LG LS091HSV3, LSN091HSV3, LSU091HSV3, LSN121HSV3, LSU121HSV3 Engineering Manual

...
SINGLE ZONE HIGH EFFCIENCY, STANDARD AND
EXTENDED PIPE WALL MOUNT ENGINEERING MANUAL
Single Zone Wall Mount Systems
3/4 to 2-3/4 Tons
This document, as well as all reports, illustrations, data, information, and
other materials is the property of LG Electronics U.S.A., Inc.
EM-SZ-HighEfficiencyWallmount-HSV3-HV3-HLV-9-16
For continual product development, LG Electronics U.S.A., Inc., reserves the right to change specifications without notice.
©LG Electronics U.S.A., Inc.
About LG Electronics, Inc.
LG Electronics, Inc. is a global leader and technology innovator in consumer electronics, mobile communications, and home appliances, employing more than 213,000 people in more than 60 countries worldwide. With $136 billion (USD) revenue in 2011, LG Electronics, Inc. is ranked among Fortune 500’s list of largest companies. LG Electronics, Inc. comprises five business units— Home Entertainment, Mobile Communications, Air Conditioning, Business Solutions, and Home Appliance. LG is one of the world’s leading producers of flat panel televisions, audio and video products, mobile handsets, air conditioners, and washing machines. LG’s commercial air conditioning business unit was established in 1968 and has built its lineup of residential and commercial products to include VRF, Flex-Multi, duct-free split systems, packaged terminal air conditioners (PTACs), and room air conditioners. In 2011, the air conditioning and energy solutions business unit grew to include LED lighting and solar products. For more information, visit www.lg.com.
Duct Free Split (DFS) Technology
LG HVAC systems offer a range of solutions that are cost efficient, quiet and attractive. Duct-Free Split (DFS) systems are “split” into indoor and outdoor units, and provide a smart alternative to both central HVAC and window-mounted air conditioners. These inverter
heat pump systems are available in a variety of configurations to suit different cooling and heating situations. Installation by a qualified HVAC contractor is safe and easy – little to no duct work or sheet metal is required.
Inverter Systems
LG Single Zone Inverter Wall Mount air-source systems offer the opportunity to minimize ductwork in the same configuration. The system offers zoning without the need for zone damper systems. The LG Single Zone Inverter Wall Mount system’s advanced controls provide exceptional building dehumidification and temperature control, and can rapidly adapt system operating parameters to the ever changing building load. The LG Single Zone Inverter Wall Mount system is easy to design, install, and maintain. The modular design allows occupants to control their environmental condition, providing individualized control of the set-point temperature and allowing oc-
cupants to condition only the occupied zones.
Quality Commitment
LG is committed to the success of DFS projects. We provide industry leading technical support during installation and commissioning. LG offers a variety of classes designed for installers and servicers to ensure that every DFS system installation is completed successfully. Classes are conducted at LG’s training centers and in field locations at various times throughout the year and upon special request.
Introduction
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG” is a registered tra demark of LG Corp.
©
3
TABLE OF CONTENTS
Architectural Appeal.............................................................................. 6
Product Features and Benets ............................................................ 8
Unit Nomenclature ................................................................................. 9
General Data ................................................................................... 10-17
Electrical Data ...................................................................................... 18
Outdoor Unit Dimensions .............................................................. 19-21
Indoor Unit Dimensions ................................................................. 22-25
Outdoor Unit Acoustic Data................................................................ 26
Indoor Unit Acoustic Data..............................................................27-28
Refrigerant Flow Diagrams ............................................................ 29-32
Wiring Diagrams ............................................................................. 33-39
Accessories .................................................................................... 40-42
Performance Data ........................................................................... 43-52
Equipment Selection Procedure ................................................... 54-56
Building Ventilation Design Guide ............................................... 57-58
Placement Considerations ............................................................ 59-61
Refrigerant Piping Design ............................................................. 64-65
Installation & Layout Best Practices ............................................ 66-70
Electrical Connections ................................................................... 71-72
Mechanical Specications .................................................................. 74
Acronyms ............................................................................................. 75
TABLE OF SYMBOLS
This symbol indicates a potentially hazardous situation which, if not avoided, may result in death, serious injury, property damage or equipment damage.
This symbol indicates additional helpful information such as an explanation, a comment, or a clarication
about the subject.
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
4 | INTRODUCTION
This symbol indicates a recommendation or tip. Recommendations instruct the user to apply the suggested
practice to ensure the best operating results in order to achieve the maximum benet of the product. Tips
contain practical information that may help the user solve a problem or describe actions that may save time.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG” is a registered tra demark of LG Corp.
©
INTRODUCTION
“Architectural Appeal” on page 6
ARCHITECTURAL APPEAL
Convergence of Technological Innovation with Flexibility and Style
Benefits of Single Zone Wall
Mount Systems
• Available from 9,000 - 33,000 Btu/h
• Inverter technology
• All season use - heat pump models for both cooling and heating capabilities
• Operating range for outdoor units of 14°F to 118°F in cooling and -4°F to 75°F in heating
• Operating range for indoor units of 64°F to 90°F in cooling and 60°F to 86°F in heating
• Quiet operation inside and outside
• Duct-free split system
Single Zone Inverter Wall Mount Systems
Single zone wall mount duct free split (DFS) systems are among the industry’s best air­conditioning units. Choosing an LG single zone wall mount product provides a system designer an edge to engineer a system with individual control, and design flexibility with advanced controls.
Single zone systems are available in a nominal capacity range of 3/4 to 2-3/4 tons. These are best suited for applications with zones that require heating or cooling, such as residential, and small business office buildings. Single zone wall mount outdoor and indoor units are available in 208–230V/60Hz/1Ph.
Adaptable and Flexible
Single zone wall mount duct-free split (DFS) systems allow cooling or heating for the entire residence or just a single room without the need for evasive ductwork. There is no tearing down of walls or altering the homes appearance. Long refrigerant piping lengths allow for extra design flex­ibility in indoor unit installation.
These units may be used for a number of residential or commercial environments such as:
• Older homes
• New home construction
• Office buildings
• Restaurants
• Hospitals / Medical facilities
• Schools
• Nursing homes
• Retail establishments
• Place of worship
Inverter Technology
Inverter variable-speed DFS systems are measurably quieter and consume less energy than conventional air conditioners. The inverter compressor ramps up or down to match the required room capacity and maintain the comfort level. When the selected temperature is reached, the inverter compressor operates at low speed to maintain that comfort level, thereby using less energy.
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG” is a registered tra demark of LG Corp.
6 | INTRODUCTION
©
PRODUCT DATA
“Product Features and Benefits” on page 8
“Unit Nomenclature” on page 9
“General Data” on page 10
“Electrical Data” on page 18
“Outdoor Unit Dimensions” on page 19
“Indoor Unit Dimensions” on page 22
“Acoustic Data” on page 26
“Refrigerant Flow Diagrams” on page 29
“Wiring Diagrams” on page 33
“Accessories” on page 40
PRODUCT FEATURES AND BENEFITS
Single Zone Systems
Single zone systems are equipped with inverter components that offer superior load matching and long piping installation. The product works for optimizing power consumption in residential and small office buildings. Utilizing multiple indoor wall mount units each with custom temperature controls allow for precise temperature settings in each zone of the building. Single zone sys­tems allow flexibility in interior design and complement any decor.
Low Sound Levels
When outdoor units operate fully loaded,they have one of the quietest sound levels in the industry. Sound is almost undetectable dur­ing off-peak operation. To promote a quiet, comfortable environment, the single zone system indoor units operate at sound levels as low as 24 dB(A) (High Efficiency Single Zone) and outdoor units as low as 45 dB(A) at full load (High Efficiency Single Zone). LG customers often ask if the outdoor unit is running after commissioning is complete. All rotating components are soft-started by the controller using digitally controlled inverters, which reduce undesirable noise caused by fans and compressors cycling on and off.
Comfort Control at Its Best
Tight temperature control through precise load matching maximizes the time that the indoor units remove moisture. Unlike
traditional air conditioning control systems, which use thermostatic controls to maintain room temperatures, LG Single Zone Inverter controls continuously adjust the indoor unit fan speed and refrigerant flow, indirectly pro­viding lower and more consistent humidity levels in the conditioned space. The longer the indoor coil temperature is below the dew-point of the room in conjunction with air movement across the coil, the space humid­ity level will vary little, compared to technolo­gies that cycle fans and compressors on and off multiple times per hour. The outdoor unit responds by varying the compressor speed
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
and outdoor fan motors as needed to main­tain system operating pressure. As a result, the single zone systems deliver precise space temperature control.
Inverter Driven
The rotary (9k-12k Btu/h systems) and twin rotary (18k-36k Btu/h systems) compressors are optimized to maximize compressor ef­ficiency, which reduces power consumption and monthly utility bills. This latest inverter technology allows single zone system out­door units to vary the compressor motor shaft speed to deliver an appropriate amount of cooling to the indoor unit. Precise refriger­ant volume delivery translates into long periods with coil surface temperatures below dew point and minimizes compressor and fan component run time. Occupants remain comfortable while utility costs are reduced.
Simplified Installation
Cooling and heating applications that use single zone systems simplify and reduce the mechanical and control system design time. The designer no longer has to be concerned with interconnecting chilled and condenser water piping, air-distribution duct systems,matching and selecting chillers, towers,pumps, coils, fans, air handlers, or Variable Air Volume (VAV) boxes.
Operating Range
Single zone systems have a nominal capac­ity range of 3/4 to 2-3/4 tons (depending on outdoor/indoor units).
Operating ranges for single zone systems: Cooling: 14°F DB to 118°F DB Heating: -4°F WB to 75°F WB Installing an optional Low Ambient Wind
Baffle Kit will allow operation down to 0°F in cooling mode for all single zone systems.
Compact Size
Single zone outdoor units have the following footprints:
Single Zone High Efficiency LSU091HSV3, LSU121HSV3
(WxHxD (in)) 30 5/16 x 21 1/2 x 11 5/16.
LSU181HSV3, LSU240HSV3
(WxHxD (in)) 34-1/4 x 31-1/2 x 12-5/8.
Single Zone Standard LSU307HV3, LSU360HV3
(WxHxD (in)) 34-1/4 x 31-1/2 x 12-5/8.
Single Zone Extended Pipe LSU240HLV, LSU300HLV, LSU360HLV
(WxHxD (in)) 34-1/4 x 31-1/2 x 12-5/8.
Fin Design with Gold­Fin™ Coating
All single zone outdoor units are provided with large surface coils made of copper tubes with louvered aluminum fins designed to maximize unit operating efficiency over a wide range of ambient conditions.
Standard from the factory, every single zone outdoor unit coil fin surface is coated with LG’s exclusive GoldFin™ anti-corrosive coating designed to prevent natural surface corrosion of the aluminum fins. This main­tains heat transfer properties of the coil for an extended time.
A hydrophilic coating is applied to the outdoor unit coil fin surface over the GoldFin coating. This coating enhances the develop­ment of heavier water droplets gathering on the fin surface. As a result, the droplets roll off the fin surfaces, delaying the point when frost forms on the coil surface during heating operation. This coating also makes it possible to easily clean the outdoor unit coil
using a mild soap.
Other Features
• Inverter variable speed compressor
• Jet Cool / Jet Heat
• Dehumidifying mode
• Chaos Wind
• Auto restart
• Auto operation
• Self-cleaning indoor coil
• Condensate sensor connection
• Cooling only function
• Precision load matching
• Meets AHRI 210/240
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
8 | PRODUCT DATA
©
Single Zone Indoor and Outdoor Units
LS N 091 HSV 3
Family LS = High Efficiency Wall Mount/
Standard Wall Mount
Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit
Nominal Capacity (Nominal cooling capacity in Btu/h) 091 = 9,000 121 = 11,200 181 = 18,200
240 = 22,000 300/307 = 30,000 360 = 33,000
UNIT NOMENCLATURE
Product Data
Indoor/Outdoor Product HV - Standard Wall Mount
HSV - High Efficiency Wall Mount HLV - Extended Pipe
Generation 3 = Third Generation
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 9
GENERAL DATA
Single Zone High Efciency & Single Zone Standard System Pairing Table
The following tables show the available outdoor and indoor units, along with the factory provided controllers.
Table 1: Single Zone High Efciency & Single Zone Standard System Pairing Table
Outdoor Unit Model Indoor Unit Model Controller
LSU091HSV3 LSU121HSV3
LSN091HSV3 LSN121HSV3
AKB73855712
LSU181HSV3
LSU240HSV3
LSU307HV3 LSU360HV3
LSN181HSV3 AKB73855712
LSN240HSV3 AKB73855713
LSN307HV3 LSN360HV3
AKB73855713
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
10 | PRODUCT DATA
©
Table 2: Single Zone Extended Pipe System Pairing Table
Outdoor Unit Model Indoor Unit Model Controller
LSU240HLV LSU300HLV LSU360HLV
GENERAL DATA
Single Zone Extended Pipe System Pairing Table
LSN240HLV LSN300HLV LSN360HLV
AKB74055401
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 11
GENERAL DATA
Single Zone High Efciency Unit Specications
Table 3: Single Zone High Efciency Unit Specications
Type Single Zone High Efciency Units
LS091HSV3
System Model Number (IDU/ODU)
Nominal Cooling Capacity (Btu/h) Cooling Power Input1 (kW) Nominal Heating Capacity (Btu/h)
1
Heating Power Input1 (kW) Cooling COP EER SEER HSPF Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
2
Cooling (°F DB) Heating (°F WB)
Indoor Unit Operating Range
2
Cooling (°F) Heating (°F)
Unit Data
Refrigerant Type
3
Refrigerant Control IDU Sound Pressure4 dB(A) (H/M/L) ODU Sound Pressure4 dB(A) Power/Communication Cable
5
(No. x AWG) IDU Net/Shipping Weight (lbs) ODU Net/Shipping Weight (lbs)
Compressor
Compressor Type (Qty)
Fan
IDU Type (Qty) ODU Type (Qty) Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM) ODU Max (CFM)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
Low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
5
All power/communication cables to be minimum 18 AWG, 4-conductor, stranded, shielded and must
comply with applicable and national code.
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
(LSN091HSV3/
LSU091HSV3)
9,000 11,200 18,200 22,000
0.67 0.89 1.4 1.7
10,800 13,300 22,000 27,600
0.70 1.0 1.7 2.3
3.90 3.66 3.69 3.66
13.3 12.5 12.6 12.5
21.5 21.5 20.5 20.0
11.0 11.0 9.7 10.2
38/33/24 39/33/24 45/40/35 46/43/39
45 45 53 54
23/28 23/28 32/41 36/42 75/79 75/79 123/131 128/137
Rotary (1) Rotary (1) Twin Rotary (1) Twin Rotary (1)
388/335/272/212 423/353/272/212 735/622/509/399 883/742/629/424
1,165 1,165 2,119 2,119
LS121HSV3
(LSN121HSV3/
LSU121HSV3)
LS181HSV3
(LSN181HSV3/
LSU181HSV3)
LS240HSV3
(LSN240HSV3/
LSU240HSV3)
208-230/60/1
14-118
-4-75
64-90 60-86
R410A
EEV
4 x 18
Cross Flow (1)
Propeller (1)
Brushless Digitally Controlled/Direct
Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units. Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
12 | PRODUCT DATA
©
Table 4: Single Zone High Efciency Unit Specications Continued
Type Single Zone High Efciency Units
LS091HSV3
System Model Number (IDU/ODU)
(LSN091HSV3/
LSU091HSV3)
Piping
Liquid Line (in, OD) Vapor Line (in, OD) Condensation Line (OD, ID) Additional Refrigerant Charge (oz/ft) Max Pipe Length6 (ft) Piping Length6 (no add’l refrigerant, ft) Max Elevation Difference (ft)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
6
Piping lengths are equivalent. Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
1/4 1/4 3/8 3/8 3/8 3/8 5/8 5/8
27/32, 5/8 27/32, 5/8 27/32, 5/8 27/32, 5/8
0.22 0.22 0.38 0.38
65.6 65.6 98.4 98.4
41.0 41.0 24.6 24.6
32.8 32.8 49.2 49.2
GENERAL DATA
Single Zone High Efciency Unit Specications
LS121HSV3
(LSN121HSV3/
LSU121HSV3)
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
LS181HSV3
(LSN181HSV3/
LSU181HSV3)
LS240HSV3
(LSN240HSV3/
LSU240HSV3)
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 13
GENERAL DATA
Single Zone Standard Specications
Table 5: Single Zone Standard Unit Specications
Type Single Zone Standard Units
System Model Number (IDU/ODU) LS307HV3 (LSN307HV3/LSU307HV3) LS360HV3 (LSN360HV3/LSU360HV3) Nominal Cooling Capacity (Btu/h) Cooling Power Input1 (kW) Nominal Heating Capacity (Btu/h)
1
Heating Power Input1 (kW) Cooling COP EER SEER HSPF Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
Cooling (°F DB) Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F) Heating (°F)
Unit Data
Refrigerant Type
2
Refrigerant Control IDU Sound Pressure3 dB(A) (H/M/L) ODU Sound Pressure3 dB(A) Power/Communication Cable
4
(No. x AWG) IDU Net/Shipping Weight (lbs) ODU Net/Shipping Weight (lbs)
Compressor
Compressor Type (Qty)
Fan
IDU Type (Qty) ODU Type (Qty) Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM) ODU Max (CFM)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4
All power/communication cables to be minimum 18 AWG, 4-conductor, stranded, shielded and must comply with applicable and national code.
30,000 33,000
3.0 4.0
32,000 35,200
3.1 3.8
2.93 2.40
10.0 8.2
18.0 16.1
9.5 9.9
208-230/60/1 208-230/60/1
14-118 14-118
-4-75 -4-75
64-90 64-90 60-86 60-86
R410A R410A
EEV EEV
49/44/39 49/44/39
55 55 4 x 18 4 x 18 36/42 36/42
128/137 128/137
Twin Rotary (1) Twin Rotary (1)
Cross Flow Cross Flow
Propeller Propeller
Brushless Digitally Controlled/Direct
883/770/629/424 883/795/629/424
2,119 2,119
Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units. Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
14 | PRODUCT DATA
©
GENERAL DATA
Single Zone Standard Specications
Table 6: Single Zone Standard Unit Specications Continued
Type Single Zone Standard Units
System Model Number (IDU/ODU) LS307HV3 (LSN307HV3/LSU307HV3) LS360HV3 (LSN360HV3/LSU360HV3)
Piping
Liquid Line (in, OD) Vapor Line (in, OD) Condensation Line (OD/ID) Additional Refrigerant Charge (oz/ft) Max Pipe Length5 (ft) Piping Length5 (no add’l refrigerant, ft) Max Elevation Difference (ft)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
5
Piping lengths are equivalent. Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
3/8 3/8 5/8 5/8
27/32, 5/8 27/32, 5/8
0.38 0.38
98.4 98.4
24.6 24.6
49.2 49.2
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 15
GENERAL DATA
Single Zone Extended Pipe Unit Specications
Table 7: Single Zone Extended Pipe Unit Specications
Type Single Zone Extended Pipe Units
System Model Number (IDU/ODU)
Nominal Cooling Capacity (Btu/h) Cooling Power Input1 (kW) Nominal Heating Capacity (Btu/h)
1
Heating Power Input1 (kW) Cooling COP EER SEER HSPF Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
Cooling (°F DB) Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F) Heating (°F)
Unit Data
Refrigerant Type
2
Refrigerant Control IDU Sound Pressure3 dB(A) (H/M/L) ODU Sound Pressure3 dB(A) Power/Communication Cable
4
(No. x AWG) IDU Net/Shipping Weight (lbs) ODU Net/Shipping Weight (lbs)
Compressor
Compressor Type (Qty)
Fan
IDU Type (Qty) ODU Type (Qty) Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM) ODU Max (CFM)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4
All power/communication cables to be minimum 18 AWG, 4-conductor, stranded, shielded and must comply with applicable and national code.
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
LS240HLV (LSN240HLV/
LSU240HLV)
22,000 30,000 33,000
1.7 3.0 4.0
27,000 32,000 35,200
2.3 3.1 3.8
3.66 2.93 2.40
12.5 10.0 8.2
21.0 18.5 16.5 11 10 10
49/44/40 49/44/40 49/44/40
55 55 55
40/46 40/46 40/46
125/133 125/133 125/133
Twin Rotary (1) Twin Rotary (1) Twin Rotary (1)
848/706/530/459 848/706/530/459 848/706/530/459
2,119 2,119 2,119
LS300HLV (LSN300HLV/
LSU300HLV)
LS360HLV (LSN360HLV/
LSU360HLV)
208-230/60/1
14-118
-4-75
64-90 60-86
R410A
EEV
4 x 18
Cross Flow
Propeller
Brushless Digitally Controlled/Direct
Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units. Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
16 | PRODUCT DATA
©
Table 8: Single Zone Extended Pipe Unit Specications Continued
Type Single ZoneExtended Pipe Units
System Model Number (IDU/ODU)
LS240HLV (LSN240HLV/
LSU240HLV)
Piping
Liquid Line (in, OD) Vapor Line (in, OD) Condensation Line (OD, ID) Additional Refrigerant Charge (oz/ft) Max Pipe Length5 (ft) Piping Length5 (no add’l refrigerant, ft) Max Elevation Difference (ft)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
5
Piping lengths are equivalent. Power wiring is field supplied and must comply with the applicable local and national codes This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
3/8 3/8 3/8 5/8 5/8 5/8
27/32, 5/8 27/32, 5/8 27/32, 5/8
0.38 0.38 0.38 164 164 164
24.6 24.6 24.6
98.4 98.4 98.4
GENERAL DATA
Single Zone Extended Pipe Unit Specications
LS300HLV (LSN300HLV/
LSU300HLV)
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
LS360HLV (LSN360HLV/
LSU360HLV)
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 17
ELECTRICAL DATA
Table 9: Single Zone High Efciency Unit Electrical Data
Model Number Nom. Tons Compressor Qty
LSU091HSV3 LSU121HSV3 LSU181HSV3 LSU240HSV3
Table 10: Single Zone Standard Unit Electrical Data
Model Number Nom. Tons Compressor Qty
LSU307HV3 LSU360HV3
Table 11: Single Zone Extended Pipe Unit Electrical Data
Model Number Nom. Tons Compressor Qty
LSU240HLV LSU300HLV LSU360HLV
3/4 1 8.7/8.7 1 0.40 10 15
1 1 8.7/8.7 1 0.40 10 15 1-1/2 1 15.4/15.4 1 0.25 19 25 1-3/4 1 15.4/15.4 1 0.25 19 25
2-1/2 1 15.4/15.4 1 0.25 19 25 2-3/4 1 15.4/15.4 1 0.25 19 25
1-3/4 1 17.3/17.3 1 0.25 23 35 2-1/2 1 17.3/17.3 1 0.25 23 35 2-3/4 1 17.3/17.3 1 0.25 23 35
Compressor (A)
Cool/Heat
Compressor (A)
Cool/Heat
Compressor (A)
Cool/Heat
Fan Qty ODU Fan (A) MCA (A) MOP (A)
Fan Qty ODU Fan (A) MCA (A) MOP (A)
Fan Qty ODU Fan (A) MCA (A) MOP (A)
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
18 | PRODUCT DATA
©
30-5/16
22
4-3/16
13-7/8
6-1/8
2-1/8
10-7/8
1
20-7/8
21-1/2
10-1/2
2-13/16
8-1/8
4
3
2
5
11-5/16
Ø18-5/16
Unit: inch
Return Air Grille
OUTDOOR UNIT DIMENSIONS
LSU091HSV3, LSU121HSV3
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 19
OUTDOOR UNIT DIMENSIONS
34-1/4
21-1/2
12-5/8
14-3/16
6-5/16
2-3/16
13-1/8
12-5/8
31-1/2
30-13/16
15-3/8
3-1/8
2
Ø20-7/8
ksrameRema
N t raP.oN metI
1 Return Air Grille
2
3
4
5
6
Unit: inch
LSU181HSV3, LSU240HSV3, LSU307HV3, LSU360HV3
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
20 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
Item No. Part Name Remarks
1 Air discharge grille
2
3
4
5
6
34-1/4
21-1/2
12 -5/8
14- 3/16
6-5/16
2- 3/16
13- 1/8
12- 5/8
31- 1/2
30-27/32
15- 7/16
3-5/32
1 -31/32
Ø 20-29/32
Unit: inch
OUTDOOR UNIT DIMENSIONS
LSU240HLV, LSU300HLV, LSU360HLV
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 21
INDOOR UNIT DIMENSIONS
Ø2-3/4
5-3/16
3-11/16
Right rear piping
Left rear piping
Installation Plate
Place a level on raised tab
Unit Outline
8-1/2
6-29/32
7-13/321
8-1/4
3
34-13/16
8-1/4
11-1/4
2
1
4
2-5/16
6-5/16
5
29/32
Unit: inch
Ø2-3/4
7-13/321
Return Air Grille
LSN091HSV3, LSN121HSV3
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
22 | PRODUCT DATA
©
9 -11/16
40-9/16
12-13/16
9-11/16
Ø 2-13/16
Ø 2 -13/16
2-11/16
2-13/16
Right rear
piping
Left rear
piping
Installation Plate
Measuring Tape
Measuring Tape
Hanger
Place a level on raised tab
Unit Outline
8 -3/32
4 -3/32
18 -3/32 22-13/32
4
Unit:inch
INDOOR UNIT DIMENSIONS
LSN181HSV3
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 23