WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death or
property damage.
• Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
• Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual.
For assistance or additional information consult
a qualified installer, service agency or the
gas supplier.
This appliance may be installed in an aftermarket,*
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is for use only with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
AFETYBARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for
future reference.
20306750 12/14 Rev. 1
Page 2
Designer Series Direct Vent Gas Fireplace
CONTENTS
Thank you and congratulations on your purchase of an
Vermont Castings Group Fireplace.
PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIONS BEFORE USING THE APPLIANCE!
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible re hazard and will void the warranty.
Important Safety Information .....................................3
Please leave these instructions with the appliance.
OWNER
Please retain these instructions for future reference
• Read this owner’s manual carefully and completely before trying to assemble, operate, or service this
replace.
• Any change to this replace or its controls can be dangerous.
• Improper installation or use of this replace can cause serious injury or death from re, burns,
explosions, electrical shock and carbon monoxide poisoning.
WARNING
This replace is a vented product. This replace must be
properly installed by a qualied service person. The glass
door must be properly seated and sealed. If this unit is not
properly installed by a qualied service person with glass
door properly seated and sealed, combustion leakage can
occur.
CARBON MONOXIDE POISONING: Early signs of carbon
monoxide poisoning are similar to the u with headaches,
dizziness and/or nausea. If you have these signs, the re-
place may not have been installed properly. Get fresh air
at once! Have the replace inspected and serviced by a
qualied service person. Some people are more affected
by carbon monoxide than others. These include pregnant
women, people with heart or lung disease or anemia,
those under the inuence of alcohol, and those at high
altitudes.
Propane/LP gas and natural gas are both odorless. An
odor-making agent is added to each of these gases. The
odor helps you detect a gas leak. However, the odor added
to these gases can fade. Gas may be present even though
no odor exists.
Make certain you read and understand all warnings. Keep
this manual for reference. It is your guide to safe and proper
operation of this replace.
1. This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases unless a certied
kit is used.
2. For propane/LP replace, do not place propane/LP
supply tank(s) inside any structure. Locate propane/LP
supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100
lbs. capacity.
3. If you smell gas
•shut off gas supply.
•do not try to light any appliance.
• do not touch any electrical switch; do not use any
phone in your building .
• immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
4. Never install the replace
• in a recreational vehicle
• where curtains, furniture, clothing, or other am-
mable objects are less than 42" from the front, top,
or sides of the replace
• in high trafc areas
• in windy or drafty areas
5. This replace reaches high temperatures. Keep children
and adults away from hot surfaces to avoid burns or
clothing ignition. Fireplace will remain hot for a time after
shutdown. Allow surfaces to cool before touching.
6. Young children should be carefully supervised when
they are in the same room as the appliance. Toddlers,
young children and others may be susceptible to accidental contact burns. A physical barrier is recommended
if there are at risk individuals in the house. To restrict
access to a replace or stove, install an adjustable
safety gate to keep toddlers, young children and other
at risk individuals out of the room and away from hot
surfaces.
7. Do not modify replace under any circumstances. Any
parts removed for servicing must be replaced prior to
operating replace.
8. Turn replace off and let cool before servicing, installing, or repairing. Only a qualied service person should
install, service, or repair the replace. Have burner
system inspected annually by a qualified service
person.
9. You must keep control compartments, burners, and
circulating air passages clean. More frequent cleaning
may be needed due to excessive lint and dust. Turn off
the gas valve and pilot light before cleaning replace.
10. Have venting system inspected annually by a qualied
service person. If needed, have venting system cleaned
or repaired. Refer to Cleaning and Maintenance, Page
48.
11. Keep the area around your replace clear of combustible materials, gasoline, and other ammable vapor and
liquids. Do not run replace where these are used or
stored. Do not place items such as clothing or decora-
tions on or around replace.
.
20306750
3
Page 4
Designer Series Direct Vent Gas Fireplace
IMPORTANT SAFETY INFORMATION
12. Do not use this replace to cook food or burn paper or
other objects.
13. Never place anything on top of replace.
14. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type
indicated on rating plate.
15. This appliance, when installed, must be electrically
grounded in accordance with local codes or in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or the Canadian Electrical Code,
CSA C22.1.
16. Do not obstruct the ow of combustion and ventilation
air in any way. Provide adequate clearances around
air openings into the combustion chamber along with
adequate accessibility clearance for servicing and
proper operation.
17. When the appliance is installed directly on carpeting,
tile or other combustible material other than wood ooring, you must set appliance on a metal or wood panel
or hearth pad extending the full width and depth of the
appliance.
18. Do not use replace if any part has been exposed to
or has been under water. Immediately call a qualied
service technician to inspect the appliance and replace
any part of the control system and any gas control which
as been submerged in water.
19. Do not operate replace if any log is broken.
20. Do not use a blower insert, heat exchanger insert, or
any other accessory not approved for use with this
replace.
21. Do not operate the replace with glass door removed,
cracked, or broken.
CODE APPROVAL
Direct Vent type appliances draw all combustion air from
outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to
comply with the established standards for DIRECT VENT
GAS FIREPLACE HEATERS in the USA and Canada as
follows:
LISTED VENTED GAS FIREPLACE HEATER
TESTED TO:
ANSI Z21.88-2014 / CSA 2.33-2014 STANDARDS
A manufactured home (USA only) or mobile home OEM
installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part
3280, or when such a standard is not applicable, the
Standard for Manufactured Home Installations, ANSI/
NCSBCS A225.1, or Standard for Gas Equipped Recre-
ational Vehicles and Mobile Housing, CSA Z240.4.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is normal for replaces fabricated of steel to
give off some expansion and/or contraction noises
during the start up or cool down cycle. Similar
noises are found with your furnace heat exchanger
or car engine.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is not unusual for gas replace to give off some
odor the rst time it is burned. This is due to the
manufacturing process.
Please ensure that your room is well ventilated
during burn off — open all windows.
It is recommended that you burn your replace for
at least ten (10) hours the rst time you use it. Place
the fan switch in the “OFF” position during this time.
Never connect unit to private (non-utility)
gas wells. This gas is commonly known
as wellhead gas.
WARNING
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
4
20306750
Page 5
INSTALLATION INFORMATION
Designer Series Direct Vent Gas Fireplace
PRODUCT SPECIFICATIONS
This appliance has been certied for use with either
•
natural or propane gas. See appropriate data plates.
• This appliance is not for use with solid fuels.
• The appliance is approved for bedroom or bedsitting
room installations.
• The appliance must be installed in accordance with local
codes if any. If none exist use the current installation
code. ANSI Z223.1/NFPA 54 in the USA, CSA B149 in
Canada.
• This appliance is mobile home approved.
• The appliance must be properly connected to a venting
system.
• The appliance is not approved for closet or recessed
installations.
HIGH ELEVATIONS
Input ratings are shown in BTU per hour and are certied
without deration for elevations up to 4,500 feet (1,370
m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the current
ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations
above 4,500 feet (1,370 m).
NOTE: Glass centerline is off center
from rought framing
dimensions.
22¹¹⁄₁₆” (576 mm)
50¹⁄₁₆” (1272 mm)
Figure 5 STLDV (See-thru) Framing
27³⁄₈” (695 mm)
The replace must be secured to the oor and/or to framing
studs as shown in Figure 5 . Use four (4) wood screws or
masonry/ concrete screws to secure replace to the oor.
Use four (4) screws to attach replace to framing. The side
brackets or nailing anges are designed to accommodate
two wall boards thicknesses, 1/2" or 5/8".
If using 5/8" drywall, remove
framing tabs and re-install
on 2nd set of holes
positioned slightly inwards
If using 5/8" drywall, remove
noncombustible supports,
rotate 180° and reinstall to
achieve 5/8" depth
The area above and on the sides of the
replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over
front face of replace.
NOTE
8
20306750
Page 9
INSTALLATION INFORMATION
"
(1224 mm)
CRLDV/CLLDV FRAMING
27¹⁄₂” (699 mm)
(1/2” Drywall)
Remove box and
Insulation for Top
Vent Congurations
Noncombustible
Material
4¹⁄₂”
(114 mm)
Min.
or
27³⁄₈” (696 mm)
(5/8” Drywall)
Designer Series Direct Vent Gas Fireplace
46¹⁄₈” (1172 mm)
(1/2” Drywall)
or
46” (1168 mm)
(5/8” Drywall)
48³⁄₁₆
8¹¹⁄₁₆”
If using 5/8" drywall,
remove framing
tabs and re-install
on 2nd set of holes
positioned slightly
inwards
Fold Outer Tabs
and Nail to Framing
Members
27⁷⁄₈” (708 mm)
Figure 6 CRLDV and CLLDV (Corner) Framing
7”
(178 mm)
Min.
(221 mm) Min,
46⁵⁄₈” (1184 mm)
If using 5/8" drywall, remove
framing tabs and re-install
on 2nd set of holes
positioned slightly inwards
If using 5/8" drywall, remove
noncombustible supports, rotate
180° and reinstall to achieve
5/8" depth
The replace must be secured to the oor and/or to framing
studs as shown in Figure 6 . Use four (4) wood screws or
masonry/ concrete screws to secure replace to the oor.
Use four (4) screws to attach replace to framing. The side
brackets or nailing anges are designed to accommodate
two wall boards thicknesses, 1/2" or 5/8".
20306750
The area above and on the sides of the
replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over
front face of replace.
NOTE
9
Page 10
Designer Series Direct Vent Gas Fireplace
STLDV FRAMING
46¹⁄₈” (1172 mm)
(1/2” Drywall)
or
46” (1168 mm)
(5/8” Drywall)
Remove box and
Insulation for Top
Vent Congurations
7”
(178 mm)
Min.
23” (584 mm)
(1/2” Drywall)
or Adjustable to
22³⁄₄” (578 mm)
(5/8” Drywall)
8¹¹⁄₁₆”
(221 mm) Min,
INSTALLATION INFORMATION
Noncombustible
Material
48³⁄₁₆”
(1224 mm)
If using 5/8" drywall, remove
framing tabs and re-install
on 2nd set of holes
positioned slightly inwards
Fold Outer Tabs
and Nail to Framing
Members
Figure 7 PFDV (Peninsula) Framing
The replace must be secured to the oor and/or to framing
studs as shown in Figure 7 . Use four (4) wood screws or
masonry/ concrete screws to secure replace to the oor.
Use four (4) screws to attach replace to framing. The side
brackets or nailing anges are designed to accommodate
two wall boards thicknesses, 1/2" or 5/8".
If using 5/8" drywall, remove
noncombustible supports,
rotate 180° and reinstall to
achieve 5/8" depth
46⁵⁄₈” (1184 mm)
NOTE: The Vermont Castings Group Model BPWC500
mantel is specially designed to comply with all mantel
temperature requirements. Any custom-built mantels must
comply with the framing clearances and the use of noncombustibles as shown in Figures 5, 6 and 7.
The area above and on the sides of the
replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over
front face of replace.
NOTE
10
20306750
Page 11
INSTALLATION INFORMATION
Designer Series Direct Vent Gas Fireplace
BEFORE YOU START
Read this homeowner manual thoroughly and follow all
instructions carefully. Inspect all contents for shipping
damage and immediately inform your dealer if any damage
is found. Do not install any unit with damaged, incomplete,
or substitute parts. Check your packing list to verify that
all listed parts have been received. You should have the
following:
• Fireplace (Firebox and Burner System)
• Log Set • Fasteners
• Rock Wool • Restrictor Plate/Disc (2)
• White Toggle Switch • Switch Cover Plate
ITEMS REQUIRED FOR INSTALLATION
• Phillips Screwdriver • Framing Materials
• Hammer • Wall Finishing Materials
• Saw and/or saber saw • Level
• Measuring Tape • Pliers
• Electric Drill and Bits • Square
• Pipe Wrench • Tee Joint
• Noncombustible Panel
• Caulking Material (noncombustible)
• Fireplace Surround Material (noncombustible)
• Piping Complying with Local Codes
• Pipe Sealant Approved for use with Propane/LPG
(Resistant to sulfur compounds)
FIREBOX FRAMING
Firebox framing can be built before or after the appliance
is set in place. Construct rebox framing following Figure
5, 6 or 7 for your specic installation requirements. The
framing headers may rest on the top of the rebox standoffs. Do not bring headers below top of standoffs. NOTE:
When planning your framing and installation, keep in mind
that the gas line and electric power come in on the same
end of the replace. Refer to Figures 2, 3 & 4 for replace
dimensions.
The rebox may be installed directly on a combustible oor
or raised on a platform of an appropriate height. When
the rebox is installed directly on carpeting, tile, or other
combustible material, other than wood ooring, the rebox
shall be installed on a metal or wood panel extending the
full width and depth of the enclosure.
FINISHING MATERIAL
NOTE: Any remote wiring (i.e. remote control, wall switch,
and optional fan) must be done prior to nal nishing to
avoid costly reconstruction.
Only noncombustible materials (i.e. brick, tile, slate, steel,
or other materials with a UL re rating of Zero) may be
used to cover the black surface of the appliance. A 300°F
minimum adhesive may be used to attach facing materi-
als to the black surface. If joints between the nished wall
and the replace surround are sealed, a 300°F minimum
sealant material (General Electric RTV103 or equivalent)
must be used.
Do not fill spaces around firebox with
insulation or other materials. This could
cause a re.
WARNING
20306750
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks
around your appliance, and wherever cold air
could enter the room, with noncombustible
material. It is especially important to insulate
NOTE
the outside chase cavity between the studs
and under the oor on which the appliance
rests, if the oor is above ground level.
NOTE: Refer to cold climate pilot information on Page 46
for more information on standing pilot vs. intermittent pilot
options.
11
Page 12
Designer Series Direct Vent Gas Fireplace
INSTALLATION INFORMATION
FIREPLACE LOCATION
Plan for the installation of your appliance. This includes
determining where the unit is to be installed, the vent conguration to be used, framing and nishing details, and
whether any optional accessories (i.e. blower, wall switch,
or remote control) are desired. Consult your local building
code agency to ensure compliance with local codes, including permits and inspections.
The following factors should be taken into consideration:
• Clearance to side-wall, ceiling, woodwork, and windows.
Minimum clearances to combustibles must be main-
tained.
• This replace may be installed along a wall, across a
corner, or use an exterior chase. Refer to Figure 8 for
suggested locations.
• Location should be out of high trafc areas and away
from furniture and draperies due to heat from appliance.
• Never obstruct the front opening of the replace.
• Do not install in the vicinity where gasoline or other
ammable liquids may be stored.
• Vent pipe routing. See Venting section found in this
manual for allowable venting congurations.
• These units can be installed in a bedroom. See National
Fuel Gas Code ANSI Z233.1/NFPA 54 — (current
edition), the Uniform Mechanical Code — (current edition), and Local Building Codes for specic installation
requirements.
• These units can be installed in a bathroom.
D
Y
C
Y
Figure 8 Locate Fireplace
A Flat on wall
A
B
X
** Island (C) and Room Divider (D) installation is possible as long
as the horizontal portion of the vent system (X) does not exceed
20’ (610cm). See details in Venting Section.
* When you install your replace in (D) Room divider or (E) Flat
on wall corner positions (Y), a minimum of 6” (152mm) clearance
must be maintained from the perpendicular wall and the front side
edge of the replace.
B **Island
C *Room divider
D *Flat on wall corner
Y 6” minimum
12
20306750
Page 13
INSTALLATION INFORMATION
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
The appliance cannot be installed on a
carpet, tile or other combustible material
other than wood ooring. If installed on
WARNING
carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or
noncombustible material panel extending
full width and depth of the appliance.
Designer Series Direct Vent Gas Fireplace
12”
Noncombustible
Material to Top of
Standoffs
16”
12”
Top of Fireplace
Opening
6”
2¹⁄₂”
10”
Ceiling
Combustible Mantel
72”
(1829 mm)
Min.
6”
(152 mm)
Min.
Figure 9 Ceiling and Side Wall Clearances
(305 mm)
Max. Depth
12"
16"
(406 mm)
Min.
FP2544
Side View
FP2818
Top View
Side of Fireplace
Opening
Figure 10 Mantel Clearance
4”
1”
5”
FP2817
Spacer
Stud
Combustible
Material Area
2”
3”
45°
6”
MANTEL CLEARANCES
NOTE: The combustible area above the facing must
not protrude more than 1/2" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
NOTE: Vermont Castings Group Model BPWC500
Mantel is designed to comply with all mantel temperature
requirements.
20306750
Never obstruct or modify the air inlet or
outlet grilles (louvers). This may create
a re hazard.
WARNING
13
Page 14
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
Read all instructions completely and
thoroughly before attempting installation.
Failure to do so could result in serious injury,
property damage or loss of life. Operation
of improperly installed and maintained
WARNING
venting system could result in serious injury,
property damage or loss of life.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the
installation. The installer must make sure to select the
proper vent system for installation. Before installing vent
kit, the installer must read this replace manual and vent
kit instructions.
Only a qualied installer/service person should install the
venting system. The installer must follow these safety
rules:
• Wear gloves and safety glasses for protection.
• Use extreme caution when using ladders or when on
rooftops.
• Be aware of electrical wiring locations in walls and ceil-
ings.
The following actions will void the warranty on your venting system:
• Installation of any damaged venting component.
• Unauthorized modication of the venting system.
• Installation of any component part not manufactured or
approved by Vermont Castings Group
• Installation other than permitted by these instructions.
OPTIONAL TOP VENT APPLICATION
The appliance is shipped as a rear vent unit. If the installa-
tion layout requires the unit to be a top vent conguration,
the appliance can be converted by following the steps
below.
When removing and retting the plates and adapter, be
sure the associated gaskets are undamaged and retted
as required.
1. Remove the eight (8) screws securing the ue pipe
adapter to the replace body. Figure 12
2. Set the ue pipe adapter aside, complete with the
gasket. Do not damage the gaskets as the adapter and
gasket must be retted.
3. Remove the eight (8) screws securing the ue pipe cover
to the top of the intake box and remove the cover and
gasket. Figure 12
Remove for Top Vent
applications
NOTICE
14
Failure to follow these instructions will
void the warranty.
FP2895
Figure 11
20306750
Page 15
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
Screws
Flue Pipe
Cover
Flue Pipe
Adapter
Figure 12 Remove 16 screws from Flue Pipe Adapter and
Flue Pipe Cover
FP2833
4. Remove six (6) screws securing the ue pipe to the
back of the intake box and remove the pipe and gasket.
Figure 13
5. Replace the ue pipe to top of rebox. Ensure the gasket
is in place and undamaged. Secure with six (6) screws.
Figure 14
6. Place the ue pipe cover and gasket removed in Step
3 over the ue opening in bottom of the intake box.
7. Ret the ue pipe adapter and gasket to the top of replace. Secure the adapter with six (6) screws removed
in Step 1.
After conversion to top vent conguration,
the 5" (127 mm) flue pipe should be
concentric with the 8" (203 mm) outer collar
within 1/4".
WARNING
Flue Cover
Flue Pipe
Figure 13 Remove Flue Pipe
Flue Pipe
Screws
Screws
FP2834
20306750
FP2835
Figure 14 -
Attach Flue Pipe to Top Vent Conguration
15
Page 16
Designer Series Direct Vent Gas Fireplace
Centerline
VENTING INSTALLATION
This replace must be vented to the outside.
The venting system must NEVER be attached
to a chimney serving a separate solid fuel
burning appliance. Each gas appliance must
use a separate vent system. Do not use
WARNING
common vent systems.
*3"
**1”
(1305 mm)
Flue Pipe
**1"
Centerline
51³⁄₈”
to Floor
Horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the ue and 1"
clearance at the sides and bottom until the
ue penetrates the outside wall. A minimum
1" clearance all around the ue is acceptable
at this point of penetration. Unless the
vertical run is 71⁄2' or higher from oor of
replace, the clearance for horizontal run
is 1" on all sides.
WARNING
Vertical sections of this vent system require
a minimum of 2" clearance to combustibles
at the top of the unit directly above the
stand-off. A minimum of 1" clearance all
around the ue is acceptable thereafter.
37⁷⁄₈”
*3"
**1”
(962 mm)
Flue Pipe
Figure 15 Combustible Clearances for Vent Pipe with Minimum Rise
to Floor
**1"
FP2819
* A minimum of 3" clearance to the top is required along horizontal
length until ue pipe penetrates outside wall.
** A minimum 1" clearance to combustibles permitted all around
ue at outside wall
16
20306750
Page 17
VENTING INSTALLATION
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to
note the wall thickness.
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. All horizontal run
of venting must have 1/4" rise for every 12" of run towards
the termination below 71⁄2' of vertical rise from oor of re-
place. With 71⁄2 feet or more of vertical rise from the oor
of the replace, the horizontal run may be level. NEVER
run vent piping down.
You may use up to three 90° elbows in this vent conguration. Refer to Vertical/Horizontal Termination Congurations
on Page 21.
Horizontal venting which incorporates the twist lock pipe
must be installed on a level plane without an inclining or
declining slope.
FOR VERTICAL TERMINATION
Measure the distance from the replace oor to the ceiling. Add the ceiling thickness, the vertical rise in an attic
or second story, and allow for sufcient vent height above
the roof line.
NOTE: You may use two 45° elbows in place of a 90°
elbow. You must follow rise to run ratios when using
45° elbows. The appliance is approved for use with
three 90° elbows maximum or a combination of 90°
and 45° elbows up to a maximum of 270°.
Designer Series Direct Vent Gas Fireplace
Never run the vent pipe down. This may
cause excessive temperatures which could
cause a re.
WARNING
For two-story applications, restops are required at each
oor level. If an offset is needed in the attic, additional pipe
and elbows will be required.
You may use a chase with a vent termination with exposed
pipe on the exterior of the house. See Installing Vent
System in a Chase below. If pipe is enclosed in chase, it
is not exposed.
It is very important that the venting system maintain its bal-
ance between the combustion air intake and the ue gas
exhaust. Certain limitations apply to vent congurations
and must be strictly followed.
INSTALLING A VENT SYSTEM IN AN
OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose
venting that runs along the outside of a building. A chase
is required for such venting.
When installing in a chase, you should
insulate the chase as you would the outside
walls of your home. This is especially
important in cold climates. Insulation
should be considered a combustible
NOTICE
material. Maintain proper clearances to all
combustible materials.
Always maintain minimum clearances around
vent systems. The minimum clearances to
combustibles for horizontal vent pipe are 3"
at the top* and 1" at the sides and bottom
of the vent system until the pipe penetrates
the nearest vertical wall (1" required). A 1"
minimum clearance all around the pipe must
be maintained at outside wall and on vertical
runs. Do not pack the open air spaces with
insulation or other materials. This could
WARNING
cause high temperatures and may present
a re hazard.
*Unless the vertical run is 7
1
⁄2 feet or higher
from oor of replace, the clearance for the
horizontal run is 1" on all sides.
20306750
Treatment of restops and construction of
the chase may vary from building type to
building type. These instructions are not
substitutes for the requirements of local
NOTICE
building codes. You must follow all local
building codes.
17
Page 18
Designer Series Direct Vent Gas Fireplace
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
B
INSIDE
CORNER DETAIL
A
G
CFM145a
V
V
V
V
V
V
V
V
TERMINATION LOCATION
Termination Locations
VENTING INSTALLATION
A = Clearance above grade, veranda, porch,
CANADIAN INSTALLATIONS
1
12" (30cm)12" (30cm)
US INSTALLATIONS
2
deck or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window12" (305mm) recommended to prevent
D = Vertical clearance to ventilated soft locat-
6" (15cm) for appliances <10,000 BTU/h
(3kW)
12" (30cm) for appliances >10,000 BTU/h
(3kW) and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h
(30kW)
6" (15cm) for appliances <10,000 BTU/h
(3kW)
9" (23cm) for appliances >10,000 BTU/h
(3kW) and <50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h
(15kW)
12" (305mm) recommended to prevent win-
window condensation
dow condensation
18" (458mm)18" (458mm)
ed above the terminal within a horizontal
distance of 2' (610 mm) from the center
line of the terminal
E = Clearance to unventilated soft12" (305mm) 12" (305mm)
F = Clearance to outside corner see next pagesee next page
G = Clearance to inside corner see next pagesee next page
H = Clearance to each inside of center line
extended above meter/regulator assembly
3' (91cm) within a height of 15' (5m) above
the meter/regulator assembly
3' (91cm) within a height of 15' (5m) above
the meter/regulator assembly
I = Clearance to service regulator vent outlet3' (91cm)3' (91cm)
J = Clearance to non-mechanical air supply
inlet to building or the combustion air inlet
to any other appliance
6" (15cm) for appliances <10,000 BTU/h
(3kW)
12" (30cm) for appliances >10,000 BTU/h
(3kW) and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h
(30kW)
6" (15cm) for appliances <10,000 BTU/h
(3kW)
9" (23cm) for appliances >10,000 BTU/h
(3kW) and <50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h
(15kW)
K = Clearance to mechanical air supply inlet6' (1.83m)3' (91cm) above if within 10' (3m) horizontally
L = Clearance above paved sidewalk or
7' (2.13m)
†
7' (2.13m)
†
paved driveway located on public property
M = Clearance under veranda, porch, deck or
12" (30cm)
‡
12" (30cm)
‡
balcony
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings
‡ Only permitted if veranda, porch, deck or balcony is fully open on a
minimum 2 sides beneath the oor.
18
NOTE: 1. Local codes or regulations may require different
clearances.
2. The special venting system used on Direct Vent
Fireplaces are certied as part of the appliance, with
clearances tested and approved by the listing agency.
3. Vermont Castings Group assumes no responsibility for
the improper performance of the appliance when the venting
system does not meet these requirements.
20306750
Page 19
VENTING INSTALLATION
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
G
Combustible
6" (152 mm)
Noncombustible
V
2" (51 mm)
Outside Corner
V
F
Designer Series Direct Vent Gas Fireplace
Alcove Applications*
D
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
C
O
C
V
E
Balcony -
with no side wall
M
V
Figure 17 Termination
Clearances
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specied for vinyl or
non-vinyl siding and softs. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.
M =
Combustible &
Noncombustible
12" (305 mm)
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimensions
of the vent system.
1. Determine the height of the center of the horizontal vent
pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph below, locate the point
intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the replace in accordance with same.
Example: If the vertical dimension from the oor of the
replace is 11' (3.4 m) the horizontal run to the face of
the outer wall must not exceed 16' (4.9 m).
Sidewall Vent Graph showing the relationship between
vertical and horizontal dimensions for a Direct Vent ue
system.
Balcony -
with perpendicular side wall
M
V
P
Combustible &
Noncombustible
M = 12" (305 mm)
P = 6” (152 mm)
323⁄4" to Center
of Horizontal
Pipe
E = Min. 2” (51 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
No.
of Caps DMin. CMax.1 3’ (914 mm) 2 x DActual2 6’ (1.8 m) 1 x DActual3 9’ (2.7 m) 2/3 x DActual4 12’ (3.7 m) 1/2 x DActual
DMin. = # of Termination caps x 3
CMax. = (2 / # termination caps) x DActual
40
38
36
34
32
30
Dimensions in
Feet
28
26
24
22
20
18
16
eg: A
14
12
10
8
6
4
2
2 4 6 8 10 12 14 16 18 20
584-15
Vertical Dimension From the Floor of Unit to the Center of the
Horizontal Vent Pipe
Horizontal dimension from the nished outside wall
Figure 18 -
to the center of the pipe on the replace
Rear Wall Venting Graph
20306750
19
Page 20
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
REAR WALL VENT INSTALLATION (5" x 8"
VENTING ONLY)
When installed as a rear vent unit, this appliance may be
vented directly to a termination located on the rear wall
behind the appliance. Only an Vermont Castings Group
brand termination is allowed for this application.
• The maximum horizontal distance between the rear
of the appliance and the termination is 20" (508 mm).
Figure 19
Maximum
20"
(508 mm)
Top View Flat
Installation
Figure 19 Rear Vent Application Maximum
Horizontal Distance
• Only one 45 degree elbow is allowed in these installa-
tions.
1. Rigid vent pipes and ttings have special twist-lock
connections. Assemble the desired combination of pipe
and elbows to the appliance adapter.
Twist-Lock Procedure: The female ends of the pipes
and ttings have three (3) locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and ttings. Push the
pipe sections together and twist one section clockwise
approximately one-quarter turn until the sections are
fully locked. Figure 20
NOTE: Seal-
ant is not
required to
assemble
fireplace
venting. Do
not use silicone sealant
at the inner
ue exhaust
connections.
Female Locking
Lugs
NOTE: Horizontal runs of
vent must be supported
every three feet (914
mm). Use wall straps for
this purpose.
Male Slots
Figure 20 Rigid Vent Pipe Connections
2. Refer to venting and termination instructions for further
instructions.
3. Locate and cut the vent opening in the wall. For combustible walls rst frame in opening.
Combustible Interior Walls: Cut a 121/2" x 101/2" hole
through the interior wall.
Combustible Exterior Walls: Cut a 101/2" x 101/2"
square hole through the exterior wall frame. Figure 21
Noncombustible Walls: Hole opening should be 81/2"
(216 mm) in diameter.
4. The center of the hole should align with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 21
Vent Opening for Combustible Walls
101⁄2”
(267 mm) Min.
101⁄2”
(267 mm)
Min.
Fireplace Hearth
Opening for Noncombustible Wall
81⁄2”
(216 mm)
Figure 21 -
Locate vent opening on wall
Fireplace Hearth
Framing Detail
FP2293
5. Apply a bead of non-hardening mastic around the
outside edge of vent cap. Position the vent cap in the
center of hole on the exterior wall with the word "UP"
on the vent cap facing up. Insure proper clearance of
1" to combustibles is maintained. Attach the vent cap
with four (4) wood screws supplied. Figure 22
NOTE: Replace the wood screws with appropriate
fasteners for stucco, brick, concrete or other types
of siding.
For vinyl siding, stucco or wood exterior, use vinyl
siding standoffs between vent cap and exterior wall for
Duravent or Selkirk Terminations only. The vinyl siding
standoff prevents excessive heat from melting the
vinyl siding material. NOTE: Vermont Castings Group
Termination does not require standoff. Bolt the vent
cap to the standoff or wall. Apply non-hardening mastic
around outside edge of the standoff instead of the vent
cap assembly. Use wood screws provided to attach the
standoff. Figure 23
20
20306750
Page 21
VENTING INSTALLATION
HOT
Vent Cap
Designer Series Direct Vent Gas Fireplace
Inerior Wall
Surface
Vent Cap
(Horizontal
Termination)
Firestop
Apply Mastic to all
Four Sides
Figure 22 Install Horizontal Termination
Cut Vinyl Siding Away
to Fit Standoff
Apply Mastic
to all Four
Sides
FP1956
Figure 23 Install Duravent/Selkirk Vinyl Siding Standoff and
Termination
Nut
Wood Screw
Wood Screw
Standoff #1250 or
5DT-VS
(Not required for
Vermont Castings
Group termination)
HOT
Bolt
6. Slide the stop over the vent pipe before connecting the
horizontal run to the vent cap. Figure 24
7. Carefully move the fireplace with vent assembly
attached toward the wall and insert the vent pipe into
the horizontal termination. The pipe overlap should
be a minimum of 11/4". Apply silicone to the outer pipe
connection. Fasten all vent connections with screws
provided.
8. Slide the wall thimble against the interior wall surface
and attach with screws. Figure 24
Termination
FP1957
Screw
Figure 24 Install Firestop on Horizontal Vent Pipe
Do not recess vent termination into any
wall. This will cause a re hazard.
WARNING
All rear vent through-the-wall applications
must use Vermont Castings Group-designed
5 x 8 square termination. No other manu-
facturer's termination is permitted in this
NOTICE
application.
For more information, follow instructions
provided with terminations.
NOTICE
Horizontal
Vent Pipe
20306750
21
Page 22
Designer Series Direct Vent Gas Fireplace
36"
(914 mm)
Max.
VENTING INSTALLATION
When installing the appliance as a rear
vent unit, the 90° or 45° transition elbow
attached directly to the rear of the unit is
NOT INCLUDED in the following criteria
and calculations and, unless specically
mentioned, should be ignored when
WARNING
calculating venting layouts.
HORIZONTAL WITH VERTICAL RISE
(THROUGH-THE-WALL)
TERMINATION CONFIGURATIONS
Since it is very important that the venting system
maintain its balance between the combustion air
intake and the ue gas exhaust, certain limitations
as to vent congurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable. Figure 18
Minimum clearance between vent pipes and combustible
materials is 3" on top and 1" from bottom and sides unless
otherwise noted (Exception: Outside wall with restop: 1"
all around pipes are allowed). If the vertical run is 7.5 feet
or more, from the oor of the replace, the clearance is 1"
on all sides of the horizontal run.
When vent termination exits through foundations less than
20" below siding outcrop, the vent pipe must be ush with
the siding.
It is best to locate the replace in such a way that minimizes
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the ue collar of the replace (or the top of the
Transition Elbow) to the face of the nished outside wall
or the mounting ange of the termination.
3 x 90°
Elbows
Figure 25 Maximum Three (3) 90°
Elbows Per Installation
Figure 26 Maximum Horizontal Run
with No Rise
A
3 x 90°
Elbows
FP1176
36"
(914 mm)
Max.
FP1177
90°
B
• The maximum number of 90° elbows per side wall
installation is three (3). Figure 25
• If a 90° elbow is tted directly on the top of the replace,
the maximum horizontal vent run before the termination
or a vertical rise is 36” (914 mm). Figure 26
• If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36". Figure 23. This does not apply if the 90° elbows
are used to increase or redirect a vertical rise. Figure
27
Example: According to the vent graph (Page 19) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 17' (5.2 m).
In Figures 27 and 28 dimension A plus B must not be
greater than 17' (5.2 m).
22
Figure 27 Horizontal Run Reduction
7’6”
FP2837
20306750
Page 23
VENTING INSTALLATION
A
10'
7'6"
Figure 28 Maximum Vent Run with Elbows
Horizontal 90° Elbow =
3' Reduction
A + B = 17' Maximum
FP2838
Designer Series Direct Vent Gas Fireplace
HORIZONTAL WITH VERTICAL RISE
(THROUGH-THE-WALL) APPLICATIONS
B
1. Locate and cut the vent opening in the wall. For
7'
combustible walls rst frame in opening.
Combustible Interior Walls: Cut a 121⁄2"H x 101⁄2" W
hole through the interior wall.
Combustible Exterior Walls: Cut a 101⁄2"H x 101⁄2"W
square hole through the exterior wall frame. Figure 25
Noncombustible Walls: Hole opening should be 81⁄2"
(216 mm) in diameter.
2. The center of the hole should line up with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 30
Vent Opening for Combustible Walls
10Z\x”
(267 mm) Min.
101⁄2”
(267 mm)
Min.
• The maximum number of 45° elbows permitted per side
wall installation is two (2). These elbows can be installed
in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18"
(457 mm). This does not apply if the 45° elbows are
installed on the vertical part of the vent system.
• The maximum number of elbow degrees in a system is
270°. Figure 24
1
2
3
4
1 + 2 + 3 + 4 = 270°
Figure 29 Maximum Elbow Usage
1
2
3
4
FP2307
Fireplace Hearth
Opening for Noncombustible Wall
8Z\x”
(216 mm)
Figure 30 -
Locate vent opening on wall
Fireplace Hearth
Framing Detail
FP2293
You may use a reducer from 5" x 8" to
5
4" x 6
⁄8" or 4" x 7" for horizontal with
vertical rise applications. ONLY use
framing instructions below when using
4" x 65⁄8" or 4" x 7" venting.
If the reducer is installed at the rear of the
unit, you must immediately follow with a 90
elbow for a vertical rise before continuing
WARNING
with any horizontal run. There is a minimum
total height of 7 feet from the replace oor
to the last section of pipe before horizontal
run. Refer to graph on Page 19.
5
NOTE: #1222DA reducer must be used when 4 x 6
venting is preferred. #7TDVP58 reducer must be used
with 4" x 7" venting is preferred. Reducer must be
installed directly onto unit at the repalce collar before
vertical rise.
⁄8"
20306750
23
Page 24
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
1. Locate and cut the vent opening in the wall. For combustible walls rst frame in opening.
1
Combustible Interior Walls: Cut a 11
⁄2"H x 91⁄2" W
hole through the interior wall.
Combustible Exterior Walls: Cut a 9
1
⁄2"H x 91⁄2"W
square hole through the exterior wall frame. Figure 31
Noncombustible Walls: Hole opening should be 71⁄2"
(190 mm) in diameter.
2. The center of the hole should line up with the center line
of the horizontal rigid vent pipe end. Allow 1/4" minimum
rise per foot. Figure 31
Vent Opening for Combustible Walls
91⁄2”
(241 mm) Min.
91⁄2”
(241 mm)
Min.
Fireplace Hearth
Opening for Noncombustible Wall
Framing Detail
1. Establish vent hole through the wall.
2.
Remove soil to a depth of approximately 16" below base
of snorkel. Install drain pipe. Install window well (not
supplied). Rell hole with 12" of coarse gravel leaving a
clearance of approximately 4" below snorkel. Figure 32
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
7. Level the soil so as to maintain a 4" clearance below
snorkel. Figure 32
Screws
Firestop
Minimum
4" Clearance
Ground
24"
Minimum
Window
Well
Gravel
71⁄2”
(190 mm)
Figure 31 -
Locate vent opening on wall
Fireplace Hearth
FP2293
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal
clearances of 12" above grade level, a snorkel kit is recom-
mended. It allows installation depth down to 7" (178 mm)
below grade level. The 7" (178 mm) is measured from the
center of the horizontal vent pipe as it penetrates through
the wall.
Ensure that sidewall venting clearances are observed.
If venting system is installed below ground, we recommend a window well with adequate and proper drainage
to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is nec-
essary. The maximum horizontal run with the 24” vertical
pipe is 36". This measurement is taken from the collar of
the replace (or transition elbow) to the face of the exterior
wall. Refer to the Sidewall Venting Graph for extended
horizontal run if the vertical exceeds 24".
Figure 32 -
Below Grade Installation
If the foundation
is recessed, use
recess brackets
(not supplied) for
securing lower portion of the snorkel.
Foundation
Recess
Fasten brackets
to wall first, then
secure to snorkel
with self drilling #8
x 1/2 sheet metal
Watertight Seal
Around Pipe
screws. It will be
necessary to extend
vent pipes out as
far as the protrud-
ing wall face. Figure
33
Figure 33 Snorkel Installation,
Recessed Foundation
Drain
Foundation Wall
FP1965
Snorkel
Wall
Screws
Sheet
Metal
Screws
FP1966
24
20306750
Page 25
VENTING INSTALLATION
VERTICAL THROUGH-THE-ROOF
APPLICATIONS
A restrictor disc must be installed on
vertical terminations that are higher than
12' (366 cm).
NOTICE
Install restrictor disc as shown in Figure 34 for vertically
vented applications.
Up to two (2) restrictor discs may be needed for 40' installation.
The two (2) restrictor discs suppled will work for most installations. If a third disc is needed order Part No. 56D3027.
You may use a reducer to 4" x 65⁄8" or
4" x 7" in vertically vented applications. If a reducer is used, only one
restrictor may be used.
Restrictor
Disc
Designer Series Direct Vent Gas Fireplace
10'
Maximum
40' Maximum Height
8' Minimum Height
Support Straps
Every 3'
Fireplace
Collar
Figure 34 Install Restrictor Disc
into Fireplace Collar
FP2839
This gas replace has been approved for,
• Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 35
NOTE: Horizontal sections of this vent system require a
minimum of 3" clearances to combustibles at the top of
the ue and 1" clearance at the sides and bottom until the
ue penetrates the outside wall. A minimum 1" clearance
all around the ue is acceptable at this point of penetration.
Unless the vertical run is 71⁄2 feet or higher form oor of
replace, the clearance for the horizontal run is 1" on all
sides.
Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.
10'
Maximum
40' Maximum Height
8' Minimum Height
Support Straps
Every 3'
FP2308
Figure 35 Support Straps for Horizontal Runs
Example: Maximum horizontal lengthNo elbows = 10’ (3 m)
1x45° elbows = 8.5’ (2.6 m)
2x45° elbows = 7’ (2.1 m)
• A minimum of an 8' (2.5 m) vertical rise is required.
• Two sets of 45°elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m)
of vent pipe can be used between elbows. Figure 27
• The maximum angular variation allowed in the system
is 270°. Figure 27
• For the minimum height of the vent above the highest
point of penetration through the roof refer to Page 27,
Figure 40.
• Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
1. Determine the route your vertical venting will take. If
ceiling joist, roof rafters or other framing will obstruct
the venting system, consider an offset. Refer to Figure
32 to avoid cutting load bearing members.
NOTE: Pay special attention to these installation instructions
for required clearances (air space) to combustibles when
passing through ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any
maximum horizontal offset limitations. Offsets must fall
within the parameters shown on Page 19, Figure 18.
2. Set replace in desired location. Drop a plumb line down
from the ceiling to the position of the ue exit. Mark the
center point where the vent will penetrate the ceiling.
Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locat-
ing hole in the ceiling. Mark the center point where the
vent will penetrate the roof. Drill a small locating hole
at this point.
FLAT CEILING INSTALLATION
1. Cut a 10
the locating hole as a center point The opening should
be framed to 10
dimensions as shown in Figure 39 using framing lumber
the same size as the ceiling joist. If the area above the
ceiling is an insulated ceiling or a room, nail restop
from the top side. This prevents loose insulation from
falling into the required clearance space. Figure 39.
Otherwise, install restop below the framed hole. The
restop should be installed with no less than three (3)
nails per side. Figure 38 or 39.
2. Assemble the desired lengths of pipe and elbows necessary to reach from the burner system ue up through
the restop. Be sure pipe and elbow connections are
fully twist-locked. Page 20, Figure 20.
3. Cut a hole in the roof using the locating hole as a center
point. (Cover any exposed open vent pipes before
cutting hole in roof). The 10
hole must be measured on the horizontal. Actual length
may be larger depending on the pitch of the roof. There
must be a 1" minimum clearance from the vent pipe to
combustible materials. (Insulation should be considered
a combustible material). Frame the opening as shown
on Page 20, Figure 21.
4. Connect a section of pipe and extend up through the
hole.
1
⁄2" (267 mm) square hole in the ceiling using
1
⁄2" x 101⁄2" (267 x 267 mm) inside
1
⁄2" x 101⁄2" (267 x 267 mm)
26
20306750
Page 27
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
Nails
Firestop
Figure 38 If Area Above is a Room, Install Firestop above
Framed Hole as Shown
10
10
"
1
2
/
1
/
2
"
NOTE: If the vent pipe passes through any occupied areas
above the rst oor, including storage spaces and closets,
you must enclose pipe. You may frame and sheetrock the
enclosure with standard construction material. Make sure
to meet the minimum allowable clearances to combustibles.
Do not ll any of the required clearance spaces with
insulation.
Horizontal Overhang
2 ft.
Min.
Termination
Vent
Storm Collar
Flashing
2 ft. Min.
Lowest
Discharge
Opening
H*
Vertical Wall
12
X
FP1971
FP1970
Nails
Figure 39 If Area Above is Not a Room, Install Firestop above
Framed Hole as Shown
Firestop
NOTE: If an offset is needed to avoid obstructions, you
must support the vent pipe every three (3) feet. Use wall
straps for this purpose. Refer to Page 26, Figure 37.
Whenever possible, use 45° elbows instead of 90° elbows.
The 45° elbow offers less restriction to the ow of the ue
gases and intake air.
5. Place the ashing over the pipe section(s) extending
through the roof. Secure the base of the ashing to
the roof and framing with roong nails. Be sure roong
material overlaps the top edge of the ashing. There
must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the
vent cap meets the minimum requirements below.
NOTE: You must increase vent height for steep roof
pitches. Nearby trees, adjoining roof lines, steep pitched
roofs, and other similar factors may cause poor draft or
down-drafting in high winds. Increasing the vent height
may solve this problem.
Concentric
Vent Pipe
Figure 40 Minimum Chimney Clearance
Roof Pitch H (feet)Flat to 6/12 1.0
Over 6/12 to 7/12 1.25
Over 7/12 to 8/12 1.5
Over 8/12 to 9/12 2.0
Over 9/12 to 10/12 2.5
Over 10/12 to 11/12 3.25
Over 11/12 to 12/12 4.0
*H - Minimum height from roof to
lowest discharge opening of vent
1" Minimum
Clearances to
Combustibles
20306750
27
Page 28
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
FLEX VENT INSTALLATION
1. Flexible UL1777 listed venting may be used in any
venting application where rigid direct vent components
can be used. All restrictions, clearances and allowances that pertain to the rigid piping apply to the
exible venting. Flex kits may not be modied. Flex
kits may be added to the end of a vent run made of rigid
vent sections using pipe manufacturer's approved ex
to pipe adapters. This may occur only if doing so does
not violate any of the venting length, height, routing,
horizontal to vertical ratio requirements or clearance
considerations detailed in this manual.
5" x 8" Flex Vent Pipe
2. The ex adapter starter kit (DVFF8A/8) is used to attach
ex venting to the appliance starting collar. It includes
5" inner and 8" outer adapter rings. Figure 41
• The inner and outer adapter rings are required to
start all ex runs.
•Never install damaged or torn exible venting.
•Over tightening clamps may rip, tear, or otherwise
damage exible venting.
• The adapter kit does not include individual pipe sec-
tions which may be purchased separately. (UL1777
listed type venting only.)
3. Start the exible vent as follows:
A. Installing the inner ex adapter and pipe. Figure
UL1777
Flex Vent
3
1
⁄4" Flexible
Pipe and
Adapter
Outer
DVFF8A/8
Inner Adapter
Outer Adapter
Appliance
Starting Collar
Figure 41 Typical 5" x 8" Appliance Connection
equidistant just
Flex vent pipe spacers: Refer to manufacturer’s
specications for correct positioning of the
spacer springs to maintain proper distance
NOTE
between inside and outside pipe.
41
Screws
(3 places,
above gear
clamp)
1. Insert the long side of the 5" inner ring into exhaust
pipe, gently tap to seat into place, and secure with
screws.
2. Slide the small gear clamp over the inner exible
vent pipe, and push out of the way.
3. Pull and extend the inner exible vent.
4. Slide the inner vent onto the adapter collar, for a
minimum 1
3
⁄4" overlap.
5. Locate the clamp at approximately 3/4" from the ex
end and tighten.
6. Secure the clamped inner section with three selftapping screws, drilled equidistant, just above the
clamp perimeter.
B. Installing the outer ex pipe. Figure 41
1. Firmly insert the 8" outer adapter ring into the
outer appliance starting collar and secure with
screws.
2. Slide the large gear clamp over the outer exible
vent pipe, and push out of the way.
3. Pull and extend the outer exible vent.
4. Slide the outer vent onto the appliance collar outer
adapter for a minimum 1
3
⁄4" overlap.
5. Locate the clamp at approximately 3/4" from the
ex end and tighten.
6. Secure the clamped outer section with three selftapping screws, drilled equidistant, just above the
clamp perimeter.
C. Routing UL1777 ex pipe.
1. Always maintain the required clearance when
routing the ex vent assembly.
2. Install restop spacers, Figure 43, when penetrat-
ing ceiling, attic spaces, or walls.
3. Do not allow the exible vent to bend in radius
tighter than 5" (127 mm). Figure 42
4. Horizontal runs of exible vent shall be supported
at maximum 2
foot intervals;
UL1777
Flex Vent
vertical runs,
five feet intervals. Metal
strapping, properly secured, is
5° Radius
an acceptable
means to sup-
port the exible
vent.
Figure 42 Minimum Radius for Flex
Vent Section
5. Flexible vent
spacers are to be installed at intervals prescribed
by the exible vent manufacturer; and in such a
way as to maintain concentric inner and outer
vent spacing.
28
20306750
Page 29
FP1974typical flex install
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
D. Attaching exible venting to vertical termination
assemblies.
1. When using Duravent pipe, an Vermont Cast-
ings Group ex-to-pipe adapter and/or rigid pipe
section(s) is required to connect the exible vent
assembly to the vertical termination by using
three self-penetrating screws.
2. Review Figure 44 and corresponding instruc-
tions for proper overlap, clamp and screw place-
ment.
3. Three each self-penetrating screws are drilled
opposite one another and below the gear
clamp.
4. Use only listed and approved terminations and
accessories, installed per the installation instructions and Figure 43.
Termination
Cap
Flashing
Rigid Pipe
Length
Flex to Pipe
Adapter
Storm Collar
Roof Support
E. Installing exible venting to horizontal termination
assemblies.
1. Connect the 5" exible vent to the horizontal
termination as in Figure 45.
2. Connect the 8" exible vent to the termination
ring as in Figure 45.
3. Review Figure 45 for proper overlap and clamp
placement.
4. Three each self-penetrating screws are drilled
opposite one another and below the gear lamp.
5. Use only listed an approved terminations and
accessories, installed per the termination instructions and Figure 45.
Rigid Pipe Length
Screws
(3 Places
equidistant
just above
gear clamp)
Gear
Clamp
Flex to Pipe Adapter
Gear Clamp
13⁄4" Flexible Pipe and Adapter
Outer Collar Overlap
If you prefer to use 4" x 7" ex pipe, you must install model
7TDVP58 reducer (5" x 8" to 4" x 7") onto the replace
collar. Then follow the the assembly guidelines for 5" x 8"
ex venting.
Use proper gas type for the replace you are installing.
If you have conicting gas type, do not install replace.
See dealer where you purchased the replace for proper
replace according to your gas type.
INSTALLING GAS PIPING TO FIREPLACE
LOCATION
A qualied installer or service person must
connect appliance to gas supply. Follow all
local codes.
WARNING
INSTALLATION ITEMS NEEDED
Before installing replace and burner system, make sure
you have the items listed below.
• External regulator • Tee joint
• Piping (check local codes) • Pipe wrench
• Sealant (resistant to propane/LP gas)
(supplied by installer)
• Test gauge connection*
• Sediment trap (recommended)
• Equipment shutoff valve*
• approved exible gas line with gas connector (if
allowed by local codes — not provided)
* A CSA design-certied equipment shutoff valve with
1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certied equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply
an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas
pressure to between 11 and 13 inches of water. If you do
not reduce incoming gas pressure, burner system regulator
damage could occur. Install external regulator with the vent
pointing down as shown in Figure 50. Pointing the vent
down protects it from freezing rain or sleet.
For propane/LP units, never connect
replace directly to the propane/LP supply.
This burner system requires an external
regulator (not supplied). Install the external
regulator between the burner system and
CAUTION
propane/LP supply.
Designer Series Direct Vent Gas Fireplace
100 gal. (min)
External
Regulator
Figure 50 External Regulator with Vent Pointing Down
(Propane/LP Only)
Propane/LP
Supply Tank
Vent Pointing
Down
FP1977
Use only new black iron or steel pipe.
Internally tinned copper or copper tubing
can be used per National Fuel Code, Section
2.6.3, providing gas meets hydrogen sulde
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data plate)
CAUTION
at the maximum ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too
small.
External regulators may be necessary for
natural gas. One- or two-pound systems
will damage this appliance and may cause
re hazard.
WARNING
When using copper or ex connectors use only ttings
approved for gas connections. The gas control inlet is
3/8" NPT.
20306750
31
Page 32
Designer Series Direct Vent Gas Fireplace
3" Minimum
FIREPLACE INSTALLATION
GAS SUPPLY LINE INSTALLATION
Only persons licensed to work with gas
piping may make the necessary gas
connections to this appliance.
WARNING
NOTE : The gas line connection may be made using 1/2"
rigid tubing or an approved ex connector. Since some
municipalities have additional local codes it is always best
to consult your local authorities and the current edition of
the National Fuel Gas Code ANSI.Z223.1, NFPA54. In
Canada CSA-B149 (1 or 2) Installation Code.
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appliance. Figure 51
IMPORTANT: Install main gas valve (equipment shutoff
valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the replace.
Check your building codes for any special requirements for
locating equipment shutoff valve to replaces.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.
A manual shutoff valve must be installed
upstream of the appliance. Union tee
and plugged 1/8" NPT pressure tapping
point should be installed upstream of the
CAUTION
appliance. Figure 51
We recommend that you install a sediment trap/drip leg
in supply line as shown in Figure 51. Locate sediment
trap/drip leg where it is within reach for cleaning. Install
in piping system between fuel supply and burner system.
Locate sediment trap/drip leg where trapped matter is not
likely to freeze. A sediment trap traps moisture and contami-
nants. This keeps them from going into the burner system
gas controls. If sediment trap/drip leg is not installed or is
installed wrong, burner system may not run properly.
Use pipe joint sealant that is resistant to
liquid petroleum (LP) gas.
CAUTION
Approved Flexible
Gas Line
Sediment Trap/Drip Leg
Figure 51 Gas Connection
CSA Design-Certied Equipment Shutoff Valve
with 1/8" NPT Tap*
Tee Joint
Pipe Nipple
Cap
Natural Gas
From Gas Meter
(4.0" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
32
20306750
Page 33
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
CHECK GAS PRESSURE
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the replace, STOP! Do not install the
appliance. Contact your dealer immediately.
2. To ease installation, a 24" (610 mm) ex line with manual
shut-off valve has been provided with on this appliance.
Install and attach 1/2" gas line onto shut-off valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 52. After taking pressure reading, be sure and
turn captured screw clockwise rmly to reseal. Do not
over torque. Check test points for gas leaks.
ELECTRICAL WIRING
General
1. This replace is equipped with the Signature Control
valve which operates on 6 volts. The 6 volt DC adapter
plugs into the replace junction box A/C power supply.
Four (4) “AA” batteries are used for back up during
power outages.
2. The Signature Command System can also be operated
without A/C power. The system can run on four (4) “AA”
batteries for approximately six (6) months under normal
use.
3. A/C power must be used to power the A/C module,
blowers, lights and AUX accessories if used with this
replace.
Optional Accessory Requirements
1. This replace may be used with a wall switch, wall
mounted thermostat and/or Signature Command wire-
less controls.
2. The command center control may be mounted on the
wall with the use of the SCSWEK 15ft. wall mount
extension kit.
Pressure Inlet
Pressure Outlet
Figure 52 Signature Command Valve
Pilot Adjustment
Screw
Do not use open ame to check for gas
leaks.
WARNING
Electrical connections should only
be performed by a qualified, licensed
electrician. Main power must be off when
connecting to main electrical power supply
or performing service. All wiring shall be
in compliance with all local, city and state
codes. The appliance, when installed, must
be electrically grounded in accordance with
WARNING
local codes or in the absence of local codes,
with the National Electrical Code ANSI/NFPA
70 (latest edition) and Canadian Electrical
Code, CSA C22.1.
FP1909a
20306750
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
CAUTION
33
Page 34
Designer Series Direct Vent Gas Fireplace
JUNCTION BOX WIRING
1. This should be done before framing the replace. Wire
the receptacle into an electrical circuit. Wire with minimum 60° C wire in accordance with prevailing codes.
2. Remove the external junction box cover by removing
the screw from the side of the outside rebox wall.
Junction box was installed at the factory.
3. The junction box cover has a factory installed “romex”
style strain relief connector. After connecting the wires,
route the wire leads through this connector. Refer to
the wiring diagram in Figure 53.
FIREPLACE INSTALLATION
120V AC
60Hz
Factory Supplied
Not Supplied
Junction Box
Figure 53 Junction Box Wiring Diagram
COMMAND CENTER WALL INSTALLATION
The command center may be mounted on the wall with
the use of the SCSWEK Kit (15ft. cable, junction box, wall
cover).
Mount the junction box provided at the desired location
on the wall. Do not extend beyond the 15 ft. wire cable
provided. If a longer distance is required, the 15 ft. may be
extended up to 30 ft. maximum by using two (2) SCSWEK
cables plugged together.
Route the wire from junction box to lower control area at
bottom of replace. Unplug the 12" cable from the command center. Attach the connector to the pins from wire
by pushing in to connector making sure to follow the color
code on connector. Plug the 15 ft. extension cable into the
2 ft. cable. Remove command center from the replace
and plug the other end of the extension cable into the
command center. Snap on wall cover provided and screw
to junction box.
WALL SWITCH INSTALLATION
The wall switch wire connection is located off the 2 ft. wire
harness from the control box to the command center. Figure 54. The connection is labeled “Wall Switch”. Unplug
the male and female connectors and connect the two (2)
low voltage wires provided. Run wire to desired location
on wall. Up to 50 ft. of 18 ga. wire may be used if necessary. Attach wires to wall switch. Mount the wall switch in
to junction box and screw on cover.
Do not connect wall switch to 110 V
circuit.
WARNING
34
20306750
Page 35
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
To Junction Box
in Fireplace
Optional
White
Light
{
White
Black
Optional
Aux.
Black
{
White
Black
Green
Optional
{
Blower
Input 300 Watt Max. Each
Optional A/C Module Replaces 6V Adapter
When Used
6V AC
Adapter
NOTE: Wall switch wires must be connected together if a wall switch is not
being used.
Gas In
Plug in
Connector
Optional
AC Module
Connector Pin
To Control Board
Control Board
Conversion
NG/LP
Plug-in Connector
Stepper Motor to
Ground
Plug-in Connector
Control Board to
Solenoid
Control Board
DC Power/Green
RF Receiver
ON/OFF Button
Black / Thermopile
Red / Thermopile
Sensor
Ignitor / Sparker
Plug-in Connector
Control Board to Command Center
OFF/LO
LED
ON/HI
Master Switch
Command Center
Gas Out
Pilot
Optional
Wall Switch
Figure 54 Signature Command Wiring Diagram
Electrical connections should only be
performed by a qualied, licensed electrician.
Main power supply must be turned off before
connecting fans to the main electrical power
CAUTION
supply or performing service.
20306750
Pilot Gas Tubing
Valve
35
Page 36
Designer Series Direct Vent Gas Fireplace
FIREPLACE INSTALLATION
Electrical Grounding Instructions: This
appliance is equipped with a three-prong
(grounding) plug for your protection against
shock hazard and should be plugged directly
into a properly grounded three-prong
WARNING
receptacle.
Electrical connections should only be
performed by a qualied licensed electrician.
Main power supply must be turned off before
connecting the fan to the main electrical
power supply or performing service.
WARNING
The black and white wires on the AC box
wiring harness are marked ‘Blower’, ‘Light’
and ‘Aux’. It is important to use the wires
marked ‘Blower’ or the control will not work
Module and the TSFSC remote to install and operate this
kit. Refer to blower instructions for installation.
NOTE: If two (2) blowers are required with the Signature
Command System SCSACM & TSFSC remote, two (2)
BLOTSTSC Kits must be purchased.
Control Board
FP2708
36
20306750
Page 37
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
BLOTBLDV AUTOMATIC DUAL THERMOSTAT BLOWER
Receptacle
Junction
Box
120VAC
BLACK
GREEN
BLACKWHITE
Speed Control
Figure 56 BLOTBLDV Blower Wiring Diagram
Before installing the blower, wire the receptacle into an
electrical circuit. This should be done before framing the
replace. Wire with minimum 60° C wire in accordance
with prevailing codes.
BLOTDL AUTOMATIC SINGLE THERMOSTAT BLOWER
Receptacle
Junction
Box
BLACKBLACKWHITE
FP2685
120VAC
BLACK
GREEN
20306750
BLACKWHITE
Speed Control
Figure 57 BLOTDL Blower Wiring Diagram
BLACKBLACKWHITE
37
Page 38
Designer Series Direct Vent Gas Fireplace
GLASS FRAME REMOVAL
FIREPLACE INSTALLATION
NOTE: You must rst remove the safety barrier before you
remove the glass frame. To remove the barrier, simply lift
up and pull out until the slots on the screen are clear of
their corresponding tabs on the rebox. Then proceed to
remove the glass frame by following the steps below.
1. Remove access panel by lifting up and out.
2. Release two clamps on bottom of replace. Figure 58
3. Tilt glass frame out and lift glass frame up until it clears
three tabs on top of replace.
4. Set glass frame aside.
Each clamp has a quick spring force. When
reinstalling clamps, keep ngers clear.
CAUTION
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Glass Frame
Figure 58 Remove Screen Barrier and Glass Frame
38
Safety Barrier
Access Panel
20306750
Page 39
FIREPLACE INSTALLATION
ROCK WOOL PLACEMENT
Place rock wool evenly in dime-sized pieces over the burner
ports. Do not place embers over the burner slots. To better
enable the gas to permeate the rock wool, apply the rock
wool in light, dime size uffy pieces.
Designer Series Direct Vent Gas Fireplace
Rock
Wool
Areas
Pin used
with Contemporary
Stone Kit
Pin used with
Contemporary
Stone Kit
Log Placement Pins
Figure 59 Rockwool placement
Do not use the entire bag of rock wool to
cover the burner. This could cause the ame
to burn poorly and may lead to sooting.
WARNING
20306750
39
Page 40
Designer Series Direct Vent Gas Fireplace
FIREPLACE INSTALLATION
LOG PLACEMENT
1. Hold log #1 with the rounded end opposite the pilot.
NOTE: Log #1 is designed to not be symmetrical. Place
log #1 aligning the two (2) pins provided making sure to
t the notches in the bottom of the log over the sides of
the grate so that it sits rmly in place. The log will rest
on the grate bar about 1/4" over the top of the burner
surface. Figure 60
Log #1
Figure 60
2. Place log #2 so the fat end of the log rests on the 2nd
tine of the grate (opposite the pilot) and the thin, right
end of the log sits on top of the key provided on the end
of log #1 closest to the pilot. Figure 61
Log #2
3. Position log #3 on the key provided on the rounded end
of log #1. The other end sits on the "false-bottom hearth"
(the sheet metal surrounding the burner and supporting
the grate), just outside of the grate. The base of the log
should be about 1" from the end of log #2. Figure 62
Log #3
FalseBottom
Hearth
Figure 62
4. On the remaining key on the top of log #1 (in the center),
place log #4 with the charred area of the log facing down
and toward the nearest glass. The other end of the log
rests on the second tine from the end closest to the
pilot. Figure 63
Figure 61
40
Figure 63
LG968
Log #4
20306750
Page 41
FIREPLACE INSTALLATION
5. Place log #5 on the key provided on log #4. Rest the
other end of the log on the "false-bottom hearth" just
outside of the grate. It should be almost touching the
end of log #1. Figure 64
Log #5
Figure 64
Designer Series Direct Vent Gas Fireplace
20306750
41
Page 42
Designer Series Direct Vent Gas Fireplace
CERTIFIED
FIREPLACE INSTALLATION
SAFETYBARRIER
SAFETY BARRIER INSTALLATION
INSTRUCTIONS
NOTE: A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this
appliance and shall be installed for the protection of
children and other at risk individuals. If the barrier
becomes damaged, the barrier shall be replaced with
the manufacturer's barrier for this appliance.* Any
safety screen, guard, or barrier removed for servicing
the appliance must be replaced prior to operating the
appliance.
* See parts list for model number.
WARNING: The safety screen barrier must
be installed after the glass front is in place.
It is NOT a replacement for the glass and
the unit must NOT be operated without the
glass in place.
Small
Safety
Barrier
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Install the Large Screen
Figure 65
1. Remove screen from packaging.
2. Align the three (3) slots in the top of the screen with
the three (3) tabs on top of the rebox. These are
the tabs on which the glass frame hangs. Slide the
screen down onto the tabs.
3. Push the bottom of the frame into the clamps at the
bottom of the rebox and secure latch.
Install the Small Screen (PFLDV, CRLDV, CLLDV)
Figure 65
1. Remove screen from packaging.
2. Remove the three (3) screws at the bottom of the
glass frame.
3. Align the three (3) slots in the top of the screen with
the three (3) tabs on top of the rebox. These are
the tabs on which the glass frame hangs. Slide the
screen down onto the tabs.
4. Push the bottom of the frame into place and re-install
the screws through the screen frame and the glass
frame into the rebox.
NOTICE: It is the responsibility of the
installer to ensure the barrier is afxed
to the replace at the time of installation.
Screws
(3)
Figure 65
42
Large
Safety
Barrier
Clamps
(2)
20306750
Page 43
OPERATING INSTRUCTIONS
Designer Series Direct Vent Gas Fireplace
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions
exactly, a fire or explosion may result
causing property damage, personal injury
or loss of lie.
WARNING
A. This appliance is equipped with an ignition device which automatically lights the pilot. Refer
to the instructions.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to
the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
• Do not attempt to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the re department.
C. Use only your nger to push in the master switch. Never use tools. If the switch will not func-
tion by hand, do not try to repair it. Call a qualied service technician. Force or attempted
repair may result in a re or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualied
service technician to inspect the appliance and to replace any part of the control system and
any gas control that has been under water.
20306750
43
Page 44
Designer Series Direct Vent Gas Fireplace
OPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. This appliance is equipped with an ignition device which automatically lights the burner. Do not try
to light the burner by hand.
3. With ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell
gas, STOP! Follow "B" in the safety information on Page 43. If you do not smell gas, go to next
step.
4. Press the master switch to the "ON" (-) position. Within eight (8) seconds it will beep once. This
indicates the system is ready.
5. Press "ON " button. Sparker will spark and pilot ame will light.
6. Once pilot ame is established, the main burner ame will light automatically.
7. If the pilot will not stay lit after several tries, turn the master switch to "OFF" and call your service
technician or gas supplier.
OFF
OFF
OFF
ON
ON
Command Center
Master
Switch
ON
TO TURN OFF GAS TO APPLIANCE
1. Turn master switch to "OFF".
2. Turn off all electrical power to the appliance if service is to be performed.
44
20306750
Page 45
SIGNATURE COMMAND SYSTEM OPERATION
Designer Series Direct Vent Gas Fireplace
FEATURES
Command Center
• Easy Access Function Operation and System Congura-
• Uninterrupted Operation During Power Outage (Automatic
Battery Backup)
• ON/OFF RF Remote Receiver
• Optional Transmitter Learn Capability
AC Module Board (Optional, requires TSFSC Remote)
RF Receiver
ON/OFF
NG/LP
Conversion
Control
Board
OFF
LED
ON
Master Switch
Command
Center
Figure 65 Signature Command System Components
Battery Door
To Thermopile
To Sensor
To Command Center
To Stepper Motor
To Valve
To Sparker
• Easy Snap-on Design
• Embedded Compact 120 VAC Adapter with Auto Battery Back up Feature
• Remote Controlled 3-step Blower, Lighting, and On/Off Auxiliary AC Outputs
Transmitter (Optional)
TSFSC TSTSC TSMSC RTSC RMSC
Three Flame Height Settings X X X X X
Low battery Indication for Transmitter X X X X X
Child Proof Lock-out X X X X X
LCD Backlight X X X X X
Security Codes 16 X X X X X
Countdown 6 hr Timer X X X -- -Standard Thermostatic Control Mode X X -- X --
Smart Mode
Three Brightness Settings for Lights X -- -- -- -Three Speed Control for Blower X -- -- -- -On/Off Auxiliary X -- -- -- -Programmable Timer to turn blower on and off X -- -- -- --
®
Thermostat (Auto Flame & Blower Modulation) X X -- -- --
BATTERY INSTALLATION
The Command Center uses four (4) "AA" batteries as back up for power outages. The system can operate for approximately six (6) months on battery power.
To Install Batteries (not included):
1. Press down the battery door tabs and pull out to remove battery door.
2. Install the batteries as indicated on Command Center.
3. Close battery door by snapping in place.
4. When the four (4) batteries are installed the system will operate without power.
5. The batteries should be replaced when the LED indicates low battery or at least once a year.
20306750
45
Page 46
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM OPERATION
SYSTEM CONFIGURATION/SETUP
All System conguration/setup is done on the Command
Center.
NOTE: When using On/Off wall switch, the switch must be
in the ON position to perform all conguration set ups at
the command center.
COLD CLIMATE OPTION
Choose the Mode That Best Suits Your Needs
The Signature Command System is designed to operate
in either Standing Pilot or Intermittent Pilot mode.
• The Standing Pilot Mode is best for colder climates
when the pilot must remain on continuously to prevent
condensation and ensure reliable operation.
• The Intermittent Pilot Mode is ideal for maximum ef-
ciency, igniting the pilot only when needed to start your
replace, lowering fuel consumption and reducing your
carbon footprint.
Either mode benets from the instantaneous battery backup, so you never have to worry about a power outage.
NOTE: The Signature Command System comes stan-
dard in the Intermittent Pilot mode, so you must follow
the instructions below to switch to Standing Pilot Mode if
needed.
Intermittent/Standing Pilot Setup (Default intermit-
tent)
1. Holding the ON button on the Command Center while
turning on the master switch will toggle between stand-
ing pilot and intermittent pilot.
2. After the above operation, one beep (for standing pi-
lot) or two beeps (for intermittent pilot) will be given as
conrmation.
Six-hour Safety Shutdown Option (Default ON)
1. The system comes preset from the factory with a six
(6) hour shutdown from its last command of operation.
This is done to prevent the replace from continuing to
operate if unattended. You may disable this feature if
you wish.
NOTE: By disabling this feature, your replace may con-
tinue to operate unattended.
2. When the master switch is in the ON position (“-”), pressing the ON button and the OFF button on the Command
Center simultaneously will toggle between enabling and
disabling the six-hour shutdown option.
3. After the above operation, one beep (for enabling the
six-hour shutdown option) or two beeps (for disabling
the six-hour shutdown option) will be given as conrma-
tion.
Remote Transmitter Learn Function (Default OFF)
1. The RF receiver button located on the Control Board
must be in the on position before the learn function can
begin. Use paper clip to depress button. One beep for
RF receiver ON or two beeps for RF receiver OFF will be
given as conrmation. Refer to Figure 57 for location.
2. After the RF receiver is on, holding the OFF button on
the Command Center while turning on the master switch
will activate the learn function for the transmitter.
3. After the above operation, two beeps will be given and
the green LED on the Command Center will ash for
10 seconds.
4. During the 10 seconds, press the OFF button on a
transmitter to learn. Another two beeps will be given
to conrm a successful learning. Refer to transmitter
instructions for remote operations.
Shutting Off the Standing Pilot (Temporary Shut Off)
To shut off the standing pilot for service or summer shut
down, press and hold the ON button on the Command
Center for 3 seconds when the master switch is in the ON
position (“-”) and the main burner is off.
Note: Pilot will resume the next time system is turned
on.
Key Combinations for System Settings
NOTE: When On/Off wall switch is used, it must be in the
On position to perform all system setups.
Function Operation Default Setting
Intermittent/Standing Hold the ON s button while turning on the master switch Intermittent
Pilot Setup (Beep once for standing pilot, twice for intermittent pilot) Pilot
Standing Pilot Temp. Hold the ON s button 3 seconds (when the master switch
Shutoff on the main burner is off)
RF Remote Receiver Push the RF receiver On/Off button on the control board RF OFF
On/Off Beep once for ON and beep twice for OFF
Learn Remote Hold the OFF t button while turning on the master switch
Transmitter (Beep twice then press any handheld remote button)
6-hour safety Press the ON s button and OFF t button simultaneously ON
shutdown setup (Beep once for ON, twice for OFF)
46
20306750
Page 47
SIGNATURE COMMAND SYSTEM OPERATION
Designer Series Direct Vent Gas Fireplace
FUNCTIONS/OPERATION
Turning on the replace
1. Turn on the master switch and wait for a beep.
2. Press the ON button on the Command Center or turn
on wall switch. Pilot will light and burner will come on
High setting or last memory setting (See Turning Off
Fireplace below). For memory feature.
Pilot Safety Lockout Function
1. If the pilot doesn’t light after sparking for 30 seconds,
pilot trial lockout happens. The LED on the Command
Center ashes Green once every 2 seconds, until reset.
2. If the pilot ame is lost during normal operation, the
system will try three (3) times to relight after three (3)
failures, ame loss lockout happens. The LED on the
Command Center ashes Red-Green once every 2
seconds, until reset.
3. Turning the master switch on the Command Center to
the off position, then ON again will reset the system.
Flame Height Control
1. Press the ON button (on the Command Center) once to
turn on the main burner with maximum ame height.
2. Press the OFF button to decrease ame height. The rst
two presses will decrease the ame height to medium
and low.
3. The third press on OFF will turn off the main burner. In
standing pilot conguration, the pilot will stay; in intermittent pilot conguration, the pilot will be shut off.
Turning the Fireplace Off
There are three ways to turn the replace off.
1. Flip the master switch to the off (“O”) position. (This will
turn the entire system OFF.)
2. Press the OFF button to Medium, Low, then Off.
3. Hold the OFF button anytime for three seconds or by
turning off the wall switch. These two commands of
OFF are (Memory Off) the system will remember all last
settings before turning off. The next time the replace is
turned on, all settings will resume. To reset, change to
the desired settings and shut off by using the Memory
Off commands and the system will be reset to those
new settings.
Command Center Operations:
The following functions are available on the Command
Center.
Function Operation
Power Up Flip the master switch to the ON ("–") position to power up the system
Fireplace ON Press the ON s button on the Command Center or turn on wall switch to turn the replace on
Fireplace OFF Flip the master switch to the OFF ("o") position OR press the OFF t button 3
times OR for Memory Off, hold the OFF t button 3 seconds, or turn off wall switch
Flame Height Up Press the ON s button once to turn on the replace with maximum ame height
Flame Height Down Press the OFF t button to lower the ame height to Medium and Low
Self Diagnostics Chart:
The Command Center has a self-diagnostic LED enabling
you to troubleshoot problems and potentially avoid a
service call. Please refer to the charts below for indicator
reference.
Fault LED Indication
Conversion Cover Missing One RED (1 time)
Spark Fail Two RED (1 time)
No Sensor Signal Three RED (1 time)
Pilot Lockout - trial One GREEN, every 2 sec. (until manual reset)
Pilot Lockout - ame loss One RED-GREEN, every 2 sec. (until manual reset)
Low Battery One RED, every 10s (continuously)
No or Low Thermopile Power Two RED, every 10s (continuously)
Learning GREEN Flashes, every 1 sec. (for 10 sec.)
AC Power On GREEN solid
Pressure Switch Failure One RED every 2 sec. (until manual reset)
Power Vent Only
20306750
47
Page 48
Designer Series Direct Vent Gas Fireplace
CLEANING AND MAINTENANCE
Turn off gas before servicing replace. It
is recommended that a qualied service
technician perform these check-ups at the
beginning of each heating season
WARNING
BURNER, PILOT AND CONTROL COMPARTMENT
Keep the control compartment, logs, and burner areas
surrounding the logs clean by vacuuming or brushing at
least twice a year. Make sure the burner porting, pilot air
opening and burner air opening are free of obstructions
at all times.
PILOT FLAME
The ames from the pilot should be visually checked as
soon as the heater is installed and periodically during
normal operation. The pilot ame must always be pres-ent when the replace is in operation. Figure 66. The
pilot ame has four distinct ames, one engulng the
thermopile, one engulng the sensor, and the other two
reaching to the main burners.
Sensor
Thermopile
FP2453
Figure 66 Pilot Flame
BURNER
Inspect area around the injector. Remove any lint or foreign
material with a brush or vacuum.
BURNER FLAME
The ames from the burner should be visually checked
as soon as the heater is installed and periodically during
normal operation. In normal operation, at full rate, and after
operating for about 15 to 30 minutes, the ame should be
yellow and slightly taller than the rear log. Figure 67
If the ame is blue and only in the center, turn off unit and
let cool. After unit is cool, remove logs and check to make
sure the back holes in the burner are not covered with rock
wool. If the back holes are clear, add more rock wool to the
center of the burner. Replace logs.
NOTE: The type of installation, vent system conguration,
and wind effects may cause the ame patterns to vary.
Figure 67 Burner Flame Appearance
48
20306750
Page 49
CLEANING AND MAINTENANCE
Designer Series Direct Vent Gas Fireplace
VENT SYSTEM
The replace and venting system should be inspected
before initial use and at least annually by a qualied eld
service person. Inspect the external vent cap on a regular
basis to make sure that no debris is interfering with the
airow. Inspect entire venting system to ensure proper
function.
GLASS DOOR
Thoroughly clean the inside of the glass door after using
the replace for ten hours. Periodically clean the glass
door as necessary.
When cleaning the glass, remember:
•Do not remove the glass when hot. Allow glass to
cool before removal.
• NEVER use abrasive materials.
• Keep children and pets a safe distance away.
• Never operate the replace without the glass door
properly secured.
• Never operate the replace if the glass is broken.
• Replace any glass that is chipped, cracked, or broken.
Replacement glass door assemblies MUST be supplied
by the replace manufacturer – No substitute materi-
als may be used.
• Handle glass door with care to avoid striking or scratch-
ing it on hard objects.
To clean glass door, follow “Glass Removal” procedure
outlined in the Final Installation section. Film deposit on the
inside of the glass should be cleaned off using a nontoxic,
non-corrosive, non-abrasive, mild-cleaning solution. Simply
apply an adequate amount to the glass and wipe off with
a damp cloth. After all maintenance has been completed,
re-install glass door.
LOGS
Leave logs installed in the replace for cleaning. Vacuum
surface of the logs with a brush attachment. If logs must be
removed for cleaning, handle carefully by holding gently at
each end. Gloves are recommended to prevent skin irrita-
tion from ceramic bers. If skin becomes irritated, wash
gently with soap and water. Vacuum surface of logs with
brush attachment or brush logs with a soft bristle brush
(i.e. clean, dry paintbrush). To place logs back in the replace, see “Log Placement” found in the Final Installation
section.
NOTE: Do not use uids to clean ceramic ber logs.
ROCK WOOL
Replace or add rock wool as required following installation instructions in the Final Installation section of this
manual.
20306750
49
Page 50
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
TROUBLESHOOTING
OPERATION
Install batteries and/or
plug in the AC board
Flip the master switch
(rocker switch) to the
ON position
After the beep
Press the ON button on
the Command Center
FAULT
No beep in about
8 seconds
No beep
or
no sound from the
valve indicating pilot
solenoid open
No sparking on
the pilot
A
B
C
Make sure
Command
Center and
the control
board are
connected by
a 2 feet or 15
feet cable
Check NG/LP
conversion cap
and control
board
connections
Check pilot
connections
DIAGNOSIS
Using
battery?
Check valve
connections
Check
grounding
Battery polarity wrong?
Battery voltage low?
AC plug is plugged to
AC mains?
The 5-pin connector on
the AC board broken or
bent?
LED on the Command
Center does not show
solid green?
Check power
supply (go
through )
A
Go through
B
ACTION
Re-install batteries
Change batteries
Plug the AC plug to
AC mains
Repair or replace the
AC Board
Replace the AC Board
Replace the Control
Board or
Command Center
Sparking is happening
elsewhere (under the
pilot), re-install/replace
the pilot
Sparking doesn’t
continue
Pilot doesn’t light
Main burner doesn’t
light
D
The Control Board is having interference from the
surrounding metal (Ground)
E
Check gas supply
F
Go through
E
Go through
The sensor on the pilot
is not in the flame
(pilot flame too small)?
Re-install the Control
Board, move it around
or change the
Control Board
Sparking is not in the
C
path of gas flow, adjust
sparker position or
replace the pilot
Adjust sensor position
or replace the pilot
50
20306750
Page 51
REPLACEMENT PARTS
Designer Series Direct Vent Gas Fireplace
3
5
4
7.
1
2
6.
FIREBOX COMPONENTS
ItemDescriptionST
Qty.
1.Glass Frame Assembly22120302401
2.Access Panel22120302126
3.Glass Frame Assembly, Short--1120302151
4.Access Panel, Short--1120302127
5.Grate11120301124
6.Large Safety Barrier Assembly22120307088
7.Small Safety Barrier Assemby--1126D2128
Junction Box Assembly (not shown)11126D2128
PF
Qty.
CR/CL
Qty.
Designer
LDV Part No.
20306750
51
Page 52
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
REPLACEMENT PARTS
15
1
12
2
3
13
4
7
11
16
6
5
9
8
52
20306750
Page 53
REPLACEMENT PARTS
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
ItemDescriptionQty.Designer NaturalDesigner LP
1.Burner Assy12030218820302188
2.Venturi Gasket145D0032
3.Venturi Assy169D1119
4.Injector170D006420H3153
5.Tube, Union to Venturi12030200920302009
6.Fitting Brass - Union 5/16 Compression137D071337D0713
NOTE: This termination is not recommended for use with the
Designer Series Fireplaces.
56
20306750
Page 57
VENTING COMPONENTS
VENT COMPONENTS FOR 5" X 8"
Designer Series Direct Vent Gas Fireplace
Current
Duravent
Qty./
Item
11Horizontal Termination Cap w/Built-in Vinyl Siding
11Horizontal Termination Cap Built-In Vinyl Siding Stand-
11Horizontal Termination Cap Built-In Vinyl Siding Stand-
18Horizontal Termination w/ 1" FirestopBHR58T/8
11Horizontal High Wind Termination Cap58DVA-HC12855DT-HC--
11Horizontal Temination Cap5DHT
21Vertical Termination58DVA-VC1280NoteNote
346" Pipe Length58DVA-0612085DT-065D6
349" Pipe Length58DVA-0912075DT-09
3412" Pipe Length58DVA-1212065DT-125D12
3424" Pipe Length58DVA-2412045DT-245D24
3436" Pipe Length58DVA-3612035DT-365D36
3448" Pipe Length58DVA-4812025DT-485D48
4481/2" Pipe Extension58DVA-08A--5DT-AJ
4416" Pipe Extension58DVA-16A----
5445° Elbow58DVA-E4512455DT-EL455D456
5445° Swivel Elbow----5DT-EL45
6490° Elbow58DVA-E9012905DT-EL90S5D906
6490° Swivel Elbow--1290G5DT-EL90S
76Flashing, 0/12 to 6/12 Roof Pitch58DVA-F612435DT-AF65DF
7Steep Roof Flashing58DVA-F121243S--
86Storm Collar58DVA-SC12535DT-SC5DSC
94Firestop58DVA-FS12635DT-FS5DFS
93" FirestopFS38FS38--
101Vinyl Siding Standoff58DVA-VSS12505DT-VS5DVS
11Attic Insulation Shield (not shown)58DVA-IS----
128Flex Adapter Starter (not shown)DVFF8A/8----
131Reducer - 5 x 8 to 4 x 65/8 (not shown)1222DA1222DA--
Box Description
Standoff Heat Deector, Firestop, and Adjustable Pipe
11" to 14
off, Heat Deector, Firestop, 90° Elbow and Adjustable
Pipe 11" to 14
off, Heat Deector, Firestop, Flexible Pipe 2-" to 48",
Adapter
5
⁄8"
5
⁄8"
or VCG
Part No.
--BHR58TK9----
--BHS58TK----
Old
Duravent
or VCG
Part No.
BHSF58TK
Selkirk
Part No.
Metal-Fab
Part No.
NOTE: This termination is not recommended for use with the
Designer Series Fireplaces.
For more information about, or instructions for, the venting components referenced above, please contact the component manufacturer:
Selkirk Corporation: www. selkirkcorp.com or 800-992-8368
Duravent: www. duravent.com or 800-835-4429
Metal-Fab, Inc.: www.metal-fabinc.com or 316-943-2351
20306750
57
Page 58
Designer Series Direct Vent Gas Fireplace
584F
VENTING COMPONENTS
HORIZONTAL VENTING - 4" x 7"
Description Model Number
Horizontal Vent Termination Kits Rear Vent Hot Touch Termination Kit w/ 10" to 16" 7TBRHTK
Adjustable Termination Pipe, Firestop, and Hot Touch
Termination w/ Siding Shield
Up and Out Side Wall Termination Kit w/ 10" to 16" 7TDVSCTK
Adjustable Termination Pipe, 90° Elbow, Firestop, and Cool Touch Termination w/ Siding Shield
Rear Vent Cool Touch Termination w/ Siding Shield for 7TRVCT/8
Straight-out Applications and Firestop - 8 pack
Rear Vent Hot Touch Termination w/ Siding Shield for 7TRVHT/8
Straight-out Applications and Firestop - 8 pack
Termination Guard for 7" T.L. Rear Vent Hot Touch 7TRVTG
Terminations 97TRVT/7TSVKT)
Snorkel Termination 7TDVSNORK
7" T.L. DVRTSB Termination Screen Guard 7TBSG
Up and Out Starter Kit w/ 40" Flex Pipe, Firestop, Cool 7FDVSCTK
Touch Termination w/ Siding Shield, and 2 ea. Clamp
Vertical Vent Termination w/ 1/12 - 6/12 Flashing, Storm 7TDVSKVA*
Collar and Ceiling Support Kit
Vertical Vent Termination w/ 6/12 - 12/12 Flashing, 7TDVSKVB*
Storm Collar and Ceiling Support Kit
Vertical Vent Termination w/ Flat Flashing, Storm Collar 7TDVSKVF*
and Ceiling Support Kit
Twist Lock Pipe 20" Rigid Pipe - single pack 7TDVP20
30" Flex Pipe - single pack 7FDVP30
12" - 18" Adjustable Vent Length 7TDVP1218
35" - 64" Adjustable Vent Length 7TDVP3564
8" Vent Pipe - 4 pack 7TDVP8/4
12" Vent Pipe - 4 pack 7TDVP12/4
24" Vent Pipe - 4 pack 7TDVP24/4
36" Vent Pipe 7TDVP36
36" Vent Pipe - 30 pack 7TDVP36/30
48" Vent Pipe 7TDVP48
48" Vent Pipe - 30 pack 7TDVP48/30
5" x 8" to 4" x 7" Adapter 7TDVP58
Flex Adapter Starter Kit DVFFA/8
Twist Lock Elbows 45° Elbow for Vertical/Horizontal Offset 7TDV45
45° Elbow for Vertical Offsets - 8 pack 7TDV45/8
90° Elbow for Vertical/Horizontal Offset 7TDV90
90° Elbow for Vertical/Horizontal Offset - 8 pack 7TDV90/8
Shields and Supports 1" Firestop 7DV1FS
1" Attic Insulation Shield 7DV1AIS
Combination Horizontal Offset/Roof Support 7DVCS
20306750
59
Page 60
Designer Series Direct Vent Gas Fireplace
MASSACHUSETTS RESIDENTS ONLY
Please read and follow these special requirements
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas tter
when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a carbon
monoxide (CO) detector installed in the residence.
Installation of the replace or vented gas log in the State of
Massachusetts requires the damper to be permanently removed
or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a
bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a
T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas tter
when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a
bedroom or bathroom regardless of size or type in the State of
Massachusetts.
Flex line installation must not exceed 36 inches and must have a
T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional
requirements:
(a) For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not limited
to decks and porches, the following requirements shall be
satised:
1. Installation of carbon monoxide detectors. At the time
of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gas tter shall observe
that a hard wired carbon monoxide detector with an alarm and
battery back-up is installed on the oor level where the gas
equipment is to be installed. In addition, the installing plumber
or gas tter shall observe that a battery operated or hard wired
carbon monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled equipment. It shall be
the responsibility of the property owner to secure the services of
qualied licensed professionals for the installation of hard wired
carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said thirty
(30) day period, a battery operated carbon monoxide detector
with an alarm shall be installed.
2. Approved Carbon Monoxide Detectors. Each carbon
monoxide detector as required in accordance with the above
provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
3. Signage. A metal or plastic identication plate shall
be permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size
no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. Inspection. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) Exemptions: The following equipment is exempt from 248
CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not
Required To Be Vented" in the most current edition of NFPA 54
as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for
residential purposes.
(c) Manufacturer requirements — Gas Equipment Venting System Provided. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides
a venting system design or venting system components with
the equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system shall
include:
1. Detailed instructions for the installation of the venting
system design or the venting system components; and
2. A complete parts list for the venting system design or
venting system.
(d) Manufacturer requirements — Gas Equipment Venting System Not Provided. When the manufacturer of a Product
Approved side wall horizontally vented gas fueled equipment
does not provide the parts for venting the ue gases, but
identies “special venting systems,” the following requirements
shall be satised by the manufacturer:
1. The referenced "special venting system" instructions
shall be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” shall be Product Approved
by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all
venting design
VENTING COMPONENTS
60
20306750
Page 61
Designer Series Direct Vent Gas Fireplace
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox,
Combustion Chamber and Heat Exchanger.
FIVE YEAR WARRANTY
The following components are warranted ve (5) years to the original owner, subject of proof of purchase:
Ceramic Fiber Logs.
BASIC WARRANTY
Vermont Castings Group warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two years from date of installation. After installation, if any of the
components manufactured by Vermont Castings Group in the appliance are found to be defective in materials
or workmanship, Vermont Castings Group will, at its option, replace or repair the defective components at
no charge to the original owner. Vermont Castings Group will also pay for reasonable labor costs incurred
in replacing or repairing such components for a period of two years from date of installation. Any products
presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualied installer in accordance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not
operated and maintained according to the operating instructions supplied with the appliance, and does not
extend to (1) rebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence
of others, including the installation thereof by unqualied installers, (2) the costs of removal, re-installation or
transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work
must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of tness for purpose and of all other obligations or liabilities. Vermont Castings Group does not
assume for it any other obligations or liabilities in connection with sale or use of the appliance. It states that
do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage,
those limitations of exclusions may not apply to you. You may also have additional rights not covered in the
Limited Lifetime Warranty.
Vermont Castings Group reserves the right to investigate any and all the claims against the Limited Lifetime
Warranty and decide upon method of settlement.
IF WARRANTY SERVICE IS NEEDED:
1. Contact your supplier. Make sure you have your warranty, your sales receipt and the model/
serial number of your Vermont Castings Group product.
2. DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
20306750
61
Page 62
Designer Series Direct Vent Gas Fireplace
This page left blank.
62
20306750
Page 63
This page left blank.
Designer Series Direct Vent Gas Fireplace
20306750
63
Page 64
Based on CSA P.4.1-09
EFFICIENCY RATINGS
ENERGUIDE RATINGS
FIREPLACE EFFICIENCY
MODEL
Natural Gas69.767.0
Liquid Propane (LP)79.468.3
PERCENTAGE
(AFUE PERCENTAGE)
D.O.E.
149 Cleveland Drive • Paris, Kentucky 40361
www.vermontcastingsgroup.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.