KLPC Series POWR-PRO® Class L Fuses

600 VAC Time-Delay 200 – 6000 Amperes

SPECIFICATIONS

Voltage Ratings:

AC: 600 Volts

 

DC: 480 Volts

Interrupting Ratings: AC: 200,000 amperes rms symmetrical 300,000 amperes rms symmetrical (Littelfuse self-certified).

DC: 20,000 amperes

Ampere Range: 200 – 6000 amperes

Approvals: AC: Standard 248-10, Class L UL Listed 601 – 6000 amps (File No: E81895)

UL Recognized 200 – 600 amps (File No: E71611)

CSA Certified 200 – 6000 amps (File No: LR29862)

QPL Federal Specifications WF-1814 700 – 6000 amps

DC: Littelfuse self-certified

AMPERE RATINGS

200

500

800

1350

2000

3500

250

600

900

1400

2100

4000

300

601

1000

1500

2200

4500

350

650

1100

1600

2300

5000

400

700

1200

1800

2500

6000

450

750

1300

1900

3000

 

Example part number (series & amperage): KLPC 1000

KLPC series POWR-PRO® fuses provide ideal overcurrent protection for circuits from 200 through 6000 amperes. KLPC series POWR-PRO® fuses specification-grade construction and performance meet or exceed the most stringent project specifications: 99.9% pure silver links, silver-plated copper end bells, glass-reinforced melamine bodies, O-ring seals between body and end bells, and granular quartz fillers.

KLPC series POWR-PRO® fuses are the only UL listed Class L fuses that provide a minimum of ten seconds time delay at 500% rated current and are also as current limiting as the fastest Class L fuse on the market. On average, the peak letthrough currents of KLPC series fuses are 10% less than any other “time-delay” Class L fuse.

APPLICATIONS

Service switches

Switchboard mains and feeders

Bolted pressure contact switches

Motor control center mains

Large motor branch circuits

UL Listed series-rated protection for molded case circuit breaker panelboards and loadcenters. (See panelboard manufacturers’ literature for recommended fuse rating.)

Primary and secondary protection for transformers

Protection of power circuit breakers

FEATURES AND BENEFITS

Eliminate unnecessary downtime — KLPC POWRPRO® series fuses’ time delay withstands system surges and keeps your circuits in service.

Best protection for system components — Maximum current limitation means less equipment and system damage when short circuits occur. Reduced damage means that electrical service can be restored quickly, reducing costly downtime, and often permitting equipment repair rather than replacement.

Coordinates with other system components — KLPC series fuses provide maximum coordination with fuses and circuit breakers both on the line and load side of the fuses. See the Fuseology section of this catalog for additional information.

Eliminate need to oversize fuses — This may permit the use of smaller less expensive switches, and, since the lower rated fuses are more current limiting, equipment receives even better protection.

300kA Interrupting Rating — Littelfuse self-certified to 300,000 amperes as standard. Meets future trend towards higher available short circuit currents.

7

Loading...
+ 2 hidden pages