McQuay ALR-012A Installation Manual

BULLETIN NO. IM 207
MAY, 1980
INSTALLATION AND
MAINTENANCE DATA
GROUP
PACKAGED AIR COOLED WATER CHILLER
TYPE ALR-012A THRU 030A
McQuay-PERFEX Inc.
13500 Industrial Park Blvd., P.O. Box 1551, Minneapolis, Mn. 55440
@

INTRODUCTION

McQUAY
automatic water cooling units that include the latest in engineered components arranged to provide a compact and efficient unit. Each unit is assembled before evacuation, charging and testing. Each unit consists of an air cooled condenser with integral subcooler section, unloading compressor and replaceable tube, shell-and-tube evaporator.
ALR SEASONPAK air cooled water chillers are

NOMENCLATURE

A L R-030 A-S
Air Cooled Condensing
Reciprocating Compressor

INSPECTION

When the equipment is received, all items should be
carefully checked against the bill of lading to insure a
complete shipment. All units should be carefully inspected
for damage upon arrival. All shipping damage should be

INSTALLATION

NOTE: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. CAUTION: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from anything other than the base, and block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet (See Figure 1). Do not let the lifting fork damage the refrigerant piping within the cabinet.
To lift the unit, 2 provided in the base of the unit. Spreader bars and cables should be arranged to prevent damage to the condenser coils or unit cabinet (See Figure 2).
-1/2-inch
diameter lifting holes are
Liquid line components included are manual liquid line shutoff valve, replaceable core filter-drier, liquid line solenoid valve, sightglass/moisture indicator and double diaphragm hydraulic element thermal expansion valve. Other features include: compressor crankcase heater, an evaporator heater for chilled water freeze protection and recycling pumpdown during “on” or “off” seasons.
Nominal Capacity (Tons)
reported to the carrier and a claim should be filed. The unit
serial plate should be checked before unloading the unit to
be sure that it agrees with the power supply available.
FIGURE 1. SUGGESTED PUSHING ARRANGEMENT
r
BLOCKING

LOCATION

Due to vertical condenser design, it is recommended that
the unit be oriented so that prevailing winds blow parallel
to the unit length, thus minimizing effects on condensing pressure. manner, a wind deflector should be constructed.
mounted on a roof or concrete slab (ground level installation). Roof-mounted units should be installed level on steel channels or an l-beam frame to support the unit above the roof. Use of vibration pads or isolators is
recommended. The roof must be strong enough to support the weight of the unit. See Table 1 for unit weights. Concrete slabs used for unit mounting should be installed level and be properly supported to prevent settling. A one-piece concrete slab with footings extended below the frost line is recommended.
TABLE 1.
If it is not practical to orient the unit in this
Units are designed for outdoor application and may be
UNIT WEIGHTS
ALR MODEL
012 015 020 025 030
OPERATING WEIGHT
1364 1661 1883 2012 2330
(LBS.)
GOOD PUSHING ARRANGEMENT -CABINET DAMAGE UNLIKELY
FIGURE 2.
PAGE 3

WATER PIPING

PIPING PRACTICES

5.
Due to the variety of piping practices; it is advisable to follow the recommendations of local authorities. They can supply the installer with the proper building and safety
codes required for a safe and proper installation.
Basically, the piping should be designed with a
minimum number of bends and changes in elevation to
keep system cost down and performance up. It should
contain:
Vibration eliminators to reduce vibration and noise transmission to the building.
Shut-off valves to isolate the unit from the piping system during unit servicing. prevent moisture condensation and possible damage to the
Manual or automatic air vent valves at the high points
of the system. Some means of maintaining adequate system water
pressure (e.g., expansion tank or regulating valve).

COOLER WATER CONNECTIONS

Temperature and pressure indicators located at the unit to aid in unit servicing.
6.
A strainer or some means of removing foreign matter from the water before it enters the pump. It should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). The use of a strainer will prolong pump life and thus keep system performance up.
Prior to insulating the piping and filling the system, a
preliminary leak check should be made.
Piping. insulation should include a vapor barrier to
building structure. It is important to have the vapor barrier on the outside of the insulation to prevent condensation within the insulation on the cold surface of the pipe.
It is suggested that horizontal water piping connections to the cooler be made through the holes provided in the base frame. Two suggested arrangements that will align the
7. Vertical connections may be made to the cooler through
the open base using
2-inch
IPS
90-degree
elbows. Figure 10
gives the necessary dimensions for either piping method.
piping with the base frame holes are shown in Figures 6 and
FIGURE 6.
FIELD
P-
2” IPS WATER PIPE
NOTE: FOR INSTALLING A CHILLED WATER THERMOSTAT IN RETURN WATER LINE A REDUCING TEE SE USED INSTEAD OF A 2” IPS 90 ELBOW. SEE FIGURE 8.
-
COOLER WATER CONNECTIONS
INSTA
2”
IPS STREET ELBOW
BASE FRAME
IPS WATER CONNECTION
(2” x
1/2” x
2”)
MAY

CHILLED WATER THERMOSTAT

The chilled water thermostat is mounted inside the unit
FIGURE 7.
FIELD INSTALLED
I
L
FIGURE 8.
OOLER WITH 2” IPS CONNECTION
IPS
45’
ELBOW
BASE FRAME
2” IPS WATER PIPE
THERMOSTAT SENSOR INSTALLATION
control center. The sensor must be installed in the return water line as shown in Figure 8. The thermostat sensor should be insulated after installation.
REDUCING TEE
THERMOSTAT
12”~ l/Z” x 2”)
BULB
W
FIELD INSTALLED
CAUTION: Thermostats have maximum operating
temperature limits of
125OF on return water. Temperatures
exceeding these limits may damage the controls.
ETURN
WATER
THERMOSTAT SENSO EVAPORATOR
RETURN WATER
LINE
CONNECTION OF
PAGE 5

FLOW SWITCH

A water flow switch or pump starter interlock is required to insure that there will be adequate water flow and cooling load to the evaporator before the unit can start. This will safeguard against slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up.
A flow switch is available from
ordering number 860-175033X-00. It is a “paddle” type switch and adaptable to any pipe size from l-inch to 6-inch nominal. Certain minimum flow rates are required to close
McQUAY
under
the switch and are listed in Table 4. Installation should be as shown in Figure 9.
Electrical connections in the unit control center should
be made at terminals 12 and 21. The normally open
contacts of the flow switch should be wired between these
two terminals. There is also a set of normally closed
contacts on the switch that could be used for an indicator
light or an alarm to indicate when a “no flow” condition
exists.
TABLE 4. FLOW SWITCH MINIMUM FLOW RATES
NOMINAL
PIPE SIZE
(INCHES)
1
l/4
1
1/2 2
MINIMUM REQUIRED
FLOW TO ACTIVATE
SWITCH (GPM)
9.80
12.70
18.80
FIGURE 10. DIMENSIONAL DRAWING
68.60 OPENING (AIR
WATER CONN.
CLEARANCE HOLES
3.62 DIA.
(2)
OUTLET SCREEN NOT SHOWN)
-
FIGURE 9.
FLOW SWITCH
NO RESTRICTIONS 5
PIPE DIAMETERS MIN.
AFTER SWITCH
FLOW DIRECTION
MARKED ON SWITCH
NO RESTRICTIONS 5 PlPE DIAMETERS MlN BEFORE SWITCH
(FIELD MOUNTED)
OPTIONAL
PAGE 6
#
14.761
LIFTING HOLES
2.50 DIA.
(2
EACH SIDE)
MOUNTING HOLES,
.750 DIA. (2 EACH
SIDE)
ALR
UNIT SIZE
012A-S 015A-S 020A-S 025AS 030A-S
POWER CONN.
J
/
k
46.00
MOUNTING HOLES
DIMENSIONS & CONNECTIONS
A
50.60
50.60
65.60
65.60
80.60
DIMENSIONS (INCHES)
B
48.88,
Inlet
36.88,
Inlet
36.88, Inlet
36.88, Inlet
Outlet
14.02,
C
7.20,Outlet
7.20.
Outlet
7.20,
Outlet
7.20,Outlet
18.06, Inlet
WATER CONN. SIZE
2”I.P.S. 2”I.P.S.
I
.P.S.
2” 2”I.P.S. 2”
I
.P.S.

REFRIGERANT

ADDING REFRIGERANT CHARGE

On systems that have been previously charged with
refrigerant, an insufficient charge is indicated by bubbling in the sightglass. On uncharged systems the system should be leak tested and evacuated before charging.
Upon charging a system the discharge and suction shut-off valves on the compressor should be open and there should be normal water flow through the cooler.
CAUTION: Do not make any safety controls
inoperative during the charging operation; cooler damage from freezing may result.
Back seat the liquid line shut-off valve and connect the
1.
charging hose to the
2.
Install pressure gauges and review start-up instructions.
3.
Purge the charging hose and open the charging cylinder
to allow refrigerant into the system.
When removing the refrigerant on water chiller systems to
prevent freeze-up, either drain the water or circulate the
water. If water cannot be drained, make sure the cooler
heater is energized; do not remove refrigerant rapidly since this can cause freeze-ups. Have a sufficient number of refrigerant containers at hand and a scale for weighing them. The containers should be clean, dry and empty.
To transfer the refrigerant to a container connect the
gauge manifold from the compressor discharge valve service
port to the container and purge the lines. Note the capacity
l/4-inch
flare connection.

REMOVING REFRIGERANT CHARGE

4.
Turn the liquid line shut-off valve in three turns to permit a back flow of refrigerant into the subcooler.
After refrigerant stops flowing into the system, close
5. the liquid line shut-off valve. Start the compressor to charge the system.
6.
If the amount of refrigerant has been predetermined,
add this amount and check the sightglass afterward. If
the amount of charge is unknown, every five minutes close the charging cylinder valve, open the liquid line shut-off valve and check for proper charge by
examining the sightglass. Continue charging and checking the sightglass until it
NOTE: Fluorocarbon refrigerants should not be
released to the atmosphere. For a means
to the following section.
of the container. Place the container in ice to cool the container so the fusible plug does not melt as the condenser
condenses. Operate the compressor normally. Turn the
discharge service valve in three turns to open the service port. Open the container valve and the gauge manifold. Do not close off the discharge valve to the condenser; discharge gas can enter the container and condense. Frequently weigh the container so as not to overfill. When the container is filled use additional ones.
clears.
I
of
recovery, refer

FIELD WIRING

Wiring should be done in accordance with all applicable codes and ordinances. Warranty is voided if wiring is not in
accordance with specifications. An open fuse indicates a short, ground or overload. Before replacing a fuse or restarting a compressor or fan motor, the trouble must be found and corrected.
Copper wire is required for all power lead terminations
at the unit.
All unit sizes are set up as standard for separate 115
volt power supply circuits for the control circuit and cooler
heater. The control circuit only, or both the control circuit
-
and the cooler heater, can be powered off the main unit power supply if the optional control circuit transformer is ordered. It may be desirable, however, to have the unit
cooler heater on a separate disconnect switch from the
main unit power supply so that the unit may be shut down without defeating the freeze protection provided by the cooler heater.
A standard feature on all ALR units is COPS
(Controlled Override of Pump Shut-down), a system for
interlocking
chiller control system. Relay RI9 is wired into the unit
control circuit so that a time clock and/or ambient thermostat can be connected to a pair of terminals (14 and
15) inside the unit control center. The time clock can energize a pump starter. Once the pump starts, the flow switch and/or pump interlock will close and energize that part of the control circuit that will allow the unit to start.
This feature makes it possible to start the chilled water pump and the chiller simultaneously only when cooling is required. For recycling
cooling, a relay (energized by the low pressure control) is also wired into this circuit to start the pump, close the flow switch and pump down the unit.
NOTE: If a time clock, ambient thermostat and/or remote on-off switch are not used, terminals 14 and 15 must be
Figure 11 shows typical field wiring that is required for unit installation.
the field supplied chilled water pump into the
pumpdown without a demand for
jumpered together before the unit will start.
PAGE 7
TABLE 6.
COMPRESSOR & CONDENSER FAN MOTORS
ALR
UNIT SUPPLY
SIZE
012A
015A
020A
025A
030A
NOTES:
ELEC.
(1)
208 230
380 460
208 230
380 460
208 230
380 460
208
230 380
460
208 230
380 460
1. Voltage limits:
RATED LOAD AMPS (2)
COMP. FAN MOTORS
44.0 4.4
44.0 4.4
22.0 2.4
22.0 2.4
64.0 4.4
64.0 4.4
32.0 2.4
32.0 2.4
80.0 4.4
80.0
41.0 2.4 41 .o
98.0 4.4
98.0 4.4
53.0 2.4
53.0 2.4
121.0 4.4 121 .o
61 .O 61 .O
Nameplate 208-Max. Nameplate 230-Max. Nameplate 380-Max. Nameplate 460-Max.
FAN MOTOR
(EACH)
4.4
2.4
4.4
2.4
2.4
229V,
253V, Min. 418V, 506V.
NO.
OF
MOTORS (EACH)
3 3
3 3
3 3
3 3
3 3
3 3
3
3 3 3
3 3
3 3
Min. 187V.
207V. Min. 342V. first winding. Min. 414V.
FAN
8.2
8.2
7.5
7.5
8.2
8.2
7.5
7.5
8.2
8.2
7.5
7.5
8.2
8.2
7.5
7.5
8.2
8.2
7.5
7.5
2. Compressor rated load amps are for wire sizing purposes only
3. Compressor locked rotor amps for part-winding start is for the
ACROSS-THE-LINE-START
do not reflect normal operating current draw.
LOCKED ROTOR AMPS
PART-WINDING-START
COMPRESSOR
228 _ 228
114 114
308 188 308 188
154 _ 154 _
428 250 428 250
214 _ 214
470 292 470 292 235
235 _ 565 340
565 340 283 _
283
COMPRESSOR
_
_
-
and
START-UP & SHUT-DOWN

PRE START-UP

With all electric disconnects open, check all screw or lug
1.
type electrical connections to be sure they are tight for good electrical contact. Check all compressor valve con-
nections for tightness to avoid refrigerant loss at start­up. Although all factory connections are tight before
shipment, some loosening may have resulted from ship-
ping vibration.
2.
Inspect all water piping for flow direction and correct
connections at the evaporator.
3.
Open all water flow valves and start the chilled water
pump. Check all piping for leaks and vent the air from the evaporator as well as from the system piping. Flush the evaporator and system piping to obtain clean,
non-corrosive water in the evaporator circuit.
4.
Check to see that the thermostat water temperature sensor is installed in the return water line (return to chiller). The sensor well should be full of heat conducting compound and the sensor should be secured
in the well with the retaining clip provided.
5.
Check the compressor oil level. Prior to start-up, the oil
level should cover at least
6.
Check the voltage of the unit power supply and see that
it is within the
*IO%
voltage unbalance must be within 42%.
7.
Check the unit power supply wiring for adequate ampacity and a minimum insulation temperature rating of 75c.
8.
Verify that all mechanical and electrical inspections have been completed per local codes.
1/2
of the oil sightglass.
tolerance that is allowed. Phase
9.
See that all auxiliary control equipment is operative and that an adequate cooling load is available for initial start-up.
10. Making sure control stop switch pumpdown pumpdown,”
switches PSI and PS2 are on “manual
throw the main power and control discon-
S1
is open (off) and
nect switches to “on.” This will energize the crankcase heaters. Wait a minimum of 12 hours before starting unit.
CAUTION: Most relays and terminals in the unit con­trol center are hot with connect on.
S1 and the control circuit dis-

START-UP

Double check that the compressor suction and dis-
1.
charge shut-off valves are back seated. Always replace valve seal caps.
Open the manual liquid line shut-off valve at the outlet
2. of the subcooler.
Allow the crankcase heater to operate for at least eight
3. hout
s
prior to start-up.
Check to see that the
4. “manual pumpdown”
switch
5.
Adjust the dial on temperature controller
(S1)
is in the “on” position.
pumpdown
position and the control stop
desired chilled water temperature. Start the auxiliary equipment for the installation by
6. turning
on the time clock, ambient thermostat and/or
switch PSI is in the
TC1
to the
PAGE 9
Loading...
+ 18 hidden pages