LG PDRYCB500 User guide

INSTALLATION MANUAL
Modbus Gateway For Indoor Unit Original instruction
LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
Manufacturer: LG Electronics Inc. Changwon 2nd factory, 84, Wanam-ro,
Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
AIR
РУССКИЙ ЯЗЫК
PORTUGUÊS
ENGLISH
MALTI
SLOVENČINA
ITALIANO ESPAÑOL
MAGYAR
中文
БЪЛГАРСКИ
SLOVENŠČINA
LATVIEŠU VALODA
FRANÇAIS
SRPSKI
LIETUVIŲ KALBA
HRVATSKI
DEUTSCH
ΕΛΛΗΝΙΚΆ
SVENSKA
GAEILGE
МАКЕДОНСКИ
ČEŠTINA
NORSK
CONDITIONER
www.lg.com
MFL70585304
Rev.01_022119
Copyright © 2015 - 2019 LG Electronics Inc. All Rights Reserved.
SUOMI
SHQIP
ÍSLENSKA
DANSK
BOSANSKI
EESTI KEEL
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
TABLE OF CONTENTS
Important Safety Instructions
Important Safety Instructions
ENGLISH
3 IMPORTANT SAFETY INSTRUCTIONS
8 SPECIFICATION
9 NAME OF EACH PART
10 INSTALLATION METHOD
10 Installation inside of the indoor unit
11 Installation
13 SETTING METHOD
13 1. Connecting Drycontact with Indoor unit PCBA and Modbus Controller
13 2. Setting Address
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product.
!
WARNING
It can result in serious injury or death when the directions are ignored.
!
CAUTION
It can result in minor injury or product damage when the directions are ignored.
!
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Installation manual 32 Modbus Gateway For Indoor Unit
Safety Precautions
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Be sure to request to the service center or installation specialty store when installing products. It will cause fire or electric shock or explosion or injury.
• Request to the service center or installation specialty store when reinstalling the installed product. It will cause fire or electric shock or explosion or injury.
• Do not disassemble, fix, and modify products randomly. It will cause fire or electric shock.
• Be sure to turn off power before installation. It will cause electric shock.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Always perform grounding. Otherwise, it may cause electrical shock.
• You need to use a safely insulated power supply which follows IEC61558-2-6 anc NEC Class2. If you do not follow, It may cause
4 Modbus Gateway For Indoor Unit
Safety Precautions
fire, electric shock, explosion or injury.
• Securely attach the electrical part cover to Module. If the electric part cover of Module is not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals. Inadequate connection and fastening may generate heat and cause a fire.
In-use
• Do not place flammable stuffs close to the product. It will cause fire.
• Do not allow water to run into the product. It will cause electric shock or breakdown.
• Do not give the shock to the product. It will cause breakdown when giving the shock to the product.
• Request to the service center or installation specialty store when the product becomes wet. It will cause fire or electric shock.
• Do not give the shock using sharp and pointed objects. It will cause breakdown by damaging parts.
• Do not touch the board when the power is connected. It can cause a fire, electric
Installation manual 5
ENGLISH
shock, explosion, injury and problem to the product.
• Unplug the unit if strange sounds, smell, or smoke comes from it. Otherwise, it may cause electrical shock or a fire.
• The appliance must only be supplied at safety extra low voltage corresponding to the marking on the appliance.
• This appliance is not intended to be accessible to the general public.
!
CAUTION
In-use
• Do not clean using the powerful detergent like solvent but use soft cloths. It will cause fire or product deformation.
• Do not press the screen using powerful pressure or select two buttons. It will cause product breakdown or malfunction.
• Do not touch or pull the lead wire with wet hands. It will cause product breakdown or electric shock.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless
SpecificationSafety Precautions
they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
ENGLISH
6 Modbus Gateway For Indoor Unit
Installation manual 7
Specification
Name of each part
Specification
1) Modbus configuration
- Network : 2 wire RS485
- Mode : Modbus RTU slave
- Baud : 9600
- Parity : None
- Stop bits : 1
- Register Base : 0
2) Data registers
Function code Register Address Name Range Notes
01(read)/05(write) 00001 0x0000 Operation 0~1
04(read) 30001 0x0000 Pipe in temprature -300~1120 Degrees (℃) × 10 04(read) 30002 0x0001 Pipe out temperature -300~1120 Degrees (℃) × 10 04(read) 30003 0x0002 Indoor temperature 100~400 Degrees (℃) × 10
04(read) 30100 0x0063 Error code 0~999
03(read)/06(write) 40001 0x0000 Set run mode (aircon) 0~4
03(read)/06(write) 40002 0x0001 Set temperature 180~300 Degrees (℃) × 10
03(read)/06(write) 40003 0x0002
03(read)/06(write) 40004 0x0003
Set run mode (ventilation)
Set sub operation (ventilation)
03(read)/06(write) 40015 0x000E Set fan speed 1~3
Above function may not work in some products.
0~2
0~2
0: Stop 1: Run
0: No error 1~999: Error code
0: Cool 2: Fan 3: Auto 4: Heat
0: Heat exchange 1: Auto 2: Bypass
0: Off 1: Fast 2: Energy saving
1: Low 2: Middle 3: High 4: Auto 7: Super High
Name of each part
Front Case Rear Case
ISO View
Side Side
Cable(1 EA)
(For Connecting with indoor unit)
Modbus Gateway For Indoor Unit
1. CN-OUT :
2. BUS-A :
3. BUS-B :
4. SW1 :
5. SWDIP :
6. LED1 :
7. LED(01~03)G :
8. CN-JIG :
Indoor Unit Connector
RS-485(+) Terminal
RS-485(-) Terminal
Reset Switch
Setting Address Switch(Refer Page 11)
RS-485 Status LED
Communication Status LED
Connector for expanding the address range
1
Installation Manual
(For expanding address range)
ON
12
765
34
4
8
PCB
Connector (1 EA)
* Others :
Screw 4 EA(For installation)
ENGLISH
3
2
8 Modbus Gateway For Indoor Unit
Installation manual 9
Installation Method
Installation Method
Installation Method
Installation inside of the indoor unit
1) Loosen and remove two screws that secure the product.
2) Loosen two screws that secure the PCB to separate rear of the case from the PCB.
3) Connect the connection wires properly according to the connection method. (Refer to the instruction and set-up description)
4) Set the switch according to the setting method. (Refer to the instruction and set-up description)
5) Secure PCB on adequate space inside of the indoor unit.
*Note
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
Installation
1) Loosen and remove two screws that secure the product.
2) Position the rear case to the direction towards to the connector for convenient cable arrangement.
3) Secure the rear case on the installation place using the supplied fixing screws.
4) Remove knock out shapes on the rear case according to the connector’s size and direction.
ENGLISH
10 Modbus Gateway For Indoor Unit
Installation manual 11
Installation Method
Indoor unit PCBA
CN_CC
12
ON
34
Modbus
Controller
12
ON
34 12
ON
34
12
ON
34 12
ON
34
12
ON
34 12
ON
34
*Status of switch
- Not attached(default): 1~8
- Attached(expanding address range): 9~16
* /Number: Address when connector is attached
12
ON
34 12
ON
34
Address 1/9 Address 2/10
Address 3/11 Address 4/12
Address 5/13 Address 6/14
Address 7/15 Address 8/16
ON OFF
12
ON
34
5) Connect the connection wires properly according to the connection method. (Refer to the instruction and set-up description)
6) Set the switch according to the setting method. (Refer to the instruction and set-up description)
7) Tighten the fixing screws on the top and bottom of the case.
*Note
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
12 Modbus Gateway For Indoor Unit
Setting method
Setting method
After change any Dry contact setting, then you must press RESET switch to reflect the setting.
1. Connecting Drycontact with Indoor unit PCBA and Modbus Controller
2. Setting Address
h In case, connect a Modbus controller with several product, Address have to be set different from
others.
h If the connector is attached to ‘CN-JIG’, the address range is expanded. (Please attach the
connector before turning on the product.)
After change any Dry contact setting, then you must press RESET switch to reflect the setting.
Installation manual 13
ENGLISH
Setting method
※ If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
※ Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
※ Qualified service technician is only possible to access to product.
Minimum cross-sectional area of conductors
Rated current of appliance
A
>0.2 and ≤3
>3 and ≤6
>6 and ≤10 >10 and ≤16 >16 and ≤25 >25 and ≤32 >32 and ≤40 >40 and ≤63
≤0.2
Nominal cross-sectional area
2
mm
Tinsel cord
a
0.5
0.75
1.0 (0.75)
1.5 (1.0)
2.5 4 6
10
a
b
b
ENGLISH
The above information applies only to India.
14 Modbus Gateway For Indoor Unit Installation manual 15