McQuay ALP-045C Installation Manual

TABLE OF CONTENTS
INTRODUCTION
General Description . . . . . . . . . . . . . . . . . . . . . . . . . ...3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...3
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...3
INSTALLATION
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...3
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4
Vibration Isolators . . . . . . . . . . . . . . . . . . . . . . . . . ...4.5
REFRIGERANT PIPING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...6
Recommended piping arrangements . . . . . . . . . . . . ...7
Refrigerant piping connections . . . . . . . . . . . . . . . . ...7
Recommended line sizes . . . . . . . . . . . . . . . . . . . . . ...8
Holding charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...8
Pressure testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...8
Leak testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...8
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...9
Charging the system . . . . . . . . . . . . . . . . . . . . . . . . . ...9
Hot gas bypass components.. . . . . . . . . . . . . . . . . ...9
Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . ...9
Pressure-vacuum equivalents . . . . . . . . . . . . . . . . ...10
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . ...10.11
DIMENSIONAL DATA . . . . . . . . . . . . . . . . . . . . . ...12.13
FIELD WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . ...14.15
Wire sizing ampacities . . . . . . . . . . . . . . . . . . . . . . ...16
Compressor and condenser fan motors . . . . . . . . ...17
Thermostat wiring and capacity reduction . . . ...17.18
Water piping for chilled water applications , . . . . . ...18
Flow switch for chilled water applications . . . . . . . ...18
Evaporator fan interlock
for air handler coil installations . . . . . . . . . . . . . ...19
UNIT LAYOUT&PRINCIPLES OFOPERATION
Major component locations . . . . . . . . . . . . . . . . . . ...19
Control center . . . . . . . . . . . . . . . . . . . . . . . . . . ...19.20
Electrical legend . . . . . . . . . . . . . . . . . . . . . . . . . . . ...21
Unit disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...21
Sequence of operation . . . . . . . . . . . . . . . . . . . . . . ...22
TYPICAL WIRING SCHEMATICS
Power schematics . . . . . . . . . . . . . . . . . . . . . . . ...23-39
Control and safety schematics . . . . . . . . . . . . . ...40-42
Thermostat schematics, . . . . . . . . . . . . . . . . . . ...43-45
Wiring schematic decision tables.. . . . . . . . . . ...46.47
STARTUP&SHUTDOWN
Pre-startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...48
Initial startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...48
Temporary shutdown . . . . . . . . . . . . . . . . . . . . . . . . ...48
Startup after temporary shutdown . . . . . . . . . . . . . ...48
Extended shutdown . . . . . . . . . . . . . . . . . . . . . . . . . ...48
SYSTEM MAINTENANCE
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...49
Fan shaft bearings . . . . . . . . . . . . . . . . . . . . . . . . . ...49
Electrical terminals . . . . . . . . . . . . . . . . . . . . . . . . . ...49
Compressor oil level . . . . . . . . . . . . . . . . . . . . . . . . ...49
Oil Equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...49
Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...49
Refrigerant sightglass . . . . . . . . . . . . . . . . . . . . . . . ...49
SERVICE
Filter-driers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...50
Liquid line solenoid valve . . . . . . . . . . . . . . . . . . . . ...50
Thermostatic expansion valve . . . . . . . . . . . . . . . . ...50
IN-WARRANTY RETURN MATERIAL PROCEDURE
Copeland compressor . . . . . . . . . . . . . . . . . . . . . . . ...51
Components other than compressors . . . . . . . . . . ...51
APPENDIX
Standard Contr61s:
Oil pressure safety control . . . . . . . . . . . . . . . . . . . ...51
High pressure control . . . . . . . . . . . . . . . . . . . . . . . ...52
Low pressure control . . . . . . . . . . . . . . . . . . . . . . . . ...52
FANTROL head pressure control . . . . . . . . . . . ...52.53
Compressor lockout . . . . . . . . . . . . . . . . . . . . . . . . ...53
Compressor motor protector . . . . . . . . . . . . . . . . . . ...53
Optional Controls:
SPEEDTROL head pressure control . . . . . . . . . . . ...54
Compressor unloaders . . . . . . . . . . . . . . . . . . . . . . ...54
Low ambient start . . . . . . . . . . . . . . . . . . . . . . . . . . ...54
High ambient unloader . . . . . . . . . . . . . . . . . . . . . . ...54
Part winding start . . . . . . . . . . . . . . . . . . . . . . . . . . ...54
Phase/voltagemonitor . . . . . . . . . . . . . . . . . . . . . . ...55
Hot gas bypass (field installed) . . . . . . . . . . . . . . . ...55
ALP controls, settings&functions . . . . . . . . . . ...56. 57
Troubleshooting chart . . . . . . . . . . . . . . . . . . . . ...58.59
Page2/lM269
“FanTrol”, “McC!uay”, “
of McQuay Air Conditioning, McOuay International, Minneapolis MN
G 1995 McOuay Air Conditioning. McQuaylnternational. Minneapolis. MN
“Bulletin illustrations cover the general appearance of Mc@ay International products al the time of publica! ior,
and we reserve the right to make changes in design and construction at any time without notice”
SeasonCon” and “SpeedTrol” are registered trademarks
INTRODUCTION
GENERAL DESCRIPTION
McQuay type SeasonCon air cooled water condensing units are designed for outdoor installations and are compatible with either air handling or chilled water systems. Each unit is com­pletely assembled and factory wired before evacuation, charg­ing and testing, and comes complete and ready for installa­tion. Each unit “consists of twin air cooled condensers with integral subcooler sections, multiple accessible hermetic com­pressors, complete discharge piping and suction connections for connection to any air or water cooling evaporator.
NOMENCLATURE
INSPECTION
When the equipment is received, all items should be careful-
Iy checked against the bill of lading to insure a complete ship­ment. All units should be carefully inspected for damage upon
arrival. All shipping damage should be reported to the car-
rier and a claim should
be filed. The unit serial plate should
The electrical control center includes all safety and oper­ating controls necessary for dependable automatic operation except for the cooling thermostat since this is somewhat dependent on the unit application. Condenser fan motors are fused in all three conductor legs and started by their own three-pole contractors. Compressors are not fused but may be protected by optional circuit breakers, or by field installed fused disconnect.
be checked before unloading the unit to be sure that it agrees with the power supply available. Physical damage to unit after acceptance is not the responsibility of McQuay.
NOTE: Unit shipping and operating weights are available
in the physical data tables on pages 10 and 11.
INSTALLATION
NOTE: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes
and regulations, and experienced with this type of equipment.
CAUTION: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
HANDLING
Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from anything other than the base, and block the pushing vehicle away from the unit to prevent damage to the sheetmetal cabinet and end frame (see Figure 1).
Never allow any part of the unit to fall during unloading or
Figure 1. Suggested Pushing Arrangement
BLOCKING REQ’D. ACROSS FULL WIDTH
moving as this may result in serious damage.
To lift the unit, 21/2” diameter lifting holes are provided in the base of the unit. Spreader bars and cables should be ar­ranged to prevent damage to the condenser coils or unit cabinet (see Figure 2).
Figure 2. Suggested Lifting Arrangement
,,,,,.,, 8,,
FIECOMMENWO (uSE CAUTION)
MO,, NUMBER 0, F..% FROM, H,SO,A. R U,,(NC METHOD R, MA, NS THE SAME
LIFT UNIT OWL Y AS SHOWN
(NOTE .0.,,0, 80., ’0,.,,0.,
IM 269 I Page 3
HOLES
LOCATION
Care should be taken in the location of the unit to provide proper airflow to the condenser, minimizing effects on con­densing pressure.
Due to the vertical condenser design of the ALP-120 thru 230 chillers, it is recommended that the unit is oriented so that prevailing winds blow parallel to the unit length, thus
minimizing the effects on condensing pressure, If it is not prac­tical to orient the unit in this manner, a wind deflector should be constructed.
Minimum clearances as shown in Figure 3 will prevent most discharge air recirculation to the condenser which will have a significant effect on unit performance,
SERVICE
Each end of the unit must be accessible after installation for periodic service work. Compressors, filter-driers, and manual liquid line shutoff valves are accessible on each side of the unit adjacent to the control box. High pressure, low pressure, and motor protector controls are on compressor. Most other operational, safety and starting controls are located in the unit control box.
Figure 3. Clearance Requirements ALP-045C thru 230C
6 !7. MIN. CLEARANCE
4 FT. MIN.
CLEARANCE au
FOR SERVICE
ACCESS
I
1
FOR AIR INLET
da
i-~ ~ti
I
6 FT. MIN. CLEARANCE
FOR AIR INLET
I
6 FT. MIN.
CLEARANCE
1
FOR AIR
INLET
VIBRATION
Vibration isolators are recommended for all roof mounted in­stallations or wherever vibration transmission is a considera­tion. Table 1 lists spring isolators for all ALP unit sizes. Figure 4 shows isolator locations in relation to the unit control center. Figure 5 gives dimensions that are required to secure each
ACCESS
On all ALP units the condenser fans and motors can be removed from the top of the unit. A complete fan/motor assembly should be removed for service.
CAUTION: Disconnect all power to unit while servicing condenser fan drives.
NOTES:
(1)Minimum clearance between units is 12 feet, (2) Units must not be installed in a pit that is deeper than the height of the unit (3) Minimum clearance on
each side is 12 feet when installed in a pit.
ISOLATORS
McQuay isolator selection to the mounting surface. Table 3 shows the isolator loads at each location shown in Figure 4, and the maximum loads for each McQuay selection are shown in Table 2.
Table 1. Vibration Isolators (Spring)
ISOLATOR LOCATIONS
SUE
045C CP
055c CP
t=!=
------ ..-— — ——, .
Cl CPI.!17 I CP1.W I CP1-28 I CP1-32 I CP1-32 I CF
Iooc,-..-.,- .. --,-..--, ----, - -­11OCICP1-32
120C I CP1-27
~ CP2-27
Page 4 I IM 269
CP1-32 CPI-32 CP1-32 CP2-27
CP1-32 CP2-27 CP2-27
CP1-27 CP1-27 CPI-32 CPI-32
CPI-32
CP2-27 CP2-27
‘1-28
CP1-32
Table 2. Spring-flex Isolators
TYPE COLOR
P+.25 RED 4n927A-25
----
tiP1-26
1
CP1-27 ORANGE
CP1-28
I
CP1-31 CPI-32
CP2-25
I
CP2-28
CP2-27
CP2-28
-.
--
CP4-27
I
CP4-28 CP4-31
I
CP4-32 WHITE 580513A-32
i=
I
I
I
I
I
1
MAX. LOAD EACN
0-=.)
2200
2400
3000
4400
5200
McOUAY
PART
NUMBER
PURPLE
GREEN
WHITE
GRAY
RED
PURPLE
ORANGE
GREEN
ORANGE
GREEN 58051 3A-26 3600
GRAY
477927A-26
I
477927A-27 477927A-26
I
4n927A-31 1100 4n927A-32 4n929A-25 900
477929A-26
4n929A-27
477929A-26 4n929A-31 4n929A-32 2600 580513A-26 58051 3A-27
I
58051 3A-31
I
450
600 750
900
1300
1200 1500 1800
Figure 4. Isolator Locations
Table 4. Isolator Locations
—c—
1-
6
3
>
Table 3. Isolator 1m=~=
ALP
? UNIT
SIZE 1
: 045C
055C
~ 070C
Osoc
‘ 090C
100C
‘ 11OC
120C
, 135C
, 150C
wbc
185C
: 205C
230C
ISOLATOR LOADS AT SACH FAOUNTING LOCATION (l-SS.)
.“”””
556 706 736 831 859 867 945
986 1135 1279 1327 1376 1423 1569 1643
2 555 687 720 845
934 946 952
1062 1108 1144 1375 1553 1596
3 441 428 466 618
~]
621 806 643
1051 1115 1128 1205 1399 1510
4 556 706 736 631 659 945 986
1135 1279 1327
1378
1423 1569 1643
5 555 687 720 845 867 934
I
946 952
1062 1108
1144
1375 1553 1598
6 441 426 466 618 620 621 806 643
1051 1115
1128
1205 1399 1410
I
I
VIBRATION MOUNT LOCATION DIMENSIONS
Figure5. Spring Isolators
ORDERING NO.
477927A-26 THRU 477927A-32
(INCHES)
ORDERING NO.
477929A-25 THRU 477929A-32
ORDERING NO.
580513A-26 THRU 580513A-32
Ls.oo --- I
1-
7,,0 ~
0,50 Dia. Positioning
Acoustical No..Skid Neoprene Pad
Adjust Mounting So Upper Housing Clears Lower HousinQ By At Least IW and Not More
2“%Ezili
6 F
Acoustical No..Skid Neoprene Pad
_ 10.25 .—~
Adjust Mounting so Upper Housing Clears Lower Housing By At Least 114” and Not
More Than 1/2”.
~ Acoustical Non:Skid
Neoprene Pad
\
IM 269/ Page 5
REFRIGERANT
PIPING
GENERAL Piping design, sizing and installation information presented in ASHRAE Handbooks should, where applicable, be followed in the design and installation of piping. McQuay type ALP condensing units are adaptable to either chilled water or air handling air conditioning applications, The only restriction on applications is that the evaporator be selected for a system using refrigerant R-22.
REFRIGERANT PIPING Piping between the condensing unit and the cooling coil must
be designed and installed to minimize pressure drop, pre­vent liquid refrigerant carryover to the compressor and to assure a continuous return of compressor oil from the system.
Piping sketches and tables are not intended to provide infor­mation on all of the possible arrangements. For example, when dual circuit evaporators are used with an unloading compressor, two liquid line solenoid valves may be used to reduce coil capacity with compressor unloading. Note especially that dual circuit evaporators should not be piped with common liquid and suction lines to more than one com­pressor circuit. Separate evaporators, evaporator circuits and piping must be run for each compressor circuit.
Piping recommendations include:
The use of type K or L clean copper tubing. All joints should
1.
be thoroughly cleaned and brazed with high temperature solder.
2.
Piping sizes should be based on temperature/pressure limitations as recommended in the following paragraphs, Under no circumstances should pipe size be based upon the coil or condensing unit piping connection size. Suction line piping pressure drop should not exceed the
3. pressure equivalent of 2° F (3 psi) per 100 feet of equivalent pipe length. After the suction line size has been deter­mined, the vertical suction risers should be checked to verify that oil will be carried up the riser and back to the compressor. The suction line(s) should be pitched in the direction of refrigerant flow and adequately supported. Lines should be free draining and fully insulated between the evaporator(s) and the compressor. Table 7, page 8, shows piping information for units operating at suction temperatures between 40F and 45 F and a condenser entering air temperature of 95F. If operating conditions are expected to vary substantially from these operating levels, the pipe sizing should be rechecked. Vertical suction risers should be checked using Table 5
4. to determine the minimum tonnage required to carry oil up suction risers of various sizes:
5. The liquid line should be sized for a pressure drop not to
exceed the pressure equivalent of 2° F (6 psi) saturated temperature. The liquid line(s) on all units must include
a liquid solenoid valve wired into the circuit as shown on the applicable unit wiring diagrams.
The control circuit for all compressors has been de­signed to include a pumpdown cycle. The use of a liquid line solenoid is required for proper unit operation. In ad­dition, a filter-drier should be located between the liquid line service valve and the solenoid valve and a combina­tion moisture indicator/sightglass should be located in the liquid line ahead of the expansion valve.
6.
Suggested piping arrangements are shown on page 7. All multiple compressor units require a separate refrigerant circuit for each compressor. The figures shown are for an air handling installation, but all components shown are recommended for chilled water vessel installations except that a refrigerant distributor is not usually required for shell and-tube evaporators.
7.
If dual suction risers are used:
Double risers are sized so that their combined cross­sectional internal area will allow full load unit operation without excessive pressure drop (see notes, Table 7). Riser “A” is sized to provide adequate suction gas velocity for proper oil return at minimum load conditions, This riser becomes effective only when the trap shown in riser “B” fills itself with oil. It should be emphasized that the trap shown in riser “B” should be designed to contain a minimum internal volume to keep the total system oil re­quirements at a minimum. Table 7 gives recommended line sizes for both single and double suction lines and for liquid lines.
The combined cross-sectional areas of the two risers
a.
must be capable of maintaining adequate refrigerant velocity for oil return at full unit tonnage, The extra riser should be of a smaller diameter than
b.
the main riser. The extra riser must include its own trap at the bottom and should enter the main suction header at twelve o’clock. The trap serving the extra riser must be as short as fit-
c.
tings permit. A “U” fitting or the combination of a 90’ standard “L” and a 90C street-L is recommended, The suction line leaving the coil should also include a
d.
trap if the expansion valve control bulb is to be on the horizontal section leaving the coil outlet, See the pip­ing sketches on page 7.
Table 5. Minimum tonnage (R-22) to carry oil up
suction riser at 400 F saturated suction.
Min. Tons
NOTE: When compressor minimum tonnage is less than shown in the above
1.50 2.50 3.80 7.60 13.10 204 29.7 41.3
table for a given line size. double suction risers will be required
I
Table 6. Equivalent feet of straight tubing for copper fittings and valves
I
I
I 90” Lono Radius I 1.0 I
.“-
TEES
VALVES
FITTING TYPE
90” Standard
90” Street 45” Standard
A6. .Wrss! 13 15 91 30
-h, .-
Full Size Reducing
Globe Valve, Open Gate Valve, Open 0.7 Angle Valve, Open 7.0 9.0
518
I
1.6 2.0
!
2.5 3.2 4.1
0.8 0.9
-.”
1
1.0
I
1.6 2.0
18 22 29
718 1%
2.6 3.3 4.0 5.0 6.0
1.4 I 1.7
“.-
1
1
1.4 1.7 2.3 2.6 3.3
0.9
I 2.3 I 2.6 I 3.
1,3
.,.
1
2.6 3.3 4.0 5.0 6.0
1.0
12
Page 6 I IM 269
1yf 1V*
5.6
1.7
---
38 43 55 69 84
1.5
15 18 24 29 35
6.3
2.1 2.6 3.2
34 45 57 64 7.3 I 85
---
1
1.8 2.3 2.8 3.2
2y* 2%
I
3
8.2
---
1
4.1 5.0 5.9 6.7
10.0 12.0 15.0 17.C
..- ----
,
4.1 5.0 5.9 6.7
31/s 3%
7.5 9.9
4.0
.-. .
!
7.5 9.0
100 120
4.0 4.5
41~
10.0
4.7
10.0
41 47
[
52
..-
Figure 6. SINGLE CIRCUIT EVAPORATOR – RECOMMENDED PIPING
If Row Split Coils Are Used, Duplicate The Piping
CONDENSING UNIT AaOVE THE EVAPORATOR
CONDENSING UNIT BELOW THE EVAPORATOR
LlOU10
TO COIL
“L___
SUCTION TRAP SHORT AS FITTINGS PERMIT
1
EXPANSION VALVE CONTROL BULB STRAP TO LINE AND lNSUIATf
SUCTION TRAP ~ SHORT AS FITTINGS PERMIT
Figure 7. DUAL CIRCUIT EVAPORATOR (FACE SPLIT) – RECOMMENDED PIPING
t
L(
SUCTION TRAP ~ SHORT AS FITTINGS PERMIT
NOTES:
1. Piping shown is for one compressor circuit; second circuit is similar. Must have separate piping for each compressor circuit.
2. Trap for double suction riser should be as small in horizontal direction as fittings will allow.
3. The thermal expansion valve equalizer line should be placed just past the thermal sensing bulb on the side or top of the pipe.
4. A separate expansion valve is required for each distributor and mounted per manufacturer’s recommendations. (See additional notes under recommended line sizes, Table 7)
L CXP4NSION VA1bl
CONTROL BULR 5TRAP To LINE AND INSULATE
ION vALVE CONTROL BuLBS STRAP TO LINE AND INSULATE
REFRIGERANT PIPING CONNECTIONS
Refrigerant piping connections will be made at the com-
pressor end of the unit. Suction and liquid lines should be
routed through the compressor enclosure on each side of the
unit. When piping, allow room for the unit disconnect and field
wiring to the unit. Figures 8 and 9 show piping connections
and sizes for each ALP model.
IM 269 I Page 7
Table 7. Recommended line sizes
COMPRESSOR CIRCUIT #1
ALP UNIT SIZE
055C 13&15h 070C 080C 090C
100C 15/&2~h
11OC
120C 2%J—25/8 135C 27+2Y8 3X? 150C
DOUBLE
.A9*_,4
1%-1 ye
1%-15h 15h—21A I
5~—2y8
15y&2y3
214—25A
170C 21h—25h 1MC 27’s-2y8 31~
205C 21&31~ 3% 230C
NOTES: Recommended line sizes shown in the above table are based on the unit
operating conditions between 40F and 45 F saturated suction temperature and condenser entering air temperature of 95F, per 100 ft. equivalent length 4. of tubing. When design conditions vary, the table values should be rechecked.
1. Liquid and suction lines based on a recommended equivalent pressure drop of 2F (3 psi for suction line, 6 psi for liquid line) per 100 ft. of equivalent length,
2. When refrigerant required to charge a circuit exceeds the pumpdown capacity of that circuit the use of a separate refrigerant storage receiver will be required. The pumpdown capacity (shown in Table 10) is based on the condenser 90% full at 90” F.
3. Wherever vertical rise occurs in the suction piping, the minimum tonnage
2%-31~
SINGLE
slJ~*,oN LIQulD
~,,
21h
z~~ 1% 15.3 21A 278
278
25~ 13~
2% 13~
37h 1ye 33.0 58.9
31~
31~
3%
11A
1% 14.7
1ah 16.6 37.6
1ye 21.3
1ye 33.4 66.7 1ye 33.9 73.6 2%-2Y8
1ya 37.9 82.5
1ye 34.4 90.4 21A 35.9 21A 40.0
MINIMUM
PART LOAD
CAPACITY
(TONS)
12.9 19.4
33.2
38.1
FULL LOAD
CAPACITY
(TONS)
23.8
29.0 15/’-21h
42.5 15/+2~h
48.9
56.1
99.8 21/&31~
111.1
COMPRESSOR CIRCUIT #2
DOUBLE SINGLE
,A,9_”
B“ SUCTION
1y&l
5/4
1y&l ya
15/*-21h
1y~—zl~
1y*—21h 2J&278 2J/4-25/a 3%
21&2y~ 37h
21A—25A 3Ys
21&31/s
fer oil entrainment should be checked and where necessary double suc­tion rlsers should be utilized. See Table 5, page 6, Wherever vertical rise occurs in the suction piping on a system with hot
gas bypass, double suction risers may not be needed as the velocity of suction gas is increased at minimum load condtions. Total equivalent feet for a given piping layout must include the equivalent
5
length of straight pipe for fittings, valves and specialties added to the total run of straight pipe. Piping design, sizing and installation information presented in ASHRAE
6
Handbooks should, where applicable, be followed in the design and stallation of piping.
‘QU’D
214 11A 15.5 23.6 21A 11A 18.5 29.1 2% 1ya 17.9 35.3 2% 1Y* 16.6 37.6
2% 1ye 21.3 278 13h X3.2 48.9 278 1ye 38.7 56.1 31A 1ya 33.0 58.9
3%
35h 21A 35h
1ya 33.4 66.7 15~ 339 73.6
1y’ 37.9 82.5
15h 34.4 904
21A
.... .... . ... I I
mlnlmum
PART LOAD
-. -.-—.. GAPAUI I Y
m-)
35.9 998
40.0 111.1
FULL LOAD
CAPACITY
I
(TONS)
42.5
I
in-
HOLDING CHARGE The Model ALP condensing unit is shipped with a holding charge of refrigerant. At the time the unit was received a visual inspection of the unit piping should have been made to be sure no breakage had occurred or that fittings might have been loosened. A pressure check should indicate a positive pressure in the unit. If no pressure is evident, the unit will have to be leak tested and the leak repaired. This should be noted and reported to your McQuay sales representative or freight carrier if the loss is due to shipping damage.
PRESSURE TESTING
No pressure testing is necessary unless damage was in-
Page 8 / IM 269
curred during shipment or rigging, Damage may be deter­mined by a visual inspection of the exterior piping assuming
no breakage has occurred or fittings have loosened, Pressure gauges should show a positive pressure. If no pressure is evident on the gauges, a leak has probably occurred releas-
ing all or part of the refrigerant charge, In this case, the unit should be leak tested to locate the leak.
LEAK TESTING
In the case of loss of the refrigerant holding charge, the unit should be checked for leaks prior to charging the complete system. If the full charge was lost, leak testing can be done by charging the refrigerant into the unit to build the pressure
to approximately 10 psig and adding sufficient dry nitrogen to bring the pressure to a maximum of 125 psig. The unit should then be leak tested with a Halide or electronic leak detector. After making any necessary repair, the system should be evacuated as described in the following paragraphs.
CAUTION: Do not use oxygen to build up pressure. A serious explosion could be the result.
EVACUATION After it has been determined that the unit is tight and there are no refrigerant leaks, the system should be evacuated. The use of a vacuum pump with a pumping capacity of approx­imately 3 cu. ft./min, and the ability to reduce the vacuum in the unit to at least 1 millimeter (1000 microns) is recom­mended.
A mercury manometer, electronic or other type of micron
1.
gauge should be connected to the unit at a point remote from the vacuum pump, For readings below 1 millimeter, an electronic or other micron gauge should be used. The triple evacuation method is recommended and is par-
2. ticularly helpful if the vacuum pump is unable to obtain the desired 1 millimeter of vacuum. The system is first evacuated to approximately 29 inches of mercury. Enough refrigerant vapor is then added to the system to bring the pressure up to O pounds. Then the system is once again evacuated to 29 inches of
3. vacuum. This procedure is repeated three times. This method can be most effective by holding system pressure at Opounds for a minimum of 1 hour between evacuations.
The first pull down will remove about 90% of the non­condensibles, the second about 90%0 of that remaining from the first pull down and after the third only 1/10 of 10% non-condensibles will remain.
Table 12, page 10, shows the relationship between pressure,
microns, atmospheres, and the boiling point of water.
HOT GAS BYPASS COMPONENTS
McQuay offers a “Hot Gas Bypass Accessory Kit” for each ALP unit size. Each kit includes a solenoid valve, a hot gas bypass valve and an instruction drawing. See page 55 for hot gas bypass operation.
Table 9. Hot gas bypass kits
COMPRESSOR
KIT
S86-580698A-01 866-580898A-01 886-580698A-02 886-5S0898A-01 886-5S0698A-02 886-580898A-01 886-580896A-02
LINE SIZES
% ~8
1IA
%
1*A
%
11A
REFRIGERANT CHARGE Each ALP condensing unit is designed for use with R-22.
Table 10 lists approximate refrigerant charges for operation of the unit. Additional refrigerant will be needed for the system piping and evaporator. Estimated total operating charge should be calculated before charging system. See Table 11 for weight of refrigerant in copper lines.
CAUTION: Total operating charge per circuit should not exceed the condenser pumpdown capacity
per circuit. A liquid receiver on each refrigerant circuit could be used in this situation. Refer to the ASHRAE Handbook for the design and installation of piping and components.
Table 10. Approximate refrigerant charge
CHARGING THE SYSTEM
Model ALP condensing units are leak tested at the factory and shipped with a holding charge of refrigerant. In the event the refrigerant charge has been lost due to shipping damage, the system should be charged with enough refrigerant to raise the unit pressure to 30 psig after first repairing the leaks and evacuating the system.
After all refrigerant piping is complete and the system has
1.
been evacuated, it can be charged as described in the paragraphs following. Connect the refrigerant drum to the gauge port on the liquid shutoff valve and purge the charg­ing line between the refrigerant cylinder and the valve. Then open the valve to the mid-position.
2,
If the system is under a vacuum, stand the refrigerant drum with the connection up and open the drum and break the vacuum with refrigerant gas. With a system gas pressure higher than the equivalent of
3. a freezing temperature, invert the charging cylinder and elevate the drum above the condenser, With the drum in this position, valves open and liquid refrigerant will flow into the condenser. Approximately 75% of the total require­ment estimated for the unit can be charged in this manner. After 75% of the required charge has entered the con-
4. denser, reconnect the refrigerant drum and charging line to the suction side of the system. Again purge the connec­ting line, stand the drum with the connection up, and place the service valve in the open position.
IMPORTANT At this point charging procedure should be in­terrupted and prestart checks made before attempting to com­plete the refrigerant charge. See startup procedures on page
48.
NOTE: It is recommended that the total operating charge per
circuit be stamped on the unit nameplate for future reference.
146
45 45 60
60 60
.-JC
070C 080C
090C 1Ooc
230C
NOTE: Condenser pumpdown capacity is based on ANS1/ASHRAE Standard
15-1976 rating of 90°/0 full of liquid at 900F. To convert values to the older
ARI standard (80% full at 800 F), multiply pumpdown capacity by 0,888.
19 19 45 19 19 45
26 26 26 26 60
26 28
99 99
I
60
60
148
I
Table 11. Weight of refrigerant R-22 in copper lines
(Pounds Per 100 Feet of Type L Tubing)
Weight of Refrigerant, Lba.
0.054 3.84
%
0.100
112
0.162 7.12 .605 .156
%
0.336 24,0 1.26 .323
%
11A 0.573 40.8 1% 0.872
1% 1.237 88.0 2~~ 2.147 25/8 3.312 31~ 3% 6.398 4% 8.313 592.0 31.1 8.00
4.728 336.0 17.7 4.55 6.750
7.12 .374 .096
62.1
153,0
236.0 12.4 3.18 4.720
456.0 24.0 6.15 9.140
.202
2.14
3.26 .839
4.62 1.190 1.770
8.04
. . —.
Suction Gee
(Superheated to 65” F)
.052
.550
2,06 3.060
.077
.143 .232 .480 .620
1.250
11.190
I
IM 269 I Page 9
Table 12. Pressure-vacuum equivalents
o
50 100 150 200
300
500 1,000 0.019 759.00 2,000 0.039
4,000 0.078 6,000
8,000 0.156 10,000 0.193 15,000 0.290 745.00 29.330 20,000 0.387 30,000 50,000 0.967
100,000 200,000 3.670 560.00 22.050 600,000 760,000 14.697 0
0 760,00 29.921
0.001 759.95 29.920
0.002
0.003
0.004
0.006 759.70 29.910
0.009
0.117 754.00 29.690
0.580
1.930 860.00 25.980
9.670 260.00 10.240
759.90
759.85
759.80
759.50 29.900
758.00 29.840
756.00 29.760
752.00 29,600
750.00
740.00 29.130 730,00
710.00 27.950
29.920
29.920 1/5,100 —33
29.910
29.880
29.530
28.740
0
PHYSICAL DATA
1/15,200 1/7,600 — 40
1/3,600 1/2,500 — 21 1/1 ,520 — 12 1/760 1 1/380 15
1/189
1/127 1/95 1/76 1/50 1138 72 1125 84 1/15 101 2/1 5 125 114 213 192
1 Atmosphere 212
— 50
— 28
152
29 39 46 52 83
NDITIONS,TONS 0 T CIRCUITS
ER COMPRESSOR
t
C)DTlntd Al CTAC!KIC
“, ,, W! .-L “In”,, .”
CONDENSERS- HIGH EFFICIENCYFIN AND TUSL . ,, - ....,, ....-”..,.- ““””””— .
I
COIL FACE AREA, SQUARE FEET I 28.9 28.9 1 43.3 43.3I433 FINNED HEIGHT FINS PER INCH
~
CO&NSEiFANS-lili.. . ..... . ... . . .. . .._
NUMBEROF FANS – FAN DIAMETER,INCHES 4–26 NUMBEROF MOTORS– HORSEPOWER 4– 1.0 4– 1.0 FAN AND MOTORRPM 1100 FAN TIP SPEED, FPM 7760
TOTAL UNIT AIRFLOW, CFM 28,460 29,640 42.030
NOTES: @ Nominal capacity based on 950F ambient air and 450F saturated suction temperature @ Capacity reduction sequence depends on how the thermostat is connected. @ Cylinder bore for 50 hp: 2,6875; for 40 hp: 2.9375 (inches).
Cylinder stroke for 50 hp: 2.3438; for 40 hp: 2.1875 (inches).
X FINNED LENGTH, INCHES I4OX1O414OX1O4140x156140x156140x156140x156140x208140x208140x208140x206]40x206 140x208l~x208 140x208
X ROWS D)EEP
IECTDRIVE PROPELLERTYPE
43.0
I
2 2
4 4
I
12.500012.667512.6875 2,9375 2.9375 2.6875 2.6875
0-28-50-78-100 O-27-5C-77-I00
NA NA NA
IF TVDC WITU lhlTC130Al Cl lRf!!l Cm
I 12X2 16x2
52.9
I
25 30 30 35 34
4 4 4
I
.ziwu-r+luu U-z< -sY-u 1- ! w
1 16x2
4–26
1100 1100 1100 1100 1100 7760 7760
I
or
0-28-50-78-100
16x2 j 12X2 16x2I16x2
64.1 2
43.9 [ 58.5
6 6 6 6 6 8 8
or
43.3 I 57.8
6–26 8–26 8–26 8–26 10–.2%
6– 1,0
75.3
I
2
58.5 j58.5 I 585
35 40 40 54 547
2.6875 2,9375 2.9375 2.6675 2..5875
O-3366-83-1OQ
G17-33-50- o-17-32-5c- &25-50-6?- 0-25-50.6S
67-83-100
57.6
16x2I16x2
8– 1.0
7760
54,240 54,240 54,240
65.1
1
2 2 2
K13-8&83-l 00 0.25-50-75-103 O-25-5C-75-1OO
67-83-100 75-88-1oo 75-88-1OC
I 57.6 57.8 I 57.8 57.8 1 57.8
16x2 1 16x2 16x2 [ 12X3
8–1.0
7760 7760
97.7
I
I 585 5&5 1862 I 862
8– 1.0
112.1
I
608C
88
2.9375 2.9375
EM
10– 1.0
llCO
n60
62.CCO
1
57.8
12x3
I
Page
10 / IM 269
Table 14.
1200
Of&l I ckt.2 I CkLl I ckt.2
­UNIT CAPACllY@ARlCONDITIONS,(TONS)@ NUMBEROF REFRIGERANTCIRCUITS
UNIT OPERATING[ PUMPDOWNCAPACITY, 900/0FULL @ 90”F CABINET DIMENSIONS,L X W X H, INCHES UNIT WEIGHT, LBS. ADD’L WEIGHT IF COPPERFINNED COILS, LBS.
: COfdPfE880f?8 - COPELAMETICFULLY AGGRiWI%t
NOMINALHORSEPOWER NUMBEROF CYLINDERS PER COMPRESSOR CYLINDERBORE, INCHES CYLINDERSTROKE, INCHES OIL CHARGE PER COMPRESSOR
~ CAPACITY REDUCTIONSTEPS - PERCENTOF COMPRESSORDISPLACEMF”’
STANDARDSTAGING
I
) HEIGHT X FINNED LENGTH, INCHES ~0 X206~0 X206~0 X208180 X208~0 X208160X206~0 X208180X2C
CHARGE,LBS. R-22
. ... . .. . ... . .. --------- - --. ., ..--. .—. -
117.8 1334> 147.2
56.1 ] 56.1 70.2
86.2 86.2 141 229X83X 59 229X83X 92
5860 6783 7099
stmi.ntnsmIw
35-25
8-4
2.6875 2.6875
=1211375 ]2187512167521875121675121875 12~875lNote3INote312~ 12~
~60-1361160-136 ~6Ll136~
0-13-60-80-100 or
I
.,,\
2
1103 1236
35-25 35-25
6-4 6-4
2.6875
.“7.
U-L(-55-73-1OO
0-27-55-82-100
I1400CAC
ALP MODELNUMBEN
135C 150C
EI+T(NOTE Q
Cftt.1 I CW2 1 Cfrt.1 I CM.2
2. 2
70.2 )0.4 70,4 73.2 73.2 141 141 ‘1 .141 141
229X83X 92 229X83X 92 229X83X 92 263X83X 92 263X83X 92
1388
35-35 35-35
6-6
6-6
2.6675 2.6875
0-25-50-75-100
40-40 40-40
35-35
6-6 6-6 8-8 8-6 6-6 8-8
2.9375 2.9375
2.6675
170C
164.9 2 2
141
\7299
1388, 2060
0-17-33-42- 0-14-27-41-
50-75-100 54-77-100
105C
Cfd.1 ckt.2
~
180.8
88.5 98.5 96.5 98.8
68.5 203 203
6005
50-40 50-50
50-40
Note 3 2.6875 2.6675
Note 3
2060 220C’
Cld.1 ckr.2 Ckt.1 citt.2
~
199.5 222.1
230
9081 9301 2429 2429
0-12-24-37- 0-13-25-37-
49-73-100
~
2 2
I 98.8
230 I 230
230
50-50
60-60
8-6 8-8 M
2.9375
2.3436 2.3438
50-75-100
60-80
2.9375
TOTAL UNIT AIRFLOW, CFM
I
NOTES: 0 Nominal capacity based on 95°F ambient air and 45°F saturated auction temperature. @ Capacity reduction sequence depends on how the thermostat is connected. COCylinder bore for 50 hp: 2.6875; for 40 hp: 2.9375 (inches)
Cylinder stroke for 50 hp: 2.3438; for 40 hp: 2.1875 (inches)
62,000
I
76,500
I
87,480
I
67,480
I
81,960
I
Table 15. Major Components
COMPRESSOR CONTACTOR DESIGNATION FOR COMPRESSOR
4D-20 hp 4D-25 hp 4D-30 hp 6D-35 hp
Eli
..
090C
1Ooc
I1OC
Osoc
6D-35 hp
I
6D-40 hp 8D-50 hp
I
BD-60 hp
120C 6D-35 hp
135C
150C 6D-35 hp
w$:$~k.i,
...
NOTES:
1. All units have two independent refrigerant systems.
2. Compressors 1 and 3 used on Circuit 1 of 4-compressor units. Compressors 2 and 4 used on Circuit 2 of 4-compressor units.
3. Compressors 3 and 4 of 4-compressor units do not use unloaders.
G:. ,.
-$’”*W “t ..’5:.$% “ $
6D-35 hp
6D-40 hp
I
8D-50 hp 6D-50 hp
1
6D-60 hp
4D-25 hp 4D-30 hp
6L-W” ,IV
I
6D-40 hp ] — 8D-50 hp 6D-60 hp ] — 6D-35 hp 6D-35 hp 6D-35 hp 6D-35 hp ] 6D 8D-40 hp 6D-40 hp 6D-40 hp 8D-50 hp 6D-50 hp 8D-50 hp 8D-60 hp 8D-60 hp
— — —
1 1 1
4D-25 hp
— — —
4D-25 hp
)-35 hp 6D-40 hp 6D-40 hp MI–M5 M2—M6 8D-50 hp 8D-60 hp
M1—M5 M2—M6 — MI—M5 M1—M5 M2—M6
Mi—MK
,.! . . , ...- ..­M1—M5 M2 MI—M5 M2—M6
I
MI–M5 M2—M6 — MI—M5 M2—M6 I
I
MI—M5 M2—M6 M3—M7 M1—M5 M2—M6 MI–M5 M2–M6
M1—M5 M2—M6
1
MI—M5 M2—M6
M2—M6
M7—M6
&flJ6
95,820
I
M3—M7 M4—M6 M3—M7 M4—M8 M3–M7 M4—M6 M3–M7 M4—M6 M3–M7 M4—M8
I
,
95,620
— — —
— — —
M4—M8
1
!
1
1
IM 269 / Page 11
1
Figure 8. Dimensional Data — ALP-045C thru 120C
~ 2.5
,—
ABINET
DIA. LIFTING HOLES
AIR DISCHARGE
\
t
\
,o~
Eli/
Lli J
2.0 TYP. -’~
SPACING FOR
1.00. DIA ISOLATOR MOUNTING HOLES (6)
II
Mac
Ossc 070c Oaoc Osoc 100C 226.7 11OC 226.7 5.7 120C
122.7
175.7
175.7
228.7 7.2 7.2 22.6
228.7 7.2
226.7
39.2
9.0
9.5
8.7
5.7
9.0 21.6
8.7 22.6
7.2 22.6
7.2 24.6
5.7 27.2
5.7 27.2
39.2 23.6
22,3 38.3
22.6 43.6 22,6 43.6
22.6 46.5 24,6 46.5
27.2 46,5
27.2 46.5
23.8 97.5
11OC
120C
00 00 00 00
00
El
61,6 22,8 43,6 52,2
43.6 52,2
46.5 52,2
46.5 52,2 46,5 52.2 46,5 52.2 97,5 93.7
FAN ARRANGEMENTS
080C 090C 1Ooc
070C
00 00
00
El
1ye
15h 2% 21A 2% 21A 21/i 21A 21A 25A 2% 25h
1ye
278 278 2%
055C
00 00
1
045C
o
00
El
% %
7% % % % 7%
11A 11A
CENTEROF lSOIATOR
7/8 % % 7/8
‘h
1~~ 11A
51.0
65.0
66.0
64.0
63.0
80.0
81.0
85.9
13.0 43.0
13.0 58.0
13.0 58.0
13.0 58.0
13.0 58.0
13.0 56.0
13.0 58.0
13.0 58.0
109.0
162.0
162.0
215.0
215.0
215.0
215.0
215.0
Page 12/ IM 269
Figure 9. Dimensional
CONTROL
CENTER
..
lid
1-8-’4
cONTROL POWERENTRY
KNOCKOUTFOR !4If CONDUIT,
BOTHSIDES OF UNIT
— ALP-135C thru 230C
Data
1
r
8
+
v
2.5,1 DIA. LIFTING HOLES
FAN ARRANGEMENTS
150C
135C
———
170C 185C
00 00 00
00
00
B
205C 230C
00 ::
00 00 00 00
%
II 4
CKT. 2 SUCTION CONNECTION,2%11
(4)
Dimensions in Inches
AK!
DISCHARGE
t
/
+~ 2.O’TYP.
SPACINGFOR
1.00~ DIA. iSOiATOR MOUNTING HOLES(6)
LENGTH “.
:
23SC
B
263.4
263.4
B ‘. ~ 6 ;.3 :’ “
39.0
39.0
24.6
24.6
101.4
100.3
ISOLA’TO,RLOCATIONS
ii ‘ ‘
13.0
13.0
“,.:”’.s-’’ ,”:
95.0
95.0
.T
249.7
249.7
IM 269 / Page 13
FIELD WIRING
Wring must comply with all applicable codes and ordinances.
Warranty is voided if wiring is not in accordance with specifi­cations. An open fuse indicates a short, ground or overload. Before replacing a fuse or restarting a compressor or fan motor, the trouble must be found and corrected.
Copper wire is required for all power lead terminations at
the unit while either aluminum or copper can be used for all
other wiring.
ALP units may be ordered with internal power wiring for either single or multiple point power connection. If single point power connection is ordered, a single
block or non-fused disconnect switch is provided and wiring
within the unit is sized
in accordance with the National Elec-
large power terminal
trical Code. A single field supplied disconnect is required, An optional factory mounted transformer may be provided,
If multiple point wiring is ordered, three power connections,
Figure 10. Typical field wiring diagram for ALP-045C
L),,mnn,d
,Ph,––-r,l--r,l
BK
~“w::z:::---~;j;j
By O!her.
Termna-
PB 1
U“,!Ma!”
Bl,ck
one per compressor circuit plus one for condenser fans, are required and wiring with the unit is sized in accordance with
the National Electrical Code. Separate field supplied discon-
nects are required for each of the three circuits. A single power block is provided for all of the condenser fans and the
optional 115V control transformer.
CAUTION: Internal power wiring to the compressors for the single point versus the the multiple point option are dif­ferent. It is imperative that the proper field wiring be in­stalled according to the way the unit is built.
Figures 10, 11 and 12 show typical field wiring that is re­quired for unit installation, Items that require field wiring are liquid line solenoids (SVI and SV2), optional hot gas bypass solenoid (SV5) and the cooling thermostat as well as the unit power supply.
— 080C with 4 steps of capacity control
Condense,U.(I Comrx-m”
1
nd Fan
T
T
M.!ors
F.,,(F,]
L..i—,
cont..! stop SW!ch,,,,
,
6
t
510
L
T,rm<na!, For
T1’,mmsta!s
8 yl+
2!3
slag, 4 G+ >N;
Co”d,n,>ngU“ 1
control,
236
.
I
PSI ,,,
,,2
~—@+w&”-–@Y ---
‘Lp’Occ’’OcO”” la”””’
camp, .1
217
0
c
Page 14 / IM 269
NOTE: Standard M separate Pcwr supply c,rcaI1s for ccc:rols
LEGEND:
@ FIELD WIRING TERFIINAL
———
FACTORY WIPING
‘-— OPTIONAL FACTORv WIRING
FIELD WIRING
BK BLACK WIRING (LINE)
WHITE WIRING (NEUTRAL)
WH
Figure11.Typicalfield wiring diagram for ALP-080C –
10C with 6 steps of
capacitycontrol
D!mmcec! B, Olht.
.--” . . ...%
ml
Si’+-:-::--?: ! :
CO.,*
stop
S.”ch,e%)
~
Nom mm.”.w!m. m .?4
5?0 m 0“.,.11 t,-. dock .“d !!0. ,.,,,.
6
t 570
L-#J;.i ~ 2aii.-e-.jNn
m 1
U“ll u.,.
TWm..( B-k
—--—
..-’3,”.!!
_ ,
~
T
h
OPI’.”.,~“-
Ca.tr.i Tr..,tc.me!
1
C.tatncec “.<1 C.m,re’t.m
I
. . . F.. ..,.-
I
---—--i”
----4
Figure 12. Typical field wiring diagram for ALP-120C –
ym;:w. ,OA m-
i
—*W m
NOTE: For ALP-120C, 135C, and 150C, R3 and R4 would replace the compressor un-
loaders for compressors 3 and
4 of those size units. See page
43 for a typical diagram.
?’(9a No,.)
,.” p,,
L.i —, —,
4
‘aMld Stw S“llchl”)
s
?
~ NOTE R.Mv. .1”. - .“d
—.-—--
s, 0,.,.,,.11 ,he dock sw lb. ,wl,ch
Stm
2
Stw.e 3
w+- ‘z
CW2
213
Stls+ 4
(+ ~c- ‘~
,13
S,qw 5
@:I-o- Y
230C with 8 steps of capacity control
~+TF&y_
w
ml
C4nds.sing U“(I
Cantmh
R78
R17
ALP , 8SC–2W Only
117
Y
I
L
..—
c-w .,
,8
IB
Sting. 6
SW.9 7
SW+ a
IM 269 / Page 15
Table 16. Wire Sizing Ampacities
3PH, 60 HZ
ALP MODEL
045C
055C
070C
090C
1Ooc
Iloc
120C
135C
150C
170C
185C
205C
230C
ELEC. POWER
POWER SUPPLY O
208 230 184 460 @
208 1 278
208 230
5ktt
T
208 412 230 412 460 @ 207
460 (B 575 203
208 230 460 ~ 575 222
206 708 230
4600
575 266 208 767
230 767 460 @ 575
206 230 460 @ 575
Single Point
Power Supply
r
m
184
I
I 93
292 292
I
246
533 533 267
652 331
385
314 926
926 455 373
I
WIRE SIZE AMPS @
Muitlple Point Power Supply O
Elec. Ckt. 1 Elec. Ckt. 2 Elec. CM. 3
Fene & tintrols Cornpr.Cti. 1 hmpf. m. 2
25.6 79
25.6
12.8
12.7
25.6 96 133
25.6
12.6 49 66
12.7 39
33.6 I 133 140
33.6 16,8 16,7 45
41.6
41.6 140
20.8 70 21,5
41.6
41.6 175 175 (1) 3“
20.6
21.5
41.6
41.6 221
20.8 110 110 (1) 2V2°
50.6 217
25.3
26.3
50.6 217
50.6
25.3
26.3
58.6 252 252 (1) 4“
58.6 252
29.3 126 126 (1) 21/2“
30.7 101 101
58.6
58.6 315 315 (2) 3“
29.3 160 160 (1) 3“
30.7
56.6 359 359 (2) 3“
58.6 346
29.3 175 175 (1) 3“
66.6 452 452 (2j 4“
33.3 225 225 (1) 4“
35.6 180
79 39 49 (1) 11/’4”
I
33 39
96
133
66 70
140
I
56 56
191
I
69 69
66
221 221
109 109 (1) 2v2 “
87 87
217
109
I
87
344
I
122 122
96
96
I
133 (1) 23/2”
45
140
56
140
140
I
70
191
I
68
221
217
252 252
126 (1) ZV2°
I
101
252
344
I
346
180 (1) 3“
POWER ENTRY HUB
I
QUANTIYY & i
I
Slngb Point
Power Supply
I
(1) 2“
ilj 2
I
‘l’ ,,,
(1) 23/2”
(1) 11A” (Ij IIA,I
I
[1)2M”
{lj 2Th” (1) lvz”
(1) l!~,,
(1)2V2“
(1) 2V2“
I
~1j 1VZ” (1) 11/4,,
(1) 3“
I
~lj 2
1) 11/2”
1(
(1) 4“ (1) 4“
I
~lj 4!s
(1) 2“ (1) 49’
ilj 4’
I
‘1’ 2<,
(1) 4“ (1) 21/2,,
(2) 3“
I
21/2,,
~1j
(2) 3“
mm. Point
Power supply
(1) 2“ (1) 2“ (1)
l%”
~lj lIA.
(1) 272” (1) 27/2“
(1)lYz”
11) 11~”
(1) 3“ (1) 3“ (1) 2’”
Jl) 1
1/2,,
(1) 3“
(1) 3“ (;) :“
(1) 4“ (1) 4“ (1) 2“
, 2.,
(1) 4“ (1) 4“ (1) 21/2“ (lj 2v2 r’
(2) 21A” (1) 1“ (2) 2Y2“ (1) 1 “ (1) 2V2“
jl j 21/2,,
(2) 2“ (1) 1’” (2) 2“ (1) 1“ (1) 21/2“
(1) 21/2“ (1)1’’(1)2’’(1)2 ?>”
(1)1’’(1)2’’(1)2Y” (1) 2Vz” ~lj z~hn
(1)1“(2) 2V2“
(1) 1“ (2)
(1) (1) 21,2,,
(1) 1“ (2) 3“ (1) 1“ (2)3” [1) 3“ [1) 21/2”
[1) 1“ (2) 3“ (1) 1“ (2) 3“
ilj 3 [1) 1“ (2) 3“
[1) 1“ (2) 3“’ [1) 4’” [1) 3~/’2“
:1) 1“ (2) 4“ :1) 1“ (2) 4“ ‘1) 4“ ;1) 4“
2Y, “
3“
I
ELECTRICAL DATA NOTES
0 ALLOWABLE VOLTAGE LIMITS:
Unit nameplate 208V/60Hz/3Ph: 187V to 253V
(except ALP-090C: 180V to 220V)
Unit nameplate 230V/60Hz/3Ph: 187V to 253V
(except ALP-090C: 207U to 253V) Unit nameplate 460V/60Hz/3Ph: 414V to 506V Unit nameplate 575V/60Hz/3Ph: 517V to 633V Unit nemerYate 360V/50Hz/3Ph: 342V to 418V
@ Compressor RLA values are for wire sizing purposes only and do not reflect
normal operating current draw If unit is equipped with SPEEDTROL motors,
the first motor on each refrigerant circuit is a 230V single phase, 1 hp
RLA of 5.6 amps
with an
@ Compressor LRA for part winding start are for the first winding. If the unit
Page 16 / IM 269
motor,
is equipped with SPEEDTROL motors, the first motor on each refrigerant circuit is a 230V single phae, 1 hp motor, with an LRA of 145 amps Unit wire size amps are equal to 125% of the largest compressor-motor
(!3
RLA plus 100o1oof RL4 of transformer Wre size amps for separate 115V control circuit po;er is 12 amps for all units shown.
o
Quantity and size of power entry hub(s) provided with unit
E’
Single fxJint ~wer supply requires a single fused disconnect to supply elec­trical power to the unit. Multiple point power supply requires three independent power circuits with
CL
separate fused disconnects Data also applies to 380V/50Hz/3Ph units
@
all other loads in the circuit includnq control
Table 17. Compressor and Condenser Fan Motors
XEO ROTOR AMPS @
COMPRESSORS
056C
“ 070C
080c
beoc
100C
11OC
.1200 ““”
f35c
160C
170C
185C
206C
Z30C
,.,’
(1) 31 (1) 39
208 (4) 4.0
230 (4) 4.0 4600 575
208 (6) 4.0 230 (6) 4.0 46063 (6) 2.0 575 (6) 2.2
208 (8) 4.0 230 (8) 4.0 460 @ (6) 2.0 575 (6) 2.2
206
230 (6) 4.0 460 @ (6) 2.0 575 (8) 2.2
208 (8) 4.0 230 460 @ (8) 2.0
575
I
208 (lo) 4.0 230
. .
460 @ (lo) 2.0 575
208 230 (lo) 4.0 460 @ (lo) 2.0 575
208 (lo) 4.0 230 460 @ 575
208 230 (12) 4.0
460 @ (12) 2.0
575
208 (12) 4.0 230 (12) 4.0 460 @ (12) 2.0 575
206 230 (12) 4.0 460 @ (12) 2.0 575
208 (14) 4.0
230 460 @ (14) 2.0 575
208 (14) 4.0 230 (14) 4.0 460 @ (14) 2.0 575 (14) 2.2
(4) 2.0 (4) 2.2
(8) 4.0
(8) 4.0
(8) 1.6
I
(lo) 4.0
(10) 1.6 (lo) 4.0
(1o) 2.2
(lo) 2.0 (lo) 2.0 (lo) 2.2
(12) 4.0
(12) 2.2
(12) 2.2 (12) 4.0
(12) 2.2
(14) 4.0
(14) 2.2
REFER TO PAGE 16 FOR ELECTRICAL DATA NOTES
(1) 26 (1) 31 (1) 77 (1) 106
(1)77 (1) 106
(1) 39 (1) 53
(1) 31 (1) 36 10.3 (1) 106 (1) 112
(1) 106(1) 112 (1) 53 (1) 56 9.9 (1) 36 (1) 45 10.3
(2) 112 (2j 112
(2) 56
%--t-ik
i2i 71
m
{2j 66 (2) 201
(2) 201 17.0
%--HE
(2j 56 (2j 39
(2) 45 (2) 31 10.3
w--l--+
i4i 56 (4j 45
(4)
153
h--l-+
m
I
I
I
I
I I
10.3
17.0
17.0
17.0
17.0
17.0
17.0
17.0
9.9
9.9
10.3
17.0
9.9
9.9
9.9
9.9
7.9
-
(2j 565 (2) 283 (2) 156
{2j 405 (2) 1070
(2) 1070 (2) 656
(2j 565 (2j 428 @j 340 @j 250 (2) 283 (2) 214
(2) 230 (2) 172 (3) 565 (1) 426
(3) 565 (1) 428 (3) 340 (1) 250 (3) 283 (1) 214 (3) 156 (1) 117 (3) 230 (1) 172 (3) 138 (1) 103
(4) 565 (4) 565 (4) 230 i4i 283 i4j 230 i4j 138
(4) 660 (4) 400
(zj340
I
(2j 262 (2) 654
(2) 156(2) 117 (2) 138 (2) 103
(3) 340 (1) 250
(4) 340
I i4i 156
km--l-L
i4j 510 I i~ 330
m
THERMOSTAT WIRING
Since it is impossible for McQuay to anticipate the type of
installation that an ALP condensing unit maybe used on, we mostat so that as successive stages of cooling are called for, do not provide a thermostat. We do, however, provide the compressors in the unit will be started to alternately in­numbered terminals inside the unit control center to which a thermostat maybe connected. These terminals are shown and labeled “Terminals For Thermostat” on the electrical show typical staging sequences for 4, 6 and 8 step schematics. thermostats.
On a two-circuit unit it is important to connect the ther-
crease the condenser load from refrigerant circuit 1 to cir­cuit 2. This is illustrated in Table 17. Figures 10, 11 and 12
IM 269 / Page 17
Table 18. Capacity reduction
UNIT WrTH STANDARD
ELECTRICAL COMPONENT
ENERGIZED SUCTION PRESSURE CONTROLLED
I
UNIT
ALP
SIZE
Svl +Ul
45C, 055C
070C
Sot, Oeoc SVl+Comp. l, U2(Ul da-energized) Ooc,
20C, 135C SVI + Comp. 1 (UI, U2 de-energized)
150C SV2 + Comp. 2 (U1, U2 de-energized)
70C, 05C, 230C
NOTES:
1. Compressor staging for units with suction pressure controlled unloaders and unloaders controlled from a remote source (discharge air, return water, efc ) is the same
2. See page 54 for more information on unloaders controlled from suction pressure.
SV2 + U2
SV1 (Ul de-energized) SV2 (U2 de-energized) SV1 +Comp. 1, Ul, U2 SV2 +Comp. 2, Ul, U2
11OC SV2+Comp.2, U2(Ul da-energized)
SVl+Comp, 1 (Ul, U2 de-energized) SV2 + Comp, 2 (Ul, U2 de-energized) SVI +Comp, 1, Ul, U2 SV2 +Comp. 2, Ul, U2
SVI + Comp. 1 + Comp. 3 (R3 energized) SV2 + Comp. 2 + Comp. 4 (R4 energized) SV1 +Comp. 1, I-H, U2 SV2+Comn. 2. U1. U2 SV1 + Comp, 1 (U1, U2 de-energized) SV2 + Comp. 2 (Ul, U2 de-energized)
1S5C
SV1 + Comp. 1, U1, U2 + Comp. 3 (R3 energized) SV2 + Comp. 2, UI, U2 + Comp. 4 (R4 energized) SV1 + Comp. 1 + Comp. 3 (Ul, U2 de-energized) SV2 + Comp. 2 + Comp. 4 (Ul, U2 de-energized)
I
1
CAPACITY REDUCTION
I
UNLOADERS
Stage 1 Stage 2 Stage 3 Stage 4 Stage 1 Stage 2
— —
Stage 3 Stage 5 Stage 4 Stage 6 Staga 1 Stage 1 Stage 2
— —
Stage 3 Stage 4 Stage 6 Stage 1 Staoe 2 Stage 3 Stage 3 Stage 4
— —
Stage 5 Stage 6
1
I
UNtTS WITH OPTiONAL CAPACITV REDUCTION
— —
Stage 1 Stage 2 Stage 3 Stage 4
Stage 2 Stage 3 Stage 4 Stage 5
Stage 1
Staae 2
Stage 4 Stage 5 Stage 6 Stage 7 Stage 6
WATER PIPiNG FOR CHILLED WATER APPLICATIONS
Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities. They can supply the installer with the proper building and safety codes required
for a safe and proper installation.
FLOW SWITCH FOR CHILLED WATER APPLICATIONS
A WATER FLOW SWITCH MUST BE MOUNTED in either the entering or leaving water line to insure that there will be adequate water flow and cooling load to the evaporator before the unit can start. This will safeguard against slugging the compressors on startup. it also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up.
A flow switch is available from McQuay under ordering
number 860-175033B-O0. it is a “paddle” type switch and
adaptable to any pipe size from 1” to 6“ nominal. Certain
Table 19. Flow switch minimum flow rates
NOMINAL PIPE SIZE
I
i
I
(INCHES) ACTIVATE SWITCH (GPh3)
1
11A
11/2
2
21/2
3 30.00 4 39.70 5 58.70 6 79.20
MINIMUM REQUIRED FLOW TO
I
6.00
9.80
12,70
I
18.80
24.30
minimum flow rates are required to close the switch and are listed in Table 18. installation should be as shown in Figure
13. Electrical connections in the unit control center should be
made at terminals 5 and 6. The normally open contacts of the flow switch should be wired between these two terminals. There is also a set of normally closed contacts on the switch
that could be used
dicate when a “no
Figure 13.
I
for an indicator light or an alarm to in­flow” condition exists.
Flow Oireclion
1.00 NPT FIOW Switch
L,,,,, 0,. -M”,rn”nl
Switch
Aiter
~ 5 Pipe Oia -Minimum
eefore %ftch
Page 18 I iM 269
EVAPORATOR FAN INTERLOCK FOR AIR HANDLER COIL INSTALLATIONS
It is important to interlock the air handler evaporator fan with
the condensing unit control to insure that there will be a cool-
ing load on the evaporator before the unit can start to pre-
vent compressor slugging. A pair of terminals for each
refrigerant circuit is available in the unit control center for this
UNIT LAYOUT & PRINCIPLES OF OPERATION
purpose. Remove the jumpers between terminals 111 and 112 for circuit 1 and211 and 212 for circuit 2. Use these ter-
minals for the evaporator fan interlock contacts. Be sure to keep circuits separate by using two contacts on dual circuit machines.
-J
Figure14.
Major Component Locations
The figures below illustrate component locations within the unit for each unit size.
COMPRESSOR No. 1
M
~ E? I@@@@
COMPRESSOR No. 2
L- -1
TOP VIEW OF UNIT
205C, 230C
*
COMPRESSOR No. 1
COMPRESSOR
No. 2
CONTROL CENTER
All electrical controls are enclosed in a weatherproof control center with keylocked, hinged access doors. The control center is composed of two separate compartments, line voltage and control voltage, All of the line voltage com­ponents, except for the input terminals of the PVM, are
‘\
COMPRESSOR No. 4
located in the compartment on the right side of the unit. The control voltage components are located on the left side with the live terminals located behind a deadfront panel. This pro­tects service personnel from live terminals when accessing the adjustable and resettable controls.
IM 269 / Page 19
CONTROL CENTER LAYOUTS – ALP-045C thru 11OC
————_
Figure 15. Left Side, 115V Control Section
Figure 16. Right Side, High Voltage Power Section
7 FHmmI
ODDOU
P
m
PB2
El
o
PB3
n
————
CBS
CB1
.—— ———
m
II EII
CONTROL CENTER LAYOUTS — ALP-120C thru 230C
Figure 17. Left Side, 115V Control Section
TB5 (40–63)
Raceway
=
El
[ TB4(II0-124)(210-224) I I I ~[~
I
I II
TB6 (70–93)
Raceway
GRD 9
IT
T2
n
NOTE: PB1, PB2, PB3 are used with multiple point power wiring.
Figure 18. Right Side, High Voltage Power Section
I
PVM
o
PB2
El
n PB3
El
~mmjm
——————
.—————
—.
————
——
EIEI
Page 20 / IM 269
EIEI
TC
1
11
mIimEIE
NOTE: PB1, PB2, PB3 are used with multiple point power wiring.
ELECTRICAL LEGEND
DESIGNATION
AB Cll, C21
CBI-S
COMPFI.1-4 CP1 CP2 DAC1 DAS1 DW FI F2 FB1–4 FS5 FB6–10 FBI ,2 GFI GRD
HPI, 2
—4
HTRI
HTR5
JB5 JS6
LP1 , 2 Ml–lo MI1-27 MJ MPI-4 MTR1 1-27 NB NSS
OP1–4
PBI–3 PC1–4 PC5, 6
PC8–10 PC12-22 Psi, 2 PVM
DESCRIPTION STD. LOCATION
ALARM SELL
CAPACITORS FOR SPEEDTROL MOTORS
CIRCUIT BREAKERS, COMPRESSOR MOTORS COMPRESSORS 1 THRU 4 CENTRAL PROCESSOR CENTRAL PROCESSOR SATELLITE DISCHARGE AIR CONTROL DISCHARGE AIR SATELLITE DISCONNECT SWITCH, MAIN FUSE, CONTROL CIRCUIT FUSE COOLER HEATER FUSEBLOCKS, COMPRESSOR MOTORS FUSE SLOCK, CONTROL POWER FUSESLOCKS, FAN MOTORS
FREEZESTATS, CONTROL GROUND FAULT INTERRUPTOR GROUND
HIGH PRESSURE CONTROLS
HEATERS, COMPRESSOR CRANKCASE
HEATER, COOLER BARREL
JUNCTION SOX FOR COOLER HEATER JUNCTION SOX FOR HEAT RECOVERY
LOW PRESSURE CONTROLS CONTRACTORS, COMRPESSOR CONTRACTORS, FAN MOTORS
MECHANICAL JUMPERS
MOTOR PROTECTORS, COMPRESSOR
MOTORS, CONDENSER FANS NEUTRAL SLOCK NIGHT SETBACK OIL PRESSURE CONTROLS POWER SLOCK, MAIN PRESSURE CONTROLS, SPECIALS PRESSURE CONTROLS, HI AMSIENT UNLOAOER PRESSURE CONTROLS, SUCTION UNLOAOER PRESSURE CONTROLS, FANTROL PUMPDOWN SWITCHES PHASE VOLTAGE MONITOR
FIELD MOUNTEO
BACK OF CONTROL SOX OR ON BULKHEAD CONTROL SOX
BASE OF UNIT CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL BOX
CONTROL SOX CONTROL BOX CONTROL BOX SUCTION LINE NEAR COOLER CONTROLSOX CONTROLSOX ON COMPRESSOR ON COMPRESSOR WRAPPEO AROUNO COOLER
SARREL NEAR COOLER ON SASE RAIL UNOERSIOE OF COIL ON lN­TERMEOIATE TUSE SHEET ON COMPRESSOR CONTROL BOX CONTROL SOX CONTROL BOX COMPRESSOR JUNCTION BOX CONOENSER SECTION CONTROL BOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX OR ON UNIT ON COIL HEADER
CONTROL SOX ON COIL HEADER CONTROL SOX CONTROL SOX
DESIGNATION
Rl, 2 R5–8 R9–12 R13, 14 R3, 4, 17, IS R19 R21 ,22
R23-30 RS14 51 S2-4 S5 SC1l, 12
SL1 Svl , 2 SV5, 6 SV1O, 20
Svll, 21 T1
T2 T3 TS2
TS3 TB4-6 TCI TC2 TCIO TC11 TC12 TC12-25 TOI-4 T05–S T09, 10 TO1l, 12, 13 TO14 T015, IS T017; 18, 19 T020–24
U1, 2
OESCFNPTION
RELAYS, RESET OR ALARM RELAYS, SAFETY RELAYS, STARTING RELAYS, LOW AMBIENT START RELAYS, CAPACITY CONTROL
RELAY, HEAT RECOVERY RELAYS, HI AMBIENT, HI RETURN SUCTION UNLOAOERS RELAYS, SPECIALS RESET SWITCHES SWITCH, CONTROL STOP SWITCHES, LEAO-LAG SWITCH, HEAT RECOVERY SPEEO CONTROLS
SOLENOIO 000R LOCK SOLENOIO VALVES, LIc2UI0 LINES SOLENOIO VALVES, HOT GAB BYPASS SOLENOIO VALVES, WATER CONOENSER (NORMALLY OPEN) SOLENOIO VALVES, AIR CONOENSER TRANSFORMER, MAIN CONTROL TRANSFORMER, 24V CONTROL TRANSFORMER, FAN SPEEOTROL TERMINAL BLOCK, 120V, FIELO TERMINAL BLOCK, 24V. FIELO TERMINAL BLOCKS, CONTROL THERMOSTAT, UNIT THERMOSTAT, COOLER SARREL THERMOSTAT, SPECIAL THERMOSTAT, HIRETURN WATER UNLOAOER CONTROLSOX THERMOSTAT, SPECIAL THERMOSTATS, FANTROL TIME OELAYS, COMPRESSOR LOCKOUT TIME OELAYS, COMPRESSOR PART WINOING CONTROL BOX TIME OELAYS, LOW AMSIENT TIME OELAYS, COMPRESSOR SEQUENCING TIME OELAY, ALARM BELL TIME OELAYS, FREEZESTAT TIME OELAYS, HEAT RECOVERY TIME OELAYS, SPECIAL UNLOADERS
WATER &
S70. LOCATION
CONTROL BOX CONTROL BOX CONTROL BOX CONTROL SOX CONTROL SOX CONTROL BOX CONTROL SOX
CONTROL BOX CONTROL BOX CONTROL SOX CONTROL SOX CONTROL BOX SACK OF CONTROL SOX OR ON BULKHEAD CONTROL SOX CONOENSER SECTION CONOENSER SECTION CONOENSER SECTION
CONDENSER SECTION CONTROL SOX CONTROL SOX ON BULKHEAD CONTROL BOX CONTROL BOX CONTROL BOX CONTROL SOX ON COOLER cONTROL sox OR ON UNIT
CONTROL SOX OR ON UNIT CONTROL BOX CONTROL BOX
CONTROL BOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX CONTROL SOX ON COMPRESSORS
Figure 19. Recommended Unit Disconnect Location
HINGEO 000RS ON CONTROL CENTER
\
NOTE: MOUNT DISCONNECT ON STATIONARY PANEL SO THAT IT 00ES NOT INTER. FERE WITH HINGED 000RS OR WITH AIR INTAKE INTO COIL.
\
S.00 MIN.
4’
IM 269 I Page 21
NORMAL SEQUENCE OF OPERATION
The following sequence of operation is typical for ALP SEASONCON air cooled condensing unit, models ALP-045C through ALP-230C (items in italics apply only to Mode/s
ALP-720C thru ALP-230C). The sequence varies somewhat
depending upon options.
Startup
stop switch S1 closed, 115V power is applied through the con­trol circuit fuse F1to the compressor crankcase heaters HTR1, HTR2 (HTR3, HTR4), the compressor motor protectors MP1,
MP2 (MP3, MP4) and the primary of the 24V control circuit transformer. The 24V transformer provides power to the con­tacts of the low pressure controls LPI and LP2 and the com-
pressor lockout time delays TDI and TD2.
When the remote time clock or manual shutdown switch
turns on the chilled water pump, the flow switch closes and
115V power is applied to the relay contacts on the unit ther-
mostat. The unit will automatically operate in response to the
unit thermostat provided the manual pumpdown switches PS1 and PS2 are closed (in the ‘(auto” position); the compressor
lockout time delays TD1 and TD2 have closed, energizing the safety relays R5, R6 (Rz R8); and the freezestats FS1 and
FS2, high pressure controls HP1 and HP2, and compressor motor protectors MP1, MP2 (MP3, MP4) do not sense failure conditions.
On a call for cooling, the unit thermostat energizes the li­quid line solenoid valve SV1 for refrigerant circuit #1. This opens the valve and allows refrigerant to flow through the ex­pansion valve and into the evaporator. As the evaporator refrigerant pressure increases, the low pressure control LPI closes. This energizes the compressor starting relay R9, start­ing the compressor via the compressor contractors Ml and
With the control circuit power on and the control
M5. Closing the R9 contacts also energizes the condenser
fan motor contacts Mll, M12, M13 and M14, starting the fan
motors.
As additional stages of cooling capacity are required, the
unit thermostat energizes the liquid line solenoid valve SV2
of the refrigerant circuit #2. After the compressor sequenc-
ing time de/ay TD77 has closed, the same starting sequence is initiated in refrigerant circuit #2.
If still more cooling is required, the unit thermostat will start the remaining compressors and then de-energize unloader solenoids until the capacity requirement is met.
Pumpdown energize unloaders and unload the compressors, and then de-energize the liquid line solenoid valves SV1 and SV2, caus­ing the valves to close, When the compressor has pumped most of the refrigerant out of the evaporator and into the con­denser, the low pressure controls LPI and LP2 WiIIopen, shut­ting down the compressors and the condenser fan motors, If refrigerant leaks into the evaporator, the increse in pressure will cause the low pressure control LPI or LP2 to close, This will energize the compressor starting relays R9 or R1O and start the compressor, which will quickly pump the refrigerant out of the evaporator and into the condenser (recycling pumpdown).
A compressor which repeats recycling pumpdown every 5
minutes indicates a malfunction due to the temperature con-
trol or a system cause. A build up of heat in the compressor without proper cooling of suction gas could cause a
mechanical failure in the compressor. McQuay recommends
corrective measures be taken if the compressor recycles
repeatedly within 15-minute intervals.
— As the unit thermostat is satisfied, it will
CANADIAN
Canadian units which are CSA listed and are equipped for multiple point power connections have a sticker (see figure at right) next to the wiring diagram in the control box, This notifies the installer that local authorities may require the unit to be connected to a single electrical power source. Check with local authorities for requirements.
CSA LISTING
Although this unit may
be provided with options requiring more than one source of electrical supply, some electrical inspection authorities may require this unit to be connected to a single external electrical supply.
Page 22 / IM 269
TYPICAL POWER WIRING DIAGRAMS
SINGLE POINT, WITHOUT SPEEDTROL
I
ALP-045C ALP-045CI055C
— 2081230V, AL, PW
380/41 514601575V, AL, PW
Ill
P%l
F“=E
L_L_T*’”
,,..,
+&t-t-.+’ ,
.!, 0“ ““ITS WITH
s.0/.13/4.0 /57,“-AL.
F
!.”.
...
I
L
I*
J
=%l=’=z
FB6
Ml!
.--,,,—
—,!, —
—,, ,—
FB7
..
I
M!2
m=’== =
ila---”
—,, s—
1“
I
<
f’”’%+y:[
7+”k @~; - –
1,
COMPR
*2
*@
=0 V./50-60 HZ
FROM 0S1 Q& PBI
I
u
+1++ b.’+ ’:2
, ‘-tam “ *.A%
,
o+”’L,
“--l=+ ~~
“*M
\
L1— L2
T( 12
I F05
ALP-055C, 2081230V
T
./,
,eo/41s/4eon73 v-AL.
INCLUDESCB6 FORCOMPRESSOR
0“ ““11s WITH
200 V /60 HZ
FROM 0S1 sx PO!
U- L2
I
,1 TZ
m
FROM DSI E PB1
U- LZ
,2 I
I
,,
m
4AG.1+
““’+mky:,
!15 v.
I ,05
I
—,,.—
—l, s—
#2
FROM 0S1 E PBI
u- L2
I
,1 12
m
“,H3H2H4
kid
FROM 0S1 X PBI
F,5
G
U- L2
I
,, T2
m
,,
I F,,
I ,,5
575 V/60 HZ
FROM 0S1 S& PE 1
u- ,2
I
,1 12
II
““’a;:,
J
,15V
I FB5
— l,e —
—,m -
—,,,—
sz—
—.-,
— ,53 —
—,s.3—
—,,,—
—!s*— —,53—
,.,.
..
IM 2691 Page 23
MULTIPLE POINT WITHOUT SPEEDTROL
ALP-045 CI055C – 2081230V, AL, PW
380/41 51i601i75V, AL, PW
~:~
,,
PHASE/VOLTAGE
MONITOR
El
,32
L
ELECTRICAL CIRCUIT 1
Ill
_,, ,—
—!,, —
—r, ,—
7+”2,, ,,”%- ,,,,
,,
cOMPR
*2
se
e g’
o-l+ ,2 ,, ,2
, ‘+ ‘3 ‘3 ‘3 - “’
7
‘“+”’L
‘+ L2
12+ L3
I l%%-%
IFe_Y’”
x
GRO LuG
$
- C,RC
—FROM Psl — I
.,
,2
l—
,, ,.
“, “3 “, . .
TJi!F
.$’”’+3,:3
I ,05
J
—,,.—
—l,, —
—l, ,—
l,c —
—,,,—
—!,, — —,, , —
—l, o—
—,,.— —,,,—
—l, ,—
Page 24 I IM 269
.,.
SINGLE POINT, WITH SPEEDTROL ALP-045C
ALP-045CI055C
– 2081230V, AL, PW
— 380141514601575V, AL, PW
1-
—,0! —
— ,0,—,!,
11. %&&-t”””
— ,o, —
1+”’,, ,,%+
,,
COMPR.
*1
*
<F
ALP-055C, 20W230V INCLUDESCB6 FOR COMPRESSOR#2
$,
COMPR
*2
,.
<T
-l+. n
,
‘+ ‘*
7
~+”’ ,,
:+ Ls
-%
,/, 0“ u,,, w,,”
SS0/4 lB/4MP7~ U - AL .
7+”2., ,,‘2T-#-
4+ ,, . %i-
s
‘+ ‘s
,
o-G”’L,
“i+ L,
“w 3
\
“/, 0“ WI,,, w,,”
S9./4lS/_O/S7S V.-AL.
,% _*+
,s
+d-
.*&
— ,e7—
— ,o. — — ,.*—
—,lo —
—,, ,—
—,,2=
—,, ,—
—,14—
—,ls —
—,,, —
—,,, —
—1,2—
— ,,, —
— ,,. —
—,3, —
— ,,, —
300 V./X7-60 HZ
FROM DS, QE PB,
,,— ,,
I
,, ,2
l-l
[ ,,5
FROM DSI m PBI
,1— M
I
,, ,2
n
FROM 0S, QL PB,
,1— u
I
,1
n
“’td.d:,
““2*;:
,,5 v . . .
I ,,5
,, I F05
~’”’+y,:c
FROM DSI Q& PBI
I
mm m, Q& PO!
,,—,,
,, ,,
“1 “, .2 “.
u
I ,05
“’”’*Y,
575 v/60 HZ
,,0. 0s, n PBI
L1— .2
,, ,,
U
,,5 v
I ,05
,,o —
—(51—
— ,,, — — ,,, —
—,,o—
—-,,1—
—1,2—
—,s3—
lM 269 / Page 25
SINGLE POINT, WITHOUT SPEEDTROL ALP-070C, 080C, 090C
ALP-1OOC
– 2081230V, AL, PW
– 380/41514601575V, AL, PW
FB6 Mll
%=’=z
“%5,, WIT”
ALP-070C, 080C, 090C, 208/230V ALP-1oOC,380/415/460/675V INCLUDESCB5 & CB6 FOR COMPRESSORS#1 & #2
‘+q+-
... ... .
FROM M ~ P81
,1— ,2
I
,( ,2
“1 “2 “4
u
~’”’ey~
1
I ,,5
sOo/4! s/460/,7, v -A,
——_
c“ !_
“,. .“ ““!7S WITH
we/. !v46o/,7, v-u
FROM 051 MT P.!
.,—.,
I
,,
I ,85
,2
$1
FROM DSI 9.? ?6,
u- ,2
I
,, ,,
u
““iifiiq?
1)3 v
I ,,5
68
FROM D51 m PO!
,1— ,2
,8
“, “3 Hz “4
w
y+gf,
,, I F05
J
FROM 0s1 m P81
,1— u
I
_,a IFB5
,,
$x
A-L;,
““Z+HIT;:<
,,$ v G
—l,. —
_,, !—
—!,, —
—“, —
_-, ,.a —
—,sl —
—l,, — —,, ,—
Page 26 / IM 269
MULTIPLE POINT, WITHOUT SPEEDTROL ALP-070C, 080C, 090C, 100C — 208/230V, AL, PW
380/41 514801575V, AL, PW
ELECTRICAL CIRCUIT 1
Ill
,,,
n-n-l “or
I 1-
F=E
l- Jxl-
PHASE/VOLTAGE
MONITOR
EF
I+”’,, ,,”:,- ,,Ec,
-
,2 ,2 L,
1,
COMPR.
#l
(-’g%
SO
1,
COMPR
4$2
,.
Qm
++
3
‘+ s ‘3 ‘1
7
,
7
M5
++* *
d
6+1”
,+”2,, ,,’’:+- ,,,,.,
-1+ l., ,2 ‘d-- ‘::
‘+ ‘3 ‘3 d_-
+M=LI
“i+ L2
‘2% L3
t
4-- *2
GRD LUG
$
CIRC
—,10—
—FROM PSI —
L(—u
I
,, ,2
n’
“LMAJ”;,
“02-;:[
I F,,
—FROM Pot —
I
—FROMPBl—
L(— ,2
I
T, 12
LF
:’”’*Y?
115 v GRD
I ,05
—FROM P81—
I
—FROMPBl
—FROMPBI
COFB5K$F’5
—l,.a —
—,,, —
—lsz — — ,,, —
—,so —
—1,1—
—,,, —
—l,, —
IM 269 I Page 27
SINGLE POINT, WITH SPEEDTROL ALP-070C, 080C, 090C
ALP-1OOC
– 2081230V, AL, PW
– 380/41514601575V, AL, PW
F“a:
L---,*’”
MONITOR
Ml
——
\
“,. w ““!7s WITH
ssor4!,/4.o/s7, v -m.
ALP-070C, 080C, 090C, 208/230V ALP-100C, 380/415/460/575V INCLUDESCB5 & CB6 FOR COMPRESSORSal & #2
“k,, .“ ““,,, w,, ”
We., !s,+$o,,,s v-.,.
- ‘$’:’”’’’C’”:
,
!
4—,
‘“ I I I I A’- !l==’i-l ‘0 ‘0” c“--
r
FB8
I~,,&#lE5&T”L’“0’-
M22
=-= 02
M23
—!, ,—
— ,,z —
—,,, —
,,4—
i; EJ===j
,,
m
—l,, —
—!,, —
FROM 0s! SE PB!
U- LZ
I
,( T2
u
+&&:,
Page 28 I IM 269
230 V/60 HZ
.!— L*
I
,, ,,
11
FROM D51 Q& P81
I ,,5
L!— ,2
I
,, ,2
11
“’kIAJ””
“+w’f%qf,
I ,05
I ,,5
185v
FFOM D51 SE P81
I
FROM 0S( S3 PBI
,,— L2
I
,, ,,
m
—!s. —
—!, , —
—,,, —
575 V/60 HZ
FROM DS, QS PBI
I
,05
I
!3
L!— .
,, ,,
I ,,5
— ,,, —
—,,.—
—l, ,—
—.-r,, — —,, ,—
SINGLE POINT, WITHOUT SPEEDTROL
P
ALP-11OC
– 2081230V, AL, PW
380/41 5/4601575V, AL, PW
i ‘VM 4-’”
--i-t
FB6 Mll
I
w%
I
-m=’
$J=:=i =“
,,
49
lo,
.ll. ——
380 V/50-60 HZ
FROM 0S1 43 P8 1
u- ,,
I
,, ,>
=+&&;:
I [ ‘:=,:,
FROM 0S1 QB PB1
u- ,2
I
,, ,,
1.1
“1 “2 “.
Ld
FROM 0S, QI PBI
““’%:?
L,— L*
I
,, ,2
u
I ,,5
“4
115 v
I FB5
I ,05
GRI
FROM 051 E PB!
I
FROM0S1 m PBI
L,— L.?
T, ,,
m
I ,05
FROM 0S1 S.E PBI
M- u
_ I FB5
I
,, T,
!$
91
—,42—
lso —
—,,, —
—l,, —
—,,,—
—,s.3—
—,,,—
z—
—,,
—ls3—
IM 269 / Page 29
MULTIPLE POINT, WITHOUT SPEEDTROL ALP-I 10C
— 2081230V, AL, PW
380/41 514601575V, AL, PW
Ml
.—
7+M2L,
n,
COMPR
*2
.*
GE’
380 v/50-60 HZ
—FROM P81 —
-g’” ~,o;g
x, xl
a-b L, T, ,+- ~g
,
‘~ ‘3
7
‘“+”’,,
“+ L2
“i& ‘3
~’”’+g?o
Soolg
501~1,...
,,, v
m
i ‘VM ‘2+531
L---T*’”
PB 3
,, ,+-
,> *-
GRO LUG
~
200 V/60 HZ
—FROM PBI —
,1— ,2
I
,$ ,2
w .2 “4
u
415 v/50HZ
—,.0. Pal —
x. :
,,. .,
I ,,5
“ xl ’00+
J
501+1,=0.
L
-~
J
230 V/60 HZ
— ,!?0. PSI —
u- ,,
,, ,2
,,
“!K3H7H.
w
L502 ~ ~~oz
!48
L502~
1
TI
—,!?0. Psl —
L(— u
_ I FE5
,, ,,
“, “, “2
K!
TI
..
,,5 v
... “,9
..
--am=
.2 ,2
--an+-
,3 ,3
l-501 +18GRr
I
T
[
,,5
“4
500 %~
“...
r+
~; tg==ii%
,3
—FROM P9, —
,1— L2
I
,, ,,
m
I F,,
w, —
—,!a —
—l, ,—
—.-!, z—
—,, ,—
—,,4—
—,, s—
—!,. —
—l, ,—
—1l, —
—,l, —
—.o —
—12, —
,,2—
—!, : —
— !,, —
82
—,, , —
—,,.— —,,,—
—1,6—
13, —
— ,,, —
l,, —
—,4. —
—,. , —
—,. ,—
—!, o—
—!, ,—
—l,, — _,,,
—!, —
—l,, — —l, ,—
Page 30 / IM 269
SINGLE POINT, WITH SPEEDTROL ALP-1 10C
– 2081230V, AL, PW
380141 514601575V, AL, PW
=
F+
PBI , ,
II
“~“or‘1~ E;
SPEEDTROLTRANS. IT31
3.30/415 B60/Y75 V. ONLY
SEE c~”fC1lON Dl&ORAUS ABOVE
(Rw:7vn~$ D: WE: m* a .10
FB6
L, ,,
Q
,lM’*4,$y~p4%-
5
NL?.&
ALTER”ATC TERII(N,L UM.E*S ‘0” ,PfFO,ROL “O,.”,
,,—, $2=:
—,ol —
— ,02 —31s
103—
~:$i=’
I %++--”+
1
T2++-n
:77 ‘-’
107—
— ,0*— — 10*—
—l!O—
—,,1—
—,,2—
— !13—
—,,4—
—,,5—
—,,s —
—,,T—
—,, m—
— l,s —
,20 —
—,,, —
— ,,, —
FB9
M22
; IF:==
M23
;~=-=
I
,,
T1
82
e5
—,,,—
—,,2—
— ,,, —
—1,4—
—l,;— — ,,. —
208 V./6O HZ
FROM 0S! 5A PBl
L!— L2
I
,, 12
m
I ,,5
FROM DSI z PBI
U- L2
I
TI 12
n
—,,,—
,,C —
—139—
,.0 —
!41 —
— ,42 —
FB5
I
— ,*. —
—,sl —
—,**—
,ss —
IM 269 / Page 31
SINGLE POINT, WITHOUT SPEEDTROL ALP-120C, 135C, 150C, 170C
– 380141514601575V, AL, PW
(ALP-185C, SEE NOTE)
FBB
—— ——
~14 I_E:=
—,c —
c,—,!,
—,c-
— ,.. —
!c!—
— l,, —
—,l,
—rll
—,, ,—
—., ,—
_,, ,,—
—!, ,,—
—,, .—
—,, —
—,l,
—,, -—
—,,
—,, ,—
ALP-120C, 135C, 150C, 170C, 20W230V ALP-185C, 280/415/460/575V INCLUDESCB5, CB7, CB6 6 CB6 FOR COMPRESSORS#l, #3, #2, & #4
\
““,,, .!, ”
.,. ,,
,ao/. 13/460/37 ,”-...
380 V/SO-60 HZ
mm 0s! 51 PO!
LZ
~“’++;:
I
,8
,, ,,
,,5
I
E?E
FROM 0S1 SE PBI
4diIAJ!:l
f-m%;:,
115 v
Ill
—,,,,—
3,—
—, — —,,2— —!, ,—
Page 32 / IM 269
SINGLE POINT, WITH SPEEDTROL ALP-120C, 135C, 150C, 170C – 380141514601575V, AL, pw
(ALP-185C, SEE NOTE)
~
PBI
L
——
“+””
PVM ,2
+’”
“+32——
lASE/VOLTAGE
I-t “’ii--l-r
,Os
‘-+..,,.0“ “N,,, WT.
380/415/.6 olB75 V- A..
ALP-120C, 135C, 150C, 170C, 2081230V ALP-185C, 280141514601575V INCLUDESCB5, CB7, CB6 & CB8 FORCOMPRESSORS#l, #3, #2, & #4
‘-d? -%%m-
++4 72
COMPR 3
#2
,s
<y -
?4/. 0!( UNITS WITH
,BO/41,/4S0/Y7S V—AL.
COMP R
*4
en
G- -
9-t&!hd-- —-— ‘3
7
‘“%,,
“*I:,
P;.
“+K T=-+
‘“-l+= ‘ — 72
2
“-kb ‘ .-.*
7
“+”=
‘3+1 = 24
,3 ,3
YE
.,, c., “m,, WITH
,,0/.15/460/575 v – *L .
II Ill
—,,3,-
131—
j?-?
C 04
~+
,,2—
— ,3s —
—,33s —
,s,c—
1,4—
— ,3s —
— ,3, —
1s7 —
—,.
l,, —
,,o —
—,4, —
—142—
FROM 0S! 9Jl PBl
L1— L2
I
11 Tz
n’
I F65
FROM 0S1 QR. P21
I
,, ,2
TI
“’w,
-502
‘*;:
L!— L2
,,.
.,J
I ,85
FROM DSI x PBI
I
m
“, “3 * M4
-’”’+gf,
L,— L2
,, 12
J
Ld
I ,65
FROM 0S1 M PB1
U- L2
I
,0 ,,
11
I FB5
,sO—
—,sl —
—,,*—
—,s, —
IM 269 I Page 33
MULTIPLE POINT, WITHOUT SPEEDTROL ALP-120C, 135C, 150C, 170C, 185C — 2081230V, AL, PW
380/41 514801i75V, AL, PW
ELECTRIC*L Cllu”ll “ !
Ill
,,, mTn ‘“~
L
F“”:r
L-x+”
,HASE/VOLTAGE
MON1TOR
3
M!
-—
:3:.
7
,
,
‘_’t&‘s
“+”5,,
‘2 -
:+
F
“-k’L
‘++ ,
“* ‘3
:~M7L,
i
‘“-&&l-
‘m
“/, 0“ “.!7, .,,.
,,0/4!, /.60/,7, V–AL
-k!%t-
COMPR3
*I
,,
<
“/. .“ ,,..,O,, -,4,,
.“0 .,,.,20, —,,,,
380/4,,,4,0 /,7s” -AL.
COMPR ,
*3
,.
e
F87 M12
—— ——
Yqy-
380 V/50-60 HZ
—mm PBl —
%-JFB5 T
.s xl
1
115v
ace 46
aOl-illGRD
M2
,,/.
m “w,, w,,
3,0/.15,.60,, ?,” —,,.
&-502~
:’”26%;:,
- C1. c
G
—FROM PB, —
.2
.,—
,, ,,
mJ
l-l
“’L&LJ”:,
,,5
v L-50 C-+GRE
415 v/50HZ
—FROM PBl —
,,5 v
[ FE,
ELEC
5003
*3
FBIO
——
.1— L,
I
,, ,2
,,
., )43 .2 .4
!.-33
-’”2*::,
460 V/60 HZ
—FROM PBl —
L!— ,2
I
,, ,2
“, “, ., .4
w
~’”’=T7&;<c
]
I F,,
F,,
““’*;:
—FRO.
P81—
,,,,
l—
7!
U
,,5 v GM
,* I FB5
—,,c—
_,, — —,,,—
—!,!—
—.,,—
—,,—
—!,, —
—!,,——
Page 341 IM 269
SINGLE POINT, WITHOUT SPEEDTROL
ALP-185C —
COMPR 3
e’
CMPR ,
<
2081230V, AL, PW
e
*I
7
,9
,3
,.
15
*3
,
,e”
!7
!8
2
3
4
5
6
Ill
qq ‘“y
0s1
g
PBI ‘I ‘2 ‘3
Ttr,
=
COMPR 3
*2
se’”
<
COMPR
*4
,0’2
e
l,, —
-
!z. —
,2, —
7
e
s
7
!1
,2
19
20
21
2
,
23
24
9! ?Bl
FROM 0S! It PBI
,1— L2
I
,, 72
m
I ,,5
FROM DSI
,1— ,,
I
,1 ,2
“, “, “2 . .
w
-’”2+;:[
I ,,5
,,
-
— lsl —
— ,,2—
— ,,, —
,33s—
,,x—
— ,,4—
—13, —
— ,,6 —
—,3, —
—l.
— ,3, —
— ,.c!—
—!41—
—,4, —
—14, —
— ,44 —
-,4, —
,s. —
—,s! —
,s, —
,53 —
IM 269 I Page 35
SINGLE POINT, WITH SPEEDTROL ALP-I 85C — 2081230V, AL, PW
COMPR 3
*I
s
%
COMPR ,
*3
9
e
NOTE
Ml!
——
3
7
4
3
e
,3
,4
,,
*
,.
,7
,0
l,,
—,31
M23
——
.—
~vc-1 1
,mM,.,, .,,.s,.,
.,,,,. .,,
,.. s,,,: -.,, MC-, PS
,!—, ,.—’
-.-—;
=
—l. l—
— ,., —,,,
,o, —
l.7—
,o*—
—-,
o,—
_l, l—
—-, !,—
— ,,, —
—!, ,#—
—,, x—
_!,.
—,,, —
— ,!, —
—!, ,—
—1l, —
—!, ,—
_,, c_
—,, ,—
—!,*—
— ,,, —
— ,*. —
- !,, —
—,,1—
— ,,, —
— ,,, —
—,,, ,—
—!,, c—
—l.
—,, ,—
— ,,’ —
r,, —
—l.
— ,,, —
—!. —
—!. l—
—,4, —
-!.3—
—!4. —
—,., —
Page 36 I IM 269
m E3FB5I
“! “2 .4
M
:“2+:: ““’+::
1
,,
“, !!3 “2 “4
k-d
!so —
—,, ! —
— ,,, —
—.3—
SINGLE POINT, WITHOUT SPEEDTROL ALP-205C, 230C — 2081230V, AL, PW
380141 514601575V, AL, PW
NOTE:
POWER B w, {Pm)
m *O8 *SO”
>
“MT, ONLY,
H
ET
,l_ET&
MONITOR
m
g$ -E?#+
7,
I_.!—— d
FROM DSI Q! ?01
— —_. 1
~g~e
‘2 J 11-
GRD LUG
$
FB6 Mll
—— ——
.. ,.,..
-EEFF=-&+
230 V /60 HZ
FROM D51 = ?81
Ill
PL
“,, l-E3
K3
-$U=.
—lo! —
— ,02 —s,s
— !0, —
m,-
— ,o, —
— ,., —
—l, o—
_.-,!,—
—!l, —
— ,,, —
l,,A—
!,, B—
,mc -
—ll. —
—,,s —
—r,*—
117—
— ,,, —
—l,, —
,*o —
— ,2, —
—,*, —
— ,*, —
—1,4—
— 12, —
— 1,(—
—!,*—
— ,,, —
— is,, —
— ,ms, —
— !,sc —
— !34—
— !,, —
— !s*—
—,,7—
—t,, —
— ,sB—
— l,o —
—,,, —
—!42—
—,4, —
—!44 —
— !4, —
—!so —
:’”’+q:c
380 V /50-60 HZ
FROM .S1 9.E PBI
u-— u
,, ,2
“1 “, “4
u
_
FROM 0S! E P81
I ,,5
I
IT-J
“’w,
““z+mkq?
L,— ,,
,1 ,,
,,s v GR1
I F,,
11111,,.
—,,,—
—,s2—
—,,, —
—lso —
—!, ,—
—!,2— —--, ,,—
IM 269 I Page 37
SINGLE POINT, WITH SPEEDTROL ALP-205C, 230C —
2081230V, AL, PW 380141514601575V, AL, PW
NOT C
,0.,” -w. (m,,
Onm,o.J:,o”
.. —_+ 1 I
Jrt:@$
p: J n s
0s1
w
QLPel
NOTE
~. “.., ,,” . . . . . ,.”*CW
,.3. ,.,,, -”,, w-,.,
,,—,
—,!, —
—,, z—
,!, —
,,14-
—!!3e —
—,nc -
—,,4——
—!,, —
— l,. —
!!7—
—,!. —
—!l, —
—-, *c—
—., —
—-l, ,—
— ,,, —
—,, .—
—,*,—
—l,, —
r,, —
— !,, —
— !13. —
— ,sm —
— ,,x —
—-!H—
—!35 —
%!a-h-l+a”--’
FBIO
=
*
— !,. —
—,, ,—
—,.
—,s, — — ,.. —
,.! —
—!. * —
—,4, —
,44 —
—,. ,—
Page 38 I IM 269
I KE’”
,,o —
—,3) —
—-,,, —
—!s, —
—,,!———
—,,*— —,s, —
MULTIPLE POINT, WITHOUT SPEEDTROL
L.Y
I.J
ALP-205C, 230C — 2081230V, AL, PW
380141514601575V, AL, PW
L=F
L-4-’”
pHAsE/ vOLTAGE
MON!TOR
EF
Ml
ELECTRICAL CIRCWT * 1
Ill
,,,~t~ ‘R”fl
I
1-
lllti2L
2 3
3
COMPR.
*I
7
,,
<’
COMPR ,
*3
,0”
G
4
5
e
,3
,4
15
t
7
17
18
‘-l%’!
8-1+,
,
‘-la @
‘“46,,
:;= Lz
,3 3
cOMPR 3
*2
98
<i
“+””u
2“+ LZ
2
7
21-M .3
=%”8,,
23+ L,
24i#d-
COMPR
#4
,,
<5
PB3
FL+­1%%-y
,, u
GRD LUG
—FROM PB I —
I
g
EL Ec
_ c,RC
G
lo, —
o—
—,,
_,l,
*2
FB8
M14
—,12—
— ,,, —
— ,
—,!, e—
—,,,c —
—1,4—
— ,,, ——
—,,6—
—,,, —
—,le —
—,, ,—
—,20—.—
—!2, ——
— ,*2—
— l,, —
— ,,4—
— ,25—
— l,!—
— ,3*—
— ,33—
— !,,A—
— ,33—
— ,,,c —
— !,4—
—,,, —
— ,,6 —
—137—
—,3s —
—,, ,—
— ,.o —
—,4!—
—,,2—
—,43—
— ,4. —
— !., —
—,,o —
,,A—
,1— L2
I
,, ,2
.&’”’+;:,
I ,,5
—FROMPB1—
,1— ,2
I
,( ,,
““24;?
I ,05
115 v GRc
—FROM Psl —
,1— u
I
,, ,,
“1 “, “2 “4
LJ
y+y:c
[ F,5
m
—,,,— —,,,—
—,,,—
o—
—,,
—,,,— —,,,—
—...—
..
IM 269 I Page 39
ALP-045C, 055C, 070
TYPICAL CONTROL AND SAFETIES WIRING DIAGRAMS
—m~,
SI
5 /y 5.X
w
—,. o—
Fl
e-x
307
‘E%==iL--zf~---z=227
I
WJ
18
‘1
,1—’20’’’0”-1
,,. 120V m
7“!.
—,s B—
N8
,0.
—22—
.1,,
-,,,—,,,
—2,, -
—,,, -,22
—*z!-
—2,7—2s3
z, 3
-.,.-
L,:GR42 C
—!44—+ , ,4,
HTR-I
R9
COMPRESSOR
CIRCUIT # I
J
w
4../37, v .,
“’~’’”*:=-
—,,,-. –,.,
—,.. —2.. —
-*,c —m,
_,,. _!l*
-108
235
—!12
,,,
—240—
—2,,
—!!s
-,.,-m
–,.2—
—*3
—262
*7,
-,’, -
7. *9,
~2,2ai21...:J,_21s=21J
—,4 4
RIO
COMPRESSOR
CIRCUIT # 2
24,
“J
TC23
~ ‘“n’
+“’=+’+2”
,T, ,.
ON .,, -,,0, “,,,, ONLY
.S.J,, n “ .,
.,,,— _,8,_,:*
,,
—,s6
—!3,
.,a. -
–,s. -..8
–,,.—132
-*,2
—I,,
!
8
r
Page 40 I IM 269
ALP-080C, 090C, Iooc, 110C
,04
FI
~t
1?
181
J_,,,=,., Q ,W, ~
140co. NC
—,44—
%3
507
+iiL--+
COMPRESSOR
cIRCUIT # I
,1—’2”V’’”J-J
~= TZ
,,. 120 v w,
, “,”
w,
m
“’~’”
“’-’’”-+&+::—
“’~’’’~’”-
-*OO —
508
,43
4UV57SV AL
-m2-
-203-
-,04-
-m6-
—220-
-221-3!7
-2,2-
—“’-i::
-2,s-
-227-2,,
-22. —!7,
_2,,_g#
-234-
-m5-
- ,,s +:
–24.—!!2 –*47 —
-2s0— ,02
-*S, —,!,
-2,2-!1s
-,s,— !!,
—24.0—
Yr
200 HI -AMMEIE6T UNL
2%=232
LO-PRES5U?E UNL. ~
‘“’+”
RS2
20, +202-2?:
‘z
J_241E#& ~
2.0 co.
“c
COMPRESSOR
CIRCUIT # 2
HTR.2
~+-i:1205::q’
24 vOLTS A, C.
2,.
-260-
239
–2s,—,20
-2,2 —
-2.,—2+2
-2.5 —
—267—,7,
-27,–::
-,,4-
-27, —
–,., —gg
-,,6 —!,,
-2@7—
—2,0—,0,
—2s( -!>2
-,,2 —!3,
-2,, — ,38
*7X
206
Q-’”’+
243
ALP-120C, 135C,150C, 170C, 185 C,205C,230C
—504 ~
++,of
—!40—
—340—
—,,.~1,
—H: ~
FI
liJ
::b+342~,
M3-AUX
503
HTR-3
R!!
R9
,3
cOMPRESSOR
343 ~:;:
“’7’”
,l—
‘“’++
,20, /.0/}—.——’
~ ,4,
w
I .s
-*.c—
—*c2-
-,.3-
-,.. -
-2c5-
—20. -
-,., -
I
- 22, -
-,, -3!-
-222-
-*23-2J:
-,z*—
-,,,-,,,
-,28 —y,;
—*2,—23-
.Z,. –j::
$
-*,, —,-
-,, .-
-., ,-
Zcs
-,1--,., ,!3
-2T*—
-,,, —
.7., —:,}.
-?. 1-!,,
-*.2-
-,.,—g?
.2 .$-,..
.,..—
-*,C -..,
-,s —,!2
-,32-.1,
-,33- !2:
—240 —
—.40—
.. ..
1
M2-AUX
mxz~,
HTR-2
‘“’+ .
L.”’”=””%=
““4+
—444 +~441
—:::+~45 “’
RI 2
3
RIO
~:;:
2 .22ti,_42,:+
443
300,. !,,4..,,., ,
-,s! -,,0
-z6*—
+-g;
-z., —
_,..
-2,
!—!..
—,,2
—,,.
-2,, -.3.
-,,, —..!
—x
,1,
Page 42 I IM 269
TYPICAL THERMOSTAT WIRING DIAGRAMS
I
,,4 ,,,
4-STAGE THERMOSTAT — ALP-045C,
s
JIQE$
WI”,, .,0, $40
R,WVZ
T
*S,, 10 m,,.,. ,,”s
s
-!( am n- SWTC” C3”mms.
6
~
so
rTEANib2TA!0Rl
767-$-’’’” ‘-~”’-’’’-’e’’”~~’e’”” --+--’
055C, 070C, 080C, 090C, 100C, 110C
JB===
no
-,,0 —,,,
-,l!—
-,,2 —
.,,, —
.,!. —
-,,s-
-,!6 -,.,
-,,7 —
-,!, —
-,,, -
-,20 -
%z-Lc ““-
Am 1,0, ““tin ,.,”.
TB4
%
,11
g ,8.
,s0 ,,3 ~::
1*~* ,,4 ,,,
115
,,, ,8
,, ,,,
118 I Is 120 121 ,22 ,23 ,24
210
,00 2, I
~,, *6.
*SO 2,3 ::i
~9= 214 ,,,
,,, 215 *,, ae
*,7 27s
218 219 m 22,
227. 223 224
I
4-STAGE THERMOSTAT — ALP-120C,
5
-
,[.0”, .,,,s .50, .!0
T
509 4!S10 TO 1NS74LL TI.E
,,.,. . . . now SW,,.
.0.,.,,,.
6
I ,,0
PVM
,,,fi~,,,
PH/VOLT. MONITCfl
,,!40”, ..,.
PI
113 @–5TfiGE 3–(+372 ‘D’~373-t4J ‘%”
2,3 219 @–STAGE 4 –(+,72 ‘“%,,,~., ‘:0
I ,8
>;
>:
135C, 150C
r
L ‘r J
,, S+&
,8 t
,,, ,@3 4B2-
HOTGAS BYPASS
-–+--
,@, 382-
a=
3,4-
.,!0—22,
.,l!—
.3!2 -
.,l, —
.,,. —
.,!, —
-,1.—265 .,17—
.324— 229
.,2,
—*M
TB4
I !0 !!1
l,, ,,.
,,3i::
,,,.
,15
,,6 l,,
3,2
Ila
,,9
,,,
,20 ,,,
,2, ,22
,23 ,24 210
273 ,,,
,,2 2.6 213 X
zg~~ 2,4 ,6,
,,2 215
216 217
.,2 2!E
47, a,
2 4.!
22( 222 2*
224
NOTE: R21 and R22 contacts with optional high head or suction pressure unloading only.
IM 269 I Page 43
6-STAGE THERMOSTAT
“. . .
.sQ.ul
W!wc, .$0, . . .
Rcw[
.,!0
m ll,,u, ,,., ax. m rLm SWITCH w,.,,,
[T’l%kkm?q
–“J1-& STAGE,–6—MJ
PvM
+kn.
‘VOLT MONITCR ,“0”, .“,.
x
&STAGE 2 —’&zeo—%LwJ —+ , ,
,,3
@–sTAGF 3–~MJ
ALP-080C,090C, 100C,11OC
1,6
2’22i;”7- 4“8’’”’=
.O “J*’’’-~’”2 ““
L,,, ~––fl=~.
T
29
‘“v l_@--!95~
L
It?
+’==
.,,0 -225
-,!!—
.,,2 —
-,,, —
.,,. —
.,l, —
-m,
.,1,
.,, -—
.,,, —
,*c–
,,z —
,2. —
104
,Ic
<,!
U ,,,
m. ,,, .“’
-~ , 1. ,,, ,,5
,* ,, -’
,, ! I I* 7,
,,, ,23 ,2) ,2, ,23 ,24 Ztc
2,. .,, !
k,, 2-
. *r, :T.
-~ 2!4 ,,,
,.. 2!s
~
*,, ,-s
,, I ,* 2.,
29 .
22 222 m,
3
6-STAGE THERMOSTAT
PvM
,,,fi~s,,
pH/v0L7 M0N17m
“,”.”, .“,.
c1
— ALP-120C, 135C, 150C, 170C, 185C, 205C, 230C
N0 COWACT
NC COWbCT
1-
‘7 J
,,?+&
1!
E2gE
.s*, —
Tw
, !0
+!,
1, ,,,
,,0,13 &
,.
,*S.
, ,,
!4
-,!0 -m
-3 .—
-,!, -
-,!, — ,23
.*I. —
-,!, — .,,, ,W
-,,. —,.,
-,--
-,, — -. , IS
.,*:—
.,*, —
~~, ,8
3-> .$, ,
,,,
,,.
= s“
,,z m
. ‘z .,,
,s
,, -.
= !.
,,. ,22
,24
21.
.2..
*!, :T,
21. ,.,
>17 ?, m
m 22! 222 223 *
I
,,
~-,
.,
Page 44 I IM 269
,,3
@—5TAGE 5—@72 &373&.,
NO cCNTbCT
213
@—SAGE 6 —~,,, ‘“’’&,,,&MJ 2:
N 0 CONTbCT
,,8
w ‘&
2!8
>:
,2,
M I ,0, 3a2—
., ,
,a, 4e2—
NOTE: R21 and R22 contacts with optional high head or suction pressure unloading only.
-,,4 —,,9
-3,, -,,,
8-STAGE THERMOSTAT – ALP-170C, 185C, 205C, 230C
5, .s
.8
4=J-
-,!0-22,
-,, ,—
-,,, —
-,, ,—
-,,4—
—,,, —
-.,,6-,6,
-,!7—
—,, a—
—3!9—
-,2. —
–3,1-
—3,2 —
-32, —
–3,. —22s
-,,,-*’,
-3,6—321
TB4
: m ,,,
l,, .,
,,0 ,,3 :y,
,,~ , ,4 ,,,
,!,
,,, !,6 ,,. , ,, lr,,37s
x
37, ,73 ,19
$77 I*O
,8, ,2 I ,,. ,22
,23 ,2. ,10
,,,
27,
,,2 ,..
,,0 ,13 ;:L
,,3. 2,4 ,.,
,,, 2,3 ,,, 2!,
27.,.70
,,6 ,,,
.,2 21s
.,, 2 t,
507 =73 4,,
22 I ,,4 222 ,,,
~
NOTE: R21 and R22 contacts with optional high head or suction pressure unloading only.
—327-32s
IM 269 I Page 45
xl
8
~ Table 20. Drawing Reference Decision Table For ALP-045C thru 230C. 03
. ~ NOTE: Each unit will have three electrical schematics: Power, Safety and Control, and Thermostat.
N m a
Power Schematics for Compressor and Condenser Fan Motors
SINGLE
WITHOUT
d
20W230V
20W230V
ALP UNIT SIZE
04s, 066C
120, 136, 160. 177X
120, 135,
11OC
046C
065C
160, mu!
206, 2m
120, 135. ~
120, 136, 160, 1 0(57
11OC 186C
070,080, 090c
1Ooc Iloc
, 0=,.
pAM14#
S231260 343124D 5831 33D 6831420 6033200
683322D 503330D M312ED S831200 583fa30 5031340 6831420 5833220
S833200 583330D 5031220 583130D 5831200 5031380 5033250 583321D 5833290 5031220 5831210 583120D 5831300 5831213D 5833210 5S3327D 5L13329D
MULTIPLEPOINTPOWER
WITHOUT
WITHOUT
070, 080,090, 10DC
070, 080, 000, 100C
070, 0s0, 090, 1 Ooc
11OC
045, 066C.
11OC
046, 066C
llDC
120.136, 160, 170, 186C 205, 230C
046, 066C
070, 080, 090, 100C
11OC
120, 136, 160, 170, 186c
205, 230C
5831270 583135D S831430
1383123D 503131 D 58313W2
583120D 5831360 683144D S833240 5033320
5831320 S03140D 1303323D
!M3331D
Table 21. Drawing Reference Decision Table For ALP-045C thru 230C,
Control and Safety Schematics
Table 22. Drawing Reference Decision Table For ALP-045C thru 230C,
Thermostat Control Schematic
WITHOUT
WITH
I
L
ALP UNIT SIZE
M5, 055, 070C
080,060,100, 11Oc
045,055, 070C
080,090,100 110C
130 THRU 330C
ORAWING NUMBER
5S3155D.01
5s31560.01
5s333s0-01
5s31530-01
5s31540-01
5333370.01
ALP UNIT SIZE NUMBER
r5”’75c”0’
r?+=’”
130 THRU 330C , ~=354m1
A“
120,135, 150C , 583=3G01
1
WITH
OUT 6
8
045 THRU “OC 583174C-01
130 THRU 230C ~351ti1
‘m ‘“Ru ‘oc ‘ 5S3353C.01
ORAWING
~
z
IQ
03
CD .
-0
SD
.P
-3
STARTUP AND SHUTDOWN
With all electric disconnects open, check all screw or lug
1.
type electrical connections to be sure they are tight for good electrical contact. Check all compressor valve con-
nections for tightness to avoid refrigerant loss at start­up. Although all factory connections are tight before ship­ment, some loosening may have resulted from shipping
vibration.
On chilled water installations, check to see that all water
2.
piping is properly connected. Check the compressor oil level. Prior to startup, the oil
3.
level should cover at least one-third of the oil sightglass. Check the voltage of the unit power supply and see that
4.
it is within the *1O% tolerance that is allowed. Phase voltage unbalance must be within * 2%. Check the unit power supply wiring for adequate ampaci-
5.
ty and a minimum insulation temperature rating of 75C. Verify that all mechanical and electrical inspections have
6.
been completed per local codes.
PRE-STARTUP
7.
See that all auxiliary control equipment is operative and
that an adequate cooling load is available for initial
startup.
8.
Open the compressor suction and discharge shutoff valves until backseated. Always replace valve seal caps.
9.
Making sure control stop switch S1 is open (off) and pumpdown switches PSI and PS2 are on “manual pump­down:’ throw the main power and control disconnect swit­ches to “on.” This will energize crankcase heaters. Wait a minimum of 12 hours before starting up unit.
10.
Open all water flow valves and start the chilled water
pump. Check all piping for leaks and vent the air from
the evaporator as well as from the system piping to ob­tain clean, non-corrosive water in the evaporator circuit.
CAUTION: Most relays and terminals in the unit control center are hot with S1 and the control circuit disconnect on. Do not close S1 until startup.
Double check that the compressor suction and discharge
1. shutoff valves are backseated. Always replace valve seal caps. Open the manual liquid line shutoff valve at the outlet of
2.
the subcooler. Adjustthe dial on temperature controller CP1 to the desired
3.
chilled water temperature. start the auxiliary equipment for the installation.
4.
Check to see that pumpdown switches PSI and PS2 are
5.
n the “manual pumpdown” (open) position. Throw the emergency stop switch S1 to the “on” position. If pressures onthe low side of the system are above 60 psig, the unit will start and pump down. Afterthe compressor lockout timer TDI has timed out, start
6.
TEMPORARY SHUTDOWN
Move pumpdown switches PSI and PS2 to the “manual pumpdown” position. After the compressors have pumped down, turn off the chilled water pump or evaporator fan. It is especially important on chilled water installations that the compressors pump down before the water flow to the evaporator is interrupted to avoid freeze-up.
CAUTION: With the unit left in this condition, it is capable of recycling pump­down operation. To defeat this mode of operation, move control stop switch S1 to the “off” position.
INITIAL
STARTUP
the system by moving pumpdown switches PSI and PS2 to the “auto pumpdown” position.
7.
After running the unit for a short time, check the oil level in each compressor crankcase, rotation of condenser fans. and check for flashing in the refrigerant sightglass (see “Maintenance”, page 49).
8.
Superheat should be adjusted to maintain between 8 and 12 degrees F.
9.
After system performance has stabilized, it is necessarythat the “Compressorized Equipment Warranty Form” [Form No. 415415Y) be completed to obtain full warranty benefits. This form is shipped with the unit, and after completion should be returned to McQuay’s Service Department through your sales representative.
1.
Close the manual liquid line shutoff valves. After the compressors have pumped down, turn off the
2.
chilled water pump or evaporator fan. Turnoff all power to the unit and to the auxiliary equipment.
3.
4.
Move the control stop switch S1 to the “off” position.
Page 48 I IM 269
STARTUP AFTER TEMPORARY SHUTDOWN Start the chilled water pump. With emergency stop switch S1 in the “on” position, move pumpdown switches PS1 and PS2 to the “auto pumpdown” position.
3.
Observe the unit operation for a short time to be sure that the compressors do not cut out on low oil pressure.
EXTENDED SHUTDOWN
(For startup after extended shutdown, refer to applicable “initial Startup” steps.)
5. Close the compressor suction and discharge valves.
6. Tag all opened disconnect switches to warn against start­up before opening the compressor suction and discharge valves.
SYSTEM MAINTENANCE
GENERAL
On initial startup and periodically during operation, it will be necessary to perform certain routine service checks. Among
these are checking the compressor oil level and taking con- on each gauge line. The valves should be closed at all times
densing, suction and oil pressure readings. During operation, except when gauge readings are being taken. On units
the oil level should be visible in the oil sightglass with the com-
pressor running. On units ordered with gauges, condensing, in the plugged ports provided on the suction and discharge
suction and oil pressures can be read from the vertical
FAN SHAFT BEARINGS
The fan shaft bearings are of the permanently lubricated type. No lubrication is required.
ELECTRICAL TERMINALS
CAUTION: ELECTRIC SHOCK HAZARD. Turn off all power before continuing with
following service.
All power electrical terminals should be retightened every six months, as they tend to loosen in service due to normal heating and cooling of the wire.
COMPRESSOR OIL LEVEL
Because of the large refrigerant charge required in an air cool­ed condensing unit, it is usually necessary to put additional
oil into the system. The oil level should be watched carefully
upon initial startup and for sometime thereafter.
At the present time, Suniso No. 3GS, Calumet R015, and Texaco WF32 oils are approved by Copeland for use in these compressors. The oil level should be maintained at about one­third of the sightglass on the compressor body.
Oil may be added to the Copeland compressor through the oil fill hole in the crankcase. To add oil, isolate the crankcase and pour or pump in the necessary oil. If the system contains no refrigerant, no special precautions are necessary other
supports on each side of the unit adjacent to the compressors.
The gauges are factory installed with a manual shutoff valve
ordered without gauges, Shrader fittings should be installed
King valves on each compressor circuit.
than keeping the oil clean and dry.
If the system contains a refrigerant charge, close the suc­tion valve and reduce crankcase pressure to 1 to 2 psig. Stop the compressor and close the discharge valve.
Add the required amount of oil. During the period the com-
pressor is exposed to the atmosphere, the refrigerant will generate a vapor pressure, retarding the entrance of con­taminants. Before resealing the compressor, purge the crankcase by opening the suction valve slightly for 1 or 2 seconds. Close the oil port, open the compressor valves and
restore the system to operation.
OIL EQUALIZATION
Units with four compressors (ALP-120C thru 230C) come equipped with oil equalization lines connecting the crankcases of both compressors in each refrigerant circuit. This allows the oil to move from one compressor crankcase to the other during normal operation, and balance between the two when the compressors are off. This method of equalization prohibits the oil level from dropping below the level of the sightglass. Some difference in crankcase oil levels will still exist during
CONDENSERS
Condensers are air cooled and constructed with 3/8“ O.D. in­ternally finned copper tubes bonded in a staggered pattern into slit aluminum fins. No maintenance is ordinarily required except the occasional removal of dirt and debris from the out­side surface of the fins. McQuay recommends the use of
foaming coil cleaners available at air conditioning supply
REFRIGERANT SIGHTGLASS
The refrigerant sightglasses should be observed period- or a restriction elsewhere in the system. On sightglasses
ically. (A monthly observation should be adequate.) A clear glass of liquid indicates that there is adequate refrigerant Kits” listed on page 8, an element inside the sightglass in­charge in the system to insure proper feed through the ex-
pansion valve. Bubbling refrigerant in the sightglass indicates that the system is short of refrigerant charge. Refrigerant gas after about 12 hours of operation, the unit should be pumped flashing in the sightglass could also indicate an excessive pressure drop in the line, possibly due to a clogged filter-drier
unit operation.
The oil equalization line contains a manual shutoff valve for isolating a compressor during service work. The ball valves are shipped in the closed position with a tag attached stating “Notice, Valve Shipped In Closed Position. Can Be Opened For Normal Operation.” pressor service, make sure they are opened again for unit operation.
outlets. Use caution when applying such cleaners as they may contain potentially harmful chemicals. Care should be taken not to damage the fins during cleaning. Periodic use of the purge valve on the condenser will prevent the buildup of non-condensables.
ordered from McQuay as part of the “Liquid Line Accessory
dicates what moisture condition corresponds to a given ele-
ment color. If the sightglass does not indicate a dry condition
down and the filter-driers changed.
When valves are closed for com-
IM 269 I Page 49
I
SERVICE
NOTE: Service on this equipment is to be performed by qualified refrigeration service per-
sonnel. Causes for repeated tripping of safety controls must be investigated and corrected. CAUTION: DISCONNECT ALL POWER BEFORE DOING ANY SERVICE INSIDE THE UNIT.
FILTER-DRIERS
To change the filter-drier, pump the unit down by moving pumpdown switches PSI and PS2 to the “manual pump­down” position.
UNIT SEE
04SC-2SOC
Move the control switch S1 to the “off” position. Turn off all power to the unit and install jumpers across the terminals shown in the table. This will jump out the low pressure con-
The liquid line solenoid valves, which are responsible for automatic pumpdown during normal unit operation, do not normally require any maintenance. They may, however, re­quire replacement of the solenoid coil or of the entire valve assembly.
The solenoid coil may be removed from the valve body without opening the refrigerant piping by moving pumpdown switches PSI and PS2 to the “manual pumpdown” position.
CIRCUIT NO.
1
2
JUMPER ACROSS
TERMINALS
44 to 48
74 to 7a
LIQUID LINE SOLENOID VALVE
trol. Close the manual liquid line shutoff valve(s). Turn power to the unit back on and restart the unit by moving the control switch S1 to the ‘“on” position. The unit will start pumping down past the low pressure setting. When the evaporator pressure reaches O—5 psig, move control switch S1 to the
“off” position.
Frontseat the suction line King valve(s). Remove and replace the filter-drier(s). Evacuate the lines through the li­quid line manual shutoff valve(s) to remove non-condensables that may have entered during filter replacement. A leak check is recommended before returning the unit to operation.
The coil can then be removed from the valve body by simply removing a nut or snap-ring located at the top of the coil. The coil can then be slipped off its mounting stud for replacement. Be sure to replace the coil on its mounting stud before retur­ning pumpdown switches PSI and PS2 to the “auto pump­down” position.
To replace the entire solenoid valve follow the steps in-
volved when changing a filter-drier.
THERMOSTATIC
The expansion valve is responsible for allowing the proper amount of refrigerant to enter the evaporator regardless of cooling load. It does this by maintaining a constant superheat. (Superheat is the difference between refrigerant temperature as it leaves the evaporator and the saturation temperature cor­responding to the evaporator pressure.) Typically, superheat should run in the range of 10F to 15F. On valves purchas­ed through McQuay, the superheat setting can be adjusted by removing the cap at the bottom of the valve to expose the adjustment screw. Turn the screw clockwise (when viewed
INLET
EXPANSION VALVE
from the adjustment screw end) to increase the superheat set­ting and counterclockwise to reduce superheat. Allow time for system rebalance after each superheat adjustment.
The expansion valve, like the solenoid valve, should not nor­mally require replacement, but if it does, the unit must be pumped down by following the steps involved when chang­ing a filter-drier.
If the problem can be traced to the power element only,
it can be unscrewed from the valve body without removing
the valve, but only after pumping the unit down.
POWER ELEMENT
(CONTAINS DIAPHRAGM)
OUTLET
l--+
SPRING
Page 50 I IM 269
ADJUSTMENT SCREW
/
CAP
IN-WARRANTY RETURN MATERIAL PROCEDURE
COMPRESSOR
Copeland Refrigeration Corporation has stocking wholesalers who maintain a stock of replacement compressors and ser­vice parts to serve refrigeration contractors and servicemen.
When a compressor fails in warranty, contact your local sales representative, or McQuay Warranty Claims Depatrment at the address on the cover of this bulletin. You will be authorized to exchange the defective compressor at a Copeland wholesaler, or an advance replacement can be ob­tained. A credit is issued you by the wholesaler for the re­turned compressor after Copeland factory inspection of the inoperative compressor. If that compressor is out of Copeland’s warranty, a salvage credit only is allowed. Pro-
vide McQuay with full details; i.e., McQuay unit model and unit serial numbers. Include the invoice and the salvage value credit memo copies and we will reimburse the difference. In this transaction, be certain that the compressor is definitely defective. If a compressor is received from the field that tests satisfactorily, a service charge plus a transportation charge will be charged against its original credit value.
On all out-of-warranty compressor failures, Copeland of-
fers the same field facilities for service and/or replacement
as described above. The credit issued by Copeland on the returned compressor will be determined by the repair charge
established for that particular unit.
COMPONENTS OTHER
Material may not be returned except by permission of authorized factory service personnel of McQuay Air Condi­tioning at Minneapolis, Minnesota. A “return goods” tag will be sent to be included with the returned material. Enter the information as called for on the tag in order to expedite han­dling at our factories and prompt issuance of credits.
The return of the part does not constitute an order for
replacement. Therefore, a purchase order must be entered
through your nearest McQuay representative. The order
APPENDIX
STANDARD CONTROLS
NOTE:
The oil pressure safety control is a manually resettable device which senses the differential between oil pressure at the discharge of the compressor oil pump and suction pressure inside the compressor crankcase. When the oil pressure reaches approximately 15 psi above the crankcase suction pressure, the pressure actuated contact of the control opens from its normally closed position. If this pressure differential cannot be developed, the contact will remain closed and energize a heater element within the control. The heater ele­ment warms a normally closed bimetallic contact and causes the contact to open, de-energizing a safety relay and break­ing power to the compressor.
It takes about 120 seconds to warm the heater element enough to open the bimetallic contact, thus allowing time for the pressure differential to develop.
If during operation, the differential drops below 10 psi, the heater element will be energized and the compressor will stop. The control can be reset by pushing the reset button on the control. If the compressor does not restart, allow a few
PERFORM AN OPERATIONAL CHECK ON ALL UNIT SAFETY CONTROLS ONCE PER YEAR.
OIL PRESSURE SAFETY CONTROL
THAN COMPRESSORS
should include part name, part number, model number and serial number of the unit involved.
Following our personal inspection of the returned part, and
if it is determined that the failure is due to faulty material or workmanship, and in warranty, credit will be issued on customer’s purchase order.
All parts shall be returned to the pre-designated McQuay
factory transportation charges prepaid.
minutes for the heater element and bimetallic contacts to cool
and reset the control again.
To check the control, pump down and shut off all power
to the unit. Open the circuit breakers or the fused discon-
nect for that compressor and install a voltmeter between ter-
minals L and M of the oil pressure control. Turn on power to the unit control circuit (separate disconnect or main unit
disconnect depending on the type of installation). Check to see that the control stop switch S1 is in the “on” position. The control circuit should now be energized, but with the absence of compressor power, no oil pressure differential can develop and thus the pressure actuated contacts of the con­trol will energize the heater element and open the bimetallic contacts of the control within 120 seconds. When this hap-
pens, the safety relay is de-energized, the voltmeter reading will rise to 24V, and the compressor contactor should open.
Repeated operations of the control will cause a slight heat buildup in the bimetallic contacts resulting in a slightly longer time for reset with each successive operation.
Pressure Actuator
Contact
Line Note 1
Line
Note 2
T2
Bimetallic Contacta
NOTES: 1. Hot only when the unit thermostat calls for compressor to run,
2. Hot only when other safety control contacts are closed.
LM
Heater Element
I
I
-
Safety Relay
Neutral
IM 269 / Page 51
HIGH PRESSURE CONTROL
The high pressure control is a single pole pressure activated switch that closes on a rxessure rise. When the switch closes, RI is energized which in turn de-energizes the control cir­cuit, shutting down the compressor circuit. R1 also locks itself in a manually resettable holding circuit through RSI. The switch is factory set to close at 400 psig and open at 300 psig.
To check the control, either block off condenser surface or start the unit with condenser fan motor fuses in only one fan fuse block (FB6) and observe the cutout point of the con­trol on a high pressure gauge.
LOW PRESSURE CONTROL
The low pressure control is a single pole pressure switch that closes on a pressure rise. It senses evaporator pressure and is factory set to close at 60 psig and automatically open at 35 psig. The control has an adjustable range of 20 inches of Hg. to 100 psig and an adjustable differential of 6 to 40 psig. To check the control (unit must be running), move the pumpdown switch(es) PSI and PS2 to the “manual pump­down” position. As the compressor pumps down, condenser pressure will rise and evaporator pressure will drop. The
FANTROL HEAD PRESSURE CONTROL
FANTROL is a method of head pressure control which auto­matically cycles the condenser fans in response to condenser pressure and ambient air temperature. This maintains head pressure and allows the unit to run at low ambient air tempera­tures.
All ALP units have dual independent circuits with the fans for circuit 1 and circuit 2 being controlled independently by the condensing pressure and ambient air of each circuit. Fans
The control is attached to a Shrader fitting and is located
on a cylinder head near the discharge King valve. CAUTION: Although there is an additional pressure relief
device in the systetq set at 450 psig, it is highly recom­mended that the “control stop” switch S1 be close at hand
in case the high pressure control should malfunction.
After testing the high pressure control, check the pressure
relief device (on the condenser header) for leaks.
lowest evaporator pressure reached before cutout is the cutout setting of the control. Wait for the compressor lockout time delays TDI and TD2 to time out. By moving the pump­down switch(es) PSI and PS2 to the “auto pumpdown” posi­tion, evaporator pressure will rise. The highest evaporator pressure reached before compressor restart is the cut-in set­ting of the control.
The control is attached to a Shrader fitting and is located
below the suction King valve body.
11 and 21 start with each compressor and fans 12 and 22 cy­cle on and off in response to condenser pressure. The cutout and cut-in pressures are given in Table 23. Fans 13 and 14 (circuit 1) and fans 23 and 24 (circuit 2) are controlled by am­bient temperature and are factory set at the values given in Table 23. Note that the number of fans on each unit varies. FANTROL sensor locations are shown in Figures 20 thru 23.
Table 23. Factory FANT
ALP
UNiT
SIZE Cutin cutout
04sc
Ossc
070C Oaoc 090c
1WC 290 1-’-
Iloc 1200
PC12(Psi)
290 170 290
290
1--
l/ul L3ull/ul —l —j—l—[—
[7cl I 90n I ‘1711 i 71 I CC
290
1,” 290 170 290 170 290 170 290
I
290 170 290 290 170
13SC 290 170 290
lSOC
170C 290 170 290 170 186C 290 170 290 170 20SC 230C 290 170
NOTES: (1) Wth SPEEDTROL, all units minimum ambient operating temperature drops to O“F. (2) Minimum head pressure on partly loaded compressor is 110 psig; on full load it is 170 psig.
290
170 290 170
290 170
ROL Settings
(Psi) TC13 (“F) TC23 (oF)
PC22
Cutin ~utout Cuths
--’-‘ ‘--
c.. sr”
/u
-“’ ---
LYUII(U
I
290 170
290 170 290 170
CONDENSER FAN
170
cutout
r%, ””, ”ti, ”7
70]65170 [65
Oajaolualuo
170
‘e’co’co’co
57152157152 [63
I
170
49 44 49 55 50 55
170
60 55 57
61 56 61 60 55 60 60 55 60 65 60 65 65 60
Cutin
cutout Cutin cutout
I ccl
fiAl _
I
44 50 52
56 66 55 65 55 65 60 70
65
60 70
TC14 (“~
1
75
I
69
I
59 60 65
TC24_~@ AMBIENT
STD.MINIMUM
1
Cutin
70 75 70 54 69 54 58 63 58 54 59 54 55 60 55 60 62 57
61 66 61 60 65 60 60 65 60 65 70 65 65 70 65 20
cutout
I
(FANTROL “F) (l)(2) (FANTROL “F) (1)(2)
OPT. STEPS OF CAPAC.
30 40
a.
.aa
20 35
10
10
10
10
20 20
20 20 20 20 20
–CAUTION–
SPEEDTROL and FANTROL will provide reasonable operating refrigerant discharge pressures to the am­bient temperatures listed for them PROVIDED THE COIL IS NOT AFFECTED BY THE EXISTENCE OF WIND.
If wind may occur, and the unit includes vertical condenser coils, it is the responsibility of the system designer
or installer to make other provisions for low ambient control. Consideration should be given to deflecting
awnings, dampers, or a floodback receiver system as required to satisfy specific job conditions.
MINIMUM AMBUENT
.
45
30 25 30 30 20 20
20 20 20 20
Page 52 /
IM 269
Figure 20.
High Ambient
Sensors
PC6 6 PC5
Figure 21.
SPEEDTROL Controls -r,
Figure 22.
t
COMPRESSOR
Compressor lockout consists of an adjustable Oto 6 minute time delay. It is wired in series with the R5 relay that energizes the R9 relay starting the compressor. Its purpose is to pre­vent rapid compressor cycling when cooling demands are er-
ratic. The circuit illustrated is for the compressor circuit #1
control circuit. The control circuit for compressor circuit #2
is wired the same way. Five minutes is recommended for the
compressor lockout time delay.
When the unit thermostat no longer calls for cooling and
the compressor contractor have opened, the lockout time
delay breaks open the circuit, preventing compressor restart.
The circuit remains open for a period of 5 minutes so that, if the unit thermostat should call for cooling before the delay period has expired, the compressor will not restart. After 5 minutes the time delay will close its contacts to complete the circuit to R5, energizing R9 and starting the compressor. When R9 is energized, another set of contacts will shunt around TD1, allowing TDI to reset open for timing out the next compressor cycle.
Figure
23.
OL
er
LOCKOUT
To check the control, the compressor must be running in-
itially. Move the pumpdown switch PS1 or PS2 to the “manual purnpdown” position. Immediately after the compressor has stopped running, move the pumpdown switch back to the “auto pumpdown” position. The compressor should not restart
for 5 minutes.
Line
R5
II
Neutral
“ne‘“%D-----
COMPRESSOR MOTOR PROTECTOR
The solid-state compressor motor protector module incor-
porates a two-minute “time off” relay utilizing the bleed down
capacitor principle. Any time the protection system opens or
power to the module is interrupted, the two-minute “time off’
delay is triggered, and the module will not reset for two
minutes. Once the two-minute period is passed, the motor protector contacts 1 and 2 reset, provided the protection
system is satisfied and power is applied to the module.
NOTE: If the power circuit is broken once the two-minute oeriod is passed the pilot circuit will reset without delay when
power is “reapplied.
24V Line
115V Line
-———.
r 1]
1 I
i
L:---’d
*1
11
MP1
i
Control Relay
u
Neutral
Neutral
IM 269 I Page 53
APPENDIX
OPTIONAL CONTROLS
SPEEDTROLHEADPRESSURECONTROL(OPTiONAL)
SeeCautiononPage52.
The SPEEDTROL system of head pressure control operates partments. Units with 460 volt power have a transformer in conjunction with FANTROL by modulating the motor speed mounted inside the condenser fan 21 fan compartment to step on fans By reducing the speed of the last fan as the condensing pressure falls, the unit can operate at lower ambient tempera- speed at approximately 105” F and maintains a minimum con­tures. densing pressure of 170 to 180 psig.
thermally protected motor specially designed for variable the bottom row of the condenser coil. SPEEDTROL controls speed application. The solid-state speed controls SC11 and SC21 are mounted inside condenser fan 11 and 21 fan com-
UNLOADERS CONTROLLED FROM SUCTION PRESSURE: solenoid U1 which increases the compressor capacity. With a decrease in load, the suction pressure drops, pressure control PC8 closes, energizing unloader solenoid U1. This closes the suction port to one cylinder bank and reduces the compressor capacity. Compressor circuit 2 operates the same way,
creases, pressure control PC8 opens, de-energizing unloader
11and 21 in response to condensing temperature. the voltage down to 230 volts for the SPEEDTROL motors.
modulate the motor
The SPEEDTROL fan motor is a single phase, 208/240 volt,
COMPRESSOR UNLOADERS (OPTIONAL)
With an increase in the load, the suction pressure in-
The SPEEDTROL control starts to
The SPEEDTROL sensors are clipped to a return bend on
and SPEEDTROL transformer are shown in Figures 21 and 23.
PC8, cut-in: 64 psig: cut-out: 72 psig PC9, cut-in: 64 psig; cut-out: 72 psig
The cut-in and cut-out pressures can be adjusted to meet field combinations. If the unloader cycles excessively, the differen­tial between cut-in and cut-out should be increased.
LOW AMBlENT START (OPTIONAL)
Low ambient start is available on all units as an option with
To check the control, turn off all power to the unit and
FANTROL and included automatically with optional SPEED- remove the wire(s) leading to the terminals of the low pressure TROL. It consists of a solid-state, normally closed time delay wired in series with a relay. These are both wired in parallel to the liquid line solenoid valve so that when the solenoid valve is energized by the unit thermostat the low ambient start relay is also energized through the time delay, The relay has con­tacts that essentially short-circuit the low pressure control and
control(s) LPI and LP2. Remove power to the compressor and
jumper across terminals 48 to 50 for circuit 1 and 78 to 80
for circuit 2. Switch the pumpdown switch(es) PSI and PS2 to the “auto pumpdown” position. Energize the control cir­cuit by turning on the control circuit disconnector main power
disconnect (depending on the installation) and the control stop freezestat and allow the compressor to start with the low switch S1. The compressor contractors should pull in instant­pressure control open.
Iy and trip back out after the 23/4 minute time delay.
After about 23/4 minutes, the time delay will open and re­energize the relay. If the system has not built up enough evaporator pressure to close the low pressure control, the compressor will stop. The time delay can be reset to its original
StartTimeDelay
Line
LowAmbient
TD9
Low Ambient
StartRelay
Neutral
normally closed position by moving the pumpdown switch(es) PSI or PS2 to the “manual pumpdown” position. Moving the pumpdown switch back to the “auto pumpdown” position will again energize the relay for another attempt at startup. If the
system has built up enough evaporator pressure, the com­pressor will continue to run.
NOTE: Line is only hot when the unit thermostat calls for compressor to run.
HIGH AMBlENT (OPTIONAL)
The high ambient control is a single pole pressure activated switch that closes on a pressure rise to partially unload one or both circuits. It senses condenser pressure and is factory set to close at 375 psig and will automatically reset at 300 psig. To check the control, either block off condenser surface or start the unit with fuses in only one condenser fan fuse-
block (FB6) and observe the cut-in point of the control by monitoring when the compressor unloads. The purpose of the control is to allow the unit to continue operating when the am­bient temperature exceeds the design temperature of the unit. High ambient sensor locations are shown in Figures 20 and
22.
PART WINDING
Part winding start is available on all voltage units and con­sists of a solid-state time delay wired in series with the con­tactor that energizes the second winding of each compressor motor. Its purpose is to limit current in-rush to the compressors upon startup. As each compressor starts, the contactor of the first motor winding is delayed for 1 second.
Control checkout is best accomplished by observation as each contactor is pulled in to see that the 1 second delay oc­curs before the second contactor pulls in.
Page 54 I IM 269
START (OPTIONAL)
Line
I
TO 1
Part Winding
Time Oelay
Compr COntaclOr
(=1 Motor Winding)
COmpr Contactor
(*2 MO1O, Wndingl
Neutral
Neutral
PHASE/VOLTAGE MONITOR (OPTIONAL)
The phase/voltage monitor is a device which provides pro­tection against three-phase electrical motor loss due to power 1. failure conditions, phase loss, and phase reversal. Whenever any of these conditions occur, an output relay is deactivated, disconnecting power to the thermostatic control circuit, 2. automatically pumping down the unit.
The output relay remains deactivated until power line con­ditions return to an acceptable level. Trip and reset delays have 3. been provided to prevent nuisance tripping due to rapid power fluctuations.
When three-phase power has been applied, the output relay should close and the “run light” should come on. If the out-
HOT GAS BYPASS (OPTIONAL)
Hot gas bypass is a system for maintaining evaporator pressure at or above a minimum value. The purpose for do­ing this is to keep the velocity of the refrigerant as it passes
through the evaporator high enough for proper oil return to the compressor when cooling load conditions are light. It also
maintains continuous operation of the chiller at light load con-
ditions. Hot gas bypass kits are described on page 9.
The solenoid valve should be wired to open whenever the unit thermostat calls for the first stage of cooling (see Figures 10 thru 12). The pressure regulating valve that McQuay of-
fers is factory set to begin opening at 58 psig (32° F for R-22) when the air charged bulb is in an 80” F ambient temperature. The bulb can be mounted anywhere as long as it senses a fairly constant temperature at various load conditions. The compressor suction line is one such mounting location. It is generally in the 50° F to 60° F range. The chart below indicates that when the bulb is sensing 500 F to 60° F temperatures, the valve will begin opening at 54 to 56 psig. This setting can be changed as indicated above, by changing the pressure of the air charge in the adjustable bulb. To raise the pressure
put relay does not close, Perform the following tests.
Check the voltages between L1–L2, L1–L2 and L2–L3. These voltages should be approximately equal and within
+ 10% of the rated three-phase line-to-line voltage. If these voltages are extremely low or widely unbalanced check the power system to determine the cause of the problem. If the voltages are good, turn off the power and interchange any two of the supply power leads at the disconnect.
This may be necessary as the phase/voltage monitor is sensitive to phase reversal. Turn on the power. The out­put relay should now close after the appropriate delay.
setting, remove the cap on the bulb and turn the adjustment screw clockwise. To lower the setting, turn the screw counter­clockwise. Do not force the adjustment beyond the range it
is designed for, as this will damage the adjustment assembly.
The regulating valve opening point can be determined by slowly reducing the system load (or increasing the required chilled water temperature setting indicated on the unit ther­mostat), while observing the suction pressure. When the bypass valve starts to open, the refrigerant line on the evaporator side of the valve will begin to feel warm to the touch.
CAUTION: The hot gas line may become hot enough to
cause injury
in a very short time, so care should be taken
during valve checkout.
On installations where the condensing unit is remote from the evaporator, it is recommended that the hot gas bypass valve be mounted near the condensing unit to minimize the amount of refrigerant that will condense in the hot gas line during periods when hot gas bypass is not required.
Hot Gas Bypass Piping Diagram
Hot Gas 6ypESS
Solenold Valve
r
\
1 1, 11
G
1
Suction
Line
n
~&’,,.Bgglve
Bypass Valve
distributors, use Sporlsn suxlllary
sldeporl connector or equlvslent)
Hot Gas Bypass Adjustment Range
80
g 40 J <
>
--
3040506070B41 90100
TEMPERATURE(“F) AT BULB LOCATION
110
IM 269 I Page 55
-0
8
(D
m co
.
z
N
m
w
HIGH PRESSURE CONTROL
LOW PRESSURE CONTROL
COMPRESSOR MOTOR PROTECTOR
fTexaa Instruments)
OIL PRESSURE CONTROL
UNLOAOER PRESSURE CONTROL
FANTROL CONDENSER PRESSURE CONTROL
PUMPDOWNSWITCH PHASEIVOLTAGE
MONITOR RESET SWITCHES
CONTROLSTOPSWITCH
LEAD-LAGSWITCHES
SPEEDTROL HEAD PRESSURE CONTROL
LIQUID LINE
SOLENOID VALVES,
HOT QAS BYPASS UNIT THERMOSTAT
(MASTER)
UNIT THERMOSTAT (SATELLITE)
COMPRESSOR LOCKOUT TIME DELAY
PART WINDING START TIME DELAY
ALP CONTROLS,
Stops compressor when discharge pressure is too high.
(Used for pumpdown.) Stops compressor when suction pressure is too low.
Protects motor from high temperature by sensing winding temperature.
Stops compressor if oil pressure drops below setpoint for 120 seconds.
Unloads compressor circuits if condenser pressure
is too high.
Maintains condenser pressure by cycling the con­denser fansin response toambient air temperature (TC) and condenser Drasaure (PC\.
Used to manually pump down compressor circuit.
Protects motor from power failure, phase loss and phase reversal.
Restarts compressor circuit if it cuts out on high
oressure or freezestat.
Shuts down entire control circuit.
Reverses sequence that compressors start in.
Modulates condenser fan speed in resonse to con­denser temperature.
Close off liquid line for pumpdown.
Close off hot gas line for pumpdown,
Measures return water temperature tocontrolcom-
pressor staging,
Adds additional stages of cooling to unit thermostat
CPI .
Prevents short cycllng of compressors. TD1—4
Reduces Inrush amp draw on startup,
LP1, 2
MP1—4
OP1—4
PC12, 22 TC13, 14,15 TC23, 24,25
Psi, 2
PVM
RSI—4 NIA Manual
S1
S2–4
Sell, 12 Maintains minimum con-
SV5, 6 NIA
CP1 NIA
CP2 NIA NIA Control box
TD5—8 1 second
AND FUNCTIONS
RESET
Closes at 400 psig. Opens at 300 psig.
Closes at 60 psig. Opens at 35 Psiq.
500 ohms cold to 20,000 ohms hot.
Pressure sensor opens at
15psig oil pressure, If pressure drops below 10, psig, the sensor closes, energizinga 120 second delay before stopping the compressor.
Closes at 375 psig. Opens at 300 psig.
See table with FANTROL settings.
Auto/manual
NIA When conditions return to
On/off Circuit 1 leads Circuit2
Circuit 2 leads Circuit 1
densing pressure of 170 to 180 psig.
NIASvl, 2SOLENOID VALVES,
Adjustable from 300F to 60” F, Should beset be­tween 42° F and 50” F,
Adjustable Oto 6 minutes,
Recommended 5 minute setpoint.
or
Manual thru RS1,2
Auto
Auto from 2700—4500 ohms
Manual
AutoHIGH AMBlENT
Auto
NIA
an acceptable level.
N/A
NIA
NIA
NIA
NIA
Auto
N/A Control box
LOCATION
On compressor 100 psig. fixed.HPI, 2
On compressor
Compressor junction box 15,000 ohms
Control box 5 psig
On condenser coil header 75 psigPC5, 6
PC12—220n coil header. TC13—25 in control box.
Control box
Control box
Control box
Control box Control box
DlFPS17Em
30 psig fixed.
I
See table with FANTROL settings.
I
NIA
I
NIA
I
NIA
I
i NIA
NIA
I
Back of control box or on bulkhead
Condenser section on liquid N/A line after filter-drier and before TEV.
Condenser section NIA
Control box, Adjustable from 1°Fto Sensor in return waterline 3°F per stage. from buildino to chiller.
Control box N/A
NIA
Adjustable thru CPI
I
NIA
I
Continued on next paga
ALP CONTROLS, SETTINGS, AND FUNCTIONS (Continued)
LOW AMBlENT START TIME DELAY
COMPRESSOR
SEQUENCING TIME DELAYS
COMPRESSOR UNLOADERS CONTROLLED
REMOTELY (Thermostat)
SUCTION UNLOADER
PRESSURE CONTROL
Bypasses low pressure control and freezestat to
I
allow evaporator pressure to build up in low
ambient conditions.
I
Staggers compressor starting to reduce in amp draw
TD9—1 o
TDII—13
TDII: 20 seconds
TD12, 13:40 seconds
Auto Control box NIA
I
Solenoid valveaon compressor heads to load or unload compressors. Energize to unload; de-ener­gize to load compressor.
Senses suction pressure to load or unload compres­sors. Cut-in (energize)to unload compressor; cut-out (de-energize) to load compressor.
Ul, 2
PC8, 9 Recommended cut-in: 84psig cut-out 72 psig
The McQuay ALP SEASONCON air cooled water condensing unit provides not only lower operating costs, but lower
installation costs, low maintenance costs and greater design flexibility,
In order for McQuay to better serve our customers, feedback of recurring service problems or complaints dealt with in the field would be appreciated. Problems or complaints can be reported to McQuay by filling out a Product Quality Report (Form No. 2S-636-784). These forms are available from McQuay service and sales representative organizations and should be routed back through these organizations to McQuay’s Engineering and Marketing departments.
NIA
Adjustable 20—1 00 psig
in both comfort and process cooling applications.
Auto
Control box Adjustable
TROUBLESHOOTING CHART
PRORLFM I POSSIBLE CAUSES
. ..--—...
COMPRESSOR WILL NOT RUN
COMPRESSOR NOISY OR VIBRATING
HIGH DISCHARGE PRESSURE
LOW DISCHARGE PRESSURE
HIGH SUCTION PRESSURE
LOW SUCTION
PRESSURE
COMPRESSOR WILL WILL NOT UNLOAD 2. Unloader mechanism defective. OR LOAD
COMPRESSOR LOADINGIUNLOADING INTERVALS TOO SHORT
LOSS OFOIL 1. Clogged suction oil strainer. PRESSUREOR NUISANCE OIL PRESSURE CONTROL TRIPS
COMPRESSOR LOSES OIL
1. Main switch open.
2. Fuse blown. Circuit breakers open.
3. Thermal overloads tripped.
4. Defective contactor or coil.
5. System shutdown by safety devices.
6. No cooling required.
7. Liquid line solenoid will not open.
8. Motor electrical trouble.
9. Loose wiring.
1. Flooding of refrigerant into’~crankcase
2, Improper piping supporl orisuction or liquid line.
3. Worn compressor.
1. Noncondensables in system.
2. System overcharged with refrigerant.
3. Discharge shutoff valve partially closed.
4. Fan not running.
5. Dirty condenser coil,
6. FANTROL outof adjustment.
1. Faulty condenser temperature regulation
2. Suction shutoff valve partially closed.’
3. Insufficient refrigerant in system. 4, Low suction pressure.
5. Compressor operating unloaded.
1. Excessive load.
2. Expansion valve overfeeding.
3. Compressor unloaders open.
1. Lack of refrigerant.
2. Evaporator dirty.
3. Clogged liquid line filter-drier.
4. Clogged suction Iineor compressor suction gas strainers.
5. Expansion valve malfunctioning.
6. Condensing temperature too low.
7. Compressor will not load.
8. Insufficient airor water flow.
1. Defective capacity control.
3. Faulty thermostat stage or broken capillary tube.
4. Stages not set for application.
1. Erratic water thermostat.
2. Insufficient water flow.
2. Excessive liquid in crankcase.
3. Oil pressure gauge defective.
4. Low oil pressure safety switch defective.
5.Worn oil pump.
6. Oil pump reversing gear stuck in wrong position.
7. Worn bearings.
8. Low oil level.
9. Loose fitting on oil lines.
10. Pump housing gasket leaks. 11, Flooding of refrigerant into crankcase.
12. Iced up evaporator coil.
13. insufficient air orwaterflow. 1, Lack of refrigerant.
2, Excessive compression ring blow-by.
3. Suction superheat too high.
4. Crankcase heater burned out.
5. Insufficient oilinaystem.
6. Suction risers too large.
7. Insufficient traps in suction risers.
1
1. Close switch. 2, Check electrical circuits andmotor w’ndngforshoflsor
grounds. Investigate for possible overloading. Replace
fuse orreset breakers aflerfault is corrected Check for loose or corroded connections.
3. Overloads areauto reset. Check unit closely wher unit comes back on line.
4. Repair or replace.
5. Determine type andcause of shutdown and correct it before resefiing safety switch.
6. None. Wait until unit calls for cooling
7. Repair or replace coil.
8. Check motor for opens, shorfcircuit, or burnout
9. Check all wire junctions. Tighten all terminal screws
1. Check setting of expansion valve.
2. Relocate. adder remove hangers
3. Replace.
1. Purge the noncondensables.
2. Remove excess.
3. Open valve
4. Check electrical circuit.
5. Clean coil.
6. Adjust FANTROL settings.
1. Check condenser control operation.
2. Open valve.
3. Check for leaks. Repair and add charge.
4. See Corrective Steps for low suction pressure be!ow
5. See Corrective Steps for failure of compressor to load below.
1, Reduce load oradd additional equipment.
2. Check remote bulb. Regulate superheat.
3. See Corrective Steps below for failure of compressor to load.
1. Check for leaks. Repair and add charge
2. Clean chemically.
3. Replace.
4. Clean strainers.
5. Check and reset for proper superheat.
6. Check means forregulafing condensing temperature.
7. See Corrective Steps below for failure of compressor to unload.
6. Adjust airflow orwatergpm.
1. Replace.
2. Replace.
3. Replace.
4. Reset thermostat setting to fit application.
1. Replace.
2. Adjust gpm.
l.Clean.
2. Check crankcase heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve operation.
3. Repair or replace. Keep valve closed except when taki~g readings.
4. Replace.
5. Replace.
6. Reverse direction of compressor rotation.
7, Replace compressor.
8. Add oil.
9. Check and tighten system.
10, Replace gasket.
11. Adjust thermal expansion valve. 12, Clean coil.
13. Adjust air flow or water gpm.
1. Check for leaks and repair. Add refrigerant.
2. Replace compressor.
3. Adjust superheat.
4. Replace crankcase heater.
5. Add oil until sightglass is V, full.
6. Check line sizing atdesign conditions and change if incorrect.
7. Install suction P4rapsat each 20 foot vertical rise
POSSIBLE CORRECTIVE STSPS
Continued on Nexl P.?ge
Page 5811M 269
..
MOTOR OVERLOAD RELAYS OPENOR BLOWN FUSES
COMPRESSOR THERMAL
PROTECTOR SWITCH
OPEN
PROBLEM
TROUBLESHOOTING CHART (Continued)
.,
‘ f?OSSIBLECiWSES
1. Low voltage during high load conditions.
2. Defective or grounded wiring in motor.
3. Loose power wiring.
4. High condensing temperature.
5. Power line fault causing unbalanced voltage
6. High ambient temperature around the overload relay.
7. Failure of second starter to pull in on part winding start svstems.
1. Operating beyond design conditions.
2. Oiacharge valve partially shut.
3. Blown valve plate gasket.
,,
POSSIBLSCORRECTIVE S=PS
1. Check supply voltage for excessive line drip.
2. Replace compressor motor.
3. Check all connections and tighten.
4. See Corrective Steps for high discharge pressure.
5. Check supply voltage. Notify power company. Do not atarl until fault is corrected.
6. Provide ventilation to reduce heat.
7. Repair or replace atarter or time delay mechanism.
1. Add facilities ao conditions are within allowable Iimita.
2. Open valve.
3. Replace gasket
lM2691Page59
Product Warranty
McQuay International, hereinafter referred to as the “Company,” Warrants that it will provide, at the Company’s
option, either free replacement parts or free repair of com­ponent parts in the event any product manufactured by the Company and used in the United States proves defective in material or workmanship within twelve (12) months from ini-
tial start-up or eighteen (18) months from the date shipped
by the Company, whichever comes first. For additional con­sideration, McQuay International warrants that for four (4) years following the initial warranty period it will provide, at
the Company’s option, free replacement parts for the motor-
compressor, or, free replacement for any integral compo­nent of the motor-compressor which proves defective in material or workmanship. For an additional consideration, McQuay International warrants that for nine (9) years follow­ing the initial warranty period it will provide free replacement of the heat exchanger in gas-fired or oil-fired furnaces which proves defective in material and workmanship. (Extended warranties for motor-compressors and heat exchangers are not applicable unless separately purchased.)
To obtain assistance under this parts warranty, extended motor-compressor warranty, or extended heat exchanger warranty, simply contact the selling agency. To obtain infor­mation or to gain factory help, contact McQuay International, Warranty Claims Department, P.O. Box 1551, Minneapolis, MN 55440, telephone (612) 553-5330.
This warranty constitutes the buyer’s sole remedy. It is given in lieu of all other warranties. There is no implied warranty of merchantability or fitness for a par-
ticular purpose. In no event and under no circumstances
shall the Company be liable for incidental or conse­quential damages, whether the theory be breach of this or any other warranty, negligence or strict tort.
This parts warranty and the optional extended warranties extend only to me original user. Of course, abuse, misuse, or alteration of the product in any manner Company’s warranty obligation. Neither the parts or extended warranty obligates the Company to pay any labor or service costs for removing or replacing parts, or any ship­ping charges. Refrigerants, fluids, oils, and expendable items such as filters are not covered by this warranty.
The extended warranties apply only to integral compo­nents of the motor-compressor or heat exchanger, not to refrigerant controls, electrical controls, or mechanical con-
trols, or to failures caused by failure of those controls.
Attached to this warranty is a requirement for equipment containing motor-compressors and/or furnaces to report start-up information. The registration form accompanying
the product must be completed and returned to McQuay
International within ten (10) days of original equipment start­up. If that is not done, the date of shipment shall be pre­sumed to be the date of start-up and the warranty shall expire twelve (12) months from that date.
No person (including any agent, salesman, dealer or dis-
tributor) has authority to expand the Company’s obligation
beyond the terms of this express warranty, or to state that
the performance of the product is other than that published
by the Company.
voids the
McQuaY”
13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, MN 55440 USA (612) 553-5330
@ Printed onrecyclecl papercontaining at least 10% post-consumerrecycled material
Loading...