LynTec shall under no circumstances be held responsible for any
loss, damage or injury resulting from the use of the XPC in a
manner inconsistent with any of the procedures outlined in this
document.
The user is responsible for determining whether this product is
appropriate for the intended application.
LynTec is not responsible for any indirect, secondary or ancillary
loss or damage, including personal injury, loss of or damage to property
or loss of income resulting from the operation or failure of this unit.
Troubleshooting the XPC ..............................................................................................40
139-0647-01.4
Page 5
Introduction
Chapter 1--Introduction
Chapter One--Overview
OVERVIEW
CONTENTS
Hardware Components
This bulletin explains how to install and operate the
LynTec XPC rack-mount controller. This product is a
controller only and does not contain circuits. Control
signals originate externally from commands received via
the communications network or from dry contact inputs.
Acceptable communications protocols include HTTP,
sACN, DMX-512 and Telnet.
Each XPC comes standard with the following hardware
components installed:
• Ethernet input
• DMX In & Thru inputs
• Emergency override input
• Four contact closure inputs
• Two outbound circuit outputs
• 24V power supply
139-0647-01.55
Page 6
Chapter One--Overview
Software Features Each XPC comes standard with the following software
features:
• Built-in web server with browser interface for super-easy
set up.
• Circuit level sequencing with selectable individual steprates (25ms to 999s)
• Smart phone, tablet or laptop control and monitoring
built in.
• Built in scheduling program with astronomical clock and
84 schedule events.
• Can be interfaced with any control system that
communicates individual circuit addresses in HTTP,
Telnet, DMX, sACN or contact closure.
• Circuit selectable load-shedding feature for emergency
shutoff
139-0647-01.66
Page 7
Chapter One--Overview
Controller Overview
Front & Back Panel OverviewFigure 1–1 shows the XPC front panel. A brief
description of each part follows in Table 1–1.
Figure 1-1: XPC Front Panel
A
LynTec
XPC
Xtend Power Controller
Figure 1-2: XPC Rear PanelFigure 1–2 shows the XPC back panel. A brief
description of each part follows in Table 1–2.
B
INPUT
24VDC
RESET
C
D
RELAY 1 RELAY 2
EO & CONTACT CLOSURES
E
DMX IN & THRU
F
NETWORK
G
Table 1-2: Parts of the XPC Front & Back Panel
ComponentDescription
A. LCD ScreenScreen shows the IP address
B. Power InputInputs 24VDC
C. Reset ButtonResets the controller.
D. Outbound relaysOutbound relays 1 and 2 rated at 1 Amp at 50V
E. Emergency Override &
Contact closure Inputs
F. DMX Input and ThruAllows the panel to be directed by a secondary DMX controller. When DMX is
G. Ethernet PortConnects the panel to a computer or network for initial setup or long-term
One set of contacts for emergency override and four contact closure inputs.
enabled, the control page is disabled.
operation using the built-in web interface. Port also provides sACN connection
139-0647-01.77
Page 8
Chapter Two--Safety Precautions
Chapter Two--Safety Precautions
This chapter contains important safety precautions that
must be followed before attempting to install, service, or
maintain electrical equipment. Carefully read and follow
the safety precautions below.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions
should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
• There are no user servicable parts inside the XPC. Do not
attempt to service yourself.
• Do not expose the XPC to moisture.
• Do not use outdoors - the enclosure is not rated for outdoor
use
• Do not mount near gas or electric heaters.
• Do not feed after midnight.
• Equipment should be mounted in locations and at heights
where it will not readily be subjected to tampering by
unauthorized personnel.
• The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
• Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
8
139-0647-01.8
Page 9
Chapter Two--Safety Precautions
Ce chapitre contient des consignes de sécurité
importantes qui Doit être suivi avant d’essayer d’installer,
de Maintenir l’équipement électrique. Lisez et suivez
attentivement Les précautions de sécurité ci-dessous.
LIRE ET SUIVRE TOUTES LES INSTRUCTIONS DE SÉCURITÉ
GARANTIES IMPORTANTES
Lors de l’utilisation d’équipements électriques, des
précautions de sécurité de base Devrait toujours être suivie, y
compris les suivantes:
LISEZ ET SUIVEZ TOUTES LES INSTRUCTIONS DE SÉCURITÉ.
• Il n’y a pas de pièces utilisables par l’utilisateur à
l’intérieur du XPC. Ne pas Tentez de vous entretenir.
• Ne pas exposer le XPC à l’humidité.
• Ne pas utiliser à l’extérieur - l’enceinte n’est pas évaluée
pour l’extérieur utilisation
• Ne montez pas près de gaz ou de radiateurs électriques.
• Ne pas nourrir après minuit.
• L’équipement doit être monté dans des endroits et à
des hauteurs Où il ne sera pas facilement soumis à une
altération par Personnel non autorisé.
• L’utilisation d’accessoires non recommandés par les Le
fabricant peut causer un état dangereux.
• N’utilisez pas cet équipement pour une utilisation autre que
prévue
CONSERVEZ CES INSTRUCTIONS
139-0647-01.99
Page 10
Chapter Three--Quick Start Guide
Chapter Three--Quick Start Guide
INTRODUCTION
StepsReference
1. Connect power to the 24VDC inputChapter 1--Back Panel Overview
2. Connect the controller to a computer or
network for panel setup.
3. Access the web page by entering the
displayed IP address or NetBIOS name into
web browser on a connected computer.
4. Complete the setup.Chapter 5--Control Setup
5. Connect the controller to a secondary
controller or add contact closures if
necessary.
7. If your XPC system does not operate as
expected, verify that everything is installed
and programmed correctly.
This chapter is a quick reference listing the steps necessary
to install the XPC system. The steps in this chapter
are provided as an installation checklist. For complete
installation instructions, refer the chapter listed.
Chapter 4--Wiring
Chapter 5--Control Setup
Chapter 4--Wiring
Chapter 5--Control Setup
Appendix B--Troubleshooting
10
139-0647-01.10
Page 11
Chapter Four--Wiring
Chapter 4--Wiring
Emergency Shutdown Wiring:To connect your fi re alarm or emergency management
system to the XPC, follow these steps.
1. From the fi re alarm unit or latching Emergency Shutoff
switch, wire the contacts to the fi rst pair of inputs on
the rear panel. Default is normally-open, but this can
be changed to normally-closed or monitored-loop in
setup (see Ch. 5)
2. When the contacts change state, all circuits that have
been selected for E. Shutoff will cycle to OFF.
Figure 4-1: Emergency shutdown
wiring
3. When the contacts change state all circuits that were
ON when E. Shutoff was activated will return to the ON
state if “Enable Recovery” is selected (Ch. 5).
See Chapter 5 to confi gure the software for emergency
shutdown.
139-0647-01.1111
Page 12
Chapter Four--Wiring
Switch Wiring InstructionsThe I/O ports on your XPC controller allow for a variety of
switch options.
LynTec SS-2 Switch Set
Figure 4-2
Lyntec SS-2 Wiring Diagram
Using a standard LynTec SS-2 Switch Set with illuminated
ON switch. See Figure 4-2
1. Wire the ON switch to Digital I/O port 2 on the rear
panel as follows:
i. Connect the 24VDC Common to the C pin of the ON
switch. Jumper the C pin of the ON switch to the +
pin.
ii. Connect the Input terminal (arrow pointing towards
header) to the NO pin of the ON switch.
iii. Connect the Output terminal (arrow pointing away
from header) to the – pin of the ON switch.
2. Wire the OFF switch to Digital I/O port 3 on the rear
panel as follows:
i. Connect the 24VDC Common terminal to the C pin
of the OFF switch.
ii. Connect the Input terminal to the NO pin of the
OFF switch
Repeat on ports 4 &5 for the second zone
12
To confi gure the Digital I/O port and link it to a zone see
Chapter 5.
139-0647-01.12
Page 13
Chapter Four--Wiring
SS-2PL and SS-2LRP Locking Switch
Sets
Using a standard LynTec SS-2PL or SS-2 LRP Switch Set with
illuminated ON switch. See Figure 4-3
1. Wire the ON switch to Digital I/O port 2 on the lrear
panel as follows:
i. Connect the 24VDC Common to the + pin of the ON
switch.
ii. Connect the + pin on the on switch to the 1 pin on
the lock.
iii. Connect the Input terminal (arrow pointing towards
header) to the NO pin of the ON switch.
iv. Connect the Output terminal (arrow pointing away
from header) to the – pin of the ON switch.
v. Connect the C pin on the ON switch to the 3 pin on
the lock.
2. Wire the OFF switch to Digital I/O port 3 on the rear
panel as follows:
Figure 4-3
iii. Connect the 3 pin on the lock to the C pin on the
OFF switch.
iv. Connect the Input terminal to the NO pin of the
OFF switch
To confi gure the Digital I/O port and link it to a zone see
Chapter 5.
139-0647-01.1313
Page 14
Chapter Four--Wiring
INITIAL POWER UP
PROCEDURE
Connect a computer with an Ethernet port and installed
web browser program to the XPC Network connector using
the provided crossover cable. Then enter the IP address
displayed on the front panel.
14
139-0647-01.14
Page 15
Chapter 5--Control Setup (Web Page)
Chapter Five--Control Setup
OVERVIEW
STATUS
CONTROL
SETUP
There are 5 main tabs on your XPC web page. This page
will give you a quick overview of the pages and their
functions.
The status page allows you to view the current status of the
circuits and zones. Zones and individual circuits cannot be
manipulated from this page.
This page allows the user to manipulate individual
circuits as well as circuit zones. “All ON/OFF” and
“Hurry-Off” commands can also be triggered from this
page.
The setup section allows you to setup and use the
XPC controller. From this section you can manipulate
the network settings, assign circuits to zones, create
sequences, activate emergency management features,
create schedules and assign contact closures.
SUPPORT
EVENT LOG
139-0647-01.1515
This page provides contact information for LynTec.
This page provides a log of events.
Page 16
Chapter Five--Control Setup
Setup
SETUP HOME
This section will guide you through the process of setting
up yur XPC Controller. First enter the IP address or NetBios
name into your web browser. When the XPC screen pulls
up. Select “Setup” and “SetupHome” Tabs.
Figure 5-1--Setup Home
16
To set the username and password for your panel, click
the Setup tab. The Setup Home tab should be displayed.
The default username displayed is “admin” and the
password fi elds is “pw”. Enter the desired username in
the fi rst fi eld, password (without spaces or symbols) in
the second and then retype the password again in the
third fi eld. When ready, click the Update Login Info button
to save the changes to the controller’s memory. Note:
Password can be any 2-8 character string.
Contact information for service can also be entered
on this page. Under the Serial Number fi eld, enter the
name and phone number of the installing contractor
(Electrician) and the system integrator (A/V Technician)
for future reference. Save this information by clicking the
Update Information button below the Clock Set portion of
the window.
139-0647-01.16
Page 17
Network setup
Chapter Five--Control Setup
Basic date and time information will be displayed in the
Clock Set fi elds. Verify that the year, month and day are
correct. Set the hour to the appropriate time for your time
zone and verify that the minute displayed is correct. Save
this information by clicking the Update Information button
below the Clock Set portion of the window.
Click the radio buttons for any pages to be printed out
under the Printable Pages header. To print the Network
Setup, Panel Setup or Panel Schedules pages at any time,
ensure the desired buttons have been selected and then
click the Print Pages button to the right. Please print a
copy for your records after setup is complete.
Figure 5-2--Network Confi guration
Figure 5-2 shows the network confi guration portion of the
Network setup.
This screen shows the current network values. If DHCP
is enabled then the fi elds will be greyed out. It is
recommended that the user consult with the network
administrator before changing these values.
The IP, Subnet and Gateway addresses are only used in the
following situations:
• When DHCP is disabled
• When DHCP is enabled, but there is no DHCP server
available on the network
• When the XPC provides DHCP addresses
If DHCP is enabled and available on the network, all these
values will be obtained from the DHCP server.
If DHCP is disabled and a static address is used, save
changes and then press “Reset RPC” or the reset button on
the controller to apply changes.
139-0647-01.1717
Page 18
Chapter Five--Control Setup
Figure 5-3: Interface options
Port TypeThe port type section is used to select the preferred
communication protocol. The controller defaults to
Ethernet (TCP/IP) for setup but can be controlled in
conjunction with sACN or DMX-512 protocols.
18
139-0647-01.18
Page 19
Chapter Five--Control Setup
DMX
Streaming ACN E1.31
For DMX operation use the following steps:
The XPC allows up to four different sets of DMX starting
addresses within a single universe.
In the fi rst set, enter the fi rst circuit address. All
circuits need to be assigned addresses manually. Do
this by clicking on each circuit in the order you would
like them to be addressed. If you need to skip an
address or group of addresses, simply create a new
zone and enter the desired starting address. If you
would like the XPC to automatically assign circuits to
consecutive addresses. you may change that in the
For sACN operation use the following steps:
The XPC allows up to four different universes with
sACN operation.
First, assign a number to the universe.
In the fi rst set, enter the fi rst individual circuit address.
All circuits need to be assigned addresses manually.
Do this by clicking on each circuit in the order you
would like them to be addressed. If you need to skip
an address or group of addresses, simply create a new
zone and enter the desired starting address. If you
would like the XPC to automatically assign circuits to
consecutive addresses. you may change that in the
“Panels” tab.
Please note that selecting sACN/DMX control for a
circuit or zone, will disable web browser or contact
closure control for that circuit/zone. Although,
circuit/zone status may still be monitored by web
browser or smartphone.
DMX and sACN are exclusive and cannot be used on
the same controller at the same time. Either can be
used to control circuits in zones while other zones are
controlled by IP commands or contact closures.
139-0647-01.1919
Page 20
Chapter Five--Control Setup
NETWORKING MULTIPLE
XRS AND XRM UNITS
Up to 9 XRS and XRM units may be networked together
to allow for zoning and sequencing across all units. To
connect XPCs together use the following steps:
1. Connect all Xtend units to the network on the same
subnet.
2. The XPC will be the “master” unit.
3. In the web interface click the “Setup” tab and then
the “Network” tab.
4. Under “Master/Remotes IP Confi guration” enter the
IP address for each remote unit.
Figure 5-3.1: Master/Remotes IP Confi guration
20
139-0647-01.20
Page 21
Chapter Five--Control Setup
Panel Setup
CIRCUIT SETUP
This section explains how to setup your XPC for
remote operation.
To add remote Xtend modules to the interface, follow these
steps:
1. Under Setup, go to the Panels tab.
2. Click the “Scan Circuits” button.
Figure 5-4
3. If panel confi gurations are correct, click “Accept
Changes”
4. Assign names to the circuits. (Figure 5-5)
Figure 5-5
139-0647-01.2121
Page 22
Chapter Five--Control Setup
ZONE SETUP
Circuits can be controlled individually or arranged into
zones. Circuits in zones can be toggled at 25 ms intervals
(Grouped Operation), at variable intervals (Sequenced
Operation), or via DMX or sACN.
To setup a Zone follow these steps:
1. Choose which zone you would like to edit. (Figure
5-6)
Figure 5-6
Select
to Edit
2. Name the Zone. (Figure 5-7)
3. Choose Grouped, Sequenced, DMX or sACN operation.
Note: DMX and sACN may not be used within the same
XPC (Figure 5-7)
Figure 5-7
Name the
Zone
Choose operation
type from the
dropdown
4. If using DMX or sACN operation, select the address
set (Figure 5-8) or universe (Figure 5-9) from the
22
139-0647-01.22
Page 23
Figure 5-8
Figure 5-9
Chapter Five--Control Setup
Choose address set
from the dropdown
Choose universe
from the
dropdown
5. Select a circuit to add to the zone by clicking on the
circuit you want to add. (Figure 5-10)
Figure 5-10
Click on the green
receptacle to add a
circuit to a zone.
139-0647-01.2323
Page 24
Chapter Five--Control Setup
S
t
6. Select the position of the circuit in the zone. This
set the order in which they turn on and off. Or
in the case of DMX or sACN, the address order.
(Figure 5-11). Note: DMX and sACN zones default
to individual addressing. If you choose “All
Available” the entire panel or panels will change
to DMX or sACN.
7. For sequenced operation, select a delay time from
the dropdown. Circuits in grouped zones toggle
in 25ms intervals. (Figure 5-11) Delay time is
the amount of time after a circuit changes state,
before the new circuit in sequence changes state.
If using one of the custom delay settings, enter
the desired delay time in the custom delay setting
fi eld. (Figure 5-12)
Figure 5-11
Click the up/down
arrows to change the
circuit’s position/
address in the zone.
Select a delay time for
the circuit.
24
139-0647-01.24
Page 25
Chapter Five--Control Setup
Figure 5-12
8. Click the “Close” button when fi nished to save. Or,
click “Remove” to remove the circuit from the zone.
9. When fi nished adding circuits to the zone, click the
“Test Mode” (Figure 5-13) button to do a blind test
(circuits will not actually toggle). Please note that
delay times larger than one second are reduced to one
second in Test Mode for expediency.
Figure 5-13
Click to test
zone operation.
Change drop down to
“Disabled” to disable
zones.
10. Disable zones that are not in use so they do not
appear in the status and control pages (Figure 5-13).
11. Click “Save Changes” (Figure 5-14) to save zone
information when fi nished.
Figure 5-14
139-0647-01.2525
Page 26
Chapter Five--Control Setup
GLOBAL PREFERENCES
SETUP
This section guides you through the setup process for the
many features and preferences in your XPC system.
LabelingIn addition to labeling circuits, each unit in your XPC
system can be named (up to 16 characters). (Figure 5-15)
For multi-unit systems, scroll down to see additional
panels/units.
Figure 5-15
Global Control PreferencesThe following features can be selected for additional
system fl exibility
Figure 5-16
Table 5-1
All Circuits On/OffTurns all the circuits on or off by order of zone and sequence
Hurry-OffTurns circuits off rapidly without sequencing
E. ShutoffTurns selected circuits off when external contacts or emergency
management system activates (uses I/O CC#1)
26
139-0647-01.26
Page 27
Chapter Five--Control Setup
Schedule SetupFollow these steps to set a schedule (not compatible with
DMX or sACN).
1. Enable Schedules in Setup Home tab
2. Rename each schedule as desired
3. Assign weekday (M-F) on and off times by clicking on
time and off time buttons, using pull-down menu and
clicking the pick button to select.
4. Assign weekend (S-S) on and off times by clicking on
time and off time buttons, using pull-down menu and
clicking the pick button to select.
5. Enable each schedule by clicking the checkbox for that
line.
Figure 5-17
Assigning Schedules to ZonesTo assign a schedule to a zone in the “Panel” screen:
1. Select the desired zone from the drop down box.
2. Save changes.
Figure 5-18
139-0647-01.2727
Page 28
Chapter Five--Control Setup
Contact Closure Setup
Figure 5-19
Confi gure the digital I/O port and link it to a zone as
follows:
Note: If the Emergency Shutoff feature is selected, the
fi rst position in the Onboard fi eld (on the Controller) is
automatically assigned to that.
1. Rename each contact closure as desired
2. Select contact closure action type
3. Use CC Module 1 and CC Module 2 only if I/O Expander
boards are installed.
4. Save Changes
Assigning Contact Closures to
Zones
Figure 5-20
28
To assign a contact closure to a zone in the “Panel”
screen:
1. Select the desired zone from the drop down box.
139-0647-01.28
Page 29
Chapter Five--Control Setup
Individual Momentary Contact ON and
OFF Pushbuttons
Using a standard LynTec SS-2 Switch Set with illuminated
ON switch or two illuminated pushbuttons:
Confi gure the Digital I/O port and link it to a zone as
follows:
1. Follow the previous instructions for naming the contact
closure and setting closure type.
2. Click the M button at the right side of the fi rst of the
two ports used. The name box and M button in the
second port should turn gray and the Action selections
should default to Momentary NO. (normally open)
3. Ensure that both of the Action selections for both ports
are set to Momentary NO.
4. Enter a name in the text fi eld of the CC used that is
indicative of the zone it will control.
5. Click the “Save Changes” button at the top of the
Onboard I/O box.
6. Follow the previous instructions for assigning a contact
closure to a zone, selecting the merged ports.
7. Click the Save Changes button in the upper left corner
of the Panels page.
Verify proper operation of your Switch Set:
1. Press the ON switch. Circuits in the selected zone
should immediately begin actuating.
2. The ON indicator should fl ash steadily until all of the
circuits are in the on state.
3. When the zone has completed, the ON indicator should
remain constantly lit.
4. Press the OFF switch. Circuits in the selected zone
should immediately begin actuating.
5. The ON indicator should fl ash steadily until all of the
circuits are in the off state.
6. When the zone has completed, the ON indicator
should remain constantly dark. Note: When using
two illuminate pushbuttons the OFF indicator will
remain constantly lit when the zone has completed.
(OFF indicator will extinguish immediately when ON is
pressed again.)
139-0647-01.2929
Page 30
Chapter Five--Control Setup
Email Alert Setup
Figure 5-21
Follow these steps to set an email alert
1. Go to Setup Alerts tab
2. Enter email addresses.
3. Select alert types (tripped circuit, BO/EO/EL, On
Recovery and/or Temperature
4. If using Temperature alerts, enter the temperature
threshold.
30
139-0647-01.30
Page 31
Chapter Six: Operating your XPC
Figure 6-1
Chapter Six--Operation
Using the built-in web page
Using a secondary controllerFor DMX and sACN follow the manufacturer’s instructions
139-0647-01.3131
To operate the XPC using the built in web page, select
the control tab from the top of the page. Once on the
CONTROL page, simply click each circuit for individual
control. Or, click a zone for zone control. “All Circuits
ON” and “All circuits OFF” commands can also be executed
using the DMX addresses entered in the NETWORK page (
see page 16).
TCP/IP schemes are in Appendix B (page 38).
Page 32
Appendix A - Telnet and HTTP Protcols
Appendix A--Telnet and TCP/IP
Protocols
TELNET PROTOCOL
Table B-1 Command Codes
Note: Telnet port = 23. Send Telnet commands to XPC IP
address/23 (e.g. 192.168.1.250/23)
CommandDecimalHexidecimal
Start Byte1760xB0
Activate circuits1800xB4
Deactivate circuits 1810xB5
Request all circuits status1830xB6
Activate zones 1830xB7
Deactivate zones1840xB8
Request zones status1850xB9
Event ON1860xBA
Event OFF1870xBB
Event status1880xBC
Request circuits status 1890xBD
Request bus status 1900xBE
Addressing Scheme
Circuit Related Commands
Circuit status identifi er2000xC8
Zone status identifi er2010xC9
Event status identifi er2020xCA
Emergency override identifi er2030xCB
Checksum identifi er2040xCC
Checksum digits 205-2140xCD - 0xD6
Stop byte2400xF0
Circuit address:
1 byte. Numbers 1 through 168 (0x01 – 0xA8) are assigned
to populated circuits in sequential order
circuit_address_1, …, circuit_address_m – addresses of
circuits to be activated circuit_address_1, …, circuit_
address_n – addresses of circuits to be deactivated
m+n<=168
zone_address_i, zone_status_i, zone_address_j, zone_
status_j, …, zone_address_n, zone_status_n – addresses and
status of zones updated by the command reply is generated
for
Event Related Commands
Reply to request zone status command: status of all 12
zones
0x40, 0xB9, byte_1, byte_2, byte_3, 0x80
byte_i: bits 7-6: status of zone # 4i, bits 5-4: status of zone
4i-1, bits 3-2: status of zone 4i-2, bits 1-0: status of zone
4i-3, i=1-3
Checksum(rev changed from 1.1.3; 1.1.3 supported old protocol)
If system is in Emergency Override mode, it replies to
circuit, zone or event on/off command with emergency
override response
0xB0, 0xCB, 0xF0
Checksum is optional. It is calculated as a sum of all bytes
of the message starting with start byte and ending with
TCP/IP PROTOCOL
TCP/IP communications and control via a third party
control system is facilitated by the use of the HTTP GET
command. In the example below, GET= the XPC’s IP
address
Example of GET command:
GET /p2.XPC?IPB002=1
Circuit Control = B
Zone Control = Z
Three modes of control are:
Circuit control = “B” Zone control = “Z” Event Control =
“E”
Refer to LynTec XPC browser set-up for circuit
numbering
GET /p2.XPC?IPB002=1
This control string will turn circuit #2 on.
GET /p2.XPC?IPB002=0
This control string will turn circuit #2 off.
Control of up to 167 circuits (4 panel system) is
possible.
Confi gure your zones (circuit groups) using the LynTec
XPC browser set-up when connected to the LynTec XPC
panel.
The above return is displaying the status of a 20 circuit
circuits system in which all are presently ON, with the
exceptions of circuit #2 and circuit #5, which are OFF.
The above return is also showing the status of 12 zones,
all are ON with the exception of zone #10, which is OFF.
The events return is showing that event #1 is active = “All
Circuits ON”
Status returns for Circuits: Status returns for Zones
and Events:
0 = OFF 0 = OFF
1 = ON 1 = ON
2 = Circuit Tripped (panels