McQuay ALR032D Installation Manual

Operating Manual OMRCPMICRO
Group: Chiller Part Number: 585571Y Effective: July 2000
Supersedes: IM 493-4
MicroTech Reciprocating Chiller / Templifier Control
Models ALR 032 D/E thru 185 D/E Models WHR 040 D/E thru 210 D/E Models THR 040 D/E thru 210 D/E
© 1999 McQuay International
Table of Contents
Introduction............................................3
General Description...............................4
Features of the MicroTech Control Panel
.................................................................4
Optional Sensor Packages.....................5
Controller Layout...................................6
Component Data....................................7
Installation and Maintenance..............10
Field Wiring..........................................12
Software Identification.........................15
Controller Inputs/Outputs....................16
Remote Demand Limiting....................22
Head Pressure Control.........................28
Pumpdown Control................................31
"Monitor Only" Sensors and Display
Items .....................................................31
Safety Systems .....................................32
Circuit Alarm Conditions......................33
System Alarm Conditions.....................35
Other Conditions ..................................36
Normal Sequence of Operation...........37
Start-Up and Shutdown.........................39
Keypad/Display....................................42
Password Information...........................43
THR Heat/Cool Changeover...............23
Soft Loading .........................................23
Compressor Control.............................24
Lead-Lag of Refrigerant Circuits........25
Manual Operation................................25
Unit Status Modes...............................26
Circuit Status Modes...........................27
McQuay" is a registered trademark of McQuay International
"Information covers McQuay International products at the time of publication and we reserve the right
to make changes in design and construction at anytime without notice"
1997 McQuay International
Keypad Key Functions.........................43
Menu Descriptions...............................45
MicroTech Keypad Directory..............50
Test Procedure - Trouble Analysis ......59
Testing Solid-State Relays...................64
MicroTech Monitoring and Networking
Options..................................................65
2 OMRCPMICRO
Introduction
This manual provides installation, setup and troubleshooting information for the MicroTech controller provided on McQuay reciprocating compressor chillers. Please refer to unit installation manuals for unit application information as well as water and refrigerant piping details. All operating descriptions contained in this manual are based on MicroTech controller software version RCPXX02G. Chiller operating characteristics and menu selections may vary with other versions of controller software. Contact McQuayService for software update information.
This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof.
The McQuay MicroTech control panel contains static sensitive components. A static discharge while handling electronic circuit boards may cause damage to the components.
CAUTION
CAUTION
To prevent such damage during service involving board replacement, McQuay recommends discharging any static electrical charge by touching the bare metal inside the panel before performing any service work.
CAUTION
Excessive moisture in the control panel can cause hazardous working conditions and improper equipment operation.
When servicing equipment during rainy weather conditions, the electrical devices and MicroTech components housed in the main control panel must be protected.
The MicroTech controller is designed to operate within an ambient temperature range of -40 to 149°F and a maximum relative humidity of 95% (non-condensing).
Figure 1, MicroTech Control
OMRCPMICRO 3
General Description
The MicroTech Unit Control Panel, available on some McQuay ALR, WHR, and THR products, contains a Model 250 microprocessor based controller which provides all monitoring and control functions required for the safe, efficient operation of the unit. The operator can monitor all operating conditions by using the panels built in 2-line by 16-character display and keypad or by using an IBM compatible computer running McQuay Monitor software. In addition to providing all normal operating controls, the MicroTech controller monitors all safety devices on the unit and will shut the system down and close a set of alarm contracts if an alarm condition develops. Important operating conditions at the time an alarm occurs are retained in the controllers memory to aid in troubleshooting and analysis.
The system is protected by a simple password scheme which only allows access by authorized personnel. A valid password must be entered into the panel keypad by the operator before any setpoints may be altered.
Features of the MicroTech Control Panel
Ø Enhanced head pressure control on air-cooled units resulting in increased total unit SEER during
transitional seasons.
Ø Preemptive control of high discharge pressures prior to a fault. Ø 12-key keypad for adjusting water temperature set points, low water temperature cutout, high pressure
cutout, suction pressure cutout, and freeze protection. The operator can use the keypad to monitor various operating conditions, setpoints or alarm messages.
Ø Easy-to-read 2-line by 16-character display for plain English readout of operating temperatures and
pressures, operating modes or alarm messages.
Ø Security password protection against unauthorized changing of set points and other control parameters. Ø Complete plain English diagnostics to inform the operator of pre-alarms and alarms. All alarms are time and
date stamped so there is no guessing of when the alarm condition occurred. In addition, some operating conditions that existed at the instant of shutdown can be recalled to aid in isolating the cause of the problem.
Ø Soft Loading feature to reduce electrical consumption and peak demand charges during start-up. Ø Adjustable load pulldown rate reduces over-shoot during loop pulldown. Ø Easy integration into building automation systems via separate 4-20 milliamp signals for chilled water reset
and demand limiting (chillers only).
Ø BAS communication capability via McQuay’s open protocol strategy to over 10 major BAS manufacturers. Ø Internal time clock for on/off scheduling. Ø 14 holidays / dates with programmable duration. Ø Communications capabilities for local system monitoring, changing of set points, trend logging, remote
reset, alarm and event detection via IBM-compatible PC. The optional modem kit supports the same features from an off-site PC running the McQuay Monitor software.
Ø Manual control mode to override automatic unit staging, useful for system checkout. Ø Pressure transducers for direct reading of system pressures.
4 OMRCPMICRO
Optional Sensor Packages
Water and air sensor package
Air-cooled units:
Ø Entering evaporator water temperature Ø Ambient outside air temperature
Water-cooled units only:
Ø Entering evaporator water temperature Ø Entering condenser water temperature Ø Leaving condenser water temperature
Refrigerant sensor package
Ø Suction line temperature, circuit #1 Ø Suction line temperature, circuit #2 Ø Liquid line temperature, circuit #1 Ø Liquid line temperature, circuit #2 (Provides direct display of subcooling and superheat).
Unit amp package
Percent total unit amperage including compressors and condenser fans. Does not include externally powered equipment such as water pumps.
OMRCPMICRO 5
Controller Layout
All major MicroTech components are mounted inside the control section side of the unit's control cabinet. The individual components are interconnected by ribbon cables, shielded multi-conductor cables or discrete wiring. Power for the system is provided by transformers T-2 and T-4. All field wiring must enter the control cabinet through the knockouts provided and is terminated on field wiring terminal strips.
The standard ALR keypad/display is located inside the control cabinet for protection from the weather while the back lit WHR and THR keypad/displays are accessible through the exterior of the control cabinet. See Figure 2 for typical control cabinet layout.
Figure 2, Typical control cabinet layout
6 OMRCPMICRO
Component Data
Microprocessor control board
The Model 250 Microprocessor Control Board contains the electronic hardware and software necessary to monitor and control the unit. The microprocessor control board receives input from the Analog/Digital Input Board (ADI) and sends commands to the output board, maintaining the unit's optimum operating mode for the current conditions. Status lights mounted on the control board indicate operating condition of the microprocessor.
Analog/digital input board (ADI)
The ADI board receives analog/digital signals from sensors and switches. The ADI board also provides optical isolation between the microprocessor control board and all 24 volt switch inputs. LEDs on the ADI board provide visual indication of the status of all digital inputs. All analog and digital signals from sensors, transducers, and switches received by the ADI board and sent to the microprocessor control board for interpretation.
Output board
The output board contains up to 16 solid-state relays and provides optical isolation between the control board and Vac load volts. These relays control all compressors, condenser fans, solenoid valves, and alarm annunciation. The output board receives control signals from the microprocessor control board through a 50 conductor ribbon cable.
Keypad and display
The keypad and display is the primary operator interface to the unit. Operating conditions, system alarms, and set points can be monitored from this display. All adjustable set points can be modified from this keypad after the operator has entered a valid password.
Thermistor sensors
MicroTech panels use a negative temperature coefficient thermistor for temperature sensing. A sensor operating correctly will measure 3,392 ohmsat 72°F. See Table 1 for temperature conversion information.
Pressure transducers
Pressure transducers are selected for a specific operating range and provide an output signal proportional to the sensed pressure. Typical range for evaporator sensor is 5 to 145 psig with a resolution of 0.1 psig. Condenser pressure sensors have a range of 20 to 450 psig and a resolution of 0.5 psig. The transducer output characteristics are shown in Figure 3 and 4 on page 9.
Table 1, MicroTech thermistors (resistance and voltage vs. temperature)
Temp°FTemp°CResistance
Ohms 0 -17.8 25,617 4.426 50 10.0 5,971 3.213 100 37.8 1,747 1.724 1 -17.2 24,817 4.410 51 10.6 5,814 3.183 101 38.3 1,708 1.698 2 -16.7 24,044 4.393 52 11.1 5,662 3,152 102 38.9 1,670 1.673 3 -16.1 23,299 4.376 53 11.7 5,514 3.121 103 39.4 1,633 1.648 4 -15.6 22,579 4.359 54 12.2 5,371 3.090 104 40.0 1,597 1.624 5 -15.0 21,883 4.341 55 12.8 5,231 3.059 105 40.6 1,562 1.600 6 -14.4 21,212 4.323 56 13.3 5,096 3.028 106 41.1 1,528 1.576 7 -13.9 20,563 4.305 57 13.9 4,965 2.996 107 41.7 1,494 1.552 8 -13.3 19,937 4.286 58 14.4 4,838 2.965 108 42.2 1,461 1.528
Table continued on next page.
VDC Input
Temp°FTemp°CResistance
Ohms
VDC Input
Temp°FTemp°CResistance
Ohms
VDC Input
OMRCPMICRO 7
Table 1, Continued from previous page
Temp°FTemp°CResistanc
e
Ohms
9 -12.8 19,332 4.267 59 15.0 4,714 2.934 109 42.8 1,430 1.505 10 -12.2 18,747 4.248 60 15.6 4,594 2.902 110 43.3 1,398 1.482 11 -11.7 18,182 4.228 61 16.1 4,477 2.871 111 43.9 1,368 1.459 12 -11.1 17,636 4.208 62 16.7 4,363 2.839 112 44.4 1,339 1.437 13 -10.6 17,108 4.187 63 17.2 4,252 2.808 113 45.0 1,310 1.415 14 -10.0 16,597 4.167 64 17.8 4,146 2.777 114 45.6 1,282 1.393 15 -9.4 16,104 4.145 65 18.3 4,042 2.745 115 46.1 1,254 1.371 16 -8.9 15,627 4.124 66 18.9 3,941 2.714 116 46.7 1,228 1.350 17 -8.3 15,166 4.102 67 19.4 3,843 2.683 117 47.2 1,201 1.328 18 -7.8 14,720 4.080 68 20.0 3,748 2.651 118 47.8 1,176 1.308 19 -7.2 14,288 4.057 69 20.6 3,655 2.620 119 48.3 1,151 1.287 20 -6.7 13,871 4.034 70 21.1 3,565 2.589 120 48.9 1,127 1.267 21 -6.1 13,467 4.011 71 21.7 3,477 2.558 121 49.4 1,103 1.247 22 -5.6 13,076 3.988 72 22.2 3,392 2.527 122 50.0 1,080 1.227 23 -5.0 12,690 3.964 73 22.8 3,309 2.496 123 50.6 1,058 1.208 24 -4.4 12,333 3.940 74 23.3 3,228 2.465 124 51.1 1,036 1.189 25 -3.9 11,979 3.915 75 23.9 3,150 2.434 125 51.7 1,014 1.170 26 -3.3 11,636 3.890 76 24.4 3,074 2.404 126 52.2 993 1.151 27 -2.8 11,304 3.865 77 25.0 3,000 2.373 127 52.8 973 1.133 28 -2.2 10,983 3.839 78 25.6 2,927 2.343 128 53.3 953 1.115 29 -1.7 10,672 3.814 79 26.1 2,857 2.313 129 53.9 933 1.097 30 -1.1 10,371 3.788 80 26.7 2,789 2.283 130 54.4 914 1.079 31 -0.6 10,079 3.761 81 27.2 2,723 2.253 131 55.0 895 1.062 32 0.0 9,797 3.734 82 27.8 2,658 2.223 132 55.6 877 1.045 33 0.6 9,523 3.707 83 28.3 2,595 2.194 133 56.1 859 1.028 34 1.1 9,258 3.680 84 28.9 2,534 2.164 134 56.7 842 1.012 35 1.7 9,002 3.653 85 29.4 2,474 2.135 135 57.2 825 0.995 36 2.2 8,753 3.625 86 30.0 2,416 2.106 136 57.8 809 0.980 37 2.8 8,512 3.597 87 30.6 2,360 2.077 137 58.3 792 0.963 38 3.3 8,278 3.569 88 31.1 2,305 2.049 138 58.9 777 0.948 39 3.9 8,052 3.540 89 31.7 2,251 2.020 139 59.4 761 0.932 40 4.4 7,832 3.511 90 32.2 2,199 1.992 140 60.0 746 0.917 41 5.0 7,619 3.482 91 32.8 2,148 1.964 141 60.6 731 0.902 42 5.6 7,413 3.453 92 33.3 2,099 1.937 142 61.1 717 0.888 43 6.1 7,213 3.424 93 33.9 2,051 1.909 143 61.7 703 0.874 44 6.7 7,019 3.394 94 34.4 2,004 1.882 144 62.2 689 0.859 45 7.2 6,831 3.365 95 35.0 1,959 1.855 145 62.8 676 0.846 46 7.8 6,648 3.335 96 35.6 1,914 1.828 146 63.3 662 0.831 47 8.3 6,471 3.305 97 36.1 1,871 1.802 147 63.9 649 0.818 48 8.9 6,299 3.274 98 36.7 1,829 1.776 148 64.4 627 0.794 49 9.4 6,133 3.244 99 37.2 1,788 1.750 149 65.0 625 0.792
VDC
Input
Temp°FTemp°CResistanc
e
Ohms
VDC
Input
Temp°FTemp°CResistanc
e
Ohms
VDC
Input
8 OMRCPMICRO
Figure 3, Evaporator transducer Figure 4, Condenser transducer
OMRCPMICRO 9
Installation and Maintenance
The MicroTech controller is factory tested and configured for the unit being controlled.
Sensors and transducers
Sensors and transducers are mounted and connected to the MicroTech ADI board with shielded cable. Transducers are on Shrader fittings and sensors are in wells except the optional suction and liquid line sensors (in the refrigerant sensor package). The suction and liquid line sensors are placed in a copper sleeve that is brazed to the copper tubing. Insulation is placed around the assembly.
Sensors and transducers are connected to the MicroTech analog inputs with IDC connectors (Insulation Displacement Connectors).
To change the transducers, just unscrew and replace. The transducers have removable cables. High pressure transducers have a red dot on them and low pressure transducers have blue dots. Sensors do not have separate cables.
Control wiring
Low voltage control wiring is installed, labeled and tested by the factory before shipment.
Remote 4-20 milliamp signals
Signals for leaving water reset and demand limiting can be provided by the customer and should be connected to the terminals on the field wiring strip inside the control cabinet. See the Field Wiring section for more details.
Interlock wiring
All interlock wiring to field devices (such as flow switches and pump starters) is provided by the installing contractor. See Figure 5, unit wiring schematics, and field wiring diagrams at the end of this manual for details.
Unit set points and calibration
The control software is installed and tested by the factory before shipping. No periodic calibration of the controller is necessary. All control and safety set points must be checked by the installing contractor and adjusted as necessary before starting the unit. Controllers for McQuay chillers and Templifiers have default set points (shown on Menus 13 through 22, in Table 8 on page 52) for:
Ø Control mode Ø Leaving water temperature Ø Head pressure settings Ø Compressor staging
The default set points are suitable for most installations. On Menu 13, the default control mode is set for "Manual Unit Off". Adjust this setting before continuing with
unit operation. Check and set the control and safety settings for the application before staging the unit. For more information on menu items, see the Menu Description section of this manual.
Ø Softloading Ø Holiday dates Ø Internal scheduling Ø Alarm functions
Modem kit
An optional modem kit allowing remote monitoring of the chiller from an off-site PC running the McQuay Monitor software is available from McQuayService. The kit, complete with modem, mounting bracket, wiring
10 OMRCPMICRO
harness, and installation instruction can be installed in the field or at the factory. Modem wiring is shown on
the MicroTech wiring schematic. For more information, see "Telephone Line" in the Field Wiring section on
page 14.
Optional sensors
Optional sensor kits, available from the factory, can be installed in the field. Thermistors in the optional sensor
kit are negative coefficient type and have the same characteristics (see Table 1) as the thermistors used on
McQuay centrifugal chillers. Contact McQuayService for retrofit kits and ordering information.
Figure 5, Typical field wiring
OMRCPMICRO 11
Field Wiring
Interconnecting wiring for the reciprocating control panel consists of:
Ø 115 VAC power wiring Ø Analog input signals Ø Digital input signals Ø Digital output signals Ø Condenser pump Ø Fan starter Ø Communications to a personal computer Ø Telephone line for remote modem access
See Figure 5 and unit field wiring diagrams at the end of this manual for more details.
Power wiring
Separate disconnects for the cooler heating tape and control circuit transformer are available as options on ALR units. The installing contractor provides the 115 VAC power source, disconnect, 10 amp fuse, and necessary wiring for these circuits. All wiring must conform to the National Electrical Code and applicable local building code. If the separate power option is used, then the installing contractor must remove wires 540 and 545 from terminals #13 and #16 on TB2 before running the unit. See the ALR Field Wiring Diagram for more detail.
Power supplies
There are several internal power supplies used by the controller and related circuitry. The regulated 5 VDC power on terminal #214 is used to support the analog inputs on the ADI board. Do not use this power supply to operate external devices. An unregulated 12 VDC power supply is available on field wiring terminal #146 and an unregulated 24 VAC power supply is available on field wiring terminal #25.
Analog input signals
All sensors and transducers required for normal chiller operation are installed and wired at the factory. All optional analog signal wiring provided by the installing contractor must be twisted, shielded pair (Belden #8760 or equal). Figure 5 and unit field wiring diagrams at the end of this manual for more detail. The optional demand limit and leaving water reset signals are 4 to 20 milliamp DC signals. The resistive load that conditions the milliamp signal is a 249 ohm resistor mounted on the ADI board at the factory.
Remote demand limit
To use the demand limit function, the installer will connect the wiring to terminals #131 and #132 on TB7. Demand Limit can only be used on WHR and ALR units. See the MicroTech schematic and Field Wiring diagrams at the end of this manual for more detail. More information on how Demand Limit works is available in the Remote Demand Limit section on page 12 of this manual.
Leaving water reset*
Leaving water reset on ALRs, WHRs and THRs may be achieved by using the "4-20mA Reset" option on Menu 14. The installer must connect wiring to terminals #134 and #135 on TB7. See the Reset Options section of this manual for more detail.
12 OMRCPMICRO
Digital input signals
Remote contacts for all digital inputs into the MicroTech controller must be dry contacts suitable for the 24
VAC control signals from the reciprocating control panel. Do not connect 120 VAC control power to these or
any other connecting circuits.
Remote stop/start
If remote stop/start control is preferred, then remove the jumper between terminals #140 and #141 on TB7.
When the remote stop/start switch is open, the controller will be in the "off: remote Sw" mode. The unit is
enabled when the switch is closed.
Chilled water flow switch
The chilled water flow switch is connected to field wiring terminals #142 and #143 on TB7. When the chilled
water pump is enabled, the MicroTech controller checks for proof-of-flow through the flow switch digital input.
Digital outputs
The MicroTech output device is a normally open solid-state relay with an on-board, replaceable 5 amp fuse.
The status of all outputs are shown by individual red LEDs.
Chilled water pump relay
The optional chilled water pump relay is connected to terminal #10 on TB2. When the unit is enabled, the
chilled water pump relay is energized. Be sure the relay coil is rated for a maximum load of 1.8 amps at 120 VAC.
External alarm annunciator circuitry
An audible alarm connected to the Alarm Output of the reciprocating control panel is highly recommended to
make certain the operator is alerted to any alarm condition.
The MicroTech panel can activate an external alarm circuit when an alarm or pre-alarm condition is detected.
The alarm signal is de-energized during normal operations. During an alarm condition the alarm circuit will
energize and the alarm status light will be lit. During a pre-alarm condition, the alarm output and status light
will pulse "on" for one-half second and "off" for four seconds.
24 VAC is available at field wiring terminal #19 to power a bell, light, relay, or other external alarm devices. The
installing contractor must provide and install an alarm enunciator rated for a maximum load of 1.8 amps at 24
VAC. See the field wiring diagrams at the end of this manual for terminal locations.
Note: The alarm signal is not active during a power failure and will not provide a "Loss of Power"
alarm.
115 VAC power for the optional control transformer is obtained from the 3-phase power connection provided
by the electrical contractor.
Condenser fan wiring for chillers without condensers
The first fan of each circuit is to be wired in parallel with the first compressor stage for each circuit. Each
refrigerant circuit has three additional digital outputs available for refrigerant head pressure control. Each
output will energize an additional bank of condenser fans with each bank consisting of 1 or 2 fans, depending
on the size of the unit. The relays used to energize the fan motors must be rated for 120 VAC, 1.5 amps
maximum per coil. If a McQuay APD condenser is used, then the relays will be supplied by the factory. Relays
and fans are denoted as M12 through M24. The first number indicates the circuit while the second number
indicates the fan or fan bank number. See the Field Wiring Diagram and Staging Schematics at the end of this
manual for more detail.
Condenser pump or fan starter
Terminals #11 and #12 on TB2 on water-cooled units are reserved for starting the first fans of each circuit on a
remote condenser or for starting a single condenser pump. The relay coils should be rated for a maximum load
OMRCPMICRO 13
of 1.8 amps at 120 VAC. The terminals are wired in parallel with the compressor outputs so the coils will be energized with the first compressor stage.
To start a condenser pump, install a jumper between terminals #11 and #12 and connect a single starter between terminals #11 and #16 on TB2. When either of the lead compressor start, the condenser pump will start.
To start a fan, connect the first fan of circuit #1 to terminals #11 and #16 on TB2. Connect the first fan of circuit #2 to terminal #12 and #16 on TB2. When the lead compressor of a circuit starts, the first condenser fan will start. See the Field Wiring Diagram and Compressor Control Schematics in the back of this manual for more detail.
PC connection
The MicroTech controller can be connected to an IBM or IBM compatible computer for local or remote system monitoring. Communication network wiring uses low voltage shielded twisted pair cable (Belden 8760 or equal). The network uses the RS232 communications standard with a maximum cable length of 50 feet. An RS232/485 adapter may be used to allow for cable runs to 5000 feet. See the Personal Computer Specification section of this manual for hardware requirements.
Telephone line
If remote access and monitoring of the unit is chosen, then a voice quality direct dial telephone line is required. The line must be a dedicated line and used only for modem access. The phone line must be terminated with a standard RJ-11 modular phone plug. See the Start-Up and Shutdown section on page 39of this manual for more detail on start-up procedures.
14 OMRCPMICRO
Software Identification
Control software is factory installed and tested in each panel prior to shipment. The software is identified by a
program code which is printed on a small label attached to the controller. The software version may also be
displayed on the keypad display be viewing the last menu item in the Misc Setup menu (menu 23).
The software "version" is the 6th and 7th digit of the software identification. In this example, the version is
"02" and the revision to the software is "G". Revisions are released in alphabetical order.
The new reciprocating codes are from a single master code which combined chiller and Templifier functions.
The new code enables selection of chiller or chiller/Templifier operation. A high memory chip is required to run
this software. Controller series 250-4 and greater can successfully run on chiller/Templifier software versions.
Example of typical software identification
RCP 2 E 01 B
Revision (A, B, C, etc.)
Version (1, 2, 3, etc.)
English/U.S. customary display units (S=SI/metric)
R-22 refrigerant (3=R-134a refrigerant)
Reciprocating chiller/Templifier code
Figure 6, Software ID tag
McQuay 06/01/95 Date Shipped
P/N 950820A-01-A Part Number
S/N 1058 Serial Number
Ver. RCP2E01B Software Version No.
OMRCPMICRO 15
Controller Inputs/Outputs
- A 4 to 20 milliamp DC signal from a building automation system
- A 4 to 20 milliamp signal from a building automation system to determine the maximum
signal from a unit mounted switch allows the unit to run in heat (0 volts - switch open) or cool (5 volts -
(standard on THR heat pumps; optional on WHR chillers) - For
common line of manifolded condenser head. The signal is used for capacity control on THRs and for
(optional) - A current transformer and adjustable voltage dropping resistor
located in the power side of the control box along with a voltage converter board sends a DC signal
Analog inputs
Analog inputs are used to read the various temperatures and pressures on the chiller as well as any customer supplied 4-20mA reset signals. The controller's internal regulated 5 VDC and 12 VDC supplies provide the correct operating voltage for the sensors. See Table 2 for details.
Input No. Description
0 Leaving evaporator water temperature - Sensor is located in the leaving chilled water nozzle. The
signal is used for capacity control and freeze protection.
1 Evaporator pressure transducer circuit #1 - Sensor is located in the common circuit #1 suction line.
Used to determine suction saturated refrigerant pressure and temperature. This sensor also provides refrigerant freeze protection for circuit #1.
2 Evaporator pressure transducer circuit #2 - Sensor is located in the common circuit #2 suction line.
Used to determine suction saturated refrigerant pressure and temperature. This sensor also provides refrigerant freeze protection for circuit #2.
3 Condenser pressure transducer circuit #1 - Saturated refrigerant pressure and temperature. 4 Condenser pressure transducer circuit #2 - Saturated refrigerant pressure and temperature. 5 Transducer power voltage ratio signal - The signal is used to correct for differences between the
controller power supply and an ideal 5 VDC supply. The controller uses this information to ensure temperature and pressure sensor accuracy and for alarm monitoring.
6 Evaporator water temperature reset
or temperature transmitter to reset the leaving chilled water set point. The impedance of the ADI board is 249 ohms.
7 Demand limit
number of cooling stages which may be energized. The impedance of the ADI board is 249 ohms.
8 Chiller/Templifier signal (on THR heat pumps only) - In place of the Demand Limit input, a 0 or 5 volt
switch closed) modes.
9 Entering evaporator water temp (optional) - Sensor is located in the entering chilled water nozzle. The
signal is used for monitoring and for the return reset option if selected.
10 Entering condenser water temp (optional) (O.A. temp for air cooled units) - Sensor is located in the
common entering condenser water nozzle or located remotely as an outside air temp sensor for air cooled units. This sensor is used for monitoring purposes only.
11 Leaving condenser water temperature
WHRs, sensor is located in leaving water nozzle of one condenser only. For THRs, sensor is located in
monitoring only on WHRs.
12 Percent of total unit amps
proportional to total motor current to the microprocessor. O VDC = 0%, 4 VDC = 100%
13 Suction temp circuit #1 (optional) - Sensor located in a copper sleeve brazed to the circuit #1 suction
line measures refrigerant temperature to calculate superheat. This sensor is used for monitoring purposes only.
14 Suction temp circuit #2 (optional) - Sensor located in a copper sleeve brazed to the circuit #2 suction
line measures refrigerant temperature to calculate superheat. This sensor is used for monitoring purposes only.
15 Liquid line temp circuit #1 (optional) - Sensor located in a copper sleeve brazed to the circuit #1 liquid
line measures refrigerant temperature to calculate subcooling. This sensor is used for monitoring purposes only.
16 OMRCPMICRO
16 Liquid line temp circuit #2 (optional) - Sensor located in a copper sleeve brazed to the circuit #2 liquid
line measures refrigerant temperature to calculate subcooling. This sensor is used for monitoring purposes only.
Front panel mount heat/cool switch front panel mount heat/cool switch
Table 2, Analog inputs
Input Function Location Range Resolution
0 Leaving Chw temperature Leaving Chw Nozzle -40 to 263°F 0.1°F 1 Circuit #1 Evaporator Pressure Circuit #1 Suction Line 5 to 145 psig 0.1 psi 2 Circuit #2 Evaporator Pressure Circuit #2 Suction Line 5 to 145 psig 0.1 psi 3 Circuit #1 Condenser Pressure - 20 to 450 psig 0.5 psi 4 Circuit #2 Condenser Pressure - 20 to 450 psig 0.5 psi 5 Voltage Ratio Signal EnGinn Power Supply - ­6 Chw Reset Signal Supplied By Others 4 to 20mA DC ­7 Demand Limit Signal Supplied By Others 4 to 20mA DC ­8 Entering Evaporator Water Temperature Entering Chw Nozzle -40 to 263°F 0.1°F
9 Entering Condenser Water Temperature Entering Condenser Water Nozzle -40 to 263°F 0.1°F 10 Leaving Conderser Water Temperature Leaving Condenser Water Nozzle -40 to 263°F 0.1°F 11 % Total Unit Amps Control Cabinet 0 to 4 VDC 1% 12 Circuit #1 Suction Temperature Circuit #1 Suction Line -40 to 263°F 0.1°F 13 Circuit #2 Suction Temperature Circuit #2 Suction Line -40 to 263°F 0.1°F 14 Circuit #1 Liquid Line Temperature Circuit #1 Liquid Line -40 to 263°F 0.1°F 15 Circuit #2 Liquid Line Temperature Circuit #2 Liquid Line -40 to 263°F 0.1°F
Digital inputs
Table 3, Digital inputs
Inpu
LED Description Circuit Closed Open
t
0 0 Mechanical high pressure switch Circuit #1 Normal High discharge pressure 1 1 Oil differential pressure switch Compressor 1 Normal Low oil pressure 2 2 Motor protection switch Compressor 1 Normal High motor temperature 3 3 Oil differential pressure switch Compressor 3 Normal Low oil pressure 4 4 Motor protection switch Compressor 3 Normal High motor temperature 5 5 System switch Unit Normal Unit shutdown 6 6 Phase/voltage monitor Unit Normal PVM alarm 7 7 Pumpdown switch Circuit #1 Normal Manual pumpdown 8 8 Mechanical high pressure switch Circuit #2 Normal High discharge pressure 9 9 Oil differential pressure switch Compressor 2 Normal Low oil pressure
10 10 Motor protection switch Compressor 2 Normal High motor temperature 11 11 Oil differential pressure switch Compressor 4 Normal Low oil pressure 12 12 Motor protection switch Compressor 4 Normal High motor temperature 13 13 Remote stop switch Unit Run Pumpdown & stop 14 14 Water flow switches Unit Normal No evaporator (condenser) flow 15 15 Pumpdown switches Circuit #2 Normal Manual pumpdown
Note: All Digital Inputs are 24 VAC. At 7.5 VAC to 24 VAC the digital input contacts are considered closed. Below 7.5 VAC, the contacts are considered open.
OMRCPMICRO 17
Relay board outputs
All of the MicroTech panel outputs are controlled by solid-state relays which are driven by the model 250 controller. The controller activates a solid-state relay by sending a "trigger" signal to the output board via the attached ribbon cable. The relay responds to the trigger by lowering its resistance which allows current to flow through its "contacts". When the controller removes the trigger signal, the relay's resistance becomes very high, causing the current flow to stop. The outputs are individually protected by a 5 amp fuse mounted on the output board adjacent to each relay. Table 4 and Table 5 provide additional information about each output. Refer to the MicroTech Stage Schematics for digital output wiring.
Table 4, ALR relay board outputs
6-Stage
Digital
Output
Number
0 Alarm Circuit Same Same Same Same 1 2 Liq Sol circ #1 Same Same Same Same
3 Liq Sol circ #2 Same Same Same Same 4 Cooling
5 Cooling
6 Cooling
7 Cooling
8 Cooling Not Used Not Used
9 Cooling Not Used Not Used
10 Condenser Fan(s) M12 11 Condenser Fan(s) M13 - Same Same Same
12 Condenser Fan(s) M14 - Same Same Same 13 Condenser Fan(s) M22 Same Same Same Same 14 Condenser Fan(s) M23 - Same Same Same 15 Condenser Fan(s) M24 - Same Same Same
Note: j Number of fans varies. Refer to the Head Pressure Control section on page 28 of this manual for Fan Staging
information.
Output
Description
Chilled Water
Pump Relay
j
4-Stage Compressor Capacity
2-Compressor 2-Compressor 4-Compressor
035-070 050-070 050-070 085-185
Same Same Same Same
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
Compressor 2
Unloader 1
Same Same Same Same
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
Compressor 2
Unloader 1
Compressor
Capacity
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
Compressor 2
Unloader 1
Compressor 1
Unloader 2
Compressor 2
Unloader 2
8-Stage Compressor
Capacity
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
Compressor 2
Unloader 1
Compressor 3
Unloader 1
Compressor 4
Unloader 2
Table 5, WHR and THR relay board outputs
4-Stage Compressor
Digital
Output
Number
0 Alarm Circuit Same Same Same 1 2 Liq Sol circ #1 Same Same Same
3 Liq Sol circ #2 Same Same Same 4 Cooling
5 Cooling
6 Cooling
Output
Description
Chilled Water
Pump Relay
Capacity
2-Compressor 2-Compressor 4-Compressor
WHR 040-085E
THR 040-110D
Same Same Same
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
18 OMRCPMICRO
6-Stage
Compressor
Capacity
WHR 070-085E
THR 070-110D
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
8-Stage Compressor
Capacity
WHR 095-210E
THR 120-170D
Compressor 1
Circuit #1
Compressor 2
Circuit #2
Compressor 1
Unloader 1
7 Cooling
8 Cooling Not Used
9 Cooling Not Used
10 Condenser Fan(s) M12
k
11 Condenser Fan(s) M13
k
12 Condenser Fan(s) M14
k
13 Condenser Fan(s) M22
k
14 Condenser Fan(s) M23
k
15 Condenser Fan(s) M24
k
Compressor 2
Unloader 1
Same Same Same Same Same Same Same Same Same Same Same Same Same Same Same Same Same Same
Compressor 2
Unloader 1
Compressor 1
Unloader 2
Compressor 2
Unloader 2
Compressor 2
Unloader 1
Compressor 3
Circuit 1
Compressor 4
Circuit 2
Note: kCondenserless WHR only. User selectable reset options are found under Menu 14, item line G "ResetOpt= " for chillers and item line H
"Reset Sig= ##.#mA" for Templifiers. Most reset options apply to leaving chilled water only—ALRs, WHRs, and THRs operated in chiller mode. The only reset options available for THRs operated in heating mode (controlled by leaving condenser water) are: "None", "4-20mA", and "Network". Selected reset option settings for chilled and heated water temperatures are displayed in Menu 14.
None
"None" is the Default Values setting. When selecting "None", the following applies:
Ø Leaving evaporator water temperature or leaving condenser water temperature, whichever is applicable
control the unit.
Ø Leaving evaporator water temperature control ALRs, WHRs, and THRs operating in the "chiller" mode. Ø Leaving condenser water temperature control THRs operating in "heat pump" mode.
Return
By selecting "Return" as the reset mode, the controller resets the leaving chilled water temperature set point as required to maintain a constant return water temperature. To choose "Return" as the reset option, first select "Return" in the "ResetOpt" mode and press <ENTER>, then in the "ReturnSpt" item, select the return water set point temperature to be maintained. The return water set point algorithm is internal to the controller. No other action is required.
4-20mA (remote reset signal)*
By selecting "4-20mA" as the reset option, the controller will reset the leaving chilled water temperature to a higher value based on a percentage of the Maximum Chilled Water Reset ("MaxChWRst"). At 4mA, the chilled water set point resets to a value equal the Leaving Evaporator Water Set Point ("Lvg Evap") plus the MaximumChilled Water Reset ("MaxChWRst") set point. Any valuebetween 4 and 20mA will add a proportional value of the Maximum Chilled Water Reset to the Leaving Chilled Water Set Point. The reset schedule is linear and may be determined using Figure 7, Leaving Water Reset, below. The external 4-20mA control signal displays under "ResetSig=" on Menu 14.
For THRs operated in heating mode, the "Lvg Evap" indicates the degree of heating reset. Using the 4-20mA reset signal, a proportional value of the Maximum Chilled Water Reset "MaxChWRst" is subtracted from the Leaving Condenser Water Set Point ("Lvg Cond" Menu #4). The reset control signal will display on Menu #14, item line "Reset Sig". The reset schedule is linear and may be determined using Figure 7, Leaving Water Reset, below.
Terminals #134 and #135 on TB7 are the field wiring 4-20mA remote reset terminal. See the field wiring diagrams in the back of this manual for more detail.
OMRCPMICRO 19
Figure 7, Leaving water reset
Ice (remote reset signal)
When in "Ice" mode, all compressors will run 100% loaded (that is no unloaders energized) to make certain that compressors cool appropriately. As a result, the number of stages in "Ice" mode will equal the number of compressors. Use approved solutions in the chilled water loop to protect the system to at least 15°F lower than the ice setpoint. When Leaving Evaporator Water (Lvg Evap") is set less than 34°F, "Ice" mode must be used. Cylinder unloading of compressors when suction temperatures fall below 25°F will prevent the compressor motor from cooling adequately. The lowest Leaving Water Ice set point for McQuay reciprocating chillers is 21°F. With an Ice set point of 21°F, saturated suction temperatures of 12°F or 13°F are typical. This is the lowest recommended saturated suction temperature for McQuay reciprocating products.
Most ice storage applications require dual reset control. Use terminals #134 and #135 on TB7 for field wiring 4­20mA remote reset connections. See the field wiring diagrams at the end of this manual for more detail.
IMPORTANT
If a 4-20mA signal device is not available, a dual contact is required, then a dry contact
between terminals #215 and #135 may be used to initiate reset. When using a dry contact,
"open" will maintain the ice set point and "close" will initiate a full reset.
If the chiller is to be used for ice storage, select the "Ice" option in Menu 14. "LvgWater Spts", "ResetOpt=". To calculate the leaving chilled water set point, the control band (Menu 14 "CntrlBand=") and shut down delta-T (Menu 14 ShutDn D-T=") must first be selected. The equation to determine leaving chilled water temperature:
Lvg Evap = Desired Ice Temp + 1/2"CntrlBand + " "ShutDn D-T"
Lvg Evap = 21°F + 1/2 (4) + 1.5°F
LvgEvap = 21 +2+ 1.5
Lvg Evap = 24.5
For day operation the maximum chilled water reset (Menu 14 "MaxChWRst=") is added to the "Lvg Evap" as calculated above to reach the desired day operating leaving chilled water temperature.
When the Ice option is selected, the resetting of the leaving chilled water set point (during day operation) via the 4-20mA input is not a functional option. To retain the option, the set points in Menu 14 must be changed by a Building Automation System through our MicroTech Open Protocol Monitor Software.
When a 4-20mA signal is used to initiate ice reset, if a signal less than 4mA is received, nothing happens—the ice mode temperature will be maintained. When a signal of 4mA or more is received, the unit changes to a non­ice building mode temperature. The control signal will be displayed under "Reset Sig" on Menu #14.
The alarm setpoints (see Menu 22) will also need to be adjusted. The following is an example of alarm set points for a typical ice operation:
20 OMRCPMICRO
1. "Frz Stat": Set to the saturated refrigerant pressure that corresponds to a temperature equal to 13.5°F
below the ice set point. For example, if the ice set point is 23°F, the "Frz Stat" would be set at 33 psig, (which is 23°-13.5° = 9.5°F; 33 psig is R-22 saturation pressure at 9.5°F).
2. "Frze H 2O": Set at least 4°F below the ice set point, but not lower than the freezing point of the solution.
In this example, the "Frze H2O" would be set at 19°F.
3. "LP CutOut": Set 8 to 10 psi below the "Frz Stat" setting but never below 20 psig.
4. "LP Cutin": Set 15 to 20 psi above "LP CutOut".
5. FreezeTimer ("FreezeTim") and Condenser High Pressure ("Hi Press"): Do not need to be adjusted.
Network
Based on the Maximum Chilled Water Reset Set Point ("MaxChWRst"), the "Network" option allows a signal to be sent that reflects 0 to 100% reset of the Leaving Chilled Water Set Point ("Lvg Evap") for chillers (except Ice mode) or Leaving Condenser Water Set Point ("Lvg Cond") for THRs. This option functions similar to the 4-20mA option.
OMRCPMICRO 21
Remote Demand Limiting
Demand limiting applies to ALR and WHR chillers only. Remote demand limiting may be accomplished by connecting to terminals #131 and #132 on TB7. A 4-20mA signal is required. Based on the 4-20mA signal, demand limiting will cause the chiller to limit the total number of stages regardless of the amount of cooling actually required. A signal of 4mA or less allow all stages to operate while a 20mA or more will allow only one stage to operate. The effect of the 4-20mA signal may be determined using Figures 8, 9 and 10. Under Menu #18, demand limits, the number of stages allowed by demand limiting will be displayed as well as the actual remote demand limit signal in milliamps.
Figure 8, Remote demand limit, 4-stage unit
Figure 9, Remote demand limit, 6-stage unit
Figure 10, Remote demand limit, 8-stage unit
22 OMRCPMICRO
THR Heat/Cool Changeover
On THR heat pumps, instead of the demand limit input, a 0 to 5 volt signal from a front panel unit-mounted switch allows the unit to run in heat and cool modes. Five volts is obtained at terminal #215, wired through the unit mounted switch and then connected to terminal #132 on TB7. When the switch is "open", the unit is in heating mode. When the switch is "closed" the unit is in cooling mode. Menu #18 shows which mode the unit is in. "ChVTmp Sig = Temp" denotes heating mode and "Chl/Tmp Sig = Chil" denotes cooling mode. In chiller mode, the unit is controlled by the leaving evaporator water. To operate the unit as a Templifier, choose "ChlTmp" under Item E of Menu #23. See Normal Sequence of Operation section of this manual for more information.
Soft Loading
Soft loading limits the number of available stages when the unit is started to prevent excessive power consumption and possible overshoot of the leaving water temperature set point. Soft loading is in effect whenever the unit is started from an "off" cycle. This option is selectable and available in Menu 15.
On initial start-up, the controller will run the chilled water pump and sample the loop water temperature for a time equal to the Load Delay set point ("LoadDelay") on Menu 15. If cooling or heating is required at the end of the time delay, then the liquid line solenoid valve will be open and refrigerant will flow. When the evaporator refrigerant pressure rises above the LP Cut In Set Point ("LP CutIn" see Menu #22), the controller will start the first compressor. On entering the "Stage" the controller starts a countdown timer to indicate how long the unit has been in the cool or heat stage mode. The number of stages allowed during soft loading is determined by the Soft Load Maximum Stages ("SoftLdMaxStg" see Menu #15). The duration of the soft load sequence is determined by the Soft Load Timer ("SoftLoad" see Menu #15). If the Soft Load Timer is set to zero, no soft loading will take place. When the soft load option is enabled, any time remaining in the Soft Load Timer will be displayed on Menu 15 under item "Time Left".
The following set points may be adjusted on Menu 15:
Ø Soft Load: This is the amount of time soft loading will be in effect after the controller begins staging. If set
to zero, no soft loading is cancelled.
Ø SoftLdMaxStg: Determines the maximum number of cooling or heating stages which may be energized
while soft loading is in effect.
Ø LoadDelay: The amount of time allowed for the controller to sample the loop water temperature before
initiating cool or heat stages.
OMRCPMICRO 23
Compressor Control
The compressor staging logic uses an adjustable control band and interstage timer to determine the correct number of cooling or heating stages to activate. A project-ahead temperature calculation and a maximum pull down rate provide stable operation. Compressor set points are shown on Menu 16.
The Control Band is the temperature range on either side of the active leaving water set point that must be exceeded for a stage change to occur. When in chiller mode and after the unit has started, the controller will stage-up when the leaving water temperature rises to the Leaving Chilled Water Set Point plus half of the Control Band. The controller will stage-down when the leaving water temperature lowers to the Leaving Chilled Water Set Point minus half the Control Band. The THR, controlled from leaving condenser water, stages up and down in the reverse order of a unit in chiller operation.
The adjustable compressor Interstage Timer set point ("InterStg", see Menu #16) sets the time delay between the current cooling or heating stage and the next stage-up request. The compressor stage-down time delay is fixed at a 1/3 ratio of the stage-up setting. For more information on staging, refer to the "Normal Sequence of Operation" section on page 37 of this manual.
The controller performs a project-ahead temperature calculation to protect against an overshoot condition when the leaving water temperature is outside the control band. Project-ahead calculation also moderates the controller's response to a rapid increase and decrease in leaving water temperature. During cooling mode, if the chilled water temperature is above the control band and the project-ahead calculation has determined that the chilled water temperature will fall below the control band within 240 seconds (4 minutes), then the controller will unload the compressors and stage-down the unit until the condition is no longer true. For THRs in the heating mode, if the project-ahead calculation has determined that the leaving condenser water temperature will rise above the control band wishing 240 seconds (4 minutes), then the controller will unload the compressors and stage-down the unit until the condition is no longer true.
As additional protection against overshooting the unit set point, the controller uses the maximum pull down rate ("MaxPullDn", on Menu #14) to determine if the leaving water temperature is pulling down or up too rapidly. Every minute, the controller checks the leaving water temperature and compares the temperature to the last reading. If the Pull Down Rate is exceeded, the controller delays additional stages. Maximum Pull Down ("MaxPullDn", on Menu #14) default setting is 0.5°F. This setting may be changed on Menu 14, Lvg Evap Spts,.
The MicroTech soft loading feature will also guard against problems of overshooting the set point. The Soft Load ("SoftLoad" on Menu #15) default setting is 20 minutes up to stage 4 of cooling and heating stages. See "Soft Loading" section of this manual for more information.
The Interstage Timer ("InterStg" on Menu #16) default setting is 180 seconds for cooling and heating stages. Interstage timers (anti-cycle) for compressors are 5 minute stop-to-start and 15 minute start-to-start.
24 OMRCPMICRO
Lead-Lag of Refrigerant Circuits
Automatic
The controller provides automatic lead-lag of refrigeration circuits. The circuit having the fewest number of starts on all compressors in the circuit will be started first. Changes to circuit capacity will be made by changing the position of the compressor unloaders when applicable. Compressors will be selected by changing unloader status. This prevents short-cycling of compressors when the cooling load is low. If both circuits are operating and a stage-down to one circuit is required, the circuit with the most operating hours will cycle off first.
Manual
The operator may manually select the lead refrigerant circuit or have the controller automatically select the lead refrigerant circuit to equalize compressor hours. Automatic lead-lag may be defeated by selecting circuit #1 or circuit #2 as the lead circuit ("Lead Circuit" Menu 16).
Manual Operation
Manual operating modes are available to facilitate setup and troubleshooting of the unit. Any of the following manual modes may be selected from the Control Mode Menu.
ManualOff: Manual unit off. Auto1Off2: Automatic Circ #1, Circ #2 off. Auto2Off1: Automatic Circ #2, Circ #1 off. ManualStaging: Manual Staging, Circ #1 & 2.
Note: These manual settings are intended to aid in troubleshooting and should not be considered to be normal operating modes. The equipment should not be left unattended during manual operation as the automatic staging controls are disabled. The chiller will remain in the manual mode until Automatic operation is selected.
OMRCPMICRO 25
Unit Status Modes
The operating status of the unit is displayed on the keypad/display when the information is requested by the operator. Description of each Unit Status Mode are listed below.
"Off: Remote SW" mode
Upon start-up, the panel will check the "Remote Stop Switch" digital input. If the switch is open, the controller will be in the "Off: Remote SW" mode. Note that from the factory, the unit will ship with a mechanical jumper between the field terminals. If remote stop/start control is desired, remove jumper between terminals 140 and
141.
"Off: Time Clock" mode
If the controller has been commanded to an off state via the internal time clock (Menu 20), the mode will be "Off: Time Clock". Note that if a customer wishes the unit to run 24 hours per day, the eight day clock must be set to start at 00:00 and stop at 23:59 for all days.
"Starting" mode
If the remote stop switch is closed and the internal time clock is calling for the unit to run, the controller will initiate "Starting" mode.
"Wait for Flow" mode
The chilled water pump output relay is energized any time the unit is enabled. The controller will check for the presence of chilled water flow via the normally open flow switch. If flow is not proven within 30 seconds, the alarm "LossofWater Flow" will be activated and the unit will remain in the "Waiting for Flow" mode until water flow is proven. Once flow is established, the alarm will automatically be cleared.
Loss of water flow during unit operation will cause the unit to log the alarm and return to the "Waiting for Flow" state. When chilled water flow has been re-established, the alarm will again automatically be cleared.
"Wait for Load" mode
With water flow established, the controller will wait for a period of time equal to the "Load Delay" set point to determine if the water loop is above or below the current active water set point. In chiller mode, if leaving chilled water temperature is above the leaving chilled water set point plus 1/2 of the control band plus the start-up delta-T, the controller will enter the stage mode otherwise the controller will wait until the end of the currently scheduled run period.
In heating mode (Templifier only), if the leaving condenser water temperature is below the leaving condenser water set point minus 1/2 the control band minus the start-up delta-T, the controller will enter the stage mode.
"Stages 1-8"
This is the normal mode the unit will be in while cooling or heating. The number of currently active stages will be displayed. The stage is only an indicator of system capacity and does not indicate which compressors or circuits are on.
"Off: Alarm"
This is the mode which will be displayed when a circuit is in an alarm condition which means no cooling or heating on that circuit is possible. Refer to the System Alarms and Circuit Alarms sections in this manual for additional details.
"Off: Manual" mode - If the control mode of the unit is "Manual Off" the unit status will be displayed as "Off: Manual" mode.
"Off: PumpDnSw's" - If the pumpdown switch digital inputs for both circuits are in the "manual " position, the mode of the unit is "Off: PumpDnSw's".
"Manual Stage" - If the control mode of the unit is "Manual Stage" the unit status will be displayed as "Manual Stage".
26 OMRCPMICRO
"Stage Up", "Stage Down" - These are momentary operating modes indicating a stage up or stage down is being initiated by the controller.
"Off: System Sw" mode - Upon start-up the panel will check the front panel "System Switch" position. If the switch is in the "stop" position, the mode will be "Off: System Sw".
Circuit Status Modes
The operating status of each refrigeration circuit is displayed on the keypad/display when the information is requested by the operator. Descriptions of each Circuit Status Mode are listed below.
"Off:System Sw" - Off due to System Switch. "Off: Manual Mode" - Off due to Control Mode Set Point. "Off: Alarm" - Off due to Alarm Condition. "Off:PumpDnSw" - Off, the circuit pumpdown switch is in the manual position. "Off: CycleTime" - Off due to anti-cycle timers. "Off: Ready" - Off Ready to start or Standby. "Pumping Down" - The circuit is in the process of pumping down, the solenoid valve is closed. "Open Solenoid" - A request has been made for the circuit to be energized for cooling or heating, the solenoid
is open and the controller is waiting for the pressure to rise above the LPCutIn set point. "% Capacity" - Circuit is running, all operating conditions are normal. The circuit percent capacity is
displayed.
OMRCPMICRO 27
Loading...
+ 61 hidden pages