GROUP McQUAY-PERFEX Inc. 13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, Mn. 55440
@)
NOTICE:
Installation and maintenance are to be performed only by
qualified personnel who are familiar with local codes and
regulations,
CAUTION:
injury hazard.
and experienced with this type of equipment.
Sharp edges and coil surfaces are a potential
Avoid contact.
page
2
Nomenclature
PROPELLER FANS
LOW POWER CONSUMING
AIR COOLED CONDENSER
Inspection
AL
-
089 A D
REFRIGERANT CIRCUITS
(D=Dual;
S=Single)
DESIGN VINTAGE
NOMINAL CAPACITY (TONS)
When the equipment is received,
against the bill of lading to insure a complete shipment.
should be carefully inspected for damage upon arrival.
all items should be carefully checked
All units
All shipping
damage should be reported to the carrier and a claim should be filed.
The unit serial plate should be checked before unloading the unit to
be sure that it agrees with the power supply available.
INSTALLATION
Handling
Care should be taken to avoid rough handling or shock due to dropping
the unit.
base,
and block the pushing vehicle away from the unit to prevent
damage to the sheet metal cabinet.
FIGURE 1
Do not push or pull the unit from anything other than the
(See Figure 1.)
SUGGESTED PUSHING ARRANGEMENT
page
4
GOOD PUSHING ARRANGEMENT
CABINET DAMAGE UNLIKELY
POOR PUSHING ARRANGEMENT
CABINET DAMAGE LIKELY
Never allow any part of the unit to fall during unloading or moving
as this may result in serious damage.
To lift the unit,
of the unit.
2+"
diameter lifting holes are provided in the base
Spreader bars and cables should be arranged to prevent
damage to the condenser coils or unit cabinet.
FIGURE 2
SPREADER BAR
SUGGESTED LIFTING ARRANGEMENT
REQD.
-MUST USE THESE RIGGING HOLES
OTE
CONTROL 60x
(N
(See Figure 2.)
L~cATI~NI
TABLE 1
ALP UNIT SIZE
067ASlD
078ASlD
089A
106A
UNIT WEIGHT
SHIPPING WEIGHTS
(Ibs)
4125
4308
4963
5134
ALP UNIT SIZE
126A
136A
149A
159A
UNIT WEIGHT
6021
6095
6873
7202
(Ibs)
Location
Due to the vertical condenser design, it is recommended that certain
precautions be taken before installation to orient the unit so that
prevailing winds blow parallel to the unit length thus minimizing
effects on condensing pressure.
the unit in this manner,
a wind deflecting fence should be consi-
If it is not practical to orient
dered.
It is also necessary to provide adequate clearance on all sides of
the unit for service access and satisfactory performance.
60 in.
(1 fan diameter) should be allowed on each side of the unit
for condenser air inlet and compressor removal on units 067
At least
&
078.
If parallel units are installed side by side, 120 in. should be allowed between units.
atures and enhance system performance and operating economy.
This will prevent excessive condensing temper-
Clear-
ance for service access should be at least 78 in. at the control cen-
ter end for compressor removal on units 089 through 159 and 42 in.
on units 067 and 078.
the control center for ease of access to bearings and drives.
Allow 36 in.
clearance at the end opposite
These
clearances are illustrated in Figure 3.
page 5
FIGURE 3 CLEARANCE AROUND UNIT
t
CLEARANCE
(2)
NOTE:
60” MINIMUM CLEARANCE (2)
60”
MINIMUM
(I)
Minimum vertical clearance above unit should be 10
feet.
(2) Clearance to condenser coil must be increased if more
than one side is obstructed or between adjacent units.
Consult your
McQUAY
sales representative.
Service Access
Each end of the unit must be accessible after installation for peri-
odic service work.
Compressors and manual liquid line shutoff valves
are accessible from the control center end of the unit through re-
movable access panels on unit sizes 089 through 159 and hinged side
access doors on unit sizes 067 and 078.
and starting controls are located in the unit control center.
are protected by a keylocked,
internal"dead front"
doors for protection of service personnel from
weatherproof enclosure which contains
All operational, safety,
They
high voltage starting controls while servicing low voltage operational controls.
just below the main control center.
All resettable or adjustable controls are located
There is one resettable control
enclosure on each side of the unit and each enclosure contains con-
trols for compressors on that side of the unit.
Capped connections
for field service gauges are also located inside these enclosures.
In addition,
each of these enclosures are removable to improve access
to compressors for field replacement.
The condenser fans, motors,
keylocked access door.
in,
and drives are accessible through a walkThe access door is located at the end of
the unit opposite the control center.
An internal fan guard is located below the condenser fans and drives
on units 089 through 159.
This guard must be removed to service the
fan drives but MUST always be reinstalled when service work is com-
plete.
On unit sizes 067 and 078,
an interlock switch kills power to conden-
ser fans whenever the door is opened for service work on fans or
drives.
CAUTION:
Disconnect all power to the unit while servicing condenser
fan drives.
page
6
Vibration Isolators
Vibration isolators are recommended for all roof mounted installa-
tions or wherever vibration transmission is a consideration.
2 lists spring isolators for all ALP unit sizes.
Figure 4 shows
isolator locations in relation to the unit control center.
gives dimensions that are required to secure each
McQuay
isolator
Table
Figure 5
selection to the mounting surface.
Table 3 shows the isolator loads at each location shown in Figure 4
and the maximum loads for each McQuay selection.
TABLE 2
VIBRATION
ISOLATORS
216404B-272164046-26
TABLE 3
IS0 LATOR LOADS
page 7
REFRIGERANT PIPING
General
McQuay type ALP condensing units are adaptable to either chilled
water or air handling air conditioning applications.
The only restriction on applications is that the evaporator be selected for a
system using refrigerant 22.
Evaporator Above Condensing Unit
Figure 6 shows an installation where the evaporator is installed
above the condensing unit.
It is shown for an air handling installation but all components shown are recommended for chilled water
installations except that a refrigerant distributor is not usually
required for shell-and-tube evaporators.
1. Piping shown is for one circuit only, second circuit is similar.
2. All piping & piping components are by others.
Figure 7 shows an installation where the evaporator is installed below the condensing unit.
It is shown for an air handling installation but all components shown are recommended for chilled water installations except that a refrigerant distributor is not usually re-
quired for shell-and-tube evaporators.
Mote that a double suction
riser is shown for this arrangement.
Risers
"A + B" are sized so that their combined cross-sectional in-
ternal area will allow full load unit operation without excessive
pressure drop (see notes, Table 4).
Riser
"B"
is sized to provide
adequate suction gas velocity for proper oil return at minimum load
conditions.
in riser "A"
the trap shown in riser "A"
This riser becomes effective only when the trap shown
fills itself with oil.
It should be emphasized that
should be designed to contain a minimum
internal volume to keep the total system oil requirements at a minimum.
Table 4 gives recommended line sizes for both single and double
suction lines and for liquid lines.
page
9
Figure 9 shows typical field wiring that is required for unit instal-
lation.
(SVl & SV2),
Items that require field wiring are:
optional hot gas bypass solenoid
liquid line solenoids
(SV5)
and the cooling
thermostat as well as the unit power supplies.
FIGURE 9
;BK
\
I
01
0 II
8
-FLOW SWITCH
PBl
DISCONNECT
BY OTHERS--\,,< TERMINAL BLOCK
3pH ---_H
POWER
SuppLy
_ _
SEPARATE
POWER FOR CONTROLS
‘,‘--
DISCONNECT BY OTHERS
A
NOTE
FUSE-IO A
(C.W.
SYSTEMS)
___/-:__
II?,“-IOA
___
__I’_
TIME
CLOCK;;-
UNIT MAIN
c
-
-
REFRIGERANT CIRCUIT I
SAFETY AND OPERATING
TYPICAL FIELD WIRING
OPTIONAL
TRANSFORMER
CONTROLS
FdSEU
CONI, llNlT
COMPRESSORS
AND FAN MOTORS
WH
I
i g_ ~~~SLT~OM~~~,~~NNECTION
I
LEGEND
irJH_WHlTt
SVl,2-LIOUID ’ INE
SVS-HOT
R3,4-COMP.
R5,6,7,E
PSI.2 -PUMPDOWN
TDl1,12,13-COMP
Rx-EVAP. FAN INTERLOCK
WlhlNG
SOL. VALVE
GAS BY PASS
SOL VALVE
384 START
RELAYS
-SAFETY
SWITCHES
CING TIME DELAYS
PREVENTS OPENING
SV’S WITHOUT LOAD
RELAYS PROVIDE
RECYCLING PUMP
DOWN DURING OFF
SEASON
fNEUT1.
RELAYS
SEOUEN-
PUMP STARTER
CIRCUIT
CC. W.
SYSTEMS1
REFRIGERANT CIRCUIT
SAFETY AND OPERATING
CONTROLS
UNIT CONDENSER
OPERATING CONTROLS
R9
6
6
a0 __:
T
2
FANS
’
I
1
I
I
I
PUMP STARTER
RIO
-C
NOTE; CIRCUIT SHOWN ASSUMES CONTINUOUS
I I
1
I I
I
POWER SUPPLY
FOR CONTROLS
PUMP
OPERATIIN~FOR
PUMP OPERATION CONSULT
INTERMITTENT
McOUAY
Thermostat Wiring
Since it is impossible for
McQuay to anticipate the type of installa-
tion that an ALP condensing unit may be used on, we do not factory
install a thermostat.
We do,
however,
provide numbered terminals in-
side the unit control center to which a thermostat may be connected.
These terminals are shown and labeled "Terminals For Thermostat" on
the electrical schematics.
On a two circuit unit it is important to connect the thermostat so
that as successive stages of cooling are called for, the compressors
in the unit will be started to alternately increase the condenser
load from refrigerant circuit 1 to circuit 2.
in Table 9.
Figure 10 shows how to install 2 independent four stage
This is illustrated
thermostats for controlling an 8 stage unit and Figure 11 shows typical field wiring for an 8 stage thermostat.
page 14
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.