LG LS-H0766KA2, AS-H0766KA2, AS-H0966KA2, LS-C0966KA2, AS-H126RKA2 Service Manual

...
LG
Room Air Conditioner
SERVICE MANUAL
LG
MODELS: AS-H0766KA2 LS-H0766KA2
AS-H0966KA2 LS-C0966KA2 AS-H126RKA2 LS-H0966KA2 AS-H186TKA2 LS-C126RKA2 LS-H246TKA2 LS-H126RKA2
website http://biz.LGservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions...............................................................................................................................
.....................
10
Symbols Used in this Manual........................................................................................................
...........10
Indoor Unit.....................................................................................................................
...........................10
Outdoor Unit....................................................................................................................
.........................11
Product Specifications ...............................................................................................................................
..
14
Installation ...............................................................................................................................
......................
16
Selection of the Best Location.....................................................................................................
.............16
Piping Length and Elevation.....................................................................................................................16
How to Fix Installation Plate.....................................................................................................................17
Drill a Hole in the Wall..............................................................................................................................17
Drain hose junction...................................................................................................................................17
Flaring work and connection of piping .......................................................................................................18
Flaring work..............................................................................................................................................18
Connection of Piping Indoor.....................................................................................................................18
Connection of the Pipes-Outdoor.............................................................................................................22
Connecting the cable between indoor unit and outdoor unit ...................................................................23
Connect the Cable to the Indoor Unit.......................................................................................................23
Connect the Cable to the Outdoor Unit ....................................................................................................24
Checking the drainage and forming the pipings........................................................................................25
Checking the Drainage.............................................................................................................................25
Form the Piping........................................................................................................................................25
AIR PURGING ................................................................................................................................................26
Air purging................................................................................................................................................26
Air purging with vacuum pump.................................................................................................................26
Test Running .................................................................................................................................................28
Operation .......................................................................................................................................................29
Function of Controls .................................................................................................................................29
Display Function ......................................................................................................................................33
Self-diagnosis Function............................................................................................................................33
Remote Control Operations......................................................................................................................34
Disassembly ..................................................................................................................................................35
Indoor Unit................................................................................................................................................35
Schematic Diagram.......................................................................................................................................38
Electric Control Device.............................................................................................................................38
Wiring Diagram.........................................................................................................................................39
Components Location ..............................................................................................................................40
Troubleshooting Guide.................................................................................................................................42
Refrigeration Cycle Diagram ....................................................................................................................42
2-way, 3-way Valve .................................................................................................................................43
Cycle Parts...............................................................................................................................................49
Electronic Parts ........................................................................................................................................50
Exploded View...............................................................................................................................................57
Replacement Parts List ................................................................................................................................62
Service Manual 3
LG Model Name
2003
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
4 Room Air Conditioner
2004~
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
ST2
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
.Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
6 Room Air Conditioner
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the
product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
Service Manual 7
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
8 Room Air Conditioner
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam­age.
Safety Precautions
Service Manual 9
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Safety Precautions
10 Room Air Conditioner
Dimensions
Dimensions
Installation plate
D
H
W
W mm 756 900 1,090
H mm 260 285 314
D mm 155 156 172
Model
Dimension
7K, 9K Btu Series 12K Btu Series 18K Btu Series
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Service Manual 11
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
7k, 9k Btu Series 12k Btu Series
DIM unit
W mm 575 717
H mm 525 498
D mm 260 229
L1 mm 301 270
L2 mm 73 56
L3 mm 392 464
L4 mm 35 17
L5 mm 100 130
Dimensions
Outdoor Unit
Dimensions
12 Room Air Conditioner
Outdoor Unit
MODEL
DIM
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
W mm 840
H mm 577
D mm 276 L1 mm 337 L2 mm 64 L3 mm 611 L4 mm 16 L5 mm 156
18K But Series
Dimensions
Service Manual 13
Dimensions
Outdoor Unit
W
L7 L6 L8 L9
D
L1
L2
L3
L10L11
L4L5
H
Gas side
Liquid side
MODEL
DIM
Wmm 870
Hmm 655
Dmm 320
L1 mm 370
L2 mm 340
L3 mm 25
L4 mm 630
L5 mm 25
L6 mm 546
L7 mm 162
L8 mm 162
L9 mm 54
L10 mm 74.5
L11 mm 79
AS-H246TKA2
14 Room Air Conditioner
Model Name
Item Unit
Cooling Capacity
Btu/h
Heating Capacity
Moisture Removal l/h
Power Source Ø,V,Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
Btu/hW
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(WxHxD)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant (R410A) g
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Product Specifications
Product Specifications
Table-1
7000 9000 12000 18500 23500
7300 9300 12500 19000 23500
11.21.22.22.9
1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz
5.0/5.7 5.8/6.6 8.8/9.5 13.4 15.1
20 20 22 42 42
34 37 40 40 47
49 49 52 54 57
730 940 1250 1760 2290
730 970 1140 1900 2450
3.2 4.1 5.6 7.9 10.5
3.2 4.2 5.1 8.5 11.0
9.59 9.57 9.6 10.51 10.26
10.0 9.58 10.96 10.0 9.59
779.52222
18 18 - 72 82.9
756x260x155 756x260x155 900x285x156 1090x314x172 1090x314x172
575x525x260 575x525x260 717x498x229 870x577x276 870x577x276
777.21212
25 26 30 50 60
660g 710g 720g 1270g 1500g
OOO OO
--- --
OOO OO
7HrOFF 7HrOFF 7HrOFF 7HrOFF 7HrOFF
OOO OO
L.C.D wireless L.C.D wireless L.C.D wireless L.C.D Wireless L.C.D Wireless
1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 3/8(9.52)
3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 5/8"(15.88) 5/8(15.88)
--- --
OOO OO
1.0mm2x3,0.75mm2x 2 1.0mm2x 3, 0.75mm2x2 1.0mm2x3,0.75mm2x 2 1.5mm2x3,0.75mm2x 2 12.5mm2x3,0.75mm2x2
1.0mm
2
1.0mm
2
1.0mm
2
3x1.5mm
2
3x2.5mm
2
AS-H0766KA2 AS-H0966KA2 AS-H126RKA2 AS-H186TKA2 AS-H246TKA2
Service Manual 15
Product Specifications
Model Name
Item Unit
Cooling Capacity
Btu/h
Heating Capacity
Moisture Removal l/h
Power Source Ø,V,Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
Btu/hW
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant (R410A) g
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Table-2
7000 9000 12000 12000 9000
7300 9000 13000 - -
1 1.2 1.2 1.2 1.2
1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz 1Ø,220-240V,50Hz
5.0/5.7 5.8/6.6 8.8/9.5 8.8/9.5 5.8/6.6
20 20 22 22 20
35 37 40 40 37
49 49 52 52 49
700 920 1310 1310 950
730 850 1250 - -
3.1 4.1 6.0 6.0 4.2
3.2 3.7 5.8 - -
10 9.78 9.16 9.16 9.47
2.93 3.1 3.05 - 3.1
779.59.57
18 18 - - 18
756x260x155 756x260x155 900x285x156 900x285x156 756x260x155
575x525x260 575x525x260 717x498x229 717x498x229 575x525x260
777.27.27
25 26 30 30 26
650g 690g 800g 670g 690g
OOOOO
-----
OOOOO
7HrOFF 7HrOFF 7HrOFF 7HrOFF 7HrOFF
OOOOO
L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless
1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35)
3/8"(9.52) 3/8"(9.52) 1/2"(12.7) 1/2"(12.7) 3/8"(9.52)
-----
OOOOO
1.0mm2x3,0.75mm2x 2 1.0mm2x 3, 0.75mm2x 2 1.0mm2x 3, 0.75mm2x 2 1.0mm2x 3, 0.75mm2x2 1.0mm2x3,0.75mm2x2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
LS-H0766KA2 LS-H0966KA2 LS-H126RKA2 LS-C126RKA2 LS-C0966KA2
16 Room Air Conditioner
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
More than "A"
More than "B"
More than 2.3m
More than "B"
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
5K~28K 10 5
30K~38K 30 12
Pipe Size
Capacit
y
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
5k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20
1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
Service Manual 17
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
Ø70mm
Left rear piping
Right rear piping
CE A
B
D
Installation plateInstallation plate
ABCD
S6 75 12 80 12 SR2 0 40 20 40 ST2 105 0 210 0
CHASSIS
(Grade)
Distance (mm)
How to Fix Installation Plate Drill a Hole in the Wall
ABC DE SM 180 115 - 115 50 SN 180 115 195 115 -
CHASSIS
(Grade)
Distance (mm)
Drain hose junction
Remove the rubber stopple in the desired drain direc­tion.
Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Only the desired direction
Connecting
part
Adhesive
Drain hose
18 Room Air Conditioner
Flaring work and connection of piping
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.(Optional)
Carry out flaring work using flaring tool as shown below.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Copper
pipe
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Ø19.05 3/4 1.0~1.3
Outside diameter A
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connection of piping -- Indoor
Tubing holder
When install, make sure that the remaining parts must be removed clearlysoasnottodamagethepip­ing and drain hose, especially power cord and connecting cable.
Service Manual 19
Flaring work and connection of piping
Route the indoor tubing and the drain hose in the direction of rear right.
Drain hose
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensurethatthehooksareproperlyseatedontheinstalla­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Connecting pipe
Connecting cable
Tape
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
For right rear piping
20 Room Air Conditioner
Flaring work and connection of piping
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Indoor unit installation
Hang the indoor unit from the hooks at the top of the instal­lation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Tape the drain hose and the connecting cable.
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
For left rear piping
Drain pipe
Connecting cable
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Loading...
+ 46 hidden pages