INSTALLATION/
OWNER'S MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
PDI STANDARD
PPWRDB000
www.lg.com
<![endif]>ЯЗЫК РУССКИЙ TÜRKÇE PORTUGUÊS DEUTSCH FRANÇAIS ESPAÑOL ITALIANO ENGLISH
P/NO : MFL67982907
<![endif]>ENGLISH
2 |
TIPS FOR SAVING ENERGY |
|
|
|
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
•Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
•Block sunlight with blinds or curtains while you are operating the air conditioner.
•Keep doors or windows closed tightly while you are operating the air conditioner.
•Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
•Speed up the fan to cool or warm indoor air quickly, in a short period of time.
•Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
•Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS |
3 |
|
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
! WARNING
It can result in serious injury or death when the directions are ignored
! CAUTION
It can result in minor injury or product damage when the directions are ignored
! WARNING
•Installation or repairs made by unqualified persons can result in hazards to you and others.
•Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
•The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
•Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
! WARNING
Installation
•Be sure to request to the service center or installation specialty store when installing products. It will cause fire or electric shock or explosion or injury.
•Request to the service center or installation specialty store when reinstalling the installed product. It will cause fire or electric shock or explosion or injury.
•Do not disassemble, fix, and modify products randomly. It will cause fire or electric shock.
In-use
•Do not place flammable stuffs close to the product. It will cause fire.
•Do not allow water to run into the product. It will cause electric shock or breakdown.
•Do not give the shock to the product.
It will cause breakdown when giving the shock to the product.
<![endif]>ENGLISH
|
4 |
IMPORTANT SAFETY INSTRUCTIONS |
|
<![if ! IE]> <![endif]>ENGLISH |
|
|
|
|
becomes wet. It will cause fire or electric shock. |
||
|
|
• Request to the service center or installation specialty store when the product |
• Do not give the shock using sharp and pointed objects. It will cause breakdown by damaging parts.
! CAUTION
In-use
•Do not clean using the powerful detergent like solvent but use soft cloths. It will cause fire or product deformation.
•Do not press the screen using powerful pressure or select two buttons. It will cause product breakdown or malfunction.
•Do not touch or pull the lead wire with wet hands. It will cause product breakdown or electric shock.
Disposal of your old appliance
1When this crossed-out wheeled bin symbol is attached to a product it means the product is covered by the European Directive 2002/96/EC.
2All electrical and electronic products should be disposed of separately from the municipal waste stream via designated collection facilities appointed by the government or the local authorities.
3The correct disposal of your old appliance will help prevent potential negative consequences for the environment and human health.
4For more detailed information about disposal of your old appliance, please contact your city office, waste disposal service or the shop where you purchased the product.
According to IEC 60335-1
This appliance is not intended for use by person (including children) with reduced physical, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
According to EN 60335-1
This appliance can be used by children aged from 8 years and above and person with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
|
|
|
|
TABLE OF CONTENTS |
5 |
|
TABLE OF CONTENTS |
|
|
|
|
||
|
|
|
|
|
||
2 |
TIPS FOR SAVING EN- |
17 |
SETTING AND USING |
|
||
|
ERGY |
|
|
METHOD |
|
|
|
|
|
|
|
|
|
3 |
IMPORTANT SAFETY IN- |
17 |
Glossary |
|
||
18 |
Setting |
|
||||
|
STRUCTIONS |
|
||||
|
20 |
Setting up detailed functions (EHP |
|
|||
|
|
|
||||
6 |
|
|
||||
NAME OF EACH PART |
|
|
products) |
|
||
26 |
Setting detailed functions (GHP prod- |
|
||||
|
|
|
||||
7 |
COMPONENTS |
|
||||
|
|
ucts) |
|
|||
|
|
32 |
How to Use Power Indicator (EHP |
|
||
8 |
INSTALLATION METHOD |
|
||||
|
|
products) |
|
|||
|
|
35 |
How to Use the Power Indicator (GHP |
|
||
8 |
Diagram of overall product configura- |
|
||||
|
|
products) |
|
|||
|
tion |
|
|
|
||
|
|
|
|
|
|
|
12 |
How to wire the product (when EHP |
39 |
Operating condition display |
|
||
|
|
|
|
|
product is connected)
13How to wire the product (when GHP product is connected)
14Wiring
<![endif]>ENGLISH
<![endif]>ENGLISH
6 |
NAME OF EACH PART |
|
|
|
NAME OF EACH PART
POWER |
WHM |
|
|
Front cover
ODU WHM CHECK
LED display |
|
|
POWER |
WHM |
|
Menu button |
|
|
LCD display |
MENU |
|
SELECT |
||
|
||
|
PPWRDB000 |
|
SELECT button |
|
|
|
ODU WHM CHECK |
|
LED display |
|
|
Navigation button |
|
Power supply
Front cover
LED display Displays current status of power indicator
Menu button Use for checking initial setting and electric power
LCD display Displays setting information and power usage
SELECT button Use for initial setting
Navigation button Use for checking initial setting and electric power
Power supply Supply power for power indicator
COMPONENTS 7
COMPONENTS
POWER |
WHM |
|
<![if ! IE]> <![endif]>mm |
MENU |
<![if ! IE]> <![endif]>mm |
<![if ! IE]> <![endif]>155 |
SELECT |
<![if ! IE]> <![endif]>155 |
|
PPWRDB000 |
|
|
ODU WHM CHECK |
|
|
270 mm |
120 mm |
|
Power distribution indicator |
Power supply |
<![endif]>ENGLISH
POWER |
WHM |
|
|
ODU WHM CHECK
Front cover Manual
1 core |
Screws |
<![endif]>ENGLISH
8 INSTALLATION METHOD
INSTALLATION METHOD
Diagram of overall product configuration
When interlocked to pulse type wattmeter
•When interlocked to EHP product
- Independent Operation of Power Indicator (interlocked to EHP products)
|
|
Pulse signal |
|
|
|
Wattmeter |
|
|
|
|
|
Pulse signal |
Power In 3 |
Wattmeter |
|
|
|
|
phase 4 wire |
|
|
|
|
|
|
||
|
|
|
|
|
|
380-415 V 3N~, |
Power In |
|
|
|
|
|
50/60 Hz |
single phase |
|
|
|
|
|
|
220-240 V~, |
|
|
|
|
|
|
50/60 Hz |
|
|
|
RS-485 |
|
|
<![if ! IE]> <![endif]>Power cable of indoorunit |
|
|
|
|
|
|
|
(00) |
(01) |
(02) |
(03) |
|
|
|
|
|
|
Pulse signal |
|
Wattmeter |
|
|
|
|
Pulse signal |
|
|
|
|
|
|
|
Power In 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
phase 4 wire |
|
|
|
|
|
|
380-415 V 3N~, |
Power In |
|
|
|
|
|
50/60 Hz |
single phase |
|
|
|
|
|
|
220-240 V~, |
|
|
|
|
|
|
50/60 Hz |
|
|
|
RS-485 |
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>of indoor unit |
|
|
|
|
|
|
<![if ! IE]> <![endif]>cablePower |
(00) |
(01) |
(02) |
(03) |
|
|
|
|
|
(10) (11) (12) (13)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit Pulse signal wire
Refrigerant pipe
INSTALLATION METHOD 9
• Interlocked Operation with Central Controller (interlocked to EHP product)
|
|
|
|
Pulse signal |
Wattmeter |
|
|
|
|
Pulse signal |
|
|
|
|
|
Power In 3 |
|
|
|
|
|
|
phase 4 wire |
|
|
|
|
|
380-415 V 3N~, |
Power In |
|
|
|
|
50/60 Hz |
single phase |
|
|
|
|
|
220-240 V~, |
|
|
|
|
|
50/60 Hz |
|
|
|
RS-485 |
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>cable of indoor unit |
(00) |
(01) |
(02) |
(03) |
|
<![if ! IE]> <![endif]>Power |
|
|
|
|
|
<![endif]>ENGLISH
(10) |
(11) |
(12) |
(13) |
RS-485 |
(LGAP) |
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit Pulse signal wire
Refrigerant pipe
!CAUTION
•Depending on the electric power, use the wattmeter for remote reading by sending the pulse signal.
•Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
•The wattmeter pulse must be able to sink at least 3 mA or more of current in the power indicator.
•Use the wattmeter of 1 W/Pulse, 2 W/Pulse, 4 W/Pulse, 6 W/Pulse, 8 W/Pulse, 10 W/Pulse, 100 W/Pulse, PT/CT (1 ~ 50 000).
•When setting the wattmeter, set it to Slave Mode.
•Maximum of 2 wattmeters can be installed.
•The distance between power indicator and wattmeter should be shorter than 10 m in normal circumstance.
•When electrical or mechanical noise is expected, more shorter wiring is needed.
•For watt-hour meter setting, inquire to the corresponding vendor
ηEHP (Electric Heat Pump): It is an electric air conditioner to drive the compressor by electric power.
<![endif]>ENGLISH
10 INSTALLATION METHOD
•When interlocked to GHP product
- Independent Operation of Power Indicator (interlocked to GHP product)
|
Pulse signal(Power) |
|
Pulse signal(Gas) |
|
Wattmeter |
|
Power In 3 |
|
phase 4 wire |
SELECT |
380-415 V 3N~, |
MENU |
|
|
50/60 Hz |
|
Gas meter |
|
RS-485 |
(00) (01) (02) (03)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
Gas pipe
Pulse signal wire(Gas)
!CAUTION
•Use the wattmeter for remote reading to send pulse signal depending on wattage.
•Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
•The wattmeter pulse must be able to sink at least 3 mA or more of current in the power indicator.
•Use the wattmeter of 1 W/Pulse, 2 W/Pulse, 4 W/Pulse, 6 W/Pulse, 8 W/Pulse, 10 W/Pulse, 100 W/Pulse, PT/CT(1 ~ 50 000).
•Use the gas meter for remote reading to send pulse signal depending on gas consumption.
•Use the gas meter with the pulse width of 50 ms or more.
•Use the gas meter containing the max. gas pressure of 0.2 m3/h ~ 10 m3/h.
•Gas meter pulse must be able to sink at least 3 mA of current or more in the power indicator.
•Use the gas meters for 1 ℓ/Pulse, 2 ℓ/Pulse, 4 ℓ /Pulse, 6 ℓ/Pulse, 8 ℓ/Pulse, 10 ℓ/Pulse, 100 ℓ/Pulse, VT&Pr(1 ~ 50 000).
•Set to Master Mode when setting the wattmeter or gas meter.
•Wattmeter or gas meter can be installed up to 1.
•Connection cable for the power indicator and wattmeter (gas meter) must not exceed 10 m in normal circumstance.
•Reduce the length of connection cable if there is any electrical or mechanical noise on the site.
•For watt-hour meter and gas meter setting, inquire to the corresponding vendor
ηGHP (Gas engine Heat Pump): It is a gas air-conditioner to drive the compressor with LNG or LPG as a heat source and the gas engine electric power.
|
|
|
|
|
|
|
|
INSTALLATION METHOD |
11 |
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- When linked with the GHP product, the central controller is linked only possible model of |
<![if ! IE]> <![endif]>ENGLISH |
||||||||||||||||||||||||
|
|||||||||||||||||||||||||
ACS IV series or later. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pulse signal(Power) |
|
|||||||||||||||||||||
|
|
|
|
||||||||||||||||||||||
|
|
|
Pulse signal(Gas) |
|
|||||||||||||||||||||
|
|
|
|
|
|
Wattmeter |
|
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power In 3 |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
phase 4 wire |
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
380-415 V 3N~, |
|
||||||||||||
|
MENU |
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50/60 Hz |
|
||||||||
|
SELECT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas meter |
|
||||||
|
|
|
RS-485 |
|
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS-485 |
(00) |
(01) |
(02) |
(LGAP) |
(03) |
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
Gas pipe
Pulse signal wire(Gas)
!CAUTION
•Use the wattmeter for remote reading to send pulse signal depending on wattage.
•Use the wattmeter with the pulse width of 50 ms ~ 400 ms.
•The wattmeter pulse must be able to sink at least 3 mA or more of current in the power indicator.
•Use the wattmeter for 1 W/Pulse, 2 W/Pulse, 4 W/Pulse, 6 W/Pulse, 8 W/Pulse, 10 W/Pulse, 100 W/Pulse, PT/CT(1 ~ 50 000).
•Use the gas meter for remote reading to send pulse signal depending on gas consumption.
•Use the gas meter with the pulse width of 50 ms or more.
•Use the gas meter containing the max. gas pressure of 0.2 m3/h ~ 10 m3/h.
•Gas meter pulse must be able to sink at least 3 mA of current or more in the power indicator.
•Use the gas meters for 1 ℓ/Pulse, 2 ℓ/Pulse, 4 ℓ/Pulse, 6 ℓ/Pulse, 8 ℓ/Pulse, 10 ℓ/Pulse, 100 ℓ/Pulse, VT&Pr(1 ~ 50 000).
•Set to Slave Mode when setting the wattmeter or gas meter.
•Wattmeter or gas meter can be installed up to 1.
•Connection cable for the power indicator and wattmeter (gas meter) must not exceed 10 m in normal circumstance.
•Reduce the length of connection cable if there is any electrical or mechanical noise on the site.
•For watt-hour meter and gas meter setting, inquire to the corresponding vendor
<![endif]>ENGLISH
12 INSTALLATION METHOD
How to wire the product (when EHP product is connected)
Wiring Power Indicator
Connection of pulse type wattmeter (Port 1~2)
POWER |
WHM |
|
|
|
MENU |
|
PPWRDB000 |
SELECT |
|
|
|
|
ODU |
WHM CHECK |
24 V~ power is supplied |
Connect to central control (outdoor unit) |
for power supply device |
RS-485 communication line |
Wiring Power Supply
220-240 V~ power cable connection terminal
Grounding cable connection terminal
Fixing clamp
L N
220-240 V~
<![endif]>V~ 24
24 V~ power cable connection terminal
! CAUTION
• Power must be turned on after the product is wired completely.
INSTALLATION METHOD 13
How to wire the product (when GHP product is connected)
Wiring Power Indicator
Connected to pulse-type wattmeter (Port 1)
Connected to pulse-type gas meter (Port 2)
POWER |
WHM |
|
|
|
MENU |
|
PPWRDB000 |
SELECT |
|
|
|
|
ODU |
WHM CHECK |
Connect to central control (outdoor unit) 24 V~ power is supplied RS-485 communication line
for power supply device
Wiring Power Supply
<![endif]>ENGLISH
220-240 V~ power cable connection terminal |
|
Grounding cable connection terminal |
L N |
220-240 V~ |
<![endif]>V~ 24
Fixing clamp
24 V~ power cable connection terminal
!CAUTION
•Power supply must be applied after wiring the product is completed, if applicable.