Majestic SB60, SB80HB Installation Manual

Installation Manual
Installation and Fireplace Setup
INSTALLER: Leave this manual with party responsible for use and operation. OWNER: Retain this manual for future reference.
This replace uses SL1100 Series Chimney
2” CLEARANCE TO COMBUSTIBLES AND BUILDING INSULATION FROM CHIMNEY REQUIRED.
NOTICE: DO NOT discard this manual!
SB60 SB80
WOODBURNING FIREPLACE
WARNING: If the information in these
instructions is not followed exactly, a re
or explosion may result causing property damage, personal injury, or death.
DO NOT store or use gasoline or other am- mable vapors and liquids in the vicinity of this or any other appliance.
DO NOT overre. Overring will void your
warranty.
• Comply with all minimum clearances to com­bustibles as specied. Failure to comply may cause house re.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable
materials.
• Keep clothing, furniture, draperies and other ammable
materials away.
Installation and service of this appliance should be performed by
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
WARNING
Fire Risk.
For use with solid wood fuel only.
Other fuels may overre and generate poisonous gases (i.e. carbon monoxide).
1
Safety Alert Key:
DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE: Indicates practices which may cause damage to the replace or to property.
Table of Contents
1 Product Specic & Important Safety Information
A. Fireplace Certication 4 B. Non-Combustible Materials 4 C. Combustible Materials 4
2 Getting Started
A. Typical Fireplace System 5 B. Design and Installation Considerations 6
1. Selecting Fireplace Locations 6
2. Locating Fireplace & Chimney 7
C. Tools and Supplies Needed 8
D. Inspect Fireplace and Components 8 E. Fireplace System Requirements 8
3 Framing and Clearances
A. Fireplace Dimensions 9
B. Clearances 11
Minimum Clearances to Combustibles 11 C. Construct the Chase 12 D. Unpack the Fireplace (I60 only) 13 E. Unpack the Fireplace (I80 only) 13 F. Frame the Fireplace 14 G. Secure and Level the Fireplace 15 H. Protective Metal Hearth Strips 15 I. Outside Air Kit 16
4 Chimney and Termination Requirements
A. Chimney Requirements 17
B. Offsets/Returns 18
C. Termination Requirements 19
5 Chimney Installation
A. Typical Chimney System 20 B. Assemble Chimney Sections 21
C. Install Chimney Air Kit 21
D. Secure Offset/Return 22 E. Install Ceiling Firestops 22
F. Install Attic Insulation Shield 23 G. Roof Penetration 24 H. Install Chase/Chase Top 24 I. Termination Cap Requirements 25 J. Install Termination Cap 25
6 Shrouds
A. Radiation Shield 27 B. Field Constructed Shrouds 27
1. Open Top Shroud 27
2. Mailbox Style Shroud 28
3. Roofed Style Shroud 28
7 Finishing
A. Finishing Material 29 B. Hearth Extension, Building and Finishing 30
1. Fireplace Installed Flush on the Floor and Hearth Extension Raised to Bottom of Firebox Opening 31
2. Raised Hearth Extension and Raised Fireplace 32
3. Fireplace Opening and Hearth Extension Flush
with the Floor 33 C. Non-Combustible Sealant Material 33 D. Sidewalls/Surrounds 34 E. Mantel and Wall Projections 35
8 Fireplace Setup
A. Gas Log/Lighter Provision 36 B. Wood Burning Inserts 36 C. Install the Refractory (I80 only) 37
9 Reference Materials
A. Chimney Components 38 B. Optional Components 41
2 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
ATTENTION INSTALLER:
Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this installation manual.
Customer: Lot/Address
Model (circle one): SB60 SB80
Date Installed: Location of Fireplace: Installer: Dealer/Distributor Phone # Serial #:
WARNING! Risk of Fire or Explosion! Failure to install fireplace acording to these instructions can lead to a fire or explosion.
Fireplace Install
Verified that the chase is insulated and sealed. (Pg. 11) Verified clearances to combustibles. (Pg. 10) Fireplace is leveled and secured. (Pg. 14) Protective hearth strips installed per manual requirements. (Pg. 14) Hearth extension size/height decided. (Pg. 29) Outside air kit installed. (Pg. 15)
Chimney Section 4 & 5 (Pg. 16)
Chimney configuration complies with diagrams. Chimney installed, locked and secured in place with proper clearance. Chimney air kit installed. Firestops installed. Attic insulation shield installed. Roof flashing installed. Termination installed.
Shrouds
Shroud is installed properly per instructions.
Section 6 (Pg. 26)
YES IF NO, WHY?
Finishing
Combustible materials not installed in non-combustible areas. Verified all clearances meet installation manual requirements. Mantels and wall projections comply with installation manual requirements. Hearth extension installed per manual requirements.
Fireplace Setup
All packaging and protective materials removed. Molded brick panels installed correctly.
Grate is properly installed. Firescreen installed properly.
Optional doors properly installed. Manual bag and all of its contents are removed from the fireplace and given to the party
responsible for use and operation.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your file.
• That this checklist remain visible at all times on the fireplace until the installation is complete.
Comments: Further description of the issues, who is responsible (Installer/Builder/Other Trades, etc.) and corrective action needed:
Comments communicated to party responsible
Section 7 (Pg. 28)
Section 8 (Pg. 35)
__________________________ by ______________________on _________ (Builder/Gen. Contractor) (Installer) (Date)
4013-302 • Rev B • 3-17-16
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
3
Product Specic & Important Safety Information
1
A. Fireplace Certication
This replace system has been tested and listed in accor­dance with UL 127 and ULC-S610 standards by Under­writers Laboratories Inc. for installation and operation in
the United States and Canada.
This replace may be installed in sleeping rooms. This replace is not approved for manufactured housing. If in­stalled with a gas log set, provisions for the National Fuel Gas Code must be met.
This replace has been tested and listed for use with the optional components specied in this manual. These optional components may be purchased separately and installed at a later date. An outside air kit, gas insert, gas log set or gas log-lighter should be installed at the time of replace installation.
WARNING! Risk of Fire! Hearth & Home Technologies disclaims any responsibility for, and the warranty and agency listing will be voided by the following actions.
DO NOT:
• installoroperatedamagedreplace
• modifyreplace
• install other than as instructed by Hearth & Home Technologies
• operate the fireplace without fully assembling all components
• overre
• install any component not approved by Hearth & Home Technologies
• install parts or components not Listed or approved
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied
installer, service agency or your dealer.
B. Non-Combustible Materials
• Materials which will not ignite and burn, composed of any combination of the following:
- Steel - Iron
- Brick - Tile
- Concrete - Slate
- Glass - Plasters
• Materials reported as passing ASTM E 136, Standard
Test Method for Behavior of Metals, in a Vertical Tube
Furnace at 750° C
C. Combustible Materials
• Materials made of or surfaced with any of the following materials:
- Wood - Compressed paper
- Plant bers - Plastic
- Plywood/OSB - Sheet rock (drywall)
• Any material that can ignite and burn; ame proofed or not, plastered or un-plastered
4 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Getting Started
2
A. Typical Fireplace System
Additional lateral support for chimney above roof (or enclosed in chase) if needed
Non-combustible roof flashing maintains minimum clearance around chimney
Support straps on rafter support chimney
Termination cap
Storm Collar
Chimney penetrates roof preferably without affecting roof rafters
Offset & Return (with hanger straps)
Ceiling firestop on floor of attic
Chimney system
Combustible framing/header on top of V-shaped standoffs
Chimney Air Kit Required in Canada. Outlet must be no less than 4 ft. (1.22 m) off ground level.
Outside combustion air
Protective metal hearth strip(s)
Attic insulation shield must be used here to keep insulation away from chimney if attic is insulated
Framing headed off in ceiling joists
)
)
))
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
Enclosed space above and around fireplace
Mantel and surround
Decorative facing and trim
Hearth extension
Factory-built fireplace
Figure 2.1 Typical Fireplace System
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
5
F
D
E
A
In an exterior chase or projecting into a garage
Across a corner
As a room divider
Along a wall
G
B A
G
G
B A
48 in.
(1219 mm)
min.
H
A
H
Note:
SB60 - 1 in. (25 mm) SB80 - 1 1/2 in. (38 mm) minimum distance from sides & back of fireplace to combustible materials. Both - 1/2 in. (13 mm) minimum at nailing flanges.
C
H
B*
1/2 in. (13 mm) all configurations
*
8 in. (203 mm) extra space included for outside air connection. If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.
A B C D E F G H
inches
45 1/2 53 1/2 85 42 1/2 19 3/8 60 1/8 28
mm
1156 1359 2159 1080 492 1527 711
inches
59 1/2 92 3/4 46 3/8 21 1/2 65 5/8 28 1/2
mm
1308 1511 2356 1178 546 1667 724
Model
SB60
SB80
24 in. (610 mm)
Minimum from FP opening to a
ny
perpendicular wall.
51 1/2
B. Design and Installation Considerations
NOTICE: Check building codes prior to installation.
• Installation MUST comply with local, regional, state and national codes and regulations.
• Consult insurance carrier, local building inspector, re ofcials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
- Where the replace is to be installed.
- The vent system conguration to be used.
- Gas supply piping.
- Electrical wiring.
- Framing and nishing details.
- Whether optional accessories - devices such as a
fan, wall switch or remote control - are desired.
1. Selecting Fireplace Locations
This replace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.2.
Locating the replace in a basement, near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance.
Consideration should be given to these factors before deciding on a location.
NOTICE: In addition to these framing dimensions, also
reference the following section:
• Clearances (Section 3).
NOTICE:
• Illustrationsandphotosreecttypicalinstallationsand
are FOR DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to scale.
• Actual installation/appearance may vary due to individual design preference.
• Hearth & Home Technologies reserves the right to alter its products.
NOTICE: SB60 - A minimum 1 in. air clearance at the back
and a minimum 1 in. air clearance to the sides of
thereplaceassemblymustbemaintained.
SB80 - A minimum 1 1/2 in. air clearance at the back and a minimum 1 1/2 in. air clearance to the sidesofthereplaceassemblymustbemain­tained
Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney sections.
6 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Figure 2.2 Fireplace Locations
2. Locating Fireplace & Chimney
Location of the replace and chimney will affect perfor­mance.
• Install within the warm airspace enclosed by the building envelope. This helps to produce more draft, especially during lighting and die-down of the re.
• Installing the replace in a basement is not recommended.
• Penetrate the highest part of the roof. This minimizes the effects of wind loading.
• Locate termination cap away from trees, adjacent structures, uneven roof lines and other obstructions.
• Minimize the use of chimney offsets.
• Consider the replace location relative to oor and ceiling and attic joists.
• Take into consideration the termination requirements in Sections 4 and 5.
Multi-level Roofs
Recommended Location:
Recommended Location:
• Above peak
• Above peak
• Inside heated space
• Install the outside air kit with the intake facing prevailing winds during the heating season.
• Ensure adequate outdoor air for all combustion appliances and exhaust equipment.
• Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the replace.
• Avoid installing the replace near doors, walkways or small isolated spaces.
• Recessed lighting should be a “sealed can” design.
• Attic hatches weather stripped or sealed.
• Attic mounted duct work and air handler joints and seams
taped or sealed.
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Recommended:
• Insulated exterior chase
Windward
Figure 2.3 Recommended Chimney Locations
Marginal Location:
• Below peak
in cooler climates
Not recommended in basement due to high negative pressure concerns that effect draft
Marginal Location:
• Wind loading possible
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Leeward
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
7
C. Tools and Supplies Needed
Before beginning the installation be sure the following tools and building supplies are available:
Reciprocating saw Framing material
Pliers Non-combustible sealant
Hammer Gloves
Phillips screwdriver Framing square
Flat blade screwdriver Electric drill and bits
Plumb line Safety glasses
Level Tape measure
1/2-3/4 in. length, #6 or #8 self-drilling screws
Misc. screws and nails
D. Inspect Fireplace and Components
WARNING! Risk of Fire and/or Explosion! Damaged parts could impair safe operation. DO NOT install dam­aged,incompleteorsubstitutecomponents.Keepre­place dry.
E. Fireplace System Requirements
The HHT replace system requirements consist of the following:
• Fireplace
- Refractory (included with replace)
- Firescreen (included with replace)
- Hearth Extension
• Outside Air System
- Air Inlet Hood (included with replace)
- Flex (required, sold separately)
• Chimney System
- Chimney air kit (required in Canada, sold separately)
- Attic Insulation Shield (included with replace)
- Chimney termination cap (required, sold separately)
- SLA10 adapter (required in Canada, sold separately)
• Non-combustible nish material
• Inspect replace for damage.
• Vent system components and doors are shipped in separate packages.
• Report to your dealer any parts damaged in shipment.
• Read all the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety
and benet.
8 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Framing and Clearances
3
A. Fireplace Dimensions
SB60
8-5/8 in.
(219 mm)
9-5/8 in.
(244 mm)
Outside Air
Gas
Knockout
9-1/4 in.
(235 mm)
9-1/2 in.
(241 mm)
27-1/2 in. (699 mm)
59-1/4 in.
(1505 mm)
49-5/8 in.
(1260 mm)
7-5/8 in.
(194 mm)
28-5/8 in. (727 mm)
44-1/2 in.
(1130 mm)
36 in.
(914 mm)
14-3/8 in. (365 mm)
9-1/2 in.
(241 mm)
49-1/8 in.
(1248 mm)
28-1/2 in. (724 mm)
55-1/2 in.
(1410 mm)
(effective height)
Gas Knockout
8-5/8 in.
(219 mm)
18-1/2 in. (470 mm)
SB80
8-5/8 in.
(219 mm)
9-5/8 in.
(244 mm)
Outside
Gas
Knockout
Air
9-1/4 in.
(235 mm)
9-1/2 in.
(241 mm)
59-1/4 in.
(1505 mm)
49-5/8 in.
(1260 mm)
7-5/8 in.
(194 mm)
27-1/2 in. (699 mm)
34-1/2 in.
(876 mm)
50-1/2 in.
(1283 mm)
42 in.
(1067 mm)
9-1/2 in.
(241 mm)
28-1/2 in. (724 mm)
(1248 mm)
55-1/2 in.
(1410 mm)
(Efective Height
49-1/8 in.
Gas
Knockout
8-5/8 in.
(219 mm)
18-1/2 in. (470 mm)
Figure 3.1 Fireplace Dimensions
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
9
Contour Front Dimensions
NOTE: CONTOUR FRONTS MUST BE INSTALLED BEFORE APPLYING ANY FINISHING MATERIALS
SB60
SB80
Figure 3.2 Contour Front Dimensions
10 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
B. Clearances
(insulation)
0 in. to level
of standoffs
Attic
Insulation
Shield
(ceiling)
(roof)
(attic)
(ceiling)
Ceiling Firestop
Offset/Return (secured
with hanger straps)
Storm Collar
Roof Flashing
Clearance to back &
sides of appliance
I60 - 1 in. (25 mm)
I80 - 1 1/2 in. (38 mm)
(except at nailing flanges
where it is 1/2 in. [13 mm])
Must have 2 in. (51 mm)
minimum clearance
to header
0 in.
to floor
2 in. (51 mm) min.
Shaded areas
represent
2 in. (51 mm) min.
air space clearance
required around pipe
Combustible Object
48 in.
1219 mm
Adapter attached here (not shown)
WARNING! Risk of Fire!
You must comply with all minimum air space clearances tocombustiblesasspeciedin Figure3.3.DO NOT pack required air spaces with insulation or other materials.
Framing or nishing material used on the front of, or in frontof,thereplacecloserthantheminimumslistedmust
be constucted entirely of non-combustible materials (i.e., steel studs, concrete board, etc.). Failure to comply may
causere.
Minimum Clearances to Combustibles
WITHIN ENCLOSURE AREA
Fireplace to backwall (I60) 1 in. (25 mm)
Fireplace to backwall (I80) 1 1/2 in. (38 mm)
Fireplace to sidewall (I60) 1 in. (25 mm)
Fireplace to sidewall (I80) 1 1/2 in. (38 mm)
Top standoffs to header 0 in. (0 mm)
Door opening to sidewall 24 in. (610 mm)
MANTEL
Mantel minimum height 12 in. (305 mm)
above opening
Maximum mantel depth 12 in. (305 mm)
Note: Chimney air kit and 11-10 in./279-254 mm adapter are not shown, but are required in
Canada.
Figure 3.3 Clearances to Combustible Materials
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
11
C. Construct the Chase
A chase is a vertical boxlike structure built to enclose the replace and/or its vent system. Vertical chimneys that run on the outside of a building must be installed inside a chase.
In cold climates, Hearth & Home Technologies recom­mends that the chase be well insulated using batt type in­sulation between the joists.
Construction of the chase may vary with the type of build­ing. These instructions are not substitutes for the require­ments of local building codes. Local building codes MUST be checked.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner. All outer walls need to be insulated.
Building codes require false ceiling and ceiling restops/ attic shields at each oor of the chase or every 10 ft (3048 mm) of clear space to control spread of re.
Walls, ceiling, base plate and cantilever oor at the rst level of the chase should be insulated (see Figure 3.3.) Vapor and air inltration barriers should be installed in the chase as per regional codes for the rest of the home. Ad­ditionally, Hearth & Home Technologies recommends that the inside surfaces be drywalled and taped (or the use of an equivalent method) for maximum air tightness.
Holes and other openings should be caulked with high tem­perature caulk or stuffed with unfaced ber glass insulation.
WARNING! You must install false ceilings and ceil-
ing restops at each oor of the chase or every 10 ft (3.05 m) to control spread of re.
WARNING! Risk of Fire! DO NOT sealareabetweenre
stop opening and chimney pipe except where they enter the attic or leave the warm air envelope of the home (use 600° F sealant).
• The chase is constructed using framing materials much the same as the walls in your home. A variety of siding materials may be used including brick, stone, veneer brick, or standard siding materials.
• In constructing the chase, several factors must be considered:
- Maintain a 2 in. (51 mm) air space around the
chimney.
- The chase top must be constructed of non-
combustible material.
- In cold climates, a restop spacer and attic insulation
shield should be installed in an insulated false ceiling at the 8 ft. (2438 mm) level above the replace assembly. This reduces heat loss through the chase.
- In cold climates, the walls of the chase should be
insulated to the level of the false ceiling as shown in Figure 3.4. This will help reduce heat loss from the home around the replace.
Round Termination Cap
Storm Collar
Metal Chase Top
Ceiling
Firestop
False Ceiling
Attic
Tabs
Insulation
False Ceiling
Figure 3.4 Chase Assembly
WARNING! Risk of Fire!
Insulation
Shield
Ceiling
Firestop
Insulation
False Ceiling
Chimney
Insulation in the
outside walls
of the chase
You must maintain a mini-
mum 2 in. (51 mm) air space clearance to insula­tion and other materials surrounding the chimney system.
• Insulationandothermaterialsmustbermlysecuredto
prevent accidental contact with chimney system.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and
makingcontactwithreplaceorchimney.
• Failure to prevent contact between insulation or other materials and chimney system may cause overheating
andre.
Three examples of chase applications are shown in Fig­ure 3.5.
1. Fireplace and chimney enclosed in an exterior chase.
2. Chimney offset through exterior wall and enclosed in chase.
3. Chase constructed on roof.
All outside walls should be insulated.
1 2 3
Figure 3.5 Chase Constructions
12 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
D. Unpack the Fireplace (SB60 only)
Front Face
Smoke Shield
Remove these screws.
Skip
Skip
• SB60 is shipped with refractory in place.
• Remove packaging.
• Remove shipping brackets as shown in Figure 3.12. Replace the screws removed from the replace.
• Remove SB60 from pallet and set aside.
• Skip to F. Frame the Fireplace.
E. Unpack the Fireplace (SB80 only)
We recommend two installers for hearth stone and refrac- tory installation!
Remove back refractory from outside of replace by
bending tabs up and lifting refractory out of brackets. See Figure 3.6.
Figure 3.6 Unpacking Back Refractory
• Bend tabs back down out of the way. See Figure 3.7. Do not remove screws or brackets from replace. If brackets are removed, ll holes in outer shell with screws.
• Repeat this process to remove side refractories.
Figure 3.9 Removing the Screen Rods
Remove hearth stone by removing three corrugated shipping spacers (Figure 3.10). Lift hearth stone out of replace. See Figure 3.11.
Figure 3.10 Shipping Spacers
Figure 3.7 Bending Refractory Shipping Tabs
Back Down
Remove smoke shield by removing ve screws. See Figure 3.8. Smoke shield is located at top of replace
front.
• Remove screens by removing screw from the end of each screen rod. See Figure 3.9.
Figure 3.8 Removing Smoke Shield
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Figure 3.11 Lifting Out the Hearth Stone
Remove replace from pallet. The replace is attached to pallet with two brackets on
each side and rear of outer shell. See Figure 3.12.
• Remove screws from bracket, pallet and fireplace. Replace screws removed from replace.
Figure 3.12 Removing Shipping Brackets
13
F. Frame the Fireplace
NOTICE: Hearth extension design must be determined before installation of replace.
If the replace is placed on the oor the maximum height of a nished raised hearth is 7-5/8 in., if you want a higher raised hearth the replace must be placed on a
platform.
Figure 3.12 shows a typical framing (using 2 x 4 lumber) of the replace, assuming combustible materials are used. All required clearances to combustibles around the replace must be adhered to. See Figure 3.3. Any fram­ing across the top of the replace must be above the level
of the top standoffs.
The
nished cavity depth must be no less than:
SB60 - 28 in. (711 mm) from the nished backwall to the outside of front wall framing.
SB80 - 28 1/2 in. (724 mm) from the nished backwall to the outside of front wall framing.
DO NOT install header until the replace is in position.
WARNING! Risk of Fire! Comply with all minimum clear-
ancesspecied.
• SB60 - A minimum 1 in. (25 mm) air clearance must
be maintained at the back and sides of the replace
assembly.
• SB80 - A minimum 1 1/2 in. (38 mm) air clearance must
be maintained at the back and sides of the replace
assembly.
Chimney sections at any level require a 2 in. (51 mm)
minimum air space clearance between the framing and chimney section.
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles. DO NOT pack required air spaces with insulation or other materi­als.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
WARNING! Risk of Fire! Prevent contact with sagging, loose insulation.
DO NOT install against vapor barriers or exposed insulation.
• Secure insulation and vapor barriers.
• Provide minimum air space clearances at the sides and
backofthereplaceassembly.
17 in. (368 mm) framing.
Header will sit on top of front stand offs after fireplace is installed.
Fireplace must be set out
1/2 in.
(13 mm)
Header MUST NOT be notched!
C = extra space needed for outside air connection. If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.
1/2 in. (13 mm) in front of the face of the framing material.
C
A
B
Model A B*
in.
SB60
SB80
45 1/2 28 8
mm
mm
1156 711 203
in.
51 1/2 28 1/2 8
1308 724 203
C
(4" duct)
* If interior of chase will be drywalled, add the thickness to
this measurement.
Figure 3.13 Framing the Fireplace
14 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
G. Secure and Level the Fireplace
This replace may be placed on either a combustible or noncombustible continuous at surface. Shipping brackets can be used to anchor the replace.
Slide the replace into position. Be sure to provide the min­imum 1 in. air clearance (SB60) or 1 1/2 in. air clearance (SB80) at the sides and back of the replace.
The replace should be positioned so the face of the re­place will be ush with the face of the drywall on the walls.
Level the replace and shim as necessary.
1 in. (25 mm) overlap
Protective metal strips are placed 2 in. (51 mm) under the front of the fireplace and must extend beyond the front and sides of fireplace opening by 2 in. (51 mm).
H. Protective Metal Hearth Strips
WARNING! Risk of Fire! Protective metal hearth
strips MUST be installed on combustible surfaces. DO NOT cover metal strips with combustible materials.
Sparksorembersmayigniteooring.
WARNING! Risk of re! High temperatures, sparks,
embers or other burning material falling from the
replacemayigniteooringorconcealedcombustible
surfaces.
• Protective metal hearth strips MUST be installed.
• Hearth extensions MUST be installed exactly as
specied.
• Locate the two protective metal hearth strips measuring approximately 26 in. x 4 in. (660 mm x 102 mm) included with this replace.
• Slide each metal strip 2 in. (51 mm) under front edge of replace.
• Overlap strips in the middle of replace opening by 1 in. (25 mm) minimum.
• Metal strips must extend beyond the front and sides of the replace opening by at least 2 in. (51 mm), Figure 3.14).
• Protect the front of a platform elevated above the hearth extension with metal strips (not included with replace) per Figure 3.15. See Section 7 for hearth extension instructions.
Figure 3.14 Position the Protective Metal Hearth Strips
Top piece must overlap
bottom piece
Raised Platform
2 in.
(51 mm)
Floor
2 in.
(51 mm)
Figure 3.15 Protect the Front of an Elevated Platform
1 in. (25 mm) min.
overlap
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
15
I. Outside Air Kit
An outside air kit must be used for combustion. Hearth & Home Technologies recommends you utilize the shortest duct run to optimize the performance of the outside air kit. The outside air inlet hood should be positioned in a manner that will not allow snow, leaves, etc. to block the inlet. In some installations the air duct may need to be run vertically. In such an installation, a 3 ft (914 mm) height difference must be maintained from the top of the upper­most chimney section to the outside combustion air inlet.
Refer to Figures 3.16 and 3.17 when placing the outside
air inlet hood.
The outside air kit is installed on the left hand side of the
replace.
• Cut a 4-1/2 in. (114 mm) hole in outside wall to accommodate air piping.
• Use 4 in. (102 mm) ex (not supplied) to directly connect outside air to replace intake. Insulated ex can be used to reduce frost condensation.
• Use the supplied outside air inlet hood.
• Seal between the wall and the pipe with silicone to
prevent moisture penetration and air leaks.
• Seal between the outside air inlet hood and the house with silicone to prevent air inltration.
CAUTION! Risk of Fire or Asphyxiation! DO NOT draw
outsidecombustionairfromwall,oororceilingcavity,or
enclosed spaces such as an attic or garage.
DO NOT place outside air inlet hood close to exhaust vents or chimneys. Fumes or odor could be drawn into
theroomthroughthereplace.
• Locate outside air inlet hood to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause combustion air starvation.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
3 ft min. from top of uppermost chimney section to air inlet.
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)))
)
))
)
)
)
))))
)
))
))
)))
)
)
))
))
))
)
))
)
))
)
)
)
))
)
)
)
)
))
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
Figure 3.16 Outside Air Inlet Locations
Note: Chimney
air kit and 11-10 in./279-254 mm
adapter are
not shown, but are required in
Canada.
NO
NO
Outlet blocked by
snow, leaves, etc.
Garage or
combustible
liquids storage
NO
Attic space
NO
Outlet placed
higher than 3 ft
below the
termination cap
YES
Clear area
outside
Factory-built
fireplace
house or in
ventilated
crawl space
• Use UL181 Class 1 or Class 0 rigid or flexible ducting.
• Install with short run or mainly straight duct, except small
dip for cold air trap which will help prevent flow of cold air.
• Secure flex duct with screws or wire ties.
Figure 3.17 Outside Air Installation
16 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Chimney and Termination Requirements
4
A. Chimney Requirements
Vertical distances are measured from the base of the replace as shown in Figure 4.1.
Table 4.1 Chimney Requirements
Minimum overall straight height 18 ft 5.49 m
Minimum height with single offset/ return
Double offset/return minimum height 24 ft 7.32 m
Maximum height 90 ft 27.43 m
Maximum chimney length between an offset and return
Maximum distance between chimney stabilizers
Maximum unsupported chimney length between the offset and return
Maximum unsupported chimney
heightabovethereplace
Maximum unsupported chimney above roof
18.5 ft 5.64 m
20 ft 6.1 m
35 ft 10.67 m
6 ft 1.83 m
35 ft 10.67 m
6 ft 1.83 m
NOTICE: A maximum of two pairs of offsets and returns may be used.
WARNING! Risk of Fire!
You must maintain 2 in. (51 mm) air space clearance to insulation and other combustible materials around the chimney sys­tem. Failure to do so may cause overheating and re.
NOTICE: You must provide support for the pipe during construction and check to be sure inadvertent loading has
notdislodged thechimneysectionfromthereplaceorat
any chimney joint.
6 ft (1.8 m) max. unsupported chimney
6 ft (1.8 m) max. unsupported run
20 ft (6 m) max. pipe between an offset & return
Attic Insulation
Shield
above roof
Table 4.2 Chimney Component Dimensions
HEIGHT OF CHIMNEY COMPONENTS in. mm
US Canada ONLY
Chimney Stabilizer
SL11 SL4 4-3/4 121
Offsets/Returns
SL1130 SL430 14-1/2 368
Chimney Sections*
SL1106 SL406 4-3/4 121
SL1112 SL412 10-3/4 273
SL1118 SL418 16-3/4 425
SL1136 SL436 34-3/4 883
SL1148 SL448 46-3/4 1187
n/a SLA10 16-3/4 425
* Dimensions reect effective height.
Ceiling Firestop
11-10 in./279-254mm
adaptor required in
Canada
CAK required in Canada but not shown
55-1/2 in.
(1410 mm)
Effective Height
(bottom of fireplace
to top of starter collar)
Figure 4.1 Chimney Requirements
35 ft (10.7 m) max. straight unsupported
chimney height
18.5 ft (5.6 m) min. height single offset-return
24 ft. (7.3 m) min. height
double offset-return
90 ft (27.4 m) max. height
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
17
B. Offsets/Returns
A
B
1-1/4 in. (32 mm)
OVERLAP
• Use an offset/return to bypass overhead obstructions.
• An offset and return can be used as a single entity or separated by chimney section(s).
WARNING! Risk of Fire! DO NOT use offset/returns greater than 30°. Chimney draft will be restricted and could cause
overheatingandre.Secureoffsetswithscrews(nottoexceed1/2”/13mminlength)Securereturnswithstrapping.
Straight chimney sections may be secured with screws. Keep chimney sections from separating or twisting.
• Measure the shift needed to avoid the overhead obstruction. Refer to dimension A in Figure 4.2.
• Find the appropriate A dimension listed in Table 4.3. The B dimension coinciding with the A dimension measurement in Table 4.3 represents the required vertical clearance needed to complete the offset/return.
• Read across the chart to nd the number of chimney sections/model numbers needed between the offset and return.
Example:
Your “A” dimension from Figure 4.2 is 14-1/2 in. (368 mm). Using Table 4.3 the dimension closest to, but not less than 14-1/2 in. (368 mm) is 15-3/4 in. (400 mm) using a 30° offset/return.
You determined from the table that you would need 36-5/8 in. (930 mm) (Dimension “B”) between the offset
and return.
The chimney component that best ts your application is
Figure 4.2 Chimney Offset/Return
two SL1112s.
Table 4.3
A B
4 7/8 124 17 7/8 454 - - - - -
7 1/4 184 22 559 1 - - - -
9 3/4 248 26 1/8 664 2 - - - -
10 1/4 260 27 1/4 692 - 1 - - -
12 3/4 324 31 3/8 797 1 1 - - -
13 1/4 337 32 3/8 822 - - 1 - -
15 3/4 400 36 5/8 930 - 2 - - -
18 1/8 460 40 3/4 1035 1 2 - - -
18 3/4 476 41 3/4 1060 - 1 1 - -
21 3/4 552 47 1194 - - 2 - -
22 1/4 565 48 1219 - - - 1 -
24 3/4 629 52 1/8 1324 1 - - 1 -
27 3/4 705 57 3/8 1457 - 1 - 1 -
28 1/4 718 58 3/8 1483 - - - - 1
30 3/4 781 62 1/2 1588 1 - - - 1
33 3/4 857 67 3/4 1721 - 1 - - 1
36 3/4 933 73 1854 - - 1 - 1
39 3/4 1010 78 1/8 1984 - - - 2 -
41 1/8 1045 82 3/8 2092 1 - - 2 -
45 3/4 1162 88 1/2 2248 - - - 1 1
48 1/8 1222 92 3/4 2356 1 - - 1 1
51 3/4 1314 98 7/8 2511 - - - - 2
Proper assembly of air cooled chimney parts results in an overlap of chimney joints of 1-1/4 in. (32 mm). Effective length is built into this table.
SL1106
SL406
SL1112
SL412
SL1118
SL418
SL1136
SL436
SL1148
SL448in. mm in. mm
Note: SL400 series pipe available
for Canada ONLY.
18 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
If using decorative cap cover(s), this distance may need to be In a staggered installation with both gas and wood terminations, the
C. Termination Requirements
• Install a cap approved and listed for this replace system.
• Locate cap where it will not become plugged by snow or other materials.
• Locate cap away from trees or other structures.
• The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m).
• The distance required between caps is shown below.
Slanted Roofs
Chimney must extend 2 ft (.6 m)
Chimney must extend 3 ft (.9 m) above the roof
above any portion of the roof or adjacent structures within 10 ft (3 m) of the chimney
Flat Roofs
Chimney must extend 3 ft (.9 m) above the roof
Multiple Chimney Locations
Gas
Termination
Cap **
Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within 10 ft (3 m) of the chimney
Gas, Wood or Fuel Oil
Termination Cap
B
A *
Wood
Minimum
(See
illustration
above)
Perpendicular Wall
Figure 4.3 Multiple Chimney Locations
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
**
wood termination cap must be higher than the gas termination cap.
19
Chimney Installation
5
A. Typical Chimney System
NOTICE: Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect performance.
• Chimney height may need adjustment if smoking or overdraft occurs.
Chimney must extend beyond combustible roof structure
Maintain minimum height of chimney above roof
Install roof flashing according to minimum requirements
Offsets/returns may not exceed 30° from vertical
Lock chimney sections together firmly to resist movement
Termination Cap
Additional support for tall chimneys
Storm Collar
Maintain minimum clearances to combustibles as specified
Support straps for offsets (not shown) must be secured to adequate framing
Offsets/returns must be secured with screws (outer pipe only)
Attic shield
Ceiling firestops are required where chimney passes through ceiling or floor
Figure 5.1 Typical Chimney System - Guidelines for Chimney System Installation
20 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
B. Assemble Chimney Sections
Use only those components described in this manual.
Substitute or damaged chimney components could impair safe operation and cause overheating and re.
Attach either a straight chimney section or an offset to the top of the replace (depending on your installation requirement). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.
The inner ue is placed to the inside of the ue section below it. The outer casing is placed outside the outer cas­ing of the chimney section below it. See Figure 5.2.
NOTICE: Chimney sections cannot be disassembled once locked together. Plan ahead!
• Lock chimney sections and/or offsets/returns together by pushing downward until the top section meets the stop bead on the lower section.
• Pull on the top section to make sure it is fully engaged
and will not separate.
• You may use #6 or #8 sheet metal screws no longer than 1/2 in. (13 mm) to fasten chimney sections together. Do NOT penetrate inner ue.
C. Install Chimney Air Kit
• Required in Canada.
• Follow instructions included with accessory.
WARNING! Risk of Fire! You MUST use screws to
fasten offset/returns to chimney sections to keep the chimney parts from twisting. Failure to do so could
causere.
• Fasten offset/returns to chimney sections. Do NOT penetrate inner ue.
• Secure chimney returns with hanger straps provided;
fasten to studs or joists.
• Vertical straight runs of chimney must be supported every 35 ft (10.7 m).
Figure 5.2 Assembling Chimney Sections
WARNING! Risk of Fire! DO NOT install substitute or damaged chimney components.
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
21
D. Secure Offset/Return
When offsets and returns are joined to straight pipe sec­tions, they must be locked into position with the screws (outer only). To prevent gravity from pulling the chimney sections apart, the returns and the chimney stabilizers have hanger straps for securing these parts to joists or rafters. See Figure 5.3.
* Use # 6 or # 8 sheet metal screw, or larger, no longer
than 1/2 in. (13 mm).
WARNING! Risk of Fire!
• Secure offsets with screws (not to exceed 1/2 in./13 mm
In length).
• Secure returns with strapping.
• Straight chimney sections may be secured with screw
(not to exceed 1/2 in./13 mm In length) at the joints.
• Keep chimney sections from separating or twisting.
Ceiling
Straps
Optional Additional Support
Firestop
Joint
Band
(Optional)
ROOM ABOVE (non-insulated ceiling)
B
Ceilng firestop
attached to bottom
of framing
2 in. (51mm)
clearance
ATTIC ABOVE (insulated ceiling)
Ceiling firestop
attached to top of
framing
2 in. (51mm)
clearance
Note: Use same dimensional lumber for framing
ceiling firestop and joists.
A B
Catalog #
FS538 17 432 17 432
FS540 17 432 26 660
in. mm in. mm
A
Figure 5.3 Secure the Chimney
E. Install Ceiling Firestops
CAUTION! Risk of Fire! Ceilingrestopsmustbeused
wheneverthechimneypenetratesaceiling/oor.
• Chaseconstructionrequiresceilingrestopsateach
oororevery10ft.(3.05m)ofclearspace.
• Theceilingrestopslowsspreadofreandreduces
coldairinltration.
• Install a ceiling restop whenever chimney penetrates ceiling/oor.
• Mark and cut an opening in ceiling as shown in Figure 5.4.
• Frame the opening with the same size lumber used in the ceiling joists.
• Nail the ceiling restop to the bottom of the ceiling joists when there is a room above.
• Use an attic insulation shield if the ceiling is insulated. The ceiling restop may then be attached above or below
the joists.
Figure 5.4 Installing the Ceiling Firestop
WARNING! Risk of Fire! DO NOT seal area between
restopopeningandchimneypipeexceptwheretheyen­ter the attic or leave the warm air envelope of the home (use 600° F sealant).
22 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Insert three
screws
Pre-bend the tabs to rest against pipe to prevent insulation from falling in.
(5)Tabs bent
in 90°
F. Install Attic Insulation Shield
WARNING! Risk of Fire! You MUST install an attic insu­lation shield when there is any possibility of insulation or other combustible material coming into contact with the chimney.
DO NOT pack insulation between the chimney and the attic insulation shield.
• Failure to keep insulation and other materials away from
chimneypipecouldcausere.
DO NOT offset chimney inside insulation shield.
Combustible material may come in contact with the attic
insulation shield as long as the required clearances are maintained to the chimney pipe.
Installation of a ceiling restop is required:
• Refer to Figures 5.5, 5.6, 5.7.
If the attic shield is pre-rolled continue. If it is a at part,
try and roll it up to aid in wrapping it around the chimney.
Pre-bend all the tabs in at the top to 45°.
• Wrap the shield (around the chimney if already installed) until you have an overlap and the three holes on each side match up (large holes on top).
• Insert three screws into the matching holes to form a tube starting at the bottom.
• Bend the tabs on the bottom of the tube inward to 90° to maintain chimney air space.
• Rest the insulation shield on the ceiling restop below.
Tape off any opening around the bottom.
Figure 5.6 Prepare Attic Insulation Shield
Pipe
2 in. (51 mm)
air space
5 Tabs bent
in 90°
Tabs bent in to
rest against pipe
Attic Insulation Shield
17 in. (432 mm)
diameter
Ceiling Firestop
If you wish to make a custom shield or barrier, follow these guidelines:
• Metal is preferred, although any material stiff enough to
hold back the insulation can be used.
WARNING! Risk of Fire! Use of cardboard or other
materialsthatcandeectunderhumidityorotherenvi­ronmental conditions is not recommended.
• The shield or barrier must be tall enough to extend
above the insulation and prevent blown-in insulation from spilling into the cavity.
• Maintain specied air spaces around chimney.
• Check instructions and local codes for further details.
Double-check the Chimney Assembly
Continue assembling the chimney sections up through the ceiling restops as needed. While doing so, be aware of the height and unsupported chimney length limitations given under Section 5.
Check each section by pulling up slightly from the top to ensure proper engagement before installing the suc­ceeding sections. If they have been connected correct­ly, they will not disengage when tested.
Pipe
13 in.
(330 mm)
Figure 5.7 Install Attic Insulation Shield (restop above ceiling)
Pipe
2 in. (51 mm)
air space
5 Tabs bent
in 90°
13 in.
(330 mm)
Figure 5.8 Install Attic Insulation Shield (restop below ceiling)
Pipe
InsulationInsulation
Seal with tape
Tabs bent in to
rest against pipe
Attic Insulation Shield
17 in. (432 mm)
diameter
InsulationInsulation
Ceiling Firestop
Seal with tape
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
23
G. Roof Penetration
• Refer to Figure 5.8.
• Plumb from roof to center of chimney.
• Drive a nail up through roof to mark center of pipe.
• Measure to either side of nail and mark the 17 in. x 17 in.
(432 mm x 432 mm) opening required.
• Measure opening on the horizontal; actual length may
be larger depending on roof pitch.
• Cut out and frame opening.
Install Flashing
• Assemble chimney so it passes through the framed
opening.
• Slip the ashing over the chimney.
NOTICE: Roongshingles mustbe belowthe ashing
plate on the lower side of a sloped roof and over the
ashingplateonthesidesandtop.
• Nail the ashing to the roof. Keep gaps between the
ashing plate and the roof to a minimum.
• Caulk the ashing plate and roof junction as well as
the vertical seam on the ashing. All nail heads must be caulked with a roong sealant.
• Caulk the overlap seam of any exposed pipe sections
that are located above the roof line to prevent leaks.
Figure 5.8 Ceiling/Attic Construction
H. Install Chase/Chase Top
• You MUST use a chase top in a chase installation. Chase tops may be eld constructed.
• Include a turndown and drip edge to prevent water from seeping into the chase.
• Include a 2 in. (51 mm) soldered, welded or spun collar around pipe opening to keep water out.
• Provide a 1/8 in. (3 mm) gap around the ue pipe.
• Slope the chase top downward away from the opening.
WARNING! Risk of Fire! DO NOT caulk the pipe to the
chase top collar.
• Caulk all seams to prevent leaks.
Slope Downward (1/4 in. per foot minimum)
Figure 5.9 Chase Top Construction
2 in. (51 mm) Collar on Chase Top
Turn-down
Drip Edge
Chase
.018 (26 ga) min. Galvanized Chase Top
24 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
I. Termination Cap Requirements
Storm Collar
Chimney
Pipe
Chase Top
Termination
Cap
Chase
4 3/4 in. (121 mm)
Maximum
Collar
2 in. (51 mm)
Minimum Height
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Do NOT block air
holes
3 clip brackets.
Slip over chase collar
and attach with screws
provided.
Assemble
storm collar
around extended
termination cap
pipe
once cap is
installed.
The last section of pipe must stop between 2 in. (51 mm) above the top of the chase and 4 3/4 in. (121 mm) below the top of the chase.
2 in. (51 mm)
maximum
• Install a cap approved and listed for this replace system.
• Locate cap where it will not become plugged by snow
or other materials.
• Locate cap away from trees or other structures.
• The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m).
J. Install Termination Cap
Install the chimney sections up through the chase enclo­sure.
Caulk the overlap seam of any exposed pipe sections
that are located above the roof line to prevent leaks.
Refer to termination cap instructions.
WARNING! Risk of Fire! The minimum overlap of cap
to pipe (as shown in the following illustrations) MUST be met or chimney may separate from cap. Separation allows sparks, heat and embers to escape.
NOTICE: Paint the termination cap with a rust-resistant
paint to protect against the effects of corrosion on those parts exposed to the weather.
Figure 5.11 I
nstalling TR11T-B Round Telescoping Termination Cap
Note: 400 Series Termination Caps available Canada
ONLY.
around chimney pipe
cap pipe is snapped
Figure 5.10 Installing a TR11/TR444 Round Termination Cap
Termination
Cap
Slip
storm collar
before termination
into the chimney
pipe.
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Storm Collar
Do NOT
block air holes
6 in. (153 mm)
Minimum top of
chase to top of
chimney pipe
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1-1/2 in. (38 mm).
Chimney
Pipe
Chase
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Flange
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Termination Cap
Chimney
Pipe
Place waterproof caulk or sealer under each flange of the termination cap and on top of each screw to help prevent leaks.
The last section of pipe must stop between 2 in. (51 mm) above the top of the chase and 4 3/4 in. (121 mm) below the top of the chase.
2 in. (51 mm)
maximum
4 3/4 in. (121 mm)
maximum
Chase
Figure 5.12 Installing an ST1175 Square Termination Cap
25
Storm Collar
Chimney
Pipe
Chase Top
Termination
Cap (not shown)
Chase
Collar
2 in. (51 mm)
Minimum Height
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Do NOT block
air holes
3 clip brackets.
Slip over chase collar
and attach with screws
provided.
Assemble
storm collar
around extended
termination cap
pipe
once cap is
installed.
CT
4-3/4 in. (121 mm)
2 in. (51 mm)
The last section of pipe must stop between 2 in. (51 mm) above the top of the chase and 4 3/4 in. (121 mm) below the top of the chase.
Remove 2 screws
from front & back
to lift the top off
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Termination Cap
Place waterproof sealer under each flange of the termination cap and on top of each screw to help prevent leaks.
The last section of pipe must stop between 2 in. (51 mm) above top of chase and 4-3/4 in. (121 mm) below top of chase
2 in. (51 mm)
4-3/4 in. (121 mm)
Chimney
Pipe
Chase
Figure 5.13 Installing a TCT1175 Terra Cotta Cap
Figure 5.14 Installing a DTO/DTS Decorative Termination Cap
26 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
6
Shrouds
WARNING! Risk of Fire! Shrouds must be constructed
asspecied.Improperconstructionmayoverheat
chase top.
Shrouds may be eld constructed where permitted by regional building codes.
NOTICE: Some regional codes require an agency-Listed
shroud.Consultyourlocalbuildingofcials.
The shrouds must be constructed from minimum .018 in. (26 ga) thick aluminzed steel.
Some shrouds require a radiation shield. Use where specied.
A. Radiation Shield
Radiation shield must be constructed of minimum 26 ga thick sheet metal.
Ø 17 1/2 in. (444.5 mm) Round Hole to fit over cap
3 in. (76 mm) tall legs
Length x Width to fit inside shroud
Figure 6.1 Radiation Shield
B. Field Constructed Shrouds
The following eld constructed shroud designs have been tested for HHT replace systems and termination caps.
1. Open Top Shroud
TR11/TR11T TV (top vented) caps do not require radia­tion shield.
Min.
Top Dim.
Min.
Top Dim.
14 1/2 in. (368 mm)
maximum height
3 in (76 mm) minimum
Min. Opening
Width
Min.
Base Dim.
TR11/11T TR11/11T TV
Min. Base Dims.
in 32 x 32 26 x 26
mm 813 x 813 660 x 660
Radiation Shield
Required
Min. Top Dims.
in 29 x 29 23 x 23
mm 737 x 737 584 x 584
Min. Opening Width
in 26 x 26 20 x 20
mm 660 x 660 508 x 508
Figure 6.2 Open Top Shroud Dimensions (with Radiation Shield)
Min.
Base Dim.
Radiation
Shield Not
Required
TR11/TR11T caps require radiation shield unless in­stalled partially above the shroud. The TR cap must be raised to the minimum dimensions (or greater) above the shroud. Refer to Figure 6.3.
Radiation
Shield
Min. Opening
Width
(TR Series)
Maximum Height
14 1/2 in. (368 mm)
Shroud
Leg
Figure 6.3 Shroud & TR Series cap with no Radiation Shield
(SHROUD)
Flue
Chase Top
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
6" Min.
Above the
Shroud.
Storm
Collar
Shroud
Leg
3 in (76 mm) air space from bottom of shroud to top of chase.
27
2. Mailbox Style Shroud
Radiation shield required
Min. Height
above bottom of
termination
cap
Radiation
Shield
Figure 6.4 Mailbox Style Shroud Dimensions
Min.
Base Dim
3 in. (76 mm) Min.
Radiation Shield Height
from top of Chase
Minimum
Opening Height
3 in. (76 mm)
Min. Opening Height
Min, Base Dim
Min, Opening Width
TR11/11T TR11/11T TV
Min. Base Dims.
in 34 x 34 28 x 30
mm 864 x 864 711 x 762
Min. Height Above Bottom of
Termination Cap
in 28-1/4 27-1/2
mm 718 698
Min. Opening Width
in 28 22
mm 7 11 559
Min. Opening Height
in 18-1/4 17-1/2
mm 464 445
3. Roofed Style Shroud
Radiation shield required
Minimum
Height above
Bottom of Termination Cap
3 in. (76 mm)
Radiation
Shield Height
Min. Base Dimension
Termination
Cap
Radiation Shield
Chase Top
Minimum Opening
Height
Minimum
Base Dimension
Min. Opening Width
TR11/11T
TR11/11T TV
Min. Base Dims.
in 34 x 34
mm 864 x 864
Min. Height
Above Bottom of
Termination Cap
in 23
mm 584
Min. Opening Width
in 28
mm 7 11
Min. Opening Height
in 12
mm 305
Figure 6.5 Roofed Style Shroud Dimensions
28 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Finishing
These metal surfaces may be covered with non-combustible material.
Non-combustible sealant around edge of fireplace and drywall.
Metal strips are placed 2 in. (51 mm) under the front of the fireplace and must extend beyond the front and sides of fireplace opening by 2 in. (51 mm)
Continuous, non-combustible sealant
Floor constructed of wood or other combustible material
HX4 Hearth Ext or equivilent insulation
Hearth Refractory
Finished combustible wall
Combustible material
Non-combustible decorative facing
2 x 4 header, flush with front of stand-offs
Non-combustible material
Tile, stone or other non-combustible material
Flat 2 x 4 stud wall
7
A. Finishing Material
Refer to Section 1 for combustible/non-combustible mate­rials. Refer to Figure 7.1 for noncombustible zone.
WARNING! Risk of Fire! You must maintain clearances.
• Use only non-combustible framing material below standoffs.
• Sheetrock, wood or other combustibles must NOT be used as sheathing or facing in the noncombustible zone.
DO NOT cover metal replace front withcombustible materials.
• Installcombustiblematerialsonlytospeciedclearances
on top front and side edges.
Figure 7.1 Noncombustible Facing
Figure 7.2 Decorative Facing
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
29
B. Hearth Extension, Building and Fin-
ishing
WARNING! Risk of Fire! High temperatures, sparks,
embersorotherburningmaterialfallingfromthere­place may ignite ooring or concealed combustible
surfaces.
• Protective metal hearth strips MUST be installed.
• Hearth extensions MUST be installed exactly as
specied.
WARNING! Risk of Fire!
• Maintain clearances.
• Use only non-combustible material below standoffs, material such as cement board is acceptable.
• Framingornishingmaterialusedonthefrontofthereplace
closer than the minimums listed, must be constructed entirely of non-combustible materials (i.e., steel studs, concrete board, etc.).
WARNING! Risk of Fire!
A hearth extension must be installed with all re­places to protect the combustible oor in front of the replace from both radiant heat and sparks.
• You MUST use a hearth extension with this replace.
• Refer to Figure 7.3 for minimum dimensions.
• This replace has been tested and approved for use with a hearth extension insulated to a minimum R value of 1.03.
• The hearth extension material MUST be covered with tile, stone or other non-combustible material.
• Manufactured hearth materials will usually have a published R value (resistance to heat) or k value (conductivity of heat). Refer to the formula in Table
7.1 to convert a k value to an R value,
• Refer to Table 7.2 for hearth extension insulation
alternatives.
WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for
discoloration, cracking or other material failures of
nishingmaterialsduetoheatexposureorsmoke.
Hearth extensions are to be installed only as illustrated to prevent high tempertures from occurring on concealed combustible materials.
Table 7.1
R = 1/k x inches of thickness
Table 7.2
Hearth Extension Insulation Alternatives, R Value = 1.03
Material
Hearth & Home HX3, HX4 0.49 2.06 1/2 in.
USG Micore 300™ 0.49 2.06 1/2 in.
USG Durock™ Cement Board 1.92 0.52 2 in.
Cement Mortar 5.0 0.20 5 1/8 in.
Common Brick 5.0 0.20 5 1/8 in.
Ceramic Tile 12.50 0.08 12 1/4 in.
Armstrong™ Privacy Guard Plus 0.46 2.18 1/2 in.
Marble 14.3-20.0 0.07-0.05 14 5/8 in. - 20 3/8 in.
k per inch
thick
r per inch
thick
Minimum
thickness
required
• Choosenishingmaterialscarefully.
SB60 36 60
SB80 42 66
Figure 7.3 Hearth Extension Dimensions
A B
12 in.
(305 mm)
A
B
12 in.
(305 mm)
20 in. (508 mm)
minimum
30 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Noncombustible Framing Material
HX4 or equivalent
Non-combustible Finishing Materials
1. Fireplace Installed Flush on the Floor and
Hearth Extension Raised to Bottom of Firebox Opening
Non-combustible ooring a minimum of 20 in. (508 mm) in front of and 12 in. (305 mm) to each side of the fuel opening is required (see Figure 7.5).
The hearth framing must be constructed of non-com­bustible materials (such as metal framing or equivalent material) and placed on HX3(s), HX4(s), or equivalent
material.
When creating the platform, allow for the thickness
of the non-combustible nishing materials.
Seal gaps between the hearth extension and the front of the replace with a bead of non-combustible sealant or grout.
Note: Maximum height from floor under fireplace to top of finished hearth extension is 7 5/8 in.
Bottom of fireplace opening
Continuous, non-combustible sealant
Note: The bottom of the fireplace opening is 7-5/8 in. (194 mm) above the bottom of the fireplace. Finished hearth must NOT extend above this level.
Noncombustible Finishing Material
Noncombustible Framing Material
1/2 in. Micore
or equivalent
insulation
Figure 7.5 Raised Platform Hearth Extension Detail
20 in. Min.
Hearth Extension
Protective Metal
Hearth Strips
Floor
Tile, stone or other non-combustible material
1/2 in. Micore
or equivalent
insulation
2 in. (51 mm) Floor constructed of wood or other combustible material
Figure 7.4 Hearth Extension Construction
required
Protective Metal Hearth Strip
Figure 7.6 Raised Platform Hearth Extension-Framing
Figure 7.7 Raised Platform Hearth Extension-Finishing
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
31
2. Raised Hearth Extension and Raised Fire­place
Non-combustible ooring a minimum of 20 in. (508 mm) in front of and 12 in. (305 mm) to each side of the fuel opening is required.
The hearth framing must be constructed of non-com­bustible materials (such as metal framing or equivalent material) and placed on HX4, or equivalent material. See Figure 7.8.
When creating the platform, allow for the thickness
of the non-combustible nishing materials.
Seal gaps between the hearth extension and the front of the replace with a bead of non-combustible sealant or grout.
Continuous, non-combustible sealant
Tile, stone or other non-combustible finishing material
20 in. minimum Hearth Extension
1/2 in. Micore or equivalent insulation
Note: The bottom of the fireplace opening is 7-5/8 in. (194 mm) above the bottom of the fireplace. Finished hearth must NOT extend above this level.
Platform must be built to raise the bottom of the fireplace opening to the level of the desired hearth height.
Protective Metal
Hearth Strips
Non-combustible
Framing Material
Figure 7.8 Raised Hearth Extension and Fireplace Framing Materials
Floor and platform constructed of wood or other combustible material
32 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
3. Fireplace Opening and Hearth Extension
Noncombustible Material
Protective Metal
Hearth Strip
20 in. Min. Hearth Extension
1/2 in. Micore
or equivalent
insulation
Finished
Floor
Note: The bottom of the fireplace opening is 7-5/8 in. (194 mm) above the bottom of the fireplace. Finished hearth must NOT extend above this level.
Non-combustible Sealant
Flush with the Floor
Non-combustible ooring a minimum of 20 in. (508 mm)
in front of and 12 in. (305 mm) to each side of the fuel opening is required.
The hearth framing must be constructed of non-com­bustible materials (such as metal framing or equivalent material) and placed on HX3(s), HX4(s), or equivalent
material.
When creating the platform, allow for the thickness
of the non-combustible nishing materials.
Seal gaps between the hearth extension and the front of the replace with a bead of non-combustible sealant or grout.
C. Non-Combustible Sealant Material
After completing the framing and applying the facing
materials over the framing, a bead of non-combustible sealant must be used to close off any gaps at the top and sides between the replace and hearth.
Figure 7.10 Place Non-combustible Sealant
Figure 7.9 Flush Hearth Extension Side View
WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for
discoloration, cracking or other material failures of
nishingmaterialsduetoheatexposureorsmoke.
• Choosenishingmaterialscarefully.
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
33
A B
Model
D. Sidewalls/Surrounds
• Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from replace opening.
• Mantle leg, surround, stub wall, whether combustible or non-combustible, may be constructed as shown in Figure 7.11.
Grid represents 1 inch scale.
FLUSH FRONT
A
22 3/8 in. [568 mm]
50° angle
B
BRICK
FRONT
39° angle
4 in.
[102 mm]
19 3/4 in. [502 mm]
24 in.
[610 mm]
Figure 7.11 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)
24 in.
[610 mm]
SB60
SB80
inches
mm
inches
mm
36 44 1/2
914
1130
42 50 1/2
1067 1283
34 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
E. Mantel and Wall Projections
The combustible mantel may have a maximum depth of 12 in. (305mm). Positioned 12 in. (305mm) above the open­ing. Combustible trim pieces that project no more than 3/4 in. (19 mm) from the face of the replace can be placed no closer than 6 in. (152 mm) from the top of the opening. Combustible trim must not cover:
• the metal surfaces of the replace
• where the non-combustible board is placed over the metal surfaces
• the space between the metal face of the replace and framing members
WARNING! Risk of Fire!
• Youmustsealaroundthenishingmaterialtoreplace.
Combustible Wall
2 x 4 stud wall
Standoffs
Non-combustible Decorative Facing such as: Steel, iron, brick, tile, concrete, slate, tile, plasters DO NOT cover any air openings in the face of the fireplace.
Seal joint with non-combustible sealant to prevent heat from being drawn into the wall cacity
Combustible Decorative Facing
12 in./305 mm
12 in./305 mm
minimum
6 in./152 mm
1 1/2 in./
38 mm
maximum
Measured from top of fireplace opening
minimum
Grid represents 1 in. squares
7 ft (2134 mm)
minimum
base of fireplace
to ceiling
Figure 7.12 Mantel Specications
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
35
Fireplace Setup
Firebox
Repack insulation knockout
Combustible materials
Maintain air clearance to combustibles.
Gas line
Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.
Gas line
1 1/2 in. (38 mm) air space around pipe
Refractory
Seal with fireplace mortar or non-combust­ible sealant
4 in.
(102 mm)
Outer shell of fireplace
8
A. Gas Log/Lighter Provision
WARNING! Fire and/or Asphyxiation Risk! Use with
solidwoodfuelordecorativegasapplianceonly.Gasre
generates fumes.
A certied gas log lighter or decorative gas log set can be installed in this replace.
• Maximum input is 100,000 BTU/hr.
• Decorative gas appliance must be certied to ANSI Z21.60/CSA 2.26 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.
• Must be installed in accordance with the National Fuel
Gas Code, ANSI Z223.1 and Natural Gas Installation Code, CAN/CGA-B149.1-M95 or the Propane Installation Code, CAN/CGA-B149.2-M95.
• A gas log set must incorporate a gas shutoff.
• Gas Log set requires the damper to be locked fully open.
• A listed automatic damper system with safety interlock may be used in this replace with only compatible, listed gas log sets. See damper system manufacturer’s instructions.
• Knockouts are provided on both sides of the replace and in refractories for 1/2 in. (13 mm) iron pipe.
• Seal refractory around pipe with replace mortar or a non-combustible sealant.
Figure 8.1 Gas Line Installation
Unvented Gas Logs
CAUTION! If an unvented gas appliance is installed in
the replace, the gas appliance must only be operated with the replace glass door fully open (if included). Only unvented gas log sets which have been found to comply with the standard for unvented room heaters, ANSI Z211.11.2, are to be installed in this replace. If an unvented gas appliance is installed it must incorpo­rate an automatic shutoff device, and must be installed in accordance with the National Fuel Gas Code Z223.1,
Latest edition.
B. Wood Burning Inserts
WARNING! Risk of Fire! Improper installation of wood in-
sertsmaycausereplaceorchimneysystemtooverheat.
If a wood burning insert is being installed in this replace, Hearth & Home Technologies recommends full reline of the chimney.
• Cooling air openings at the top of the chimney must not be obstructed in any manner.
• Hearth & Home Technologies recommends securing the reline at the top of the ue and using the cap certied for use with this replace system.
36 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
C. Install the Refractory (SB80 only)
We recommend two installers for hearth stone and refrac- tory installation!
Note: Before installing refractories and hearth stone, be sure all back edges of each piece are smooth to ensure proper t. Scrape away excess with a regular screwdriver. See Figure 8.2.
Figure 8.2 Scrape Away Rough Edges
• Set back refractory into place, making sure refractory is centered and notches are to the bottom of rebox.
• Place grate brackets in outer two notches of refractory. See Figure 8.3.
Secure back refractory in place with a screw and bracket supplied in hardware package. See Figure 8.4.
Note: To ensure proper installation, gas knockouts in the side
re fractory sh ould b e po sitioned to wards bac k of r ep lace. S ee Figure 8.5.
GAS
KNOCKOUT
Figure 8.5 Gas Knockout
Tilt top of side refractory towards center of rebox when placing it into replace. Push side refractory towards back corner of replace until it ts tightly against back refractory.
Secure side refractory in place with a screw and bracket provided in the hardware package.
• Repeat these two steps for installation of the other side
refractory.
When placing hearth stone into replace, slide it back until it ts tightly against back refractory (underneath grate brackets). See Figure 8.6.
GRATE BRACKETS
Figure 8.3 Back Refractory with Grate Brackets in Place
REFRACTORY
BRACKET
GRATE BRACKET
Figure 8.6 Sliding Bottom Refractory Towards
Back of Fireplace
Place grate into grate brackets. See Figure 8.7.
Replace smoke shield.
GRATE BRACKET
Figure 8.7 Grate Secured in Grate Bracket
Figure 8.4 Attaching Back Refractory
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Replace left and right screens.
37
Reference Materials
9
A. Chimney Components
Catalog #
DescriptionUS CAN
CAK5A CAK5A Chimney Air Kit
ID4/ID6 ID4 Insulated Duct/Outside Air
UD4/UD6 UD4 Uninsulated Duct/Outside Air
SLA10 11-10 in. (279-254mm) Adapter
SL1106 SL406 Chimney Section - 6 in. (152 mm) long
SL1112 SL412 Chimney Section - 12 in. (305 mm) long
SL1118 SL418 Chimney Section - 18 in. (457 mm) long
SL1136 SL436 Chimney Section - 36 in. (914 mm) long
SL1148 SL448 Chimney Section - 48 in. (1219 mm) long
SL11 SL4 Chimney Stabilizer
SL1130 SL430 Chimney Offset/Return - 30 deg
FS538 FS538 Ceiling Firestop - Straight
FS540 FS540 Ceiling Firestop - 30 deg
AS10 AS10 Straight Attic Insulation Shield, 24 in. (610 mm)
JB577 JB577 Chimney Joint Band
CB576 CB576 Chimney Bracket
RF570 RF570 Roof Flashing - Flat to 6/12 Pitch
RF571 RF571 Roof Flashing - 6/12 to 12/12 Pitch
TR11 TR444 Round Termination Cap
TR11T-B TR442 Round Telescoping Termination Cap
TCT1175 Terra Cotta Termination Cap
ST1175 ST475 Square Termination Cap
TR-TVK TR-TVK TR Top Vent Kit
DTO134 n/a Short Octagon Decorative Cap
DTO146 n/a Tall Octagon Decorative Cap
DTS134 n/a Short Square Decorative Cap
DTS146 n/a Tall Square Decorative Cap
LDS33 LDS33 Decorative Shroud - 3 ft x 3 ft (.91 m x .91 m)
LDS46 LDS46 Decorative Shroud - 4 ft x 6 ft (1.22 m x 1.83 m)
LDS-BV LDS-BV Decorative Shroud - 26 in. x 26 in. (660 mm x 660 mm)
Field Constructed Shrouds (See “Woodburning Termination Cap”)
CT-11A-B n/a Adapter-May be used with the following caps
14 in.
(356 mm)
5-1/4 in.
(133 mm)
13 in.
(330 mm)
CAK5A Chimney Air Kit
A
11 in.
(279 mm)
B
Chimney Sections
Catalog # A B
US CAN in mm in mm
SL1106 SL406 6 152 4-3/4 121
SL1112 SL412 12 305 10-3/4 273
SL1118 SL418 18 457 16-3/4 425
SL1136 SL436 36 914 34-3/4 883
SL1148 SL448 48 1219 46-3/4 1187
A = Actual Length B = Effective Length (length of
chimney part after it has been snapped to another)
18 in.
(457 mm)
SLA10 Adapter
14 in.
(356 mm)
4 in. (102 mm)
13 in.
(330 mm)
n/a CT-Series
n/a DT-Series
20-3/4 in.
Inside Diameter
SL4 - 10 in. (254 mm)
SL11 - 11 in. (279 mm)
(527 mm)
Outside Diameter
13 in. (330 mm)
SL11/SL4 Chimney Stabilizer
38 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
Assembled
Diameter: 17 in./432 mm
15-1/4in.
15-1/4 in.
Inside Diameter
SL1100
11 in. (279 mm)
SL400
10 in. (254 mm)
A
21 in.
(533 mm)
SL1130/SL430 Offset/Return
AS10 Straight Attic Insulation Shield
Outside
Diameter
13 in.
(330 mm)
13 in.
(330 mm)
2 in.
(51 mm)
B
Catalog # A B
FS538 0-deg. 17 in. 432 mm
FS540 30-deg. 26 in. 660 mm
17 in. (432 mm)
(387 mm)
29 in.
(737 mm)
RF570 Roof Flashing
25-1/4 in.
(641 mm)
(387 mm)
JB577 Chimney Joint Band
13 in.
(330 mm)
CB576 Chimney Joint Band
39-7/8 in.
(1013 mm)
RF571 Roof Flashing
TR-TVK - Top Vent Kit
28 in.
(711 mm)
CT-11A-B
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
39
DTO134
A B C
DTO146
DTS134
A B C
DTS146
15-3/4 in. (400 mm)
TR11/TR444 - Round Termination Cap
TR11T-B - Round Telescoping Termination Cap
ST1175/ST475 - Square Termination Cap
B
B
A
A
C
DTS134/DTS146 DTO134/DTO146
Decorative Caps
in mm
in mm
34 20 24
864 508 610
46 22.7 26
1168 576 660
C
in mm
in mm
34 21.18 24
864 538 610
46 21.18 26
1168 538 660
TCT1175 - Terra Cotta Cap
40 Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
B. Optional Components
E
52 in.
(1321 mm)
16 in.
(406 mm)
C
HX3 Hearth Extension
1/2 in.
(13 mm)
ID4 Insulated Duct
42 in.
(1067 mm)
UD4 Uninsulated Duct
42 in.
(1067 mm)
66 in.
(1676 mm)
1/2 in.
(13 mm)
4 in. (102 mm) i.d.
4 in. (102 mm) i.d.
20 in.
(508 mm)
HX4 Hearth Extension
D
A
LDS33/LDS46 Decorative Shroud
A B C D
Catalog #
LDS33 36 914 36 914 8.5 216 11 279
LDS46 48 1219 72 1829 8.5 216 11 279
in. mm in. mm in. mm in. mm
B
LDSCPM - Corner Post Kit (for custom sizes)
D
C
B
A
LDS-BV Decorative Shroud
Catalog # A B C E E
LDS-BV
in. 26 12.5 15.5 22 23
mm 660 318 394 533 584
Majestic, a brand of Hearth & Home Technologies
7571 215th Street West, Lakeville, MN 55044
www.majesticproducts.com
Majestic Biltmore Series • SB60/SB80 • 4013-300 Installers Manual • Rev E • 09/17
41
Loading...