LG PTVSMA0 Owner's Manual

Installation/Operation Manual
Human Detection Sensor Kit
P/NO : MFL69847202
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands [Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
Original instruction
4-WAY CEILING CASSETTE
www.lg.com
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
Make sure that you read the Safety Precautions section before inspection or use of the prod­uct. The Safety Precautions section provides information on ensuring safety and preventing property damages.
ENGLISH ITALIANO
ESPAÑOL FRANÇAIS
DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
2
Table of Contents
Safety Precautions ..............................3
Components of Human Detection
Sensor Kit ............................................3
Installation of Human Detection
Sensor Kit ............................................4
Functions of Human Detection
Sensor....................................................7
Using the Human Detection
Sensor Kit..............................................7
Maintenance ..........................................8
Open Source License ..........................8
Warning - Make sure that you turn off the main power before installation.
Caution - This kit can only be installed in designated products. If the kit is
not installed according to this manual, it may not be assembled properly.
3
ENGLISH
Make sure that you read Safety Precautions before using the product. The Safety Precautions section provides information on ensuring safety of users and preventing property damages. After reading this user manual, keep it at a place where it can be easily accessed.
Warning - If these instructions are not followed, serious injuries or even
death may occur.
Caution - If these instructions are not followed, injuries or property dam-
ages may occur.
안안안 안안 안안 안안Safety Precautions
Components of Human Detection Sensor Kit
!
!
!
!
Since the installation work requires specialized techniques, it must only be carried out by the
service center or the installation center approved by LG Electronics. (If installation is carried out by a person without an installation license, the person is responsible for all problems related to the installation, and, in such cases, LG Electronics shall provide no free maintenance or repair service.)
After completing the installation, be sure to show the customer that the product functions nor-
mally and has no problem.
Before installation, make sure that you read the installation manual.
Note
Human Detection
Sensor Kit
Wired Remote
Control
(separately sold)
User Manual
Model Name
PREMTB100
Installation/Operation Manual
Human Detection Sensor Kit
Make sure that you read the Safety Precautions section before inspection or use of the prod­uct. The Safety Precautions section provides information on ensuring safety and preventing property damages.
4-WAY CEILING CASSETTE
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands [Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
P/NO : MFL69847202
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
www.lg.com
12 m
6 m
4
Front of the Front Panel
Installation of Human Detection Sensor Kit
Make sure that you install the Human Detection Sensor kit before installing the front panel.
- If the front panel has already been installed, you cannot install the Human Detection Sensor kit. In such a case, separate the front panel, install the kit, and re-install the front panel.
- You can operate the kit using remote controls described in the Components of Human Detec­tion Sensor Kit section (page 3).
- A protective film is attached on the exterior of the Human Detection Sensor kit. Make sure that you remove the protective film after installation is completed.
Caution
!
1. Check the mounting direction of the Human Detection Sensor kit. (Install it on the right corner of the front panel when seen from the display PCB.) There is no available installation location other than this, and installing the product in another location may cause product malfunction or damage.
1-1. Determine the installation direction of the sensor kit based on the conditions of the site
where the air conditioner is to be installed.
- When the horizontal width is greater: General installation
- When the vertical width is greater: 90-degree rotated installation
(Installation Examples)
The horizontal width is greater than the
vertical width.
The vertical width is greater
than the horizontal width.
Front of the Front Panel
12 m
6 m
Front of the Front Panel
90-degree
Rotated Installation
General
Installation
Installation Space
Installation Space
Display PCB Human Detection
Sensor Kit
5
ENGLISH
When installing the sensor kit, make sure that the insulating material is not torn or fall off while de­taching or attaching the motor cover. (If the finish of the insulating material is defective, air may leak out.)
Caution
!
1-3. After installing the Human Detection Sensor kit, set the installation direction of the kit
(general, 90-degree rotated). Refer to the remote control manual for details on how to set the installation direction.
2. Attach the kit to the product.
2-1. Detach the corner cover at the installation location of the kit. 2-2. To mount the kit, insert the connecting wire into the space that appears when the
corner cover is detached.
2-3. Detach the motor cover by loosening two screws.
2-4. Organize the connecting wire as shown in the figure, and attach the motor cover.
(Secure a margin of approximately 6 - 10 cm for the connecting wire to make it easy to detach the Human Detection Sensor kit.)
2-5. Align the connecting wire to the wire guide and fix it with the hooks.
Figure. 2-1 Figure. 2-3Figure. 2-2
Figure. 2-4
Remove ScrewsMotor CoverDetach Corner Cover
Display PCB Connecting Wire
Insulating
Material
Attachment
Parts
6~10cm
Figure. 2-5
Figure. 90-degree Rotated Installation
Remove Screws
Rotate PCB
Assembly
Tighten Screws
Fix with Hooks
Fix with Hooks
1-2. The default factory setting is for general installation, and you can rotate the PCB 90 de­grees depending on the site conditions.
6
3. Use the front panel fixing bolts to fasten the panel and the main body together.
- Refer to the user manual for the 4-Way front panel.
- After fixing the panel, remove the protective film from the exterior of the Human De­tection Sensor kit.
4. Open the control box cover of the main body.
5. Refer to the wiring diagram attached to the control box to connect all the connecting wires on the panel to the connector inside PCB.
5-1. Connect the connecting wires of the kit to the yel-
low connector (CN_BLDC2) on the PCB as shown in the figure.
6. Fasten the control box cover and attach the air intake grille.
7. After completing the installation, check for normal operation by performing the following steps:
7-1. Set the installation direction of the sensor kit in the Installer Settings of the remote
control.
7-2. After starting the operation, select 'Body Sensing Operation' in the 'Function Set-
tings'. 7-3. Set 'Body Sensing Wind Direction' to 'Indirect Wind'. 7-4. Check if the vane in the direction of the movement operates properly.
Figure. 5-1
Figure. 2-7
Fix with Hooks
2-7. Place the connecting wire inside the guide and fix it with the hooks, then attach the
motor cover.
2-6. Detach the motor cover by loosening two screws.
Figure. 2-6
Remove Screws
Display PCB
Motor Cover
Insulating Material Attachment Parts
7
ENGLISH
• The Human Detection Sensor detects movement within the detection range.
• Detection Ranges Installation height 2.7 m: 12 m X 6 m Installation height 3.2 m: 15 m X 8 m
Power Saving Operation Using Human Detection Sensor
• On/Off Power Saving: When no movement is detected, the operation is turned off to
save power.
• Temperature Power Saving: When no movement is detected, the power saving opera-
tion is performed to reach the desired temperature.
h The time for detecting the absence of a person can be set to 5, 10, 15, 30, 60 or 90
minuts.
h The effect of the Power Saving operation may differ depending on the model, capacity,
or surrounding environment.
Human Detection Wind Direction
• Direct Wind: When a movement is detected, the wind is automatically controlled to
reach the location of the movement.
• Indirect Wind: When a movement is detected, the wind is automatically controlled not to
reach the location of the movement.
Precautions
• Do not conceal the sensor or touch it with a hand.
• When the sensor has dirt or other foreign substance, wipe it with a soft cloth. (There is a
risk of product malfunction if water enters the product. Do not immerse the product under water. Make sure that you wipe it with a dry cloth.)
• The Human Detection Sensor detects the presence of human body based on move-
ment.
• When there is no movement, the sensor regards that there is no human body around.
• When an object moves away from the sensor, the sensor detects a big movement and
regards it as a human movement.
• When there are many moving objects, the wind direction adjustment function may be
delayed.
• Setting the detection result transmission period (5 seconds, 30 seconds (Default), 1
minute, 3 minutes) to 30 seconds (Default) or longer is recommended. When setting it to 5 seconds, the probability of false detection can be increased as it judges by motion.
• A change in the indoor lighting condition or the sunlight shown through a window can be
sensed as a body movement.
• If you stop the operation using a remote control while On/Off Power Saving is on, the
product maintains the stopped state even when a movement is detected.
• If a movement is detected while On/Off Power Saving is on, the air conditioner may not
be turned off.
• The turning-off of the air conditioner may be delayed depending on the indoor conditions
while On/Off Power Saving is on.
Functions of Human Detection Sensor
Using the Human Detection Sensor Kit
Loading...