‘“McQuay” and “SeasonCon” are registered tradenames of SnyderGeneral Corporation. “FanTrol” and “SpeedTrol” are tradenames of SnyderGenera! Corporation.
01994 SnyderGeneral Corporation. All rights reserved throughout the world.
“Bulletin illustrations cover the general appearance of SnyderGeneral Corporation products at the time of publication
and we reserve the right to make changes in design and construction at any time without notice.”
Page2/lM404
Introduction
Model type ALP air cooled condensingunits are designed
for outdoor installationsand are compatible with either air
handling or chilled water systems. Each unit is completely
assembledand factory wired before evacuation,charg-
ing and testing. Each unit consists of an air cooled condenser
with integral subcooler section with complete discharge piping and suction and liquid connections for connection to any
air or water cooling evaporator.
Inspection
When the equipment is received, all items should be carefullyrier and a claim should be filed. The unit serial plate should
checked against the bill of lading to insure a complete shipment. All units should be carefully inspected for damage upon
arrival. All shipping damage should be reported to the car-
be checked before unloading the unit to be sure that it agrees
with the power supply available.
Installation
Note: Installation and maintenanceare to be performedonly by qualified personnelwho are familiar with local codes and
regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces area potential injury hazard.
Avoid contact with” them.
Rigging and Moving Units
The exact method of handling and setting the unit depends
on available equipment, size of unit, final location, and other
variables. It is therefore up to the judgment of the riggers and
movers to determine the specific method of handling each
unit.
All units are equipped with built-in skids for rigging and
moving.
Figure 1. Suggestedrigging
Location
Due to vertical condenser design, it is recommended that the
unit is oriented so that prevailing winds blow parallel to the
unit Iength, thus minimizing effects on condensing pressure.
If it is not practical to orient the unit in this manner, a wind
deflector should be constructed.
Units are designed for outdoor applicationand may be
mounted on a roof or concrete slab (ground level installation).
Roof-mountedunits should be installed level on steel channels or an l-beam frame to support the unit above the roof.
The roof must be strong enough to support the weight of
the unit. See Physical Data for unit weight. Concrete slabs
used for unit mounting should be installed level and be properly supported to prevent settling. A one-piece concrete slab
with footings extended below the frost line is recommended.
Figure 2. Clearancearoundunit
t
5 Ft. Min. Clearance
For Air Inlet
&u
COND. COIL
Min.r- =
4 Ft.
Clearance~ g
For Service
“o”
rcp
COND. COIL
Ft. Min. Clearance
5
For Air
COMP.Clearance
Inlet
6 Ft. Min.
For Service
NOTES
1. Minimum clearance between units is 12 feet.
2. Units must not be Installed in a pit that is deeper than the height of the unit.
3. Minimum clearance on each side is 12 feet when installed in a pit.
IM 404 I Page 3
RefrigerantPiping
General
Piping design, sizing and installation information presented
in ASHRAE Handbooks should, where applicable, be followed
in the design and installationof piping. McQuay type ALP
condensing units are adaptable to either chilled water or air
handling air conditioning applications. The only restriction on
applicationsis that the evaporator be selected for a system
using refrigerantR-22.
RefrigerantPiping
Piping between the condensing unit and the cooling coil must
be designed and installed to minimize pressure drop, prevent liquid refrigerantcarryover to the compressor and to
assure a continuous return of compressor oil from the system.
Piping sketches and tables are not intended to provide information on all of the possible arrangements.
Piping recommendationsinclude:
1.
The use of type K or L clean copper tubing. All joints should
be thoroughly cleaned and brazed with high temperature
solder.
2.
Piping sizes should be based on temperature/pressure
limitations as recommendedin the following paragraphs.
Under no circumstancesshould pipe size be based upon
the coil or condensingunit piping connection size.
3.
Suction line piping pressure drop should not exceed the
pressure equivalent of 2° F (3 psi) per 100 feet of equivalent
pipe length. After the suction line size has been determined, the vertical suction risers should be checked to
verify that oil will be carried up the riser and back to the
compressor.The suction line should be pitched in the
direction of refrigerant flow and adequatelysupported.
Lines should be free draining and fully insulated between
the evaporator and the compressor. Table 3 shows piping information for units operating at suction temperatures
between 40Fand 45Fand a condenserentering air
temperature of 95° F. If operating conditions are expected
to vary substantially from these operating levels, the pipe
sizing should be rechecked.
4.
Vertical suction risers should be checked using Table 1
to determine the minimum tonnage required to carry oil
up suction risers of various sizes.
The Iiquid line should be sized for a pressure drop not to
5.
exceed the pressure equivalent of 2° F (6 psi) saturated
temperature.The liquid line on all units must include a
liquid solenoid valve wired into the circuit as shown on the
applicableunit wiring diagrams.
The control circuit for all compressorshas been de-
signed to include a pumpdown cycle. The use of a liquid
line solenoid is required for proper unit operation. In ad-.
dition, a filter-drier should be located between the liquid
line service valve
andthe solenoid valve and a combina-
tion moisture indicator/sightglassshould be located in the
liquid line ahead of the expansion valve.
Suggested piping arrangements are shown on page 5. The
6
figures shown are for an air handling installation,but all
componentsshown are recommendedfor chilled water
vessel installations except that a refrigerant distributor is
not usually required for shell-and-tubeevaporators.
If dual suction risers are used:
7
Double risers are sized so that the combined crosssectional internal area will allow full load unit operation
without excessive pressure drop (see notes, Table 3). Riser
“A” is sized to provide adequate suction gas velocity for
proper oil return at minimum load conditions. This riser
becomes effective only when the trap shown in riser “B”
fills itself with oil. It should be emphasizedthat the trap
shown in riser “B”should be designed to contain a
minimum internal volume to keep the total system oil requirementsat a minimum. Table 3 gives recommended
line sizes for both single and double suction lines and for
Iiquid lines,
a.
‘ The combined cross-sectionalareas of the two risers
must be capable of maintainingadequate refrigerant
velocity for oil return at full unit tonnage.
b.
The extra riser should be of a smaller diameter than
the main riser. The extra riser must include its own trap
at the bottom and should enter the main suction header
at twelve o’clock.
The trap serving the extra riser must be as short as fit-
c.
tings permit. A “U” fitting or the combinationof a 90’
standard “L” and a 90° street-L is recommended.
d.
The suction line Ieaving the coil should also include a
trap if the expansion valve control bulb is to be on the
horizontal section leaving the coil outlet. See the piping sketches on page 5.
Table 1. Minimum
tonnage(R-22) to carry oil up
suctionriser at 40” F saturatedsuction.
Line Size OD1%
Min. Tons1.502.503,80
NOTE: When compressor minimum tonnage is less than shown in the above
table for a given line size. double suction risers will
1
7.6013.1020.4
21A2%3~/’E 378
1 ye
3/3
4y~
29.741.3
be required
Table 2. Equivalentfeet of straighttubing for copper fittingsand valves
7/8
0,9
1%
1.7
2.13.03.4
1.7
2.63.3
29
1.0
12
ELBOWS
900 Standard
90° Long Radius
900 Street
45o Standard
45” Street
180° aEND
TEES
Full Size
Reducing
VALVES
Globe Valve, Open
Gate Valve, Open
Angle Valve, Open
FITTING TYPE
5/8
I
1.62.02.63.3
1.01.4
2.53.24.15.66.3
0.60.91.31.72.1
1.31.5
2.5.3.24.15.66.38.2
1.01.4
1.62,0
1622
0.7
7.09.0
Page 4 I IM 404
1ye1ya2Y8
4.0
2.32,63.3
2.32.63.3
4.05.06.0
384355
1.51.8
1518
5.0
8.2
2.63.2
4.55.2
2.32.83.24.0
24293541
25A3~/4
6.0
4.15.0
10.012.015.017.0
10.0
4.15.0
6984100
7.5
4.0
6.47.38.5
12.0
7.5
378
I
9.0
5.9
4.75.2
15.0
5.9
9.0
49A
10.0
6.7
17.0
6.7
10.0
I
120
4.5
47
.
I
Table 3. Recommendedline eizes
ALP UNIT0.0. COPPER
SIZE
!
027C
032C
037C
041C
)
NOTES:
Recommended line sizes shown in the above table are based on the unit
operating conditions between 40° F and 45” F saturated suction temperature
and condenser entering air temperature of 95” F, per 100 ft. equivalent length
of tubing. When design conditions vary, the table values should be rechecked.
Liquid and suction lines based on a recommended equivalent pressure
1.
drop of 2F (3 psi for suction line, 6 psi for liquid line) per 100 ft. of
equivalent length.
When refrigerant required to charge a circuit exceeds the pumpdown
2.
capacity of that circuit the use of a separate refrigerant storage receiver
will be required. The pumpdown capacity is based on the condenser
full at 90iF (see Physical Data).
3.
Wherever vertical rise occurs in the suction piping, the minimum tonnage
for oil entrainment should be checked and where necessary double suction risers should be utilized. See Table 1.
4.
Wherever vertical rise occurs in the suction piping on a system with hot
gas bypass, double suction risers may not be needed as the velocity of
suction gas is increased at minimum load conditions.
5.
Total equivalent feet for a given piping layout must include the equivalent
length of straight pipe for fittings, valves and specialties added to the total
run of straight pipe.
Piping design, sizing and installation information presented in ASHRAE
6.
Handbooks should, ‘where applicable, be followed in the design and installation of piping.
DOUBLE
A–B
134 — lye21A
1% — 1%2%1~~
SINGLE
lye — 21A2%
lye — 21A2’%1ye
SUCTIONLINESIZE
LIQUID LINE
SIZE
O.D. COPPER
11A
l%
90%
Table 4. Weight of refrigerantR-22 in copperlines
(poundsper 100 feet of type L tubing)
0.0.
Vol.per
Line100 Ft.Llquld
in Cu. Ft. r@lOO”F
Size
0.0543.64
%
V20.1007.12.374
0.1627.12.605.156
%
0.336
‘h
11A0.57340.82.14
Weight of Refrigerant, Lbe.
Hot Gas
@120”F(Superheated to 65” F)
Cond.20” F40” F
.202
24.01.26
.052.077
.096
.323
.550
Suction Gas
1%0.67262.13.26.6391.250
1%1.23786.0
2%2.147153.06.042.063.060
2%3.312236.0
3%
3y,
4j~6.313592.031.18.0011.190
t
4.726
6.398I456.024.0
I
336.0
4.62
12.4
17.7
1.1901.770
3.16
4.556.750
6.15
.143
.232
.460
.620
4.720
9.140
I
Figure 3. Typical refrigerantpiping diagram
Evaporatoror cooler
below condensingunit
AIR FLOW
Evaporatoror cooler
ab
I
LEGEND
a Filter-drier
b Solenoid valve
c 8ightglass/moistureindicator
d Thermal expansion valve
e Suction line, pitched toward compressor
f Liquid line
g Vibration absorber
A & B Double suction riser (see Note 2)
NOTES:
1. All piping and piping components are by others.
2. Trap for double suction riser should be as small in the horizontal direction as fittings will allow.
3. Cooler suction connection should always be top connection.
lM 404 I Page 5
Figure 4. Recommendedliquid line piping
CONDENSING UNIT
SEALED CORE
FILTER DRIER
LIQUID LINE
\/
BALL VALVES TO ISOLATE
FILTER DRIER FOR SERVICE
Hot Gas Bypass Components
Hot gas bypass kits are available for each ALP unit size. Each
kit includes a solenoid valve, a hot gas bypass valve and instruction drawing. See page 20 for hot gas bypass operation.
Table 5. Hot gas bypass kits
ALP UNIT
SIZE
027C
032C
037C
041 c886-580898A-04
y.
KIT NUMbER
886-580898A-031ye
886-580898A-041ye
888-580898A-031ye
LINE SIZE
O.D. (IN.)
1ye
RefrigerantPiping Connections
Refrigerantpiping connectionswill be made at the compressor end of the unit. Suction and liquid lines should be
routed through the compressor enclosure on the side of the
unit.
HoldingCharge
The Model ALP condensingunit is shipped with a holding
charge of refrigerant. At the time the unit was received a visual
inspection of the unit piping should have been made to be
sure no breakage had occurred or that fittings might have
been loosened. A pressure check should indicate a positive
pressure in the unit. If no pressure is evident, the unit will
have to be leak tested and the leak repaired. This should be
noted and reported to your sales representative or freight carrier if the loss is due to shipping damage.
Leak Testing
In the case of loss of the refrigerant holding charge, the unit
should be checked for leaks prior to charging the complete
system. If the full charge was lost, leak testing can be done
by charging the refrigerant into the unit to build the pressure
to approximately10 psig and adding sufficient dry nitrogen
to bring the pressure to a maximum of 125 psig. The unit
should then be leak tested with a Halide or electronic leak
detector. After making any necessary repair, the system
should be evacuated as describedin the followingparagraphs.
Caution: Do not use oxygen to build up pressure. A serious
explosion could be the result.
Evacuation
After it has been determined that the unit is tight and there
are no refrigerantleaks, the system should be evacuated.
The use of a vacuum pump with a pumping capacity of approximately 3 cu. ft./rein. and the ability to reduce the vacuum
in the unit to at least 1 millimeter (1000 microns) is recommended.
LIQUID LINE
SOLENOID
AIR HANDLER
u
r“n\”
SIGHTGLASS
EXPANSION
VALVE
1. A mercurv manometer, electronic or other type of micron
gauge should be connected to the unit at a-point remote
from the vacuum pump. For readings below 1 millimeter,
an electronic or other micron gauge should be used.
2. The triple evacuation method is recommended and is particularly helpful if the vacuum pump is unable to obtain
the desired 1 millimeterof vacuum. The system is first
evacuated to approximately 29 inches of mercury. Enough
refrigerant vapor is then added to the system to bring the
pressure up to O pounds.
3. Then the system is once again evacuated to 29 inches
of vacuum. This procedure is repeated three times. This
method can be most effective by holding system pressure
at Opounds for a minimum of 1 hour between evacuations.
The first pull down will remove about 90% of the noncondensables,the second about 90% of that remaining
from the first pull down and after the third only 1/10 of 1%
noncondensableswill remain.
Table 6 shows the relationship between pressure, microns,
atmospheres,and the boiling point of water.
Chargingthe System
After all refrigerant piping is complete and the system has
1.
been evacuated, it can be charged as described in the
paragraphs following. Connect the refrigerant drum to the
gauge port on the liquid line and purge the charging line
between the refrigerant cylinder and the valve. Then open
the valve to the mid-position.
2.
If the system is under a vacuum, stand the refrigerant drum
with the connection up and open the drum and break the
vacuum with refrigerantgas.
3.
With a system gas pressure higher than the equivalent
of a freezing temperature, invert the charging cylinder and
elevate the drum above the condenser. With the drum in
this position, valves open and liquid refrigerant will flow
into the condenser. Approximately 75% of the total requirement estimated for the unit can be charged in this manner.
After 75% of the required charge has entered the con-
4.
denser, reconnect the refrigerant drum and charging line
to the suction side of the system. Again purge the connecting line, stand the drum with the connection up, and
place the service valve in the open position.
Important:At this point charging procedure should be in-
terrupted and prestart checks made before attempting to com-
plete the refrigerantcharge (see start-up procedures).
Itis recommendedthat the total operating charge
Note:
be stamped on the with nameplatefor future reference.
Page 6 I IM 404
RefrigerantCharge
Each ALP condensing unit is designed for use with R-22. See
physical data for approximate refrigeration charges for operation of the unit. Additional refrigerant will be needed for the
system piping and evaporator.Estimated total operating
charge should be calculated before charging system.
Table 6. Pressure-vacuumequivalents
ABSOLUTE PRESSURE ABOVE ZERO
MICRONSPSIA
o
500.001759.95
1000.002
1500.003759,85
2000.004
3000.006759,70
5000.009759.50
1,0000.019
0
2,0000.039
4,0000.078
VACUUM BELOW ONE ATMOSPHEREAPPROXIMATE
MERCURYMERCURYFRACTION OF
(mm)
760,00
759.9029.920
759.8029.910
759.0029.880
758.0029.840
756.0029.760
6,0000.117754.00
6,000
10,0000.193
15,0000.290
20,0000.387
30,0000.580
50,0000.967
100,0001.930
200,000_—..500,000
760,00014.697
0.156
1
3.870560.00
9.670
I
752.0029.600
750.0029.530
745.00
740.00291301/38
730.00
710.00
660.0025.960
260.0010.240
001 Atmosphere
Caution:Tots/ operating charge shou/dnotexceed the
condenser pumpdown capacity plus the capacity of the liquid
Iine. A liquid receivershould be used if the unit operating
charge exceedsthe pumpdowncapacity.Refer to the
ASHRAE Handbook for the design and installation of piping
and components.