DUCT AVERAGING TEMPERATURE SENSORS
For Additional Information See TE-705 Data Sheet
RoHS
Model TE-705
Technical Information
TI.705-03
SPECIFICATIONS
Platinum RTD Sensors:
±0.1% @ 32°F (0°C), Alpha: 385 per DIN 43760
Nickel RTD Sensors (#2):
±0.5°C @ 0°C (32°F), 5,000 PPM/K T.C.R.
Nickel RTD Sensors (#4):
±0.5°F @ 70°F (21.1°C), 6,000 PPM/K T.C.R.
Balco RTD Sensors:
±0.5°F @ 70°F (21.1°C), 4,300 PPM/K T.C.R.
±0.2°C interchangeability @ 77°F (25°C)
Operating Temperature:
-40°F to 210°F (-40°C to 100°C)
Probe Material:
3/8" (9 mm) Bendable aluminum
Flange Material:
Galvanized Steel
Steel NEMA-1 (IP-30):
18 Ga. Galvanized Steel
ORDERING INFORMATION: TE-705-
INSTALLATION TEMP SENSOR
B Galvanized Steel Enclosure (NEMA-1 / IP-30)
C Painted Steel Enclosure (NEMA-4 / IP-65)
1 100-Ohm Platinum RTD
2 1,000-Ohm Nickel RTD
(5,000 PPM)
3 1,000-Ohm Platinum RTD
4 1,000-Ohm Nickel RTD
(6,000 PPM)
5 1,000-Ohm Balco RTD
7 10,000-Ohm NTC Thermistor
(Type III)
8 10,000-Ohm NTC Thermistor (Carel)
10 3,000-Ohm NTC Thermistor
12 10,000-Ohm NTC Thermistor
(Type II)
13 5,000-Ohm NTC Thermistor
14 1,035-Ohm Silicon PTC
15 100,000-Ohm NTC Thermistor
16 10,000 ohm NTC Thermistor
..........(Eliwell)
17 20,000-Ohm NTC Thermistor
18 2,252-Ohm NTC Thermistor
21 1,800-Ohm NTC Thermistor
PROBE
LENGTH
A 6 ft (1.8 m)
B 12 ft (3.6 m)
C 24 ft (7.2 m)
PROBE
TYPE
1 Bendable 3/8" Aluminum
Steel NEMA-4 (IP-65):
18 Ga. Cold Rolled Steel, Powder coated
Warranty:
Five Years (Lifetime on Moisture Migration)
EMC Conformance: EN 55022, 55024, 61000-3-3, 61000-4-2, 3, 4, 5, 6 & 11
U.S. PATENT NO. 6592254, 7465087
Example: TE-705-B-10-B-1: Duct Averaging Temp Sensor, NEMA-1 enclosure, 12 ft. bendable 3/8" aluminum, 3,000 ohm NTC thermistor.
For Resistance vs. Temperature tables, please refer to TI.700-11.
INSTALLATION
Inspection
Requirements
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
Appropriate accessories
Two #8 self-tapping mounting screws (not provided)
Training: Installer must be a qualified, experienced technician.
Page 2
Page 2 of 2
RoHS
Model TE-705
Technical Information
TI.705-03
DUCT AVERAGING TEMPERATURE SENSORS
Mounting
Location: Install the sensor in a location where it will sample the average duct air temperature. Avoid areas where the air is stratified because these areas can cause sensing errors.
TE-705: Refer to Figure 2 for mounting dimensions.
1. Drill a 7/16-inch (11 mm) hole into the duct where the sensor will be installed.
2. Gently uncoil the sensor’s rigid probe and insert it into the duct.
3. Use the flange as a template to mark and drill two holes for the #8 self-tapping sheet metal screws (not provided).
4. Fasten the sensor to the duct with the sheet metal screws. Refer to Figure 1.
Probe
Two #8 self-tapping
screws (not included)
1/2" knockout
DIMENSIONAL DATA
Figure 2 - TE-705 Duct Averaging Temperature Sensor dimensions shown in inches and millimeters (mm).
2.00"
(51 mm)
1/2" knockout
4.00" (102 mm)
System duct
or plenum
Figure 1 - Installing the TE-705 Sensor
CHECKOUT
Allow the sensor to stabilize in the duct air stream for a minimum of five minutes before taking a resistance measurement.
1. Disconnect the sensor lead wires from the controller.
2. Connect an ohmmeter across the lead wires.
3. Ensure that nominal resistance measurements are in accordance with the resistance/temperature curves. (Refer to Tables 1 & 2. For complete Resistance vs. Temperature tables, please refer to TI.700-11 - Temperature Sensor section.)
4. Reconnect sensor lead wires to the controller.
5. Check operation of the complete control system.
MAINTENANCE
FIELD REPAIR
Regular maintenance of the total system is recommended to assure sustained optimum performance.
None. Replace with a functional unit.
1/2" NPT fitting
2.50"
(64 mm)
For Technical / Application Assistance call your nearest office
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com • www.mamacsys.com
EUROPE
4200 Waterside Centre
Solihull Parkway
Birmingham • West Midlands
B37 7YN • United Kingdom
01384-271113 • Fax 01384-271114
ASIA
1 Fullerton Road #02-01
One Fullerton
Singapore • 049213
65-31581826 • Fax 65-31581826
MAMAC Systems, Inc., reserves the right to change any specifications
without notice to improve performance, reliability, or function of our products.
905-474-9215 • Fax 905-474-0876
08-8395-4333 • Fax 08-8395-4433
CANADA
675 Cochrane Drive
East Tower • 6th Floor
Toronto • Ontario
L3R 0B8 • Canada
AUSTRALIA
4 Armiger Court, Unit 2
Adelaide • S.A.
5088 • Australia
TI.705-03
Loading...