Before installation, read the following instructions carefully. Each Liberty pump is individually factory tested to insure proper
performance. Closely following these instructions will eliminate potential operating problems, assuring years of trouble-free service.
Risk of electric shock. Always disconnect the controller from the power source before opening the enclosure.
This controller is supplied with a grounding conductor and grounding-type attachment plug. To reduce the risk of
electric shock, be certain that it is connected only to a properly grounded, grounding-type receptacle.
DO NOT bypass grounding wires or remove ground prong from attachment plugs.
This controller requires a separate, properly fused and grounded branch circuit. Make sure the power source is
properly sized for the voltage and amperage requirements of the pumps, as noted on the nameplate.
The electrical outlet shall be within the length limitations of the power cord, and at least 4 feet above floor level to
minimize possible hazards from flood conditions. DO NOT use an extension cord.
The installation must be in accordance with the National Electric Code, Uniform Plumbing Code, International
Plumbing Code, as well as all applicable local codes and ordinances.
DO NOT use this product for flammable or corrosive liquid.
DO NOT use this product in applications where human contact with the pumped fluid is common (such as swimming
pools, fountains, etc.)
The ProVore® Duplex Control system (PDC-series) monitors the
operation of two ProVore® grinder pumps. The control system comes in
two parts, the controller with user interface and the float switches
mounted inside the basin. The P680 system includes two ProVore®
pumps and two float ball switches. The two float ball switches are
connected such that only three cords exit the cover. All three cords, two
pump power cords and control cord, must be plugged into the controller
box for the indoor models, PDC-115 and PDC-230. The outdoor units
require hard wiring, the plug ends of the pumps and switch must be cut
off and stripped appropriately. The control box monitors the liquid level
in the basin and alternates the two grinder pumps each cycle such that
both pumps receive equal wear. In the event one pump should fail, the
system will automatically switch to the other pump. On the face of the
controller are a number of LED lights and push buttons that allow the
user to monitor and control the system. Both controllers require a
dedicated circuit of the proper ampacity. The PDC(W)-115 requires
115V, 20 amp service while the PDC(W)-230 is 230V, 15 amp service.
Models: PDCW-115 and PDCW-230 require hard
wiring, the inner panel must be removed to provide
access to the terminal block(s) inside the panel. The
plug of the pumps and switch must be cut off and wires
stripped. Feed the cords, along with the incoming
power, through the water tight strain relief bushings
and wire into the terminal block mounted in the PDC
panel. A wiring schematic is provided beside the
terminal block. The panel has a secondary terminal
block for auxiliary contacts if required.
The controller normally operates on primary power
(115Vac or 230Vac), but if that power fails, an internal
9 volt battery allows the controller to monitor liquid
level and to activate the alarm if required.
On alarm backup power ( 9 volt ), the controller cannot
run the pumps. Pumps will only operate when primary
power is supplied to the control panel.
On alarm backup power, the operator can test the
alarm circuits and can change the horn enable/disable
status. Since pumps do not operate while the controller
is on alarm backup power, the manual run feature will
not be functional.
General operation – On primary Power (115Vac or 230Vac)
The PDC panel controls the operation of two ProVore® grinder pumps in a pump-down application. Two floats are
mounted to the quick tree: a primary pump control float switch and an alarm float switch. On the front panel of the
controller are indicators that show various operating conditions such as pump run status, alarm status, horn
enable/disable status, and other conditions. Operator push-button controls are available to manually run the pumps, to
manually test the alarm, and to disable or enable the alarm horn, as well as reset the system. Both pumps are individually
protected with a manual reset fuse to isolate a failed pump.
When the incoming water activates the primary pump switch, the controller will energize one of the pumps. Normally the
water level in the sump will recede as the pump operates; the pump will turn off when the primary pump switch drops to
the off position. Upon the next pumping cycle the controller will activate the next pump in sequence from the one that ran
previously, providing a pumping redundancy for the system. The controller will continue to alternate pumps on each cycle.
Alarm Operation
In the event water fills the tank faster than it can be pumped out, or if a pump fails to operate, the level can reach an alarm
point by flipping the alarm float switch. The following occurs when an alarm condition activates:
1) The pump that is (or should be) running is turned OFF and the next pump in sequence is turned ON.
2) If the Alarm float remains closed (up position) for 4 sec. the alarm indicator on the front panel of the controller will
illuminate solid
3) The auxiliary relay will activate, closing its normally open contacts and opening its normally closed contacts.
4) If the horn is enabled (i.e. its indicator is NOT flashing) the horn will sound.
Note, an alarm condition will remain active until the liquid level drops below the Pump Float switch. When that occurs, the
following things will take place:
1) The running pump will turn OFF.
2) The front panel alarm indicator will turn OFF.
3) The auxiliary relay will de-activate.
4) The horn (if on) will turn OFF.
If the alarm float remains closed (up position) for 6 hours but the primary float switch is open (down position) the alarm
light will flash and the pump is turned off. This feature prevents the pump from running indefinitely.
Primary power to the panel is OFF; the panel is on alarm backup power. Pumps will
NOT run. See Front-Panel indicators – On Alarm backup power.
*Horn disable
LED
Blinking
Horn operation is DISABLED. The horn will NOT sound in an alarm condition.
OFF
Horn operation is ENABLED. The horn WILL sound in an alarm condition
Alarm LED
OFF
There is no alarm condition
On constantly
An alarm condition is active
Blinking
The Alarm Float switch is not working properly
Pump 1 LED
OFF
The pump is not being called to run
On constantly
The pump is being called to run
Blinking
A pumping alarm condition occurred multiple times; see the section Pumping Alarm
Condition below
Pump 2 LED
OFF
The pump is not being called to run
On constantly
The pump is being called to run
Blinking
A pumping alarm condition occurred multiple times; see the section Pumping Alarm
Condition below
Both pump 1 &
Pump 2 LED
Blinking
The primary float switch is not working properly.
Horn
OFF
No alarm condition is present, and the alarm backup battery is in good condition
ON
An alarm condition is present
Chirping
The voltage of the alarm backup battery is low and the battery should be replaced
*Horn disable LED is on PDC-115 and PDC230 units only. Outdoor units, PDCW-115 and PDCW-230, have an alarm
silence switch on the exterior of the unit.
Blinking LED
Related problem
Power light
No AC power, main breaker has tripped or power outage
Pump 1
Pump failed to operate; fuse tripped, jammed impeller, unplugged, short circuit…
Pump 2
Pump failed to operate; fuse tripped, jammed impeller, unplugged, short circuit…
Pump 1 and pump 2
Primary float switch; mechanically stuck open or tangled in an open condition.
Alarm light
Alarm float switch; mechanically stuck closed or tangled in a closed condition.
The horn and LED indicators on the front panel are used to show various conditions of the controller. Each indicator is
described below.
Pumping Alarm Condition – On Primary Power
The controller monitors a “pumping alarm condition” where a pump is called to run and the liquid level continues to rise
and goes above the Alarm Float switch. If a pumping alarm condition occurs three or more of the last five times a pump is
called to run, the pump indicator will blink indicating system components should be checked. Any of the following
conditions could cause a pumping alarm condition:
1) A pump fails to operate
2) The Alarm Float switch stays (mechanically stuck) in the closed (on, or up) position.
3) There is a problem (blocked or leak) in the out-flow plumbing
4) The water in-flow rate is greater than the pump-out rate
5) The Primary Float switch stays (mechanically stuck) in the open (off, or down) position.
A blinking light indicates a component failed and service is required. To assist the service technician the controller will
indicate which component has failed.
Horn Disable indicator will turn OFF and the horn be Enabled
HORN DISABLE
indicator is OFF.
Horn Disable indicator will start blinking and the horn will be
disabled for 12 hours. After 12 hours, the indicator will turn
OFF automatically and the horn will then be Enabled.
ALARM TEST
Alarm indicator, auxiliary relay, and horn (if enabled) turn On.
These actions remain until the button is released.
MANUAL RUN
A pump is running
The pump that is running will be turned OFF; the next pump in
sequence will be turned ON. That pump will remain on as long
as the button is held. When the button is released, that pump
will turn off if the condition calling for a pump to run is no
longer present.
Neither pump is running
The next pump in sequence will be turned ON and will remain
on Until the button is released.
SYSTEM
RESET
Alarm, Pump 1 and / or
Pump 2 LED’s are
blinking
The system will reset and the Alarm, Pump 1 and / or Pump 2
LED’s will stop blinking.
FUSE
Blown fuse
Manual resettable fuse
*Horn disable LED is on PDC-115 and PDC230 units only. Outdoor units, PDCW-115 and PDCW-230, have
an alarm silence switch on the exterior of the unit.
An operator has access to front – panel push-button controls to change the horn enable status, to test the alarm circuits,
and to manually run the pumps. Each pump is protected by a manual resettable fuse; the fuses are located on the side
panel.
General operation – On Alarm Backup Power
On alarm backup power, the controller CANNOT run the pumps. Pumps will ONLY operate when primary (115Vac or
230Vac) is supplied to the control panel.
The Alarm Float switch mounted in the tank is used to monitor liquid level to possibly indicate when an alarm level might
be reached. The Pump Float switch is not used when the panel is on alarm backup power, since pumps cannot operate.
Front panel indicator show various operating conditions like alarm status, horn disable status, and other conditions.
Operator push-button controls are available to manually test the alarm circuits, and to disable the alarm horn.
When the liquid level drops below the Alarm Float, the switch will be open and there is no alarm condition; when the liquid
level rises above the ALARM Float, the switch will be CLOSED and an alarm condition will be indicated.
Alarm Operation – On Alarm Backup power
While on alarm backup power, if water fills the tank and the liquid level rises above the Alarm Float, the float switch will be
ON and an alarm condition is activated. The following occurs when an alarm condition activates:
1) The alarm indicator on the front panel of the controller will blink.
2) The auxiliary relay will activate once for one minute, closing its normally open contacts and opening its normally
closed contacts, then will de-activate.
3) If the horn is enabled (i.e. its indicator is NOT blinking) the horn will beep.
Horn Disable indicator will stop blinking and the horn will be enabled.
HORN DISABLE
indicator is OFF
Horn disabled indicator will start blinking and the horn will be disabled for
12 hours. After 12 hours, the indicator will turn off automatically and the
horn will then be enabled
ALARM TEST
Horn, alarm indicator, and auxiliary relay will turn on. They will remain in
that state until the button is released
MANUAL RUN
The button press is ignored due to lack of primary power.
*Horn disable LED is on PDC-115 and PDC230 units only. Outdoor units, PDCW-115 and PDCW-230, have an alarm
silence switch on the exterior of the unit.
Indicator
Indicator State
Description
POWER
LED
Off
Power is off to the panel and the backup alarm battery is dead.
Blinking
Primary power to the panel is Off; the panel is on alarm backup power. Pumps will
NOT run. See the section on Alarm Backup Power.
*Horn
Disable LED
Off
Horn operation is Enabled. The horn Will beep on and off in an alarm condition.
Blinking
Horn operation is Disabled.
Alarm LED
Off
There is no alarm condition.
Blinking
An alarm condition is active.
PUMP 1
LED
OFF
The Pump 1 indicator will always be OFF when on alarm backup power.
PUMP 2
LED
OFF
The Pump 2 indicator will always be OFF when on alarm backup power.
HORN
OFF
No alarm condition is present.
BEEPING
An alarm condition is present.
*Horn disable LED is on PDC-115 and PDC230 units only. Outdoor units, PDCW-115 and PDCW-230, have an alarm
silence switch on the exterior of the unit.
The operator has access to front – panel push – button controls to change the horn enable status, to test the alarm
circuits, and to manually run the pumps.
Front-Panel Indicators – On Alarm Backup Power (9 volt battery)
The horn and LED indicators on the front panel, are used to show various conditions in the controller. Each indicator is
described below.