Inc. 13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, Mn. 55440
@
TABLE OF CONTENTS
INTRODUCTION
NOMENCLATURE
PRE-INSTALLATION
INSTALLATION
HANDLING
LOCATION
ACCESS FOR SERVICING
VIBRATION ISOLATORS
WATER PIPING
PIPING PRACTICES
CHILLED WATER THERMOSTAT
FLOW SWITCH
PIPING CONNECTIONS
FIELD WIRING
START-UP AND SHUT-DOWN
ELECTRICAL
CONTROL CENTER
CONTROL PANEL LAYOUTS
ELECTRICAL LEGEND
SEQUENCE OF OPERATION
PUMPDOWN
MAJOR COMPONENT LOCATIONS
WIRING SCHEMATICS
DESCRIPTION OF UNIT CONTROLS
UNIT MAINTENANCE
GENERAL
REFRIGERANT SIGHT GLASS
FILTER-DRIERS
LIQUID LINE SOLENOID VALVE
THERMOSTATIC EXPANSION VALVE
EVAPORATOR
CONDENSERS
COMPRESSOR WEAR AND LEAD-LAG
COMPRESSOR OIL LEVEL
FAN BELT TENSION
FAN SHAFT BEARINGS
FAN MOTOR BEARINGS
ELECTRICAL TERMINALS
McQuay type ALR Seasonpak air cooled water chillers are complete self
contained automatic refrigerating units that include the latest in
engineered components arranged to provide a compact and efficient
unit.
evacuation,
installation.
with integral subcooler sections,
pressors,
and complete refrigerant piping.
included are:
filter driers,
dicators,
valves.
evaporator heater for chilled water freeze protection, recycling
pumpdown during "on" or "off" seasons,
alternate the compressor starting sequence,
of compressors.
The electrical control center includes all safety and operating con-
trols necessary for dependable automatic operation.
and fan motor is fused in all three conductor legs and started by its
own three pole contactor.
Each unit is completely assembled and factory wired before
charging and testing,
Each unit consists of: twin air cooled condensers
replaceable tube dual circuit shell and tube evaporator,
manual liquid line
liquid line solenoid valves, sight glass/moisture in-
and double diaphragm hydraulic element thermal expansion
Other features include:
and comes complete and ready for
multiple accessible hermetic com-
Liquid line components that are
shutoff
compressor crankcase heaters, an
compressor lead lag switch to
valves,
and sequenced starting
replaceable core
Each compressor
NOMENCLATURE
RECIPROCATING COMPRESSORS
LOW POWER CONSUMING
AIR COOLED CONDENSER
11
-It
ALR- 085AD
DUAL REFRIGERANT CIRCUITS
DESIGN VINTAGE
NOMINAL CAPACITY (TONS)
PRE-INSTALLATION
Inspection
When the equipment is received,
against the bill of lading to insure a complete shipment.
should be carefully inspected for damage upon arrival.
damage should be reported to the carrier and a claim should be filed.
The unit serial plate should be checked before unloading the unit to
be sure that it agrees with the power supply available.
all items should be carefully checked
All units
All shipping
Page 3
Handling
INSTALLATION
Care should betaken to avoid rough handling or shock due to
ping the unit.
Do not push or pull the unit from anything other
drop-
than the base,and block the pushing vehicle away from the unit to
prevent damageto the sheet metal cabinet.
FIGURE 1
SUGGESTED PUSHING ARRANGEMENT
7
GOOD PUSHING ARRANGEMENT
CABINET DAMAGE UNLIKELY
(See Figure 1).
BLOCKING
POOR PUSHING ARRANGEMENT
CABINET DAMAGE LIKELY
Never allow any part of the unit to fall during unloading or moving
as this may result in serious damage.
To lift the unit,
2%"
diameter lifting holes are
provided in the base
of the unit. Spreader bars and cables should bearranged to prevent
damage to the condenser coils or unit cabinet.
FIGURE 2
SPRE
SUGGESTED LIFTING ARRANGEMENT
:ADER
(See Figure 2).
Page 4
‘LMUST
(NOTE CONTROL
USE THESE RIGGING HOLES
Box
LOCATION)
Location
Due to the vertical condenser design, it is recommended that certain
precautions be taken before installation to orient the unit so that
prevailing winds blow parallel to the unit length thus minimizinq
effects on condensing pressure.
the unit in this manner, a wind
If it is not practical to orient
deflecting fence should be
consi-
dered.
It is also necessary to provide
the unit for service access and
60 in.
(1
fan diameter) should be allowed on each side of the unit
for condenser air inlet and compressor removal on units 060
adequate clearance on all sides of
satisfactory performance.
At least
&
065.
If parallel units are installed side by side, 120 in. should be
allowed between units.
This will prevent excessive condensing
temperatures and enhance system performance and operating economy.
Clearance for service access should be at least 78 in. at the
control center end for compressor removal on units 075 thru 130
and sufficient at the end opposite the control center for evaporator tube replacement.
FIGURE 3
60” MINIMUM-CLEARANCE
These clearances are illustrated in Figure 3.
CLEARANCE AROUND UNIT
FOR AIR INLET
11
60” MINIMUM CLEARANCE
FOR AIR INLET AND COMPRESSOR
REMOVAL ON ALR-060,065
NOTE: Minimum vertical clearance above unit should be
4
h
10 feet
I I
Access for Servicing
Each end of the unit must be accessible after installation for peri-
odic service work.
Compressors,
filter driers,
and manual liquid
line shutoff valves are accessible from the control center end of the
unit through removable access panels on unit sizes 075 thru 130 and
hinged side access doors on unit sizes 060 and 065.
safety,
They are protected by a keylocked,
tains internal "dead front"
nel from high
operational controls.
located just below the main control center.
and starting controls are located in the unit control center.
weatherproof enclosure which con-
doors for protection of service person-
voltage starting controls while servicing low voltage
All resettable or adjustable controls are
There is one resettable
All operational,
control enclosure on each side of the unit and each encl.osure contains
controls for compressors on that side of the unit.
Capped connections
for field service gauges are also located inside these enclosures. In
addition,
each of these enclosures are removable to improve access to
compressors for field replacement.
Page 5
The condenser fans, motors,
and drives are accessible through a walk-
in, keylocked access door on units ALR-075 thru 130 or a removable
access panel on units ALR-060 and
located at the end of the unit opposite the control center.
065.
The access door or panel is
Expan-
sion valves are accessible from the same access door on unit sizes
075 thru 130 and from side access doors at the control center end
on unit sizes 060 and 065.
An internal fan guard is located below the condenser fans and drives
on units 075 thru 130.
This guard must be removed to service the
fan drives but must always be re-installed when service work is com-
plete.
On unit sizes 060 and 065,
an interlock switch kills power
to condenser fans whenever the access panel is removed for service
work on fans or drives.
CAUTION:
Disconnect all power to the unit while
servicing condenser fan drives.
Vibration Isolators
Vibration isolators are recommended for all roof mounted installa-
tions or wherever vibration transmission is a consideration.
lists spring isolators for all ALR unit sizes.
tor locations in relation to the unit control center.
Figure 4 shows isola-
Figure 5 gives
Table 1
dimensions that are required to secure each McQuay isolator selection
to the mounting surface.
For applications which require a higher degree of isolation efficiency,
Table 2 shows the isolator loads at each location shown in Figure 4,
and the maximum loads for each McQuay selection.
TABLE 1
I
ALR LOCATIONS LOCATIONS
UNIT
SIZE
060A
065A
075A 2 164048-28
085A 2 16404B-28
105A
IIOA
120A
130A
I
l&4
t
ORDERING
NUMBER NUMBER
(877-j
216404B-27
216404B-27216404B-27
2164048.31
216404B.31
216404B.32216404B-32
216404B.32216404B
VIBRATION ISOLATORS
SPRING ISOLATORS
Z&5
I
ORDERING
(877-j
216404B~27
216404B-28
216404B-28
216404B-31
2164048-31
32
__-
I
I
LOCATIONS
3&6
ORDERING
NUMBER
(877-i
216404B-28
216404B-28
216404B-27
216404B-27
216404B-31
216404B.31
216404B-32
216404B-32
I
1
_
TABLE 2
Page 6
ISOLATOR LOADS
WATER PIPING
Piping Practices
Due to the variety of piping practices, it is advisable to follow
the recommendations of local authorities.
They can supply the in-
staller with the proper building and safety codes required for a
safe and proper installation.
Basically,
the piping should be designed with a minimum number of
bends and changes in elevation to keep system cost down and perfor-
mance up.
1.
Vibration eliminators to reduce vibration and noise transmission
It should contain:
to the building.
Shutoff valves to isolate the unit from the piping system dur-
2.
ing unit servicing.
Manual or automatic air vent valves at the high points of the
3.
system.
4.
Some means of maintaining adequate system water pressure (e.g.;
expansion tank or regulating valve).
5.
Temperature and pressure indicators located at the unit to aid
in unit servicing.
6.
A strainer or some means of removing foreign matter from the
water before it enters the pump.
It should be placed far enough
upstream to prevent cavitation at the pump inlet (consult pump
manufacturer for recommendations).
The use of a strainer will
prolong pump life and thus keep system performance up.
Prior to insulating the piping and filling the system, a preliminary
leak check should be made.
Piping insulation should include a vapor barrier to prevent moisture
condensation and possible damage to the building structure.
It is
important to have the vapor barrier on the outside of the insulation
to prevent condensation within the insulation on the cold surface
of the pipe.
Chilled Water Thermostat
The chilled water thermostat is mounted inside the unit control center.
On models ALR-075A through
130A,
the thermostat sensor is fac-
tory mounted in the return water connection of the evaporator. On
models
water line as shown in Figure 6.
ALR-060A
and
065A,,
the sensor must be installed in the return
The thermostat sensor should be in-
sulated after installation.
FIGURE 6
THERMOSTAT
SENSOR
REDUCING
BUSHING
THERMOSTAT SENSOR INSTALLATION
RETURN WATER CONNECTION
OF EVAPORATOR
7
1
LRETURN WATER LINE
Page 8
CAUTION:
Flow Switch
Thermostats have maximum operating temperature limits of:
ALR-060 and 065
140F on return water for standard ca-
pacity reduction.
125F on return water for optional capacity reduction.
ALR-075 throuqh 130
125F on return water for standard capacity reduction.
250F on return water for optional ca-
pacity reduction.
Temperatures exceeding these limits may damage the controls.
WATER FLOW SWITCH
A
ing water line to insure that there will be adequate water
cooling load to the evaporator before the unit can start.
safeguard against slugging the compressors on start up.
MUST
BE MOUNTED in either the entering
or
leav-
flow and
This will
It also
serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze up.
A flow switch is available from McQuay under ordering number 860-
175033x-00.
size from
to close the switch and are listed in Table 3.
It is a "paddle"
1"
to 6" nominal.
type switch and adaptable to any pipe
Certain minimum flow rates are required
Installation
should be as shown in Figure 7.
TABLE
3
FLOW SWITCH MINIMUM FLOW RATES
NOMINAL
PIPE SIZE
(INCHES)
1
1
l/4
1
l/2
2
2112
3
4
5
6
MINIMUM REQUIRED
FLOW TO ACTIVATE
SWITCH
6.00
9.80
12.70
18.80
24.30
30.00
39.70
58.70
79.20
(GPM)
FIGURE 7
+ FLOW4
DIA.
-
5 PIPE
AFTER SWITCH
MINIMUM 5 PIPE DIA.-MINIMUM
FLOW DIRECTION
/
J’
MARKED ON SWITCH
1.00
NPT FLOW SWITCH
CONNECTION
BEFORE SWITCH
Electrical connections in the unit control center should be made at
terminals 11 and 12.
should be wired between these two terminals.
_
normally closed contacts on the switch that could be used for an in-
The normally open contacts of the flow switch
There is also a set of
dicator light or an alarm to indicate when a "no flow" condition
exists.
Page 9
Piping Connections
Water piping connections at the unit vary in size and style depen-
ding on the baffle option ordered.
These connection variations are
shown in the table with Figure 8.
Piping through the unit cabinet can be through the end or bottom of
the unit as the application dictates.
hole centers for piping through the end of the unit.
Pilot holes locate
Figure 8 gives
the proper
the necessary dimensions for either piping method.
-Warranty is voided if wiring is not in accordance with specifica-
tions.
An
open fuse indicates a short, ground, or overload.
Before
replacing a fuse or restarting a compressor or fan motor, the trouble must be found and corrected.
Copper wire is required for all power lead terminations at the unit
while either aluminum or copper can be used for all other wiring.
All unit sizes are set up as standard for separate 115 volt power
supply circuits for the control circuit and cooler heater.
The con-
trol circuit only or both the control circuit and cooler heater can
be powered off of the main unit power supply if the optional control
circuit transformer is ordered.
have the unit
the main unit
out defeating
cooler heater on a separate disconnect switch from
power supply so that the unit may be shut down with-
the freeze protection provided by the cooler heater.
It may be desirable, however, to
TABLE 4
Wire sizing ampacities and recommended power lead wire sizes
Notes: 1. Separate terminals provide for the field connection of a
separate
2. Wire sizing amps are equal to 125% of the Nameplate
Amps of the largest motor plus 100% of the Nameplate
Amps of all other loads in the circuit (the control circuit
is not included). To include the control circuit, add 10
amps to 208 or 230 volt units and 5 amps to 460 volt
units. Recommended power lead wire and maximum fuse
sizes are not affected.
3. Recommended power lead wire sizes for three conductors per conduit are based on 100% conductor
115/60/1
power supply to the control circuit.
ampacity at 86 F ambient for no more than 3 conductors
per conduit. Wire sizes for six conductors per conduit are
based on 80% of the above mentioned conductor
ampacity in accordance with NEC. Voltage drop has not
been included, therefore, it is recommended that power
leads be kept short. All terminal block connections must
be made with copper wire.
4.
The unit power terminal block has two lugs per phase.
Single or parallel conductors per phase may be used for
power hookup as listed under “Recommended Power
Lead Wire Size.”
The cooler heater cable current draw is 3.5 amps.
5.
Page 11
A standard feature on all ALR units is
COPSTM(Controlled
Override of
Pump Shutdown),a system for interlocking the field supplied chilled
water pump into the chiller control system.
A relay (R-19) is wired
into the unit control circuit so that a time clock and/or ambient
thermostat can be connected to a pair of terminals (6 and 11) inside the unit control center.
starter.
Once the pump starts,
The time clock can energize a pump
the flow switch and/or pump inter-
lock will close and energize that part of the control circuit that
will allow the unit to start.
This feature makes it possible to start the chilled water pump and
the chiller simultaneously only when cooling is required.
For re-
cycling pumpdown without a demand for cooling, a pair of relays
(energized by low pressure controls) are also wired into this cir-
cuit to start the pump,
close the flow switch and pump down the
unit.
NOTE:
If a time clock,
ambient thermostat and/or re-
mote on-off switch are not used, terminals 6
and 11 must be jumpered together before the
unit will start.
Figure 9 shows typical field wiring that is required for unit installation.
FIGURE 9
TYPICAL FIELD WIRING DIAGRAM
Standard is separate power supply circuits for controls
and cooler heater. These circuits may be combined by
installing jumpers from terminals 1
NOTE C:
Pump starter, contacts of R9,
terminals 7 & 8 are limited to 250 volts maximum.
CUSTOMER CONNECTION
FIELD WIRING
FACTORY WIRING
BLACK WIRING (LINE)
WHITE WIRING (NEUTRAL)
flow switch and/or starter interlock.
-
9 & 10 - 20.
R10,
and
R19
between
START - UP AND SHUT DOWN
Pre Start-Up
1.
With all electric disconnects open,
check all screw or lug type
electrical connections to be sure they are tight for good electrical contact.
fore shipment,
Although all factory connections are tight be-
some loosening may have resulted from shipping
vibration,
2.
Inspect all water piping for flow direction and correct connections at the evaporator.
Page 13
3.
4.
5.
6.
7.
8.
9.
10.
Open all water flow valves and start the chilled water pump.
Check all piping for leaks and vent the air from the evaporator
as well as from the system piping.
system piping to obtain clean,
orator circuit.
Check to see that the thermostat water temperature sensor is installed in the return water line (return to chiller).
075A through
ALR-060A
tion,
and the sensor should be secured in the well with the retaining
clip provided. On ALR-075A through 130A units with optional cap-
acity reduction,the sensor is installed directly into the return
water line i.e.;
Check the compressor oil level. Prior to start-up, the oil level should cover at least
Remove the (8) compressor shipping blocks that are attached to the
compressor rails and the base of the unit.
not have shipping blocks.
Check the voltage of the unit power supply and see that it is
within the
balance must be with _+ 2%.
Check the unit power supply wiring for adequate ampacity and a
minimum insulation temperature rating of 75C.
Verify that all mechanical and electrical inspections have been
completed per local codes.
See that all auxiliary control equipment is operative and that
an adequate cooling load is available forinitial start up.
and 065A units with standard or optional capacity reduc-
the sensor well should be full of heat conducting
13OA
+
10%
units with standard capacity reduction, or
no well or heat conducting compound is required.
l/2
tolerance that is allowed.
non-corrosive water in the evap-
of the oil sight glass.
Flush the evaporator and
On
ALR-
compound
The ALR 060 and 065 do
Phase voltage un-
_
Start-Up
1.
Open the compressor suction and discharge
back seated.
2.
Open the manual liquid line shutoff valve at the outlet of the
subcooler.
Check to see that pumpdown switches
3.
pumpdown"position and the control stop switch
"on
"
position.
Adjust the dial on temperature controller
4.
chilled water temperature.
Throw the main power and control circuit disconnects to the "on"
5.
position.
CAUTION:
6.
Allow the crankcase heaters to operate for at least 8 hours prior
to start-up.
Start the auxiliary equipment for the installation by turning
7.
on the time clock,
if the unit and chilled water pump are electrically interlocked
by using the COPS
8.
Start the system by moving pumpdown switches
"auto.
9.
After system performance has stabilized, it
"Compressorized Equipment Warranty Form" (form no. 206036A) be
completed to obtain full warranty benefits.
with the unit and after completion should be returned to McQuay's
Service Department through your sales representative.
pumpdown" position.
Always replace valve seal caps.
(PSl &
Most relays and terminals in the unit
control center are hot with
control circuit
ambient thermostat and/or remote on/off switch
method discussed in "Field Wiring".
disconnect
shutoff valves until
PS2) are in the
(Sl)
is in the
TCl
to the desired
Sl
and the
on.
(PSl &
is
necessary that the
This form is shipped
PS2) to the
"man.
Page 14
Temporary Shut-Down
Move pumpdown switches
After
pump.
It is important that the compressors pump down before the water flow
to the unit is interrupted to avoid freeze up in the evaporator.
Start-Up After Temporary Shut-Down
1.
2.
3.
Extended Shut-Down
1.
2.
3.
4.
5.
6.
7.
the compressors have pumped down, turn off the chilled water
NOTE:
Start the chilled water pump.
With control stop switch
down switches
Observe the unit operation for a short time to be sure that the
compressors do not cut out on low oil pressure.
Close the manual liquid line shutoff valves.
After the compressors have pumped down, turn off the chilled
water pump.
Turn off all power to the unit and to the chilled water pump.
Move the control stop switch
Close the compressor suction and discharge valves.
Tag all opened disconnect switches to warn against start up be-
fore opening the compressor suction and discharge valves.
Drain all water from the unit evaporator and chilled water pip-
ing if the unit is to be shut down during winter.
With the unit left in this condition, it is
capable of recycling pumpdown operation. To
defeat this mode of operation, simply move
control stop switch
(PSl &
(PSl
& PS2) to the "man. pumpdown" position.
(Sl)
to the "off" position.
(Sl)
in the
PS2) to the "auto. pumpdown" position.
(Sl)
to the "off" position.
"on"
position, move pump-
Start-Up After Extended Shut-Down
1.
Inspect all auxiliary equipment to see that it is in satisfac-
tory operating condition.
2.
Remove all debris that has collected on the surface of the condenser coils.
3.
Open the compressor suction and discharge valves.
4.
Open the manual liquid line shut off valves.
c
J.
Check to see that pumpdown switches
ual pumpdown position.
6.
Turn on the electric power to the unit and other parts of the
system.
7.
Allow the crankcase heaters to operate for at least 8 hours
prior to start-up.
8.
Start the chilled water pump and purge the water piping as well
as the evaporator in the unit.
9.
Check to see that the control stop switch
tion.
CAUTION:
Most relays and terminals in the unit
control center are hot with
control circuit disconnect on.
(PSl
and PS2) are in the man-
(S1)is
Sl
in the
and the
"on"
posi-
Page 15
10.
Start the unit by moving
pumpdown
switches
(PSl
& PS2) to the
"auto.pumpdown" position.
11.
After running the unit for a short time check the oil level in
each compressor crankcase and check for flashing in the refrigerant sight glass (see "Maintenance" on Page 47).
ELECTRICAL
Control Center
All electrical controls are enclosed in a weatherproof control cen-
ter with keylocked, hinged access doors.
posed of three separate enclosures.
The upper enclosure is the
largest and contains all of the 208, 230,
fan motor starting controls.
Also included in this enclosure but
partitioned separately are the exposed terminal type
ational controls.
A "dead front"
cover over the high voltage sec-
The control center is com-
or 460 volt compressor and
-
115 volt oper-
tion protects service personnel from high voltage starting controls
while servicing low voltage operational controls.
Below the upper enclosure are two smaller,
contain 115 volt adjustable or resettable controls.
separate enclosures that
There is one of
these enclosures on each side of the unit, and each contains controls
for the compressors on that side.
Power supply conduits are intended to come into the bottom of the
upper enclosure and between the two lower enclosures.
mended that the unit disconnect switch be mounted away
but
Figure 10 recommends unit mounting arrangements if the disconnect
it is recomfrom the unit
must be unit mounted.
Page 16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.