McQuay ALR-060A Installation Manual

BULLETIN NO. IM 172
JULY 1978
INSTALLATION AND
MAINTENANCE DATA
PACKAGED AIR COOLED WATER CHILLER
TYPE ALR-060 THRU 130A
GROUP
McQuay-PERFEX
@

TABLE OF CONTENTS

INTRODUCTION
NOMENCLATURE
PRE-INSTALLATION
INSTALLATION
HANDLING LOCATION
ACCESS FOR SERVICING
VIBRATION ISOLATORS
WATER PIPING
PIPING PRACTICES CHILLED WATER THERMOSTAT FLOW SWITCH
PIPING CONNECTIONS FIELD WIRING START-UP AND SHUT-DOWN ELECTRICAL
CONTROL CENTER
CONTROL PANEL LAYOUTS
ELECTRICAL LEGEND
SEQUENCE OF OPERATION
PUMPDOWN
MAJOR COMPONENT LOCATIONS
WIRING SCHEMATICS
DESCRIPTION OF UNIT CONTROLS UNIT MAINTENANCE
GENERAL
REFRIGERANT SIGHT GLASS
FILTER-DRIERS
LIQUID LINE SOLENOID VALVE THERMOSTATIC EXPANSION VALVE EVAPORATOR CONDENSERS COMPRESSOR WEAR AND LEAD-LAG COMPRESSOR OIL LEVEL FAN BELT TENSION FAN SHAFT BEARINGS FAN MOTOR BEARINGS ELECTRICAL TERMINALS
IN WARRANTY RETURN MATERIAL PROCEDURE
TROUBLE SHOOTING CHART
...................................................
...................................................
...............................................
...............................................
...................................................
...................................................
...................................
....................................
.............................................
...........................................
...............................
................................................
......................................
.............................................
...................................
...............................................
......................................
...................................
.......................................
................................
CYCLE
..........................................
...............................
....................................
.........................
.........................................
.................................................
.................................
...........................................
..............................
.........................
...........................................
..............................................
............................
....................................
........................................
......................................
......................................
....................................
......................................
.-.8-l
..11-13 ..13-16 ..16-4 7
.-.16-l
..18-19
..21-3 9
..40-4 7 ..47-5 1
..48-4 9 ..49-5 0
.......................
. . .
..4- 7
. .
..5- 6 ..6- 7
0
.
..8- 9
.
..10
7 ..17 ..18
..19
..2 0
..4 7 ..4 7 ..4 7 ..4 8
..5 0 ..5 0 ..5 0
..5 1
..5 1 ..5 1 ..5 1 ..5 1 ..5 2
Page 2

INTRODUCTION

McQuay type ALR Seasonpak air cooled water chillers are complete self contained automatic refrigerating units that include the latest in
engineered components arranged to provide a compact and efficient
unit.
evacuation,
installation. with integral subcooler sections, pressors,
and complete refrigerant piping.
included are:
filter driers, dicators, valves.
evaporator heater for chilled water freeze protection, recycling
pumpdown during "on" or "off" seasons,
alternate the compressor starting sequence, of compressors.
The electrical control center includes all safety and operating con-
trols necessary for dependable automatic operation.
and fan motor is fused in all three conductor legs and started by its own three pole contactor.
Each unit is completely assembled and factory wired before
charging and testing,
Each unit consists of: twin air cooled condensers
replaceable tube dual circuit shell and tube evaporator,
manual liquid line
liquid line solenoid valves, sight glass/moisture in-
and double diaphragm hydraulic element thermal expansion
Other features include:
and comes complete and ready for
multiple accessible hermetic com-
Liquid line components that are
shutoff
compressor crankcase heaters, an
compressor lead lag switch to
valves,
and sequenced starting
replaceable core
Each compressor

NOMENCLATURE

RECIPROCATING COMPRESSORS LOW POWER CONSUMING AIR COOLED CONDENSER
11
-It
ALR- 085AD
DUAL REFRIGERANT CIRCUITS DESIGN VINTAGE
NOMINAL CAPACITY (TONS)

PRE-INSTALLATION

Inspection
When the equipment is received,
against the bill of lading to insure a complete shipment. should be carefully inspected for damage upon arrival.
damage should be reported to the carrier and a claim should be filed.
The unit serial plate should be checked before unloading the unit to
be sure that it agrees with the power supply available.
all items should be carefully checked
All units
All shipping
Page 3

Handling

INSTALLATION

Care should betaken to avoid rough handling or shock due to ping the unit.
Do not push or pull the unit from anything other
drop-
than the base,and block the pushing vehicle away from the unit to prevent damageto the sheet metal cabinet.
FIGURE 1
SUGGESTED PUSHING ARRANGEMENT
7
GOOD PUSHING ARRANGEMENT
CABINET DAMAGE UNLIKELY
(See Figure 1).
BLOCKING
POOR PUSHING ARRANGEMENT
CABINET DAMAGE LIKELY
Never allow any part of the unit to fall during unloading or moving as this may result in serious damage.
To lift the unit,
2%"
diameter lifting holes are
provided in the base of the unit. Spreader bars and cables should bearranged to prevent damage to the condenser coils or unit cabinet.
FIGURE 2
SPRE
SUGGESTED LIFTING ARRANGEMENT
:ADER
(See Figure 2).
Page 4
‘LMUST
(NOTE CONTROL
USE THESE RIGGING HOLES
Box
LOCATION)

Location

Due to the vertical condenser design, it is recommended that certain precautions be taken before installation to orient the unit so that prevailing winds blow parallel to the unit length thus minimizinq effects on condensing pressure. the unit in this manner, a wind
If it is not practical to orient
deflecting fence should be
consi-
dered.
It is also necessary to provide the unit for service access and 60 in.
(1
fan diameter) should be allowed on each side of the unit
for condenser air inlet and compressor removal on units 060
adequate clearance on all sides of
satisfactory performance.
At least
&
065.
If parallel units are installed side by side, 120 in. should be allowed between units.
This will prevent excessive condensing temperatures and enhance system performance and operating economy. Clearance for service access should be at least 78 in. at the control center end for compressor removal on units 075 thru 130 and sufficient at the end opposite the control center for evapora­tor tube replacement.
FIGURE 3
60” MINIMUM-CLEARANCE
These clearances are illustrated in Figure 3.
CLEARANCE AROUND UNIT
FOR AIR INLET
11
60” MINIMUM CLEARANCE
FOR AIR INLET AND COMPRESSOR
REMOVAL ON ALR-060,065
NOTE: Minimum vertical clearance above unit should be
4
h
10 feet
I I

Access for Servicing

Each end of the unit must be accessible after installation for peri-
odic service work.
Compressors,
filter driers,
and manual liquid
line shutoff valves are accessible from the control center end of the
unit through removable access panels on unit sizes 075 thru 130 and
hinged side access doors on unit sizes 060 and 065. safety, They are protected by a keylocked,
tains internal "dead front" nel from high operational controls.
located just below the main control center.
and starting controls are located in the unit control center.
weatherproof enclosure which con-
doors for protection of service person-
voltage starting controls while servicing low voltage
All resettable or adjustable controls are
There is one resettable
All operational,
control enclosure on each side of the unit and each encl.osure contains
controls for compressors on that side of the unit.
Capped connections
for field service gauges are also located inside these enclosures. In addition,
each of these enclosures are removable to improve access to
compressors for field replacement.
Page 5
The condenser fans, motors,
and drives are accessible through a walk-
in, keylocked access door on units ALR-075 thru 130 or a removable access panel on units ALR-060 and located at the end of the unit opposite the control center.
065.
The access door or panel is
Expan-
sion valves are accessible from the same access door on unit sizes 075 thru 130 and from side access doors at the control center end
on unit sizes 060 and 065.
An internal fan guard is located below the condenser fans and drives on units 075 thru 130.
This guard must be removed to service the
fan drives but must always be re-installed when service work is com-
plete.
On unit sizes 060 and 065,
an interlock switch kills power
to condenser fans whenever the access panel is removed for service
work on fans or drives.
CAUTION:
Disconnect all power to the unit while
servicing condenser fan drives.
Vibration Isolators Vibration isolators are recommended for all roof mounted installa-
tions or wherever vibration transmission is a consideration.
lists spring isolators for all ALR unit sizes.
tor locations in relation to the unit control center.
Figure 4 shows isola-
Figure 5 gives
Table 1
dimensions that are required to secure each McQuay isolator selection to the mounting surface.
For applications which require a higher degree of isolation efficiency, Table 2 shows the isolator loads at each location shown in Figure 4, and the maximum loads for each McQuay selection.
TABLE 1
I
ALR LOCATIONS LOCATIONS UNIT SIZE
060A 065A 075A 2 164048-28 085A 2 16404B-28 105A
IIOA
120A 130A
I
l&4
t
ORDERING
NUMBER NUMBER
(877-j
216404B-27 216404B-27 216404B-27
2164048.31
216404B.31 216404B.32 216404B-32 216404B.32 216404B

VIBRATION ISOLATORS

SPRING ISOLATORS
Z&5
I
ORDERING
(877-j
216404B~27
216404B-28 216404B-28 216404B-31
2164048-31
32
__-
I
I
LOCATIONS
3&6
ORDERING
NUMBER
(877-i
216404B-28 216404B-28 216404B-27
216404B-27
216404B-31
216404B.31 216404B-32 216404B-32
I
1
_
TABLE 2
Page 6
ISOLATOR LOADS

WATER PIPING

Piping Practices Due to the variety of piping practices, it is advisable to follow
the recommendations of local authorities.
They can supply the in-
staller with the proper building and safety codes required for a safe and proper installation.
Basically,
the piping should be designed with a minimum number of
bends and changes in elevation to keep system cost down and perfor-
mance up.
1.
Vibration eliminators to reduce vibration and noise transmission
It should contain:
to the building.
Shutoff valves to isolate the unit from the piping system dur-
2. ing unit servicing.
Manual or automatic air vent valves at the high points of the
3.
system.
4.
Some means of maintaining adequate system water pressure (e.g.; expansion tank or regulating valve).
5.
Temperature and pressure indicators located at the unit to aid in unit servicing.
6.
A strainer or some means of removing foreign matter from the
water before it enters the pump.
It should be placed far enough
upstream to prevent cavitation at the pump inlet (consult pump
manufacturer for recommendations).
The use of a strainer will
prolong pump life and thus keep system performance up.
Prior to insulating the piping and filling the system, a preliminary leak check should be made. Piping insulation should include a vapor barrier to prevent moisture condensation and possible damage to the building structure.
It is
important to have the vapor barrier on the outside of the insulation to prevent condensation within the insulation on the cold surface of the pipe.

Chilled Water Thermostat

The chilled water thermostat is mounted inside the unit control cen­ter.
On models ALR-075A through
130A,
the thermostat sensor is fac-
tory mounted in the return water connection of the evaporator. On models
water line as shown in Figure 6.
ALR-060A
and
065A,,
the sensor must be installed in the return
The thermostat sensor should be in-
sulated after installation.
FIGURE 6
THERMOSTAT SENSOR
REDUCING BUSHING
THERMOSTAT SENSOR INSTALLATION
RETURN WATER CONNECTION OF EVAPORATOR
7
1
LRETURN WATER LINE
Page 8
CAUTION:

Flow Switch

Thermostats have maximum operating temper­ature limits of:
ALR-060 and 065
140F on return water for standard ca-
pacity reduction.
125F on return water for optional ca­pacity reduction. ALR-075 throuqh 130
125F on return water for standard ca­pacity reduction.
250F on return water for optional ca-
pacity reduction.
Temperatures exceeding these limits may dam­age the controls.
WATER FLOW SWITCH
A ing water line to insure that there will be adequate water cooling load to the evaporator before the unit can start. safeguard against slugging the compressors on start up.
MUST
BE MOUNTED in either the entering
or
leav-
flow and
This will
It also
serves to shut down the unit in the event that water flow is inter­rupted to guard against evaporator freeze up.
A flow switch is available from McQuay under ordering number 860-
175033x-00.
size from to close the switch and are listed in Table 3.
It is a "paddle"
1"
to 6" nominal.
type switch and adaptable to any pipe
Certain minimum flow rates are required
Installation
should be as shown in Figure 7.
TABLE
3
FLOW SWITCH MINIMUM FLOW RATES
NOMINAL
PIPE SIZE
(INCHES)
1
1
l/4
1
l/2
2
2112
3
4
5 6
MINIMUM REQUIRED
FLOW TO ACTIVATE
SWITCH
6.00
9.80
12.70
18.80
24.30
30.00
39.70
58.70
79.20
(GPM)
FIGURE 7
+ FLOW4
DIA.
-
5 PIPE
AFTER SWITCH
MINIMUM 5 PIPE DIA.-MINIMUM
FLOW DIRECTION
/
J’
MARKED ON SWITCH
1.00
NPT FLOW SWITCH
CONNECTION
BEFORE SWITCH
Electrical connections in the unit control center should be made at terminals 11 and 12. should be wired between these two terminals.
_
normally closed contacts on the switch that could be used for an in-
The normally open contacts of the flow switch
There is also a set of
dicator light or an alarm to indicate when a "no flow" condition
exists.
Page 9
Piping Connections Water piping connections at the unit vary in size and style depen-
ding on the baffle option ordered.
These connection variations are
shown in the table with Figure 8.
Piping through the unit cabinet can be through the end or bottom of
the unit as the application dictates.
hole centers for piping through the end of the unit.
Pilot holes locate
Figure 8 gives
the proper
the necessary dimensions for either piping method.
FIGURE 8
1
ALR
r\,
Y
Y
060AD 192 80.0 73.8 36.1 16.3 33.7 24.0 065AD 192 80.0 73.8 36.1 16.3 33.7 24.0 075AD 228 98.8 92.5 47.0 8.0 76.0 30.0 91.4
*COOLER CONNECTIONS
Y
-
Ail
connections
couplings by others.
DIMENSIONS (INCHES)
are NPS steel
Page 10
tib.1
pipe.
4
thru
6-inch
pipe
connections are
furnished
COOLER
with grooves for
I
victaulic
Field Wirinq

FIELD WIRING

Wiring should be done in accordance with
all applicable codes and
ordinances.
Warranty
-­Warranty is voided if wiring is not in accordance with specifica-
tions.
An
open fuse indicates a short, ground, or overload.
Before
replacing a fuse or restarting a compressor or fan motor, the trou­ble must be found and corrected.
Copper wire is required for all power lead terminations at the unit
while either aluminum or copper can be used for all other wiring.
All unit sizes are set up as standard for separate 115 volt power
supply circuits for the control circuit and cooler heater.
The con-
trol circuit only or both the control circuit and cooler heater can
be powered off of the main unit power supply if the optional control
circuit transformer is ordered.
have the unit
the main unit
out defeating
cooler heater on a separate disconnect switch from
power supply so that the unit may be shut down with-
the freeze protection provided by the cooler heater.
It may be desirable, however, to
TABLE 4
Wire sizing ampacities and recommended power lead wire sizes
Notes: 1. Separate terminals provide for the field connection of a
separate
2. Wire sizing amps are equal to 125% of the Nameplate Amps of the largest motor plus 100% of the Nameplate Amps of all other loads in the circuit (the control circuit is not included). To include the control circuit, add 10 amps to 208 or 230 volt units and 5 amps to 460 volt units. Recommended power lead wire and maximum fuse sizes are not affected.
3. Recommended power lead wire sizes for three con­ductors per conduit are based on 100% conductor
115/60/1
power supply to the control circuit.
ampacity at 86 F ambient for no more than 3 conductors per conduit. Wire sizes for six conductors per conduit are based on 80% of the above mentioned conductor ampacity in accordance with NEC. Voltage drop has not been included, therefore, it is recommended that power
leads be kept short. All terminal block connections must
be made with copper wire.
4.
The unit power terminal block has two lugs per phase. Single or parallel conductors per phase may be used for power hookup as listed under “Recommended Power
Lead Wire Size.” The cooler heater cable current draw is 3.5 amps.
5.
Page 11
A standard feature on all ALR units is
COPSTM(Controlled
Override of
Pump Shutdown),a system for interlocking the field supplied chilled
water pump into the chiller control system.
A relay (R-19) is wired
into the unit control circuit so that a time clock and/or ambient thermostat can be connected to a pair of terminals (6 and 11) in­side the unit control center. starter.
Once the pump starts,
The time clock can energize a pump
the flow switch and/or pump inter-
lock will close and energize that part of the control circuit that
will allow the unit to start.
This feature makes it possible to start the chilled water pump and the chiller simultaneously only when cooling is required.
For re-
cycling pumpdown without a demand for cooling, a pair of relays
(energized by low pressure controls) are also wired into this cir-
cuit to start the pump,
close the flow switch and pump down the
unit.
NOTE:
If a time clock,
ambient thermostat and/or re-
mote on-off switch are not used, terminals 6
and 11 must be jumpered together before the
unit will start.
Figure 9 shows typical field wiring that is required for unit in­stallation.
FIGURE 9
TYPICAL FIELD WIRING DIAGRAM
Standard is separate power supply circuits for controls and cooler heater. These circuits may be combined by installing jumpers from terminals 1 NOTE C: Pump starter, contacts of R9, terminals 7 & 8 are limited to 250 volts maximum.
CUSTOMER CONNECTION FIELD WIRING FACTORY WIRING BLACK WIRING (LINE) WHITE WIRING (NEUTRAL)
flow switch and/or starter interlock.
-
9 & 10 - 20.
R10,
and
R19
between

START - UP AND SHUT DOWN

Pre Start-Up
1.
With all electric disconnects open,
check all screw or lug type electrical connections to be sure they are tight for good elec­trical contact. fore shipment,
Although all factory connections are tight be-
some loosening may have resulted from shipping
vibration,
2.
Inspect all water piping for flow direction and correct connec­tions at the evaporator.
Page 13
3.
4.
5.
6.
7.
8.
9.
10.
Open all water flow valves and start the chilled water pump. Check all piping for leaks and vent the air from the evaporator as well as from the system piping. system piping to obtain clean,
orator circuit.
Check to see that the thermostat water temperature sensor is in­stalled in the return water line (return to chiller).
075A through ALR-060A tion, and the sensor should be secured in the well with the retaining
clip provided. On ALR-075A through 130A units with optional cap-
acity reduction,the sensor is installed directly into the return water line i.e.;
Check the compressor oil level. Prior to start-up, the oil lev­el should cover at least
Remove the (8) compressor shipping blocks that are attached to the
compressor rails and the base of the unit. not have shipping blocks. Check the voltage of the unit power supply and see that it is within the balance must be with _+ 2%. Check the unit power supply wiring for adequate ampacity and a minimum insulation temperature rating of 75C. Verify that all mechanical and electrical inspections have been
completed per local codes.
See that all auxiliary control equipment is operative and that an adequate cooling load is available forinitial start up.
and 065A units with standard or optional capacity reduc-
the sensor well should be full of heat conducting
13OA
+
10%
units with standard capacity reduction, or
no well or heat conducting compound is required.
l/2
tolerance that is allowed.
non-corrosive water in the evap-
of the oil sight glass.
Flush the evaporator and
On
ALR-
compound
The ALR 060 and 065 do
Phase voltage un-
_
Start-Up
1.
Open the compressor suction and discharge back seated.
2.
Open the manual liquid line shutoff valve at the outlet of the subcooler.
Check to see that pumpdown switches
3. pumpdown"position and the control stop switch
"on
"
position.
Adjust the dial on temperature controller
4.
chilled water temperature.
Throw the main power and control circuit disconnects to the "on"
5. position.
CAUTION:
6.
Allow the crankcase heaters to operate for at least 8 hours prior to start-up.
Start the auxiliary equipment for the installation by turning
7. on the time clock,
if the unit and chilled water pump are electrically interlocked
by using the COPS
8.
Start the system by moving pumpdown switches
"auto.
9.
After system performance has stabilized, it
"Compressorized Equipment Warranty Form" (form no. 206036A) be
completed to obtain full warranty benefits.
with the unit and after completion should be returned to McQuay's
Service Department through your sales representative.
pumpdown" position.
Always replace valve seal caps.
(PSl &
Most relays and terminals in the unit control center are hot with control circuit
ambient thermostat and/or remote on/off switch
method discussed in "Field Wiring".
disconnect
shutoff valves until
PS2) are in the
(Sl)
is in the
TCl
to the desired
Sl
and the
on.
(PSl &
is
necessary that the
This form is shipped
PS2) to the
"man.
Page 14
Temporary Shut-Down
Move pumpdown switches
After
pump.
It is important that the compressors pump down before the water flow
to the unit is interrupted to avoid freeze up in the evaporator.
Start-Up After Temporary Shut-Down
1.
2.
3.
Extended Shut-Down
1.
2.
3.
4.
5.
6.
7.
the compressors have pumped down, turn off the chilled water
NOTE:
Start the chilled water pump.
With control stop switch
down switches Observe the unit operation for a short time to be sure that the compressors do not cut out on low oil pressure.
Close the manual liquid line shutoff valves. After the compressors have pumped down, turn off the chilled water pump.
Turn off all power to the unit and to the chilled water pump. Move the control stop switch
Close the compressor suction and discharge valves.
Tag all opened disconnect switches to warn against start up be-
fore opening the compressor suction and discharge valves. Drain all water from the unit evaporator and chilled water pip-
ing if the unit is to be shut down during winter.
With the unit left in this condition, it is
capable of recycling pumpdown operation. To
defeat this mode of operation, simply move
control stop switch
(PSl &
(PSl
& PS2) to the "man. pumpdown" position.
(Sl)
to the "off" position.
(Sl)
in the
PS2) to the "auto. pumpdown" position.
(Sl)
to the "off" position.
"on"
position, move pump-
Start-Up After Extended Shut-Down
1.
Inspect all auxiliary equipment to see that it is in satisfac-
tory operating condition.
2.
Remove all debris that has collected on the surface of the con­denser coils.
3.
Open the compressor suction and discharge valves.
4.
Open the manual liquid line shut off valves.
c
J.
Check to see that pumpdown switches ual pumpdown position.
6.
Turn on the electric power to the unit and other parts of the
system.
7.
Allow the crankcase heaters to operate for at least 8 hours prior to start-up.
8.
Start the chilled water pump and purge the water piping as well
as the evaporator in the unit.
9.
Check to see that the control stop switch tion.
CAUTION:
Most relays and terminals in the unit
control center are hot with control circuit disconnect on.
(PSl
and PS2) are in the man-
(S1)is
Sl
in the
and the
"on"
posi-
Page 15
10.
Start the unit by moving
pumpdown
switches
(PSl
& PS2) to the
"auto.pumpdown" position.
11.
After running the unit for a short time check the oil level in
each compressor crankcase and check for flashing in the refrig­erant sight glass (see "Maintenance" on Page 47).

ELECTRICAL

Control Center

All electrical controls are enclosed in a weatherproof control cen-
ter with keylocked, hinged access doors.
posed of three separate enclosures.
The upper enclosure is the largest and contains all of the 208, 230, fan motor starting controls.
Also included in this enclosure but
partitioned separately are the exposed terminal type
ational controls.
A "dead front"
cover over the high voltage sec-
The control center is com-
or 460 volt compressor and
-
115 volt oper-
tion protects service personnel from high voltage starting controls
while servicing low voltage operational controls.
Below the upper enclosure are two smaller, contain 115 volt adjustable or resettable controls.
separate enclosures that
There is one of
these enclosures on each side of the unit, and each contains controls
for the compressors on that side.
Power supply conduits are intended to come into the bottom of the upper enclosure and between the two lower enclosures.
mended that the unit disconnect switch be mounted away but
Figure 10 recommends unit mounting arrangements if the disconnect
it is recom­from the unit
must be unit mounted.
Page 16
Loading...
+ 36 hidden pages