Liberty Pumps SXL21=3, SXL24=3, SXH21=3, SXH24=3 Installation Manual

Single Phase Simplex
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product. A qualified service person must install and service this product according to applicable electrical and plumbing codes.
EXPLOSION OR FIRE HAZARD
Do not use this product with flamable liquids Do not install in hazardous locations as defined by National Electrical Code, ANSI/NFPA 70.
Failure to follow these precautions could result in serious injury or death. Replace product immediately if switch cable becomes damaged
or severed. Keep these instructions with warranty after installation. This product must be installed in accordance with National Electric
Code, ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.
SXL21=3, SXL24=3, SXH21=3, and SXH24=3
Manufactured by SJE-Rhombus
Installation Instructions and Operation/Troubleshooting Manual
7000 Apple Tree Avenue
Bergen, New York 14416
Phone: 1-800-543-2550
Email: liberty@libertypumps.com
www.libertypumps.com
This control panel must be installed and serviced by a licensed electrician in accordance
with the National Electric Code NFPA-70, state and local electrical codes.
All conduit running from the sump or tank to the control panel must be sealed with conduit sealant to prevent moisture or gases from entering the panel. NEMA 1 enclosures are for indoor use only, primarily to provide a degree of protection against contact with enclosed equipment. Cable connectors are not required to be liquid-tight in NEMA 1 enclosures. Do not use NEMA 1 enclosures if subjected
to rain, splashing water or hose-directed water. NEMA 4X enclosures are for indoor or outdoor use, primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water and hose-directed water. Cable connectors must be liquid-tight in NEMA 4X enclosures.
®
Warranty void if panel is modifi ed.
Call factory with servicing questions:

7203000B

1-800-543-2550
Installation Instructions
Installation of Floats
A standard single phase simplex panel is designed to operate with three fl oats. These oats operate pump stop, pump start, and high level alarm functions.
Note: Options ordered may affect the number of fl oats and their functions. Please reference the schematic provided with the control panel for proper installation.
CAUTION: If control switch cables are not wired
and mounted in the correct order, the pump system will not function properly.
WARNING: Turn off all power before installing oats in pump chamber. Failure to do so could result in serious or fatal electrical shock.
FIGURE 1: Float Locations
Float Locations Off Float - 6” above pump inlet On Float - 6” below basin Alarm Float - 3” below basin
1. Use fl oat label kit to label fl oats for specifi c operation (stop, start, alarm, etc.). See sche-
matic for fl oat options.
2. Determine your normal operating level, as il­lustrated in Figure 1.
3. Place the cord into the clamp as shown in Figure 2 or 3.
4. Locate the clamp at the desired position from
step 2, and secure the clamp to the discharge pipe as shown in Figure 2 or 3.
5. Make sure the movement of floats is not restricted.
6. Wire switch per wiring diagram.
7. Check installation. Allow system to cycle to
insure proper operation.
FIGURE 2: Clamp detail, mounting to pipe:
Note: Approximate activation level of 1.5 inches (4 cm)
above or below horizontal.
FIGURE 3
Clamp detail, mounting to Liberty Pumps “Quick Tree”:
NOTE: Do not install cord under hose clamp. Do not install switch in direct line of incoming liquid.
7203000B
- 2 -
Installation Instructions
Mounting the Control Panel
1. Determine mounting location for panel. If dis­tance exceeds the length of either the fl oat switch cables or the pump power cables, splicing will be required. For outdoor or wet installation, we recommend the use of an SJE-
®
Rhombus tight connectors to make required connections.
You must use conduit sealant to prevent moisture or gases from entering the panel.
2. Mount control panel (mounting anges are
furnished with control panel).
3. Determine conduit entrance locations on con­trol panel. Check local codes and schematic for the number of power circuits required.
NOTE: Be sure the proper power supply volt-
age, and phase are the same as the pump motor being installed. If in doubt, see the pump identifi cation plate for electrical requirements.
liquid-tight junction box with liquid-
9. Identify and label each wire before pulling through conduit into control panel and junction box. Pull pump power cables and control switch cables through connectors into junction box. Make wire splice connections at junction box.
10. Firmly tighten all fi ttings on junction box. Insure all cable connectors are liquid-tight and sealed.
11. If a junction box is not required, identify and
label cables on both fl oat and stripped ends.
12. Connect pump and fl oat wires to proper posi- tion on terminals. See schematic inside control panel for terminal layouts.
13. Connect control, alarm and pump power con­ductors to proper position on terminals. See schematic inside control panel for terminal connections.
4. Drill proper size holes for type of connectors being used.
NOTE: If using conduit, be sure that it is of ad-
equate size to pull the pump and switch cables through. You must use conduit sealant to
prevent moisture or gases from entering the panel.
5. Attach cable connectors and/or conduit con-
nectors to control panel.
FOR INSTALLATION WITHOUT
A SPLICE, GO TO STEP 11;
FOR INSTALLATION REQUIRING
A SPLICE, FOLLOW STEPS 6-10.
6. Determine location for mounting junction box according to local code requirements. Do not mount the junction box inside the sump or basin.
NOTE: It is the recommendation of the factory
to use separate pump and control/alarm power sources.
VERIFY CORRECT OPERATION OF
CONTROL PANEL AFTER
INSTALLATION IS COMPLETE.
7. Mount junction box to proper support.
8. Run conduit to junction box. Drill proper size
holes for the type of conduit used. Attach liquid­tight connectors to junction box.
7203000B
- 3 -
Operations
Simplex control panels are designed to operate in a three fl oat system as standard. When all fl oats are in the open or OFF position, the panel is inac­tive. As the liquid level changes and closes the stop fl oat, the panel remains inactive until the start oat also closes. At this point the pump will start, providing the HOA switch is in the AUTOMATIC mode and the power is ON. The pump will remain ON until both the stop and start fl oats open (return to the OFF position). If the liquid level travels be­yond both the stop and start fl oats and reaches the alarm fl oat, the alarm will be activated. The alarm horn can be silenced by moving the test/normal/ silence switch to the silence position.
Alarm System (Horn and Indicator)
When an alarm condition occurs, a red light and horn will be activated. If the test/normal/silence switch is moved to the silence position, the horn will be silenced. When the alarm condition is cleared, the alarm system is reset. The alarm system can be tested by moving the test/normal/silence switch to the test position.
Pump Run Light
The run light will be ON in either the hand or the automatic mode when the pump is called to run.
Circuit Breaker (optional)
The pump circuit has a thermal-magnetic circuit breaker which provides pump disconnect and branch circuit protection.
Dry Auxiliary Contacts (optional)
Normally open - Contacts are open under normal conditions and closed when alarm condition is present. Normally closed - Contacts are closed under normal conditions and open when alarm condition is present. Both types automatically reset once alarm condition is cleared.
NOTE: Some options ordered may not be in­cluded in this manual.
HOA Switch
A hand-off-automatic switch is provided for the pump. In the hand mode, the pump will turn on unless other safety features are employed. In the automatic mode, the pump will turn on from com­mands by the fl oat switches.
For information regarding the operations
of options not listed here or servicing
questions, please call a Liberty Pumps
customer service technician at
1-800-543-2550
7203000B
Warranty void if panel is modifi ed.
- 4 -
Loading...
+ 8 hidden pages