Mayser SG RSV 2X9 User Manual

Page 1/6
Control Unit SG-RSV 2X9 Operating Instructions
Control Unit
in accordance with EN 50155 and EN 50121-3-2 class S2 in accordance with EN 50155 EN 954 Category 2 EN 50129 SIL1
for sensors with monitoring resistor 1k2
These operating instruction apply to the following control units:
1004156 SG-RSV 209 2s 24 V = 1004155 SG-RSV 209 8s 24 V = 1004093 SG-RSV 209 12s 24 V = 1004764 SG-RSV 219 2s 110 V = 1004765 SG-RSV 219 8s 110 V = 1004091 SG-RSV 219 12s 110 V =
Relay “fault”
Relay
“activated”
Relay
“monitoring loop”
Sensor 1 Sensor 2
Control system
The Control Unit has two monitoring circuits which operate the output relays. The electronics monitor the electrical resistance of the connected sensors which have a dened zero signal current. When the sensors are not activated (normal operating conditions), the out­put relays are energised. If a break occurs in the supply line bet­ween the sensor and the control unit, the relays “fault” and “monitoring loop” are deactivated. Depending on the internal train signals and the sensors, the relays “activated” and “monitoring loop” are deactivated.
Enclosure
W × H × D (mm) 45 × 75 × 108 Protection class IP20 Plug connection 2× 8-pin Cable clamps max. 2.5 mm Weight approx. 195 g
2
Parts supplied
Version 5
Mayser Polymer Electric Postfach 30 48 89020 Ulm GERMANY Tel. +49 731 2061-0 Fax +49 731 2061-222
250609 v2.5
- Control Unit
Enclosure with electronics module and plug connections with lift-up lock release.
- Operating Instructions
Mayser Polymer Electric Postfach 30 48 89020 Ulm GERMANY Tel. +49 731 2061-0 Fax +49 731 2061-222
250609 v2.5
Page 2/6
Control Unit SG-RSV 2X9
IMPORTANT NOTES! Please read!
To ensure correct and safe operation of the unit, it must be properly trans­ported and stored, properly installed and commissioned, and operated in accordance with its intended use. Only persons familiar with the instal­lation, commissioning and operation, and with the corresponding qualica­tions to prove their skills, may work on the units. They must observe the contents of these instructions, the information given on the type plate of the unit and the relevant safety regula­tions for the installation and operation of electrical systems.
This unit is designed and tested in accordance with EN 50155 and EN 50121-3-2 and left the factory in a perfectly safe condition. To maintain this condition, you must observe the safety regulations marked WARNING! in these operating instructions. Failure to observe the safety regulations can lead to death, injury to personnel, or damage to the unit and other systems and equipment. Should the information given in these operating instructions be inadequate in any way, please contact your local technical centre, subsidiary or represen­tative.
Technical Data
Connecting voltage US
SG-RSV 209 DC 24 V (S2) SG-RSV 219 DC 110 V (S2) SG-RSV 279 DC 72 V (S2) Voltage tolerance -30% to +30% Nominal frequency ­Frequency tolerance ­Power consumption < 3 W
Times
Follow-through time tN 200 ms Extension time tD 0.1 to 2.5 s factory setting: 200 ms Active time tA 2 to 15 s factory setting: 2 s, 8 s or 12 s
Sensor voltage
max. DC 12 V
When using the device outside the European Union, you must observe the relevant regulations valid for the country of use.
Important notes:
- Supply voltage
must correspond to the connecting voltage Us on the type plate.
- Permissible temperature range
When installing in switch cabinet, maintain sufcient distance from heat sources (min. 2 cm).
- Fusing of the relay contacts
due to risk of welding, externally with
1.0 A inert.
Switching thresholds at +23 °C Y1 / Y2 Y3 / Y4
activated < 430 Ohm < 430 Ohm cable break > 2k5 >2k5
Status sensor voltage
Relay data AC 12 DC 12
Switching current max. 1 A max. 1 A Switching voltage max. AC 250 V max. DC 150 V Breaking capacity max. 250 W max. 30 W (AC 12) (DC 12) Switching operations
mechanical > 2× 10 electrical > 1× 105 (AC 250 V / 1 A)
Operating conditions
Perm. ambient temperature -30 °C to +70 °C Rel. humidity max. 95% Vibration fatigue limit
Frequency range 5 to 150 Hz Excursion amplitude ± 2 mm Acceleration amplitude 5 g in all 3 levels
max. U
s
7
Note:
When switching inductive loads the user must be tted out with spark absorbers.