OmniLink II
Press Automation
Control
OPERATING MANUAL
Version 1.0
LINK ELECTRIC & SAFETY CONTROL COMPANY |
|
444 McNALLY DRIVE, |
NASHVILLE TN 37211 |
PH (615)-833-4168 |
FAX (615)-834-1984 |
II OmniLink
Section 1 Introduction.................................................................................. |
|
1.1 |
Section 1.1 Base System...................................................................................................................................................... |
|
1.1 |
Section 1.1.1 Base System Standard Features................................................................................................................. |
|
1.1 |
Section 1.1.2 Base System Optional Features................................................................................................................. |
|
1.2 |
Section 1.2 Optional Hardware Modules............................................................................................................................. |
|
1.2 |
Section 1.3 System Overview.............................................................................................................................................. |
|
1.3 |
Section 2 Installation.................................................................................... |
|
2.1 |
Section 2.1 Preliminary Installation Considerations............................................................................................................ |
|
2.1 |
Section 2.2 Mounting System Components......................................................................................................................... |
|
2.4 |
Section 2.2.1 Mounting the Operator Terminal Enclosure.............................................................................................. |
2.4 |
|
Section 2.2.2 Mounting the Resolver .............................................................................................................................. |
|
2.5 |
Section 2.2.3 Mounting Optional Control and Monitoring Modules .............................................................................. |
2.6 |
|
Section 2.3 Wiring System Modules and Components........................................................................................................ |
|
2.8 |
Section 2.3.1 Conduit Runs............................................................................................................................................. |
|
2.8 |
Section 2.3.2 Wiring the Resolver to the R/D-Brake Monitor Module........................................................................... |
2.9 |
|
Section 2.3.3 Wiring 115VAC Power From Press Control to Operator Terminal ........................................................ |
2.12 |
|
Section 2.3.4 Wiring the Valve Voltage Circuit ........................................................................................................... |
|
2.14 |
Section 2.3.5 Wiring the OmniLink Stop Circuit Output.............................................................................................. |
|
2.14 |
Section 2.3.6 Wiring the Optional Setup Mode Input................................................................................................... |
|
2.16 |
Section 2.3.7 Wiring Optional Analog Input/Output Board Circuits ............................................................................ |
2.17 |
|
Section 2.3.7.1 Wiring to Display Motor Load Current ........................................................................................... |
2.17 |
|
Section 2.3.7.2 Wiring the Analog Speed Input and Output .................................................................................... |
2.17 |
|
Section 2.3.8 Optional Solid State Relay Outputs......................................................................................................... |
|
2.20 |
Section 2.4 Additional Mounting and Wiring if the Operator Terminal, R/D-Brake Monitor Module, and (Optionally) |
|
|
Solid State Relay Module are Provided Without Enclosure for Customer Panel Mounting.............................................. |
2.21 |
|
Section 2.4.1 Mounting the Base Components in the Customer Enclosure .................................................................. |
2.21 |
|
Section 2.4.2 Wiring the Base Components in the Customer Enclosure....................................................................... |
2.22 |
|
Section 2.5 Wiring Serial Ports for Serial Feed Interface, PLC Interface, and LinkNet Information System Options ..... |
2.22 |
|
Section 2.6 Wiring the Parallel Port for Messages from Auxiliary Equipment (Optional)................................................ |
2.23 |
|
Section 3 Operator Terminal Basics........................................................... |
|
3.1 |
Section 3.1 OmniLink II Press Automation Control LCD Operator Terminal .................................................................... |
3.1 |
|
Section 3.2 Operator Terminal Modes................................................................................................................................. |
|
3.2 |
Section 3.3 Softkeys ............................................................................................................................................................ |
|
3.3 |
Section 3.4 ACC Key .......................................................................................................................................................... |
|
3.3 |
Section 3.5 CHG Key .......................................................................................................................................................... |
|
3.4 |
Section 3.6 Arrow keys........................................................................................................................................................ |
|
3.4 |
Section 3.7 Numeric Data Entry .......................................................................................................................................... |
|
3.4 |
Section 3.8 Alphanumeric Data Entry ................................................................................................................................. |
|
3.5 |
Section 3.9 Access Control Operation for Settings and Actions in Program Mode............................................................. |
3.8 |
|
Section 3.9.1 Program/Run Key Switch Operation......................................................................................................... |
|
3.8 |
Section 3.9.2 Using Key Only Access to Program Mode for Settings and Actions........................................................ |
3.9 |
|
Section 3.9.3 Code (Password) System Operation........................................................................................................ |
|
3.11 |
Section 3.9.4 Automatic Log Out ................................................................................................................................. |
|
3.14 |
Section 4 Device and Main Configuration Menus.................................... |
4.1 |
|
Section 4.1 Device Configuration Menu ............................................................................................................................. |
|
4.1 |
Section 4.2 The Main Configuration Menu ......................................................................................................................... |
|
4.4 |
Section 4.2.1 Machine Parameters Menu........................................................................................................................ |
|
4.7 |
Section 4.2.1.1 Configuring the Encoder (Resolver) Type......................................................................................... |
4.7 |
|
Section 4.2.1.2 Setting Top of Stroke Angle.............................................................................................................. |
|
4.7 |
Section 4.2.1.3 Setting Minimum Press Speed and Loss Of Motion Time ................................................................ |
4.8 |
|
Section 4.2.1.4 Temporarily Setting Other Items on the Machine Parameter Screen So that the Press Can be Stroked |
||
Without Generating Brake Monitor or Motion Detector Faults ................................................................................. |
4.9 |
|
Section 4.2.1.5 Setting Encoder Offset ...................................................................................................................... |
|
4.9 |
Section 4.2.1.6 Use Mode Input Setting................................................................................................................... |
|
4.12 |
Section 4.2.1.7 Setting Clutch Engagement Time Limit .......................................................................................... |
4.12 |
|
August 30, 2002 Manual Version 1.0 |
i |
|
Section 4.2.1.8 Setting Brake Monitor Top Stop and Brake Monitor Mid Stroke Stop Limits ................................ |
4.13 |
|
Section 4.2.2 Speed/Load Configuration Menu Settings |
............................................................................................... |
4.14 |
Section 4.2.2.1 Setting Speed Mode......................................................................................................................... |
|
4.15 |
Section 4.2.2.2 Calibrating Variable Speed Drive Input ...............................SPM When “Input Only” is Selected |
4.16 |
|
Section 4.2.2.3 Calibrating Variable Speed Drive Input SPM When Output Without Recall or Output With Recall is |
||
Selected for Speed Mode.......................................................................................................................................... |
|
4.17 |
Section 4.2.2.4 Calibrating the Analog Output SPM Signal ......................................to Give Correct Drive Speed |
4.17 |
|
Section 4.2.2.5 Calibrating Percent Motor Load ...................................................................................................... |
|
4.20 |
Section 4.2.2.6 Setting Speed Parameters................................................................................................................. |
|
4.20 |
Section 4.2.3 Top Stop Calibration Menu Settings ....................................................................................................... |
|
4.20 |
Section 4.2.3.1 Top Stop Calibration for Fixed Speed .................................................................................Presses |
4.22 |
|
Section 4.2.3.2 Variable Speed Press Auto Top Stop ............................................................................Calibration |
4.23 |
|
Section 4.2.4 Operator Terminal Configuration............................................................................................................ |
|
4.26 |
Section 4.2.4.1 Top Area (Screen) Display Configuration ....................................................................................... |
4.26 |
|
Section 4.2.4.2 Zeroing Stroke Count....................................................................................................................... |
|
4.27 |
Section 4.2.4.3 Key/Code Access Configuration...................................................................................................... |
|
4.28 |
Section 4.2.4.4 Auxiliary Communications Setup.................................................................................................... |
|
4.33 |
Section 4.2.5 Auxiliary Equipment Messages............................................................................................................... |
|
4.33 |
Section 5 Using the OmniLink II Press Automation Control Standard |
|
|
Functions and Optional Speed Adjust .......................................Function |
5.1 |
|
Section 5.1 Main Menu (Screen) ......................................................................................................................................... |
|
5.1 |
Section 5.2 Brake Monitor and Diagnostic Screen .............................................................................................................. |
|
5.2 |
Section 5.2.1 Brake Monitor ........................................................................................................................................... |
|
5.3 |
Section 5.2.2 Clutch Engagement Time Monitor ............................................................................................................ |
|
5.4 |
Section 5.2.3 Critical Angle and Intellistop .................................................................................................................... |
|
5.4 |
Section 5.2.4 Stopping Degrees....................................................................................................................................... |
|
5.6 |
Section 5.2.5 Auxiliary Equipment Messages................................................................................................................. |
|
5.7 |
Section 5.2.6 Reason for the Last Stop............................................................................................................................ |
|
5.7 |
Section 5.2.7 Present Running Status.............................................................................................................................. |
|
5.7 |
Section 5.2.8 Diagnostics ................................................................................................................................................ |
|
5.7 |
Section 5.2.9 Module Limit Switch................................................................................................................................. |
|
5.8 |
Section 5.3 Counters ............................................................................................................................................................ |
|
5.9 |
Section 5.3.1 Production Counters .................................................................................................................................. |
|
5.9 |
Section 5.3.1.1 Production Counters On/OFF .......................................................................................................... |
|
5.10 |
Section 5.3.1.2 Production Counters Change Limit ................................................................................................. |
|
5.11 |
Section 5.3.1.3 Production Counters Reset............................................................................................................... |
|
5.11 |
Section 5.3.1.4 Production Counters Increment/Decrement..................................................................................... |
5.11 |
|
Section 5.3.1.5 Production Counters Change Count................................................................................................. |
|
5.12 |
Section 5.3.2 Stroke Counter......................................................................................................................................... |
|
5.12 |
Section 5.3.3 Scrap Counter .......................................................................................................................................... |
|
5.12 |
Section 5.3.4 Configure Counters ................................................................................................................................. |
|
5.13 |
Section 5.3.4.1 Configure Auxiliary Counter Names ............................................................................................... |
|
5.13 |
Section 5.3.4.2 Configure Counter Count By Value ................................................................................................ |
|
5.14 |
Section 5.3.4.3 Configure Counter Every How Many ........................................................................Stroke Value |
5.14 |
|
Section 5.3.4.4 Configure Counter Reset When Order .....................................................................Counter Reset |
5.15 |
|
Section 5.3.4.5 Configure Counter Enable ............................................................................................................... |
|
5.15 |
Section 5.3.4.6 Configure Reset Counters When Job ................................................................................Recalled |
5.15 |
|
Section 5.4 Motor Speed Adjustment (Option).................................................................................................................. |
|
5.15 |
Section 5.5 Quick Access (ACC key) ................................................................................................................................ |
|
5.16 |
Section 5.5.1 Machine Notes......................................................................................................................................... |
|
5.17 |
Section 5.5.2 Job Notes ................................................................................................................................................. |
|
5.17 |
Section 5.5.3 Editing Machine Notes and Job Notes..................................................................................................... |
|
5.17 |
Section 5.5.4 Auxiliary Communications...................................................................................................................... |
|
5.18 |
Section 5.5.5 LOGOUT Softkey ................................................................................................................................... |
|
5.18 |
Section 5.6 Job Setups (Storage and Recall)...................................................................................................................... |
|
5.18 |
Section 5.6.1 Store Setup .............................................................................................................................................. |
|
5.19 |
August 30, 2002 Manual Version 1.0 |
ii |
|
Section 5.6.2 Recall Setup ............................................................................................................................................ |
5.20 |
Section 5.6.3 Erase Setup.............................................................................................................................................. |
5.21 |
August 30, 2002 Manual Version 1.0 |
iii |
Section 1 Introduction
The OmniLink II Press Automation Control for part revolution clutch mechanical power presses is a flexible, intelligent, modular system that can be applied to presses with existing clutch brake and motor controls to provide a wide variety of control; press, die, and process monitoring; and management information functions. The system integrates setting and display of all functions through the OmniLink II Color LCD Operator Terminal, which includes a 9.2” diagonal color TFT liquid crystal display (LCD) with high brightness and large viewing angle, membrane keys for entry and navigation, and a Program/Run keyswitch.
Section 1.1 Base System
The base system hardware package consists of the OmniLink II Color Operator Terminal and R/D-Brake Monitor Module in an enclosure (panel mount versions are also available), and a resolver and its cable with connector. The Operator Terminal is the central operator interface for display and settings of all system functions and diagnostics. The easy to use large color TFT LCD display of the operator terminal provides the screens and menus. The operator terminal keypad is used to program settings or store or recall jobs. The resolver provides precise press crank or eccentric shaft angular position and speed to sequence and monitor press automation functions.
Section 1.1.1 Base System Standard Features
•Control reliable time base brake monitor with dual limits for top and midstroke stopping.
•Clutch engagement time monitor that can aid in determining when clutch adjustment or disc replacement should be done.
•Motion detection to detect resolver decoupling from the crankshaft.
•Powerful counting capability with 12 counters, 10 with flexible configuration.
•Six serial ports are provided, one of which is a high speed serial interface over which the operator terminal and optional modules communicate. Others are used to communicate with intelligent controllers that control automation related to the press production system. One can be used provide Link’s optional Serial Feed Interface that sets up a feed for a job when recalled from storage on the OmniLink II Operator Terminal and displays feed settings on the operator terminal screen. Another can be used for Link’s optional PLC Interface to send job settings to a PLC programmed to perform automation and display status and diagnostic messages from the PLC.
•Auto top stop compensation for variable speed presses in the Continuous mode.
•Operator screens in English or Spanish at the touch of a key, intelligent diagnostics of the base system and all system options in English and Spanish, “Help” in English and Spanish that automatically appears on the display screen for many data entry fields for settings.
•500 job storage for all settings associated with standard and optional functions of the system.
August 30, 2002 Manual Version 1.0 |
1.1 |
Section 1.1.2 Base System Optional Features
•An optional analog input/output card allows stroking speed to be adjusted and displayed on the operator terminal even when not stroking for variable speed presses. It also allows motor load current to be displayed.
•Serial Feed Interface for most available electronic roll feeds.
•A flexible PLC interface that allows the OmniLink II Operator Terminal to send settings for jobs and receive status and diagnostic messages from the PLC for display on the operator terminal screen.
•LinkNet Shopfloor Information System - networks your presses to computer(s) to gather information and provide comprehensive management information database and reporting system.
Section 1.2 Optional Hardware Modules
The system is designed to allow additional hardware modules to be added to the base system package to perform a wide variety of control and monitoring functions. The system uses distributed intelligence -- each optional module has its own microprocessor to perform its logic functions. This provides increased computing power and superior performance, allowing more logic functions to be performed at greater speeds. All optional modules communicate to each other and to the OmniLink II Operator Terminal through a high speed serial bus cable with only four connections. This eliminates the need to individually wire all inputs and outputs back to the operator terminal. Adding modules is simple and quick, mount the module and wire the 3 wire and drain connection cable from the last module previously installed to the newly installed module.
Optional hardware modules that are currently available for the system are:
•The 5120 series Die Protection and Process Monitor modules available with 8 or 16 sensor inputs per module. Up to five 5120 series modules may be used with the system, giving a maximum of 80 total inputs for digital die protection and process monitoring.
•The 5105 series PLS/Logic Module available with 8 or 16 output relays (electromechanical, solid state ac, and solid state dc relays available) for programmable limit switch (PLS) or other output relay (OR) logic functions. Each module also has 16 inputs available for logic or sensing applications. Up to four 5105 series modules may be used with the system for a maximum of 32 PLS outputs, 32 OR outputs, and 64 sensing or logic inputs.
Optional hardware modules that are planned as additions to those currently available are:
•A 5108 series of Signature and Tonnage Monitor modules.
•A 5110 series of Auto Setup Modules that can automatically recall and set up shutheight, counterbalance pressure, cushion pressure, etc., when a job is recalled.
•A 5130 series of Analog Die Protection and Process Monitoring modules to measure production process variables and part features during stamping. Gives capability for 100% “in process” parts quality inspection when used with appropriate input sensors.
August 30, 2002 Manual Version 1.0 |
1.2 |
Section 1.3 System Overview
Figure 1.1 shows the base package hardware components for the OmniLink II Press Automation Control.
Crank or |
RESOLVER |
Eccentric |
|
Shaft |
|
OMNILINK II PRESS AUTOMATION CONTROL
RESOLVER CABLE
Figure 1.1 OmniLink II Press Automation Control Base System Package
Figure 1.2 (next page) shows the existing and planned components and features of the system with optional components.
August 30, 2002 Manual Version 1.0 |
1.3 |
CRANK OR |
RESOLVER |
|
|
ECCENTRIC |
|
SHAFT |
|
OMNILINK II PRESS AUTOMATION CONTROL
RESOLVER CABLE
LINKNET
HIGH SPEED SERAIL BUS CABLE (3 WIRES AND DRAIN)
SERIAL PLC INTERFACE CABLE
FEED
PROGRAMMABLE
LOGIC
CONTROLLER
SERIAL FEED INTERFACE CABLE
UP TO 32 PROGRAMMABLE LIMIT SWITCH AND
32 LOGIC OUTPUTS - 8 OR 16 RELAYSPER MODULE UP TO 80 DIE PROTECTION & PROCESS 16 LOGIC & MONITORING INPUTS PER MODULE
MONITORING INPUTS -- 8 OR 16 PER MODULE
MODEL |
MODEL |
MODEL 5120 |
MODEL |
|
|
|
|
MODEL 5100-5 |
|
MODEL 5100-5 |
||
|
|
|
PROGRAMMABLELINKLIMIT SWITCH |
|||||
|
|
|
LINK |
|
||||
LINK |
LINK |
|
DIE PROTECTION& |
& |
PROGRAMMABLE LIMIT SWITCH |
|||
|
DIE PROTECTION & |
|||||||
DIE PROTECTION & |
DIE PROTECTION & |
|
|
PROCESS |
|
|
PROCESS&MONITOR |
|
PROCESS MONITOR |
PROCESS |
MORE |
|
MODULE |
|
|
MODULE |
|
MODULE |
MODULE |
|
NUMBER/ |
|
|
NUMBER/ |
|
|
NUMBER/ |
NUMBER/ |
|
|
|
|
|
|
|
|
|
MODULES |
LINK ELECTRIC & SAFETY CONTROL |
LINK ELECTRIC & SAFETY CONTROL |
||||
|
|
|
444 |
McNally Drive |
Nashville, TN |
444 McNally Drive |
Nashville, TN |
|
|
|
|
|
37211 |
|
|
37211 |
|
|
|
|
|
Phone: (615) 833-4168 |
Phone: (615) 833-4168 |
OTHER MODULES TO BE
DEVELOPED
Analog Die & Process Monitor Module
Tonnage & Signature Monitor Module
AutoSets for Shut Height and
Figure 1.2. Existing and Planned System Components and Functions
August 30, 2002 Manual Version 1.0 |
1.4 |
Section 2 Installation
Section 2.1 Preliminary Installation Considerations
1.Before you begin to install your OmniLink II Press Automation Control, you should read this entire manual carefully. This will help you to understand system functions and plan the installation to save time and the necessity to rework portions of the installation.
2.The high speed serial bus used to communicate between system modules begins with the OmniLink II LCD Operator Terminal and goes first to the R/D-Brake Monitor Module located in the back of the operator terminal enclosure, then on to each optional hardware module used with the system as shown in Figure 2.1. Every hardware module used with the system has a switch that can be closed to terminate the serial bus. The termination switch on the module installed at the far end of the serial bus should be thrown to the closed position. The switches on modules installed between the operator terminal and the last module should be in the open position. If only one optional module is used with the system, the termination switch on this module should be thrown to the closed position. If no optional modules are used with the system, the bus termination switch on the 802-5 R/D-Brake Monitor Module should be thrown to the closed position. The location of the termination switch for the 802-5 R/D-Brake Monitor Module is shown in Figure 2.1.
802-5 R/D-Brake Monitor Module |
||||||
Analog Input/Output |
|
|
|
|
|
|
Board Option |
Microprocessor 2 |
|
|
|
||
|
|
|
|
|||
|
|
|
|
|
|
Transformer |
|
|
Microprocessor 1 |
|
|
||
|
Microproc. 1 |
|
|
|
||
|
Prog. Memory |
|
|
|
||
|
R/D |
|
|
|
|
Output |
|
|
|
|
|
Relays |
|
|
IC |
|
|
|
|
|
CON8 |
|
|
|
CanBus Termination |
|
|
|
|
|
Switch |
|
Fuse |
|
1 2 3 4 5 |
|
|
|
|
||
CON7 |
|
CON1 |
|
CON2 |
CON5 |
CON4 |
R1 2 3 4 5 6 7 8 9 10 11 12 13 |
SHLD GND CANH |
CANL |
1 2 3 4 5 6 7 8 |
L1 L2 G ND 1 2 3 4 |
||
|
|
|
|
|
||
Figure 2.1 802-5 R/D-Brake Monitor Module |
|
|
3.As shown in Figure 2.2, optional hardware modules may come with one module or multiple modules per enclosure, depending on the number and type of modules ordered. The modules do not have to be connected in any particular order on the serial bus, but the serial bus cable must connect to each module in the daisy chain fashion shown in Figure 2.2. It is desirable to run the cable for the serial bus to connect the optional hardware modules with the shortest total length of cable. The total length of serial bus cable used with the system must not exceed 300 feet.
August 30, 2002 Manual Version 1.0 |
2.1 |
It is also convenient to run the 115VAC power along with the high-speed serial bus cable to each module(s) enclosure in the same flexible liquid tight conduit with ground, as indicated in Figure 2.2.
|
USE THE SWITCH ON THE OPTION INSTALLED |
|
OPERATOR |
||
AT THE FAR END OF THE CABLE FROM THE |
||
TERMINAL |
||
OPERATOR TERMINAL TO TERMINATE THE |
||
ENCLOSURE |
||
SERIAL BUS CABLE. |
||
|
||
|
|
SERIAL BUS CABLE AND POWER FOR
MODULES RUN IN SAME CONDUIT
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O |
|
|
|
|
O |
|
|
O |
|
|
|
O |
|
|
|
|
|
|
|
|
O |
|
||||||||||||||||||||||||||
|
|
|
|
P |
|
|
|
|
P |
|
|
|
P |
|
|
|
|
P |
|
|
|
|
|
|
|
|
|
P |
|
||||||||||||||||||||||
|
|
|
|
T |
|
|
|
|
T |
|
|
|
T |
|
|
|
|
T |
|
|
|
|
|
|
|
|
|
T |
|
||||||||||||||||||||||
|
|
|
|
|
I |
|
|
|
|
|
I |
|
|
|
|
I |
|
|
|
|
|
I |
|
|
|
|
|
|
|
|
|
I |
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
O |
|
|
|
|
O |
|
|
O |
|
|
|
O |
|
|
|
|
|
|
|
|
O |
|
||||||||||||||||||||||||||
|
|
|
N |
|
|
|
|
N |
|
|
N |
|
|
|
N |
|
|
|
|
|
|
|
|
N |
|
||||||||||||||||||||||||||
|
|
|
|
|
1 |
|
|
|
|
2 |
|
|
3 |
|
|
4 |
|
|
|
|
|
|
|
|
5 |
|
|
|
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 2.2 Serial Bus Connections
3.Dual connector plugs are used for each optional module shown in Figure 2.2 for both the highspeed serial bus and 115VAC power connection to the module. This allows both the serial bus and power connections to be strung from module to module as shown in Figure 2.3.
Cable Wire Color |
Connector |
SHIELD MUST BE |
SERIAL BUS CABLE |
|||
TO NEXT MODULE |
||||||
|
Terminal |
CONNECTED TO PLUG |
||||
|
|
|
||||
White |
|
CANL |
|
|
||
Orange |
|
CANH |
|
|
||
Blue |
|
GND |
SERIAL BUS CABLE |
PLUGS INTO MODULE |
||
Bare |
|
Shield |
FROM LAST MODULE |
CONNECTOR HEADER |
||
|
|
|
|
|
FOR THIS MODULE |
|
|
|
|
|
|
SERIAL BUS CONNECTOR |
|
|
|
115VAC TO NEXT |
PLUG FOR THIS MODULE |
|||
|
|
MODULE |
|
|
||
|
L1 |
|
|
16 GA RED, WHITE, |
|
|
|
L2 |
G |
GREEN WIRES |
|
||
|
|
|
||||
|
|
|
|
|
||
|
|
|
N |
|
|
|
|
|
|
D |
PLUGS INTO MODULE |
|
|
115VAC FROM |
|
|
|
CONNECTOR HEADER |
|
|
|
|
|
FOR THIS MODULE |
|
||
LAST MODULE |
|
|
|
|
||
|
|
|
|
|
||
16 GA RED, WHITE, |
115VAC CONNECTOR PLUG |
|
||||
GREEN WIRES |
FOR THIS MODULE |
|
||||
Figure 2.3 Dual Connector Plugs for Modules for Serial Bus and Power |
||||||
August 30, 2002 Manual Version 1.0 |
|
|
2.2 |
|
4. NEVER use any cable other than that supplied by Link Systems for the high-speed serial bus that interconnects the various components of the OmniLink II Press Automation Control. This cable has been chosen to optimize communication speed and distance for the serial bus. Use of other cables may result in communication faults that cause nuisance stops of your press production system. DO NOT splice sections of cable between OmniLink II modules. Use unbroken runs of cable between modules.
5.The wiring instructions for installation contained in this manual are necessarily generic since the OmniLink II Press Automation Control may be interfaced with a wide variety of control systems using multiple relay and electronic components. If the installer has questions related to the proper installation of the system, contact the service personnel at Link Systems. Always test each component of the system installation to see that proper function is obtained. In particular, make certain that all stop outputs from the OmniLink system to the press control are interfaced properly.
!WARNING! Improper system installation or improper interface of stop outputs from the OmniLink system to the press control may result in damage to press, dies or other equipment and increase the possibility of injury to operators and others. Use qualified installers.
6.Installation of this system should be done in accordance with OSHA’s lockout/tagout regulations (see CFR 1910.147). You will be mounting OmniLink components on the press, and may be exposed to mechanical hazards if press movement should occur during mounting activities. You will also be wiring electrical circuits that will use 115VAC (nominal) voltages. Unless these circuits are de-energized during wiring activities, a serious or even fatal shock may occur. Depending on the options purchased with your OmniLink system, you may also be installing air valves or pressure sensors for air counterbalance or air cushion systems. These air systems could cause serious injury if not depressurized before installation is started. Remove hazardous energy during OmniLink system installation in accordance with CFR 1910.147.
!WARNING! Failure to comply with CFR 1910.147 regulations and remove hazardous energy during installation of the OmniLink II Press Automation Control may result in serious injury or death! Use only qualified installers trained in lockout procedures for installation.
August 30, 2002 Manual Version 1.0 |
2.3 |
Section 2.2 Mounting System Components
Section 2.2.1 Mounting the Operator Terminal Enclosure
The OmniLink II LCD Operator Terminal must be mounted in a position that is easily seen and accessed by the operator. The liquid crystal display is designed for optimum viewing from the bottom of the display. If the operator terminal is mounted in a vertical plane, it should be mounted slightly above the operator's eye level for best visibility. If mounted in a sloped position, it should be mounted so that the operator's line of sight is from the bottom of the LCD. The desirable orientations are shown in Figure 2.4.
Figure 2.4 LCD Mounting Orientations
The OmniLink II Press Automation Control operator terminal is usually furnished mounted on the front of an enclosure, which also contains the R/D-Brake Monitor Module mounted in the back of the enclosure and pre-wired to the operator terminal. Figure 2.5 gives the dimensions of the operator terminal enclosure, including mounting dimensions.
August 30, 2002 Manual Version 1.0 |
2.4 |
|
|
|
|
|
|
11.00 ( 27.74) |
|
|
|
|
0.312 (.792) |
|
|
|
|
|
|
|
|
|
|
|
Diameter |
||
|
|
|
|
|
|
|
|
|
|
|
|
(4 Places) |
|
|
|
OmniLink II LCD |
|
|
|
|
|||||
|
|
|
|
OPERATOR TERMINAL |
|
|
|
|
||||
|
|
0 |
0 |
Driv e |
|
0 SP M |
Order |
N |
|
|
|
|
|
|
|
Speed |
|
C ount er |
Counter OFF |
|
|
|
|
||
|
T OP |
Strok e |
Stroke |
|
0 SP M |
SYS TEM STATUS |
|
|
|
|
||
|
Mode |
|
OK |
|
|
|
|
|
||||
|
|
Speed |
|
READY TO STROKE |
|
|
|
|
||||
|
|
|
|
|
|
|
|
MAIN |
|
|
|
|
|
|
|
|
|
|
|
|
SCREEN |
|
|
|
|
|
|
|
|
|
STATUS: |
|
BRAKE |
CHG |
|
ACC |
|
|
|
|
|
|
|
|
PRESS |
|
|
||||
|
|
|
|
|
OK |
|
|
MOCONTRNITORL |
|
|
|
|
11.65 |
|
|
|
|
STATUS: |
|
AUTO |
|
|
|
|
|
(29.59) |
|
|
|
|
ALL CON DITI ONS OKAY |
SETS |
|
|
|
|
||
|
|
|
|
STATUS: |
|
TONNAGE |
7 |
8 |
9 |
11.125 |
||
|
|
|
|
|
|
|||||||
10.4 |
|
|
|
|
ALL CON DITI ONS OKAY |
|||||||
|
|
|
|
MON ITOR |
||||||||
|
|
|
|
|
|
|
|
|
|
|
(28.26) |
|
(26.42) |
SPM |
% LOAD |
|
STATUS: |
|
DIE |
4 |
5 |
6 |
|||
|
0 |
161 |
|
|
ALL CON DITI ONS OKAY |
PROTEC TION |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JOB NUMBER |
DESCRIPTION |
LIMIT |
1 |
2 |
3 |
|
|||
|
|
|
SWITCH |
|
||||||||
|
|
|
|
100000 |
|
FRONT BRACKET |
|
|||||
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
COUNTER LIMIT |
|
QUANTI TY |
STATE |
JOB |
CLR |
0 |
ENT |
|
|
|
|
|
ORDER |
2000 |
|
7 |
ON |
|
||||
|
|
|
|
SETUPS |
|
|||||||
|
|
|
|
|
|
|
||||||
|
|
|
BATCH |
500 |
|
7 |
ON |
|
|
|
|
|
|
MOTOR |
|
|
|
|
|
|
C OUNTERS |
|
|
|
|
|
SPEED |
|
|
|
|
|
|
|
|
|
|
|
LINK ELECTRIC & SAFETY C ONTROL CO. |
PROG |
RUN |
444 McN ALLY DR. NASHVILLE, TN 37211 |
|
|
PHONE (615) 833-4168 |
|
|
OmniLink II Press Automation Control
Enclosure Depth: 6 (15.24)
13.50 (34.29)
Figure 2.5 Dimensions for Mounting OmniLink II LCD Operator Terminal
Section 2.2.2 Mounting the Resolver
Mounting the resolver to be driven in a one to one ratio by the crank or eccentric shaft. The resolver may be direct driven by a coupling off the center of the shaft or driven by a chain and sprockets as shown in Figure 2.6.
NOTE! A CHAIN GUARD
IS NECESSARY TO MEET OSHA 1910.219 STANDARDS
|
|
|
|
|
|
|
|
|
|
|
|
RESOLVER |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
CHAIN |
|
|
|
|
|
|
|
|
PRESS |
|||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
CROWN |
|||||||
ECCENTRIC |
|
|
|
|
|
|
|
|
|||||
CRANK OR |
|
|
|
|
|
|
|
||||||
SHAFT |
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 2.6 Mounting the 2500 or 5000 Resolver
August 30, 2002 Manual Version 1.0 |
2.5 |
The standard resolver used with the OmniLink II press Automation Control is the 2500 Resolver. A 5000 Resolver can optionally be used with the system. In either case, a spring loaded mounting base, as shown in Figure 2.7, will be supplied with the resolver to maintain chain tension if the resolver is chain and sprocket driven. Mount the resolver on the spring base. Mount the spring base to accommodate alignment of chain and sprockets so that they may be driven by crank or eccentric shaft.
|
|
ER |
|
LV |
|
SO |
|
|
RE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SE |
|
||
|
|
|
|
EDBA |
|
|||
|
|
|
AD |
|
|
|
|
|
|
|
G |
LO |
|
|
|
|
|
|
RIN |
|
|
|
|
|
|
|
|
SP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CHAIN
CRANK OR ECCENTRIC
SHAFT
Figure 2.7 Resolver Mounted on Spring Base to Maintain Chain Tension for Chain Drive
Chain and sprockets may have been purchased from Link Systems. If so, the sprockets will be 35B28 (28 teeth) and chains will be size 35 roller chain. Link suggests that, if the customer provides chain and sprocket, the same type be used. This resolver electronic offset during calibration can only correct +/- 10o of mechanical misalignment, and 28 teeth make it easier to be within the offset that can be corrected.. If you have a press that only provides access to an intermediate shaft or back shaft for connection of the resolver, you will have to determine how many turns this shaft makes for each turn of the crank or eccentric shaft. You must then use sprockets of different size, chosen to provide one turn of the resolver for one turn of the crank or eccentric shaft.
Section 2.2.3 Mounting Optional Control and Monitoring Modules
If you have purchased Die Protection & Process Monitoring, PLS/Logic, Auto Sets, Tonnage & Signature Monitoring, or other optional modules, these may be packaged in separate or combined enclosures, depending on how they were ordered. Figure 2.8 shows the mounting dimensions for the 8 or 16 channel Die Protection and Process Monitor Module enclosure and the enclosure for a single PLS/Logic Module. Mount the enclosures for these modules in locations where the enclosure doors can be easily opened for module access and wiring. Multiple module enclosures will be shipped with mounting dimensions inside the enclosure.
August 30, 2002 Manual Version 1.0 |
2.6 |
|
.312 (.7925) 4 Places |
|
8 OR 16 CHANNEL |
|
DIE PROTECTION AND |
|
PROCESS MONITOR |
|
MODULE ENCLOSURE |
11.125 |
10.5 |
(28.258) |
(26.67) |
|
6.6 |
|
(16.76) |
|
4” DEEP |
|
4.25 |
|
(10.795) |
|
.312 (.7925) 4 Places |
|
ENCLOSURE FOR SINGLE |
|
PLS/LOGIC MODULE |
13.75 |
13.3 |
(34.925) |
(33.782) |
|
7 |
|
(17.78) |
|
4.75” DEEP |
|
4.75 |
|
(12.065) |
Figure 2.8 Mounting Dimensions for 8 or 16 Channel Die Protection or Single PLS/Logic Units
August 30, 2002 Manual Version 1.0 |
2.7 |
Section 2.3 Wiring System Modules and Components
Section 2.3.1 Conduit Runs
Wiring between the enclosures for OmniLink II Press Automation Control components should be run in conduit. The use of flexible liquid tight conduit with ground is suggested, but hard conduit can also be used. Figure 2.9 shows some of the typical conduit runs that may be required.
CHAIN
CRANK OR
ECCENTRIC
1/2’ Flexible liquid tight conduit with ground for 2500 Resolver cable. (3/4” for 5000 Resolver.)
RESOLVER
PRESS |
PR ESS CONTROL
1/2” Flexible conduit with ground for 115VAC from press control transformer, connections to control dual valve output, stop outputs from OmniLink to press control.
1/2” Flexible liquid tight conduit with ground for high speed serial bus cable and power to OmniLink II Press Automation Control optional modules
|
|
|
OmniLink II LCD |
|
|
|
|||||
|
|
|
|
OPERATOR T ERMINAL |
|
|
|
||||
|
0 |
0 |
|
Drive |
0 SP M |
Or der |
CounterONOFF |
|
|
|
|
|
|
|
S peed |
Co unter |
|
|
|
||||
TOP |
S troke |
|
S troke |
0 SP M |
SYSTEM ST ATUS |
|
|
|
|||
Mode |
|
OK |
|
|
|
|
|||||
|
|
S peed |
REA DY TO STROKE |
|
|
|
|||||
|
|
|
|
|
|
|
|
MAIN |
|
|
|
|
|
|
|
|
|
|
|
SCREEN |
|
|
|
|
|
|
|
|
S TA TUS: |
|
BRAP ESSKE |
CH G |
|
AC C |
|
|
|
|
|
|
OK |
|
|
MONICON TROLT OR |
|
|
|
|
|
|
|
|
S TA TUS: |
|
AUTO |
|
|
|
|
|
|
|
|
|
ALL CONDITIONS OKAY |
SETS |
|
|
|
||
|
|
|
|
|
S TA TUS: |
|
TO NNAGE |
7 |
8 |
9 |
|
|
|
|
|
|
ALL CONDITIONS OKAY |
MON ITOR |
|||||
SPM |
% LOAD |
|
|
S TA TUS: |
|
DIE |
4 |
5 |
6 |
||
161 |
|
|
|
ALL CONDITIONS OKAY |
|||||||
0 |
|
|
|
|
|
|
|
P ROT EC TION |
|
|
|
|
|
|
J OBN UMBER |
DES CRIP TION |
LIM IT |
1 |
2 |
3 |
|||
|
|
|
|
1000 00 |
FRON T BRACKET |
SW ITCH |
|
|
|
||
|
|
|
COU NTER |
L MIT |
QUANTITY |
S TATE |
JOB |
C LR |
0 |
E NT |
|
|
|
|
ORDER |
|
2000 |
7 |
ON |
||||
|
|
|
|
SE TUPS |
|
|
|||||
|
|
|
BATCH |
|
500 |
7 |
ON |
|
|
|
|
MOTOR |
|
|
|
|
|
|
|
C OUN TERS |
|
|
|
SPEED |
|
|
|
|
|
|
|
|
|
|
|
L IN K E LECTRIC & SAFET Y CONTROL CO. |
|
|
PROG |
|
RUN |
||||||
4 4 M cNALL YDR. |
NAS HVIL LE, TN |
37 2 1 |
|
|
|
|
|
|
|||
PH ONE (61 5) |
83 3-4 1 68 |
|
|
|
|
|
|
|
|
OmniLink II Press Automation Control
1/2” Flexible liquid tight conduit(s) with ground for other OmniLink system options
1/2” Flexible liquid tight conduit with ground if any optional low voltage connections: setup mode input, analog speed or motor current signals are used.
Figure 2.9. General View of Components and Wiring Runs for Installation.
August 30, 2002 Manual Version 1.0 |
2.8 |
The conduit runs that you will or may need, depending on the options you purchase and features that you wish to use on your OmniLink II, are:
•Conduit from resolver to R/D-Brake Monitor Module in OmniLink Operator Terminal enclosure.
•Conduit for 115VAC connections between OmniLink Operator Terminal and Press Control.
•Conduit for low voltage connections between OmniLink Operator Terminal and Press Control (only if options or press control circuits require low voltage as set forth in following sections).
•Conduit for 115VAC power and high speed serial bus cable from Operator Terminal to any remote enclosure containing optional module(s) ,such as Die Protection, PLS, etc., selected to be connected as the first module on the serial bus.
•Conduit runs from the enclosure containing the first optional module on the serial bus to successive enclosures containing optional module(s) to be connected on the serial bus.
•If optional Serial Feed Interface is purchased, conduit from the OmniLink II Operator Terminal enclosure to the feed control enclosure.
•If optional PLC Interface is purchased, conduit from the OmniLink II Operator Terminal enclosure to the enclosure housing the PLC.
NOTE! Do not run both 115VAC and lower voltage circuits in the same conduit from the OmniLink II Operator Terminal to the press control. If you have both 115VAC circuits and low voltage circuits, run them in separate conduits as shown in Figure 2.9. It is permissible to run 115VAC power wires and the high speed serial bus cable from the Operator Terminal to the first optional module and any successive modules used in the same conduit(s).
Section 2.3.2 Wiring the Resolver to the R/D-Brake Monitor Module
The standard resolver used with the OmniLink II Press Automation Control is Link’s 2500 Resolver. Link’s 5000 Resolver may be optionally provided. The resolver provides crankshaft angle to the OmniLink II and its cable must be wired to the 802-5 R/D-Brake Monitor Module, located on the inside back of the Operator Terminal enclosure (the module may be located elsewhere if the Operator Terminal is furnished without enclosure).
The 2500 Resolver comes with a cable with 3 pairs with a drain for each pair and a 6-pin MS connector to plug into the resolver. Run a ½” conduit from the 2500 Resolver to the knockout on the bottom left of the Operator Terminal enclosure. Pull the cable through the conduit and wire to the 802-5 R/D-Brake Monitor Module as shown in Figure 2.10.
The 5000 Resolver comes with a cable with 6 pairs with a drain for each pair and a 14-pin MS connector to plug into the resolver. Run a 3/4” conduit from the 5000 Resolver to the knockout on the bottom left of the Operator Terminal enclosure. Pull the cable through the conduit and wire as shown in Figure 2.11.
August 30, 2002 Manual Version 1.0 |
2.9 |
|
|
|
|
|
802-5 R/D-Brake Monitor Module |
|
|
|||||||||||
Analog Input/Output |
|
|
|
|
|
|
|
|
|
|
|
|
INSIDE OF |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
OPERATOR |
||||||
Board Option |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
Micr opr ocessor 2 |
|
|
|
|
|
|
|
|
TERMINAL |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Micr opr ocessor 1 |
|
|
Transforme r |
ENCLOSURE |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
Micropr oc. 1 |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
P rog. Me mor y |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
R/ D |
|
|
|
|
|
|
|
|
Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R elays |
|
|
||
|
|
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
|
|
|
|
CON8 |
|
|
|
|
|
|
|
|
|
C an Terminatio n |
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
Switch |
|
|
|
Fuse |
|
|||
1 |
2 |
3 4 |
|
5 |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
CON7 |
|
|
CON1 |
CANL |
|
|
CON2 |
|
|
CON5 |
CON4 |
|
|
|
R1 |
2 3 |
4 |
5 |
6 7 |
8 9 |
10 11 12 |
13 |
SHLD GND CANH |
1 |
2 |
3 4 5 6 |
7 |
8 |
L1 L2 GND 1 |
2 3 |
4 |
|
|
|
|
|
SYSTEM 2500 RESOLVER CABLE CONNECTION TO
CON7 OF 802-5 R/D-BRAKE MONITOR MODULE.
RUN IN 1/2” FLEXIBLE CONDUIT.
CONNECTION FOR CLOCKWISE |
|
CONNECTION FOR COUNTER-CLOCKWISE |
|||||||||||||||||||||||||||||||||||||||||||||||||
ROTATION OF CRANK OR ECCENTRIC |
|
ROTATION OF CRANK OR ECCENTRIC |
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
CON 7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CON 7 |
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R1 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R2 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R3 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R4 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 PIN AMPHENOL RESOLVER |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 PIN AMPHENOL RESOLVER |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
|
CABLE CONNECTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CABLE CONNECTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R5 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
WHITE/BLACK |
|
|
|
|
R6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHITE/BLACK |
|
|
|
R6 |
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
DRAIN |
BLACK |
|
|
|
|
R7 |
|
|
|
|
|
|
|
|
|
|
|
|
DRAIN |
BLACK |
|
|
|
R7 |
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
WHITE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHITE |
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R8 |
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
GREEN/BLACK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GREEN/BLACK |
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
DRAIN |
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DRAIN |
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
|
|
|
|
|
BLACK |
|
|
|
|
R9 |
|
|
|
|
|
|
|
|
|
|
|
|
|
GREEN |
|
|
|
R9 |
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
SINE GREEN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SINE BLACK |
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R10 |
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
RED/BLACK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RED/BLACK |
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
DRAIN |
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DRAIN |
|
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
RED |
|
|
|
|
R11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
RED |
|
|
|
R11 |
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
COS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
COS |
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
BLACK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BLACK |
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R12 |
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
DRAINS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DRAINS |
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R13 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R13 |
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 2.10. Wiring Connections from 2500 Resolver to 802-5 R/D-Brake Monitor Module
August 30, 2002 Manual Version 1.0 |
2.10 |
|
|
|
|
802-5 R/D-Brake Monitor Module |
|
INSIDE OF |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Analog Input/Output |
|
|
|
|
|
|
|
|
|
|
|
|
OPERATOR |
||||
Boa rd Option |
|
Micr opr ocessor 2 |
|
|
|
|
|
|
|
|
TERMINAL |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Tra nsforme r |
ENCLOSURE |
||
|
|
|
|
|
|
|
Micr opr ocessor 1 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
Mi cropr oc. 1 |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
P rog. Memor y |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
R/ D |
|
|
|
|
|
|
|
|
Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Relay s |
|
|
||
|
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
|
|
|
CON8 |
|
|
|
|
|
|
|
|
C an Terminatio n |
|
|
|
|||||
|
|
|
|
|
|
|
|
Switch |
|
|
|
Fus e |
|
||||
1 2 |
3 |
4 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
CON7 |
|
|
CON1 |
CANL |
|
|
CON2 |
|
|
CON5 |
CON4 |
|
|
|
R1 2 3 |
4 |
5 |
6 7 |
8 9 |
10 11 12 |
13 |
SHLD GND CANH |
1 |
2 |
3 4 5 6 |
7 |
8 |
L1 L2 GND 1 |
2 3 |
4 |
|
|
|
|
|
CON 7
SYSTEM 5000 RESOLVER CABLE CONNECTION TO CON7 OF 802-5 R/D-BRAKE MONITOR MODULE. RUN IN 3/4” FLEXIBLE CONDUIT.
CONNECTION FOR CLOCKWISE |
|||
ROTATION OF CRANK OR ECCENTRIC |
|||
14 PIN AMPHENOL RESOLVER |
|
|
|
CABLE CONNECTOR |
|
|
|
|
BROWN/BLACK |
|
|
DRAIN |
PAIR W/DRAIN |
|
|
|
CON 7 |
||
|
|
||
|
|
BROWN |
R1 |
|
|
|
|
|
|
BLACK |
R2 |
|
|
|
|
|
YELLOW/BLACK |
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
YELLOW |
R3 |
|
|
|
|
|
|
BLACK |
R4 |
|
|
|
|
|
RED/BLACK |
|
|
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLACK |
R5 |
|
|
|
|
|
|
RED |
R6 |
|
WHITE/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLACK |
R7 |
|
|
|
|
|
|
WHITE |
R8 |
|
BLUE/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLACK |
R9 |
|
SINE |
|
|
|
BLUE |
R10 |
|
|
|
||
|
GREEN/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
GREEN |
R11 |
|
|
|
|
|
COS |
BLACK |
R12 |
|
|
|
|
|
|
DRAINS |
R13 |
|
|
|
CONNECTION FOR COUNTER-CLOCKWISE |
|||
ROTATION OF CRANK OR ECCENTRIC |
|||
14 PIN AMPHENOL RESOLVER |
|
|
|
CABLE CONNECTOR |
|
|
|
|
YELLOW/BLACK |
||
DRAIN |
PAIR W/DRAIN |
|
|
|
CON 7 |
||
|
|
||
|
|
YELLOW |
R1 |
|
|
BLACK |
R2 |
|
BROWN/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BROWN |
R3 |
|
|
|
|
|
|
BLACK |
R4 |
|
|
|
|
|
RED/BLACK |
|
|
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLACK |
R5 |
|
|
|
|
|
|
RED |
R6 |
|
WHITE/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLACK |
R7 |
|
|
|
|
|
|
WHITE |
R8 |
|
BLUE/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
BLUE |
R9 |
|
SINE |
|
|
|
BLACK |
R10 |
|
|
|
||
|
GREEN/BLACK |
||
|
|
||
DRAIN |
PAIR W/DRAIN |
|
|
|
|
|
|
|
|
GREEN |
R11 |
|
COS |
|
|
|
BLACK |
R12 |
|
|
|
|
|
|
|
DRAINS |
R13 |
|
|
|
Figure 2.11. Wiring Connections from 5000 Resolver to 802-5 R/D-Brake Monitor Module
August 30, 2002 Manual Version 1.0 |
2.11 |
Section 2.3.3 Wiring 115VAC Power From Press Control to Operator Terminal
Pull red, white and green 16 gauge wires in the 115VAC conduit between the OmniLink II Operator Terminal enclosure and the press control (along with other wiring to be run in this conduit) and connect as shown in Figure 2.13. The control transformer in the press control will preferably be used to supply the 115VAC power for all the components of the OmniLink II Press Automation Control. As shown previously in Figure 2.3, all the modules for the system have a dual power connector plug so that, normally, power can be wired from module to module without having to put two (2) wires under a single terminal. The exception to this is the dual connector on the R/D-Brake Monitor Module when optional modules are used with the system. Three sets of wires must be wired to the dual terminal for Connector 5 of the R/D-Brake Monitor Module when optional modules are used: the incoming power from the press control, the outgoing power to the OmniLink II LCD Operator Terminal, and the outgoing power to the first optional module. This is shown in Figure 2.12 with two wires under each top terminal.
16 GA BLACK, WHITE, GREEN WIRES FROM PRESS CONTROL (115VAC SUPPLY FOR OMNILINK II PRESS AUTOMATION CONTROL)
L1 |
L2 |
G |
|
||
|
|
|
|
|
N |
|
|
D |
PLUGS INTO CONNECTOR HEADER FOR R/D-BRAKE MONITOR MODULE
|
115VAC CONNECTOR PLUG |
|
16 GA BLACK, WHITE, |
FOR THIS MODULE |
|
|
||
GREEN WIRES FOR |
16 GA BLACK, WHITE, |
|
OMNILINK II OPERATOR |
||
GREEN WIRES |
||
TERMINAL POWER |
||
|
||
(115VAC) |
|
115VAC TO FIRST OPTIONAL
MODULE (NOT NECESSARY
IF NO OPTIONALMODULES ARE USED)
Figure 2.12 Wiring to the R/D-Brake Monitor Module 115VAC Power Plug
The power consumption of the OmniLink II Press Automation Control base system (Operator Terminal and Resolver) is 24VA (0.2Amp at 115VAC). The maximum power required for each 16 input Die Protection and Process Monitor is 56VA (.48Amp at 115VAC), although this power is dependent on the number and power requirements of sensors used and will rarely be required in most applications. The maximum power required for each PLS/Logic Unit Module is 30VA (.26A at 115VAC). The typical OmniLink II Press Automation Control will usually require less than 1Amp at 115VAC, but as options expand the system, 2 to 3 Amps may be required for very large systems. The control transformer in the existing press control should be adequate to supply the OmniLink II system power for most applications, but for larger systems, an additional control transformer or another source of 115VAC power may be required.
August 30, 2002 Manual Version 1.0 |
2.12 |
INSIDE OF OPERATOR TERMINAL ENCLOSURE
802-5 R/D-Brake Monitor Module |
|||||
Analog Input/Output |
|
|
|
|
|
Board Option |
|
|
|
|
|
Microprocessor 2 |
|
|
|
||
|
|
|
|
|
Transformer |
Microprocessor 1 |
|
|
|||
Microproc. 1 |
|
|
|
||
Prog. Memory |
|
|
|||
R/D |
|
|
|
|
Output |
|
|
|
|
Relays |
|
IC |
|
|
|
|
|
CON8 |
|
|
Can Termination |
|
|
|
|
Switch |
|
Fuse |
|
1 2 3 4 5 |
|
|
|
||
CON7 |
CON1 |
CANL |
CON2 |
CON5 |
CON4 |
R 1 2 3 4 5 6 7 8 9 1 0 11 12 1 3 |
GND CANH |
1 2 3 4 5 6 7 8 |
L1 L2 G ND 1 2 3 4 |
||
HLDS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Contacts on R/D- Brake Monitor Module used to provide both immediate stop |
|
||||||||||
and top stop signals from OmniLink to press control. These contacts open |
CR1 CR2 |
||||||||||
immediately when an immediate stop is required and are delayed in opening |
|
as appropriate to stop the press on top when top stop is required.
|
PRESS CONTROL |
|
CON5 |
CON4 |
|
|
|
|
L1 L2 GND 1 |
2 |
3 |
4 |
|
|
|
|
||||
|
115VAC CONTROL TRANSFORMER |
|
|
|
|
|
115VAC |
SECONDARY WINDING |
|
|
|
|
|
FUSE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note! If press |
|
|
|
|
|
|
control clutch |
|
|
BLACK |
|
|
|
stop circuit is |
|
|
WHITE |
|
|
|
low voltage |
|
|
GREEN |
|
|
|
|
|
|
|
|
|
instead of 115V, |
|
|
|
RED |
|
|
|
|
|
|
RED |
|
|
|
run these wires |
|
MOTOR |
RED |
|
|
|
in conduit for |
|
RED |
|
|
|
||
|
|
|
|
low voltage |
||
|
CONTROLS |
1/2” CONDUIT CONTAINING |
||||
|
connections. |
|||||
|
|
|||||
|
|
ONLY 115VAC CONNECTION |
||||
|
|
CIRCUITS |
|
|
|
|
|
CLUTCH/BRAKE |
CONNECTOR 5 TERMINALS |
|
|
||
|
L1,L2,GND - 115VAC Power for OmniLink |
|||||
|
CONTROL |
|||||
|
|
Press Automation Control from |
||||
|
|
|
||||
|
|
|
press control transformer. |
|||
|
IMMEDIATE |
CONNECTOR 4 TERMINALS |
|
|
||
|
CLUTCH STOP |
|
|
|||
|
CIRCUIT |
1,2 --- |
Wire to Press Control Dual Valve |
|||
|
|
|||||
|
|
|
solenoid. Tells OmniLink when |
|||
|
|
|
press strokes or stops for Brake |
|||
|
|
|
Monitor & Motion Detector. |
|||
|
|
3,4--- |
Wire into immediate clutch |
|||
CLUTCH/BRAKE DUAL AIR VALVE |
|
(stroking) stop circuit. Provides |
||||
|
both immediate and top stop. |
Figure 2.13 115VAC Wiring Between Press Control and Operator Terminal
August 30, 2002 Manual Version 1.0 |
2.13 |
Section 2.3.4 Wiring the Valve Voltage Circuit
The OmniLink II Press Automation Control brake monitor and motion detector functions require a signal from the press clutch/brake control that indicates when the press strokes and stops stroking. This signal is derived from the voltage across the dual air valve solenoid (in some cases a hydraulic valve may be used) that controls stroking. Two red wires must be pulled through the 115VAC conduit between press control and the OmniLink II Operator Terminal enclosure. On the press control end the wires must be connected to opposite sides of one solenoid of the dual air valve. On the Operator Terminal end, the wires must be connected to terminals 1 and 2 of the plug for Connector 4. This is shown in Figure 2.13. Some presses have a single dual air valve that operates both clutch and brake. Others have two dual air valves, one for the clutch and one for the brake. When two dual air valves are used, always wire to a solenoid for the valve that controls the clutch.
Section 2.3.5 Wiring the OmniLink Stop Circuit Output
Two cross checked, force guided contacts operated by two separate microprocessors on the 802-5 R/D- Brake Monitor Module are used to provide both immediate stop and top stop signals to the press clutch/brake control to stop press stroking when faults are detected by the OmniLink II Press and Automation Control. These contacts, located between terminals 3 and 4 of Connector 4 are normally open, energized closed. They open to give a stop command to the press control. They should be wired into an immediate stop circuit of the press control as indicated in Figure 2.13. An immediate stop circuit is one that can immediately stop stroking of the press and will require use of the operator controls to resume stroking after the stop is removed. On many press controls, placing the contacts in series with the red color stop buttons (often referred to as “Emergency Stop Buttons”) is the desirable wiring method. This circuit used must not drop out motor controls on the press. Link engineers will assist you in determining where to wire the contacts into the press control if you need help.
If the immediate stop circuit in the press clutch/brake control is a 115VAC circuit (such as in most relay controls), pull two red wires in the 115VAC conduit between the OmniLink II Operator Terminal enclosure and the press control. Wire to terminals 3 and 4 of Connector 4 on the 802-5 R/D-Brake Monitor Module located in the back of the operator terminal enclosure and into the 115VAC stop circuit in the press control.
If the immediate stop circuit in the press clutch/brake control is a low dc voltage circuit (such as in most solid state controls), pull two blue wires in the low voltage conduit between the OmniLink II Operator Terminal enclosure and the press control. Wire to terminals 3 and 4 of Connector 4 on the 802-5 R/D-Brake Monitor Module located in the back of the operator terminal enclosure and into the low voltage stop circuit in the press control.
Figure 2.14 illustrates the appropriate stop circuit connections for Link’s SS501 press controls. Since these are solid state controls with low voltage dc circuits, 2 blue wires should be pulled through the low voltage conduit between the OmniLink II Operator Terminal enclosure and the press control for this connection.
August 30, 2002 Manual Version 1.0 |
2.14 |
R/D-Brake Monitor Module
CONN4
1 2 3 4
|
|
|
|
Jumpers inside this box if no |
|
|
|
|
|
|
light curtain is present |
|
|
|
|
|
|
1RCSA |
|
E.S. Buttons |
15 |
X X X |
36 |
Slot 26 |
76 |
20 |
6 |
X |
|
501-8A or |
|
|
||
|
REMOVE |
|
501-20 Card |
Light Curtain |
60 |
46 |
|
|
|
|
|||
|
JUMPER |
|
|
2RCSA |
|
|
|
|
|
|
|
|
|
|
|
|
LINK SS501 CONTROLSTANDARD CARDS |
|
R/D-Brake Monitor Module
CONN4 1 2 3 4
|
|
|
|
Jumpers inside this box if no |
|
|
|
|
|
|
light curtain is present |
|
|
Slot 20 |
|
|
|
1RCSA |
|
E.S. Buttons |
|
|
Slot 26 |
|
|
|
|
15 501-16 |
30 |
36 |
76 |
20 |
6 |
|
Timer |
X X |
|
501-8A or |
|
|
|
|
|
501-20 Card |
Light Curtain |
|
|
|
Card |
|
|
60 |
46 |
||
REMOVE |
|
|
|
|||
|
|
|
|
JUMPER
2RCSA
LINK SS 501 CONTROL WITH 501-16 CARD OPTION
Figure 2.14 Stop Circuit Connections from OmniLink II Automation Control to Link Press Controls
August 30, 2002 Manual Version 1.0 |
2.15 |
Section 2.3.6 Wiring the Optional Setup Mode Input
The OmniLink II Press Automation Control provides an optional setup mode input that is used to bypass certain die protection and process monitoring functions, counters, and tonnage monitor low limits during setup activities that require stroking the press. This avoids nuisance faults that have to be reset on the die protection and tonnage monitor and false part counts based on stroking during setup activities. Most presses will use the INCH mode as the setup mode. It also allows a fixed setup mode speed to be set for variable speed presses with the Analog Input/Output option. An isolated contact that closes in the INCH mode must be used as an input. If you don’t have a spare INCH mode contact on the mode selector switch, one solution is to remove an existing switch contact closed only in INCH from the circuit and add a relay with 2 normally open contacts to the control circuit. Use the contact closed in INCH mode to energize the relay coil, use one normally open contact of the relay to insert in the control circuit where the INCH contact was previously located, and use the second normally open contact as the Setup Mode input to the OmniLink. Figure 2.15 shows the wiring of this setup mode input. Run wiring in a conduit reserved for low voltage circuits between press control and OmniLink operator terminal.
|
|
|
802-5 R/D-Brake Monitor Module |
|
INSIDE OF |
||||||||
Analog Input/Output |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
OPERATOR |
||||
Board Option |
|
|
Microprocessor 2 |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
TERMINAL |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Microprocessor 1 |
|
|
Transformer |
ENCLOSURE |
||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
Microproc. 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Prog. Memory |
|
|
|
|
|
|
|
|
|
|
|
|
R/D |
|
|
|
|
|
Output |
|
|
|
|
|
|
|
|
|
|
|
|
Relays |
|
|
||
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
CON8 |
|
|
|
|
|
|
Can Termination |
|
|
|
|||
|
|
|
|
|
|
Switch |
|
|
|
Fuse |
|
||
1 2 3 4 5 |
|
|
|
|
|
|
|
|
|
|
|||
|
CON7 |
|
CON1 |
|
CON2 |
|
|
CON5 |
CON4 |
|
|
||
R1 2 3 4 5 |
6 |
7 |
8 |
9 10 11 |
12 13SHLD GNDCANH CANL |
1 |
2 3 4 5 6 |
7 |
8 |
L1 L2 GND1 |
2 3 |
4 |
|
PRESS CONTROL
OPTIONAL CUSTOMER SUPPLIED ISOLATED SELECTOR SWITCH OR RELAY CONTACT CLOSED IN SETUP MODE (SUCH AS INCH) ONLY.
|
|
|
|
|
CON2 |
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
1 |
|
|
|
|
|
7 |
|
|
BLUE |
12VDC |
|
|
|
|
|
|
SETUP MODE |
||
|
SUPPLIED BY |
|
|
|
|
|
||||
BLUE |
TERMINAL 1 |
|
|
|
|
|
INPUT |
|||
|
|
|
|
|
|
|
|
|
|
LOW VOLTAGE CONDUIT
Figure 2.15. Optional Setup Mode Input Wiring.
August 30, 2002 Manual Version 1.0 |
2.16 |
Section 2.3.7 Wiring Optional Analog Input/Output Board Circuits
Section 2.3.7.1 Wiring to Display Motor Load Current
If the optional Analog Input/Output board is specified with the OmniLink II Press Automation Control, and you wish to graphically and numerically display motor load current on the OmniLink II Operator Terminal, refer to Figure 2.16. For fixed speed presses and presses with eddy current variable speed drives, use a current transformer and an instrument transformer and wire as shown in the upper press control illustration in Figure 2.16. These transformers will normally be supplied by Link if your order indicated that motor load current display is desired.
DC Motor Drives and Adjustable Frequency AC Motor Drives will usually provide an analog motor load current output of 0-10V or 4-20ma. Wire as shown in the lower press control illustration in Figure 2.16. If a 4-20ma output is used, throw position 3 of the 4-Pole switch on the Analog Input/Output board to the closed position. If a 0-10V analog output is used, leave position 3 of the switch open.
In addition to the wiring described in this installation section, it will also be necessary to calibrate the % Motor Load current displayed on the OmniLink Operator Terminal. This calibration is described in
Section 4.2.2.5 of this manual.
Section 2.3.7.2 Wiring the Analog Speed Input and Output
The optional Analog Input/Output board also allows you to display the drive SPM for electronic variable speed drives on the OmniLink Operator Terminal, and to set the desired SPM with an analog voltage output from the Operator Terminal rather than with a potentiometer or keypad on the drive itself. Displaying drive SPM allows you to know how fast the press will stroke even when the clutch is not engaged. Without this feature, you can only display the stroking speed while the press is actually stroking.
To wire the isolated analog speed input and output, refer to figure 2.17. If you have an eddy current variable speed drive, refer to the upper box labeled press control. If one side of the tach generator is referenced to ground in the eddy current drive circuit, make sure position 1 on the switch located on the right side of the Analog Input/Output board is closed. If the tach generator drives a bridge rectifier on the eddy current drive, switch position 1 on the switch to open. The SPM OUT terminal on the Analog Input/output board should be wired to the eddy current drive SPM input (the input that sets desired speed). If desired, you may wire analog speed input only, leaving the speed setting to an existing potentiometer or keypad, but it is generally better to integrate press speed setting into the OmniLink II Operator Terminal.
To wire a DC Drive or an Adjustable Frequency AC variable speed drive, refer to the lower box labeled press control in Figure 2.17. Position 1 of the switch on the right side of the Analog Input/Output board should always be closed for DC or AC variable speed drives.
In addition to the wiring described in this installation section, it will also be necessary to calibrate the drive SPM displayed on the OmniLink Operator Terminal and the output signal that sets the speed of the variable speed drive. These calibrations are described in Sections 4.2.2.2, 4.2.2.3, and 4.2.2.4 of this manual.
August 30, 2002 Manual Version 1.0 |
2.17 |
|
4 |
OPEN |
2 3 |
|
1 |
|
|
|
|
|
|
802-5 R/D-Brake Monitor Module |
|
INSIDE OF |
|||||||
|
|
|
|
|
|
|
Analog Input/Output |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
OPERATOR |
||||
|
|
|
|
|
|
|
|
Board Option |
|
|
|
|
|||
|
|
|
|
|
|
|
|
SWITCH |
|
|
|
|
|
|
TERMINAL |
|
|
|
|
|
|
4 |
|
Microprocessor 1 |
|
Transformer |
ENCLOSURE |
||||
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|||
|
|
|
|
|
|
2 |
|
Microproc. 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Prog. Memory |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R/D |
|
|
|
|
Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Relays |
|
|
||
|
|
|
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
CON8 |
|
|
|
|
|
|
|
Can Termination |
|
|
|
|||
|
|
|
|
|
|
|
|
Switch |
|
|
Fuse |
|
|||
1 |
2 3 |
4 |
5 |
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
CON7 |
|
CON1 |
|
CON2 |
|
CON5 |
CON4 |
|
|
||
R1 |
2 3 |
4 |
5 |
6 |
7 |
8 |
9 10 11 |
12 13SHLD GNDCANH CANL |
1 |
2 3 4 5 6 7 |
8 |
L1 L2 GND1 |
2 3 |
4 |
|
|
SPM IN |
ISO GND |
SPM OUT |
%LOAD |
ISO GND |
|
|
|
|
||
|
|
CON8 |
|
||
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
Throw switch 3 |
|
|
|
|
|
to closed position |
|
|
4 |
5 |
for DC or AC Motor Control with 4-20ma Input. Otherwise leave open.
PRESS CONTROL |
|||
SIMPSON INSTUMENT |
|
||
TRANSFORMER BUL 270-5014 |
|||
3 |
1 |
CURRENT |
|
4 |
2 |
||
TRANSFORMER |
|||
|
|
X:5 RATIO |
|
|
|
1 PRIMARY TURN OR |
|
|
|
2 PRIMARY TURNS |
|
1OL |
|
MAIN MOTOR |
|
|
|
||
1OL |
|
1M |
|
|
|
||
1OL |
|
|
Current Transformer1 Ratios & Turns
for Various Size Motors
Current Transformer |
Motor HP |
Motor HP |
Ratio and Turns____ |
@220VAC |
@ 440VAC |
50:5 (2 Primary Turns) |
2 to 3 |
5 to 7.5 |
50:5 (1 Primary Turn) |
5 to 7.5 |
10 to 15 |
100:5 (1 Primary Turn) |
10 to 15 |
20 to 30 |
200:5 (1 Primary Turn) |
20 to 30 |
40 to 75 |
400:5 (1Primary Turn) |
40 to 75 |
100 to 150 |
Figure 2.16 Wiring the Analog Motor Load Current Input
FOR FIXED SPEED OR EDDY CURRENT DRIVE VARIABLE SPEED PRESSES
PRESS CONTROL
DC MOT OR DRIVE OR
AC ADJUST ABL E
FREQUENCYDRIVE
ANALOG 0-10V OR 4-20MA
MOTOR LOAD OUTPUT
COMMON (REF)
FOR DC MOTOR DRIVEOR AC ADJUST ABL E FREQUENCYDRIVE VARIABLE SPEED PRESSES
August 30, 2002 Manual Version 1.0 |
2.18 |
|
4 |
OPEN |
2 3 |
|
1 |
|
|
|
|
|
|
802-5 R/D-Brake Monitor Module |
|
INSIDE OF |
|||||||||
|
|
|
|
|
|
|
|
Analog Input/Output |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
OPERATOR |
||||
|
|
|
|
|
|
|
|
|
Board Option |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
SWITCH |
|
|
|
|
|
|
|
TERMINAL |
|
|
|
|
|
|
4 |
|
|
Microprocessor 1 |
|
|
Transformer |
ENCLOSURE |
||||
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
2 |
|
|
Microproc. 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Prog. Memory |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R/D |
|
|
|
|
|
Output |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Relays |
|
|
|||
|
|
|
|
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
|
CON8 |
|
|
|
|
|
|
|
|
Can Termination |
|
|
|
||||
|
|
|
|
|
|
|
|
|
Switch |
|
|
|
Fuse |
|
|||
1 |
2 3 |
4 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
CON7 |
|
|
CON1 |
|
CON2 |
|
|
CON5 |
CON4 |
|
|
||
R1 |
2 3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 12 13SHLD GNDCANH CANL |
1 |
2 3 4 5 6 |
7 |
8 |
L1 L2 GND1 |
2 3 |
4 |
|
Throw switch 1 to closed position if eddy current tach generator is referenced to ground on eddy current drive & for DC or AC motor
drives with analog voltage speed outputs. Switch to open position for eddy current tach generator that is input to a bridge rectifier (rarely the case) on the eddy current drive.
S PMIN |
ISOGND |
SPMOUT |
%LOAD |
ISOGND ISOLATED |
PRESS CONTROL |
|
1OL |
MAIN MOTOR |
|||||
|
||||||
|
CON8 |
INPUTS & |
1OL |
|
||
|
|
|
|
OUTPUT |
1M |
|
1 |
2 |
3 |
4 |
5 |
|
|
1OL |
|
|||||
|
|
No Connection |
|
|||
|
|
|
|
|||
|
|
|
|
SHIELDED CABLE |
|
|
|
|
|
|
IN LOW VOLTAGE |
|
EDDY CURRENT |
|
|
|
|
CONDUIT |
TACH |
COUPLING COIL |
|
|
|
|
|
|
|
|
|
|
|
SHIELD |
GENERATOR |
EDDY CURRENT DRIVE |
|
|
|
|
|
||
|
|
|
|
|
|
DRIVE SPM FEEDBACK |
|
|
|
|
|
|
DRIVE GROUND |
|
|
|
|
|
|
DRIVE SPM INPUT |
1 |
2 |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
FOR EDDY CURRENT DRIVE PRESSES |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
No Connection |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SHIELDED CABLE |
PRESS CONTROL |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
IN LOW VOLTAGE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
CONDUIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DC MOTOR DRIVE OR |
|
|
||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC ADJUSTABLE |
|
|
||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
SHIELD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FREQUENCY DRIVE |
|
|
|||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ANALOG0-10V SPM OUTPUT |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DRIVE GROUND |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DRIVE SPM INPUT |
|
|
|||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
FOR DC MOT OR DRIVE OR AC ADJUSTABLE |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
FREQUENCY DR IVE VARIABLE SPEED PRESSES |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 2.17 Wiring to Display and Set SPM Through OmniLink II Operator Terminal
August 30, 2002 Manual Version 1.0 |
2.19 |
Section 2.3.8 Optional Solid State Relay Outputs
The OmniLink II Press Automation Control provides an optional solid state relay module. It can be supplied with a combination of AC or DC solid state relays specified by the customer. If the module is provided, the relays provide the following functions:
•R1 and R2 – Module programmable limit switches 1 and 2. Simple on at an angle off at an angle PLS’s for limited applications.
•R3 – Provides an output to drive an external light that indicates die protection is bypassed.
•R4 – Provides an output to drive an external light to indicate that a downtime code has been entered when the optional LinkNet information system software is used.
Figure 2.18 shows the wiring of the relay drive inputs from R/D-Brake Monitor Module connector 2 to the solid state relay module. Wire PLS relay outputs (relay 1 and 2)as desired to sequence auxiliary equipment associated with the press. Wire relay outputs 3 and 4 to indicator lights placed in a highly visible location if you wish an external indication that die protection is bypassed or the press has a downtime condition or event.
|
|
|
|
INSIDE OF OPERATOR TERMINAL ENCLOSURE |
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
802-5 R/D-Brake Monitor Module |
|
|
|
|
|
|
|
|
|
|||||||
Analog Input/Output |
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
|
|
|||||
Boa rd Option |
Microprocess or 2 |
|
|
|
|
|
|
|
CON9 |
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
OPTIONAL 802-5 |
||||||||||
|
|
|
|
|
|
|
|
|
|
Transfor mer |
SS RELAY MODULE |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
Microprocess or 1 |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
Microproc. 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Prog. Memory |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
Outp ut |
|
R1 |
R2 |
R3 |
R4 |
|||||
|
|
|
|
|
R/D |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Relays |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
IC |
|
|
|
|
|
|
|
|
|
|
CON2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Can Terminatio n |
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
CO N8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
Switch |
|
Fuse |
|
|
|
|
|
|
|
|
||||
1 2 |
3 |
4 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
CO N7 |
|
HLDS |
CO N1 |
|
CO N2 |
CO N5 |
CO N4 |
|
SOLID STATE RELAY |
|||||||
|
|
|
|
|
|
GND CANH ANLC |
|
|
|
|
|
OUTPUTS. USE BLUE |
||||||||
R1 2 |
3 |
4 |
5 |
6 7 8 9 |
10 11 12 |
13 |
|
1 |
2 3 4 5 6 7 8 |
L 1 L2 G ND 1 |
2 3 |
4 |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
WIRE FOR DC AND |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
RED WIRE FOR AC |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
RELAY OUTPUTS. |
|
|
|
|
SOLID STATE RELAY |
12VDC |
|
||
|
|||
|
DRIVE SIGNALS |
||
|
|
|
Figure 2.18 Wiring the Optional Solid State Relay Module
August 30, 2002 Manual Version 1.0 |
2.20 |
Section 2.4 Additional Mounting and Wiring if the Operator Terminal, R/D-Brake Monitor Module, and (Optionally) Solid State Relay Module are Provided Without Enclosure for Customer Panel Mounting
The OmniLink II Press Automation Control base system package may be purchased without the operator terminal, R/D-Brake Monitor module, and (optionally) Solid State Relay Module already mounted and pre-wired inside an Operator Terminal enclosure. This allows the customer to install the basic components of the system into his own enclosure(s). When this is the case, the customer will need to perform the additional component mounting and wiring.
Section 2.4.1 Mounting the Base Components in the Customer Enclosure
Mount the OmniLink II LCD Operator Terminal in an enclosure with viewing angle considerations as shown in Figure 2.4 and with clearance to easily operate the membrane keys on the terminal. Figure 2.19 shows the mounting hole dimensions of the operator terminal. The R/D-Brake Monitor module should be mounted on the inside of the enclosure on which the operator terminal is mounted. When furnished for customer panel mount, it will be come mounted on an intermediate fixture that aids customer mounting. See mounting dimensions in Figure 2.20. Similarly, if the optional 4-channel Output Relay Module is provided, this should be mounted on the inside of the enclosure on which the operator terminal is mounted. Mounting Dimensions
Figure 2.19 OmniLink II LCD Operator Terminal Mounting Dimensions
August 30, 2002 Manual Version 1.0 |
2.21 |