Inc. 13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, Mn.
ALP-O16A
thru -033A
55440 @
.
McQUAY
type ALP SEASONCON air cooled condensing
units are designed for outdoor installations and are
compatible with either air handling or chilled water
systems. Each unit is completely assembled and factory
INTRODUCTION
consists of an air cooled condenser with integral subcooler
section,
piping and suction and liquid connections for connection to
any air or water cooling evaporator.
an unloading compressor, complete discharge
wired before evacuation, charging and testing. Each unit
NOMENCLATURE
A L P-033 A-S
Nomtnal
Capacity
(Tons)
INSPECTION
When the equipment is received, all items should be
carefully checked against the bill of lading to insure a
complete shipment. All units should be carefully inspected
for damage upon arrival. All shipping damage should be
INSTALLATION
NOTE: Installation and maintenance are to be performed only by qualified personnel who are familiar
with local codes and regulations, and experienced with this type of equipment. CAUTION: Sharp edges
and coil surfaces are a potential injury hazard. Avoid contact with them.
HANDLING
Care should be taken to avoid rough handling or shock due
to dropping the unit. Do not push or pull the unit from
anything other than the base, and block the pushing vehicle
away from the unit to prevent damage to the sheet metal
cabinet. (See Figure 1.)
To lift the unit,
provided in the base of the unit. Spreader bars and cables
should be arranged to prevent damage to the condenser
coils or unit cabinet. (See Figure 2.)
LOCATION
Due to vertical condenser design, it is recommended that
the unit is oriented so that prevailing winds blow parallel to
the unit length, thus minimizing effects on condensing
pressure. If it is not practical to orient the unit in this
manner, a wind deflector should be constructed.
Units are designed for outdoor application and may be
mounted on a roof or concrete slab (ground level
installation). Roof-mounted units should be installed level
on steel channels or an l-beam frame to support the unit
above the roof. Use of vibration pads or isolators is
recommended. The roof must be strong enough to support
the weight of the unit. See Table 1 for unit weights.
Concrete slabs used for unit mounting should be installed
level and be properly supported to prevent settling. A
one-piece concrete slab with footings extended below the
frost line is recommended.
TABLE 1. UNIT WEIGHTS
ALP MODEL
016A
019A
023A
027A
033A
2-1/2-inch
diameter lifting holes are
OPERATING WEIGHT (LBS.)
1122
1383
1471
1600
1866
reported to the carrier and a claim should be filed. The unit
serial plate should be checked before unloading the unit to
be sure that it agrees with the power supply available.
FIGURE 1.
GOOD PUSHING ARRANGEMENT -CABINET DAMAGE UNLIKELY
SUGGESTED PUSHING ARRANGEMENT
FIGURE 2.
-?
PAGE 3
ACCESS
It is necessary to provide adequate clearance on all sides of
the
unit for service access and satisfactory performance.
Necessary clearances are shown in Figure 3.
VIBRATION ISOLATORS
Vibration isolators are recommended for all roof-mounted
installations or wherever vibration transmission is a
potential problem. Table 2 lists spring and rubber-in-shear
isolators for all ALP unit sizes. Table 3 shows isolator loads
FIGURE 3.
CLEARANCE AROUND UNIT
and the maximum allowable load for each isolator. Figure 4
shows isolator locations in relation to the unit control
“A-‘MIN.
CLEARANCE
FOR AIR INLET
panel. Figure 5 gives dimensions that are required to secure
each
Each unit base frame is provided with the necessary holes
to accept the
isolator.
-i%q
Acc~~~~~N
pQ%z-
TABLE 2.
’
ALP LOCATIONS
UNIT
SIZE ORDERING NUMBER
016A
019A
023A
027A
033A
By removing the access screens, access can be gained to
the compressor, refrigerant lines, refrigerant components,
condenser fans and SPEEDTROL components. All other
controls are located in the unit control panel. They are
protected by a keylocked, weatherproof enclosure which
contains an internal “dead front” door for protection of
service personnel from high voltage starting controls while
servicing low voltage operational controls.
FIGURE 5.
ISOLATOR DIMENSIONS
(IN.)
Spring-Flex Isolators
ADJUST MOUNTING SO UPPER
HOUSING CLEARS LOWER
TABLE 3.
LATO R LOADS
IS0
0.50 DIA.
ACOUSTkAL NONSKlD
NEOPRENE PAD
HOUSING
AND NOT MORE
”
Rubber-In-Shear Isolators
,600
Dia. Pin
Mounting Molded
in
Neoorene
L4.12---
-\1’2.5”7
5.50
2 Holes
A
1
PAGE
ALP
UNIT
SIZE LOCATION
016A
019A
023A
027A
033A
4
ISOLATOR LOADS AT
EACH MOUNTING LOCATION
1.2,3
&
4 SPRING-FLEX
281
346
368
400
467
MAXIMUM LOADS ALLOWABLE
FOR EACH ISOLATOR SELECTION
RUBBER-IN-SHEAR
450
600
600
600
750
525
525
525
525
750
REFRIGERANT PIPING
McQUAY
adaptable to either chilled water or air handling air
conditioning applications using refrigerant 22. Refrigerant
piping to and from the unit should be sized and installed
according to the latest
type ALP SEASONCON condensing units are
ASHRAE
Guide. The following
discussion is for use as a general guide to sound, economical
and trouble-free piping. The correct application of the
principles discussed here is the responsibility of the
installer.
EVAPORATOR ABOVE CONDENSING UNIT
Figure 6 shows an installation where the evaporator is
installed above the condensing unit. It is shown for an air
handling installation, but all components shown are
recommended for chilled water installations except that a
refrigerant distributor is not usually required for
shell-and-tube evaporators.
FIGURE 6.
Evaporator Above Condensing Unit
-G-AIR
FLOW
EVAPORATOR BELOW CONDENSING
UNIT
Figure 7 shows an installation where the evaporator is
installed below the condensing unit. It is shown for an air
handling installation, but all components shown are
recommended for chilled water installations except that a
refrigerant
distributor is not usually required for
shell-and-tube evaporators. Note that a double suction riser
is shown for this arrangement.
Risers
“A + B”
are sized so that their combined
cross-sectional internal area will allow full load unit
operation without excessive pressure drop (see notes, Table
4). Riser
“B” is sized to provide adequate suction gas
velocity for proper oil return at minimum load conditions.
This riser becomes effective only when the trap shown in
riser “A” fills itself with oil. It should be emphasized that
the trap shown in riser “A” should be designed to contain a
minimum internal volume to keep the total system oil
requirements at a minimum. Table 4 gives recommended
line sizes for both single and double suction lines and for
liquid lines.
FIGURE 7.
Evaporator Below Condensing Unit
LEGEND
a Filterdrier
b Solenoid valve
c
Sightglasslmoisture indicator
d Thermal expansion valve
e
Suction line, pitched toward compressor
f Liquid line
g Vibration absorber
NOTES: All piping and piping components are by others.
TABLE 4.
ALP
UNIT
SIZE
016A-S
019A-S 1318-l 318 2118
023A-S 1518-l
027A-S 1518-l 318 2118 1l/8
033A-S 1518-l 518 2118 1 118
Note: Liquid and suction lines based on a recommended pressure
drop of 3 PSIG
RECOMMENDED LINE
DOUBLE
+y;.?l
1
118-l
l/8 1518
318 2 118 1l/8
12OF)
per 100 ft.
SINGLE
SUCTION
equrvalent
SIZE
LIQUID
718
718
length.
e-AIR
FLOW
LEGEND
a Filterdrier
b Solenoid valve
c
Sightglass/moisture
d Thermal expansion valve
e
Suction line, pitched toward compressor
f Liquid line
g
Vibration absorber
A+8 - Double suction riser (see note 2)
NOTES:
1. All piping and piping components are by others.
2. Trap for double suction riser should be as small in the
horizontal direction as fittings will allow.
indicator
REFRIGERANT PIPING CONNECTIONS
Refrigerant piping connections should be made through the
holes provided in the base frame on access screen side of
the unit.
PAGE 5
LIQUID LINE COMPONENTS
McQUAY
each ALP unit size. Table 5 shows the ordering number to
be used for each ALP unit size. The components included
in these kits are:
has available a “Liquid Line Accessory Kit” for
TABLE 5. LIQUID LINE ACCESSORY KITS
ALP LIQUID LINE
UNIT ACCESSORY KIT
SIZE ORDERING NUMBER
016A-S
019A-S
023A-S
027A-S
033A-S
,
886-368903641
886366903641
8863689039-01
886-368903841
aa6-36890384x2
FILTER-
DRIER VALVE GLASS
718718
718
718718718
7/a7/a7/a
7ta
Replaceable core type filter-drier.
1.
Filter-drier core element.
2.
3
Refrigerant
Refrigerant
4:
Expansion valve.
5.
CONNECTION SIZES O.D.
SOLENOID SIGHT-
7/a
718718
solenoid valve.
sightglass/moisture
(IN.1
7ta
7/a
indicator.
EXPANSION VALVE
IN
718
7/a
718
718
718
OUT
I
318
i
3/a
I
3/a
i
318
i
3/a
FIGURE 8.
DIMENSIONAL DRAWING
REFRIGERANT CHARGE
Each ALP condensing unit is designed for operation using
refrigerant 22. Table 6 lists refrigerant charge required for a
condensing unit/cooler combination.
TABLE 6. APPROXIMATE REFRIGERANT CHARGE
PAGE 6
ALP
MODEL
016A-S
019A-S
023A-S
027AS
033A-S
l
Refrigerant
will require
charge is for a
an additional charge.
‘R-22 REFRIGERANT
CHARGE (LBS.)
17
23
32
37
53
close-coupled
system. A remote cooler
ADDING REFRIGERANT CHARGE
On systems that have been
refrigerant, an
insufficient
previously
charge is indicated by bubbling
in the sightglass. On uncharged systems, the system should
be leak tested and evacuated before charging. Upon
charging
a system, the discharge and suction shut-off valves
on the compressor should be open and there should be
normal water flow through the cooler.
CAUTION: Do not make any safety controls inoperative
during the charging operation: cooler damage from freezing
may result.
1. Back seat the liquid line shut-off valve and connect the
charging hose to the
1/4-inch
flare connectron.
2. Install pressure gauges and review start-up instructions.
3. Purge the charging hose and open the
to allow refrigerant
into
the system.
charged with
charging
cylinder
Turn the liquid line shut-off valve in three turns to
‘4.
permit a back flow of refrigerant into the subcooler.
After refrigerant stops flowing into the system, close the
5.
liquid line shut-off valve. Start the compressor to charge
the system.
If the amount of refrigerant has been predetermined,
6.
add this amount and check the sightglass afterward.
If the amount of charge is unknown, close the charging
cylinder valve every five minutes, open the liquid line
shut-off valve and check for proper charge by examining
the sightglass. Continue charging and checking the
sightglass until it is clear.
NOTE: Fluorocarbon refrigerants should not be released to
the atmosphere. For a means of recovery, refer to the
following section.
REMOVING REFRIGERANT CHARGE
To prevent freeze-up when removing the refrigerant for
ALP installations on water chiller systems, either drain the
water or circulate the water. If water cannot
make sure the cooler heater is energized. Do not remove
refrigerant rapidly since this can cause freeze-ups. Have a
sufficient number of refrigerant containers and a scale for
weighing them. The containers should be clean, dry and
empty.
gauge manifold from the compressor discharge valve service
port to the container and purge the iines. Note the capacity
of the container. Place the container in ice to cool the
container so the fusible plug does not melt as the
refrigerant condenses. Operate the compressor normally.
Turn the discharge service valve in three turns to open the
gauge manifold. Do not close off the discharge valve to the
condenser. Discharge gas can enter the container and
condense.
overfill. When the container is filled use additional ones.
FIELD WIRING
WARNING: USE ONLY COPPER CONDUCTORS IN MAIN TERMINAL BLOCK.
Wiring should be done in accordance with all applicable
codes and ordinances. Warranty is voided if wiring is not in
accordance with specifications. An open fuse indicates a
short, ground or overload. Before replacing a fuse or
restarting a compressor or fan motor, the trouble must be
found and corrected.
All standard units require a 115 volt power supply for
the control circuit. If the optional control circuit
transformer is ordered, the control circuit is powered off
the main power supply.
unit installation. Items that require field wiring are liquid
line solenoid
and the cooling thermostat, as well as the unit power
supplies.
be
drained,
To transfer the refrigerant to a container, connect the
Frequently weigh the container so as not to
Figure 9 shows typical field wiring that is required for
SV1,
optional hot gas bypass solenoid
SV5
FIGURE 9.
TYPICAL FIELD WIRING
““ll Ml,”
PB1
,
Since it is impossible for
installation that an ALP condensing unit may be used on,
we do not factory install a thermostat. We do, however,
provide numbered terminals inside the unit control center
McQUAY
to anticipate the type of
THERMOSTAT WIRING
to which a thermostat may be connected. These terminals
are shown and labeled “Terminals For Thermostat” on the
electrical schematics. Figure 9 shows typical field wiring for
a thermostat with temperature controlled unloading.
PAGE 7
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.