8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com • www.mamacsys.com
For Additional Information See PR-274/275 Data Sheet
SPECIFICATIONS
Accuracy*: ±1% FS
Overpressure: 10 PSID
Supply Voltage: 12-40 VDC
12-35 VAC (VDC output units only)
Supply Current: VDC Units - 10 mA max.
mA Units - 20 mA max.
Enclosure: 18 Ga C. R. Steel NEMA 4 (IP-65) or Panel Mount Chassis
Finish: Baked on enamel-PMS2GR88B
EMC Conformance: EN 55022, 55024, 61000-3-3,
61000-4-2, 3, 4, 5, 6 & 11
Compensated Temp Range: 25°F-150°F (-4°C-65°C)
T. C. Error: ±0.0125%/°F (.02%/°C)
Operating Temp Range: 0°F-175°F (-18°C-80°C)
Media Compatibility: Clean dry air or any inert gas
Environmental: 10-90%RH Non-Condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga max.
Load Impedance: 1.6K ohms max. at 40 VDC (mA output units)
1K ohms min. (VDC output units)
Weight: Enclosure - 1.0 lbs. (.45 kg)
Panel Mount - 0.5 lbs. (.25 kg)
ORDERING INFORMATION
PACKAGINGRANGEOUTPUT
274 (enclosure)
275 (panel mount)
R1
0 TO 0.10 / -0.05 TO +0.05
("wc)
R2
0 TO 1.0 / 0 TO 0.5 / 0 TO 0.25 /
("wc)
-0.5 TO +0.5 / -0.25 TO +0.25 /
-0.125 TO +0.125
R3
0 TO 5.0 / 0 TO 2.5 / 0 TO 1.25 /
("wc)
-2.5 TO +2.5 / -1.25 TO +1.25 /
-0.625 TO +0.625
0 TO 30 / 0 TO 15 / 0 TO 7.5 /
R4
-15.0 TO +15.0 / -7.5 TO +7.5 /
("wc)
-3.75 TO + 3.75
0 TO 25 / -12.5 TO +12.5
R5
(pa)
0 TO 250 / 0 TO 125 / 0 TO 62.5 /
R6
-125 TO +125 / -62.5 TO +62.5 /
(pa)
-31.25 TO +31.25
0 TO 1250 / 0 TO 625 / 0 TO 312.5 /
R7
-625 TO +625 / -312.5 TO +312.5 /
(pa)
-156.25 TO +156.25
0 TO 7500 / 0 TO 3750 / 0 TO 1875 /
R8
-3750 TO +3750 / -1875 TO +1875 /
(pa)
-937.5 TO +937.5
mA
(4-20 mA
2-wire)
VDC
(0-5 VDC or
0-10 VDC field
selectable)
INSTALLATION
Inspection - Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the package and
inspect the device for obvious damage. Return damaged products.
RoHS
Requirements
Mounting
Wiring
Model PR-274/275
Technical Information
TI.274/275-06
LOW PRESSURE SENSOR
Enclosure Mount
Transducer
• Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
• Appropriate accessories
• Two #8 self-tapping mounting screws (not provided)
• Training: Installer must be a qualified, experienced technician
Warning:
• Disconnect power supply before installation to prevent electrical
shock and equipment damage.
• Make all connections in accordance with the job wiring diagram
and in accordance with national and local electrical codes. Use
copper conductors only.
Caution:
• Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
• Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMA Type 4 housings
are intended for outdoor use primarily to provide a degree of
protection against wind-blown dust, rain, and hose-directed water.
• Do not exceed ratings of the device.
Caution:
• Condensate or moisture must not enter pressure sensor ports
The PR-274/275 must be mounted as indicated by the arrows on
the enclosure. Refer to Figure 7 for mounting dimensions.
1. Remove the transducer cover using a Phillips head
screwdriver.
2. Select the mounting location.
3. Mount transducer on a vertical surface with two #8
self-tapping screws (not provided).
4. Transducer must be mounted above the pressure pick-up or a
J-Loop must be incorporated in the tubing to function as a
condensate trap.
5. Pull wires through bottom of enclosure and make
necessary connections.
6. Replace cover and make pneumatic connections.
Use maximum 12 AWG wire for wiring terminals. Use flexible 1/4"
O.D. 5/32" I.D. tubing for the high and low pressure connections.
Refer to Figures 1, 2, 3, & 4 for wiring information and Figures 5 &
6 for switch designations.
(Wiring Instructions continued on pages 2 and 3.)
Panel Mount
Transducer
Page 2
Page 2 of 4
Model PR-274/275
Technical Information
TI.274/275-06
RoHS
Wiring PR-274/275 Units with mA Output
PR-274/275 Low Pressure Transducer with mA Output
Zb
Zu
S
Zb
Zu
S
PR-274/275 pressure transducers with 4-20 mA output are powered with a
12-40 VDC supply.
The following describes the proper wiring of these pressure transducers with
mA output:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+] and [-] terminal markings on the board.
3. Attach the supply voltage to the [+] lead.
4. Connect the 4-20 mA output ([-] terminal) to the controller’s input terminal.
5. Ensure that the power supply common is attached to the common bus of the
controller.
6. Re-insert the terminal block to the circuit board and apply power to the unit.
7. Check for the appropriate output signal using a DVM set on DC milliamps
connected in series with the [-] terminal.
Zb
MAMAC 9280
High
S1 S2
ON
ON
Zu
S
Zb
Low
MAMAC9280
High
S1 S2
ON
ON
Zu
S
Low
LOW PRESSURE SENSOR
Wiring PR-274/275 Units with VDC Output
PR-274/275 Low Pressure Transducer with VDC Output
S3
Zb
Zu
S
Zb
Zu
ON
+
0
S1
ON
Zb
S2
ON
Zu
S
S3
+
0
S1
ON
S2
ON
Zu
S
High
Low
ON
Zb
S
PR-274/275 pressure transducers with VDC output are field selectable 0-5 VDC
or 0-10 VDC output and can be powered with either a 12-40 VDC or 12-35 VAC.
The following describes the proper wiring of these pressure transducers with
VDC output:
1. Remove the terminal block by carefully pulling it off the circuit board.
2. Locate the [+], [-] and [O] terminal markings on the board.
3. Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the
negative terminal.
4. Connect the [O] terminal, which is the positive VDC output terminal, to the
controller’s input terminal.
5. Re-insert the terminal block to the circuit board and apply power to the unit.
6. Check the appropriate VDC output using a voltmeter set on DC volts across
the [O] and [-] terminals.
MAMAC 9280
MAMAC9280
High
Low
TYPICAL APPLICATIONS (wiring diagrams)
Figure 1 and Figure 2 illustrate typical wiring diagrams for the mA output low
pressure transducer.
Figure 1 - Wiring for mA Low Pressure Transducers with an External DC Power
Supply
mA Output Transducer Only12-40 VDC Power Supply
+
Figure 2 - Wiring for mA Output Transducers where the Controller or Meter has an
Internal DC Power Supply
mA Output Transducer Only
+
Caution: If you are using grounded AC, the hot wire must be on the [+] terminal. Also, if you are using a controller without built-in isolation, use an isolation transformer to supply the PR-274/275.
Caution: This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave rectifier power supplies.
Caution: When multiple PR-274/275 units are powered from the same transformer, damage will result unless all 24G power leads are connected to the same power lead on all devices. It is
mandatory that correct phasing be maintained when powering more than one device from a single transducer.
+
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
TYPICAL APPLICATIONS (wiring diagrams)
Figure 3 and Figure 4 illustrate typical wiring diagrams for the VDC output low
pressure transducer.
Figure 3 - Wiring for VDC Low Pressure Transducers When Applied with External
AC Supply
VDC Output Transducer Only12-35 VAC Transformer
Figure 4 - Wiring for VDC Low Pressure Transducers When Applied with External
DC Power Supply
VDC Output Transducer Only12-40 VDC Power Supply
Supply
Common
Signal
Supply
Common
Signal
Hot
+
O
+
O
+
Neutral
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
+
Controller / Meter / Recorder
Input Signal
+
Common
Shield/Ground
Page 3
Page 3 of 4
S1
S3
+ 0
Model PR-274/275
Technical Information
TI.274/275-06
RoHS
Figure 5 - Switch Selections for Low Pressure Transducers with mA Outputs
Zb
+ -
Range Configuration:
R1/R5 0 - 0.10 "wc / 25 pa
R2/R6 0 - 1.0 "wc / 250 pa (default)
R3/R7 0 - 5.0 "wc / 1250 pa (default)
R4/R8 0 - 30.0 "wc / 7500 pa (default)
ON
ON
1
2
1
2
S2
Zu S
S1
Uni-Directional
0 - 0.5 "wc / 125 pa
0 - 0.25 "wc / 62.5 pa
0 - 2.5 "wc / 625 pa
0 - 1.25 "wc / 312.5 pa
0 - 15.0 "wc / 3750 pa
0 - 7.5 "wc / 1875 pa
mA Output
Switch 1 (S1)
Factory
Sealed
O N
1
2
O N
1
2
O N
2
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
LOW PRESSURE SENSOR
Range Configuration:
R1/R5 +/- 0.05 "wc / 12.5 pa
R2/R6 +/- 0.5 "wc / 125 pa (default)
+/- 0.25 "wc / 62.5 pa
+/- 0.125 "wc / 31.25 pa
R3/R7 +/- 2.5 "wc / 625 pa (default)
+/- 1.25 "wc / 312.5 pa
+/- .625 "wc / 156.25 pa
R4/R8 +/- 15.0 "wc / 3750 pa (default)
+/- 7.5 "wc / 1875 pa
+/- 3.75 "wc / 937.5 pa
Output Configuration:
Uni-directional (default)
Bi-directional
Bi-Directional
Switch 1 (S1)
Factory
Sealed
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
Switch 2 (S2)
O N
1
2
O N
1
2
Figure 6 - Switch Selections for Low Pressure Transducers with VDC Outputs
ON
1
2
S3
+ - 0
Range Configuration:
R1/R5 0 - 0.10 "wc / 25 pa
R2/R6 0 - 1.0 "wc / 250 pa (default)
0 - 0.5 "wc / 125 pa
0 - 0.25 "wc / 62.5 pa
R3/R7 0 - 5.0 "wc / 1250 pa (default)
0 - 2.5 "wc / 625 pa
0 - 1.25 "wc / 312.5 pa
R4/R8 0 - 30.0 "wc / 7500 pa (default)
0 - 15.0 "wc / 3750 pa
0 - 7.5 "wc / 1875 pa
Output Configuration:
Uni-directional (default)
Bi-directional
S1
Zb
ON
ON
1
2
1
2
Zu S
S2
Uni-Directional
VDC Output
Switch 1 (S1)
Factory
Sealed
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
Switch 2 (S2)
O N
1
2
O N
1
2
Range Configuration:
Bi-Directional
R1/R5 +/- 0.05 "wc / 12.5 pa
R2/R6 +/- 0.5 "wc / 125 pa (default)
+/- 0.25 "wc / 62.5 pa
+/- 0.125 "wc / 31.25 pa
R3/R7 +/- 2.5 "wc / 625 pa (default)
+/- 1.25 "wc / 312.5 pa
+/- .625 "wc / 156.25 pa
R4/R8 +/- 15.0 "wc / 3750 pa (default)
+/- 7.5 "wc / 1875 pa
+/- 3.75 "wc / 937.5 pa
Output Configuration:
0 - 10 (default)
0 - 5 VDC
Switch 1 (S1)
Factory
Sealed
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
O N
1
2
Switch 3 (S3)
O N
1
2
O N
1
2
Page 4
Page 4 of 4
Model PR-274/275
Technical Information
TI.274/275-06
RoHS
CHECKOUT
Transducer
Operation
CALIBRATION
1. Verify that the unit is mounted in the correct position.
2. Verify appropriate input signal and supply voltage.
Caution: Never connect 120 VAC to these transducers. Never
connect AC voltage to a unit intended for DC supply.
3. Verify appropriate configuration range.
This is a rough functional check only.
1. Adjust the pressure to obtain maximum output signal for
appropriate range.
2. Output should be 20 mA or 5 or 10 VDC.
3. Adjust the pressure to obtain minimum output signal.
4. Output should be 4 mA or 0 VDC.
NOTE: The PR-274/275 is a highly accurate device. For
applications requiring a high degree of accuracy, the use of
laboratory quality meters and gauges are recommended.
All units are factory calibrated to meet or exceed published
specifications. If field adjustment is necessary, follow the
instructions below.
1. Connect terminals [+] and [-] to the appropriate power
source.
2. Connect the DVM in series on the [-] terminal.
3. Apply low pressure to the unit. If configured for
uni-direction, adjust Zu trimmer to achieve desired low
output. If configured for bi-direction, adjust Zb trimmer to
achieve desired low output.
4. Apply high pressure to the unit and adjust span trimmer [S]
to obtain the desired high output pressure.
5. Repeat steps 3 and 4 until desired calibration is achieved.
Calibration of PR-274/275 VDC Units
1. Connect terminals [+] and [-] to the appropriate power
source. The [-] terminal is also the negative output terminal.
2. Connect the DVM on DC volts across [O] and [-] terminal.
3. Apply low pressure to the unit. If configured for
uni-direction, adjust Zu trimmer to achieve desired low
output. If configured for bi-direction, adjust Zb trimmer to
achieve desired low output.
4. Apply high pressure to the unit and adjust span trimmer [S]
to obtain the desired high output pressure.
5. Repeat steps 3 and 4 until desired calibration is achieved.
Regular maintenance of the total system is recommended to
assure sustained optimum performance.
None. Replace with a functional unit.
See Data Sheet for additional information.
3.25"
(83 mm)
2.50"
63.5 mm)
(
3.00" (76 mm)3.00" (76 mm)
4.00"
(102 mm)
For Technical / Application Assistance call your nearest office
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
sales@mamacsys.com • www.mamacsys.com
EUROPE
4200 Waterside Centre
Solihull Parkway
Birmingham • West Midlands
B37 7YN • United Kingdom
01384-271113 • Fax 01384-271114
ASIA
1 Fullerton Road #02-01
One Fullerton
Singapore • 049213
65-31581826 • Fax 65-31581826
905-474-9215 • Fax 905-474-0876
08-8395-4333 • Fax 08-8395-4433
CANADA
675 Cochrane Drive
East Tower • 6th Floor
Toronto • Ontario
L3R 0B8 • Canada
AUSTRALIA
4 Armiger Court, Unit 2
Adelaide • S.A.
5088 • Australia
MAMAC Systems, Inc., reserves the right to change any specifications
without notice to improve performance, reliability, or function of our products.
TI.274/275-06
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.