McQuay ALP-159A Maintenance Manual

Page 1
BULLETIN NO. IM
173
JULY 1978
INSTALLATION AND
MAINTENANCE DATA
PACKAGED AIR COOLED CONDENSING UNIT
TYPE ALP-067A THRU 159A
@)
Page 2
NOTICE:
Installation and maintenance are to be performed only by
qualified personnel who are familiar with local codes and
regulations,
and experienced with this type of equipment.
CAUTION:
Sharp edges and coil surfaces are a potential
injury hazard.
Avoid contact.
page
2
Page 3
Page 4
Nomenclature
PROPELLER FANS LOW POWER CONSUMING AIR COOLED CONDENSER
AL
-
089 A D
REFRIGERANT CIRCUITS
(D=Dual;
S=Single)
DESIGN VINTAGE
NOMINAL CAPACITY (TONS)
Inspection
When the equipment is received,
all items should be carefully checked
against the bill of lading to insure a complete shipment.
All units
should be carefully inspected for damage upon arrival.
All shipping
damage should be reported to the carrier and a claim should be filed. The unit serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available.
INSTALLATION
Handling Care should be taken to avoid rough handling or shock due to dropping
the unit.
Do not push or pull the unit from anything other than the
base,
and block the pushing vehicle away from the unit to prevent
damage to the sheet metal cabinet.
(See Figure 1.)
FIGURE 1
SUGGESTED PUSHING ARRANGEMENT
GOOD PUSHING ARRANGEMENT
CABINET DAMAGE UNLIKELY
POOR PUSHING ARRANGEMENT
CABINET DAMAGE LIKELY
page
4
Page 5
Never allow any part of the unit to fall during unloading or moving as this may result in serious damage.
To lift the unit,
2+"
diameter lifting holes are provided in the base
of the unit.
Spreader bars and cables should be arranged to prevent
damage to the condenser coils or unit cabinet.
(See Figure 2.)
FIGURE 2
TABLE 1
SUGGESTED LIFTING ARRANGEMENT
SPREADER BAR
REQD.
-MUST USE THESE RIGGING HOLES
(N
OTE
CONTROL 60x
L~cATI~NI
SHIPPING WEIGHTS
ALP UNIT SIZE
UNIT WEIGHT
(Ibs)
067ASlD
4125
078ASlD
4308
089A
4963
106A
5134
ALP UNIT SIZE
126A 136A 149A 159A
UNIT WEIGHT
(Ibs) 6021 6095 6873 7202
Location Due to the vertical condenser design, it is recommended that certain
precautions be taken before installation to orient the unit so that prevailing winds blow parallel to the unit length thus minimizing effects on condensing pressure.
If it is not practical to orient
the unit in this manner,
a wind deflecting fence should be consi-
dered.
It is also necessary to provide adequate clearance on all sides of
the unit for service access and satisfactory performance.
At least
60 in.
(1 fan diameter) should be allowed on each side of the unit
for condenser air inlet and compressor removal on units 067
&
078. If parallel units are installed side by side, 120 in. should be al­lowed between units.
This will prevent excessive condensing temper-
atures and enhance system performance and operating economy.
Clear-
ance for service access should be at least 78 in. at the control cen-
ter end for compressor removal on units 089 through 159 and 42 in.
on units 067 and 078.
Allow 36 in.
clearance at the end opposite
the control center for ease of access to bearings and drives.
These
clearances are illustrated in Figure 3.
page 5
Page 6
FIGURE 3 CLEARANCE AROUND UNIT
t
60” MINIMUM CLEARANCE (2)
60”
MINIMUM
CLEARANCE
(2)
NOTE:
(I)
Minimum vertical clearance above unit should be 10
feet.
(2) Clearance to condenser coil must be increased if more
than one side is obstructed or between adjacent units. Consult your
McQUAY
sales representative.
Service Access Each end of the unit must be accessible after installation for peri-
odic service work.
Compressors and manual liquid line shutoff valves
are accessible from the control center end of the unit through re-
movable access panels on unit sizes 089 through 159 and hinged side
access doors on unit sizes 067 and 078.
All operational, safety,
and starting controls are located in the unit control center.
They
are protected by a keylocked,
weatherproof enclosure which contains
internal"dead front"
doors for protection of service personnel from high voltage starting controls while servicing low voltage opera­tional controls.
All resettable or adjustable controls are located
just below the main control center.
There is one resettable control
enclosure on each side of the unit and each enclosure contains con-
trols for compressors on that side of the unit.
Capped connections
for field service gauges are also located inside these enclosures. In addition,
each of these enclosures are removable to improve access
to compressors for field replacement.
The condenser fans, motors,
and drives are accessible through a walk-
in,
keylocked access door.
The access door is located at the end of
the unit opposite the control center.
An internal fan guard is located below the condenser fans and drives on units 089 through 159.
This guard must be removed to service the
fan drives but MUST always be reinstalled when service work is com-
plete.
On unit sizes 067 and 078,
an interlock switch kills power to conden-
ser fans whenever the door is opened for service work on fans or
drives.
CAUTION:
Disconnect all power to the unit while servicing condenser fan drives.
page
6
Page 7
Vibration Isolators Vibration isolators are recommended for all roof mounted installa-
tions or wherever vibration transmission is a consideration.
Table
2 lists spring isolators for all ALP unit sizes.
Figure 4 shows
isolator locations in relation to the unit control center.
Figure 5
gives dimensions that are required to secure each
McQuay
isolator
selection to the mounting surface. Table 3 shows the isolator loads at each location shown in Figure 4
and the maximum loads for each McQuay selection.
TABLE 2
VIBRATION
ISOLATORS
216404B-27 2164046-26
TABLE 3
IS0 LATOR LOADS
page 7
Page 8
Page 9
REFRIGERANT PIPING
General McQuay type ALP condensing units are adaptable to either chilled
water or air handling air conditioning applications.
The only re­striction on applications is that the evaporator be selected for a system using refrigerant 22.
Evaporator Above Condensing Unit Figure 6 shows an installation where the evaporator is installed
above the condensing unit.
It is shown for an air handling instal­lation but all components shown are recommended for chilled water installations except that a refrigerant distributor is not usually required for shell-and-tube evaporators.
FIGURE 6
EVAPORATOR ABOVE CONDENSING UNIT
Legend
a
Filter-drier
b
Solenoid valve
:
Sight-glass/moisture indicator Thermal expansion valve
e
Suction line, pitched toward compressor
f
Liquid line
9
Vibration absorber
Notes:
1. Piping shown is for one circuit only, second circuit is similar.
2. All piping & piping components are by others.
Evaporator Below Condensing Unit Figure 7 shows an installation where the evaporator is installed be-
low the condensing unit.
It is shown for an air handling installa­tion but all components shown are recommended for chilled water in­stallations except that a refrigerant distributor is not usually re-
quired for shell-and-tube evaporators.
Mote that a double suction
riser is shown for this arrangement. Risers
"A + B" are sized so that their combined cross-sectional in­ternal area will allow full load unit operation without excessive pressure drop (see notes, Table 4).
Riser
"B"
is sized to provide
adequate suction gas velocity for proper oil return at minimum load conditions.
This riser becomes effective only when the trap shown
in riser "A"
fills itself with oil.
It should be emphasized that
the trap shown in riser "A"
should be designed to contain a minimum
internal volume to keep the total system oil requirements at a mini-
mum.
Table 4 gives recommended line sizes for both single and double
suction lines and for liquid lines.
page
9
Page 10
Page 11
Page 12
Page 13
Page 14
Figure 9 shows typical field wiring that is required for unit instal-
lation.
Items that require field wiring are:
liquid line solenoids
(SVl & SV2),
optional hot gas bypass solenoid
(SV5)
and the cooling
thermostat as well as the unit power supplies.
FIGURE 9
TYPICAL FIELD WIRING
PBl
DISCONNECT
UNIT MAIN
BY OTHERS--\,,< TERMINAL BLOCK
3pH ---_H
___
POWER
___/-:__
CONI, llNlT
COMPRESSORS
c
AND FAN MOTORS
;BK
SuppLy
_ _
__I’_
-
-
WH
I
\
SEPARATE
II?,“-IOA
LEGEND
POWER FOR CONTROLS
I
‘,‘--
DISCONNECT BY OTHERS
OPTIONAL
FdSEU
i g_ ~~~SLT~OM~~~,~~NNECTION
01
8
A
NOTE
I
TRANSFORMER
FUSE-IO A
0 II
-FLOW SWITCH
(C.W.
SYSTEMS)
irJH_WHlTt
WlhlNG
fNEUT1.
SVl,2-LIOUID ’ INE
SOL. VALVE
REFRIGERANT CIRCUIT I SAFETY AND OPERATING
SVS-HOT
GAS BY PASS
CONTROLS
SOL VALVE
R3,4-COMP.
384 START
TIME
CLOCK;;-
RELAYS
R5,6,7,E
-SAFETY
RELAYS
PSI.2 -PUMPDOWN
SWITCHES
TDl1,12,13-COMP
SEOUEN-
CING TIME DELAYS
Rx-EVAP. FAN INTERLOCK
PREVENTS OPENING SV’S WITHOUT LOAD
RELAYS PROVIDE RECYCLING PUMP
DOWN DURING OFF
SEASON
REFRIGERANT CIRCUIT
2
SAFETY AND OPERATING
CONTROLS
UNIT CONDENSER
FANS
OPERATING CONTROLS
POWER SUPPLY FOR CONTROLS
I
1
I
I
I
PUMP STARTER
PUMP STARTER
CIRCUIT
R9
RIO
NOTE; CIRCUIT SHOWN ASSUMES CONTINUOUS
6
6
T
-C
PUMP
OPERATIIN~FOR
INTERMITTENT
CC. W.
SYSTEMS1
a0 __:
I I
1
PUMP OPERATION CONSULT
McOUAY
I I
I
Thermostat Wiring Since it is impossible for
McQuay to anticipate the type of installa-
tion that an ALP condensing unit may be used on, we do not factory
install a thermostat.
We do,
however,
provide numbered terminals in-
side the unit control center to which a thermostat may be connected. These terminals are shown and labeled "Terminals For Thermostat" on the electrical schematics.
On a two circuit unit it is important to connect the thermostat so that as successive stages of cooling are called for, the compressors
in the unit will be started to alternately increase the condenser load from refrigerant circuit 1 to circuit 2.
This is illustrated
in Table 9.
Figure 10 shows how to install 2 independent four stage thermostats for controlling an 8 stage unit and Figure 11 shows typi­cal field wiring for an 8 stage thermostat.
page 14
Page 15
Page 16
Page 17
Page 18
Flow Switch for Chilled Water Applications
A WATER FLOW SWITCH MUST BE MOUNTED in either the entering or leav­ing water line to insure that there will be adequate water flow and cooling load to the evaporator before the unit can start.
This will
safeguard against slugging the compressors on start up.
It also
serves to shut down the unit in the event that water flow is inter­rupted to guard against evaporator freeze up.
A flow switch is available from McQuay under ordering number
860-
175033x-00.
It is a "paddle"
size from 1" to 6" nominal.
type switch and adaptable to any pipe
Certain minimum flow rates are required
to close the switch and are listed in Table 11.
Installation should
be as shown in Figure 13.
TABLE 11
FIGURE 13
FLOW SWITCH MINIMUM FLOW RATES
NOMINAL
MINIMUM REQUIRED
PIPE SIZE
FLOW TO ACTIVATE
(INCHES)
SWITCH
(GPM)
1
6.00
1
l/4
9.80
1
l/2
12.70
2
18.80
2
l/2
24.30
3
30.00
4
39.70
5
58.70
6
79,20
FLOW DIRECTION MARKED ON SWITCH
1.00 NPT FLOW SWITCH CONNECTION
G%
O:Nl.,.
AFTER
SWiTCH
BEFORE SWITCH
Electrical connections in the unit control center should be made at terminals 11 and 12.
The normally open contacts of the flow switch
should be wired between these two terminals.
There is also a set of
normally closed contacts on the switch that could be used for an in­dicator light or an alarm to indicate when a "no flow" condition exists.
Evaporator Fan Interlock for Air Handler Coil Installations
It is important to interlock the air handler evaporator fan with the condensing unit control center to insure that there will be a cooling load on the evaporator before the unit can start, to prevent com­pressor slugging.
A pair of terminals for each refrigerant circuit
is available in the unit control center for this purpose.
These
terminal numbers are shown in Figure 12.
page 18
Page 19
Control Center
All electrical
controls are enclosed in a weatherproof control cen-
UNIT LAYOUT AND PRINCIPLES OF OPERATION
ter with keylocked,
hinged access doors.
The control center is com-
posed of three separate enclosures.
The upper enclosure is the
largest and contains all of the 208,
230, or 460 volt compressor and
fan motor starting controls.
Also included in this enclosure but
partitioned separately are the exposed terminal type
-
115 volt oper-
ational controls. A "dead front"
cover over the high voltage section
protects service personnel from high voltage starting controls while
servicing low voltage operational controls.
Below the upper enclosure are two smaller,
separate enclosures that
contain 115 volt adjustable or resettable controls.
There is one of
these enclosures on each side of the unit, and each contains controls for the compressors on that side.
Power supply conduits are intended to come into the bottom of the upper enclosure and between the two lower enclosures.
It is recom­mended that the unit disconnect switch be mounted away from the unit but Figure 14 recommends a unit mounting arrangement if the discon-
nect must be unit mounted.
FIGURE 14
POWER CONDUIT ENTRY
CONTROL
~
CENTER
DISCONNECT
Power
into unit
ALP-089A THRU 159A
ALP
-
067A THR U 078A
page 19
Page 20
Page 21
Page 22
Sequence of Operation The following sequence of operation is typical for ALP Seasoncon air
cooled condensing unit operation.
It is written for a 4 compressor
unit,
but where components that apply to the fourth compressor are
referred to,
the equivalent components for the third and second com-
pressors are indicated in parentheses.
With the control circuit power on,
control stop switch
Sl
closed,
and manual pumpdown switches
PSl
and PS2 closed ("Auto." position),
115 volt power is applied through control circuit fuse
Fl
to the com-
pressor crankcase heaters
HTRl
through HTR4, (HTR3,
HTR2),
and also
to the contacts of low pressure switches
LPl
and LP2.
When the remote time clock, ambient thermostat, manual shutdown
switch and/or evaporator fan interlocks energize the thermostatic circuit,
and provided that high pressure controls HP1 and 2 and com-
pressor motor protectors
MPl
through PIP4
(MP3,
MP2) do not sense an
alarm condition,safety relays R5 through R8 (R7,
R6)
are energized
closed applying power to the temperature control thermostat. At this
point the unit will operate automatically in response to the thermo-
stat.
On a call for cooling,
the temperature control thermostat
TCl
ener-
gizes liquid line solenoid valve
SVl,
opening the valve and allowing
refrigerant to flow into the evaporator.
As refrigerant pressure
builds up,
low pressure control
LPl
closes,energizing low pressure
relay
R9
which closes to energize compressor contactor Ml, starting
compressor number 1. Closing relay
R9
contacts also energizes con-
denser fan relay
R17.
Closing its contacts and providing power to
condenser fan motor contactors Mll,12
&
13 on 3 & 4 compressor units,
or
Mll, & 12 on 2 compressor units.
If additional stages of cooling are required, temperature control thermostat
TCl
energizes liquid line solenoid valve SV2 after time
delay relay
TDll
has sequenced closed,to initiate the same starting
sequence in refrigerant circuit number 2.
On 3 and 4 compressor units,if additional cooling is still required,
the third and fourth stages of temperature control thermostat
TCl energize the third and fourth compressors after time delay relays TD12 and TD13 have sequenced closed.
Pumpdown Cycle
As the temperature control thermostat is satisfied, it opens its con-
tacts,
de-energizing liquid line solenoid valve
SVl,
causing the
valve to close. When the compressor has pumped most of the refrig-
erant from the evaporator to the condenser, the low pressure control LPl
opens,shutting down the compressor and condenser fan motors.
Should a closed solenoid valve allow refrigerant to leak to the low side of the refrigerant circuit during unit "off" time, the buildup in pressure will cause the low pressure control to close, energizing the low pressure relay and starting the compressor for pumpdown.
NOTE:
Models ALP-067AS and 078AS have single refrigerant circuits but dual pumpdown switches
(PSl &
PS2). To manually pump
these units down,
it is recommended that both pumpdown
switches be moved to the "man.pumpdown" position simultane-
ously.
page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Page 30
Page 31
Page 32
Page 33
Page 34
Page 35
Page 36
Page 37
START-UP AND SHUT-DOWN
Pre Start--Up
1.
2.
3.
4.
5.
6.
7.
8.
With all electric disconnects open, check
all screw or lug type electrical connections to be sure they are tight for good elec­trical contact.
fore shipment,
Although all factory connections are tight be-
vibration.
some loosening may have resulted from shipping
a) On chilled water installations,
check to see that all water piping is properly connected. b)
Open all water flow valves and start the chilled water pump. Check all piping for leaks and vent the air from the evaporator and system piping to obtain clean,
non-corrosive
water in the evaporator circuit. Check the compressor oil level.
Prior to start-up, the oil level
should cover at least
l/2
of the oil sight glass.
Remove the
(8)
compressor shipping blocks that are attached to the
compressor rails and the base of the unit.
The ALP 067 and 078
do not have shipping blocks. Check the voltage of the unit power supply and see that it is
within the
+
10%
tolerance that is allowed.
Phase voltage unbal-
ance must be within
t
2%.
Check the unit power supply wiring for adequte ampacity and a
minimum insulation temperature rating of 75C. Verify that all mechanical and electrical inspections have been
completed per local codes. See that all auxiliary control equipment is operative and that an adequate cooling load is available for initial start up.
Initial Start-Up
1.
Open the compressor suction and discharge shutoff valves until
back seated.
2.
Always replace valve seal caps. Open the manual liquid line shutoff valve at the outlet of the subcooler.
3.
Check to see that pumpdown switches
(PSl &
PS2)
are in the
Isman.
pumpdown"
position and the control stop switch
(Sl)
is in the
IIon"
position.
4.
Adjust the dial on the temperature controller to the desired
chilled water or leaving air temperature.
5. Throw the main power and control circuit disconnects to the "on"
position.
CAUTION:
Most relays and terminals in the unit control center are hot with
Sl
and the control circuit disconnect on.
6.
Allow the crankcase heaters to operate for at least 8 hours prior to start-up.
7.
Start the auxiliary equipment for the installation.
8.
Start the system by moving pumpdown switches
(PSl &
PS2) to the
"auto.
pumpdown" position.
9.
After system performance has stabilized,
it is necessary that the
"Compressorized Equipment Warranty Form" (form no.
206036A)
be
completed to obtain full warranty benefits.
This form is shipped
with the unit and after completion should be returned to McQuay's
Service Department through your sales representative.
page
37
Page 38
Temporary Shut-Down
Move pumpdown switches
(PSl &
PS2) to the "man. pumpdown" position.
After the compressors have pumped down,
turn off the chilled water
pump or evaporator fan.
It is especially important on chilled water
installations that the compressors pump down before the water flow
to the evaporator is interrupted to avoid freeze up. Start-Up After Temporary Shut-Down
1.
Start the chilled water pump or evaporator fan.
2.
With control stop switch
(Sl)
in the
"on"
position, move pumpdown
3.
switches
(PSl &
PS2) to the '"auto. pumpdown" position.
Observe the unit operation for a short time to be sure that the
compressors do not cut out on low oil pressure.
Extended Shut-Down
1.
Close the manual liquid line shutoff valves.
2.
After the compressors have pumped down, turn off the chilled water pump or evaporator fan.
3.4.Turn off all power to the unit and to the auxiliary equipment. Move the control stop switch
(Sl)
to the
"off"
position.
5.
Close the compressor suction and discharge valves.
6.
Tag all opened disconnect switches to warn against start up be-
fore opening the compressor suction and discharge valves.
Start-Up After Extended Shut-Down
1.
2.
3.
4.
5.
6.
7.
8.
9.
Inspect all auxiliary equipment (pumps, fans, etc.) to see that each device is in satisfactory operating condition. Remove all debris that has collected on the surface of the con-
denser coils.
Open the compressor suction and discharge valves.
Open the manual liquid line shutoff valves. Check to see that pumpdown switches
(PSl 6;
PS2) are in the "man. pumpdown" position. Turn on the electric power to the unit and other parts of the
system. Allow the crankcase heaters to operate for at least 8 hours prior to start-up. On chilled water installations,
start the chilled water pump and
purge the water piping as well as the evaporator.
Check to see that the control stop switch (Sl) is in the
"on"
position.
CAUTION:
Most relays and terminals in the unit control center are hot with
Sl
and the control circuit disconnect on.
10.
Start the unit by moving pumpdown switches
(PSl &
PS2) to the
"auto.
pumpdown" position.
11.
After running the unit for a short time, check the oil level in
each compressor crankcase and check for flashing in the refri-
gerant sight glass.
page 38
Page 39
SYSTEM MAINTENANCE
General
On initial start up and periodically during operation it will be
necessary to perform certain routine service checks.
Among these are checking the compressor oil level and taking condensing, suc­tion and oil pressure readings.
During operation, the oil level
should be visible in the oil sight glass with the compressor run-
ning.
On units ordered with gauges,condensing,suction and oil pressures can be read from the unit control center. The gauges are factory installed with a manual shutoff valve on each gauge
line.
The valves should be closed at all times except when gauge readings are being taken. On units ordered without gauges, the gauge shutoff valves come factory installed inside the unit control
center for convenient connection of service gauges form outside the
unit. Fan Shaft Bearings The fan shaft bearings do not require lubrication at the time the
unit is put into service.
The fan shaft bearings should be greased once a year using STANDARD OIL COMPANY AMCO Multi-Purpose Lithium Grease.
DO NOT OVERLUBRICATE.
Fan Motor Bearings
All fan motors are ball bearing,
pre-lubricated and do not require
the addition of grease at the time of installation.
Periodically,
the ball bearings should be cleaned and the grease renewed, to gain
the ultimate in service from the motor bearings. Extreme care must be exercised to prevent foreign matter from enter-
ing the ball bearings.
It is also important to avoid overgreasing. Only a high grade clean mineral grease having the following charac­teristics should be used.
Consistency: A little stiffer than that
of Vaseline,maintained over the operating temperature range; melting
point preferably over 150C
(302OF);
freedom from separation of oil and soap under operating and storage conditions and freedom from a­brasive matter, acid, alkali and moisture.
Specific greasing instructions are to be found on the label attached
to the unit and should be generally followed. Electrical Terminals CAUTION:
ELECTRIC SHOCK HAZARD,
TURN OFF ALL POWER BEFORE CONTINU-
ING WITH FOLLOWING SERVICE.
All power electrical terminals should be retightened every 6 months,
as they tend to loosen in service due to normal heating and cooling at the wire.
Compressor Oil Level Because of the large refrigerant charge required in an air cooled
condensing unit it is usually necessary to put additional oil into the system.
The oil level should be watched carefully upon initial
start up and for sometime thereafter.
page 39
Page 40
At the present time,Suniso
#3GS
oil is the only oil approved by
Copeland for use in these compressors.
The oil level should be main­tained at about the midpoint of the sight glass on the compressor body.
Condensers
Condensers are air cooled and constructed with
3/8 0-D.
copper tubes
bonded in a staggered pattern into rippled aluminum fins.
No main­tenance is ordinarily required except the occasional removal of dirt and debris from the outside surface of the fins.
Care should be
taken not to damage the fins during cleaning.
Periodic use of the
purge valve on the condenser will prevent the buildup of non-conden-
sables. Refrigerant Sight Glass
The refrigerant sight glasses should be observed periodically.
(A
monthly observation should be adequate.)
A clear glass of liquid in-
dicates that there is adequate refrigerant charge in the system to
insure proper feed through the expansion valve.
Bubbling refriger-
ant in the sight glass indicates that the system is short of refri-
gerant charge. On sight glasses ordered from XcQuay as part of the
"Liquid Line Accessory Kits" listed on page 12, an element inside
the sight glass indicates what moisture condition corresponds to a
given element color.
If the sight glass does not indicate a dry con-
dition after a few hours of operation,
the unit should be pumped down
and the cores in the filter-driers changed.
SERVICE
SERVICE ON THIS EQUIPMENT TO BE PERFORMED BY QUALIFIED REFRIGERATION SERVICE PER-
SONNEL. CAUSES FOR REPEATED TRIPPING OF SAFETY CONTROLS MUST BE INVESTIGATED AND
CORRECTED.
Filter-Driers
To change the filter drier core(s)
,
pump the unit down by moving
pumpdown switches
(PSl &
PS2) to the "man. pumpdown" position.
Turn
off all power to the unit and install jumpers from terminals 21 to
24 and 41 to 44.
Turn power to the unit back on and re-start the
unit by moving pumpdown switches
(PSl &
PS2) to the "auto. pumpdown"
position.
Close the manual liquid line shutoff valve(s) and when
evaporator pressure reaches 0 PSIG,
(Sl)
to the "off" position.
move the control stop switch
This will close the liquid line sole-
noid valve(s) and isolate the short section of refrigerant piping
containing the filter-drier(s).
Remove the cover plate from the
filter-drier shell and replace the core(s).
After core replacement,
replace the cover plate.
A leak check a­round the flange of the filter-drier shell is recommended after the cores have been changed.
page
40
Page 41
Liquid Line Solenoid Valve The liquid line solenoid valves,
which are responsible for automatic
pumpdown during normal unit operation,
maintenance.
do not normally require any
They may, however,require replacement of the solenoid
coil or of the entire valve assembly. The solenoid coil may be removed from the valve body without opening
the refrigerant piping by moving pumpdown switches
(PSl & PS2)
to
the
1'man.
pumpdown" position.
The coil can then be removed from the valve body by simply removing a nut or snap ring located at the top of the coil.
The coil can then be slipped off its mounting stud for
replacement.
Be sure to replace the coil on its mounting stud before
returning pumpdown switches
(PSl
&
PS2)
to the "auto. pumpdown" po-
sition.
To replace the entire solenoid valve,
the unit must be pumped down
by use of the manual liquid line shutoff valve. Thermostatic Expansion Valve
The expansion valve is responsible for allowing the proper amount of refrigerant to enter the evaporator regardless of cooling load. It does this by maintaining a constant superheat.
(Superheat is the difference between refrigerant temperature as it leaves the evapor­ator and the saturation temperature corresponding to the evaporator
pressure.)
Typically,
15F.
superheat should run in the range of
10F
to
On valves purchased through
McQuay,
the superheat setting can be adjusted by removing a cap at the bottom of the valve to expose the adjustment screw.
Turn the screw clockwise (when viewed from the adjustment screw end) to increase the superheat setting and counter­clockwise to reduce superheat.
Allow time for system rebalance af-
ter each superheat adjustment.
INLET
POWER ELEMENT (CONTAINS DIAPHRAGM)
OUTLET
SPRING
ADJUSTMENT SCREW
CAP
page 41
Page 42
Trouble Shooting Chart
PROBLEM POSSIBLE CAUSES
POSSIBLE CORRECTIVE STEPS
1. Main switch open.
1.
Close switch.
2. Fuse blown. Circuit breakers open.
2. Check electrical circuits and motor winding for shorts or grounds. Investigate for possible overloading. Re­place fuse or reset breakers after fault is corrected.
3. Thermal overloads tripped.
3. Overloads are auto. reset. Check unit closely when
Compressor will
unit comes back on
line.
not run
4. Defective contactor or coil. 4. Repair or replace.
5. System shut down by safety devices.
5. Determine type and cause of shutdown and correct it before resetting safety switch.
6. No cooling required.
6. None. Wait until unit calls for
cooling.
7. Liquid line solenoid will not open. 7. Repair or replace coil.
8. Motor electrical trouble 8. Check motor for opens, short circuit, or burn out.
9. Loose wiring.
9. Check all wire junctions, Tighten all terminal screws.
I.
Flooding of refrrgerant Into crankcase. 1. Check setting of expansion valve. Compressor noisy 2. Improper piping support on suction or 2. Relocate, add or remove hangers. or vibrating liquid line.
3. Worn compressor
3. Replace.
1.
Non-condensibles in system.
I.
Purge the non-condensibles.
High Discharge
2. System overcharged with refrigerant.
2. Remove excess.
Pressure
3. Discharge shut off valve partially closed.
3. Open valve.
4. Seasontrol out of adjustment 4. Adjust Seasontrot valves.
5. Fan not running.
5. Check belts and electrical
crrcuit.
I.
Faulty condenser temperature regulation.
I.
Check condenser control operation.
2. Suction shut-off valve partially closed.
2. Open valve.
Low Discharge
3. insufficient refrrgerant in system.
3. Check for leaks. Repair and add charge.
Pressure
4. Low suction pressure.
4. See Corrective Steps for low suction pressure below.
5. Compressor operating unloaded. 5. See Corrective Steps for failure of compressor to load up below.
1. Excessive load.
1.
Reduce load or add additional equipment.
High Suction 2.
Expansron
valve
overfeedrng.
2. Check remote bulb. Regulate superheat.
Pressure
3. Compressor unloaders open.
3. See Corrective Steps below for failure of compressor to load up.
1. Lack of refrigerant.
1.
Check for leaks. Repair and add charge.
2. Evaporator dirty. Plugged
acr
filters.
2. Clean
chemrcally.
3. Clogged
liqurd lrne
filterdrier.
3. Replace cartridge(s).
Low Suction
4. Clogged suction line or compressor suction. 4. Clean
strarners.
Pressure
gas strainers.
5. Expansion valve malfunctioning.
5. Check and reset for proper superheat.
6. Condensing temperature too low.
6. Check means for regulating condensing temperature.
7. Compressor will not unload. 7. See
Correctrve Steps for failure of compressor to
unload.
Compressor will not 1. Defective
capacrty
control.
I.
Replace.
unload or load up. 2. Pressurestat not set for application. 2. Reset pressurestat setting to fit applicatron.
1. Clogged suction oil strainer.
1. Clean.
2. Excessive liquid
rn
crankcase.
2. Check crankcase heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve
operation.
3. Oil pressure gauge defective.
3. Repair or replace. Keep valve closed except when taking readings.
Little or no oil
4. Low oil pressure safety switch defective.
4. Replace.
pressure
5. Worn
011
pump.
5. Replace.
6. Oil pump reversing gear stuck in wrong
6. Reverse
drrectron
of compressor rotation.
position.
7. Worn
bearrngs.
7. Replace compressor.
8. Low oil level.
8. Add oil.
9. Loose fitting on oil lines.
9. Check and tighten system.
10. Pump housing gasket leaks.
10. Replace gasket.
11. Flooding of refrigerant into crankcase.
11. Adjust thermal expansion valve.
Compressor loses
1. Lack of refrrgerant.
1.
Check for leaks and repair Add refrigerant.
oil
2. Excessive compression ring blow-by.
2. Replace compressor.
1. Low voltage during high load conditions.
1. Check supply voltage for excessive
lrne
drip.
2. Defective or grounded wring in motor.
2. Replace compressor motor.
3. Loose power wiring.
Motor overload
3. Check all connections and tighten.
4. High
condensrng
temperature.
4. See Corrective Steps for high discharge pressure.
relays or circuit
5. Power line fault causing unbalanced voltage.
5. Check supply voltage. Notify power compnay. Do not
breakers open
start until fault is corrected.
6. High ambient temperature around the
over-
6. Provide ventilation to reduce heat.
load relay.
7. Failure of second starter to pull in on
part-
7. Repair or replace starter or time delay mechanism.
winding start systems.
Compressor thermal protector switch open.
1. Operating beyond design conditions.
2. Discharge valve partially shut.
3. Blown valve plate gasket.
I. Add facilities so that conditions are within allowable
limits.
2. Open valve.
3. Replace gasket.
page 42
Page 43
IN-WARRANTY RETURN MATERIAL PROCEDURE
Compressor
Copeland Refrigeration Corporation has stocking wholesalers who main­tain a stock of replacement compressors and service parts to serve
refrigeration contractors and servicemen.
When a compressor fails in warranty,
contact your local sales represen-
tative,
or McQuay Warranty Claims Department at the address on the cover of this bulletin. You will be authorized to exchange the de­fective compressor at a Copeland Wholesaler,or an advance replace­ment can be obtained. A salvage credit is issued to you by the whole-
saler on the returned compressor after Copeland factory inspection of the inoperative compressor. Provide McQuay with full details and in­voices and we
will
reimburse the difference.
In this transaction, be
certain that the compressor is definitely defective.
If a compressor
is received from the field that tests satisfactorily, a service charge plus a transportation charge will be charged against its original cre­dit value.
On all out-of-warranty compressor failures,
Copeland offers the same
field facilities for service and/or replacement as described above. The credit issued by Copeland on
the returned compressor will be deter-
mined by the repair charge established for that particular unit. Components Other Than Compressors
Material may not be returned except by permission of authorized fac-
tory service personnel of McQuay, Inc., at Mpls., MN. A "Return Goods"
tag will be sent to be included with the returned material. Enter the information as called for on the tag in order to expedite handling at our factories and prompt issuance of credits.
The return of the part does not constitute an order for replacement. Therefore,
a purchase order must be entered through your nearest McQUAY Representative. The order should include part name, part num­ber,
model number and serial number of the unit involved.
Following our personal inspection of the returned part, and if it is determined that the failure is due to faulty material or workmanship, and in warranty,credit will be issued on customer's purchase order.
All parts shall be returned to the pre-designated McQUAY factory,
transportation charges prepaid.
APPENDIX
STANDARD CONTROLS
Oil Pressure Safety Control The oil pressure safety control is a manually resettable device which
senses the differential between oil pressure at the discharge of the compressor oil pump and suction pressure inside the compressor crank­case.
When the oil pressure reaches approximately 15 PSI above the
crankcase suction pressure,
the pressure actuated contact of the con-
trol opens from its normally closed position.
If this pressure dif­ferential cannot be developed,the contact will remain closed and energize
a heater element within the control.
The heater element warms a normally closed bimetallic contact and causes the contact to open de-energizing a safety relay and breaking power to the compres­sor.
page 43
Page 44
It takes about 120 seconds to warm the heater element enough to open the bimetallic contact thus allowing time for the pressure differen­tial to develop.
If during operation,the differential drops below 10 PSI, the heater element will be energized and the compressor will stop.
The control can be reset by pushing the reset button on the control. If the com­pressor does not re-start,allow a few minutes for the heater element
and bimetallic contacts to cool and reset the control again. To check the control,
pump down and shutoff all power to the unit. Remove the compressor fuses,and install a voltmeter between termin­als
"L"
and
"M"
of the oil pressure control.
Turn on power to the
unit control circuit (separate disconnect or main unit disconnect de-
pending on the type of installation).
Check to see that the control
stop switch
(Sl)
is in the "on" position.
The control circuit
should now be energized but with the absence of the compressor fuses,
__
no oil pressure differential can develop and thus the pressure actu­ated contacts of the control will energize the heater element and open the bimetallic contacts of the control within 120 seconds.
When
this happens,the safety relay is de-energized, the voltmeter read-
ing will rise to
115V,
and the compressor contactor should open. Re-
peated operations of the control will cause a slight heat buildup
in the bimetallic contacts resulting in a slightly longer time for
reset with each successive operation.
LINE (SEE NOTE
1)
NEUTRAL
-
HEATER ELEMENT
CONTACT
L
M
LINE (SEE NOTE 2)
41
NEUTRAL
BIMETALLIC CONTACTS
SAFETY RELAY
NOTES:
1. Hot only when the unit thermostat calls for compressor to run.
2. Hot only when other safety control contacts are closed.
High Pressure Control
The high pressure control is a single pole pressure activated switch that opens on a pressure rise to de-energize the entire control cir­cuit except for compressor crankcase heaters.
It senses condenser pressure and is factory set to open at 380 PSIG and can be manually reset closed at 315 PSIG.
To check the control, either block off
condenser surface or start the unit with fuses in only one fan fuse
block
(FBll)
and observe the cut-out point of the control by watch-
ing condenser pressure rise.
The highest point reached before cut­out is the cut-out setting of the control. CAUTION:
Although there is an additional pressure relief device in the system set at 425 PSIG,
it is highly recommended that
the
"control
stop"
switch
(Sl)
be close at hand in case
the high pressure control should malfunction.
page 44
Page 45
Low Pressure Control
The low pressure control is a single pole pressure switch that closes on a pressure rise.
It senses evaporator pressure and is factory set
to close at 60 PSIG and automatically open at 25 PSIG.
The control
has an adjustable range of 20 in. of Hg.
to 100 PSIG and an adjusta-
ble differential of 6 to 40 PSIG.
To check the control (unit must
be running),
move the pumpdown
switch(es) (PSl
and PS2) to the "man.
pumpdown" position.
As the compressor pumps down condenser pressure
will rise and evaporator pressure will drop.
The lowest evaporator pressure reached before cut-out is the cut-out setting of the control. By moving the pumpdown
switch(es) (PSl
and PS2) to the "auto. pump-
down"
position,
evaporator pressure will rise.
The highest evapora-
tor pressure reached before compressor re-start is the cut in setting of the control.
Fantrol
-
Head Pressure Control
--
Fantrol is a system for progressively turning on or off condenser
fans when they are no longer required.
This isdone to reduce con-
denser capacity (typically in low outdoor ambient temperatures) and is accomplished by a combination of pressure and temperature actuated controls.
The first fan (No.
11) is started by its contactor when
the first compressor in the unit starts.
The second fan (No. 12) is
controlled by a pair of parallel wired pressure switches, one of
which senses condenser pressure in refrigerant circuit No. 1, and
one which senses pressure in refrigerant circuit No. 2.
The third
fan (No.
13-3 fan units only) is controlled by a pair of parallel
wired temperature switches,
one of which senses condenser air inlet temperature for refrigerant circuit No. 1 and one for circuit No. 2. Pressure temperature control set points are indicated below.
j:::_ll
WITH COMPRESSOR WITH COMPRESSOR
To check the cut-in points of the controls,
the unit must initially
be off.
With the unit prepared for start up according to the proce-
dures outlined in this bulletin,
move pumpdown switches
(PSl &
PS2)
to the "auto. pumpdown" position.
Evaporator pressure will begin to
rise and the compressor(s) should start with fan No. 11 starting im-
mediately.
After the compressor(s) starts,
observe condenser pres-
sure as it rises.
When the condenser pressure reaches approximately
270 PSIG, contactor Ml2 should pull in to start fan No. 12.
On 3
fan units, fan No.
13 should start via contactor Ml3 whenever the
ambient air at the condenser inlet reaches 80F. It may be difficult to check the cut-out point of fan No. 13 (on 3
fan units) at the instant it happens, but it should be off whenever the ambient air at the condenser inlet is below 70F.
To check the
cut-out point of fan No. 12,
some means of reducing the load on the
unit must be available or the fan operation and condenser pressure(s)
must be observed as the load drops off naturally.
When the condenser
pressure drops to approximately 170 PSIG,
contactor Ml2 should drop
out to turn off fan No. 12.
page 45
Page 46
OPTIONAL CONTROLS Dampertrol
-
Optional Head Pressure Control
Dampertrol is an optional system for reducing condenser capacity. It
consists of an assembly of damper blades,
linkages and blade operators
installed over the first fan turned on by Fantrol (Fan No. 11) and
arranged to operate as shown.
The blade operators sense condenser
pressure and extend or contract in response to the pressure to open
or close the damper blades as required to maintain adequate conden­ser pressure.
The operators are factory set to begin opening the
damper blades at 170
+
5 PSIG and to be fully open at 250 2 10 PSIG.
To check the damper blade operator pressure settings, the unit should be started with the fuses removed from fans
11
and 13 (on 3 fan units
only).
At condenser pressures below 170 & 5 PSIG, the damper blades
should be completely closed.
As pressure rises above 170
&
5 PSIG,
the damper blades should begin opening and be fully open at 250
+_
10 PSIG.
Leaving the fuses in on fan 12 will prevent head pressure
from becoming excessive since this fan will start after the fully
open setting of the damper operators has been observed.
DAMPERTROL IN OPEN POSITION
/DAMPER
SECTION
1
/-
UNIT CONDENSER
DAMPER SECTION
-
rtz3qf
UNIT CONDENSER
DAMPERTROL IN CLOSED POSITION
page 46
Page 47
Part Winding Start
-
Optional
Part winding start is available on all voltage units and consists of
a solid state time delay wired in series with the contactor that ener-
gizes the 2nd winding of each compressor motor.
Its purpose is to
limit current in-rush to the compressors upon start up.
As each com-
pressor starts,
the contactor for the first motor winding is energized instantly while that for the second motor winding is delayed for 1 second.
Control checkout is best accomplished by observation as each contac-
tor is pulled in to see that the 1 second delay occurs before the second contactor pulls in.
LINE
NEUTRAL
PART WINDING TIME DELAY
1
COMPRESSOR CONTACTOR
(1st
MOTOR WINDING)
LINE
.-%..,
NEUTRAL
A-
COMPRESSOR CONTACTOR
(2nd MOTOR WINDING)
Low Ambient Start - Optional Low ambient start is available on all units as an option with Fantrol
and included automatically with optional Dampertrol.
It consists of a solid state normally closed time delay wired in series with a relay. These are both wired in parallel to the liquid line solenoid valve so that when the solenoid valve is energized by the unit thermostat, the low ambient start relay is also energized through the time delay. The relay has contacts that essentially short circuit the low pres­sure control and allow the compressor to start with the low pressure control open.
After about 2
3/4
minutes,
the time delay will open and de-energize
the relay.
If the system has not built up enough evaporator pressure
to close the low pressure control,
the compressor will stop.
The
time delay can be reset to its original normally closed position by
moving the pumpdown
switch(es) (PSl
or PS2) to the "man. pumpdown"
position.
Moving the pumpdown switch back to the "auto. pumpdown" position will again energize the relay for another attempt at start up
.
If the system has built up enough evaporator pressure, the com-
pressor will continue to run.
To check the control,
turn off all power to the unit and remove the
wire(s) (No.
113
&
213) leading to the low pressure control(s)
(LPl
&
LP2) from terminal 4 in the unit control center.
Remove the com-
pressor fuses and jumper across terminals L & M of the freeze con­trols(s) and oil pressure safety control(s).
Energize the control
circuit by turning on the control circuit disconnect or main power disconnect (depending on the installation) and the control stop
switch
Sl.
The compressor contactors should pull in instantly.
page 47
Page 48
NOTE: Line is only hot when the unit thermostat calls for compressor to run.
Compressor Lockout - Optional Compressor lockout consists of a solid state time delay wired in
series with the compressor contactor(
Its purpose is to prevent
rapid compressor cycling when cooling demands are erratic.
The cir-
cuit illustrated above is for the lead compressor in each refriger­and circuit.
The circuit for the second compressor(s) performs the
same function but is wired differently (see unit wiring diagram).
When the unit thermostat no longer calls for cooling and the com-
pressor contactor have opened,
the lockout time delay breaks open
the circuit preventing compressore re-start.
The circuit remains open for a period of 5 minutes so that if the
unit thermostat should call for cooling before the delay period has expired,
the compressor will not re-start.
After 5 minutes, the
time delay will close its contacts to complete the circuit and be ready for start up.
The time delay opens its contacts whenever pow­er to terminal 4 is interrupted and resets closed automatically af­ter the time delay period.
To check the control,
the compressor(s) must be running initially.
Move the pumpdown switch
(PSl
or
PS2)
to the "man. pumpdown" posi-
tion.
Immediately after the compressor(s) have stopped running,
move the pumpdown switch back to the "auto. pumpdown" position.
The
lead compressor should not re-start for 5 minutes.
The second com-
pressor in the refrigerant circuit should start approximately 20
seconds after the lead compressor, high enough to require it.
provided that the cooling load is
the same way.
Each refrigerant circuit can be checked
LINE
(SEE NOTE)
-
COMF!
LOCKOUT
TIME DELAY
x-k-
TO UNIT THERMOSTAT
NOTE:
Hot whenever freeze control and high
pressure control permit safe operation.
page 48
Page 49
Alarm Bell - Optional
The 24 volt alarm bell is mounted inside the control center but not
wired to the control circuit.
It is expected that in most cases, the customer will want to relocate the bell where it will be more easily heard in the event of a safety failure.
There are leads for connection of the bell inside a junction box which is located in the unit control center.
All that is necessary is that the bell be
mounted in a preferred location and wired to the leads in the junc-
tion box. The bell is wired into the control circuit so that it will sound
whenever there is a failure due to low oil pressure, motor overload,
or excessive condenser pressure. Hot Gas Bypass
-
Optional
Hot gas bypass is a system for maintaining evaporator pressure at or
above a minimum value.
The purpose for doing this is to keep the ve­locity of the refrigerant as it passes through the evaporator high enough for proper oil return to the compressor when cooling load con­ditions are light.
The system usually consists of a solenoid valve piped in series with a pressure regulating valve as shown. Units are available with op­tional hot gas connection with a manual shutoff valve and capped stub.
A hot gas bypass kit consisting of a 115 volt solenoid valve and a
pressure regulating valve is available from McQuay under ordering number 886-321262B-02 for ALP units 067AS/D through 159AD.
The solenoid valve should be wired to open whenever the unit
thermo-
stat calls for the first stage of cooling (see Figure 10).
The pres-
sure regulating valve that McQuay offers is factory set to begin
opening at 58 PSIG
(32F
for R-22) when the air charged bulb is in
an 80F ambient temperature.
The bulb can be mounted anywhere as
long as it senses a fairly constant temperature at various load con-
ditions.
The compressor suction line is one such mounting location.
It is generally in the 50F to 60F range.
The chart on page 50 indicates
that when the bulb is sensing 50F to 60F temperatures, the valve will
begin opening at 54 to 56 PSIG.
This setting can be changed as in­dicated above, by changing the pressure of the air charge in the adjustable bulb.
To raise the pressure setting, remove the cap on
the bulb and turn the adjustment screw clockwise.
To lower the set-
ting,
turn the screw counter-clockwise.
Do not force the adjustment beyond the range it is designed for as this will damage the adjust­ment assembly.
The regulating valve opening point can be determined by slowly reduc-
ing the system load while observing the suction pressure.
When the
bypass valve starts to open,
the refrigerant line on the evaporator
side of the valve will begin to feel warm to the touch.
CAUTION:
The hot gas line may become hot enough to cause injury in
a very short time so care should be taken during valve checkout.
page 49
Page 50
On installations where the condensing unit is remote from the evapor­ator,
it is recommended that the hot gas bypass valve be mounted near the condensing unit to minimize the amount of refrigerant that will condense in the hot gas line during periods when hot gas bypass is not required.
The expansion valve,
like the solenoid valve, should not normally re-
quire replacement, but if it does,
the unit must be pumped down by
using the manual liquid line shutoff valve.
If the problem can be
traced to the power element only,
it can be unscrewed from the valve
body without removing the valve but only after pumping the unit down
with the manual liquid line shutoff valves.
HOT GAS BYPASS PIPING
Hot Gas Bypass
Solenoid Valve
DIAGRAM
HOT GAS BYPASS ADJUSTMENT RANGE
REMOTE
BULB
ADJUSTMENT RANGE
a0
I
I I
I
I
I
I
r
SuctionsLine
;,
L
Discharge
Line
Remote Bulb
External Equalizer Connection to Suction
Side of Evapoator
Bypass Valve
Inlet After Expansion Valve
TEMP
ioFI
AT BULB LOCATION
page 50
Loading...