Loren Cook ACSC-XP User Manual

Description
Certifications:
Construction:
Belts and Drives:
Model
Wheel:
Motor:
Bearings:
Product:
Typical Specifications
: ACSC-XP
:
upblast extended pressure centrifugal exhaust ventilator. Fan shall be manufactured at an ISO 9001 certified facility. Fan shall be listed by
Underwriters Laboratories as a “Power Ventilator for Smoke Control Systems” and UL listed as “Power Ventilator for Smoke Control Systems Certified for Canada”. Fan shall bear the AMCA Certified Ratings Seal for Sound and Air Performance.
The fan shall be of bolted and welded construction utilizing corrosion resistant
fasteners. The spun aluminum structural components shall be constructed of minimum 16 gauge marine alloy aluminum, bolted to a rigid aluminum support structure. The steel base shall have a one piece inlet spinning and continuously welded curb cap corners for maximum leak protection. The windband shall have a rolled bead for added strength. A two piece top cap shall have stainless steel quick release latches to provide access into the motor compartment without the use of tools. An external wiring compartment with integral conduit chase shall be provided into the motor compartment to facilitate wiring connections. The motor, bearings and drives shall be mounted on a minimum 14 gauge steel power assembly. These components shall be enclosed in a weather-tight compartment, separated from the exhaust airstream. A one inch thick, three pound density foil backed heat shield shall be utilized to protect the motor and drive components from excessive heat. Lifting lugs shall be provided to help prevent damage from improper lifting. Unit shall be tested to operate at 500 excess of 15 minutes per SBCCI requirements. Unit shall bear an engraved aluminum nameplate.
maximum fan RPM.
Packaging.
Wheel shall be centrifugal backward inclined, constructed of steel, including a
precision machined steel hub. Wheel inlet shall overlap an aerodynamic steel inlet cone to provide maximum performance and efficiency. Wheel shall be balanced in accordance with AMCA Standard 204-96, Balance Quality and Vibration Levels for Fans.
Motor shall be heavy duty type with permanently lubricated sealed ball bearings and
furnished at the specified voltage, phase and enclosure.
Bearings shall be designed and individually tested specifically for use in air handling
applications. Construction shall be heavy duty regreasable ball type in a cast iron pillow block housing selected for a minimum L50 life in excess of 200,000 hours at maximum cataloged operating speed.
Belts shall be oil and heat resistant, non-static type. Drives shall be precision
machined cast iron type, keyed and securely attached to the wheel and motor shafts. Drives shall be sized for 150 percent of the installed motor horsepower. The variable pitch motor drive must be factory set to the specified fan RPM.
Fan shall be model ACSC-XP as manufactured by
Loren Cook Company of Springfield, Missouri.
°F for 4 hours per IRI requirements and operate at 1000°F in
Nameplate shall indicate design CFM, static pressure, and
Unit shall be shipped in ISTA Certified Transit Tested
10/20/03