LynTec Xtend Power Controller Instruction Bulletin

Page 1
LynTec XPC
Instruction Bulletin
Xtend Power Controller
Retain for future use.
139-0701-01 8/1/19
Page 2
DISCLAIMER
The user is responsible for determining whether this product is appropriate for the intended application.
LynTec is not responsible for any indirect, secondary or ancillary loss or damage, including personal injury, loss of or damage to property or loss of income resulting from the operation or failure of this unit.
Page 3
XPC Table of Contents
Contents
Disclaimer ................................................................................................................ 2
Chapter 1--Introduction ..................................................................................................... 5
OVERVIEW ................................................................................................................. 5
CONTENTS ................................................................................................................ 5
Hardware Components ............................................................................................. 5
Software Features .................................................................................................. 6
Front & Back Panel Overview ..................................................................................... 7
Chapter Two--Safety Precautions .......................................................................................... 8
Chapter Three--Quick Start Guide .......................................................................................10
Introduction .............................................................................................................10
Chapter 4--Wiring ...........................................................................................................11
Emergency Shutdown Wiring: ....................................................................................11
Switch Wiring Instructions ........................................................................................12
LynTec SS-2 Switch Set ............................................................................................12
SS-2PL and SS-2LRP Locking Switch Sets ........................................................................13
Initial Power up procedure ............................................................................................14
Chapter 5--Control Setup (Web Page) ...................................................................................15
OVERVIEW ................................................................................................................15
Status ....................................................................................................................15
Control ...................................................................................................................15
Setup .....................................................................................................................15
Support ...................................................................................................................15
Event Log ................................................................................................................15
Setup ..........................................................................................................................16
Setup Home .............................................................................................................16
Network setup ...............................................................................................................17
Networking Multiple XRS and XRM Units ............................................................................20
Panel Setup ..................................................................................................................21
Circuit setup ............................................................................................................21
Zone setup ...............................................................................................................22
Global Preferences .....................................................................................................26
Setup .....................................................................................................................26
Labeling .............................................................................................................26
Global Control Preferences .......................................................................................26
Selecting Circuits for Emergency Shutdown or Brownout ...................................................27
Voltage Thresholds .................................................................................................27
Schedule Setup .....................................................................................................28
Assigning Schedules to Zones ....................................................................................28
Contact Closure Setup .............................................................................................29
Assigning Contact Closures to Zones ............................................................................29
139-0647-01.3 3
Page 4
XPC Table of Contents
Individual Momentary Contact ON and OFF Pushbuttons ....................................................30
Email Alert Setup ..................................................................................................31
Chapter Six: Operating your XPC ........................................................................................32
Using the built-in web page ......................................................................................32
Using a secondary controller .....................................................................................32
Appendix A--Telnet and TCP/IP Protocols ...............................................................................33
Telnet Protocol ..........................................................................................................33
Addressing Scheme ................................................................................................33
Circuit Related Commands .......................................................................................33
Zone Related Commands ..........................................................................................35
Event Related Commands .........................................................................................36
Checksum ...........................................................................................................38
TCP/IP Protocol .........................................................................................................38
Circuit Control = B .................................................................................................38
Zone Control = Z ...................................................................................................38
Events Control = E .................................................................................................39
Appendix B--Troubleshooting ..............................................................................................40
Troubleshooting the XPC ..............................................................................................40
139-0647-01.4
Page 5
Introduction
Chapter 1--Introduction
Chapter One--Overview
OVERVIEW
CONTENTS
Hardware Components
This bulletin explains how to install and operate the LynTec XPC rack-mount controller. This product is a controller only and does not contain circuits. Control signals originate externally from commands received via the communications network or from dry contact inputs. Acceptable communications protocols include HTTP, sACN, DMX-512 and Telnet.
Each XPC comes standard with the following hardware components installed:
• Ethernet input
• DMX In & Thru inputs
• Emergency override input
• Four contact closure inputs
• Two outbound circuit outputs
• 24V power supply
139-0647-01.5 5
Page 6
Chapter One--Overview
Software Features Each XPC comes standard with the following software
features:
• Built-in web server with browser interface for super-easy set up.
• Circuit level sequencing with selectable individual step­rates (25ms to 999s)
• Smart phone, tablet or laptop control and monitoring built in.
• Built in scheduling program with astronomical clock and 84 schedule events.
• Can be interfaced with any control system that communicates individual circuit addresses in HTTP, Telnet, DMX, sACN or contact closure.
• Circuit selectable load-shedding feature for emergency shutoff
139-0647-01.66
Page 7
Chapter One--Overview
Controller Overview
Front & Back Panel Overview Figure 1–1 shows the XPC front panel. A brief
description of each part follows in Table 1–1.
Figure 1-1: XPC Front Panel
A
LynTec
XPC
Xtend Power Controller
Figure 1-2: XPC Rear Panel Figure 1–2 shows the XPC back panel. A brief
description of each part follows in Table 1–2.
B
INPUT 24VDC
RESET
C
D
RELAY 1 RELAY 2
EO & CONTACT CLOSURES
E
DMX IN & THRU
F
NETWORK
G
Table 1-2: Parts of the XPC Front & Back Panel
Component Description
A. LCD Screen Screen shows the IP address B. Power Input Inputs 24VDC C. Reset Button Resets the controller.
D. Outbound relays Outbound relays 1 and 2 rated at 1 Amp at 50V E. Emergency Override &
Contact closure Inputs
F. DMX Input and Thru Allows the panel to be directed by a secondary DMX controller. When DMX is
G. Ethernet Port Connects the panel to a computer or network for initial setup or long-term
One set of contacts for emergency override and four contact closure inputs.
enabled, the control page is disabled.
operation using the built-in web interface. Port also provides sACN connection
139-0647-01.7 7
Page 8
Chapter Two--Safety Precautions
Chapter Two--Safety Precautions
This chapter contains important safety precautions that must be followed before attempting to install, service, or maintain electrical equipment. Carefully read and follow the safety precautions below.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
• There are no user servicable parts inside the XPC. Do not attempt to service yourself.
• Do not expose the XPC to moisture.
• Do not use outdoors - the enclosure is not rated for outdoor use
• Do not mount near gas or electric heaters.
• Do not feed after midnight.
• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
8
139-0647-01.8
Page 9
Chapter Two--Safety Precautions
Ce chapitre contient des consignes de sécurité importantes qui Doit être suivi avant d’essayer d’installer, de Maintenir l’équipement électrique. Lisez et suivez attentivement Les précautions de sécurité ci-dessous.
LIRE ET SUIVRE TOUTES LES INSTRUCTIONS DE SÉCURITÉ
GARANTIES IMPORTANTES
Lors de l’utilisation d’équipements électriques, des précautions de sécurité de base Devrait toujours être suivie, y compris les suivantes:
LISEZ ET SUIVEZ TOUTES LES INSTRUCTIONS DE SÉCURITÉ.
• Il n’y a pas de pièces utilisables par l’utilisateur à l’intérieur du XPC. Ne pas Tentez de vous entretenir.
• Ne pas exposer le XPC à l’humidité.
• Ne pas utiliser à l’extérieur - l’enceinte n’est pas évaluée pour l’extérieur utilisation
• Ne montez pas près de gaz ou de radiateurs électriques.
• Ne pas nourrir après minuit.
• L’équipement doit être monté dans des endroits et à des hauteurs Où il ne sera pas facilement soumis à une altération par Personnel non autorisé.
• L’utilisation d’accessoires non recommandés par les Le fabricant peut causer un état dangereux.
• N’utilisez pas cet équipement pour une utilisation autre que prévue
CONSERVEZ CES INSTRUCTIONS
139-0647-01.9 9
Page 10
Chapter Three--Quick Start Guide
Chapter Three--Quick Start Guide
INTRODUCTION
Steps Reference
1. Connect power to the 24VDC input Chapter 1--Back Panel Overview
2. Connect the controller to a computer or network for panel setup.
3. Access the web page by entering the displayed IP address or NetBIOS name into web browser on a connected computer.
4. Complete the setup. Chapter 5--Control Setup
5. Connect the controller to a secondary controller or add contact closures if necessary.
7. If your XPC system does not operate as expected, verify that everything is installed and programmed correctly.
This chapter is a quick reference listing the steps necessary to install the XPC system. The steps in this chapter are provided as an installation checklist. For complete installation instructions, refer the chapter listed.
Chapter 4--Wiring
Chapter 5--Control Setup
Chapter 4--Wiring Chapter 5--Control Setup
Appendix B--Troubleshooting
10
139-0647-01.10
Page 11
Chapter Four--Wiring
Chapter 4--Wiring
Emergency Shutdown Wiring: To connect your re alarm or emergency management
system to the XPC, follow these steps.
1. From the fi re alarm unit or latching Emergency Shutoff switch, wire the contacts to the fi rst pair of inputs on the rear panel. Default is normally-open, but this can be changed to normally-closed or monitored-loop in setup (see Ch. 5)
2. When the contacts change state, all circuits that have been selected for E. Shutoff will cycle to OFF.
Figure 4-1: Emergency shutdown wiring
3. When the contacts change state all circuits that were ON when E. Shutoff was activated will return to the ON state if “Enable Recovery” is selected (Ch. 5).
See Chapter 5 to confi gure the software for emergency shutdown.
139-0647-01.11 11
Page 12
Chapter Four--Wiring
Switch Wiring Instructions The I/O ports on your XPC controller allow for a variety of
switch options.
LynTec SS-2 Switch Set
Figure 4-2 Lyntec SS-2 Wiring Diagram
Using a standard LynTec SS-2 Switch Set with illuminated ON switch. See Figure 4-2
1. Wire the ON switch to Digital I/O port 2 on the rear panel as follows:
i. Connect the 24VDC Common to the C pin of the ON
switch. Jumper the C pin of the ON switch to the + pin.
ii. Connect the Input terminal (arrow pointing towards
header) to the NO pin of the ON switch.
iii. Connect the Output terminal (arrow pointing away
from header) to the – pin of the ON switch.
2. Wire the OFF switch to Digital I/O port 3 on the rear panel as follows:
i. Connect the 24VDC Common terminal to the C pin
of the OFF switch.
ii. Connect the Input terminal to the NO pin of the
OFF switch
Repeat on ports 4 &5 for the second zone
12
To confi gure the Digital I/O port and link it to a zone see Chapter 5.
139-0647-01.12
Page 13
Chapter Four--Wiring
SS-2PL and SS-2LRP Locking Switch Sets
Using a standard LynTec SS-2PL or SS-2 LRP Switch Set with illuminated ON switch. See Figure 4-3
1. Wire the ON switch to Digital I/O port 2 on the lrear panel as follows:
i. Connect the 24VDC Common to the + pin of the ON
switch.
ii. Connect the + pin on the on switch to the 1 pin on
the lock.
iii. Connect the Input terminal (arrow pointing towards
header) to the NO pin of the ON switch.
iv. Connect the Output terminal (arrow pointing away
from header) to the – pin of the ON switch.
v. Connect the C pin on the ON switch to the 3 pin on
the lock.
2. Wire the OFF switch to Digital I/O port 3 on the rear panel as follows:
Figure 4-3
iii. Connect the 3 pin on the lock to the C pin on the
OFF switch.
iv. Connect the Input terminal to the NO pin of the
OFF switch
To confi gure the Digital I/O port and link it to a zone see Chapter 5.
139-0647-01.13 13
Page 14
Chapter Four--Wiring
INITIAL POWER UP PROCEDURE
Connect a computer with an Ethernet port and installed web browser program to the XPC Network connector using the provided crossover cable. Then enter the IP address displayed on the front panel.
14
139-0647-01.14
Page 15
Chapter 5--Control Setup (Web Page)
Chapter Five--Control Setup
OVERVIEW
STATUS
CONTROL
SETUP
There are 5 main tabs on your XPC web page. This page will give you a quick overview of the pages and their functions.
The status page allows you to view the current status of the circuits and zones. Zones and individual circuits cannot be manipulated from this page.
This page allows the user to manipulate individual circuits as well as circuit zones. “All ON/OFF” and “Hurry-Off” commands can also be triggered from this page.
The setup section allows you to setup and use the XPC controller. From this section you can manipulate the network settings, assign circuits to zones, create sequences, activate emergency management features, create schedules and assign contact closures.
SUPPORT
EVENT LOG
139-0647-01.15 15
This page provides contact information for LynTec.
This page provides a log of events.
Page 16
Chapter Five--Control Setup
Setup
SETUP HOME
This section will guide you through the process of setting up yur XPC Controller. First enter the IP address or NetBios name into your web browser. When the XPC screen pulls up. Select “Setup” and “SetupHome” Tabs.
Figure 5-1--Setup Home
16
To set the username and password for your panel, click the Setup tab. The Setup Home tab should be displayed. The default username displayed is “admin” and the password fi elds is “pw”. Enter the desired username in the fi rst fi eld, password (without spaces or symbols) in the second and then retype the password again in the third fi eld. When ready, click the Update Login Info button to save the changes to the controller’s memory. Note: Password can be any 2-8 character string.
Contact information for service can also be entered on this page. Under the Serial Number fi eld, enter the name and phone number of the installing contractor (Electrician) and the system integrator (A/V Technician) for future reference. Save this information by clicking the Update Information button below the Clock Set portion of the window.
139-0647-01.16
Page 17
Network setup
Chapter Five--Control Setup
Basic date and time information will be displayed in the Clock Set fi elds. Verify that the year, month and day are correct. Set the hour to the appropriate time for your time zone and verify that the minute displayed is correct. Save this information by clicking the Update Information button below the Clock Set portion of the window.
Click the radio buttons for any pages to be printed out under the Printable Pages header. To print the Network Setup, Panel Setup or Panel Schedules pages at any time, ensure the desired buttons have been selected and then click the Print Pages button to the right. Please print a copy for your records after setup is complete.
Figure 5-2--Network Confi guration
Figure 5-2 shows the network confi guration portion of the Network setup.
This screen shows the current network values. If DHCP is enabled then the fi elds will be greyed out. It is recommended that the user consult with the network administrator before changing these values.
The IP, Subnet and Gateway addresses are only used in the following situations:
• When DHCP is disabled
• When DHCP is enabled, but there is no DHCP server available on the network
• When the XPC provides DHCP addresses
If DHCP is enabled and available on the network, all these values will be obtained from the DHCP server.
If DHCP is disabled and a static address is used, save changes and then press “Reset RPC” or the reset button on the controller to apply changes.
139-0647-01.17 17
Page 18
Chapter Five--Control Setup
Figure 5-3: Interface options
Port Type The port type section is used to select the preferred
communication protocol. The controller defaults to Ethernet (TCP/IP) for setup but can be controlled in conjunction with sACN or DMX-512 protocols.
18
139-0647-01.18
Page 19
Chapter Five--Control Setup
DMX
Streaming ACN E1.31
For DMX operation use the following steps:
The XPC allows up to four different sets of DMX starting addresses within a single universe.
In the fi rst set, enter the fi rst circuit address. All circuits need to be assigned addresses manually. Do this by clicking on each circuit in the order you would like them to be addressed. If you need to skip an address or group of addresses, simply create a new zone and enter the desired starting address. If you would like the XPC to automatically assign circuits to consecutive addresses. you may change that in the
For sACN operation use the following steps:
The XPC allows up to four different universes with sACN operation.
First, assign a number to the universe.
In the fi rst set, enter the fi rst individual circuit address. All circuits need to be assigned addresses manually. Do this by clicking on each circuit in the order you would like them to be addressed. If you need to skip an address or group of addresses, simply create a new zone and enter the desired starting address. If you would like the XPC to automatically assign circuits to consecutive addresses. you may change that in the “Panels” tab.
Please note that selecting sACN/DMX control for a circuit or zone, will disable web browser or contact closure control for that circuit/zone. Although, circuit/zone status may still be monitored by web browser or smartphone.
DMX and sACN are exclusive and cannot be used on the same controller at the same time. Either can be used to control circuits in zones while other zones are controlled by IP commands or contact closures.
139-0647-01.19 19
Page 20
Chapter Five--Control Setup
NETWORKING MULTIPLE XRS AND XRM UNITS
Up to 9 XRS and XRM units may be networked together to allow for zoning and sequencing across all units. To connect XPCs together use the following steps:
1. Connect all Xtend units to the network on the same subnet.
2. The XPC will be the “master” unit.
3. In the web interface click the “Setup” tab and then the “Network” tab.
4. Under “Master/Remotes IP Confi guration” enter the IP address for each remote unit.
Figure 5-3.1: Master/Remotes IP Confi guration
20
139-0647-01.20
Page 21
Chapter Five--Control Setup
Panel Setup
CIRCUIT SETUP
This section explains how to setup your XPC for remote operation.
To add remote Xtend modules to the interface, follow these steps:
1. Under Setup, go to the Panels tab.
2. Click the “Scan Circuits” button.
Figure 5-4
3. If panel confi gurations are correct, click “Accept Changes”
4. Assign names to the circuits. (Figure 5-5)
Figure 5-5
139-0647-01.21 21
Page 22
Chapter Five--Control Setup
ZONE SETUP
Circuits can be controlled individually or arranged into zones. Circuits in zones can be toggled at 25 ms intervals (Grouped Operation), at variable intervals (Sequenced Operation), or via DMX or sACN.
To setup a Zone follow these steps:
1. Choose which zone you would like to edit. (Figure
5-6)
Figure 5-6
Select
to Edit
2. Name the Zone. (Figure 5-7)
3. Choose Grouped, Sequenced, DMX or sACN operation. Note: DMX and sACN may not be used within the same XPC (Figure 5-7)
Figure 5-7
Name the Zone
Choose operation type from the dropdown
4. If using DMX or sACN operation, select the address set (Figure 5-8) or universe (Figure 5-9) from the
22
139-0647-01.22
Page 23
Figure 5-8
Figure 5-9
Chapter Five--Control Setup
Choose address set from the dropdown
Choose universe from the dropdown
5. Select a circuit to add to the zone by clicking on the circuit you want to add. (Figure 5-10)
Figure 5-10
Click on the green receptacle to add a circuit to a zone.
139-0647-01.23 23
Page 24
Chapter Five--Control Setup
S
t
6. Select the position of the circuit in the zone. This set the order in which they turn on and off. Or in the case of DMX or sACN, the address order. (Figure 5-11). Note: DMX and sACN zones default to individual addressing. If you choose “All Available” the entire panel or panels will change to DMX or sACN.
7. For sequenced operation, select a delay time from the dropdown. Circuits in grouped zones toggle in 25ms intervals. (Figure 5-11) Delay time is the amount of time after a circuit changes state, before the new circuit in sequence changes state. If using one of the custom delay settings, enter the desired delay time in the custom delay setting eld. (Figure 5-12)
Figure 5-11
Click the up/down arrows to change the circuit’s position/ address in the zone.
Select a delay time for the circuit.
24
139-0647-01.24
Page 25
Chapter Five--Control Setup
Figure 5-12
8. Click the “Close” button when fi nished to save. Or, click “Remove” to remove the circuit from the zone.
9. When fi nished adding circuits to the zone, click the “Test Mode” (Figure 5-13) button to do a blind test (circuits will not actually toggle). Please note that delay times larger than one second are reduced to one second in Test Mode for expediency.
Figure 5-13
Click to test zone operation.
Change drop down to “Disabled” to disable zones.
10. Disable zones that are not in use so they do not appear in the status and control pages (Figure 5-13).
11. Click “Save Changes” (Figure 5-14) to save zone information when fi nished.
Figure 5-14
139-0647-01.25 25
Page 26
Chapter Five--Control Setup
GLOBAL PREFERENCES SETUP
This section guides you through the setup process for the many features and preferences in your XPC system.
Labeling In addition to labeling circuits, each unit in your XPC
system can be named (up to 16 characters). (Figure 5-15) For multi-unit systems, scroll down to see additional panels/units.
Figure 5-15
Global Control Preferences The following features can be selected for additional
system fl exibility
Figure 5-16
Table 5-1
All Circuits On/Off Turns all the circuits on or off by order of zone and sequence Hurry-Off Turns circuits off rapidly without sequencing E. Shutoff Turns selected circuits off when external contacts or emergency
management system activates (uses I/O CC#1)
26
139-0647-01.26
Page 27
Chapter Five--Control Setup
Schedule Setup Follow these steps to set a schedule (not compatible with
DMX or sACN).
1. Enable Schedules in Setup Home tab
2. Rename each schedule as desired
3. Assign weekday (M-F) on and off times by clicking on time and off time buttons, using pull-down menu and clicking the pick button to select.
4. Assign weekend (S-S) on and off times by clicking on time and off time buttons, using pull-down menu and clicking the pick button to select.
5. Enable each schedule by clicking the checkbox for that line.
Figure 5-17
Assigning Schedules to Zones To assign a schedule to a zone in the “Panel” screen:
1. Select the desired zone from the drop down box.
2. Save changes.
Figure 5-18
139-0647-01.27 27
Page 28
Chapter Five--Control Setup
Contact Closure Setup
Figure 5-19
Confi gure the digital I/O port and link it to a zone as follows:
Note: If the Emergency Shutoff feature is selected, the rst position in the Onboard fi eld (on the Controller) is automatically assigned to that.
1. Rename each contact closure as desired
2. Select contact closure action type
3. Use CC Module 1 and CC Module 2 only if I/O Expander boards are installed.
4. Save Changes
Assigning Contact Closures to Zones
Figure 5-20
28
To assign a contact closure to a zone in the “Panel” screen:
1. Select the desired zone from the drop down box.
139-0647-01.28
Page 29
Chapter Five--Control Setup
Individual Momentary Contact ON and OFF Pushbuttons
Using a standard LynTec SS-2 Switch Set with illuminated ON switch or two illuminated pushbuttons:
Confi gure the Digital I/O port and link it to a zone as follows:
1. Follow the previous instructions for naming the contact closure and setting closure type.
2. Click the M button at the right side of the fi rst of the two ports used. The name box and M button in the second port should turn gray and the Action selections should default to Momentary NO. (normally open)
3. Ensure that both of the Action selections for both ports are set to Momentary NO.
4. Enter a name in the text fi eld of the CC used that is indicative of the zone it will control.
5. Click the “Save Changes” button at the top of the Onboard I/O box.
6. Follow the previous instructions for assigning a contact closure to a zone, selecting the merged ports.
7. Click the Save Changes button in the upper left corner of the Panels page.
Verify proper operation of your Switch Set:
1. Press the ON switch. Circuits in the selected zone should immediately begin actuating.
2. The ON indicator should fl ash steadily until all of the circuits are in the on state.
3. When the zone has completed, the ON indicator should remain constantly lit.
4. Press the OFF switch. Circuits in the selected zone should immediately begin actuating.
5. The ON indicator should fl ash steadily until all of the circuits are in the off state.
6. When the zone has completed, the ON indicator should remain constantly dark. Note: When using two illuminate pushbuttons the OFF indicator will remain constantly lit when the zone has completed. (OFF indicator will extinguish immediately when ON is pressed again.)
139-0647-01.29 29
Page 30
Chapter Five--Control Setup
Email Alert Setup
Figure 5-21
Follow these steps to set an email alert
1. Go to Setup Alerts tab
2. Enter email addresses.
3. Select alert types (tripped circuit, BO/EO/EL, On Recovery and/or Temperature
4. If using Temperature alerts, enter the temperature threshold.
30
139-0647-01.30
Page 31
Chapter Six: Operating your XPC
Figure 6-1
Chapter Six--Operation
Using the built-in web page
Using a secondary controller For DMX and sACN follow the manufacturer’s instructions
139-0647-01.31 31
To operate the XPC using the built in web page, select the control tab from the top of the page. Once on the CONTROL page, simply click each circuit for individual control. Or, click a zone for zone control. “All Circuits ON” and “All circuits OFF” commands can also be executed
using the DMX addresses entered in the NETWORK page ( see page 16).
TCP/IP schemes are in Appendix B (page 38).
Page 32
Appendix A - Telnet and HTTP Protcols
Appendix A--Telnet and TCP/IP Protocols
TELNET PROTOCOL
Table B-1 Command Codes
Note: Telnet port = 23. Send Telnet commands to XPC IP address/23 (e.g. 192.168.1.250/23)
Command Decimal Hexidecimal
Start Byte 176 0xB0 Activate circuits 180 0xB4 Deactivate circuits 181 0xB5 Request all circuits status 183 0xB6 Activate zones 183 0xB7 Deactivate zones 184 0xB8 Request zones status 185 0xB9 Event ON 186 0xBA Event OFF 187 0xBB Event status 188 0xBC Request circuits status 189 0xBD Request bus status 190 0xBE
Addressing Scheme
Circuit Related Commands
Circuit status identifi er 200 0xC8 Zone status identifi er 201 0xC9 Event status identifi er 202 0xCA Emergency override identifi er 203 0xCB Checksum identifi er 204 0xCC Checksum digits 205-214 0xCD - 0xD6 Stop byte 240 0xF0
Circuit address:
1 byte. Numbers 1 through 168 (0x01 – 0xA8) are assigned to populated circuits in sequential order
Zone number: 1 byte (1-12)
Activate circuits
0xB0, 0XB4, circuit_address_1, …, circuit_address_m, 0xF0
circuit_address_1, …, circuit_address_m – addresses of circuits to be activated m<=168
32
139-0647-01.32
Page 33
Appendix A - Telnet and HTTP Protcols
Deactivate circuits
0xB0, 0xB5, circuit_address_1, …, circuit_address_n, 0xF0
circuit_address_1, …, circuit_address_n – addresses of reakers to be deactivated n<=168
Activate/deactivate circuits
0xB0, 0XB5, circuit_address_1, …, circuit_address_m, 0xB6, circuit_address_1, …, circuit_address_n, 0xF0
circuit_address_1, …, circuit_address_m – addresses of circuits to be activated circuit_address_1, …, circuit_ address_n – addresses of circuits to be deactivated m+n<=168
Request all circuits status
0xB0, 0xB6, 0xF0
Request circuits status
0xB0, 0xBD, circuit _address_i, circuit _address_j, …, circuit _address_n, 0xF0
circuit_address_1, …, circuit_address_n – addresses of circuits, status of which is requested
Request bus status
0xB0, 0xBE, bus, 0xF0 bus=0-7 – number of bus, status of which is requested
Reply to activate/deactivate circuits command: status of updated circuits
0xB0, 0xC8, circuit_address_i, circuit_status_i, circuit_ address_j, circuit_status_j, …, circuit_address_n, circuit_ status_n, 0xF0
circuit_address_i, circuit_status_i, circuit_address_j, circuit_status_j, …, circuit_address_n, circuit_status_n
139-0647-01.33 33
Page 34
Appendix A - Telnet and HTTP Protcols
Addresses and status of circuits updated by the command reply is generated for
Reply to request circuits status command:
Same format as “Request Bus Status”; contains addresses and status of the circuits specifi ed in the request command
Reply to request all circuits status command: status of all circuits
0xB0, 0xB6, byte_1, …, byte_84, 0xF0
byte_i: bits 7-4: status of circuit # 2i, bits 3-0: status of circuit # 2i-1, i=1-84
Reply to request bus status command: status of all circuits of the requested bus
Zone Related Commands
0xB0, 0xBE, byte_1, …, byte_11, 0xF0
byte_i format is identical to 3.9, except i=1-11
Circuit status description (4 bits) (3,5 &6 panels only)
Value 12 Status Off On
Activate zone
0xB0, 0xB7, zone_number_1, …, zone_number_m, 0xF0
zone_number_1, … zone_number_m – numbers of zones to be activated m<=12
Deactivate zone
0xB0, 0xB8, zone_number_1, …, zone_number_n, 0xF0
zone_number_1, … zone_number_n – numbers of zones to be deactivated n<=12
Activate/deactivate zone
34
0xB0, 0xB7, zone_number_1, … zone_number_m, 0xB8, zone_number_1, …, zone_number_n, 0xF0
zone_number_1, … zone_number_m – numbers of zones to be activatedzone_number_1, … zone_number_n –
139-0647-01.34
Page 35
Appendix A - Telnet and HTTP Protcols
numbers of zones to be deactivatedm+n<=12
Request zones status
0xB0, 0xB9, 0xF0
Reply to activate/deactivate zone command: status of updated zones
0xB0, 0xC9, zone_address_i, zone_status_i, zone_ address_j, zone_status_j, …, zone_address_n, zone_ status_n, 0xF0
zone_address_i, zone_status_i, zone_address_j, zone_ status_j, …, zone_address_n, zone_status_n – addresses and status of zones updated by the command reply is generated for
Event Related Commands
Reply to request zone status command: status of all 12 zones
0x40, 0xB9, byte_1, byte_2, byte_3, 0x80
byte_i: bits 7-6: status of zone # 4i, bits 5-4: status of zone 4i-1, bits 3-2: status of zone 4i-2, bits 1-0: status of zone 4i-3, i=1-3
Zone status description (2 bits)
Value 123 Status Off On Sequencing
Event ON
0xB0, 0xBA, event_number_1, …, event_number_m, 0xF0
event_number_1, … event _number_m – numbers of events to be turned on
m<=2
Event OFF
0xB0, 0xBB, event_number_1, …, event_number_n, 0xF0
event_number_1, … event_number_n – numbers of events to be turned off
n<=2
Event ON/OFF
0xB0, 0xBA, event_number_1, … event_number_m, 0xBB,
139-0647-01.35 35
Page 36
Appendix A - Telnet and HTTP Protcols
event_number_1, …, event_number_n, 0xF0
event_number_1, … event_number_m – numbers of events to be activated
event_number_1, … event_number_n – numbers of events to be deactivated
m+n<=2
Request event status
0xB0, 0xBC, 0xF0
Reply to activate/deactivate event command: status of updated events
0xB0, 0xCA, event_address_i, event_status_i, < event_ address_j, event_status_j>, 0xF0
Device Discovery
Emergency override response to circuit, zone, or event on/ off command
event_address_i, event_status_i, < event_address_j, event_status_j>– addresses and status of events updated by the command reply is generated for
Reply to request event status command: status of all 2 events
0xB0, 0xBC, status_byte, 0xF0
status_byte: bits 3-2: status of event #2, bits 1-0: status of event #1
Event status description (1 bit)
Value 123 Status Off On Processing
Beacon request
“AMX\r”
Beacon
“AMXB<-SDKClass=Utility><-Make=Lyntec><-Model=XPC><­Revision=1.1.4>\r”
36
139-0647-01.36
Page 37
Appendix A - Telnet and HTTP Protcols
Checksum (rev changed from 1.1.3; 1.1.3 supported old protocol)
If system is in Emergency Override mode, it replies to circuit, zone or event on/off command with emergency override response
0xB0, 0xCB, 0xF0
Checksum is optional. It is calculated as a sum of all bytes of the message starting with start byte and ending with
TCP/IP PROTOCOL
TCP/IP communications and control via a third party control system is facilitated by the use of the HTTP GET command. In the example below, GET= the XPC’s IP address
Example of GET command:
GET /p2.XPC?IPB002=1
Circuit Control = B
Zone Control = Z
Three modes of control are: Circuit control = “B” Zone control = “Z” Event Control =
“E”
Refer to LynTec XPC browser set-up for circuit numbering
GET /p2.XPC?IPB002=1
This control string will turn circuit #2 on.
GET /p2.XPC?IPB002=0
This control string will turn circuit #2 off.
Control of up to 167 circuits (4 panel system) is possible.
Confi gure your zones (circuit groups) using the LynTec XPC browser set-up when connected to the LynTec XPC panel.
GET /p2.XPC?IPZ002=1
This control string will turn zone #2 on.
GET /p2.XPC?IPZ002=0
This control string will turn zone #2 off.
139-0647-01.37 37
Page 38
Appendix A - Telnet and HTTP Protcols
Events Control = E Events include:
Event 1 = “All Circuits ON” Event 2 = “All Circuits OFF” Event 3 = “Hurry OFF” zips all circuits off fast. Event 4 = “EO” Emergency override (status only) Event 5 = “Audio Timer” (NA) (status only) Event 6 = “BO” Brown-Out (status only Event 7 = “DMX/sACN” Event 8 = “EL” Emergency Lighting
Verifi cation Scheme: The following GET command will return the current status
of all circuits, zones and events in the XPC system.
GET /p2.XPC
The system will return the following:
circuits=10110111111111111111 zones=111111111011 events=1000000
The above return is displaying the status of a 20 circuit circuits system in which all are presently ON, with the exceptions of circuit #2 and circuit #5, which are OFF.
The above return is also showing the status of 12 zones, all are ON with the exception of zone #10, which is OFF.
The events return is showing that event #1 is active = “All Circuits ON”
Status returns for Circuits: Status returns for Zones
and Events:
0 = OFF 0 = OFF 1 = ON 1 = ON 2 = Circuit Tripped (panels
2 = Processing
only) 3 = Failure 4 = Manual On (panels only) 5 = Empty
38
139-0647-01.38
Page 39
Appendix B--Troubleshooting
Appendix B--Troubleshooting/FAQ
TROUBLESHOOTING THE XPC
Use the following table if you need to troubleshoot the XPC controller.
Table B-1: XPC Controller Troubleshooting
Condition Possible Causes Solutions
Front panel LCD Dark, no activity
Unable to connect to web page
Unable to control with switch set
No power connected to input #1.
Incorrect IP address Verify IP address on front panel display
Anti-Virus software on PC Disable AV software to test
Incorrect wiring
Contact closure setup incomplete
Connect power to input #1
Test continuity of wiring. Check to make sure solder connections are secure
Check to make sure CC setup is complete. See Ch.5 for instructions
139-0647-01.39 39
Page 40
Appendix B--Troubleshooting/FAQ
Inputs Five (5) independently
confi gurable digital inputs/ outputs
Input Types Maintained N.O.
Maintained N.C. Momentary N.O. Momentary N.C. Momentary toggle
Status Output 24 Vdc (60mA maximum load for
all outputs combined) Indicator output on each I/O port
Communication Interface RJ-45 (8P8C) Ethernet/Web
Server
DMX in/thru 3-wire Circuit circuit delay 0.025 sec to 999 sec (selectable) Environmental Standards Operating Temperature: –5°C to
+60°C (internal emperature)
Storage Temperature: –20°C to
85°C
Operating Humidity: 5% to 95% Time Clock Operation during absence of
power = >2 years Memory Retention Program: > 20 years Standards Pending
ESD Immunity IEC 1000, Level 4 RF Susceptibility IEC 1000, Level 3 Electrical Fast Transient
Susceptibility Electrical Surge Suceptibility--
power line Electrical Surge Suceptibility--
data line FCC--Part 15, Class A ETL Tested to: Pending
IEC 1000, Level 3
IEC 1000, Level 4
IEC 1000, Level 3
40
139-0647-01.40
Loading...