ALS Unit Control.......................................................... 67
ALS 8-Stage Output .................................................... 68
ALS MicroTech ............................................................ 69
ALS Field Wiring .......................................................... 70
IM 5493
Introduction
This manual provides installation, setup and troubleshooting
information for the MicroTech controller provided on McQuay
screw compressor chillers. Please refer to installation manual
IM548 for unit application information as well as water and
refrigerant piping details. All operating descriptions contained in this manual are based on MicroTech controller
software version SC2-X18B, SC3XX19 and SC4XX19A. Chiller
operating characteristics and menu selections may vary with
other versions of controller software. Contact McQuayService
for software update information.
!
CAUTION
This equipment generates, uses and can radiate radio
frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for a class A digital
device, pursuant to part 15 of the FCC rules. These
limits are designed to provide reasonable protection
against harmful interference when the equipment is
operated in a commercial environment.
Operation of this equipment in a residential area is
likely to cause harmful interference in which case the
user will be required to correct the interference at his
own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof.
!
CAUTION
The McQuay MicroTech control panel contains static
sensitive components. A static discharge while handling electronic circuit boards may cause damage to
the components.
To prevent such damage during service involving
board replacement, McQuay recommends discharging
any static electrical charge by touching the bare metal
inside the panel before performing any service work.
!
CAUTION
Excessive moisture in the control panel can cause
hazardous working conditions and improper equipment operation.
When servicing equipment during rainy weather conditions, the electrical devices and MicroTech components housed in the main control panel must be
protected.
The MicroTech controller is designed to operate within an
ambient temperature range of minus 40 to plus 185°F and a
maximum relative humidity of 95% (non-condensing).
General Description
The MicroTech Unit Control Panel, available on all McQuay
ALS and PFS products, contains a Model 250 Microprocessor based controller which provides all monitoring and
control functions required for the safe, efficient operation of
the unit. The operator can monitor all operating conditions by
using the panel’s built in 2 line by 16 character display and
keypad or by using an IBM compatible computer running
McQuay Monitor software. In addition to providing all normal
operating controls, the MicroTech controller monitors all
safety devices on the unit and will shut the system down and
close a set of alarm contacts if an alarm condition develops.
Important operating conditions at the time an alarm occurs
are retained in the controller’s memory to aid in troubleshooting and fault analysis. The system is protected by a password
scheme which only allows access by authorized personnel.
A valid password must be entered into the panel keypad by
the operator before any set points may be altered.
Table 1.
Unit Identification
ALSAir Cooled Chiller with Screw Compressors
PFSWater Cooled Chiller with Screw Compressors
4IM 549
Control P anel Featur es
●
Flexible control of leaving chilled water with convenient
reset capability.
●
Enhanced head pressure control on air cooled units
resulting in increased total unit SEER.
●
Convenient, easy to read 2 line by 16 character display for
plain English readout of operating temperatures and
pressures, operating modes or alarm messages.
●
Keypad adjustment of unit safeties such as low water
temperature cutout, high pressure cutout, suction pressure cutout, and freeze protection. The operator can use
the keypad to monitor various operating conditions, set
points or alarm messages.
●
Security password protection against unauthorized changing of set points and other control parameters.
●
Complete plain English diagnostics to inform the operator
of system warnings and alarms. All alarms are time and
date stamped so there is no guessing of when the alarm
Software Identification
Controller software is factory installed and tested in each
panel prior to shipment. The software is identified by a
program code which is printed on a small label attached to
the controller. The software version may also be displayed
on the keypad/display by viewing the last menu item in the
Misc. Setup menu.
condition occurred. In addition, the operating conditions
that existed at the instant of shutdown can be recalled to
aid in isolating the cause of the problem.
●
Soft loading feature to reduce electrical consumption and
peak demand charges during chilled water loop pulldown.
●
Easy integration into building automation systems via
separate 4-20 milliamp signals for chilled water reset and
demand limiting. McQuay’s Open Protocol feature is fully
supported.
●
Flexible internal time clock for on/off scheduling.
●
Communications capabilities for local system monitoring,
changing of set points, trend logging, remote reset, alarm
and event detection, via IBM compatible PC. The optional
modem kit supports the same features from an off-site PC
running McQuay Monitor software.
●
Special service modes may be used to override automatic
unit staging during system checkout and service.
The software “version” is the 5th & 6th digit of the software
number. In the example, the version is “17” and the revision
to the software is “G”.
Revisions are released in alphabetical order.
Hardware Software
Screw Chiller
Number of Compressors
Refrigerant
Type 2 = R22
Type 3 = R134a
SC32E 19A
Revision
Version
English
IM 5495
Controller Layout
All major MicroTech components are mounted inside the
control section side of the unit’s control cabinet. The individual components are interconnected by ribbon cables,
shielded multi-conductor cables or discrete wiring. Power
for the system is provided by transformers T-2 and T-4. All
field wiring must enter the control cabinet through the
Figure 1. Typical control cabinet layout — 2 compressor unit
Keypad
F1 CB F2
NB
High voltage wireway
T4
T8
wireway
High voltage
TB3TB2
T2
T7
ADXEXV
Low voltage wireway
Modem
MDBI
Low voltage wireway
TB4TB5
Low voltage wireway
Fax alarm
option
ADI
Mech. relays
High voltage wireway
Output
board
Low voltage wireway
Low voltage wireway
GD1
GD2
RES1
SC
knockouts provided and be terminated on field wiring terminal strips. The standard ALS keypad/display is located inside
the control cabinet for protection from the weather while the
PFS Keypad/Display is accessible through the exterior of the
control cabinet. See Figure 1 for typical control cabinet layout.
FB6
M11M12M13M15 M23M25
T10
M21M22M14M24
OL5
CB5CB1
M5M1
FB8FB7
OL1
C1
FB9
PVM
FB10
C2
FB11
T1
CT1
OL2OL6
CB2
M2M6
FB5
GRD
PB1
CB6
GFP
S
GFP
R
Component Data
Microprocessor Control Board (MCB1)
The Model 250 Microprocessor Control Board contains the
electronic hardware and software required to monitor and
control the unit. It receives input from the ADI Board and
sends commands to the Output Board to maintain the unit’s
optimum operating mode for the current conditions. Status
lights are mounted on the control board to indicate the
operating condition of the microprocessor.
6IM 549
Figure 2. MCB1
Analog/Digital Input Board (ADI Board)
The ADI Board provides low voltage power for the temperature and pressure sensors. It also provides electrical isolation between the Microprocessor Control Board and all 24V
switch inputs. LEDs are furnished on the board to give a
Figure 3. ADI
Output Board
The Output Board contains up to 24 solid state relays which
are used to control all compressors, condenser fans, solenoid valves and alarm annunciation.
Figure 4. Output board
visual indication of the status of all digital inputs. All analog
and digital signals from sensors, transducers and switches
are received by the ADI Board and then sent to the Microprocessor Control Board for interpretation.
It receives control signals from the Microprocessor Con-
trol Board through a 50 conductor ribbon cable.
Electronic Expansion Valve Board (EXV Board)
Each EXV Board will directly control up to two electronic
expansion valves. The boards may be cascaded together for
Figure 5. EXV board
units with more than two EXV’s. Control instructions for the
board are generated by the M250 controller.
IM 5497
Analog Output Board (AOX Board) (With Optional SpeedTrol)
The AOX Board converts control instructions from the M250’s
expansion bus into an analog control signal suitable for
Figure 6. AOX board
driving a variable speed condenser fan. Each AOX Board is
factory set via jumper to provide an output signal of 0 - 10 VDC.
Keypad/Display
The Keypad/Display is the primary operator interface to the
unit. All operating conditions, system alarms and set points
can be monitored from this display and all adjustable set
points can be modified from this keyboard if the operator has
entered a valid operator password.
Entering Condenser Water Temperature
Leaving Condenser Water Temperature
Thermistor Sensors
MicroTech panels use a negative temperature coefficient
thermistor for temperature sensing. A normal sensor will
measure 3000 ohms at 77°F.
Liquid Line Temperature, Circuit #1, 2, 3 & 4
(Provides direct display of subcooling and superheat)
Entering Evaporator Water Temperature
Ambient O.A. Temperature
Air and water cooled units:
Percent Unit Amps on 2 Compressor Units
(Percent total unit amperage including compressors and
condenser fans. Does not include externally powered equipment such as water pumps.)
Percent Compressor Amps On 3 Compressor Units And
Percent Circuit Amps (1 & 3, 2 & 4) On 4 Compressor Units.
These transducers are selected for a specific operating
range and provide an output signal which is proportional to
the sensed pressure. The typical range for evaporator sensors is 0 to 150 psig with a resolution of 0.1 psig. Condenser
pressure sensors have a range of 0 to 450 psi and a resolution
Figure 9.
Red dot – condenser
Blue dot – evaporator
Liquid Presence Sensor
The presence of liquid refrigerant is determined by a liquid
level sensor mounted at the liquid injection port in the
compressor casting. Whenever the glass prism sensor tip is
of 0.5 psig. The pressure transducers require an external 5
VDC power supply to operate which is provided by the
MicroTech controller. This connection should
power any additional devices.
in contact with liquid, the sensor output signal will be high
(>7VAC). If no liquid is detected, the output will be low
(0VAC).
S07Demand LimitN/A
S08Evaporator Entering Water Temperature705830B-02
Condenser Entering Water Temperature
S09
(or Outside Air)
S11Total Unit Amps
S12Suction Temperature Circuit #1705830B-02
S13Suction Temperature Circuit #2705830B-01
S14Liquid Line Temperature Circuit #1705830B-01
S15Liquid Line Temperature Circuit #2705830B-02
Figure 11.
Part
Number
N/A
705830B-01
S00
Out
S08
S12
S13
S03
S02
S01S14
S15S04
Inside of
control box
on power
& control
panels
S11
S09
Back of
control box
12IM 549
Analog Inputs
Analog inputs are used to read the various temperature and
pressure sensors installed on the chiller as well as any
customer supplied 4-20mA reset signals. The controller’s
Table 4a. Analog inputs — 2 compressor units
No.DescriptionSensor Location
S00Evaporator Leaving Water TempLeaving chilled water nozzle
S01Evap Pressure Transducer, Cir #1Common cir #1 suction line
S02Evap Pressure Transducer, Cir #2Common cir #2 suction line
S03Cond Pressure Transducer, Cir #1Compressor #1 discharge cover
S04Cond Pressure Transducer, Cir #2Compressor #2 discharge cover
S05Transducer Power Voltage Ratio(Internal)
S06Reset-Evap Water TemperatureExternal 4-20 mA signal
S07Demand LimitExternal 4-20 mA signal
S08Entering Evaporator Water TempEntering chilled water nozzle
S09O.A.T. (Ent Cond Water Temp)Back of the control box
S10Condenser Leaving Water TempLeaving condenser water nozzle
S11Percent Unit AmpsSignal converter board
S12Suction Temperature Circuit #1Well brazed to the cir #1 suction line
S13Suction Temperature Circuit #2Well brazed to the cir #2 suction line
S14Liquid Line Temperature Circuit #1Well brazed to the cir #1 liquid line
S15Liquid Line Temperature Circuit #2Well brazed to the cir #1 liquid line
internal regulated 5 VDC and 12 VDC supplies provide the
correct operating voltage for the sensors.
Table 4b. Analog inputs — 3 compressor units
Sensor
Number
S00Evaporator Leaving Water Temperature
S01Low Pressure Transducer Circuit #1
S02Low Pressure Transducer Circuit #2
S03High Pressure Transducer Circuit #1
S04High Pressure Transducer Circuit #2
S06Evaporator Water Temperature Reset (Field Supplied)
S07Demand Limit (Field Supplied)
S08Evaporator Entering Water Temperature
S09Outside Air Temperature
S10Percent Circuit Amps Circuit #1
S11Percent Circuit Amps Circuit #2
S12Suction Temperature Circuit #1
S13Suction Temperature Circuit #2
S14Liquid Line Temperature Circuit #1
S15Liquid Line Temperature Circuit #2
S16Low Pressure Transducer Circuit #3
S17High Pressure Transducer Circuit #3
S18Suction Temperature Circuit #3
S19Liquid Line Temperature Circuit #3
S20Discharge Temperature Circuit #1
S21Discharge Temperature Circuit #2
S22Discharge Temperature Circuit #3
S23Percent Circuit Amps Circuit #3
Description
Table 4c. Analog inputs — 4 compressor units
Sensor
Number
S00Evaporator Leaving Water Temperature
S01Low Pressure Transducer Circuit #1
S02Low Pressure Transducer Circuit #2
S03High Pressure Transducer Circuit #1
S04High Pressure Transducer Circuit #2
S06Evaporator Water Temperature Reset (Field Supplied)
S07Demand Limit (Field Supplied)
S08Evaporator Entering Water Temperature
S09Outside Air Temperature
S10Percent Circuit Amps Circuit #1 & 3
S11Percent Circuit Amps Circuit #2 & 4
S12Suction Temperature Circuit #1
S13Suction Temperature Circuit #2
S14Liquid Line Temperature Circuit #1
S15Liquid Line Temperature Circuit #2
S16Low Pressure Transducer Circuit #3
S17High Pressure Transducer Circuit #3
S18Suction Temperature Circuit #3
S19Liquid Line Temperature Circuit #3
S20Low Pressure Transducer Circuit #4
S21High Pressure Transducer Circuit #4
S22Suction Temperature Circuit #4
S23Liquid Line Temperature Circuit #4
Description
IM 54913
Sensor Locations – 3 Scr ew Compressor Unit
Sensor Locations – 4 Scr ew Compressor Unit
14IM 549
Digital Inputs
Note: All digital inputs are 24 VAC.
At 7.5 VAC to 24 VAC the digital input contacts are
considered closed, and the signal level is high.
Below 7.5 VAC, the contacts are considered open, and
the signal level is low.
Table 5a. Digital inputs — 2 compressor unit
NumberDescriptionLo SignalHi Signal
0Mechanical High Pressure Switch, Circuit #1AlarmNormal
1Liquid Presence Switch, Compressor #1AlarmNormal
2Motor Protect, Compressor #1AlarmNormal
3Oil Level Sensor, Compressor #1AlarmNormal
4(Reserved)
5System Switch (S1)StopRun
6Phase Voltage MonitorAlarmNormal
7Pump Down Switch, Circuit #1NormalPumpdown
8Mechanical High Pressure Switch, Circuit #2AlarmNormal
0Alarm LED and Contact(Programmable)(Programmable)
1Chilled Water PumpStopRun
2EXV Serial Data 1
3EXV Serial Data 2
4MCR relay, Compr #1StopRun
5Top Solenoid, Compr #1HoldLoad
6Bottom Right Solenoid, Compr #1HoldLoad
7Bottom Left Solenoid, Compr #1HoldLoad
8MCR Relay, Compr #2StopRun
9Top Solenoid, Compr #2HoldLoad
10Bottom Right Solenoid, Compr #2HoldUnload
11Bottom Left Solenoid, Compr #2HoldLoad
12Condenser Fan #1, Circ #1 (M12)OffOn
13Condenser Fan #2, Circ #1 (M13)OffOn
14Condenser Fan #3, Circ #1 (M14)OffOn
15Condenser Fan #4, Circ #1 (M15)OffOn
16Condenser Fan #1, Circ #2 (M22)OffOn
17Condenser Fan #2, Circ #2 (M23)OffOn
18Condenser Fan #3, Circ #2 (M24)OffOn
19Condenser Fan #4, Circ #2 (M25)OffOn
20Liquid Solenoid Valve, Cir #1CloseOpen
21Liquid Solenoid Valve, Cir #2CloseOpen
22(Spare)
23(Spare)
Table 7b. Digital outputs — 3 compressor unitTable 7c. Digital outputs — 4 compressor unit
RelayDescription
0Alarm Circuit
1Chilled Water Pump Relay
2EXV Control
3EXV Control
4Compr #1 Contactor
5Compr #1 Top Solenoid Valve
6Compr #1 Bottom Right Solenoid Valve (feed)
7Compr #1 Bottom Left Solenoid Valve (vent)
8Compr #2 Contactor
9Compr #2 Top Solenoid Valve (feed)
10Compr #2 Bottom Right Solenoid Valve (feed)
11Compr #2 Bottom Left Solenoid Valve (vent)
12Condenser Fan Contactor M-12
13Condenser Fan Contactor M-13
14Condenser Fan Contactor M-14
15Condenser Fan Contactor M-15
16Condenser Fan Contactor M-22
17Condenser Fan Contactor M-23
18Condenser Fan Contactor M-24
19Condenser Fan Contactor M-25
20Compr #3 Contactor
21Compr #3 Top Solenoid Valve (feed)
22Compr #3 Bottom Right Solenoid Valve (feed)
23Compr #3 Bottom Left Solenoid Valve (vent)
24Condenser Fan Contactor M-32
25Condenser Fan Contactor M-33
26Condenser Fan Contactor M-34
27Condenser Fan Contactor M-35
28Hot Gas Bypass - SV5
29Hot Gas Bypass - SV6
RelayDescription
0Alarm Circuit
1Chilled Water Pump Relay
2EXV Control
3EXV Control
4Compr #1 Contactor
5Compr #1 Top Solenoid Valve
6Compr #1 Bottom Right Solenoid Valve (feed)
7Compr #1 Bottom Left Solenoid Valve (vent)
8Compr #2 Contactor
9Compr #2 Top Solenoid Valve (feed)
10Compr #2 Bottom Right Solenoid Valve (feed)
11Compr #2 Bottom Left Solenoid Valve (vent)
12Condenser Fan Contactor M-12
13Condenser Fan Contactor M-13
14Condenser Fan Contactor M-14
15Condenser Fan Contactor M-15
16Condenser Fan Contactor M-22
17Condenser Fan Contactor M-23
18Condenser Fan Contactor M-24
19Condenser Fan Contactor M-25
20Compr #3 Contactor
21Compr #3 Top Solenoid Valve (feed)
22Compr #3 Bottom Right Solenoid Valve (feed)
23Compr #3 Bottom Left Solenoid Valve (vent)
24Condenser Fan Contactor M-32
25Condenser Fan Contactor M-33
26Condenser Fan Contactor M-34
27Condenser Fan Contactor M-35
28Hot Gas Bypass — SV5
29Hot Gas Bypass — SV6
30Not Used
31Compr #4 Contactor
32Compr #4 Top Solenoid Valve (feed)
33Compr #4 Bottom Right Solenoid Valve (feed)
34Compr #4 Bottom Left Solenoid Valve (vent)
35Condenser Fan Contactor M-42
36Condenser Fan Contactor M-42
37Condenser Fan Contactor M-42
38Condenser Fan Contactor M-42
IM 54917
Installation
Controller Calibration
The control software is installed and tested by the factory
prior to shipping therefore no periodic calibration of the
controller is required. All control and safety set points will be
checked and adjusted if necessary by the McQuayService
Field Wiring
start-up technician prior to starting the unit. The MicroTech
controller contains default set points which will be appropriate for most common installations.
Analog sensors and transducers
All sensors and transducers required for normal chiller operation are installed and wired by the factory. Any optional
analog signals provided by the installing contractor require
twisted, shielded pair wire (Belden #8760 or equal).
Digital input signals
Remote contacts for all digital inputs such as the chilled
water flow switch and the remote start/stop switch must be
dry contacts suitable for the 24 VAC control signals produced by the screw chiller control panel.
Digital outputs
Devices wired to the digital outputs typically be an optional
Chilled Water Pump control relay or an Alarm Annunciator.
The MicroTech output device is a normally open solid state
relay with an on board, replaceable 5 amp fuse. The model
250 controller activates a solid state relay by sending a
“trigger” signal to the output board via the attached ribbon
cable. The relay responds to the trigger by lowering it’s
resistance which allows current to flow through its “contacts”. When the controller removes the trigger signal, the
relay’s resistance becomes very high, causing the current
flow to stop. The status of all outputs are shown by individual
red LEDs for ease of determining output status.
Interlock wiring
All interlock wiring to field devices such as flow switches and
pump starters is provided by the installing contractor. Refer
to the Field Wiring Drawing as well as the unit wiring schematics and typical application drawings at the end of this
manual for details.
External alarm circuit
The MicroTech panel can activate an external alarm circuit
when an alarm or pre-alarm condition is detected. A 24VAC
voltage source is available at field wiring terminal #107 to
power an external alarm device such as a bell, light or relay.
An alarm annunciator rated for a maximum load of 1.8 Amps
at 24VAC is to be provided and wired by the installing
contractor. The normal and alarm states for the 24VAC alarm
signal are programmable by the operator. Available settings are:
115VAC power for the control transformer is derived from the
3-phase power connection provided by the electrical contractor.
A separate disconnect for the cooler heating tape and
control circuit transformer may be supplied as options on
some installations. Wiring for these circuits is to be provided
by the installing contractor and should conform to the National Electrical Code and all applicable local building codes.
Power supplies
There are several internal power supplies used by the controller and its associated circuitry. The regulated 5 VDC
power on terminal #42 is used to support the analog inputs
on the ADI Board and should not be used to operate any
external devices. An unregulated 12 VDC power supply is
available on field wiring terminal #56 and an unregulated 24
VAC supply is provided at terminal #81. Both of these may be
used for powering external devices such as low current
relays and lights.
Demand limit and chilled water reset signals
Separate 4-20 milliamp signals for remote chilled water reset
and demand limit can be provided by the customer and
should be connected to the appropriate terminals on the field
wiring strip inside the control cabinet. The optional demand
limit and chilled water reset signals are 4 to 20 milliamp DC
signals. The resistive load used to condition the milliamp
input signals is a 249 ohm resistor factory mounted on the
ADI Board.
Communication ports
Communication port “A” is provided on the MicroTech controller for connection to an IBM compatible computer for
local or remote system monitoring (Belden 8762 or equivalent). The network uses the RS232 communication standard
with a maximum cable length of 50 feet. All communication
network wiring utilizes low voltage shielded twisted pair
cable. See the Personal Computer Specification section of
this manual for specific hardware requirements.
Communication port “B” is used to link the unit controller
into a MicroTech network using the RS-485 communication
standard. Refer to the field wiring drawing in this manual for
details.
18IM 549
Modem Kit
An optional modem kit may be installed for remote monitoring of the chiller from an off-site PC running McQuay’s
Monitor software. The kit comes complete with modem,
wiring harness and installation instructions.
Remote monitoring of the MicroTech controller requires a
dedicated telephone line supplied by the equipment owner.
The McQuay Monitor software package used to establish a
remote connection to the modem kit must be purchased
separately.
Unit Sequence of Operation
Telephone line for remote modem access
A voice quality, direct dial telephone line is required if remote
access and monitoring of the unit controller is desired. The
phone line should be terminated with a standard RJ-11
modular phone plug.
The following sequence of operation is typical for McQuay
ALS air cooled and PFS water cooled chillers. The sequence
Off Conditions
With power supplied to the unit, 115 VAC power is applied
through the control fuse F1 to the compressor crankcase
heaters, the compressor motor protector circuits, the primary of the 24V control circuit transformer and optionally,
the evaporator heater (HTR5). The 24V transformer provides
power to the MicroTech controller and related components.
With 24V power applied, the controller will check the position
of the front panel System Switch (S1). If the switch is in the
“stop” position the chiller will remain off and the display will
indicate the operating mode to be OFF:SystemSw. The
controller will then check the PumpDown Switches. If any
switch is in the “stop” position, that circuit’s operating mode
will be displayed as OFF:RemoteComm if this operating
Start-up
If none of the above “Off” conditions are true, the MicroTech
controller will initiate a start sequence and energize the
chilled water pump output relay. The display will indicate
Starting as the operating mode. The chiller will remain in the
Waiting For Flow mode until the field installed flow switch
Waiting for Load
Once flow is established the controller will sample the chilled
water temperature and compare it against the Leaving Chilled
Water Set point, the Control Band and the Load Delay which
have been programmed into the controller’s memory. If the
leaving chilled water temperature is above the Leaving
may vary depending on various options which may be
installed on the chiller.
mode is in effect. If an alarm condition exists which prevents
normal operation of both refrigerant circuits, the chiller will be
disabled and the display will indicate OFF:AllCompAlarm.
The MicroTech controller allows the operator to manually
set the chiller to an off mode via the keypad. The display
indicates this operating mode with the message
OFF:ManualMode.
Assuming none of the above “Off” conditions are true, the
controller will examine the internal time schedule to determine if the chiller should start. The operating mode will be
OFF:TimeClock if the time schedule indicates an “off” time
period.
indicates the presence of chilled water flow. If flow is not
proven within 30 seconds, the alarm output will be activated
and the chiller will continue to wait for proof of chilled water
flow. When chilled water flow is re-established, the alarm will
be automatically cleared.
Chilled Water Set point plus + the adjustable Control Band
plus the Start-up Delta Temperature Set point, the controller
will select the refrigerant circuit with the lowest number of
starts as the lead circuit and initiate the compressor start
sequence.
Start Requested
In the Start Requested Mode, the electronic expansion valve
is assumed to be fully closed. The MicroTech controller will
read the evaporator pressure to ensure at least 4 psi of
refrigerant pressure is present. If the evaporator pressure is
less than 4 psi the compressor will not be enabled and the
display will read “NoStart-LoEvap”.
Prepurge
In order to purge the compressor of any liquid refrigerant that
may be present, the lead compressor is operated at 50%
capacity while the electronic expansion valve is held fully
closed. The refrigerant circuit will continue to run in this
mode until either the evaporator refrigerant pressure drops
IM 54919
to less than 40 psi or 45 seconds has elapsed. If the
evaporator pressure does not drop to 40 psi within the 45
seconds, the compressor will stop and the display will read
“Failed Prepurge”. The alarm output will be activated.
Opened EXV
With the evaporator pressure less than 40 psi and the
compressor still running, the electronic expansion valve will
be driven open to 200 steps. If the evaporator pressure rises
above the freeze stat set point, the chiller will advance to
Low Ambient Start
If the difference between the freeze stat set point and the
evaporator refrigerant pressure is greater than 12 psi, the low
ambient start timer will be set to 180 seconds. The compressor will continue to run for 180 seconds from the moment the
expansion valve is opened in an attempt to build up the
evaporator pressure. If the difference between the freeze
stat set point and the evaporator refrigerant pressure is
greater than 12 psi, the following calculation will be used to
set the low ambient start timer:
Cool Stage
Circuit capacity at initial start will be 50%. Once the chiller
has started, the MicroTech controller will add or subtract
cooling capacity to maintain the chilled water set point. The
current cooling stage will be displayed on the keypad/display.
Cool Staging Mode. If the circuit is in Cool Staging Mode and
after 20 seconds, the evaporator pressure remains below the
freeze state set point but is greater than 2 psi, the controller
will transition to Low Ambient Start Mode.
Low Ambient Timer = 360 - (Pressure Difference x 15)
If the calculated low ambient timer value is greater than
360, the compressor will be stopped, the alarm output will
be activated and the display will indicate
“FailLowAmbStart”.
Automatic chiller staging may be overridden by selecting
“Manual Cooling” as the operating mode and then choosing
the desired cooling stage.
Compressor Control
Normal Compressor Staging Logic
The Compressor Staging Logic uses an adjustable control
band and interstage timers to determine the correct number
of cooling stages to activate. A project-ahead temperature
calculation provides stable operation. The total number of
cooling stages for each circuit is dependent upon the “number of cooling stages” set point.
The Project-Ahead Calculation provides protection against
an overshoot condition when the chilled water temperature
is outside the control band. During cooling mode, if the
Chilled Water Temperature is above the control band and the
rate of temperature reduction is so great that in 120 seconds
the chilled water temperature will be below the control band,
the controller will stage down. The Project-Ahead Calculation also moderates the controllers response to a rapid
increase in leaving water temperature.
Interstage Timer
The minimum time delay between stage up commands is set
by the interstage timer set point (default=210 sec). The
interstage timer for stage down commands is 1⁄3 of the stage
up timer.
Anti-Cycle Timer
Anti-cycle timers are used to protect the compressors from
excessive starts and high motor winding temperature. The
anti-cycle timers are 5 minutes stop-to-start and 15 minutes
start-to-start.
Compressor Heater Control
Compressor Heater Control for PFS units is based on the
suction line superheat. If the superheat reading drops below
IM 54921
3°F, the heater will be energized. The heater will be deenergized when the superheat rises above 8°F.
Lead-Lag of Refrigerant Circuits
The following compressor control rules are enforced in the
control software.
●
The MicroTech controller will never turn on the lag compressor until the lead compressor is at 75% capacity or
greater and additional cooling capacity is required.
Automatic Lead-Lag
The controller provides automatic lead-lag of refrigeration
circuits based on compressor operating hours and the number of starts. The circuit with the fewest number of starts will
Manual Lead-Lag
The operator may override automatic circuit selection by
manually selecting the lead circuit via the keypad.
When the set point equals “auto”, the lead compressor is
selected by the MicroTech controller based upon which
Electronic Expansion Valve
Overview
McQuay screw compressor chillers are supplied with Sporlan
SE-series electronic expansion valves. The MicroTech controller generates valve positioning signals to maintain refrigerant circuit superheat to within 1.5°F of the superheat set
point. Valve positioning signals are converted to actuator
●
The Micro Tech controller will not turn off the lag compres-
sor until the lead compressor is running at 50% capacity,
the lag compressor is running at 25% capacity and a
reduction in cooling capacity is required.
be started first. If circuits are operating and a stage down is
required, the circuit with the most operating hours will cycle
off first.
circuit has the least operating hours. Regardless of the mode
selected, if the lead circuit cannot operate due to an alarm
condition or if off on cycle timers, the controller will switch to
the lag circuit.
step pulses by the EXV board which in turn drive the valve’s
3-phase DC stepper motor open or closed as required. A
control range of 0 steps (full closed) to 760 steps (full open)
is available to provide precise control of the valve position.
EXV Superheat Control
The electronic expansion valve position will be adjusted to
maintain the refrigerant circuit’s superheat set point. Superheat set points are based on refrigerant circuit capacity. For
circuit capacity of 25% to 50%, the superheat set point will
be 8.0°F. For circuit capacity of 75% to 100%, the superheat
set point will be 10.0°F.
When the chiller control panel is powered up, the expansion valve will be driven closed 800 steps. This ensures that
the valve is fully closed prior to a call for cooling. When all
refrigerant circuit safeties are satisfied, the controller will
initiate a start sequence. When the start sequence reaches
“open solenoid”, the expansion valve will be driven open to
the First Open set point (default=200 steps). The current
Forced EXV Position Change
With an increase in circuit capacity, the electronic expansion
valve position will be opened by a fixed percentage of its
current position. This change will not occur if the superheat
is less than 4°F below the superheat set point.
Table 8a.
When Staging Up
FromToOpen
25%50%65%
50%75%50%
75%100%25%
suction line temperature is compared against the Suction
Line Temperature set point (evaporator temp plus superheat
spt) to calculate superheat error (Err). The current suction line
temperature is also compared with the previous reading to
calculate delta superheat error (DErr). These two error values
are used to determine the magnitude and direction of the
expansion valve positioning signal. A new valve positioning
signal is calculated every 10 seconds, however, the interval
at which these signals are issued to the EXV board is
dependent on the magnitude of the required positional
change. If no change is required, the interval will be 60
seconds.
With a decrease in circuit capacity, the electronic expansion
valve position will be closed by a fixed percentage of its
current position.
Table 8b.
When Staging Down
FromToClose
100%75%18%
75%50%40%
50%25%60%
22IM 549
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.