water temperature cutout, high pressure cutout,
suction pressure cutout, and freeze protection. The operator can use the keypad to monitor
various operating conditions, setpoints or alarm messages.
Ø Security password protection against unauthorized changing of setpoints and other control
parameters.
Ø Complete plain English diagnostics to inform the operator of system warnings and alarms. All
alarms are time and date stamped so there is no guessing of when the alarm condition occurred.
In addition, the operating conditions that existed at the instant of shutdown can be recalled to
aid in isolating the cause of the problem.
Ø Soft loading feature to reduce electrical consumption and peak demand charges during chilled
water loop pulldown.
Ø Easy integration into building automation systems via separate 4-20 milliamp signals for chilled
water reset and demand limiting. McQuay's Open Protocol feature is fully supported.
Ø Flexible internal time clock for on/off scheduling.
Ø Communications capabilities for local system monitoring, changing of setpoints, trend logging,
remote reset, alarm and event detection, via IBM compatible PC. The optional modem kit
supports the same features from an off-site PC running McQuay Monitor software.
Ø Special service modes may be used to override automatic unit staging during system checkout
and service.
Unit Identification
4OM ALSMICRO
Software Identification
Version
Software
Controller software is factory installed and tested in each panel prior to shipment. The software is
identified by a program code that is printed on a small label attached to the controller. The software
version may also be displayed on the keypad/display by viewing the last menu item in the Misc.
Setup menu.
The software "version" is the 6th & 7th location of the software number. In the example, the version
is "19" and the revision to the software is "A".
Revisions are released in alphabetical order.
Number of Compressors
Controller Layout
All major MicroTech components are mounted inside the control section side of the unit's control
cabinet. The individual components are interconnected by ribbon cables, shielded multi-conductor
cables, or discrete wiring. Transformers T-2 and T-4 provide power for the system. All field wiring
must enter the control cabinet through the knockouts provided and be terminated on field wiring
terminal strips. The standard ALS keypad/display is located inside the control cabinet for protection
from the weather. See Figure 1 for typical control cabinet layout.
Figure 1, Typical control cabinet layout
Hardware
Screw Chiller
Refrigerant
Type 2 = R22
Type 3 = R134a
SC 3 2 E 19 A
Revision
E = I-P
S = SI
OM ALSMICRO5
Component Data
Microprocessor Control Board (MCB1)
The Model 250 or 280 Microprocessor Control Board contains the electronic hardware and software
required to monitor and control the unit. It receives input from the ADI Board and sends commands
to the Output Board to maintain the unit's optimum operating mode for the current conditions. Status
lights are mounted on the control board to indicate the operating condition of the microprocessor.
Figure 2, MCB1
Analog/Digital Input Board (ADI Board)
The ADI Board provides low voltage power for the temperature and pressure sensors. It also
provides electrical isolation between the Microprocessor Control Board and all 24V switch inputs.
LEDs are furnished on the board to give a visual indication of the status of all digital inputs. All
analog and digital signals from sensors, transducers and switches are received by the ADI Board and
then sent to the Microprocessor Control Board for interpretation.
Figure 3, ADI
Output Board
The Output Board contains up to 24 solid state relays, which are used to control all compressors,
condenser fans, solenoid valves and alarm annunciation.
It receives control signals from the Microprocessor Control Board through a 50-conductor ribbon
cable.
6OM ALSMICRO
Figure 4, Output board
Electric Expansion Valve Board (EXV Board)
Each EXV Board will directly control up to two electronic expansion valves. The boards may be
cascaded together for units with more than two EXV's. Control instructions for the boards are
generated by the M250 controller.
Figure 5, EXV board
Analog Output Board (AOX Board) (With Optional SpeedTrol)
The AOX Board converts control instructions from the M250's expansion bus into an analog control
signal suitable for driving a variable speed condenser fan. Each AOX Board is factory set via jumper
to provide an output signal of 0 - 10 VDC.
Figure 6, AOX board
The Keypad/Display is the primary operator interface to the unit. All operating conditions, system
alarms and setpoints can be monitored from this display and all adjustable setpoints can be modified
from this keyboard if the operator has entered a valid operator password.
OM ALSMICRO7
Figure 7, Keypad display
Sensors and Transducers
Standard Sensors
Evaporator Leaving Water Temperature
Evaporator Refrigerant Pressure, Circuit #1, 2, 3 & 4
Condenser Refrigerant Pressure, Circuit #1, 2, 3 & 4
Suction Temperature, Circuit #1, 2, 3 & 4
Liquid Line Temperature, Circuit #1, 2, 3 & 4 (Provides direct display of subcooling and superheat)
Entering Evaporator Water Temperature
Outside Ambient Air Temperature
Optional Sensor Packages
Percent Unit Amps on 2 Compressor Units (Percent total unit amperage including compressors and
condenser fans. Does not include externally powered equipment such as water pumps.)
Percent Compressor Amps on 3 Compressor Units and Percent Circuit Amps (1 & 3, 2 & 4) on 4
Compressor Units.
Thermistor Sensors
MicroTech panels use a negative temperature coefficient thermistor for temperature sensing. A
normal sensor will measure 3000 ohms at 77°F.
These transducers are selected for a specific operating range and provide an output signal, which is
proportional to the sensed pressure. The typical range for evaporator sensors is 0 to 150 psig with a
resolution of 0.1 psi. Condenser pressure sensors have a range of 0 to 450 psi and a resolution of 0.5
psi. The pressure transducers require an external 5 VDC power supply to operate that is provided by
the MicroTech controller. This connection should not be used to power any additional devices.
Figure 9, Pressure Transducer
Red Dot - Condenser
Blue Dot - Evaporator
Liquid Presence Sensor
A liquid level sensor mounted at the liquid injection port in the compressor casting determines the
presence of liquid refrigerant. Whenever the glass prism sensor tip is in contact with liquid, the
sensor output signal will be high (>7 VDC). If no liquid is detected, the output will be low (O VDC).
Figure 10, Liquid Presence Sensor
10OM ALSMICRO
Sensor Data
Sensor Locations
Analog Inputs
Analog inputs are used to read the various temperature and pressure sensors installed on the chiller as well
as any customer supplied 4-20mA reset signals. The controller's internal regulated 5 VDC and 12 VDC
supplies provide the correct operating voltage for the sensors.
Input05Transducer Power Voltage Ratio(Internal)
Input06Reset-Evaporator Water TemperatureExternal 4-20 mA Signal
Input07Demand LimitExternal 4-20 mA Signal
S08Entering Evaporator Water TemperatureEntering Chilled Water Nozzle
S09O.A.TBack of the Control Box
S11Percent Unit AmpsCT1 and Signal Converter Board
S12Suction Temperature Circuit #1Well Brazed to the Circuit #1 Suction Line
S13Suction Temperature Circuit #2Well Brazed to the Circuit #2 Suction Line
S14Liquid Line Temperature Circuit #1Well Brazed to the Circuit #1 Liquid Line
S15Liquid Line Temperature Circuit #2Well Brazed to the Circuit #2 Liquid Line
OM ALSMICRO11
DescriptionSensor Location
Figure 12, Sensor Locations - 3 Compressor Unit
Table 4, Analog Inputs - 3 Compressor Units
Sensor NumberDescription
S00Evaporator Leaving Water Temperature
S01Low Pressure Transducer Circuit #1
S02Low Pressure Transducer Circuit #2
S03High Pressure Transducer Circuit #1
S04High Pressure Transducer Circuit #2
S06Evaporator Water Temperature Reset (Field Supplied)
S07Demand Limit (Field Supplied)
S08Evaporator Entering Water Temperature
S09Outside Air Temperature
S10Percent Circuit Amps Circuit #1 (CT1)
S11Percent Circuit Amps Circuit #2 (CT2)
S12Suction Temperature Circuit #1
S13Suction Temperature Circuit #2
S14Liquid Line Temperature Circuit #1
S15Liquid Line Temperature Circuit #2
S16Low Pressure Transducer Circuit #3
S17High Pressure Transducer Circuit #3
S18Suction Temperature Circuit #3
S19Liquid Line Temperature Circuit #3
S20Discharge Temperature Circuit #1
S21Discharge Temperature Circuit #2
S22Discharge Temperature Circuit #3
S23Percent Circuit Amps Circuit #3 (CT3)
12OM ALSMICRO
Figure 13, Sensor Locations - 4 Compressor Unit
Table 5, Analog Inputs - 4 Compressor Units
Sensor NumberDescription
S00Evaporator Leaving Water Temperature
S01Low Pressure Transducer Circuit #1
S02Low Pressure Transducer Circuit #2
S03High Pressure Transducer Circuit #1
S04High Pressure Transducer Circuit #2
S06Evaporator Water Temperature Reset (Field Supplied)
S07Demand Limit (Field Supplied)
S08Evaporator Entering Water Temperature
S09Outside Air Temperature
S10Percent Circuit Amps Circuit #1 & 3 (CT1)
S11Percent Circuit Amps Circuit #2 & 4 (CT2)
S12Suction Temperature Circuit #1
S13Suction Temperature Circuit #2
S14Liquid Line Temperature Circuit #1
S15Liquid Line Temperature Circuit #2
S16Low Pressure Transducer Circuit #3
S17High Pressure Transducer Circuit #3
S18Suction Temperature Circuit #3
S19Liquid Line Temperature Circuit #3
S20Low Pressure Transducer Circuit #4
S21High Pressure Transducer Circuit #4
S22Suction Temperature Circuit #4
S23Liquid Line Temperature Circuit #4
OM ALSMICRO13
Digital Inputs
Note: All digital inputs are 24 VAC.
At 7.5 VAC to 24 VAC nominal the digital input contacts are considered closed, and the signal level is
high. Below 7.5 VAC nominal, the contacts are considered open, and the signal level is low.
Table 6, Digital Inputs - 2 Compressor Unit
NumberDescriptionLow SignalHigh Signal
0Mechanical High Pressure Switch, Circuit #1AlarmNormal
1Liquid Presence Switch, Compressor #1AlarmNormal
2Motor Protect, Compressor #1AlarmNormal
3High Liquid Pressure Drop, #1AlarmNormal
4(Reserved)--
5System Switch (S1)StopRun
6Phase Voltage MonitorAlarmNormal
7Pump Down Switch, Circuit #1NormalPumpdown
8Mechanical High Pressure Switch, Circuit #2AlarmNormal
0Alarm LED and Contact(Programmable)(Programmable)
1Chilled Water PumpStopRun
2EXV Serial Data 1
3EXV Serial Data 2
4MCR Relay. Compressor#1StopRun
5Top Solenoid, Compressor #1HoldLoad
6Bottom Right Solenoid, Compressor #1HoldLoad
7Bottom Left Solenoid, Compressor #1HoldLoad
8MCR Relay, Compressor #2StopRun
9Top Solenoid, Compressor #2HoldLoad
10Bottom Right Solenoid, Compressor #2HoldUnload
11Bottom Left Solenoid, Compressor #2HoldLoad
12Condenser Fan #1, Circuit #1 (M12)OffOn
13Condenser Fan #2, Circuit #1 (M13)OffOn
14Condenser Fan #3, Circuit #1 (M14)OffOn
15Condenser Fan #4, Circuit #1 (M15)OffOn
16Condenser Fan #1, Circuit #2 (M22)OffOn
17Condenser Fan #2, Circuit #2 (M23)OffOn
18Condenser Fan #3, Circuit #2 (M24)OffOn
19Condenser Fan #4, Circuit #2 (M25)OffOn
20Liquid Solenoid Valve, Circuit #1CloseOpen
21Liquid Solenoid Valve, Circuit #2CloseOpen
22(Spare)
23(Spare)
Table 11, Digital Outputs - 3 Compressor Unit
RelayDescription
0Alarm Circuit
1Chilled Water Pump Relay
2EXV Control
3EXV Control
4Compressor #1 Contactor
5Compressor #1 Top Solenoid Valve
6Compressor #1 Bottom Right Solenoid Valve (feed)
7Compressor #1 Bottom Left Solenoid Valve (vent)
8Compressor #2 Contactor
9Compressor #2 Top Solenoid Valve (feed)
10Compressor #2 Bottom Right Solenoid Valve (feed)
11Compressor #2 Bottom Left Solenoid Valve (vent)
12Condenser Fan Contactor M-12
13Condenser Fan Contactor M-13
14Condenser Fan Contactor M-14
15Condenser Fan Contactor M-15
16Condenser Fan Contactor M-22
17Condenser Fan Contactor M-23
18Condenser Fan Contactor M-24
19Condenser Fan Contactor M-25
20Compressor #3 Contactor
21Compressor #3 Top Solenoid Valve (feed)
22Compressor #3 Bottom Right Solenoid Valve (feed)
23Compressor #3 Bottom Left Solenoid Valve (vent)
24Condenser Fan Contactor M-32
25Condenser Fan Contactor M-33
16OM ALSMICRO
26Condenser Fan Contactor M-34
27Condenser Fan Contactor M-34
28Optional Hot Gas Bypass - SV5
29Optional Hot Gas Bypass - SV6
Table 12, Digital Outputs - 4 Compressor Unit
RelayDescription
0Alarm Circuit
1Chilled Water Pump Relay
2EXV Control
3EXV Control
4Compressor #1 Contactor
5Compressor #1 Top Solenoid Valve
6Compressor #1 Bottom Right Solenoid Valve (feed)
7Compressor #1 Bottom Left Solenoid Valve (vent)
8Compressor #2 Contactor
9Compressor #2 Top Solenoid Valve (feed)
10Compressor #2 Bottom Right Solenoid Valve (feed)
11Compressor #2 Bottom Left Solenoid Valve (vent)
12Condenser Fan Contactor M-12
13Condenser Fan Contactor M-13
14Condenser Fan Contactor M-14
15Condenser Fan Contactor M-15
16Condenser Fan Contactor M-22
17Condenser Fan Contactor M-23
18Condenser Fan Contactor M-24
19Condenser Fan Contactor M-25
20Compressor #3 Contactor
21Compressor #3 Top Solenoid Valve (feed)
22Compressor #3 Bottom Right Solenoid Valve (feed)
23Compressor #3 Bottom Left Solenoid Valve (vent)
24Condenser Fan Contactor M-32
25Condenser Fan Contactor M-33
26Condenser Fan Contactor M-34
27Condenser Fan Contactor M-35
28Optional Hot Gas Bypass - SV5
29Optional Hot Gas Bypass - SV6
30Not Used
31Compressor #4 Contactor
32Compressor #4 Top Solenoid Valve (feed)
33Compressor #4 Bottom Right Solenoid Valve (feed)
34Compressor #4 Bottom Left Solenoid Valve (vent)
35Condenser Fan Contactor M-42
36Condenser Fan Contactor M-43
37Condenser Fan Contactor M-44
38Condenser Fan Contactor M-45
OM ALSMICRO17
Installation
Controller Calibration
The control software is installed and tested by the factory prior to shipping therefore no periodic
calibration of the controller is required. All control and safety setpoints will be checked and adjusted
if necessary by the McQuayService start-up technician prior to starting the unit. The MicroTech
controller contains default setpoints that will be appropriate for most common installations.
Field Wiring
Analog sensors and transducers
All sensors and transducers required for normal chiller operation are installed and wired by the
factory. Any optional analog signals provided by the installing contractor require twisted, shielded
pair wire (Belden #8760 or equal).
Digital input signals
Remote contacts for all digital inputs such as the chilled water flow switch and the remote start/stop
switch must be dry contacts suitable for the 24 VAC control signals produced by the screw chiller
panel.
Digital outputs
Devices wired to the digital outputs typically are an optional Chilled Water Pump control relay or an
Alarm Annunciator. The MicroTech output device is a normally open solid state relay with an on
board, replaceable 5 amp fuse. The model 250 controller activates a solid state relay by sending a
"trigger" signal to the output board via the attached ribbon cable. The relay responds to the trigger
by lowering its resistance that allows current to flow through its "contacts". When the controller
removes the trigger signal, the relay's resistance becomes very high, causing the current flow to stop.
The status of all outputs is shown by individual red LEDs for ease of determining output status.
Interlock wiring
The installing contractor provides all interlock wiring to field devices such as flow switches and pump
starters. Refer to the Field Wiring Drawing as well as the unit wiring schematics and typical
application drawings at the end of this manual for details.
External alarm circuit
The MicroTech panel can activate an external alarm circuit when an alarm or pre-alarm condition is
detected. A 24 VAC voltage source is available at field wiring terminals #102 through #107 to power
an external alarm device such as a bell, light or relay. An alarm annunciator rated for a maximum load
of 1.8 Amps at 24 VAC is to be provided and wired by the installing contractor. The normal and alarm
states for the 24 VAC alarm signal are programmable by the operator. Available settings are:
115 VAC power for the control transformer is derived from the 3-phase power connection provided by
the electrical contractor.
A separate disconnect for the cooler heating tape and control circuit transformer may be supplied as
options on some installations. Wiring for these circuits is to be provided by the installing contractor
and should conform to the National Electrical Code and all applicable local building codes.
Power supplies
There are several internal power supplies used by the controller and its associated circuitry. The
regulated 5 VDC power on terminal #42 is used to support the analog inputs on the ADI Board and
18OM ALSMICRO
should not be used to operate any external devices. An unregulated 12 VDC power supply is
available on field wiring terminal #56 and an unregulated 24 VAC supply is provided at terminal #81.
Both of these may be used for powering external devices such as low current relays and lights.
Demand limit and chilled water reset signals
Separate 4-20 milliamp signals for remote chilled water reset and demand limit can be provided by the
customer and should be connected to the appropriate terminals on the field wiring strip inside the
control cabinet. The optional demand limit and chilled water reset signals are 4 to 20 milliamp DC
signals. The resistive load used to condition the milliamp input signals is a 249 ohm resistor factory
mounted on the ADI Board.
Communication ports
Communication port "A" is provided on the MicroTech controller for connection to an IBM
compatible computer for local or remote system monitoring (Belden 8762 or equivalent). The network
uses the RS232 communication standard with a maximum cable length of 50 feet. All communication
network wiring utilizes low voltage shielded twisted pair cable. See the Personal Computer
Specification section of this manual for specific hardware requirements.
Communication port "B" is used to link the unit controller into a MicroTech network using the RS485
communication standard. Refer to the field wiring in this manual for details.
Modem Kit
An optional modem kit may be installed for remote monitoring of the chiller from an off-site PC
running McQuay's Monitor software. The kit comes complete with modem, wiring harness and
installation instructions.
Remote monitoring of the MicroTech controller requires a dedicated telephone line supplied by the
equipment owner. The McQuay Monitor software package used to establish a remote connection to
the modem kit must be purchased separately.
Telephone line for remote modem access
A voice quality, direct dial telephone line is required if remote access and monitoring of the unit
controller is desired. The phone line should be terminated with a standard RJ-11 modular phone plug.
OM ALSMICRO19
Unit Sequence of Operation
The following sequence of operation is typical for McQuay ALS air-cooled chillers. The sequence
may vary depending on various options that may be installed on the chiller.
Off Conditions
With power supplied to the unit, 115 VAC power is applied through the control fuse F1 to the
compressor casing heaters, the compressor motor protector circuits, the primary of the 24V control
circuit transformer and optionally, the evaporator heater (HTR5). The 24V transformer provides power
to the MicroTech controller and related components. With 24V power applied, the controller will
check the position of the front panel System Switch (S 1). If the switch is in the "stop, position the
chiller will remain off and the display will indicate the operating mode to be OFF:SystemSw. The
controller will then check the PumpDown Switches. If any switch is in the "stop" position, that
circuit's operating mode will be displayed as OFF:RemoteComm if this operating mode is in effect. If
an alarm condition exists which prevents normal operation of both refrigerant circuits, the chiller will
be disabled and the display will indicate OFF:AllCompAlarm.
The MicroTech controller allows the operator to manually set the chiller to an off mode via the
keypad. The display indicates this operating mode with the message OFF:ManualMode.
Assuming none of the above "Off" conditions are true, the controller will examine the internal time
schedule to determine if the chiller should start. The operating mode will be OFF:TimeClock if the time
schedule indicates an "off"' time period.
Start-up
If none of the above "Off" conditions are true, the MicroTech controller will initiate a start sequence
and energize the chilled water pump output relay. The display will indicate Starting as the operating
mode. The chiller will remain in the Waiting For Flow mode until the field installed flow switch
indicates the presence of chilled water flow. If flow is not proven within 30 seconds, the alarm output
will be activated and the chiller will continue to wait for proof of chilled water flow. When chilled
water flow is re-established, the alarm will be automatically cleared.
Waiting for Load
Once flow is established the controller will sample the chilled water temperature and compare it
against the Leaving Chilled Water Setpoint, the Control Band and the Load Delay which have been
programmed into the controller's memory. If the leaving chilled water temperature is above the
Leaving Chilled Water Setpoint plus ½ the adjustable Control Band plus the Start-up Delta Temperature
Setpoint, the controller will start the lead compressor.
Start Requested
In the Start Requested Mode, the electronic expansion valve is fully closed. The MicroTech controller
will read the evaporator pressure to ensure that at least 4 psi of refrigerant pressure is present. If the
evaporator pressure is less than 4 psi the compressor will not be enabled and the display will read
"NoStart-LoEvap".
Prepurge
In order to purge the compressor of any liquid refrigerant that may be present, the starting compressor
is operated at 50% capacity while the electronic expansion valve is held fully closed. The refrigerant
circuit will continue to run in this mode until either the evaporator refrigerant pressure drops to less
than 40 psi or 60 seconds has elapsed. If the evaporator pressure does not drop to 40 psi within the
60 seconds, the compressor will continue to run and the display will read "Failed Prepurge". The
alarm is logged in the alarm buffer.
20OM ALSMICRO
Opened EXV
With the evaporator pressure less than 40 psi and the compressor still running, the electronic
expansion valve will be driven open to 300 steps. If the evaporator pressure rises above the freezestat setpoint, the chiller will advance to Cool Staging Mode. If the circuit is in Cool Staging Mode and
after 20 seconds, the evaporator pressure remains below the freeze state setpoint but is greater than 2
psi, the controller will transition to Low Ambient Start Mode.
Low Ambient Start
If the difference between the freeze stat setpoint and the evaporator refrigerant pressure is greater
than 12 psi, the low ambient start timer will be set to l80 seconds. The compressor will continue to run
for 180 seconds from the moment the expansion valve is opened in an attempt to build up the
evaporator pressure. If the difference between the freeze stat setpoint and the evaporator refrigerant
pressure is greater than 12 psi, the following calculation will be used to set the low ambient start timer:
Low Ambient timer = 360 - (Pressure Difference X 15)
If the calculated low ambient timer value is greater than 360, the compressor will be stopped, the alarm
output will be activated and the display will indicate "FailLowAmbStart".
Cool Stage
Circuit capacity at initial start will be 50%. Once the chiller has started, the MicroTech controller will
add or subtract cooling capacity to maintain the chilled water setpoint. The current cooling stage will
be displayed on the keypad/display. Automatic chiller staging may be overridden by selecting
"Manual Cooling" as the operating mode and then choosing the desired cooling stage.
"Manual Cooling" will by-pass all interstage timers. This will result in rapid
compressor stage up and possible chilled water temperature overshoot. The unit will
not unload as the chillers water temperature reaches the setpoint.
Compressor Control
Normal Compressor Staging Logic
The Compressor Staging Logic uses an adjustable control band and interstage timers to determine the
correct number of cooling stages to activate. A project-ahead temperature calculation provides stable
operation. The total number of cooling stages for each circuit is dependent upon the "number of
cooling stages" setpoint.
Operation at 25% is not allowed on compressors #3 and #4.
For compressors #1 and 2, 25% is selectable by setting MinStage = 1. Then 30 minutes is the
maximum timer setting allowed at 25%. If the evaporator Delta-T is less than 1 degree F. then 5
minutes at 25% load is allowed.
Operation at 25% load is not allowed if the outside ambient air temperature is below the minimum
setpoint of 60°F.
The Project-Ahead Calculation provides protection against an overshoot condition when the chilled
water temperature is outside the control band. During cooling mode, if the Chilled Water Temperature
is above the control band and the rate of temperature reduction is so great that in 120 seconds the
chilled water temperature will be below the control band, the controller will stage down. The ProjectAhead Calculation also moderates the controller's response to a rapid increase in leaving water
temperature.
Interstage Timer
The minimum time delay between stage up commands is set by the interstage timer setpoint
(default=120 sec). The interstage timer for stage down commands is 1/5 of the stage up timer.
Anti-Cycle Timer
Anti-cycle timers are used to protect the compressors from excessive starts and high motor winding
temperature. The anti-cycle timers are 5 minutes stop-to-start and 15 minutes start-to-start.
OM ALSMICRO23
Lead-Lag of Refrigerant Circuits
The following compressor control rules are enforced in the control software.
Ø The MicroTech controller will never turn on the lag compressor until the lead compressor is at
75% capacity or greater and additional cooling capacity is required.
Ø The MicroTech controller will not turn off the lag compressor until the lead compressor is
running at 50% capacity, the lag compressor is running at 25% capacity and a reduction in
cooling capacity is required. Three and four compressor units lag at 50% before pumpdown.
Automatic Lead-Lag
The controller provides automatic lead-lag of refrigeration circuits based on compressor operating
hours and the number of starts. The circuit with the fewest number of starts will be started first. If
circuits are operating and a stage down is required, the circuit with the most operating hours will cycle
off first.
Manual Lead-Lag
The operator may override automatic circuit selection by manually selecting the lead circuit via the
keypad or monitor.
When the setpoint equals "auto", the lead compressor is selected by the MicroTech controller based
upon which circuit has the least operating hours. Regardless of the mode selected, if the lead circuit
cannot operate due to an alarm condition or if off on cycle timers, the controller will switch to the lag
circuit.
Electronic Expansion Valve
Overview
McQuay screw compressor chillers are supplied with Sporlan SE-series electronic expansion valves.
The MicroTech controller generates valve positioning signals to maintain refrigerant circuit superheat
to within 1.5°F of the superheat setpoint. Valve positioning signals are converted to actuator step
pulses by the EXV board which in turn drives the valve's 3-phase DC stepper motor open or closed as
required. A control range of 0 steps (full closed) to 760 steps (full open) is available to provide precise
control of the valve position.
EXV Superheat Control
The electronic expansion valve position will be adjusted to maintain the refrigerant circuit's superheat
setpoint. Superheat setpoints are based on refrigerant circuit capacity. For circuit capacity of 25% to
50%, the superheat setpoint will be 8.0°F. For circuit capacity of 75% to 100%, the superheat setpoint
will be 10.0°F.
When the chiller control panel is powered up, the expansion valve will be driven closed 800 steps.
This ensures that the valve is fully closed prior to a call for cooling. When all refrigerant circuit
safeties are satisfied, the controller will initiate a start sequence. When the start sequence reaches
"open solenoid", the expansion valve will be driven open to the First Open setpoint (default=300
steps). The current suction line temperature is compared against the Suction Line Temperature
setpoint (evaporator temp plus superheat spt) to calculate superheat error (Err). The current suction
line temperature is also compared with the previous reading to calculate delta superheat error (Derr).
These two error values are used to determine the magnitude and direction of the expansion valve
positioning signal. A new valve positioning signal is calculated every 10 seconds, however, the
24OM ALSMICRO
interval at which these signals are issued to the EXV board is dependent on the magnitude of the
required positional change. If no change is required, the internal will be 60 seconds.
Forced EXV Position Change
With an increase in circuit capacity, the electronic expansion valve position will be opened by a fixed
percentage of its current position. This change will not occur if the superheat is less than 4°F below
the superheat setpoint.
With a decrease in circuit capacity, the electronic expansion valve position will be closed by a fixed
percentage of its current position.
Table 13, Staging Up
When Staging Up
FromToOpen
25%50%65%
50%75%50%
75%100%25%
Table 14, Staging Down
When Staging Down
FromToClose
100%75%18%
75%50%40%
50%25%60%
EXV Evaporator Pressure Control
The electronic expansion valve control will maintain a constant superheat for suction line temperature
up to 60°F. For suction line temperatures greater than 61°F, the expansion valve control logic will
maintain a constant evaporator temperature to avoid overloading the compressor motor. The control
point will be the Evap Temp setpoint (default=50°F) and the control method will be the standard
MicroTech Step and Wait algorithm. When the suction line temperature drops below 57°F, the
MicroTech logic will resume normal superheat control.
OM ALSMICRO25
Chilled Water Reset Options
Chilled Water Reset (Remote 4-20mA)
The controller resets the chilled water setpoint based on an external 4 to 20mA signal. At 4mA or less,
no reset will occur. At 20mA, the chilled water setpoint will be reset by an amount equal to the value
stored in the Maximum Reset setpoint. The reset schedule is linear and may be calculated using
Figure 14.
Figure 14, Chilled Water Reset Schedule
Ice Mode
The MicroTech controller has dual chilled water setpoints when ice mode is selected. With an external
reset signal of 4mA or less, the chilled water reset will be zero. If the external reset signal is greater
than 4mA, maximum reset will be in effect. The following set points should be adjusted to
accommodate the reduced ice mode system temperature and pressure.
Table 15
SetpointMonitorsDefaultIce Mode
FreezeStatLow Evap Pressure54 psig
FreezeH20Leaving Solution36°F
StpPumpDnFinal Pumpdown34 psig
Note: Once the load is satisfied in Ice Mode, restart of chiller can not occur for 12 hours.
A pressure value equivalent to the
leaving solution temperature minus 10°F
A temperature value equal to the leaving
solution temperature minus 4°F
A pressure value equal to the
FreezeStat setpoint minus 10 psi
Network Reset
The reset mode can be set to "network" if chilled water reset via communications network is desired.
The chiller controller receives a signal from the network master panel in the range of 0% to 100% of
maximum reset.
Return Water Reset
When return water is selected as the reset mode, the MicroTech controller will adjust the leaving
chilled water setpoint to maintain a constant return water temperature equal to the return water
setpoint. The return water temperature is sampled every 5 minutes and a proportional correction is
made to the leaving chilled water setpoint. The corrected leaving water setpoint is never set to a
26OM ALSMICRO
value greater than the return water setpoint and is never set to a value less than the actual leaving
chilled water setpoint.
Remote Demand Limit
The controller will limit the total number of stages based on an external 4 to 20mA signal regardless of
the amount of cooling actually required. A 4mA or less signal will enable all stages while a 20mA
signal will allow only 1 stage to operate. The effect of the reset signal may be calculated by using
Figure 15.
Network Demand Limit
Unit demand limit via network communication may be selected if desired. The chiller controller
receives a demand limit signal from the network master panel in the range of 0% to 100% with 0
equaling no limit.
Keypad Selectable Demand Limit
In the menu Demand Limit, set Manual Demand = Stage, which is below the maximum available for the
unit.
Soft Loading
The soft loading feature limits the number of cooling stages which may be energized by the controller
to prevent unnecessary electrical demand and possible over-shoot of the desired leaving water
temperature. Soft loading is typically used during morning start-up. When the controller enters the
"Cool Staging" mode of operation, the controller will start a count down timer to indicate how long the
unit has been in the cool staging mode. The maximum number of cooling stages will be limited to the
soft load setpoint until the soft load count down timer equals zero.
Max Pull Down
The controller can limit the rate at which the chilled water loop temperature is reduced. Whenever the
rate of temperature decrease exceeds the maximum pull down setpoint, no additional cooling stages
will be activated.
OM ALSMICRO27
Condenser Fan Control
Condenser Fan Staging
The first condenser fan stage will be started in conjunction with the first compressor to provide initial
head pressure control. The MicroTech controller continuously monitors the lift pressure referenced
to several head pressure control setpoints and will adjust the number of operating condenser fans as
required to maintain proper head pressure.
Head Pressure Control
For each circuit, the first stage of condenser fans will be wired in parallel with the compressor output
so that they are energized with the compressor. For chillers with optional SpeedTrol, the first
condenser fan stage will receive a control signal from the AOX board that in turn modulates the
Johnson Controls S66DC-1 to provide variable speed fan operation. Each circuit has 3 additional
digital outputs available for refrigerant head pressure control. Each output will energize an additional
bank of condenser fans with each bank consisting of 1 or 2 fans depending on the size of the unit.
Each output energizes additional heat rejection due to increased airflow across the air-cooled
condenser regardless of the number of fans. If the outdoor ambient temperature is greater than 60°F
when the unit is started, one additional condenser fan stage will be energized. If the outdoor ambient
temperature is greater than 80°F, two additional fan stages will be energized.
ALS unit EERs are maximized by not allowing the last condenser fan stage to operate when the unit
capacity is 25% and the condenser pressure is below 200 psi. The last fan stage will operate if the
condenser pressure is above 220 psi at 25% unit capacity.
Lift Pressure Calculation
The expansion valve determines the minimum acceptable lift pressure. At low tonnage capacities, a
minimum lift pressure of approximately 60 psid must be maintained. At high tonnage capacities, a
higher lift pressure must be maintained to provide proper refrigerant flow through the expansion
valve. Refer to the following table for the lift pressure values maintained at various unit capacities.
Individual head pressure setpoints are provided at 25%, 50%, and 100% circuit capacity to optimize
chiller operation. For operation at 75% capacity and greater with outdoor air temperatures less than
60°F, the minimum lift will automatically be reset downward. The maximum available reset at 100%
capacity is 40 psid while the maximum reset at 75% capacity is 20 psid.