Settings And Adjustments.................................................................. 12
System Checkout and Troubleshooting .............................................. 13
Zone Terminal User's Guide.............................................................. 16
Zone Terminal Glossary.................................................................... 21
"McQuay" is a registered trademarks of McQuay International
"Illustrations and information cover McQuay International products at the time of publication and we reserve the right to make
changes in design and construction at anytime without notice"
2IOM UNT33
1996 McQuay International
Introduction
This controller is the standard controller on ALR "C", "D" or “E” vintage and WHR "D" or "E"
vintage packaged chillers where control of leaving water temperature is desired. On these units with
the controller factory installed, the control is pre-set and calibrated and should not need any
adjustment other than the control setpoint.
For further information on the AS-UNT33n-1 Microprocessor based leaving water controller and
accessories contact McQuay International for specification sheets for each individual control.
The controller and sensor covered in this Installation and Operating Manual is also available as a
substitute replacement for earlier ALR and WHR units.
General Description
The AS-UNT33n-1 Microprocessor-based Leaving Water Control is designed to control multiple
capacity steps of cooling from a single sensor.
The AS-UNT33n-1 operation is based on an adjustable Setpoint and Control Band as shown in the
OPERATION section of this document. If the leaving chilled water temperature begins to rise to the
desired Setpoint plus Control Band/2 (upper limit) , Cooling Stage 1 brings on the first stage of cooling.
Additional stages of cooling will follow as long as the leaving water temperature remains above the
upper limit of the Control Band. As the leaving water temperature begins to drop to Setpoint minus
Control Band/2 (lower limit), cooling stages will begin to de-energize.
There will be no energizing or de-energizing of cooling stages as long as the leaving water temperature
is between the upper and lower limits of the Control Band.
As a rule, anytime the leaving water temperature is above the upper limit of the Control Band, stages
will be energized, and anytime the leaving water temperature falls below the lower limit of the Control
Band, stages will be de-energized.
At the initial start of the unit a time delay will occur. There is a 60 second Interstage On Delay
between stages. Each stage incorporates minimum on and off timers with a maximum cycle rate of six
cycles per hour.
CAUTION-Offering this control
device is not intended to imply that
rapid cycling of compressors is
condoned. If an application
produces rapid cycling, the control
and/or the application must be
reviewed and altered to prevent
compressor failure.
Table 1, Standard Control Characteristics
DESCRIPTION
AS-UNT-33n-1
Setpoint Range
Control Band Range
Interstage On Delay Between Stages60 seconds
Minimum Off Time (each stage)5 minutes
Minimum On Time (each stage)60 seconds
Soft Start During Start-up
10°F to 60°F (-12°C to
+15°C) Adjustable
0°F to 10°F (0°C to 6°C)
Adjustable
50% command over 5
minutes
SETTING
Table 2, Controller Specific Characteristics
CONTROLLER
DESCRIPTION
AS-UNT330-14 or 6Honeywell
AS-UNT332-18Honeywell
AS-UNT334-14 or 6Johnson Controls
AS-UNT336-18Johnson Controls
IOM UNT333
NUMBER OF
STAGES
LEAVING WATER
SENSOR
Specifications
Electrical Ratings:
Input voltage and frequency (terminals
24 VAC–COMMON) 20 to 30 VAC at 50/60 Hz
(50 Hz requires download.)
Power Consumption:
25 VA at 24 VAC and 50/60 Hz
Input Signal:
Honeywell sensor—positive temperature
coefficient of 4.8 ohms/Degree F; resistance of
3484 ohms at 77°F.
Johnson Controls sensor—positive temperature
Number of Stages Selection:
Refer to Table 5, Figure 1 for stage selection
Temperature Ranges:
Ambient: -40°F to +150°F.
Humidity Rating:
5 to 90% RH non-condensing.
Leaving Water Sensor:
The Honeywell C7173Al017, Honeywell
C7170A1010, or Johnson Controls TE-6300-300
senses Leaving Water Temperature on control
terminals AI3 and AI3 COM.
coefficient of 3 ohms/Degree F; resistance of 1000
ohms at 70°F.
.
Model No.
Johnson TE-6313P-10703123011Outdoor Air SensorUsed for reset of Leaving Water Setpoint.
Johnson TE-6300-3000703124011Immersion Sensor (30 ft. cord)Senses Leaving or Return Water Temperature.
Sensor Well0474415061Immersion WellUsed with TE-6300-300.
Johnson TE-6410S2000
Johnson AS-ZTU3301
Honeywell
C7173A1017
Honeywell
C7170A1010
Honeywell 121371A0484424031Copper Immersion WellUsed with C7173A1017 or C7170A1010.
Honeywell 121371E0484424041Stainless Steel Immersion WellUsed with C7173A1017 or C7170A1010.
Johnson AS-KIT100-01Resistor Test KitUsed for field diagnostics.
McQuay
Part No.
070312801
0703127011Zone Terminal
0484424051Immersion Sensor (30 ft. cord)Sensing of Leaving Water Temperature.
0484424021Immersion Sensor (10 ft. cord)Sensing of Leaving Water Temperature.
Quantit
y
depends on
# of zones
DescriptionApplication
Zone Temperature SensorUsed for zone temperature reset.
Used for monitoring and local control of
designated points.
4IOM UNT33
Installation
AS-UNT330-1
STANDARDS COMPLIANCE
The UNT Controller complies with the following standards:
* CSA C22.2 No. 205* UL 916* IEEE 472
* IEEE 446* VDE 0871 Class B* IEEE 587 Category A
* IEEE 518* FCC Part 15, Subpart A, Cl. J * NEMA ICS 2, Part 2-230
All wiring must comply with local codes and ordinances:
1. Disconnect power before making connections to avoid electrical shock or equipment damage.
2.Check ratings given in the specification and on the product to make sure the controller fits the application.
3.Choose a location for the AS-UNT33n-1 controller that is not exposed to the weather and where controls,
connections, and the zone bus phone jack are accessible.
4.Mount the controller with three No. 8 screws through the mounting holes in the base. (See Figure 2.)
5.Install immersion well and sensor bulb in the Leaving Chilled Water piping as instructed by the installation manual
for the unit being controlled.
6.Connect 24 VAC to terminals marked 24 VAC and COM. CAUTION: Never spark the 24 V power leads to check for
power.
CAUTION:Do not run low-voltage wiring in the same conduit as line-voltage wiring (30 VAC or above) or
wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
7.Wire the compressor and capacity controls steps to the individual controller relay terminals as shown in the unit
wiring diagram.
8. Adjust SW1 and SW2 on AI2 for the appropriate number of cooling stages. The AS-UNT330-1/AS-UNT334-1 is
factory set for 6 stages by Johnson Controls. The AS-UNT332-1/AS-UNT336-1 is factory set for 8 stages.
Table 5, Dipswitch Settings
Dipswitch Settings
Factory
Set
Stage
Select
Factory Set
AS-UNT33n-1AI 1AI 2AI 3AI 4AI 5AI 6
AS-UNT330-1SW210 V••••
AS-UNT334-12 V••
4 stage
SW1T•
(set by others)V•••••
AS-UNT330-1SW210 V••••
AS-UNT334-12 V••
Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to AI-1 and AI-CM.
Figure 3, Wiring Diagram
Note: See Additional Features on page 11 for explanation.
DEMAND LIMIT*
(1)
(2)
0-10 VDC
LEAVING
WATER SENSOR
SHUTDOWN*
COMP LEAD/LAG*
ICE MODE*
FLOW INTERLOCK
Indicates
*
optional
feature.
24VAC
(+)
AI CM
25
26
528
529
(-)
AI CM
AI CM
AI CM
AI CM
AI CM
+15VDC
24VAC
24VAC
24VAC
24VAC
24 C OM Z
VAC B U S
P5P6
AI1
AI2
AI3
AI4
AI5
AI6
+15VDC
BI1
BI2
BI3
BI4
ANALOG INPUTS BINARY IN
DS
REF N 2 N 2
18
28
512/518
519
- +
P4
(1)
(2) Field connections must be made between TB3-18 and BI-4 for unit to operate.
NNotes:
1. Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to Al-1 and Al-CM.
2. Field connections must be made between TB3-18 and Bl-4 for unit to operate.
3. If a time clock is desired, it should be installed between 24 VAC and Bl1. The time clock switch should be installed as follows:
Open to Run and Close to Stop.
Figure 4, Stage Relay Configuration
M cQuay
C ONT ROL BA ND
S ET PO I NT
RE SET
RECIPROCATING
CHILLER CONT ROL
COO L 6
COO L 5
COO L 4
COO L 3
COO L 2
COO L 1
C
B
A
CB
A
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
Stage Relays
COM
NC
NO
Note: Refer to Unit Wiring
Diagram for Stage
Wiring.
IOM UNT337
Table 6, Wiring Location Cross Reference
Lead #
512TB3-18 to TB3-29(4,6,8 Stages)Not Needed (See Note 1 and 2)
518TB3-29 to "TR""TB3-18 to 24 VAC
519"TR""Common
522Ground"Not Needed
524"7""Not Needed (See Note 3)
525TB3-23 to TB3-24"Not Needed
526"6""Not Needed (See Note 3)
527"P" to "P1""Not Needed or Zone Terminal Adjust
528"T""
529"T1""
400 OHM Resister"7" to "8"4 Stages
600 OHM Resister"7" to "8"6 StagesSee Table 5
800 OHM Resister"7" to "8"8 Stages
Note 1: To install Flow Switch Contacts, connect between TB3-18 and UNT BI-4.
Note 2: To install Time Clock Contacts, connect between TB3-18 and UNT BI-1.
Note 3: The options are as follows. (Option A is standard; options B, C, and D require field download. See "Features Requiring
Configuration and/or Field Adjustment" section for more information):
A. The standard is Demand Limit Input. 0-10VDC signal is required. Connect leads to AI-1 and AI-CM on the
controller.
B. Johnson Controls Outdoor Air Sensor if Outdoor Air Reset is used.
C. Johnson Controls Zone Temperature Sensor if Zone Temperature Reset is used.
D. Johnson Controls Return Water Sensor if Return Water Reset is used.
Honeywell (H/W)
W7100G
Stages
AI-3 (JCI or H/W Leaving Water Sensor. See
Johnson Controls (JCI)
AS-UNT33n-1
appropriate sensor section)
AI-CM (JCI or H/W Leaving Water Sensor.
See appropriate sensor section)
8IOM UNT33
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.