McQuay ALP-037A Installation Manual

BULLETIN NO. IM 269-2
OCTOBER, 1984
FORM NO. 4154631
SEASONCON
PACKAGED AIR COOLED CONDENSING UNIT
MODELS ALP-037A THRU 107A,
159B, &
179A
m
WkIJUR\I
AIR connmonlnG
13600 Industrial Park Blvd.. P 0.
60~
1551, Minneapolis, MN 55440

TABLE OF CONTENTS

INTRODUCTION
General description. Nomenclature
Inspection....................................
INSTALLATION
Handling....................................
Location......................................
Service access Vibration isolators
REFRIGERANT PIPING
General......................................
Evaporator above condensing unit
Evaporator below condensing unit
Refrigerant piping connections
Liquid line components
Recommended line sizes
Dimensionaldrawings.............
Hot gas bypass components..................
Refrigerant charge..........................
FIELD WIRING
Wire sizing ampacities and
recommended power lead sizes
Compressor and condenser fan motors..........
Thermostat wiring
Typical field wiring for thermostats
Flow switch for chilled water applications
Evaporator fan interlock
for air handler coil installations
UNIT LAYOUT AND PRINCIPLES OF OPERATION
Major component locations
Control center
Sequence of operation
Electrical legend Power schematics
Compressor control schematics..............
.........................
...............................
.............................
...........................
...............
...............
.................
.....................
..........
.1:::.:1.11.18
...............
............................
.............
..........
.................
...................
...............................
.....................
..........................
.........................
.3 .3
.3,4
4,5
.6 .6 .6
6,7
.9 .9
10,ll
.12
.12
13,14
15
.15
.16 .17
.18,19
.19
.20-23
.24-39
START-UP AND SHUTDOWN
Pre Start-up
.
. .
.
7
InitialStart-up Temporary shutdown
Start-up after temporary shutdown..............
Extended shutdown.........................
SYSTEM MAINTENANCE
General...................................
Fanshaftbearings..........................
Electrical terminals Compressor oil level
Condensers................................
Refrigerant sightglass.
SERVICE
Filter-driers Liquid line solenoid valve Thermostatic expansion valve
IN-WARRANTY RETURN MATERIAL PROCEDURE
Copeland compressor. Components other than compressor
APPENDIX
Standard Controls Oil pressure safety controls High pressure control Low pressure control FANTROL head pressure control Optional Controls SPEEDTROL head pressure control
DAMPERTROL head pressure control...........
Part winding start Low ambient start
Compressor lockout
Hotgasbypass...........................
TROUBLE SHOOTING CHART.
...
..11::‘:::::::::::::::::::::::..4
.........................
..........................
.......................
........................
.................................
......................
..................
........................
....................
.....................
.........................
..........................
............................
.......................
..................
.............
...............
.............
.40
0
.40
.40
..4 0
41
..4 1
.41 .41
..4 1
.41
.42
.42
.42
.43
.43
.43
.44 .44
.44
.45 .45 .46
.46
.46
..4 7
.48
Page 2 I lM269
“DAMPERTROL”, “FANTROL”,
“McQUAY”,
of McQuay Inc., Minneapolis, Minnesota.
“SEASONPAK”, and “SPEEDTROL” are registered trademarks

INTRODUCTION

GENERAL DESCRIPTION

McQuay type ALP SEASONCON air cooled condensing units are designed for outdoor installations and are compatible with either air handling or chilled water systems. Each unit is com­pletely assembled and factory wired before evacuation, charg­ing and testing. Each unit consists of twin air cooled con­densers with integral subcooler sections, multiple accessi­ble hermetic compressors, complete discharge piping and suction connections for connection to any air or water cool-

NOMENCLATURE

ALP-089BD
ing evaporator.
The electrical control center includes all safety and operating controls necessary for dependable automatic operation except for the cooling thermostat since this is somewhat depended upon the unit application. Compressors and fan motors are fused in all three conductor legs and started by their own three pole contactor.
TTT 1-TT
Refrigerant Circuits
=
Dual; S = Single)
(D
Propeller Fan

INSPECTION

When all the equipment is received, all items should be carefully checked against the bill of lading to insure a complete ship­ment. All units should be carefully inspected for damage upon arrival. All shipping damage should be reported to the carrier and a claim should be filed. The unit serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available.
Design Vintage Nominal Capacity (Tons)

INSTALLATION

NOTE: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. CAUTION: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

HANDLING

Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from anything other than the base, and block the pushing vehicle away from
the unit to prevent damage to the sheetmetal cabinet and end
frame (see Figure 1).
Never allow any part of the unit to fall during unloaing or
moving as this may result in serious damage.
To lift the unit, the base of the unit. Spreader bars and cables should be ar­ranged to prevent damage to the condenser coils or unit cabinet (see Figure 2).
Due to the vertical condenser design, it is recommended that certain precautions be taken before installation to orient the unit so that prevailing winds blow parallel to the unit length, thus minimizing effects on condensing pressure. If it is not practical to orient the unit in this manner, a wind deflecting fence should be considered.
The clearance requirements for these units are given in
Figure 3.
Each end of the unit must be accessible after installation for
periodic service work. Compressors, filter-driers, and manual
liquid line shutoff valves are accessible from the control center
end of the unit through removable access panels on unit sizes 089,106, and 126 through 179 and hinged side access doors on unit sizes 037 through 078, 091, 098 and 107. All opera­tional, safety, and starting controls are located in the unit con­trol center. Capped connections for field service gauges are
also located inside these enclosures.
CAUTION: Disconnect all power
2V2”
diameter lifting holes are provided in

LOCATION

SERVICE ACCESS

condenser fan drives.
to
the unit while servicing
Figure 1. Suggested Pushing Arrangement
BLOCKING
\
0
Figure 2. Suggested Lifting Arrangement
SPREADER
ACROSS FULL WIDTH
MUST UiE HOLES FOR ALP-0898 THRU
159B. (NOTE CONTROL BOX
LOCATION.)
THESE RIGGING
REQ’D.
lM269 I
Page 3

REFRIGERANT PIPING

GENERAL McQuay type ALP condensing units are adaptable to either chilled water or air handling air conditioning applications, The only restriction on applications is that the evaporator be selected for a system using refrigerant 22.
EVAPORATOR ABOVE CONDENSING UNIT Figure 6 shows an installation where the evaporator is in­stalled above the condensing unit. It is shown for an air han­dling installation but all components shown are recommended for chilled water installations, except that a refrigerant distributor is not usually required for shell-and-tube evaporators.
EVAPORATOR BELOW CONDENSING UNIT Figure 7 shows an installation where the evaporator is in­stalled below the condensing unit. It is shown for an air
han-
dling installation, but all components shown are recom­mended for chilled water installations except that a refrigerant distributor is not usually required for shell-and-tube evaporators. Note that a double suction riser is shown for this arrangement.
Risers “A +
B”
are sized so that their combined
cross­sectional Internal area will allow full load unit operation without excessive pressure drop (see notes, Table 4). Riser
“B”
is sized to provide adequate suction gas velocity for proper oil return at minimum load conditions. This riser becomes ef­fective only when the trap shown in riser “A” fills itself with oil. It should be emphasized that the trap shown in riser “A” should be designed to contain a minimum internal volume to keep the total system oil requirements at a minimum. Table 4 gives recommended line sizes for both single and double suction lines and for liquid lines.
Figure 6. Evaporator Above Condensing Unit
a
Filter-drer
b
Solenoid valve
Slghtglasslmolsture indicator
d”
Thermal
expansion Suction Ime. pttched Liquid
line
Vlbratton
absorber
Double suction riser (see Note 3)
A&:
e
f
valve
toward compressor
NOTES:
1. Piping
shown IS for one circut; second
2. All
pIping
3. Trap for double
and pIpIng components are by others
suction riser
clrcult IS slmllar
should be as small in the
Figure 7. Evaporator Below Condensing Unit
horizontal
dlwctlon as ilttlngs
WIII
allow
AIR FLOW

REFRIGERANT PIPING CONNECTIONS

Refrigerant piping connections must be made at the control center end of the unit. Suction and liquid lines should be routed through the compressor end access panels on units ALP-089B, 106B,
1268 thru 1598, and
179A
and out the
tom through the side access panels above the compressor
McQuay has available a “Liquid Line Accessory Kit” for each ALP unit size. Components selected for these kits were selected on the basis of a total combined pressure drop of 7 psi (includes 100 ft. of tubing). Table 5 shows the ordering number to be used for each ALP unit size. The components in these kits are:
Page 6
/
lM269
side access door on units ALP-037A thru and 107A. When piping, allow room for mounting the
nect
on this same access panel. Figure 8 gives connection
bot-
locations and sizes for all ALP models.

LIQUID LINE COMPONENTS

1.
Replaceable core type filter-driers.
2.
Filter-drier core elements. Refrigerant solenoid valves.
3. Refrigerant
4.
Expansion valves (one per circuit).
5.
078B,091A, 098A
discon-
sightglass/moisture indicators.
Figure 18. ALP-089B,
Power into unit
106B,
126B thru
Recommended field mounted disconnect
159A, & 179A
switch

SEQUENCE OF OPERATION

For ALP-037A thru 0788, 091A, 098A
&
107A Units:
The components for a two-compressor unit, models ALP-046A, 057A, given in parentheses (
The following sequence of operation is for ALP
0678,
078B, 091A,
).
098A and
107A
SEASON­CON air cooled condensing unit operation. With control cir­cuit power on, control stop switch pumpdown
switch
PS1
(PS2) closed (“auto” position), 115 volt power is applied through control circuit fuse compressor crankcase heater
HTR1
S1
closed, and manual
F1
(HTR2).
When the remote time clock contacts are closed, the flow switch contacts are closed (chiller applications) and the manual shutdown switch is on; then relay
R11
is energized, closing contacts 4 through 6 and 7 through 9. If high pressure control HP1 pressure control
(HP2),
motor protector
OP1
(OP2) do not sense an alarm condi-
MP1
(MP2) and oil
tion, then the thermostat will energize. The unit will operate automatically in response to the thermostat.
On a call for cooling,
solenoid
SV1,
opening the valve and allowing refrigerant to
TC1,
stage 1, energizes liquid line
flow into the evaporator. As refrigerant pressure builds up, low pressure control tactor Ml, starting the compressor.
LP1
closes to energize compressor
LP1
also energizes con­denser fan motor 11 and condenser fan motor controls PC1 2, TC13, and TC14
(TC14
on models ALP-037 067 and 078).
On two-compressor units, if additional stages of cooling are
required, temperature control thermostat
TC1
energizes li­quid line solenoid valve SV2 after time delay relay TD1 sequenced closed, to initiate the same starting sequence in
refrigerant circuit number 2.
On units with compressor unloading, if additional stages
of cooling are required, the unloader
U1
(U2) is de-energized
and the compressor is loaded.
For
ALP-089B, 106B,
1268 thru 1598, & 107A Units
The following sequence of operation is typical for ALP SEASONCON air cooled condensing unit operation. It is writ­ten for a four-compressor unit. Components referred to in the sequence, but not used in a three-compressor unit are HTR3,
Page 18
/
lM269
Control Center Layout
MP3, R7, TD12, M3 and M7.
With the control circuit power on, control stop switch Sl
are
closed, and manual closed (“auto” position), 115 volt power is applied through control circuit fuse Fl to the compressor crankcase heaters HTR1 and HTR4 and, if safety contacts HP1 and HP2 are closed, then power is supplied to low pressure switches and LP2.
to the
When the remote time clock or manual shutdown switch turns on, a pair of contacts close in the thermostatic circuit. If all safeties (HP1 and HP2, through MP4) do not sense an alarm condition, then safety
R5, R7,
relays plied to the thermostat automatically in response to TC1.
On a demand for cooling, the unit thermostat energizes liquid line solenoid refrigerant to flow into the evaporator. As refrigerant pressure builds up, low pressure control pressor contactor Ml, starting the compressor. energizes
con-
tactors Ml 1, Ml2 and M13. A second contact on R9 shuts out TD15, opening up TD15. If R9,
then compressors 1 and 3 cannot be started until TD15
times out and energizes safety relays
NOTE: The new motor protectors have a two-minute time
delay. When power is interrupted to terminals 3 and 4 of any
1 has
motor protector, the MP contacts across terminals 1 and 2
will not close for two minutes.
If additional stages of cooling are required, the thermostat energizes liquid line solenoid valve SV2 after time delay relay TD11
has sequenced closed, to initiate the same starting se-
quence in refrigerant circuit number 2.
If additional cooling is still required, the third and fourth stages of the thermostat energize the third and fourth com-
pressors after time delay relays TD12 and TD13 have se­quenced closed.
pumpdown
switches PS1 and PS2
OP1
through OP4 and
R6 and R8 are energized. Power is then sup-
TC1
and the unit will operate
SV1,
opening the valve and allowing
LP1
closes, energizing com-
R9
which in turn provides power to fan motor
LP1
opens, cutting power to
R5
and R7.
LP1
LP1
MP1
also
con-

START-UP AND SHUTDOWN

1.
With all electrical disconnects open, check all screw or lug type electrical connections to be sure they are tight for good electrical contact. Check all compressor valve connections for tightness to avoid refrigerant loss at start­up. Although all factory connections are tight before ship­ment, some loosening may have resulted from shipping vibration.
2.
On chilled water installations, check to see that all water piping is properly connected.
Check the compressor oil level. Prior to start-up, the oil
3. level should cover at least one-third of the oil sightglass.
4.
Remove the eight (8) compressor shipping blocks that are attached to the compressor rails and the base of the unit. Units ALP-037 through 078, 091, 098 and 107 do not have shipping blocks.
Check the voltage of the unit power supply and see that
5. it is within the
voltage unbalance must be within * 2%. Check the unit power supply wiring for adequate
6.
ty and a minimum insulation temperature rating of 75C.
f
10% tolerance that is allowed. Phase
ampaci-

PRE START-UP

7.
2.
9.
10.
11.
CAUTION: Most relays and terminals in the unit control center
are hot with S1 and the control circuit disconnect on.
Verify that all mechanical and electrical inspections have
been completed per local codes.
See that all auxiliary control equipment is operative and that an adequate cooling load is available for initial start-up.
Open the compressor suction and discharge shutoff
valves until backseated. Always replace valve seal caps.
Making sure control stop switch
pumpdown
pumpdown,” throw the main power and control discon-
nect switches to “on.”
heaters. Wait a minimum of 12 hours before starting up
unit.
Open all water flow valves and start the chilled water
pump. Check all piping for leaks and vent the air from
the evaporator and system piping to obtain clean, non-
corrosive water in the evaporator circuit.
switches
PS1
and PS2 are on “manual
This will energize crankcase
S1
is open (off) and

INITIAL START-UP

1.
Double check that the compressor suction and discharge shutoff valves are backseated. Always replace valve seal caps.
2.
Open the manual liquid line shutoff valve at the outlet of the subcooler.
3.
Check to see that in the “manual pumpdown” position. Throw the control stop switch
4.
Adjust the dial on the temperature controller to the desired chilled water or leaving air temperature.
5.
Allow the crankcase heaters to operate for at least 12 hours prior to start-up.
Move
pumpdown turn off the chilled water pump or evaporator fan. It is especially important on chilled water installations that the compressors pump down before the water flow to the evaporator is interrupted to avoid freeze-up.
1. Start the chilled water pump or evaporator fan.
2. With control stop switch
postion.
3. Observe the unit operation for a short time to be sure that the compressors do not cut out on low oil pressure.
pumpdown
S1
to the “on” position.
switches PS1 and PS2 to the “manual pumpdown” position. After the compressors have pumped down,
switches
S1
in the “on” position, move
PS1
and PS2 are

TEMPORARY SHUTDOWN

START-UP AFTER TEMPORARY SHUTDOWN

pumpdown
Start the auxiliary equipment for the installation. Start the system by moving
PS2 to the “automatic pumpdown” position. After running the unit for a short time, check the oil level
in each compressor crankcase and check for flashing in the refrigerant sightglass (see “Maintenance”, page 41).
After system performance has stabilized, it is necessary that the “Compressorized Equipment Warranty Form” (Form No. 206036A) be completed to obtain full warranty benefits. This form is shipped with the unit and after com­pletion should be returned to through your sales representative.
switches
PS1
and PS2 to the “automatic pumpdown”
pumpdown
McQuay
switches PS1 and
Service Department
(For start-up after extended shutdown, refer to applicable “Initial Start-up” steps.)
1. Close the manual liquid line shutoff valves.
2. After the compressors have pumped down, turn off the
chilled water pump or evaporator fan.
3. Turn off all power to the unit and to the auxiliary
equipment.
Page
40 / lM269

EXTENDED SHUTDOWN

4.
Move the control stop switch S1 to the “off” position.
5.
Close the compressor suction and discharge valves.
6.
Tag all opened disconnect switches to warn against start-
up before opening the compressor suction and discharge
valves.

SYSTEM MAINTENANCE

GENERAL

On initial start-up and periodically during operation, it will be
necesasry to perform certain routine service checks, Among these are checking the compressor oil level and taking densing, the oil level should be visible in the oil sightglass with the compressor running. On units ordered with gauges, sing, suction, and oil pressures can be read from the unit
suction and oil pressure readings. During operation,
con-
conden-
con-
trol center. The gauges are factory installed with a manual shut-off valve on each gauge line. The valves should be closed at all times except when gauge readings are being taken. On units ordered without gauges, the gauge shutoff valves come factory installed inside the unit control center for convenient connection of service gauges from outside the
unit.
ALP-089B, 106B,
The fan shaft bearings do not require lubrication at the time the unit is put into service. The fan shaft bearings should be greased once a year using Standard Oil Company
CAUTION: ELECTRIC SHOCK HAZARD. TURN OFF ALL POWER
BEFORE CONTINUING WITH THE FOLLOWING SERVICE.
All power electrical terminals should be retightened every six months, as they tend to loosen in service due to normal heating
and cooling of the wire.
Because of the large refrigerant charge required in an air
cooled condensing unit, it is usually necessary to put addi­tional oil into the system. The oil level should be watched carefully upon initial start-up and for sometime thereafter.
At the present time, Suniso No. 3GS oil is the only oil ap­proved by Copeland for use in these compressors. The oil level should be maintained at about one-third of the sightglass
on the compressor body.
Oil may be added to the
oil fill hole in the crankcase and to the Sundstrand compressor through the To add oil, isolate the crankcase and pour or pump the
necessary oil in. If the system contains no refrigerant, no
318”
process tube on the side of the compressor.
Copeland
compressor through the

FAN SHAFT BEARINGS

126B thru
Amco
Multi-Purpose Lithium Grease. DO NOT OVERLUBRICATE.

ELECTRICAL TERMINALS

COMPRESSOR OIL LEVEL

159B,
and 179A
special precautions are necessary other than keeping the oil clean and dry.
If the system contains a refrigerant charge, close the suc­tion valve and reduce crankcase pressure to 1 to 2 psig. Stop the compressor and close the discharge valve.
Add the required amount of oil. During the period the com­pressor is exposed to the atmosphere, the refrigerant will generate a vapor pressure, retarding the entrance of con­taminants. Before resealing the compressor, purge the crankcase by opening the suction valve slightly for 1 or 2 seconds. Close the oil port, open the compressor valves and restore the system to operation.

CONDENSERS

Condensers are air cooled and constructed of per tubes bonded in a staggered pattern into rippled aluminum fins. No maintenance is ordinarily required except the occasional removal of dirt and debris from the outside
The refrigerant sightglasses should be observed periodical-
ly.
(A monthly observation should be adequate.) A clear glass
of liquid indicates that there is adequate refrigerant charge
in the system to insure proper feed through the expansion valve. Bubbling refrigerant in the sightglass indicates that the
system is short of refrigerant charge. On sightglasses ordered
3/8”0.0. cop-

REFRIGERANT SIGHTGLASS

surface of the fins. Care should be taken not to damage the fins during cleaning. Periodic use of the purge valve on the condenser will prevent the buildup of non-condensables.
from McQuay as part of the “Liquid Line Accessory Kits” listed on page 6, an element inside the sightglass indicates what moisture condition corresponds to a given element color. If the sightglass does not indicate a dry condition after a few
hours of operation, the unit should be pumped down and the
cores in the filter-drier changed.
lM269 /
Page
41

SERVICE

NOTE: Service on this equipment is to be performed by qualified refrigeration service personnel. Causes for repeated tripping of safety controls must be investigated and corrected. CAUTION: Disconnect ail power before doing any ser­vice inside the unit.

FILTER-DRIERS

To change the filterdrier core(s), pump the unit down by
ing
pumpdown
switches
PS1
and PS2 to the “manual
down” position. Turn off all power to the unit and install
jumpers across the terminals shown in the table below.
ALP CIRCUIT JUMPER ACROSS
UNIT SIZE
037
thru
076, 091, 098 107
037
thru
076, 091, 09.9, 107
099,106,
069, 106, 126
126th~
thru
NUMBER
179
179
1 2
1
2
TERMINALS
114
214
114 to 118
214 to 218

LIQUID LINE SOLENOID VALVE

The liquid line solenoid valves, which are responsible for automatic pumpdown during normal unit operation, do not normally require any maintenance. They may, however, re­quire replacement of the solenoid coil or of the entire valve assembly.
The solenoid coil may be removed from the valve body without opening the refrigerant piping by moving switches PS1 and PS2 to the “manual pumpdown” position.
mov-
pump-
to
116
to
216
pumpdown
Turn power to the unit back on and restart the unit by mov-
ing
pumpdown
switches
PS1
and PS2 to the “automatic
pumpdown” position. Close the manual liquid line shutoff valve(s) and when evaporator pressure reaches 0 psig, move the control stop switch
S1
to the “off” position. This will close the liquid line solenoid valve(s) and isolate the short section of refrigerant piping containing the filter-drier(s). Remove the cover plate from the filter-drier shell and replace the core(s).
After core replacement, replace the cover plate. A leak
check around the flange of the filter-drier shell is
recom-
mended after the cores have been changed.
The coil can then be removed from the valve body by simply
removing a nut or snap-ring located at the top of the coil. The
coil can then be slipped off its mounting stud for replacement.
Be sure to replace the coil on its mounting stud before ing
pumpdown
switches
PS1
and PS2 to the “automatic
return-
pumpdown” position.
To replace the entire solenoid valve, the unit must be
pumped down by use of the manual liquid line shutoff valve.

THERMOSTATIC EXPANSION VALVE

The expansion valve is responsible for allowing the proper amount of refrigerant to enter the evaporator regardless of cooling load. it does this by maintaining a constant superheat. (Superheat is the difference between refrigerant temperature as it leaves the evaporator and the saturation temperature corresponding to the evaporator pressure.) Typically, superheat should run in the range of 1 OF to 15F. On valves purchased through McQuay, the superheat setting can be adjusted by removing a cap at the bottom of the valve to
ex­pose the adjustment screw. Turn the screw clockwise (when viewed from the adjustment screw end) to increase the
INLET
superheat setting and counterclockwise to reduce superheat. Allow time for system rebalance after each superheat ad­justment.
The expansion valve, like the solenoid valve, should not normally require replacement, but if it does, the unit must be pumped down by using the manual liquid line shutoff valve. If this problem can be traced to the power element only, it
can be unscrewed from the valve body without removing the valve, but only after pumping down the unit with the liquid
line shutoff valves.
POWER ELEMENT
(CONTAINS DIAPHRAGM)
OUTLET
SPRING
Page 42
/
lM269
ADJUSTMENT SCREW
CAP

IN-WARRANTY RETURN MATERIAL PROCEDURE

COMPRESSOR

Copeland who maintain a stock of replacement compressors and ser­vice parts to serve refrigeration contractors and servicemen.
sales representative, or McQuay Warranty Claims Depart­ment at the address on the cover of this bulletin. You will be authorized to exchange the defective compressor at a Copeland tained. A credit is issued to you by the wholesaler for the returned compressor after
inoperative compressor. If that compressor is out of
Copeland’s warranty, a salvage credit only is allowed. Pro-
Material may not be returned except by permission of authorized service personnel of McQuay Inc. at Minneapolis, Minnesota. A “Return Goods” tag will be sent to be in­cluded with the returned material. Enter the information as called for on the tag in order to expedite handling at our fac­tories and prompt issuance of credits.
replacement. Therefore, a purchase order must be entered
through your nearest McQuay representative. The order
Refrigeration Corporation has stocking wholesalers
When a compressor fails in warranty, contact your local
wholesaler, or an advance replacement can be ob-
Copeland
factory inspection of the

COMPONENTS OTHER THAN COMPRESSORS

The return of the part does not constitute an order for
vide McQuay with full details: McQuay unit model and unit serial numbers. Include the invoice and the salvage value credit memo copies and we will reimburse the difference. In this transaction, be certain that the compressor is definitely defective. If a compressor is received from the field that tests satisfactorily, a service charge plus a transportation charge will be charged against its original credit value.
On all out-of-warranty compressor failures, Copeland of­fers the same field facilities for service and/or replacement as described above. The credit issued by Copeland on the
returned compressor will be determined by the repair charge
established for that particular unit.
should include part name, part number, model number and serial number of the unit involved.
Following our personal inspection of the returned part, and if it is determined that the failure is due to faulty material or workmanship, and in warranty, credit will be issued on customer’s purchase order.
All parts shall be returned to the pre-designated McQuay factory, transportation charges prepaid.
APPENDIX: STANDARD CONTROLS
NOTE: PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR.

OIL PRESSURESAFETY CONTROL

The oil pressure safety control is a manually resettable device which senses the differential between oil pressure at the discharge of the compressor oil pump and suction pressure inside the compressor crankcase. When the oil pressure reaches approximately 15 PSI above the crankcase suction pressure, the pressure actuated contact of the control opens from its normally closed position. If this pressure differential cannot be developed, the contact will remain closed and energize a heater element within the control. The heater ele-
ment warms a normally closed bimetallic contact and causes
the contact to open, de-energizing a safety relay and break-
ing power to the compressor.
It takes about 120 seconds to warm the heater element enough to open the bimetallic contact, thus allowing time for the pressure differential to develop.
If during operation, the differential drops below 10 PSI, the heater element will be energized and the compressor will stop. The control can be reset by pushing the reset button on the control. If the compressor does not restart, allow a few
LINE (SEE NOTE
LINE
(SEE
11
ACTUATED
CONTACT
NOTE
21
L M
minutes for the heater element and bimetallic contacts to cool and reset the control again.
To check the control, pump down and shut off all power to the unit. Remove the compressor fuses, and install a voltmeter between terminals
“L”
and
“M”
of the oil pressure control. Turn on power to the unit control circuit (separate disconnect or main unit disconnect, depending on the type of installation). Check to see that the control stop switch is in the “on” position. The control circuit should now be energized, but with the absence of the compressor fuses, no oil pressure differential can develop and thus, the pressure actuated contacts of the control will energize the heater ele-
ment and open the bimetallic contacts of the control within 120 seconds. When this happens, the safety relay is
energized, the voltmeter reading will rise to
115V,
and the compressor contactor should open. Repeated operations of the control will cause a slight heat buildup in the bimetallic contacts, resulting in a slightly longer time for reset with each successive operation.
-
t
-
BIMETALLIC CONTACTS
HEATER ELEMENT
NEUTRAL
NEUTRAL
SAFETY RELAY
S1
de-
NOTES: 1. Hot only when the unit thermostat calls for compressor
to run.
2.
Hot only when other
safety
control contacts are closed.
lM269
/ Page 43

HIGH PRESSURE CONTROL

The high pressure control is a single pole pressure activated switch that opens on a pressure rise to de-energize the
en­tire control circuit except for compressor crankcase heaters. It senses condenser pressure and is factory set to open at 380 psig and can be manually reset closed at 315 psig. To check the control, either block off condenser surface or start the unit with fuses in only one fan fuse block
(FBll)
and
observe the cut-out point of the control by watching condenser

LOW PRESSURE CONTROL

The low pressure control is a single pole pressure switch that closes on a pressure rise. It senses evaporator pressure and is factory set to close at 60 psig and automatically open at 25 psig. The control has an adjustable range of 20 inches of Hg. to 100 psig and an adjustable differential of 6 to 40 psig. To check the control (unit must be running), move the pumpdown
switch(es) PSI and PS2 to the “manual
pump-
down” position. As the compressor pumps down, condenser
pressure rise. The highest point reached before cut-out is the cut-out setting of the control.
CAUTION: Although there is an additional pressure relief device in the system set at 450 psig, it is highly
recom-
mended that the “control stop” switch S1 be close at hand
in case the high pressure control should malfunction.
pressure will rise and evaporator pressure will drop. The lowest evaporator pressure reached before cut-out is the cut­out setting of the control. By moving the pumpdown switch(es) PS1
and PS2 to the “automatic pumpdown” position, evaporator pressure will rise. The highest evaporator pressure reached before compressor restart is the cut-in setting of the
control.
FANTROL
-
HEAD
FANTROL is a method of head pressure control which automatically cycles the condenser fans in response to con­denser pressure and ambient air temperature. This maintains head pressure and allows the unit to run at low ambient air temperatures.
For ALP-037A thru 0788,
Models ALP-037A thru 0788, dual independent circuits with the fans for circuit 1 (fans
091A,
098A,
091A, 098A,
107A:
and
107A
have
11,
12, 13, 14) and circuit 2 ( fans 21, 22, 23, 24) being con­trolled independently by the condensing pressure and am­bient air of each circuit. Fans 11 and 21 start with each com­pressor and fans 12 and 22 cycle on and off in response to condenser pressure. The cut-out and cut-in pressures are
Table 13. Factory FANTROL Settings
UNIT SIZE
ALP-OBSB, 106B 1268
thru
159B,
&
l?QA
I
270 psi’ 170 psi’
-
-
8OFt
PRESSURE CONTROL
given in Table 13. Fans 13 and 14, circuit 1, and fans 23 and 24, circuit 2, are controlled by ambient temperature and are factory set at the values given in Table 13. Note that the
number of fans on each unit varies. For ALP-089B,
106B, 126B
thru
159B,
and
179A:
The first fan (11) is started when the first compressor in the
unit starts. Fan 12 is controlled by parallel wired pressure
switches which sense condenser pressure in circuit 1 and
2. The third fan (13) is controlled by parallel wired temperature switches, one of which senses condenser inlet air for circuit 1 and the other senses condenser inlet air for circuit 2. Refer
to Table 13 for cut-out and cut-in settings of these controls.
CONDENSER FAN
70Ft
-
- - -
I
l PC1 and PC2
Page 44 I lM269
t
TC5 and TC6
APPENDIX: OPTIONAL CONTROLS

SPEEDTROL -HEAD PRESSURE CONTROL

ALP-037A thru
The SPEEDTROL system of head pressure control operates in conjunction with FANTROL by modulating the motor speed on fans 11 and 21 in response to condensing pressure. By reducing the speed of the last fan as the condensing pressure falls, the unit can operate at lower ambient temperatures.
The SPEEDTROL fan motor is a single phase, thermally protected motor specially designed for variable speed application. The solid-state speed controls SC1 1 and
DAMPERTROL
ALP-089B, 1068, 1268 thru 1598, and
DAMPERTROL is an optional system for reducing condenser capacity. It consists of an assembly of damper blades, linkages and blade operators installed over the first fan turned on by FANTROL (fan 11) and arranged to operate as shown. The blade operators sense condenser pressure and extend or contract in response to the pressure to open or close the damper blades as reuired to maintain adequate con­denser pressure. The operators are factory set to begin open-
ing the damper blades at 170 + 5 psig and to be fully open
at 250 + 10 psig.
208/240
078B,
091A, 098A and 107A
SC21 are mounted inside the compressor compartment near the top of the condenser coils, Units with 460 volt power have a transformer mounted on the back of the control box to step the voltage down to 230 volts for the SPEEDTROL motor.
volt,
-
HEAD PRESSURE CONTROL
speed at approximately 230 psig and maintains a minimum condensing pressure of 170 to 180 psig.
unit should be started with the fuses removed from fans 11
and 13 (on three-fan units only). At condenser pressures
below 170
ly closed. As pressure rises above 170 + 5 psig, the damper
blades should begin opening and be fully open at 250 f 10
psig. Leaving the fuses in on fan 12 will prevent head pressure
from becoming excessive, since this fan will start after the
fully open setting of the damper operators has been observed.
The SPEEDTROL control starts to modulate the motor
179A
To check the damper blade operator pressure settings, the
+
5 psig, the damper blades should be complete-
DAMPER
SECTION
y
COIL
DAMPERTROL IN OPEN POSITION
Part winding start is available on all voltage units and sists of a solid-state time delay wired in series with the tactor that energizes the second winding of each compressor Control checkout is best accomplished by observation as motor. Its purpose is to limit current inrush to the compressors upon start-up. As each compressor starts, the contactor for occurs before the second contactor pulls in.
LINE
1
PART WINDING START (OPTIONAL)
con-
con-
DAMPERTROL IN CLOSED POSITION
the first motor winding is energized instantly while that for
the second motor winding is delayed for 1 second.
each contactor is pulled in to see that the 1 second delay
PART WINDING
(2nd MOTOR
WINDING)
lM269
/
Page 45
LOW AMBIENT START (OPTIONAL)
Low ambient start is available on all units as an option with FANTROL and included automatically with optional
TROL or DAMPERTROL. It consists of a solid-state normal-
ly closed time delay wired in series with a relay. These are
both wired in parallel to the liquid line solenoid valve so that when the solenoid valve is energized by the unit thermostat, the low ambient start relay is also energized through the time delay. The relay has contacts that essentially short-circuit the
low pressure control and allow the compressor to start with the low pressure control open.
After about energize the relay. If the system has not built up enough evaporator pressure to close the low pressure control, the compressor will stop. The time delay can be reset to its
2% minutes, the time delay will open and
SPEED-
de-
original normally closed position by moving the switch(es) tion. Moving the pumpdown” position will again energize the relay for another attempt at start-up. If the system has built up enough evaporator pressure, the compressor will continue to run.
To check the control, turn off all power to the unit and remove the wire(s) leading to the terminals of the low pressure control(s) LPI and LP2. Remove the compressor fuses and
jumper across terminals
and oil pressure safety control(s). Energize the control cir­cuit by turning on the control circuit disconnect or main power disconnect (depending on the installation) and the control stop switch
PS1
or PS2 to the “manual pumpodown” posi-
pumpdown
S1.
The compressor
switch back to the “automatic
“L”
and
“M”
of the freeze control(s)
contactors
should pull in instantly.
pumpdown
f
L,NE
NOTE :
COMPRESSOR LOCKOUT (OPTIONAL)
Compressor lockout consists of a solid-state time delay wired in series with the compressor contactor( It purpose is to prevent rapid compressor cycling when cooling demands are erratic. The circuit illustrated below is for the lead compressor in each refrigerant circuit. The circuit for the second com­pressor(s) performs the same function but is wired different­ly (see unit wiring diagram).
When the unit thermostat no longer calls for cooling and the compressor contactor have opened, the lockout time delay breaks open the circuit, preventing compressor restart.
The circuit remains open for a period of 5 minutes so that if the unit thermostatshould call for cooling before the delay period has expired the compressor will not restart. After 5 minutes, the time delay will close its contacts to complete
Line is only hot when the unit thermostat calls for compressor to run.
Low
*zzA:%lEUTRAL
-
ALP-937A thru 078B,
the circuit and be ready for start-up. The time delay opens
its contacts whenever power to terminal 4 is interrupted and resets closed automatically after the time delay period.
To check the control, the compressor(s) must be running initially. Move the “manual pumpdown” position. Immediately after the com­pressor(s) have stopped running, move the pumpdown switch back to the “automatic pumpdown” position. The lead com­pressor should not restart for 5 minutes. The second com­pressor in the refrigerant circuit should start approximately 20 seconds after the lead compressor, provided that the cool­ing load is high enough to require it. Each refrigerant circuit
can be checked the same way.
091A,
pumpdown
098A, 107A
switch PSI or PS2 to the
Page
46 I
lM269
NOTE:
1 C&P
TO UNIT THERMOSTAT
Hot whenever freeze control and high
pressure control permit safe operation.
LOCKOUT
TIME DELAY
HOT GAS BYPASS (OPTIONAL)
Hot gas bypass is a system for maintaining evaporator pressure at or above a minimum value. The purpose for do­ing this is to keep the velocity of the refrigerant as it passes through the evaporator high enough for proper oil return to the compressor when cooling load conditions are light. Hot gas bypass kits are described on page 9.
The solenoid valve should be wired to open whenever the
unit thermostat calls for the first stage of cooling (see Figure
11). The pressure regulating valve that
McQuay
offers is fac­tory set to begin opening at 58 psig (32F for R-22) when the air charged bulb is in an
80F
ambient temperature. The bulb can be mounted anywhere as long as it senses a fairly con­stant temperature at various load conditions. The compressor suction line is one such mounting location. It is generally in the 50F to 60F range. The chart on page 47 indicates that when the bulb is sensing 50F to 60F temperatures, the valve will begin opening at 54 to 56 psig. This setting can be changed as indicated above, by changing the pressure of the air charge in the adjustable bulb. To raise the pressure set-
ting, remove the cap on the bulb and turn the adjustment screw clockwise. To lower the setting, turn the screw counterclockwise. Do not force the adjustment beyond the range for which it is designed, as this will damage the ad-
justment assembly.
The regulating valve opening point can be determined by slowly reducing the system load while observing the suction pressure. When the bypass valve starts to open, the refrigerant line on the evaporator side of the valve will begin to feel warm to the touch.
CAUTION: The hot gas line may become hot enough to cause
injury in a very short time so care should be taken during valve checkout.
On installations where the condensing unit is remote from
the evaporator, it is recommended that the hot gas bypass valve be mounted near the condensing unit to minimize the
amount of refrigerant that will condense in the hot gas line
during periods when hot gas bypass is not required.
HOT GAS BYPASS PIPING DIAGRAM

Hot Gas Bypass

Solenoid Valve
in ALP Unit
Bypass Valve
Expansion Valve (On DX Coils with
Distnbutors, Sporlan Auxiliary Sideport Connector
or Equivalent)
use
HOT GAS BYPASS ADJUSTMENT RANGE
REMOTE BULB ADJUSTMENT RANGE
30
70
bL
30
30
40
50 60 TEMP IOFI
AT BULL? LOCATION
70
80 90 100
110
lM269 I Page 47

TROUBLESHOOTING CHART

PROBLEM
Compressor Not Run
Compreesor or Vibrating
High Pressure
Low Pressure 2. Suction shutoff valve partially closed. 2. Open valve.
High Suction
Pressure
.ow
Suction 1. Lack of refrigerant.
Pressure
kmpressor Will
Jnload or Load Up Little
Pressure
Compressor
Loses
Motor Overload
Relays Open or Blown Fuses
Compressor Thermal Protector
Dpen
Will 1. Main switch open.
Noisy
Discharge
Discharge
or No Oil
Oil
Switch
I
2. Fuse blown. Circuit breakers open.
3. Thermal overloads tripped.
4. Defective contactor or coil. 4. Repair or replace.
5. System shutdown by safety devices. 5. Determine type and cause of shutdown and correct it before reset-
6. No cooling required.
7. Liquid line solenoid will not open. 7. Repair or replace coil.
8. Motor electrical trouble. 8. Check motor for opens, short circuit, or burnout.
9. Loose wiring. 9. Check all wire junctions. Tighten all terminal screws.
1.
Flooding of
2. Improper piping line.
3. Worn compressor.
1.
Non-condensibles in system.
2. System overcharged with refrigerant.
3. Discharge shutoff valve partially closed.
4. Fan not running.
1.
Faulty condenser temperature regulation. 1. Check condenser control operation.
3. Insufficient refrigerant in system. 3. Check for leaks. Repair and add charge.
4. Low suction pressure.
5. Compressor operating unloaded.
1. Excessive load.
2. Expansion valve overfeeding.
3. Compressor unloaders open.
2. Evaporator dirty. Plugged air filters.
3. Clogged liquid line filter-drier.
4. Clogged suction line or compressor suction gas strainers.
5. Expansion valve malfunctioning.
6. Condensing temperature too low.
7. Compressor will not unload.
Not
1.
Defective capacity control.
2. Pressurestat not set for application.
1. Clogged suction oil strainer. 1. Clean.
2. Excessive liquid in crankcase.
3. Oil pressure gauge defective.
4. Low oil pressure safety switch defective.
5. Worn oil pump.
6. Oil pump reversing gear stuck in wrong postion.
7. Worn bearings.
8. Low oil level.
9. Loose fitting on oil lines.
10. Pump housing gasket leaks.
11. Flooding of refrigerant into crankcase.
1. Lack of refrigerant
2. Excessive compressor ring blow-by.
1. Low voltage during high load conditions.
2. Defective or grounded wiring in motor.
3. Loose power wiring.
4. High condensing temperature.
5. Power line fault causing unbalanced voltage.
6. High ambient temperature around the overload relay.
7. Failure of second starter to pull in on winding
1. Operating beyond design conditions.
2. Discharge valve partially shut.
3. Blown valve plate gasket.
POSSIBLE CAUSES
refrigerant
start
supprt
systems.
into crankcase.
on
suction
or
liquid
part-
I
1. Close switch.
2. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading. Replace fuse or reset breakers
after fault is corrected.
3. Overloads are auto. reset. Check unit closely when unit comes back on-line.
ting safety switch.
6. None. Wait until unit calls for cooling.
1. Check setting of expansion valve.
2. Relocate, add or remove hangers.
3. Replace.
1.
Purge the non-condensibles.
2.
Remove excess.
3. Open valve.
4. Check electrical circuit.
4. See Corrective Steps for low suction pressure below.
5. See Corrective Steps for failure of compressor to load up below.
1.
Reduce load or add additional equipment.
2. Check remote bulb. Regulate superheat.
3. See Corrective Steps below for failure of compressor to load up.
1 Check for leaks. Repair and add charge 2 Clean chemically. 3 Replace cartridge(s). 4 Clean strainers.
5 Check and reset for proper superheat.
6 Check means for
7. See
COrreCtwe
1.
Replace.
2. Reset pressure setting
2. Check crankcase heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve operation.
3. Repair or replace. Keep valve closed except when taking readings.
4. Replace.
5. Replace.
6. Reverse direction of compressor rotation.
7. Replace compressor.
8. Add oil.
9. Check and tighten system.
10. Replace gasket.
11. Adjust thermal expansion valve.
1.
Check for leaks and repair. Add refrigerant.
2. Replace compressor.
1. Check supply voltage for excessive line drip.
2. Replace compressor motor.
3. Check all connections and tighten.
4. See Corrective Steps for high discharge pressure.
5. Check supply voltage. Notify power company. Do not start until fault is corrected.
6. Provide ventilation to reduce heat.
7 Repair or replace starter or
1.
Add facilities so that conditions are within allowable limits.
2. Open valve.
3. Replace gasket.
POSSIBLE
___. -_-
regulating
Steps for failure of compressor to unload,
CnRRFCTlVF STFPR
_- . .
.._ -.._-
condensing temperature.
to
fit application.
time
delay
_.-.
mechanism.
_
Loading...