McQuay Air-Cooled Global Water Chillers are complete, self-contained automatic
refrigerating units. Every unit is completely assembled, factory wired, charged, and
tested. Each unit consists of twin air-cooled condensers with integral subcooler
sections, two tandem or triple scroll compressors, brazed-plate or replaceable tube, dual
circuit shell-and-tube evaporator, and complete refrigerant piping. Liquid line
components include manual liquid line shutoff valves, sight-glass/moisture indicators,
solenoid valves, and thermal expansion valves. Other features include compressor
crankcase heaters, an evaporator heater for chilled water freeze protection, limited
pumpdown during “on” or “off” periods, automatic compressor lead-lag to alternate the
compressor starting sequence, and sequenced starting of compressors.
The electrical control center includes all equipment protection and operating controls
necessary for dependable automatic operation. Condenser fan motors are protected in
all three phases and started by their own three-pole contactors.
This manual covers units with software versionAGZDU0102C. Installation,
maintenance and service information is in IMM AGZ-7 (or current latest dash number)
manual.
BOOT Version 3.0F
BIOS Version 3.56
Air-Cooled
Global
Scroll Compressor
Nomenclature
A G Z - XXX B S
Application
S= Standard Ambient, Packaged
M= Standard Ambient, Remote
H= High Ambient, Packaged
B= High Ambient, Remote
Design Vi ntage
Model Size
(Nominal Tons)
OM AGZ-1 AGZ 026B through 130B 3
Ambient Air Temperature Limitations
Standard/High Ambient Panels
Models AGZ-B (26 to 130 tons, two circuit) have electrical data and subsequent field wiring
requirements that are tailored to individual applications.
There are many installations where the expected summer ambient air temperatures will be at
105°F (40.1°C) or less, resulting in smaller unit electrical requirements compared to operation at
106°F (41.1) and above. In these lower temperature cases, there can be considerable installation
cost savings by using smaller and more appropriate electrical service.
Therefore, the AGZ electrical data is divided into two classifications based on the design ambient
temperature where the unit will operate. Standard Ambient unit electrical data (BS and BM
models) is for operation in ambient temperatures of 105°F (40.1°C) or less. Units with the High
Ambient designation (BH and BB models) are for use above 105°F (40.1°C) to 125°F (51.7°C).
The AGZ-B units for high ambient operation require the addition of the High Ambient Control
Panel Option, which includes the addition of a small fan with a filter in the air intake to cool the
control panel, and a unit nameplate that lists the larger electrical requirements.
All units with the optional VFD low ambient fan control automatically include the High Ambient
Control Panel Option. Operation of the VFD generates a quantity of panel heat best removed by
use of a control panel fan.
Winter Operation Temperatures
0°F to 34°F 35°F and Above
Fan Control Optional High VFD (1) Standard FanTrol (2)
Design Ambient Air Temperature
Electrical Data (3)
≤105°F >106°F ≤105°F >106°F
Standard
Ambient
High
Ambient
Standard
Ambient
High
Ambient
Panel Fan Required (4) Yes Yes No Yes
Model Designator (5)
1. VFD is variable speed, fan control through the MicroTech Ii controller.
2. FanTrol is fan cycling off discharge pressure.
3. Standard Ambient and High Ambient electrical data is located in the installation and
maintenance manual.
4. The VFD option automatically includes the factory-installed panel fan and filter set
5. The designator is the last two characters in the model number, i.e. AGZ 100BS.
Panel Ratings
Vo ltage
208-230
240
380-460
575
Standard
Standard Options
Panel
Optional
VFD
High Short Circuit
Panel (kA)
High Interrupt Panel w/
Disconnect Swt. (kA)
35 5 120 120
35 5 100 100
35 5 65 65
5 5 25 25
4 AGZ 026B through 130B OM AGZ-1
Water Flow Limitations
The evaporator flow rates and pressure drops shown on page 11 are for full load design purposes in
order to maintain proper unit control. The maximum flow rate and pressure drop are based on a 6degree temperature drop. Avoid higher flow rates with resulting lower temperature drops to prevent
potential control problems resulting from very small control bands and limited start up/shut off
temperature changes.
The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees.
Evaporator flow rates below the minimum values can result in laminar flow causing freeze-up problems,
scaling and poor control. Flow rates above the maximum values will result in unacceptable pressure
drops and can cause excessive erosion, potentially leading to failure.
This full load minimum flow is not to be confused with the part load minimum flow rat e that must be
maintained for chillers operating in primary variable flow pumping systems. As chiller capacity drops,
the flow rate for this pumping system will reduce proportionally. See the following table for the part load minimum flo w rates.
These minimum flow rates assume that flow will be reduced proportionally to the cooling load.
Table 1, Minimum Part Load Flow Rates
AGZ Model 026 030 035 040 045 050 055 060 065
Minimum Part
Load Flow (GPM)
AGZ Model 070 075 085 090 100 110 120 130
Minimum Part
Load Flow (GPM)
26 29 32 37 41 45 50 55 59
63 71 119 128 146 161 180 194
System Water Volume Considerations
All chilled water systems need adequate time to recognize a load change, respond to that load change
and stabilize, without undesirable short cycling of the compressors or loss of control. In air
conditioning systems, the potential for short cycling usually exists when the building load falls below
the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum
cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time
for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a
rule of thumb of “gallons of water volume equal to two to three times the chilled water gpm flow rate”
is often used.
A properly designed storage tank should be added if the system components do not provide sufficient
water volume.
Variable Speed Pumping
Variable water flow involves reducing the water flow through the evaporator as the load decreases.
McQuay chillers are designed for this duty provided that the rate of change in water flow is not greater
than 10 percent of the change per minute.
The water flow through the vessel must remain between the minimum and maximum values listed on
11. If flow drops below the minimum allowable, large reductions in heat transfer can occur. If
page
the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.
OM AGZ-1 AGZ 026B through 130B 5
Glycol Solutions
T
The use of a glycol/water mixture in the evaporator to prevent freezing will reduce system capacity and
efficiency, as well as increase pressure drop. The system capacity, required glycol solution flow rate,
and pressure drop with glycol may be calculated using the following formulas and tables.
1. Capacity – Multiply the capacity based on water by the Capacity correction factor
Table 2 through Table 5.
from
2. Flow – Multiply the water evaporator flow by the Flow correction factor from
Table 2 through Table 5 to determine the increased evaporator flow due to glycol.
If the flow is unknown, it can be calculated from the following equation:
×
=
(gpm) Flow GlycolFactorCorrectionFlow
For Metric Applications
– Use the following equation for metric applications:
(l/s) Flow Glycol
CapacitykW
Delta
−×=18.4
3. Pressure drop -- Multiply the water pressure drop from page
correction factor from
Table 2 through Table 5. High concentrations of propylene
glycol at low temperatures may cause unacceptably high pressure drops.
4. Power -- Multiply the water system power by Power correction factor from
through
Table 5.
Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in
service stations) to determine the freezing point. Obtain percent glycol from the
freezing point table below. It is recommended that a minimum of 25% solution by
weight be used for protection against corrosion or that additional compatible inhibitors
be added.
Concentrations above 35 percent do not provide any additional burst protection and
should be carefully considered before using.
glycolCapacityTons
)(24
−
TDelta
×
×
FactorCorrectionFlow
)
11 by Pressure Drop
Table 2
CAUTION
Do not use an automotive grade antifreeze. Industrial grade glycols must be
used. Automotive antifreeze contains inhibitors which will cause plating on the
copper tubes within the chiller evaporator. The type and handling of glycol used
must be consistent with local codes.
Table 2, Ethylene Glycol Factors for Models AGZ 026B to 070B
Performance tables are based at sea level. Elevations other than sea level affect the performance of
the unit. The decreased air density will reduce condenser capacity consequently reducing the unit's
performance. For performance at elevations other than sea level, refer to
Table 6 and Table 7.
Evaporator Temperature Drop Factors
Performance tables are based on a 10°F (5°C) temperature drop through the evaporator. Adjustment
factors for applications with temperature ranges from 6°F to 16°F (3.3°C to 8.9°C) are in
Table 7.
Table 6 and
Temperature drops outside this 6°F to 16°F (3.3°C to 8.9°C) range can affect the control system's
capability to maintain acceptable control and are not recommended.
The maximum water temperature that can be circulated through the evaporator in a non-operating
mode is 100°F (37.8°C).
Fouling Factor
Performance tables are based on water with a fouling factor of
As fouling is increased, performance decreases. For performance at other than 0.0001 (0.0176)
fouling factor, refer to
Foreign matter in the chilled water system will adversely affect the heat transfer capability of
the evaporator and could increase the pressure drop and reduce the water flow. Maintain
proper water treatment to provide optimum unit operation.
22
per ARI 550/590-98.
)/0176.0(/0001.0
kWCmorBTUFhrft°×°××
OM AGZ-1 AGZ 026B through 130B 7
Table 6, Capacity and Power Derates, Models AGZ 026 to 070
Evaporator freeze-up can be a concern in the application of air-cooled water chillers. To
protect against freeze-up, insulation and an electric heater cable are furnished with the
unit. This protects the evaporator down to -20°F (-29°C) ambient air temperature.
Although the evaporator is equipped with freeze protection, it does not protect water
piping external to the unit or the evaporator itself if there is a power failure or heater
cable burnout. Consider the following recommendations for additional protection.
1. If the unit will not be operated during the winter, drain evaporator and chilled water
piping and flush with glycol. Drain and vent connections are provided on the
evaporator to ease draining.
2. Add a glycol solution to the chilled water system to provide freeze protection.
Freeze point should be approximately ten degrees below minimum design ambient
temperature.
3. The addition of thermostatically controlled heat and insulation to exposed piping.
4. Continuous circulation of water through the chilled water piping and evaporator.
OM AGZ-1 AGZ 026B through 130B 9
The evaporator heater cable is factory wired to the 115-volt circuit in the control box.
This power should be supplied from a separate source, but it can be supplied from the
control circuit. Operation of the heater cable is automatic through the ambient sensing
thermostat that energizes the evaporator heater cable for protection against freeze-up.
Unless the evaporator is drained in the winter, the disconnect switch to the evaporator
heater must not be open.
Operating/Standby Limits
Maximum standby ambient air temperature, 130°F (55°C)
Maximum operating ambient air temperature
Standard Ambient Unit, 105°F (40.6°C) and below, Models BS and BM
High Ambient Unit, above 105°F (40.6°C) to 125°F 51.7°C), Models BH and BB
Minimum operating ambient temperature (standard), 35°F (2°C)
Minimum operating ambient temperature (with optional low-ambient control), 0°F (-
18°C)
Leaving chilled water temperature, R-22, 40°F to 60°F (4.4°C to 15.6°C)
Leaving chilled water temperature, R-407C, 42°F to 60°F (5.5°C to 15.6°C)
Leaving chilled fluid temperatures (with anti-freeze), 20°F to 60°F (-7°C to 16°C
Design chilled water Delta-T range, 6 degrees F to 16 degrees F (3.3 degrees C to 8.9
degrees C)
Part load minimum flow for variable flow systems, varies with unit size, see table
below.
Maximum operating inlet fluid temperature, 76°F (24°C)
Maximum non-operating inlet fluid temperature, 100°F (38°C)
Water Flow Limitations, Variable Flow
The full load, minimum flow limitation for constant flow is not to be confused with the
part load minimum flow rate that must be maintained for chillers operating in primary
variable flow pumping systems. As chiller capacity drops, the flow rate for this
pumping system will reduce proportionally. See the following table for the part load
minimum flo w rates.
Other design practices for variable flow systems requiring a range of evaporator flow
rates can be found below.
These minimum flow rates assume that flow will be reduced proportionally to the
cooling load.
Figure 2, AGZ 026B – AGZ 130B, Typical Field Wiring
3 PHASE
POWER
DISCONNECT
(BY OTHERS)
UNIT MAIN
TERMINAL BLOCK
GND LUG
TO COMPRESSOR(S)
AND FAN MOTORS
NOTE: ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1
WIRING SYSTEM WITH CONDUCTOR
RATED 600 VOLTS
FIELD SUPPLIED
REMOTE STOP SWITCH
(BY OTHERS)
ICE MODE SWITCH
(BY OTHERS)
ALARM BELL
OPTION
CHW FLOW SWITCH
---MANDATORY–(BY OTHERS)
OPTION
CONTROL POWER
N
120VAC
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL RELAY
TIME
CLOCK
FUSED CONTROL
CIRCUIT TRANSFORMER
DISCONNECT
(BY OTHERS)
10A
FUSE
(BY OTHERS)
CHW PUMP RELAY
120 VAC 1.0 AMP MAX
OFF
AUTO
ON
MANUAL
OFF
AUTO
ON
MANUAL
(BY OTHERS)
120 VAC
CONTROLLER
TB1
TB2
TB1-20
1
2
35
33
34
CONTROL
CIRCUIT
FUSE
120 VAC
N
120 VAC
32
GND
IF REMOTE STOP
52
72
43
83
54
CONTROL IS USED,
REMOVE LEAD 585
585
FROM TERM. 52
TO 72.
BELL
12
ALARM BELL OPTION
ALARM BELL
RELAY
COM NO
74
NOR. OPEN PUM P AUX.
CONTACTS (OPTIONAL)
44
61
4-20MA FOR
EVAP. WATER RESET
(BY OTHERS)
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
DWG. 330423101 REV.0A
+
-
+
-
LESS EVAPORATOR ONLY
LIQUID LINE #1 SOLENOID
24 VAC 1.5 AMP MAX
LIQUID LINE #2 SOLENOID
24 VAC 1.5 AMP MAX
68
69
70
71
GND
91
93
92
93
24 VAC
N
24 VAC
N
12 AGZ 026B through 130B OM AGZ-1
R-407C Units
AGZ chillers are available with R-407C refrigerant as non-ARI certified units. R-407C is a
zeotropic blend of three compounds, and as such exhibits the characteristic of glide. It does
not behave as one substance like R-22 does. Glide is the difference (in degrees F) between the
beginning and end phase-change process in either the evaporator or condenser. During these
processes, different ratios of the refrigerant’s components change phase from the beginning to
the end of the process. The following functions, conditions and settings will differ from units
charged with R-22.
1. Polyolester lubricants are used instead of mineral oil.
2. The saturated pressure/temperature relationship
3. Control and alarm settings
4. Charging procedures
1.Lubrication. The units are factory-charged with polyoester (POE) lubricant and one of
the following lubricants must be used if lubricant is to be added to the system:
Copeland Ultra 22 CC
Mobil EAL™ Arctic 22 CC
ICI EMKARATE RL RL™ 32CF
POEs are very hydroscopic and will quickly absorb moisture if exposed to air. Pump the
lubricant into the unit through a closed transfer system. Avoid overcharging the unit.
2.Pressure/temperature relationship. See
temperature chart. Due to refrigerant glide, use the following procedures for superheat
and subcooling measurement.
To determine superheat, only vapor must be present at the point of measurement, no
liquid. Use the temperature reading, the pressure reading and the Saturated P/T Chart. If
the pressure is measured at 78 psig, the chart shows the saturated vapor
50.6°F. If the temperature is measured at 60°F, the superheat is 9.4 degrees F.
To determine subcooling, only liquid must be present, no vapor. Use the temperature
reading, the pressure reading and the Saturated P/T Chart. If the pressure is measured at
250 psig, the chart shows the saturated liquid
temperature is measured at 98°F, the subcooling is 10.2 degrees F.
The P/T relationship between R-407C and R-22 is similar enough to allow the use of R-22
expansion valves. The valves may be marked as “R-22’ or “R-22/R-407C”.
3.Control and alarm settings. The software that controls the operation of the unit is
factory-set for operation with R-407C, taking into account that the pressure/temperature
relationship differs from R-22. The software functionality is the same for either
refrigerant.
4.Charging procedure. The units are factory-charged with R-407C. Use the following
procedure if recharging in the field is necessary:
Whether topping off a charge or replacing the circuit’s entire charge, always remove the
refrigerant from the charging vessel as a liquid. Many of the cylinders for the newer
refrigerants have a dip tube so that liquid is drawn off when the cylinder is in the upright
position. Do not vapor charge out of a cylinder unless the entire contents will be charged
into the system.
Figure 3 on page 14 for the saturated pressure-
temperature to be
temperature to be 108.2°F. If the
With the system in a 250-micron or lower vacuum, liquid can be charged into the
high side. Initially charge about 80 percent of the system total charge.
OM AGZ-1 AGZ 026B through 130B 13
Start the system and observe operation. Use standard charging procedures (liquid
only) to top off the charge.
It may be necessary to add refrigerant through the compressor suction. Because the
refrigerant leaving the cylinder must be a liquid, exercise care to avoid damage to
the compressor. A sight glass can be connected between the charging hose and the
compressor. It can be adjusted to have liquid leave the cylinder and vapor enter the
compressor.
Set Screens Defined ........................................................ 46
Building Automation Systems (BAS)...............................53
OM AGZ-1 AGZ 026B through 130B 15
Overview
MicroTech II controller’s state-of-the-art design not only permits the chiller to run more
efficiently, but also can simplify troubleshooting if a system failure occurs. Every
MicroTech II controller is programmed and tested prior to shipment to facilitate startup.
Operator-friendly
The MicroTech II controller menu structure is separated into three distinct categories
that provide the operator or service technician with a full description of 1) current unit
status, 2) control parameters, and 3) alarms. Security protection prevents unauthorized
changing of the setpoints and control parameters.
MicroTech II control continuously performs self-diagnostic checks, monitoring system
temperatures, pressures and protection devices, and will automatically shut down a
compressor or the entire unit should a fault occur. The cause of the shutdown will be
retained in memory and can be easily displayed in plain English for operator review.
The MicroTech II chiller controller will also retain and display the date/time the fault
occurred. In addition to displaying alarm diagnostics, the MicroTech II chiller
controller also provides the operator with a warning of limit (pre-alarm) conditions.
General Description
AGZ-B Inputs/Outputs
Table 9, Analog Inputs
No. Description Type Signal Source Range
1 Evaporator Refrigerant Pressure #1 C1 0 to 132 psi
2 Evaporator Refrigerant Pressure #2 C2 0 to 132 psi
3 Condenser Refrigerant Pressure #1 C1 3.6 to 410 psi
4 Leaving Evaporator Water Temperature UT NTC Thermister (10k@25°C) -58 to 212°F
5 Outside Ambient Temperature UT NTC Thermister (10k@25°C) -58 to 212°F
6 Condenser Refrigerant Pressure #2 C2 3.6 to 410 psi
7 Reset of Leaving Water Temperature UT 4-20 mA Current
8 Demand Limit UT 4-20 mA Current 0-100 % Load
9 Compressor Suction Temperature #1 C1 NTC Thermister (10k@25°C) -58 to 212°F
10 Compressor Suction Temperature #2 C2 NTC Thermister (10k@25°C) -58 to 212°F
NOTES:
1. C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
2.Value at the converter board input. Value at the converter board output is 0.1 VDC – 0.9 VDC.
0.5 - 4.5 VDC (NOTE 2)
0.5 - 4.5 VDC (NOTE 2)
0.5 - 4.5 VDC (NOTE 2)
0.1 to 0.9 VDC
Table 10, Analog Outputs
No. Description Output Signal Range
1 Fan #1 VFD 0 to 10 VDC 20 to 60 Hz
2 Fan #2 VFD 0 to 10 VDC 20 to 60 Hz
0 to10 degrees
60°F max inlet
16AGZ 026B through 130B OM AGZ-1
Table 11, Digital Inputs
# Description Type Signal Signal
1 Unit OFF Switch UT 0 VAC (Disable) 24 VAC (Enable)
2 Pump Down Switch #1 C1 0 VAC (Disable) 24 VAC (Enable)
3 Evaporator Water Flow Switch UT 0 VAC (No Flow) 24 VAC (Flow)
4 Open
5 Open
6 Pump Down Switch #2 C2 0 VAC (Disable) 24 VAC (Enable)
7 Open
8 Open
9 Phase Voltage Fault #1 (See Note 1) C1 0 VAC (Fault) 24 VAC (No Fault)
10 Phase Voltage Fault #2 (See Note 1) C2 0 VAC (Fault) 24 VAC (No Fault)
11 Ground Fault Prot. #1 (See Note 2 Below)C1 0 VAC (Fault) 24 VAC (No Fault)
12 Ground Fault Prot. #2 (See Note 2 Below)C2 0 VAC (Fault) 24 VAC (No Fault)
13 Remote Start/Stop UT 0 VAC (Disable) 24 VAC (Enable)
14 Open
15 Mechanical High Pressure/Motor Protect
Circuit 1
16 Mechanical High Pressure/Motor Protect
Circuit 2
17 Ice Mode Switch UT 0 VAC (Cool) 24 VAC (Ice)
18 Open
NOTES:
1. See Safety Alarms Table for “Phase Voltage Protection”. Units with single point electrical connection
will have one PVM with Inputs 9 and 10 wired together. Units with multiple point connection will
have two PVM’s with Input 9 for Electrical Circuit #1 and Input 10 for Electrical Circuit #2.
C2 0 VAC (Fault) 24 VAC (No Fault)
C2 0 VAC (Fault) 24 VAC (No Fault)
2. See Safety Alarms
Table 14 for “Ground Fault Protection”. Units with single point electrical
connection will have one GFP with Inputs 11 and 12 wired together. Units with multiple point
connection will have two GFP’s with Input 11 for Electrical Circuit #1 and Input 12 for Electrical
Circuit #2.
Table 12, Digital Outputs
No. Description Type Load Output OFF Output ON
1 Alarm C1,C2,UT Alarm Indicator Alarm OFF Alarm ON
2 Evaporator Water Pump UT Pump Contactor Pump OFF Pump ON
3 Condenser Fan #1 C1 Fan Contactor Fan OFF Fan ON
Motor Control Relay #1 =
4
Compr#1
Motor Control Relay #3 =
5
Compr#3
Motor Control Relay #5 =
6
Compr#5
7 Liquid Line #1 C1 Solenoid Cooling OFF Cooling ON
8 Condenser Fan #2 C2 Fan Contactor Fan OFF Fan ON
Motor Control Relay #2 =
9
Compr#2
Motor Control Relay #4 =
10
Compr#4
Motor Control Relay #6 =
11
Compr#6
12 Liquid Line #2 C2 Solenoid Cooling OFF Cooling ON
13 Condenser Fan #3 C1 Fan Contactor Fan OFF Fan ON
14 Hot Gas Bypass #1 C1 Solenoid Cooling OFF Cooling ON
15 Hot Gas Bypass #2 C2 Solenoid Cooling OFF Cooling ON
16 Condenser Fan #4 C2 Fan Contactor Fan OFF Fan ON
Condenser Fan #5 ( on 8
17
Fans Only)
Condenser Fan #6 ( on 8
18
Fans Only)
C1 Starter Compressor OFF Compressor ON
C1 Starter Compressor OFF Compressor ON
C1 Starter Compressor OFF Compressor ON
C2 Starter Compressor OFF Compressor ON
C2 Starter Compressor OFF Compressor ON
C2 Starter Compressor OFF Compressor ON
C1 Fan Contactor Fan OFF Fan ON
C2 Fan Contactor Fan OFF Fan ON
OM AGZ-1 AGZ 026B through 130B 17
Setpoints
The setpoints shown in Table 13 are retained by battery-back-up and remembered
during power off, are factory set to the Default value, and can be adjusted within the
values shown in Range.
The PW (password) column indicates the password. Passwords are as follows:
O = Operator =0100 M = Manager=2001
Table 13, Setpoints
Description Default Range PW
Unit Enable OFF OFF, ON O
Unit Mode COOL COOL, COOL w/Glycol, ICE w/Glycol, TEST O
Control source DIGITAL IN KEYPAD, BAS, DIGITAL INPUT O
Available Modes COOL
Cool LWT O
Ice LWT O
Evap Delta T O
Startup Delta T O
Stop Delta T O
Max Pulldown Rate M
Evap Recirculate Timer 30 15 to 300 sec M
Low Ambient Lockout M
Demand Limit No No,Yes M
* Refrigerant Select None R22, R407c -* Multipoint Power No No,Yes M
Ice Time Delay 12 1 to 23 hrs.
Clear Ice Delay No No, Yes
Protocol Modbus BACnet, LonWorks, Modbus M
Ident number (Modbus only) 001 001-999 M
Baud rate (Modbus only) 9600 1200,2400,4800,9600,19200 M
Compressor
* Number of Compressors 4 4,6 M
Stage Up Delay 240 90 to 480 sec M
Stage Down Delay 30 20 to 60 sec M
Start-Start 15 min 10 to 60 min M
Stop-Start 5 min 3 to 20 min M
Clear Cycle Timers No No,Yes M
Alarms
Low Evap Pressure-Hold, R22 59 psi Glycol =31 to 65 psi Cool=55 to 65 psi M
Low Evap Pressure-Hold,R407c 60 psi Glycol =26 to 75 psi Cool=58 to 75 psi M
Low Evap Pressure-Unload,R22 58 psi Glycol =31 to 65 psi Cool=55 to 65 psi M
Low Evap Pressure-Unload,R407 59 psi Glycol =26 to 75 psi Cool=58 to 75 psi M
High Condenser Stage Down 370 psi 365 to 380 psi M
High Condenser Pressure 385 psi 385 to 390 psi M
Evaporator Water Freeze M
* Phase Voltage Protection No No,Yes M
* Ground Fault Protection No No,Yes M
Evap Flow Proof 3 sec 1 to 10 sec A
Condenser Fans
VFD Enable No No,Yes M
* Number of Fans 4 4,6,8 M
Stage Down 2 Deadband 6 to 10 F M
VFD Max Speed 100% 90 to 110% M
VFD Min Speed 25% 25 to 60% M
Sat Condenser Temp Target 100 M
Forced Fan 1 1 1 to # Fans Per Circuit M
Forced Fan 2 2 1 to # Fans Per Circuit M
Forced Fan 3 3 1 to # Fans Per Circuit M
(*) These items are factory set prior to shipment.
44. 0°F 20.0(40.0) to 60.0 °F
40. 0°F 20.0 to 40.0 °F
10. 0°F 6.0 to 16.0 °F
10.0°F 1.0 to 15.0 °F
0.5°F 0.5 to 3.0°F
1.0°F 0.2 to 5.0 °F
35 °F –2 to 70°F
38.0 °F 18(37) to 42°F
15°F
10°F
10°F
15°F
15°F
10°F
10°F
COOL, COOL w/GLYCOL, COOL/ICE
w/GLYCOL, ICE w/GLYCOL. TEST
15 to 25oF Stage Up 2 Deadband M
10 to 15oF Stage Up 3 Deadband M
10 to 15oF Stage Up 4 Deadband M
15 to 20oF Stage Down 0 Deadband M
10 to 15oF Stage Down 1 Deadband M
6 to 10oF Stage Down 3 Deadband M
90 to 120°F
M
18 AGZ 026B through 130B OM AGZ-1
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.