McQuay ALR C Installation Manual

Installation and Operating Manual
Leaving Water Controller, AS-UNT33n-1
Applied to ALR C/D/E and WHR D/E
IOM UNT33n
Group: Chiller Date: May 2000 Supersedes: IM 552
© 1996 McQuay International
Table of Contents
Introduction........................................................................................3
Specifications.....................................................................................4
Installation..........................................................................................5
Dimensional Data................................................................................6
Electrical Data.....................................................................................7
Operation...........................................................................................9
Additional Features............................................................................11
Settings And Adjustments.................................................................. 12
System Checkout and Troubleshooting .............................................. 13
Zone Terminal User's Guide.............................................................. 16
Zone Terminal Glossary.................................................................... 21
"McQuay" is a registered trademarks of McQuay International
"Illustrations and information cover McQuay International products at the time of publication and we reserve the right to make
changes in design and construction at anytime without notice"
1996 McQuay International
Introduction
This controller is the standard controller on ALR "C", "D" or “E” vintage and WHR "D" or "E" vintage packaged chillers where control of leaving water temperature is desired. On these units with the controller factory installed, the control is pre-set and calibrated and should not need any adjustment other than the control setpoint.
For further information on the AS-UNT33n-1 Microprocessor based leaving water controller and accessories contact McQuay International for specification sheets for each individual control.
The controller and sensor covered in this Installation and Operating Manual is also available as a substitute replacement for earlier ALR and WHR units.
General Description
The AS-UNT33n-1 Microprocessor-based Leaving Water Control is designed to control multiple capacity steps of cooling from a single sensor.
The AS-UNT33n-1 operation is based on an adjustable Setpoint and Control Band as shown in the OPERATION section of this document. If the leaving chilled water temperature begins to rise to the desired Setpoint plus Control Band/2 (upper limit) , Cooling Stage 1 brings on the first stage of cooling. Additional stages of cooling will follow as long as the leaving water temperature remains above the upper limit of the Control Band. As the leaving water temperature begins to drop to Setpoint minus Control Band/2 (lower limit), cooling stages will begin to de-energize.
There will be no energizing or de-energizing of cooling stages as long as the leaving water temperature is between the upper and lower limits of the Control Band.
As a rule, anytime the leaving water temperature is above the upper limit of the Control Band, stages will be energized, and anytime the leaving water temperature falls below the lower limit of the Control Band, stages will be de-energized.
At the initial start of the unit a time delay will occur. There is a 60 second Interstage On Delay between stages. Each stage incorporates minimum on and off timers with a maximum cycle rate of six cycles per hour.
CAUTION-Offering this control device is not intended to imply that rapid cycling of compressors is condoned. If an application produces rapid cycling, the control and/or the application must be reviewed and altered to prevent compressor failure.
Table 1, Standard Control Characteristics
DESCRIPTION
AS-UNT-33n-1
Setpoint Range
Control Band Range
Interstage On Delay Between Stages 60 seconds Minimum Off Time (each stage) 5 minutes Minimum On Time (each stage) 60 seconds
Soft Start During Start-up
10°F to 60°F (-12°C to +15°C) Adjustable 0°F to 10°F (0°C to 6°C) Adjustable
50% command over 5 minutes
SETTING
Table 2, Controller Specific Characteristics
CONTROLLER
DESCRIPTION
AS-UNT330-1 4 or 6 Honeywell AS-UNT332-1 8 Honeywell AS-UNT334-1 4 or 6 Johnson Controls AS-UNT336-1 8 Johnson Controls
NUMBER OF
STAGES
LEAVING WATER
SENSOR
Specifications
Electrical Ratings:
Input voltage and frequency (terminals 24 VAC–COMMON) 20 to 30 VAC at 50/60 Hz (50 Hz requires download.) Power Consumption: 25 VA at 24 VAC and 50/60 Hz Input Signal: Honeywell sensor—positive temperature coefficient of 4.8 ohms/Degree F; resistance of 3484 ohms at 77°F. Johnson Controls sensor—positive temperature
Number of Stages Selection:
Refer to Table 5, Figure 1 for stage selection
Temperature Ranges:
Ambient: -40°F to +150°F.
Humidity Rating:
5 to 90% RH non-condensing.
Leaving Water Sensor:
The Honeywell C7173Al017, Honeywell C7170A1010, or Johnson Controls TE-6300-300 senses Leaving Water Temperature on control
terminals AI3 and AI3 COM. coefficient of 3 ohms/Degree F; resistance of 1000 ohms at 70°F. .
Table 3, Contact Rating
CONTACT VOLTAGE (V) INRUSH (VA) RUNNING (VA)
N.O. 24 240 60 N.C. 24 75 30 N.O. 120/240 750 75 N.C. 120/240 240 40
Table 4, Accessories
Model No. Johnson TE-6313P-1 070312301 1 Outdoor Air Sensor Used for reset of Leaving Water Setpoint.
Johnson TE-6300-300 070312401 1 Immersion Sensor (30 ft. cord) Senses Leaving or Return Water Temperature. Sensor Well 047441506 1 Immersion Well Used with TE-6300-300. Johnson TE-6410S­2000 Johnson AS-ZTU330­1 Honeywell C7173A1017 Honeywell C7170A1010 Honeywell 121371A 048442403 1 Copper Immersion Well Used with C7173A1017 or C7170A1010. Honeywell 121371E 048442404 1 Stainless Steel Immersion Well Used with C7173A1017 or C7170A1010. Johnson AS-KIT100-0 1 Resistor Test Kit Used for field diagnostics.
McQuay
Part No.
070312801
070312701 1 Zone Terminal
048442405 1 Immersion Sensor (30 ft. cord) Sensing of Leaving Water Temperature.
048442402 1 Immersion Sensor (10 ft. cord) Sensing of Leaving Water Temperature.
Quantit
y
depends on
# of zones
Description Application
Zone Temperature Sensor Used for zone temperature reset.
Used for monitoring and local control of designated points.
Installation
AS-UNT330-1
STANDARDS COMPLIANCE
The UNT Controller complies with the following standards: * CSA C22.2 No. 205* UL 916 * IEEE 472 * IEEE 446 * VDE 0871 Class B * IEEE 587 Category A * IEEE 518 * FCC Part 15, Subpart A, Cl. J * NEMA ICS 2, Part 2-230 All wiring must comply with local codes and ordinances:
1. Disconnect power before making connections to avoid electrical shock or equipment damage.
2. Check ratings given in the specification and on the product to make sure the controller fits the application.
3. Choose a location for the AS-UNT33n-1 controller that is not exposed to the weather and where controls, connections, and the zone bus phone jack are accessible.
4. Mount the controller with three No. 8 screws through the mounting holes in the base. (See Figure 2.)
5. Install immersion well and sensor bulb in the Leaving Chilled Water piping as instructed by the installation manual for the unit being controlled.
6. Connect 24 VAC to terminals marked 24 VAC and COM. CAUTION: Never spark the 24 V power leads to check for power.
CAUTION: Do not run low-voltage wiring in the same conduit as line-voltage wiring (30 VAC or above) or wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
7. Wire the compressor and capacity controls steps to the individual controller relay terminals as shown in the unit wiring diagram.
8. Adjust SW1 and SW2 on AI2 for the appropriate number of cooling stages. The AS-UNT330-1/AS-UNT334-1 is factory set for 6 stages by Johnson Controls. The AS-UNT332-1/AS-UNT336-1 is factory set for 8 stages.
Table 5, Dipswitch Settings
Dipswitch Settings
Factory
Set
Stage
Select
Factory Set
AS-UNT33n-1 AI 1 AI 2 AI 3 AI 4 AI 5 AI 6
AS-UNT330-1 SW2 10 V AS-UNT334-1 2 V
4 stage
SW1 T (set by others) V AS-UNT330-1 SW2 10 V AS-UNT334-1 2 V
6 Stage
SW1 T
(Factory Set) V AS-UNT332-1 SW2 10 V AS-UNT336-1 2 V
8 Stage
SW1 T
(Factory Set) V
Figure 1, Analog Input Switches
C D V 5 1 +
A N A LO G I N PU TS
B IN A R Y IN
COM
PW R
I N
2 4V
B IN A R Y CO M
A C
BIN ARY INA NAL OGIN PUTS
BINA RY OUT PUT S
ANAL O G I N PU TS
1 2 3 4 5 6 1 2 3 4
A N A L OG I N P U TS
CO MM ON
B IN A RY OU TP U T 1 2 3 4 5 6 7 8
2 4V A C TO L OA D S
Dimensional Data
Figure 2, Dimensional Data
These relays are for the 7th and 8th stages.
COOL 8
COOL 7
7.78
8.95
SW2 SW1
ANALOG INPUTS BINARY IN
1.245.80
C B
A C B A
BINARY OUTPUTS
McQuay
RECIPROCATING CHI LLER CONTROL
SETPOIN T
RESET
CON TROL BAND
COOL 6
COOL 5
COOL 4
COOL 3
COOL 2
COOL 1
C B A C B A
C B A C B A
C B A C B
A
8.95
9.23
0.89
14.90
= mounting holes
5.16
2.23
0.74
2.17
2.77
0.25
Electrical Data
Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to AI-1 and AI-CM.
Figure 3, Wiring Diagram
Note: See Additional Features on page 11 for explanation.
DEMAND LIMIT*
(1)
(2)
0-10 VDC
LEAVING
WATER SENSOR
SHUTDOWN*
COMP LEAD/LAG*
ICE MODE*
FLOW INTERLOCK
Indicates
*
optional feature.
24VAC
(+)
AI CM
25
26
528
529
(-)
AI CM AI CM AI CM AI CM
AI CM
+15VDC
24VAC 24VAC
24VAC 24VAC
24 C OM Z
VAC B U S
P5 P6
AI1 AI2 AI3
AI4 AI5
AI6
+15VDC
BI1 BI2
BI3 BI4
ANALOG INPUTS BINARY IN
DS
REF N 2 N 2
18
28
512/518
519
- +
P4
(1) (2) Field connections must be made between TB3-18 and BI-4 for unit to operate.
NNotes:
1. Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to Al-1 and Al-CM.
2. Field connections must be made between TB3-18 and Bl-4 for unit to operate.
3. If a time clock is desired, it should be installed between 24 VAC and Bl1. The time clock switch should be installed as follows: Open to Run and Close to Stop.
Figure 4, Stage Relay Configuration
M cQuay
C ONT ROL BA ND
S ET PO I NT
RE SET
RECIPROCATING CHILLER CONT ROL
COO L 6
COO L 5
COO L 4
COO L 3
COO L 2
COO L 1
C
B
A
C B
A
C
B
A
C
B A
C
B A
C
B A
C
B
A
Stage Relays
COM
NC
NO
Note: Refer to Unit Wiring
Diagram for Stage Wiring.
Table 6, Wiring Location Cross Reference
Lead #
512 TB3-18 to TB3-29 (4,6,8 Stages) Not Needed (See Note 1 and 2) 518 TB3-29 to "TR" " TB3-18 to 24 VAC 519 "TR" " Common 522 Ground " Not Needed 524 "7" " Not Needed (See Note 3) 525 TB3-23 to TB3-24 " Not Needed 526 "6" " Not Needed (See Note 3) 527 "P" to "P1" " Not Needed or Zone Terminal Adjust
528 "T" "
529 "T1" "
400 OHM Resister "7" to "8" 4 Stages 600 OHM Resister "7" to "8" 6 Stages See Table 5 800 OHM Resister "7" to "8" 8 Stages
523 Ground 8 Stages Not Needed 535 "1" " Not Needed 536 "2" " Not Needed 537 "3" " Not Needed 538 "4" " Not Needed 539 "5" " Not Needed
Note 1: To install Flow Switch Contacts, connect between TB3-18 and UNT BI-4. Note 2: To install Time Clock Contacts, connect between TB3-18 and UNT BI-1. Note 3: The options are as follows. (Option A is standard; options B, C, and D require field download. See "Features Requiring
Configuration and/or Field Adjustment" section for more information): A. The standard is Demand Limit Input. 0-10VDC signal is required. Connect leads to AI-1 and AI-CM on the
controller.
B. Johnson Controls Outdoor Air Sensor if Outdoor Air Reset is used. C. Johnson Controls Zone Temperature Sensor if Zone Temperature Reset is used. D. Johnson Controls Return Water Sensor if Return Water Reset is used.
Honeywell (H/W)
W7100G
Stages
AI-3 (JCI or H/W Leaving Water Sensor. See
Johnson Controls (JCI)
AS-UNT33n-1
appropriate sensor section)
AI-CM (JCI or H/W Leaving Water Sensor.
See appropriate sensor section)
Loading...
+ 16 hidden pages