Installation is to be performed by qualified personnel who are familiar with local codes and regulations.
CAUTION
Sharp edges on unit and coil surfaces are a potential hazard to personal safety. Avoid contact with them.
General Description
McQuay Air-Cooled Water Chillers are complete, selfcontained automatic chiller units designed for outdoor
installation. Every unit is completely assembled, factory wired,
charged, and tested.
The electrical control center includes all equipment protection
and operating controls necessary for dependable automatic
operation.
Additional Manuals
This manual covers the installation, of dual circuit, AGZ-DH
packaged, scroll compressor chillers using R-410A.
Operating and maintenance information is contained in the
operating manual OMM 1087, available at www.mcquay.com.
Inspection
Check all items carefully against the bill of lading. Inspect all
units for damage upon arrival. Report shipping damage and
file a claim with the carrier. Check the unit nameplate before
unloading, making certain it agrees with the power supply
available. McQuay is not responsible for physical damage after
the unit leaves the factory.
Figure 1: Suggested Pushing Arrangment
Figure 2: Required Lifting Arrangement
Handling
Be careful to avoid rough handling of the unit. Do not push or
pull the unit from anything other than the base. Block the
pushing vehicle away from the unit to prevent damage to the
sheet metal cabinet and end frame (see Figure 1).
To lift the unit, 2-1/2" (64mm) diameter lifting eyes are
provided on the base of the unit. Arrange spreader bars and
cables to prevent damage to the condenser coils or cabinet (see
Figure 2).
IM 11003
CAUTION
All lifting locations must be used to prevent damage to unit.
Installation and Application Information
Unit Placement
AGZ units are for outdoor applications and can be mounted
either on a roof or at ground level. For roof mounted
applications, install the unit on a steel channel or I-beam frame
to support the unit above the roof. For ground level
applications, install the unit on a substantial base that will not
settle. Use a one-piece concrete slab with footings extended
below the frost line. Be sure the foundation is level within the
lesser of 0.25” per foot (6mm per 254mm) or 0.5"(13mm) over
its length and width. The foundation must be strong enough to
support the weights listed in the Physical Data Tables
beginning on page 28.
Install the unit on vibration pads, springs or some other devise
to keep the steel rais off the concrete pad if the unit is so
mounted.
Service Clearance
Sides: Minimum of 4 feet (1.22 m)
Control panel end: Minimum of 4 feet
Opposite control panel:
• Minimum 4 feet on models 025 to 130;
• 12 feet on models 140-190 (allows clearance to remove
the evaporator ).
Air Clearance
Sufficient clearance must be maintained between the unit and
adjacent walls or other units to allow the required unit air flow
to reach the coils. Failure to do so will result in a capacity
reduction and an increase in power consumption. No
obstructions are allowed above the unit at any height.
Spacing Requirements
In general, with a small performance penalty in some cases,
AGZ-D units can be spaced at four feet from other units or a
wall. Curves on the following pages give the minimum
clearance for different types of installations and also capacity
reduction and power increase if closer spacing is used.
For convenience, the table below gives the minimum unit
spacing with no performance penalty. Closer spacing will incur
capacity penalties, however, these penalties are quite small and
a unit may still meet the building load requirements.
Wind diretion and velocity can affect recirculation.
Table 1: Minimum Full Capacity Unit Spacing
AGZ-D Unit Size025-070 075-100 110-130 140-180 190
Case
Side Wall (Note 2)
1
4
(1.2)4 (1.2)6(1.8)6 (1.8)7 (2.1)
Case
2 Units, Side-by-Side
2
Case33 or More Units,
Side-by-Side (Note 3)
Case5Pit, No Deeper than
Unit Height (Note 4)
Note 1: Units of Measure: ft (m)
Note 2: For a wall higher than the unit, wall openings or greater distance is
required for full capacity.
Note 3: Use Case 3 table value for inside unit. Use Case 2 value for either
outside unit.
4
(1.2)4 (1.2)6(1.8)6(1.8)14(4.3)
4
(1.2)4 (1.2)8 (2.4)10(3.0)12(3.7)
6
(1.8)8(2.4)8 (2.4)10(3.0)10(3.0)
4IM 1100
Installation and Application Information
Full Load Capacity Reduction (AGZ110-130)
0.0
1.0
2.0
0812162024
Wall Height (ft)
Distance = 4ftDistance = 5ft
Power Increase (AGZ110-130)
0.0
1.0
2.0
0812162024
Wall Height (ft)
% Power Increase
Distance = 4ftDista nce = 5f t
Full Load Capa city Reduction (AGZ140-180)
0.0
1.0
2.0
0812162024
Wa ll Height (ft)
Distance = 4ftDistance = 6f t
Power Increase (AGZ140-180)
0.0
1.0
2.0
0812162024
Wall Height (ft)
% Power Increase
Distance = 4ftDistance = 6ft
Full Load Capacity Reduction (AGZ190)
0.0
1.0
2.0
0812162024
Wall Height (ft)
Dist ance = 4ftDistance = 5ftDistance = 7ft
Power Increase (AGZ190)
0.0
1.0
2.0
3.0
0812162024
Wall Height (ft)
% Power Increase
Distance = 4ftDistance = 5ftDistance = 7ft
Case 1: Wall on One Side
In this case a solid wall up to 24-feet is considered. (For walls
higher than 24 ft, use the 24-foot values.) Also use these charts
for an adjacent building. For perforated screening walls, use
Case 4. Spacing is differentiated by unit size families.
Figure 3: Wall on One Side of Unit
Note: Maintain a minimum of 4-feet on all sides; except models
140-190, which require 12-feet opposite the control
panel to remove the evaporator.
For models AGZ 025-100: use 4 feet from any height wall. For
models 110-190, use Performance Adjustment curves below.
Figure 5: Case 1 Adjustment Factors (AGZ140D-180D)
% Capacity Reduction
Figure 4: Case 1 Adjustment Factors (AGZ110D-130D)
Figure 6: Case 1 Adjustment Factors (AGZ190D)
% Ca pacity Reduction
% Capacity Reduction
IM 11005
Installation and Application Information
Full Load Capacity Reduction
0.0
0.5
1.0
1.5
2.0
2.5
3.0
4568
Distance Betwe en Units (ft)
% Capacity Reduction
AGZ075-100DAGZ110-130DAGZ140-180DAGZ190D
Power Increase
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
4568
Distance Between Units (ft)
% Power Increase
AGZ075-100DAGZ110-130DAGZ140-180D
D
Full Load Capacity Reduction
0
1
2
3
4
5
6
4568
Distance Between Units
% Capacity Reduction
AGZ075-100DAGZ110-130DAGZ 14 0-1 8 0DAGZ190D
Power Incre ase
0
1
2
3
4
5
6
7
8
9
4568
Distance Between Units (ft)
% Power Increase
AGZ075-100DAGZ110-130DAGZ140-180DAGZ190D
Case 2: Two Units, Side-by-Side
Maintain a minimum of 6-feet on all sides; except models 140190, which require 12-feet opposite the control panel to
remove the evaporator.
Figure 7: Case 2 - Two units side by side
For models AGZ 025-100: use 4 feet between units. For
models 110-190, use Performance Adjustment chart in
Figure 8.
Figure 8: Case 2 Adjustment Factors
Case 3: Three or More Units, Side-by-Side
Maintain a minimum of 6-feet on all sides; except models 140190, which require 12-feet opposite the control panel to
remove the evaporator. For more than three units, allow an
additional 2-feet clearance between units.
Figure 9: Case 3 - 3 units side by side
Data is for the middle unit - with a unit on each side. See Case
2, page 6 for Adjustment Factors for the two outside units.
Figure 10: Case 3 Adjustment Factors
6IM 1100
AGZ190
Installation and Application Information
Wall Free Area vs. Distance
0
1
2
3
4
5
6
7
8
0 1020304050
% Open Wall Area
Distance from Wall to Unit (ft)
AGZ025-070AGZ075-130AGZ140-190
Full Load Capacity Reduction (AGZ025-0 70)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0810121314
Depth of Pit (ft)
% Capacity Red uction
Distance = 4 ftDistance = 5 ftDistance = 6 ft
Power Increase (AGZ025-070)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0810121314
Depth of Pit (ft)
% Power Increase
Distance = 4 ftDistance = 5 ftDistance = 6 ft
Case 4: Open Screening Walls
Decorative screening walls are often used to help conceal a
unit either on grade or on a rooftop. Design these walls such
that the combination of their open area and distance from the
unit do not require performance adjustment. It is assumed that
the wall height is equal to or less than the unit height when
mounted on its base support. If the wall height is greater than
the unit height, see Case 5, Pit Installation, page 7. The
distance from the sides of the unit to the side walls must be
sufficient for service, such as opening control panel doors. For
uneven wall spacing, the distance from the unit to each wall
can be averaged providing no distance is less than 4 feet.
Values are based on walls on all four-sides.
Figure 11: Case 4 Adjustment Factor
Case 5: Pit Installation
Pit installations can cause operating problems resulting from
recirculation and restriction, and require care that sufficient air
clearance is provided, safety requirements are met and service
access is provided. Pit covers must have abundant open area at
least equal to the chiller footprint.A solid wall surrounding a
unit is substantially a pit and this data should be used.
Steel grating is sometimes used to cover a pit to prevent
accidental falls or trips into the pit. The grating material and
installation design must be strong enough to prevent such
accidents, yet provide abundant open area to avoid
recirculation problems. Have any pit installation reviewed by
McQuay prior to installation to ensure it has sufficient air-flow
characteristics, and approved by the installation design
engineer avoid risk of accident.
Figure 12: Case 5 - Pit Installation
IM 11007
Figure 13: Case 5 Adjustment Factors (AGZ025D-070D)
Installation and Application Information
Full Load Capacity Reduction (AGZ075-130)
0
1
2
3
4
5
6
0810121314
Depth of Pit (ft)
% Capacity Reduction
Distance = 5 ftDistance = 6 ftDistance = 8 ft
Power Increase (AGZ075-130)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0810121314
Depth of Pit / Wall Heig ht (ft )
% Power In crease
Distance = 5 ftDistance = 6 f tDistance = 8 f t
Full Load Capacity Reduction (AGZ140-190)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0810121314
Depth of Pit (ft)
% Capacity Reduction
Distance = 6 ftDi sta nc e = 8 f tDis tanc e = 10 ft
Power Increase (AGZ140-190)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0810121314
Depth of Pit / Wall Height (ft)
% Power Increase
Distance = 6 ftDistance = 8 ftDistance = 10 ft
Figure 14: Case 5 Adjustment Factors (AGZ075D-130D) Figure 15: Case 5 Adjustment Factors (AGZ140D-190D)
8IM 1100
Installation and Application Information
Chilled Water Piping
Flush the system water piping thoroughly before making
connections to the unit evaporator. Install a 40-mesh strainer in
the inlet pipe to the chiller. Design the water piping so the
chilled water circulating pump discharges into the evaporator
inlet.
Connect the return water line to the evaporator inlet
connection. Connect the supply water line to the evaporator
outlet connection.
Install a flow switch in the horizontal piping of the supply
(evaporator outlet) water line.
Provide drain connections at low points in the system to permit
complete drainage of the system. Locate air vents at the high
points in the system to purge air out of the system. A vent
connection on top of the evaporator vessel allows air to be
purged out of the evaporator. Purge air from the water system
before unit start-up to provide adequate flow through the
evaporator.
Install pressure gauges in the inlet and outlet water lines to the
evaporator. Measure pressure drop through the evaporator and
compare to flow as shown on page 34. Vibration eliminators
are recommended in both the supply and return water lines.
Insulate chilled water piping to reduce heat loss and prevent
condensation. Chillers not running in the winter should have
their water systems thoroughly drained to protect against
freezing. If the chiller operates year-round, or if the system is
not drained for the winter, protect the chilled water piping
exposed to outdoor temperature against freezing. Wrap the
lines with a heater cable and add proper amount of glycol to
the system to further protect the system.
The evaporator flow rates and pressure drops shown on page
page 34 are for full load design purposes. The maximum flow
rate and pressure drop are based on a 6°F temperature drop.
Avoid higher flow rates with resulting lower temperature drops
to prevent potential control problems resulting from very small
control bands and limited start up/shut off temperature
changes.
The thermostat sensor is factory mounted in the leaving water
well. If a field supplied and installed return water sensor is
desired, install the sensor bulb in a field supplied well or strap
to the outside of the water line.
Optional Inlet Strainer
An inlet water strainer kit is available to be field-installed,
sized per Tabl e 2 and with the pressure drop show in
Figure 16. This pressure drop must be accounted for in the
total system pressure drop. The kit consists of:
• (1) Y-type 40% open area strainer with 304 stainless
steel perforated basket, Victaulic pipe connections and
strainer cap
• (1) Extension pipe with (2) Schrader fittings that can be
used for a pressure gauge and thermal dispersion flow
switch. The pipe provides sufficient clearance from the
evaporator for strainer basket removal.
• (1) ½-inch blowdown valve
• (2) Victaulic clamps
The minimum flow and pressure drop is based on a full load
evaporator temperature drop of 16°F. Evaporator flow rates
below the minimum values can result in laminar flow causing
freeze-up problems, scaling and poor control. Flow rates above
the maximum values will result in unacceptable pressure drops
and can cause excessive erosion, potentially leading to failure.
Evaporator Variable Flow
Reducing evaporator flow in proportion to load can reduce
system power consumption. The rate of flow change should be
a maximum of 10 percent of the flow per minute. For example,
if the maximum design flow is 200 gpm and it will be reduced
to a flow of 140 gpm, the change in flow is 60 gpm. Ten
percent of 200 gpm equals 20 gpm change per minute, or a
minimum of three minutes to go from maximum to minimum.
Do not reduce flow lower than the minimum flows listed in the
evaporator pressure drop section, page 45. The water flow
through the vessel must remain between the minimum and
maximum values listed on page 45. If flow drops below the
minimum allowable, large reductions in heat transfer can
occur. If the flow exceeds the maximum rate, excessive
pressure drop and tube erosion can occur.
Figure 18: Typical Piping, Shell and Tube Evaporator (models AGZ140D-190D)
Water Piping
Piping for units with brazed-plate evaporators must have a
drain and vent connection provided in the bottom of the lower
connection pipe and to the top of the upper connection pipe
respectively. These evaporators do not have drain or vent
connections due to their construction.
Local authorities can supply the installer with the proper
building and safety codes required for safe and proper
installation.
Install piping with minimum bends and changes in elevation to
minimize pressure drop. The following issues should be
considered when designing and installing water piping:
1 Vibration eliminators to reduce vibration and noise
transmission to the building.
2 Shutoff valves are required to isolate the unit from the
piping during unit servicing.
10IM 1100
3 Manual or automatic air vent valves at the high points of
the system. Drains must be installed at the lowest points
in the system.
4 Adequate water pressure must be maintained (expansion
tank or regulating valve).
5 Temperature and pressure indicators located at the unit
are required to aid in unit servicing.
6 A 40-mesh strainer or other means of removing foreign
matter from the water before it enters the evaporator
must be installed. The use of a strainer will prolong unit
life and help maintain system performance.
7 Chilled water piping and strainer must be supported
independently from the unit.
Installation and Application Information
8 Models AGZ 025D through 130D require field-installed
drains and vents adjacent to the unit. Their brazed-plate
evaporators are not so equipped.
9 Flush the system water piping thoroughly before making
connections to the unit evaporator. Design the water
piping so the chilled water circulating pump discharges
into the evaporator inlet.
10 The unit's evaporator has a thermostat and heater to
prevent freeze-up down to -20 F ( 29 C). The heating
cable can be wired to a separate 115 V supply circuit. As
shipped from the factory, the heating cable is wired to the
control circuit. All water piping to the unit must also be
protected to prevent freezing.
11 If the unit is used as a replacement chiller, flush the
system thoroughly before unit installation. Regular water
analysis and chemical water treatment for the evaporator
loop is recommended immediately at equipment start-up.
12 The total water volume in the system should be sufficient
to prevent frequent "on-off" cycling. Turnover rate
should not be less than 4 minutes for normal variable
cooling loads.
13 When glycol is added to the water system for freeze
protection, the refrigerant suction pressure will be lower,
cooling performance less, and water side pressure drop
greater. If the percentage of glycol is high, or if
propylene is used instead of ethylene glycol, the added
pressure drop and loss of performance could be
substantial. When Glycol or Ice are selected as Unit
Mode, the MicroTech II control will automatically reset
the available range for the Leaving Water Temperature,
Freezestat and Evaporator Pressure settings.
14 Reset the freezestat setting to 6 degrees F (3.3 degrees C)
below the leaving chilled water setpoint temperature
after the glycol percentage is verified safe for the
application. See the section titled "Glycol Solutions" on
page 14 for additional information concerning glycol.
15 Perform a preliminary leak check before insulating the
piping and filling the system.
16 Piping insulation should include a vapor barrier to
prevent condensation and possible damage to the
building structure.
Water Connections
Bring water piping to the evaporator through the side between
the vertical supports. Provide taps for the connection of
pressure gauges and thermometers in the inlet and outlet lines.
Check the inlet and outlet labels on the unit against the
certified drawings supplied on the job and be sure the water
piping is hooked up correctly. Contact the McQuay sales office
if any discrepancies exist.
System Water Volume Considerations
All chilled water systems need adequate time to recognize a
load change, respond to that load change and stabilize, without
undesirable short cycling of the compressors or loss of control.
In air conditioning systems, the potential for short cycling
usually exists when the building load falls below the minimum
chiller plant capacity or on close-coupled systems with very
small water volumes. Some of the things the designer should
consider when looking at water volume are the minimum
cooling load, the minimum chiller plant capacity during the
low load period and the desired cycle time for the
compressors. Assuming that there are no sudden load changes
and that the chiller plant has reasonable turndown, a rule of
thumb of "gallons of water volume equal to two to three times
the chilled water gpm flow rate" is often used. A storage tank
may have to be added to the system.
BAS should enable chiller only when there is a cooling
demand.
Evaporator Freeze Protection
Evaporator freeze-up can be a concern in the application of aircooled water chillers. To protect against freeze-up, insulation
and electric heaters are furnished with the unit. Models 140
through 190 have immersion heaters with a thermostat; models
025 through 130 have an external plate heater and thermostat.
They protect the evaporator down to -20° F (-29° C) ambient
air temperature. Although the evaporator is equipped with
freeze protection, it does not protect water piping external to
the unit or the evaporator itself if there is a power failure or
heater cable burnout. Consider the following recommendations
for additional protection.
1 If the unit will not be operated during the winter, drain
evaporator and chilled water piping and flush with
glycol. Drain and vent connections are provided on the
evaporator to ease draining.
2 Add a glycol solution to the chilled water system to
provide freeze protection. Freeze point should be
approximately ten degrees (F) below minimum design
ambient temperature.
3 The addition of thermostatically controlled heat and
insulation to exposed piping.
The evaporator heater cable is factory wired to the 115 volt
circuit in the control box. This power should be supplied from
a separate source, but it can be supplied from the control
circuit. Operation of the heaters is automatic through the
ambient sensing thermostat that energizes the evaporator
heaters for protection against freeze-up. Unless the evaporator
is drained in the winter or contains an adequate concentration
of anti-freeze, the disconnect switch to the evaporator heater
must not be open.
Temperature and Water Flow Limitations
Evaporator flow rates below the minimum values can result in
laminar flow causing freeze-up problems, scaling and poor
control. Flow rates above the maximum values will result in
unacceptable pressure drops and can cause excessive erosion,
potentially leading to failure.
IM 110011
Installation and Application Information
Low Ambient Operation
Compressor staging is adaptively determined by system load,
ambient air temperature, and other inputs to the MicroTech III
control. A low ambient option with fan VFD allows operation
down to -10° F (-23° C). The minimum ambient temperature is
based on still conditions where the wind is not greater than
five mph. Greater wind velocities will result in reduced
discharge pressure, increasing the minimum operating ambient
temperature. Field installed hail/wind guards are available to
allow the chiller to operate effectively down to the ambient
temperature for which it was designed.
High Ambient Operation
AGZ-D units for high ambient operation (105ºF to 125 F, 40.1
C to 51.7 C) require the addition of the optional high ambient
package that includes a small fan with a filter in the air intake
to cool the control panel.
All units with the optional VFD low ambient fan control
automatically include the high ambient option.
Flow Switch
All chillers require a chilled water flow switch to check that
there is adequate water flow through the evaporator ant to shut
the unit down if there isn't. McQuay has two options for
meeting this requirement.
1 A factory-mounted thermal dispersion flow switch.
2 A "paddle" type flow switch is available from McQuay
(part number 017503300) for field mounting and wiring.
Certain flow rates are required to open the switch and are
listed in Figure 3. Wire from switch terminals Y and R to
the unit control panel terminals shown on the field
wiring diagrams, page 36 and page 37. Mount the flow
switch in the leaving water line to shut down the unit
when water flow is interrupted. A flow switch is an
equipment protection control and should never be used to
cycle a unit.
Installation should be per manufacturer's instructions included
with the switch . There is also a set of normally closed contacts
on the switch that can be used for an indicator light or an alarm
to indicate when a "no flow" condition exists. Freeze protect
any flow switch that is installed outdoors. .
NOTE: Differential pressure switches are not recommended
for outdoor installation. They can freeze and not indicate a noflow condition
Table 3: Flow Switch Minimum/Maximum Flow Rates
Pipe Size (NOTE !)
Min.
Adjst.
Max.
Adjst.
1 A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.
2 Flow rates for a 2-inch paddle trimmed to fit the pipe.
3 Flow rates for a 3-inch paddle trimmed to fit the pipe.
4 Flow rates for a 3-inch paddle.
5 Flow rates for a 6-inch paddle
Model sizes AGZ 140 and larger have shell-and-tube
evaporators. They are drained of water in the factory and
shipped with evaporator drain plugs removed and stored in the
control panel or with an open ball valve in the drain holes. The
drain is located on the bottom of the vessel. Be sure to replace
plugs or close the valves prior to filling the vessel with fluid.
12IM 1100
Installation and Application Information
Glycol Solutions
The use of a glycol/water mixture in the evaporator to prevent
freezing will reduce system capacity and efficiency, as well as
increase pressure drop. The system capacity, required glycol
solution flow rate, and pressure drop with glycol may be
calculated using the following formulas and tables.
1 Capacity - Multiply the capacity based on water by the
Capacity correction factor from Tabl e 4or Table 5.
2 Flow - Multiply the water evaporator flow by the Flow
correction factor fromTabl e 4 or Table 5 to determine
the increased evaporator flow due to glycol. If the flow is
unknown, it can be calculated from the following
equation:
For Metric Applications - Use the following equation for
metric applications:
3 Pressure drop - Multiply the water pressure drop from
Table 20, page 34 by Pressure Drop correction factor
from Tabl e 4 or Table 5 . High concentrations of
propylene glycol at low temperatures may cause
unacceptably high pressure drops.
4 Power - Multiply the water system power by Power
correction factor from Tabl e 4 or Table 5.
Test coolant with a clean, accurate glycol solution hydrometer
(similar to that found in service stations) or refractto determine
the freezing point. Obtain percent glycol from the freezing
point table below. It is recommended that a minimum of 25%
solution by weight be used for protection against corrosion or
that additional compatible inhibitors be added. Concentrations
above 35% do not provide any additional burst protection and
should be carefully considered before using.
CAUTION
Do not use an automotive-grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors
which will cause plating on the copper tubes within the chiller evaporator. The type and handling of glycol used must be
Maximum standby ambient temperature130°F (55°C)
Maximum operating ambient temperature105°F (40°C)
-with optional high ambient package (see information under High Ambient Operation‚ page 12125°F (52°C)
Minimum operating ambient temperature (standard control)35°F (2°C)
Minimum operating ambient temperature (with optional low-ambient control)-10°F (-23°C)
Leaving chilled water temperature40°F to 60°F (2°C to 16°C)
Leaving chilled fluid temperatures (with anti-freeze) - Unloading is not permitted with fluid leaving
temperatures below 25°F (-4°C). When ambient air temperature is above 100º F, minimum leaving
chilled fluid temperature (with antifreeze) is 25°F (4°C)
Operating chilled water delta-T range6 to 16°F (-14 to -9°C)
Maximum evaporator operating inlet fluid temperature76°F (24°C)
Maximum evaporator non-operating inlet fluid temperature100°F (38°C)
15°F to 60°F (-9°C to 16°C)
Vibration and Sound Isolation
Vibration isolators are recommended for all roof-mounted
installations or wherever vibration transmission is a
IM 110013
Installation and Application Information
consideration. The tables beginning page 23list isolator loads
for all unit sizes. Isolators are also recommended for slab
installations, primarily to keep the unit base from resting its
entire length directly on the slab.
Spring Isolator Installation
The unit should be initially installed on shims or blocks at the
listed free height. When all piping, wiring, flushing, charging,
etc. is completed, adjust the springs upward to load them and
to provide clearance to remove the shims or blocks.
Installation of spring isolators requires flexible piping
connections and at least three feet of conduit flex tie-ins.
Piping and conduit must be supported independently of the
unit.
Sound Isolation
The low sound level of the AGZ chiller is suitable for most
applications. When additional sound reduction is necessary,
locate the unit away from sound sensitive areas. Avoid
locations beneath windows or between structures where
normal operating sounds may be objectionable.
Reduce structurally transmitted sound by isolating water lines,
electrical conduit and the unit itself. Use wall sleeves and
rubber isolated piping hangers to reduce transmission of water
or pump noise into occupied spaces. Spring isolators are
effective in reducing the low amplitude sound generated by
scroll compressors and for unit isolation in sound sensitive
areas.
Compressor sound blankets are available as a factory or field
installed option. They will reduce sound levels by two or three
dB depending on unit size.
14IM 1100
Dimensions
Figure 19: AGZ025DH - 035DH (Packaged)
Dimensions
IM 110015
Dimensions
Figure 20: AGZ040DH - 070DH (Packaged)
16IM 1100
Figure 21: AGZ075DH - 100DH (Packaged)
Dimensions
IM 110017
Dimensions
Figure 22: AGZ110DH - 130DH 208/230 volt models (460/575 next page)