LG LAN181CNW, LAU181CNW, LA180CPI, LA180CPO User Manual

Page 1
website http://www.lgservice.com
LG
Room Air Conditioner
SERVICE MANUAL
MODELS: LAN181CNW(ASNC183VML3)
LAU181CNW(ASUC183VML3) LA180CPI (ASNC183VML3)
LG
LA180CPO (ASUC183VML3)
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Page 2
2 Room Air Conditioner
Details of 2006 LG Model Name.................................................................................................... 3
Safety Precautions......................................................................................................................... 4
Functions...................................................................................................................................... 10
Product References .................................................................................................................... 12
Dimensions................................................................................................................................... 13
Refrigeration Cycle Diagram....................................................................................................... 15
Wiring Diagram............................................................................................................................. 16
Operation Details ......................................................................................................................... 17
Display Function.......................................................................................................................... 23
Self-diagnosis Function ...............................................................................................................23
Introduction...................................................................................................................................24
Installation.................................................................................................................................... 25
Operation...................................................................................................................................... 42
Disassembly of the parts (Indoor Unit)...................................................................................... 43
2-way, 3-way Valve ....................................................................................................................... 46
Cycle Troubleshooting Guide ..................................................................................................... 54
Electronic Control Device............................................................................................................ 64
Schematic Diagram...................................................................................................................... 67
Exploded View and Replacement Parts List.............................................................................. 69
Air Conditioner Service Manual
TABLE OF CONTENTS
Page 3
Service Manual 3
Details of 2006 LG Model Name
12
Code Type Code of Model Meaning
1 Producing Center/ A~Z
L: ChangWon R22, A: ChangWon R410A, C: ChangWon
R407C
Refrigerant 2 Type of Air conditioner A~Z S: Split Type Air conditioner 3 Cooling/Heating A~Z C: C/O, H: H/P, X: C/O + E/H, Z: H/P + E/H
4,5 Capacity(Btu/h) 1~9 Cooling/Heating Capacity
Ex. "09" ➔ 9,000Btu/h
6 Electric Range 1~9 Electric Standard
1 115V/60Hz 6 220~240V/50Hz 2 220V/60Hz 7 110V, 50/60Hz 3 208~230V/60Hz 8 ➔ 380~415V/50Hz 5 200~220V/50Hz 9 380~415V/60Hz
7 Chassis A~Z Name of tool of unit 8 Color A~Z R: Mirror B: Blue N: Walut
W: White M: Metal C: Cherry
9 Function A~Z
10 Serial No. 0~9
-
Basic A Basic + 4Way B Plasma Filter C Plasma Filter + 4Way D Tele + LED + 4Way E Tele + LCD + Plasma F + 4Way F Tele Multi + LCD + Plasma F + 4Way G Low A + Plasma F H Low A + Plasma F + 4Way J Plasma F + 4Way + Oxygen Generator K A/change + Plasma F L A/change + Plasma F + 4Way M
345678910
Details of 2006 LG Model Name
Page 4
4 Room Air Conditioner
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electri­cian, or an Authorized Service Center.
• There is risk of fire or electric shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (cus­tomer).
• There is risk of fire, electric shock, explosion or injury.
Page 5
Service Manual 5
Safety Precautions
Operation
Be cautious when unpacking and installing the product.
• Shape edges could cause injury. Be especially careful of the sharp edges.
For installation, always contact the dealer or an Authorized Ser­vice Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air con­ditioner could fall with it, causing property damage, product failure, and personal injury.
Install the indoor unit on the wall where the height from the floors more then 8ft(2.4m)
• There are sharp moving parts that could cause personal injury.
Do not handle the pipe by your­self(customer)
• High-Pressure refrigent may cause personal injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electric shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electric shock.
Do not allow water to run into electric part.
• There is risk of fire, failure of the product, and/or electric shock.
8ft(2.4m)
Page 6
6 Room Air Conditioner
Safety Precautions
Do not place a heater or other appliances near the power cable.
There is risk of fire, failure of the product, and/or electric shock.
Do not let the air conditioner run for a long time when the humidi­ty is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Do not store of use flammable gas or combustibles near the air conditioner.
• There is risk of fire or product fail­ure.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
• Some ventilation by opeing win­dow is necessary for the fresh air.
When flammable gas leaks, turn off the gas and open a window for venti­lation before turning the product on. Do not use the telephone or turn switches on or off.
• There is risk of explosion or fire.
Unplug the unit if strange sounds odors or smoke comes from it.
There is risk of fireproduct failure and/or electric shock.
Stop operation and close any window in storm or hurricane. before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of electrical shock.
Thinner
Wax
Page 7
Service Manual 7
Safety Precautions
Ventilate the product from time to time when operating it togeth­er with a stove, etc.
• There is risk of fire or electrical shock.
Unplug the appliance before performing cleaning or mainte­nance.
• There is risk of electric shock.
When the product is not be used for a long time disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended opera­tion.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• There could result in personal injury and product damage.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There are sharp and moving parts that could cause personal injury.
Always check for gas(refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause product failure.
Install the drain hose to ensure that water is drained away prop­erly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leak­age.
Do not install the product where the noise or hot air from the out­door unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Installation
90˚
Page 8
8 Room Air Conditioner
Safety Precautions
Operation
Use two or more people to lift and transport the air conditioner
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion in the product. Corrosion, particularly on the condenser and evaporator fins, could cause product mal­function or inefficient operation.
Do not direct airflow at room occupants.
This could damage your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor unit)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficien­cy of the air conditioner and
Page 9
Service Manual 9
Safety Precautions
Do not drink the water drained from the unit.
It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
Be careful and avoid personal injury.
Replace all the batteries in the remote.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
The chemicals in batteries could cause burns or oth­er health hazards.
Disuse
Page 10
10 Room Air Conditioner
Functions
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 sec at the starting.
Restarting is inhibited for approx. 3 minutes.
High, Med, Low, CHAOS
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops dur­ing defrosting.
The indoor fan stops until the evaporator pipe temperature will be reached at 28°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
Signal Receptor Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.) Operation Indication Lamps
On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation. Defrost Mode : Lights up during Defrost Mode or
Hot Start operation.(Heat pump model only)
Outdoor unit operation : Lights up during outdoor unit operation.
(Cooling model only)
Functions
Operation indication lamps
Page 11
Service Manual 11
Functions
Healthy Dehumidification Operation Mode.
( )
Remote Control
Operation ON/OFF
Reset
Operation Mode Selection
Temperature Setting
Timer Selection
Timer Setting
JET COOL
Timer Cancel
Sleep Operation
Airflow Direction Control
(Cooling
model only)
(Heating
model only)
TEMPERATURE
LOW HIGH
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Air Circulation
°C To °F Swiching Button
Room, Temperature Checking
Setting the Time or Timer
Fan Speed Selection
(Low) (Med) (High)
ON
OFF
CANCEL
SET
2nd F
°C/°F
: (Low:11°C High:39°C)
: OFF, ON, OFF ON
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Fan Operates without cooling or heating.
Cooling
Down to 18°C Up to 30°C
Heating
Down to 16°C Up to 30°C
Page 12
Product References
Product References
Items Unit Power Supply ø, V, Hz 1, 208/230, 60 Cooling Capacity BTU/h 17 800/18 000 Input W 2,000/2,000 Running Current A 9.8/8.9 COMP. Locked Rotor AMP. A 25*2 S.E.E.R 13 Air Circulation m3/min(cfm) 13(460) Moisture Removal l/h(pts/hr) 2.5(5.3) Noise Level Indoor, High dB(A)±3 44 (Sound Med dB(A)±3 40
Pressure, 1m) Low dB(A)±3 36
Outdoor, Max dB(A)±3 55
Features Temperature Control Thermistor
Air Deflection 4-way Steps, Fan/Cool 3/4 Airflow Direction Control(up&down) Auto Airflow Direction Control(left&right) Auto Remocon Type Wireless LCD Setting Temperature Range, Cooling Mode 64~86°F(18~30°C) Temperature Increment 2°F(1°C) Auto Operation(electronic control) Yes Self Diagnosis Yes Timer 24hr, On/Off Sleep Operation Yes Healthy Dehumidification Mode Yes
Restart Delay minutes 3 Refrigerant(R-410A) Charge g(oz) 900(31.8) Power cord AWG #: P*mm Fuse or breaker Capacity A 20 Connecting Cable AWG #: P*mm Connecting Tube Liquid Side mm(in) 6.35(1/4) (ø. Socket Flare) Gas Side mm(in) 12.7(1/2)
Length, std m(ft) 7.5(25) Additional Drain Hose(Outer Dia.) mm(in) 19(3/4) Dimensions Indoor mm 928*522*147 (WxHxD) in 361/2*2019/32*525/32
Outdoor mm 870*655*320
in 341/4*2513/16*125/8
Net Weight Indoor kg(lbs) 17(37.5)
Outdoor kg(lbs) 68(149.9) Gross Weight Indoor kg(lbs) 19(41.9)
Outdoor kg(lbs) 71(156.5)
LA*181CNW(AS-C183VML3)/LA180CP* (AS-C183VML3)
2
2
14:3*2.5
18:4*0.75
NOTE: Please refer to Label Quality on the product since this specification may be changed for improving
performance
12 Room Air Conditioner
Page 13
Service Manual 13
Dimensions
522
928
147
Pipe Hole Fix Hole
MODEL
DIM Unit
W mm(inch) 928(36.5)
H mm(inch) 522(20.6) D mm(inch) 147(5.8)
Indoor Unit
Dimensions
Indoor Unit
Page 14
14 Room Air Conditioner
Dimensions
W
L6 L5 L7 L8
D
L1
L2
L9L10
L3L4
H
Gas side 3-way valve
Liquid side 2-way valve
MODEL
OUTDOOR UNIT
DIM
W mm(inch) 870(34.3)
H mm(inch) 655(25.8)
D mm(inch) 320(12.6) L1 mm(inch) 370(14.6) L2 mm(inch) 25(1.0) L3 mm(inch) 630(24.8) L4 mm(inch) 25(1.0) L5 mm(inch) 546(21.5) L6 mm(inch) 162(6.4) L7 mm(inch) 162(6.4) L8 mm(inch) 54(2.1) L9 mm(inch) 74.5(2.9)
L10 mm(inch) 79(3.1)
Outdoor Unit
Page 15
Service Manual 15
Refrigeration Cycle Diagram
For installation over rated, *a proper quantity of refrigerant should be added for each meter.
Ex) 18K: When installed at a distance of 30m, 450g of
refrigerant should be added. (30-7.5) x 20g = 450g
INDOOR UNIT
HEAT EXCHANGER (EVAPORATOR)
HEAT EXCHANGER (CONDENSER)
COMPRESSOR
GAS SIDE
CAPILLARY TUBE
LIQUID SIDE
OUTDOOR UNIT
MODEL
18K
(Cooling Only)
Pipe size(Diameter:ø) Piping length Elevation
Gas Liquid Rated Max Rated Max
1/2" 1/4" 7.5m(24.6ft) 30m(98.4ft) 5m(16ft) 15m(49ft)
a proper quantity of refrigerant
18K 20g
Refrigeration Cycle Diagram
Cooling Only Models
Page 16
16 Room Air Conditioner
Wiring Diagram
18K (Cooling Only Models)
Wiring Diagram
Indoor Unit
Outdoor Unit
Page 17
Service Manual 17
Operation Details
• DISPLAY
1) C/O Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Sleep Timer Indicator
ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Sleep Timer Indicator
ON while in sleep timer mode, OFF when sleep timer cancel or appliance operation pause.
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp ➲ Setting Temp+0.5°C Compressor OFF Temp Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp ➲ 25°C 24°C Intake Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Operation Details
MAIN UNIT FUNCTION
Page 18
18 Room Air Conditioner
Operation Details
While in compressor off, the indoor f an repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the defrost control time is 7 min or longer, defrost control is then carried out.
While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con­trol is completed and heating mode operation is carried out.
While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost control stops and heating mode operation is carried out regardless of the above condition.
When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of the defrost conditions above.
While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
Page 19
Service Manual 19
Operation Details
Fuzzy Operation (C/O Model)
According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp ➲ 25°C 24°C Intake Air Temp < 26°C Intake Air Temp + 1°C 22°C Intake Air Temp < 24°C Intake Air Temp + 0.5°C 18°C Intake Air Temp < 22°C Intake Air Temp Intake Air Temp<18°C 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Fuzzy Operation (H/P Model)
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C Inatake Air Temp Fuzzy Operation for Cooling 21°C Inatake Air Temp<24°C Fuzzy Operation for Dehumidification Inatake Air Temp<21°C Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C Compressor OFF Temp Setting Temp + 0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°CIntake Air Temp ➲ 25°C 24°CIntake Air Temp<26°C Intake Air Temp + 1°C 22°CIntake Air Temp<24°C Intake Air Temp + 0.5°C 18°CIntake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem­perature.
Page 20
20 Room Air Conditioner
Operation Details
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp + 0.5°C Compressor OFF Temp Setting Temp+0.5°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
26°C Intake Air Temp ➲ 25°C 24°C Intake Air Temp<26°C Intake Air Temp+1°C 22°C Intake Air Temp<24°C Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C Intake Air Temp Intake Air Temp<18°C ➲ 18°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp ➲ Setting Temp Compressor OFF Temp Setting Temp + 3°C
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.
20°CIntake Air Temp Intake Air Temp + 0.5°C Intake Air Temp<20°C 20°C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Page 21
Service Manual 21
Operation Details
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the
low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Swing Mode
By the Chaos Swing key input, the louvers vane automatically operate with the Chaos Swing or they are fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at
extremely high speed for 30 minutes setting the room temp. automatically to 18°C.
CLOSED
OPEN
< Cooling Mode >
CLOSED
OPEN
< Heating Mode >
Page 22
22 Room Air Conditioner
Operation Details
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 60 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at extremely high speed for 60 minutes setting the room temp. automatically to 30°C.
Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem­perature and resets in 18±1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
If you want to stop the operation, re-press the button.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
Remote Control Operation Mode
When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool- ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Heat pump Model
Cooling Model
Room Temp. ≥24°C21°C ≤Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
High High High High
Setting Temperature
22°C22°C23°C24°C
Page 23
Service Manual 23
Display Function
3sec 3sec 3sec
(once)
Error Code
1
Error Display LED
(Indoor body operation LED)
Error contents
Indoor room temperature thermistor open/short
Indoor pipe temperature thermistor open/short.
Indoor Thermistor assembly check
SVC check point
1. Heating Model 2. Cooling Model
Cooling, Soft Dry, Fan, Heating • Cooling, Soft Dry, Fan
Sleep Mode Sleep Mode
Timer Mode Timer Mode
Hot-start, Defrost
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Defrost Indicator
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
Display Function
Self-diagnosis Function
Page 24
24 Room Air Conditioner
Introduction
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that may cause harm to the air conditioner.
This symbol indicates special notes.
Symbols used in this Manual
Features
Signal Receptor
Front Panel
Air Inlet
Air Discharge
Power Cord
Air Filter
Air Intake Vents
Air Outlet Vents
Connecting Wires
Piping
Drain Hose
Base Plate
NEO Plasma Filter
NOTICE
Page 25
Service Manual 25
Installation
Installation
Type "A" screw and plastic anchor
Type "B" screw
Remote control holder
Installation plate
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Horizontal meter
Flaring tool set
Name
Installation Parts
Installation Tools
Read carefully, and then follow step by step.
Page 26
26 Room Air Conditioner
Installation
Installation Map
Installation parts you should purchase.
NOTICE
(Left and right
are identical)
More than 12"(30cm)
More than 28"(70cm)
More than 24"(60cm)
More than 12"(30cm)
Sleeve Bushing-Sleeve
Putty(Gum Type Sealer)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
Vinyl tape (Wide)
To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Apply after carrying out a drainage test.
Saddle
More than
3.9"(10cm)
More than
19.6"(50cm)
Gas side piping (Optional Part) Liquid side piping (Optional Part) Additional drain pipe
Vinyl tape (Narrow) Connecting cable
(Optional Part)
More than 12"(30cm)
Page 27
Service Manual 27
Installation
1. Check the quality label on the indoor and outdoor unit.
2. Make certain that the refrigerant is R-410A.
THIS PRODUCT CONTAINS R-410A REFRIGERANT
1) Different compressor oil
- R-410A(Polyol ester) / R-22(Mineral).
- Do not mix the existing mineral oil.
- Do not apply used pipe, tools and gauges covered with the existing mineral oil.
2) Absorption of moisture
-Compressors oil has the high absorption rate of moisture.
3) Composition
- R-410A(R32:R125=50:50wt%). NOTE: Never mix with other refrigerants
4) High pressure.
- 1.6 times higher than R-22.
- High Pressure refrigerant may cause personal injury.
Do not handle the pipe by yourself (customer) High-pressure refrigerant may cause personal injury.
- manifold gauge ,charging and any piping tools must be dedicated to R-410A systems.
Confirm The Refrigerant
Boiling Pt.(
°C) Vapor pressure(25 °C)(kg f/cnf) Vapor density(25°C)(kg/m2)
R-410A -51.4 15.9 64 R-22 -40.8 9.6 44.4
NOTICE
Example : Split type 12,000 Btu/h
120
100
80
60
40
20
0 R-410A R-22
100
100%
93
70% 50% 30%
89
84
76
0%
100%70%50%30%0%
Page 28
28 Room Air Conditioner
Installation
Read completely , then f ollo w step by step.
1) Select the best location
1. Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front
of the unit.
Make sure that condensation drainage can be con­veniently routed away.
Do not install near a doorway.
Ensure that the space around the left and right of
the unit is more than 50cm(19.7). The unit should be installed as high on the wall as possible, allowing a minimum of 10cm(3.9) from ceiling.
Use a stud finder to locate studs to prevent unnec­essary damage to the wall.
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radia­tion from the condenser is not restricted.
Ensure that the space around the back and sides is more than 30cm(12") . The front of the unit should have more than 70cm(27.5") of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit loca­tion. Consult local codes regarding rooftop mount­ing.
2) Piping length and elevation
More than
10cm(3.9")
More than
50cm(19.7")
More than
2m(6.6ft)
More than
50cm(19.7")
More than 30cm(12") More than 30cm(12")
More than 60cm(24")
More than 60cm(24")
More than 70cm(28")
In case more than 5m(16.4ft)
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters(16.4~23ft).
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION
Install the indoor unit on the wall where the height from the floors more than 2m(6.6ft).
CAUTION
18k 1/2" 1/4"
7.5 15 30 20
(24.6ft)
(49.2ft) (98.4ft)
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B
(m)
Standard
Length
(m)
Installation of indoor, Outdoor unit
Page 29
Service Manual 29
Installation
1. Open panel front
First,Pull the grille bottom, then remove screws(2 pieces), and close grille bottom again.
The moment of lifting the both lower parts of panel front, you can hear sound this panel came out, In this time panel front is separated
After pull down this panel a bit, and separate con­necting wire with product.
Pipe hole
Side cover
Panel F ront
Connector
2. Cover pipe and cover side remove
Remove two screws(for fixing cover pipe)
Pull up the cover side of desired connecting direc-
tion, then cover side is separated.
In case connecting direction is left or right, path through the hole of cover side.
When connecting pipe path through rear wall, don’t remove the hole.
3. Drain hose junction
Remove the rubber stopple of desired drain direc­tion.
As the following picture, Insert drain hose in the handle of drain pan, and join drain hose and con­necting hose.
rubber cap
Only one
desiring direction
Connecting
part
Adhesive
Drain
hose
3) Preparing work for Installation
After removing the pipe hole, cut the burr for safety.
CAUTION
Page 30
30 Room Air Conditioner
Installation
4) How to fix installation plate
The wall you select should be strong and solid enough to prevent vibration
Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
5) Preparing work for installation
1. Drill a hole in the wall
Drill the piping hole with a ø50mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Installation Plate
240mm
(19.4")
240mm
(19.4")
60mm
(2.4")
60mm
(2.4")
Type "A" screw
Ø 70mm
(2.8")
Ø 70mm
(2.8")
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
B
A
Page 31
Service Manual 31
Installation
1) Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.
1. Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
2. Burr removal
Completely remove all burrs from the cut cross sec­tion of pipe/tube.
Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid drop­ping burrs into the tubing.
3. Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
4. Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Carry out flaring work using flaring tool as shown below.
5. Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
2) Connection of piping Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
1. Route the indoor tubing and the drain hose in the direction of rear left or right.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 1.1~1.3 Ø9.52 3/8 1.5~1.7 Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8
Outside diameter A
Drain hose
Flaring Work and Connection of Piping
Page 32
32 Room Air Conditioner
Installation
2.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
3. Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the instal­lation plate.) Ensure that the hooks are properly seat­ed on the installation plate by moving it left and right.
4. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
5. Wrap the insulation material around the connecting portion.
Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping housing section with vinyl tape.
Bundle the piping and drain hose together by wrap­ping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting cable
Gas side piping
Liquid side piping
Drain hose
Loop
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Drain hose
Connecting
cable
mm inch Kgf.cm
Ø6.35 1/4 180~250 Ø9.52 3.8 340~420
Ø12.7 1/2 350~660 Ø15.88 5/8 630~820 Ø19.05 3/4 990~1210
Outside diameter Torque
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Page 33
Service Manual 33
Installation
3) Connection of the pipes-Outdoor
1. Align the center of the pipings and sufficiently tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Installation Information (For right piping)
Good case
For right piping. Follow the instruction below.
Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
Following bending type from left to right could cause problem of pipe damage.
CAUTION
mm inch Kgf.cm
Ø6.35 1/4 180~250 Ø9.52 3/8 340~420
Ø12.7 1/2 550~660 Ø15.88 5/8 630~820 Ø19.05 3/4 990~1210
Outside diameter
Torque
Outdoor unit
Liquid side piping (Smaller diameter)
Gas side piping (Bigger diameter)
Torque wrench
Page 34
34 Room Air Conditioner
Installation
1
Indoor Unit Outdoor Unit
2 3 4
1 2 3 4 5 6
G
To branch circuit
Ground
Power supply
a
L1
*
L2
Connecting cable(Low voltage)
b
Terminal
(4P)
Terminal
(6P)
Outdoor unit
Wiring Diagram
Terminal block
Over 5mm
(2")
Cover control
Conduit panel
Connecting
cable
Power supply
cord
*
L1 is neutral for 115V models.
1) Connection of the cable
1. Remove the cover control from the unit by loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit panel.
4. Properly connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
1. shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of
withstanding temperatures up to 167°F.
4. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch
refrigerant tubing, the compressor or any moving parts.
Connector trade size for this unit is 1/2". Refer to "How to connect wiring to the terminals" for instructions on connecting depending on the wire type you are using.
WARNING
NOTE
Power Supply
Model
Power source
18K 1ø, 208/230V 14 18 20A
AWG(MIN.)
ⓐⓑ
Fuse or breaker
Capacity
NOTE
Connecting The Cable Between Indoor Unit and Outdoor Unit
Page 35
Service Manual 35
Installation
G
Terminal block
Cap (Remove)
Clamp cord
Lock nut
Conduit panel
Loop
Round terminal
Screw with special washer
Screw with special washer
Round terminal
Terminal plate
Wire
Wire
Round terminal
Insulation
Strip 25mm(15/16")
Strip 10mm(3/8")
Solid wire
Cap(Reuse)
Taping
(for sealing)
Low voltage line
(connecting cable)
Power supply line (1ø, 115V, 208/230V)
Hole
(for low voltage line)
Strand wire
2) Connection method of the connecting cable(Example)
(1) Dismount two-caps on the conduit panel. (2) Make a hole appropriate for the passage of
connection cable through on cap by tool.
(for low voltage line) (3) Pass the connecting cable through the hole. (4)
Properly connect the cable on the terminal block. (5) Fix the connection cable with clamp cord
provided on the unit not to have strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight. (6) Wind the vinyl tape round the connecting cable
for sealing between the surface of the
connection cable and cap. (7) Mount the taped part of cable on the cap. (8) Finally, mount the holed cap with the
wound cable on the conduit panel.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For solid core wiring (or F-cable) (1) Cut the wire end with a wire cutter of wire-
cutting pliers, then strip the insulation to expose
the solid wire about 25mm(15/16") (2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate. (3) Using pliers, bend the solid wire to from a loop
suitable for the terminal screw. (4) Shape the loop wire properly, place it on the
terminal plater and tighten securely with the
terminal screw using a screwdriver.
For strand wiring (1) Cut the wire end with a wire cutter or wire-
cutting pliers, then strip the insulation to expose
the strand wiring about 10mm(3/8"). (2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate. (3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a
round terminal. (4) Position the round terminal wire, and replace
and tighten the terminal screw using a
screwdriver.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
WARNING
Page 36
36 Room Air Conditioner
Installation
After the confirmation of the above conditions, prepare the wiring as follows:
1)
Never fail to have an individual power cir cuit specificall y for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of contr ol cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) Confirm that the starting voltage is maintained at more than 90 percent of the rated volt­age marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.
7) Always install an GFCI circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, open fuse, disturbance of the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm(0.12in) in each active(phase) conductors.
Page 37
Service Manual 37
Installation
2) Form the piping
1. Form the piping by wrapping the connecting por­tion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using saddle or equivalent.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
1) Checking the drainage
1. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain exit.
2. Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Checking the Drainage and forming the pipings
Page 38
38 Room Air Conditioner
Installation
CAUTION
CAUTION
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
3) Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit
and the terminal No. are the same as those of indoor unit respectively. (Refer to Wiring diagram on page16.)
Be sure to refer to the wiring diagram label inside the grille and carry out the correct field wiring. Wrong wiring can cause the unit to misoperate to result in a fire hazard.
Check local electrical codes and any specified wiring instructions or limitations.
WARNING
Connecting cable
Page 39
Service Manual 39
Installation
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1) Air purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block
capillary tubing.
Water may lead to corrosion of parts in the refrigera­tion system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacu­ated to remove any noncondensables and moisture from the system.
2) Air purging with vacuum pump
1. Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been prop­erly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
CAUTION
CAUTION
Air Purging
Page 40
40 Room Air Conditioner
Installation
3. Evacuation
Connect the charge hose end described in the pre­ceding steps to the vacuum pump to evacuate the tub­ing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
4. Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clock­wise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way
valves. (2) Remove the service-port cap from the 3-way valve. (3) To open the 2-way valve tur n the valve stem coun-
terclockwise approximately 90°, wait for about 2~3
sec, and close it. (4) Apply a soap water or a liquid neutral detergent on
the indoor unit connection or outdoor unit connec-
tions by a soft brush to check for leakage of the
connecting points of the piping. (5) If bubbles come out, the pipes have leakage.
Soap water method
Required time for evacuation when 30 gal/h vacuum pump is
used
10 min. or more 15 min. or more
If tubing length is less than 10m
(33 ft)
if tubing length is longer than 10m
(33 ft)
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Indoor unit
Pressure gauge
Open
Outdoor unit
Manifold valve
Lo Hi
Close
Vacuum pump
Page 41
Service Manual 41
Installation
1. First, Check the side cover assembly exactly, Fix power cord in the bottom groove of cover side left.
2. Assemble connecting lead wire with controller and first fix the upper part of panel front, then match the lower part of panel front
3. Drive three screws.
Panel F ront
Connector
Panel Front Assembly
Page 42
42 Room Air Conditioner
Installation
1. Check that all tubing and wiring have been properly
connected.
2. Check that the gas and liquid side service valves are
fully open.
1. Prepare remote control
1. Remove the battery cover
by pulling it according to the arrow direction.
2. Insert new batteries making
sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
NOTE:
Use 2 AAA(1.5volt) batteries. Do not use recharge-
able batteries.
Remove the batteries from the remote control if the
system is not going to be used for a long time.
2. Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed
to the hose, secure the unit with an anti-vibration bushing.
3. Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake tempera-
ture and the discharge is more than 8°C(46°F) (Cool­ing) or (Heating).
4. For reference; the gas side pressure of optimum con­dition is as below.(Cooling)
NOTE: If the actual pressure is higher than shown, the
system is most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Bolt
Tubing connection
Discharge air
Discharge temperature
Intake temperature
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Test Running
Page 43
Service Manual 43
Operation
Operation
Remote Control Operations
The controls will look like the following.
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
5.
JET COOL
Used to start or stop the speed cooling.(speed cooling operates super high fan speed in cooling mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. NEO PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
14. RESET BUTTON
Used prior to resetting time.
15. 2nd F Button
Used prior to using modes printed in blue at the bottom of buttons.
16. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
17. ˚C TO ˚F SWITCHING BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
ON
OFF
CANCEL
AUTO CLEAN
SET
1
3
5
4
9
10
12
15
17
7
2
8
13 14
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
16
Operation Mode
1 2 3
Page 44
44 Room Air Conditioner
Disassembly of the parts (Indoor unit)
Warning :
Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.
1. To remove the Grille from the Chassis.
- Push mark[ ] on the grille bottom then pull it down and remove 3 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting wire with product.
2. To remove the Control Box.
- Before removing the control box, be sure to disconnect the wires from PWB.
- Pull the cover control out from the control box and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.
CN-TH1CN-UDCN-DC/DC
CN-LR2
CN-LR1
CN-MOTOR 1 (LEFT)
CN-MOTOR 2 (RIGHT)
Panel Front
Connector
Disassembly of the parts (Indoor unit)
Page 45
Service Manual 45
Disassembly of the parts (Indoor unit)
3. To remove the Evaporator.
- Remove 1 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.
4. Before removing the Turbo Fan.
- Remove the securing screws from the chassis.
- Pull the pipe cover, top cover and the air guide.
5. To remove the Motor.
- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the chassis and lift up the motor mount and the bracket.
Top Cover
Air Guide
Pipe Cover
Bolt
Motor Mount
Bracket
Turbo Fan
Page 46
46 Room Air Conditioner
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
2-way, 3-way Valve
Page 47
Service Manual 47
2-way, 3-way Valve
1. Air purging
Required tools : hexagonal wrench, adjustable
wrench, torque wrenches, wrench to hold the joints, and gas leak detec­tor.
The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not be done correctly and there gas leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.
Procedure
(1) Recheck the piping connections. (2) Open the valve stem of the 2-way valve coun-
terclockwise approximately 90°, wait 10 sec­onds, and then set it to closed position.
– Be sure to use a hexagonal wrench to operate
the valve stem.
(3) Check for gas leakage.
Check the flare connections for gas leakage.
(4) Purge the air from the system.
– Set the 2-way valve to the open position and
remove the cap from the 3-way valves service port.
– Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
(5) Use torque wrench to tighten the service port
nut to a torque of 1.8kg.cm.
Caution
If gas leakage are discovered in step (3) above, take the following mesures :
If the gas leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, dis­charge all of the gas through the service por t, and then recharge with the specified amount of gas from a gas cylinder.
Service port nut: Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
* CAUTION : Do not leak the gas in the air during Air purging.
Liquid side
Outdoor unit
3-way valve
Gas side
Indoor unit
2-way valve
Open
Clsed
Page 48
48 Room Air Conditioner
2-way, 3-way Valve
2. Pumping down
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valve’s stem nuts and the ser- vice port nut.
– Use torque wrench to tighten the service por t
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Do not use the existing charge set for R-22. It is necessary to use new charge set for R­410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pres­sure side gauge of charge set should be used higher pressure gauge of 50kg/cm2range.
Page 49
Service Manual 49
2-way, 3-way Valve
1) Re-air purging
(Re-installation)
Procedure
(1) Confirm that both the 2-way valve and the 3-
way valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the 3-way valve.
Leave the valve on the gas cylinder closed.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
– After purging the air, use a torque wrench to
tighten the flare nut on the 2-way valve.
(4) Check for gas leakage.
Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.
(6) Disconnect the charge set and the gas cylin-
der, and set the 2-way and 3-way valves to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service por t
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
* CAUTION:
Do not leak the gas in the air during Air Purg­ing.
Lo
Closed
OPEN
Closed
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
2-Way valve
3-Way valve
Page 50
50 Room Air Conditioner
2-way, 3-way Valve
2) Balance refrigerant of the 2-way, 3-way valves
(Gas leakage)
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed. Connect the charge hose with the push pin to
the service port.
(3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the gauge indicates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not run­ning is higher than 1 kg/cm2G), discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2G. if this is the case, it will not be neces­sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
2-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 51
Service Manual 51
2-way, 3-way Valve
3. Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the charge set’s
center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
2-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Use vacuum pump equipped with check value applied to be prevented from flowing backward.
Page 52
52 Room Air Conditioner
2-way, 3-way Valve
4. Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale
and revers the cylinder so that the system can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
This unit is charged with R-410A. Pay attention not to charge R-22.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Liquid side
Gas side
Lo
CLOSE
Charging cylinder
Indoor unit
Check valve
(1)
OPEN
2-Way
Open
valve
Open
3-Way valve
Outdoor unit
Page 53
Service Manual 53
2-way, 3-way Valve
Additional gas charging
(Gas leakage)
When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal oper­ating suction pressure.
Use the graph or the equation below to get operating suction pressure according to indoor and out­door temperature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12 11 10
9 8 7 6 5
5 10152025303540
50˚C
40˚C
30˚C
20˚C 10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure (For R410A)
(According to Indoor & Outdoor Temperature)
Page 54
54 Room Air Conditioner
Cycle Troubleshooting Guide
1. Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Operating Current
Temp. difference :approx. 0°F Current :less than 80% of
rated current
Temp. difference :approx. 8°C(14°F) Current :less than 80% of
rated current
Temp. difference :less than 8°C(14°F) Current :less than 80% of
rated current
Temp. difference :over 8°C(14°F)
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humid­ity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 8.5~9.5 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with put­ty.
Suction pressure
(Compared with the
normal value)
Temperature
(Compared with the
normal value)
Cause of Trouble Description
Higher
High
Defective compressor Defective 4-way reversing valve
Excessive amount of refrigerant
High pressure does not quickly rise at the beginning of operation.
Current is low.
Normal
Lower Higher
Insufficient amount of refrigerant(Leakage) Clogging
Current is low. Current is low.
Cycle Troubleshooting Guide
Page 55
Service Manual 55
Cycle Troubleshooting Guide
2. Product does not operate at all. (* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of po wer(About A C 208V/A C230V, 60Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Ass'y(Outdoor unit)
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
Connector related to CN-POWER
Connector related to CN-FAN
Connector contacting of Outdoor Fan/Compressor
Display PWB Ass'y Check
Connector related to CN-DC/DC
Check each load(Indoor/Outdoor Fan Motor, Com­pressor, Stepping Motor) and contacting condition of related connector(including connecting cable of Indoor/Outdoor Unit)
NO
YES
(After 20 seconds)
PCB Board Operation Check
Items
Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
IC01D(7812) Output (Indoor/Outdoor unit)
IC02D(7805) Output
(Indoor unit)
IC04D(7805) Output
(Outdoor unit)
IC01A(KIA7036, Reset IC) OSC01B(4MHz) (Indoor/Outdoor unit)
Replace SMPS Mod­ule
Replace IC01D
Replace
IC02D(Indoor unit) IC04D(Outdoor unit)
Replace faulty parts
- About
AC 208V/AC 230V±10%
- Check the power voltage
- About DC15V±3
DC +12V
DC +5V
Voltage of Outdoor unit Micom No. 18,
Voltage of Indoor unit Micom No. 43 and soldering condition
Content Remedy
Page 56
56 Room Air Conditioner
Cycle Troubleshooting Guide
3. The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote controller
Cause by the remote controller
When the mark( ) is displayed in LCD screen, replace battery .
Check the contact of CN-D1/D2 connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN-D2 - : DC +5V
When the detect switch(double k e y) inside the remote controller door is fault, it is impossible to oper ate temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote controller MICOM (No. ) - R17(2) - IR LED - Q1 - R16(2.2KΩ).
Check point
Check the connecting circuit between PIN - R75(1K)
- C71(1000PF) - MICOM PIN
Check Receiver Ass'y
Page 57
Service Manual 57
Cycle Troubleshooting Guide
4. Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 2°F at least.
When in Fan Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of R02(12.1K), R04(6.2K), Micom (No.27) (Indoor unit).
Check the indoor temper ature sensor is disconnected or not(About 10kΩ/ at 77°F).
When the temperature around Outdoor PWB Ass'y is above 163°F the com­pressor is stop and only Outdoor Fan is operating.
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of Compressor/Outdoor
Fan Motor.
Check Relay(RY - COMP) for driving compressor.
When the power(About AC200V) is applied to the connecting wire terminal support transferred to compressor, PWB Ass'y is normal.
Check the circuit related to the relay(Outdoor unit).
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
5, 6) and GND
Between IC01M, IC02M(No. 9)
Below DC 1V
About DC12V
and
IC01M, IC02M(No. 8)
(app)
Page 58
58 Room Air Conditioner
Cycle Troubleshooting Guide
5. When Indoor Fan does not operate.
Check connecting condition of the CN-MOTOR CON­NECTOR
Does the voltage of terminal of CN-DC/DC CONNECTOR in Indoor unit corresponds to the values in the table of page 63?
Do the voltage of terminal of CN-DC/DC CONNECTOR in Outdoor unit corresponds to the values in the table of page 63?
Check the patterns and the conditions of outdoor unit PWB Assy's.
Check the connecting condi­tion and disconnection of connecting wires between Indoor and Outdoor unit.
Check the pattern and the condition of Indoor unit PWB Ass'y.
Check the interference of Indoor Fan.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in Indoor unit corresponds to values in the Table of page 63?
Check the motor of Indoor Fan
Indoor Fan ma y be stopped in the Soft Dry Mode(change to the Cooling Operation Mode). Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lo wer than 79°F. (At that times, Defrost indicator is turned on)
NO
YES
Page 59
Service Manual 59
Cycle Troubleshooting Guide
Confirm that the Vertical Louver is normally geared with the shaft of Step­ping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-U/D, CN-L/R Connector
Check the soldering condition(on PWB) of CN-U/D, CN-L/R Connector
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-U/D, CN-L/R and GND.
Confirm that there is a soldering short at following terminals.
- Between 62 , 61 , 60 and 59 of MICOM
- Between 57 , 56 , 55 and 54 of MICOM
- Between
51 ,
50 , 49 and 48 of MICOM
- Between
1 , 2 , 3 , 4 and 5 of CN-U/D, CN-L/R
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
6. When Vertical Louver does not operate.
Page 60
60 Room Air Conditioner
Cycle Troubleshooting Guide
The operation indicator of Indoor unit blinks five times.
The red indicator of Outdoor unit blinks five times.
Check the connecting wires between Indoor and Outdoor unit for the connecting error and the contacting condition.
Check the installation condition of outdoor unit.
Check for the communication error and the operating condition of product after also operating with the remote controller, then taking above 2 minutes.
Apply the power again after about 20 seconds by the power of Outdoor unit is off.
Check for the communication error and the operating condition of product after also operating with the remote controller, then taking above 2 minutes.
Check the PWB assembly of Indoor and Outdoor unit.
Caution: If the connecting wires of Indoor and Outdoor unit are not connected within 2 minutes after the power
of Outdoor unit is applied, a communication error will occur. Therefore, the power should be applied after connecting them.
7. When a comunication error occurs.
Page 61
Service Manual 61
Cycle Troubleshooting Guide
8. The phenomena in case of connecting error INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
( and ) of ROOM-TH.
Short between terminals
( and ) of PIPE-TH.
Short between terminals
The same as the phenomenon of Outdoor Unit.
The up/down vane does not operate.
The up/down vane does not smoothly operate.
It does not operate with a remote controller.
The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
The compressor operates continuously regardless of the setting temperature and the variation of room temperature.
The operation indicator blinks once (on for 0.5 second, off for 3 seconds)
Continuous operation
The operation indicator blinks once.
The compressor and the outdoor fan stop.
The indoor fan speed is low.
The indoor fan does not operate.
The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-UD
CN-D1/D2
CN-TH
Blue Black Brown Red
Phenomena
On for 0.5 second
Off for 3 seconds
Page 62
62 Room Air Conditioner
Cycle Troubleshooting Guide
OUTDOOR UNIT
Connector Type
Condition
OPEN
PWB pattern is damaged when applying the power .
Connecting reversely
Connecting reversely
OPEN
OPEN
OPEN
OPEN
Connecting error
( )
Connecting error
( )
Connecting error
( )
Connecting error
( )
Connecting error
( )
Connecting error
( )
All functions stop.
The operation with the remote controller, forced and
test one do not operate.
All functions stop.
The operation with the remote controller, forced and
test one do not operate.
The Indoor Fan does not operate.
The signal of remote controller is inputted, but the
product does not operate.
The RED indicator of outdoor unit and the operation indicator of indoor one blinks 5 times after 2 minutes with applying the power .
No power for Indoor unit.
The signal input of the remote controller and opera-
tion of product is impossible.
The thermal protector of the Power Trans operates
when let it alone for long time.
The signal of the remote controller is inputted.
The fuse and Q61 in the Outdoor unit are damaged
when the indoor fan is operated.
No power for Indoor unit.
The signal input of the remote controller and opera-
tion of product is impossible.
The RED indicator of the Outdoor unit blinks 5 times
after 2 minutes with applying the power.
All functions stop.
The operation with the remote controller , f orced and test
one do not operate.
The only signal of remote controller operation/stop is
inputted, but the product does not operate.
The RED indicator of outdoor unit blinks 5 times after 2
minutes with applying the power .
The beep sound, such as "beep, beep, beep, beep,
beep", occurs periodically in Indoor unit.
The signal input of a remote controller and operation of
product is impossible.
The RED indicator blinks 5 times after 2 minutes with
applying the power .
All functions stop or the compressor does not operate.
The operation with the remote controller , f orced and test
one do not operate.
All functions stop .
The operation with the remote controller , f orced and test
one do not operate.
CN-POWER
RY-COMP
terminal
CN-TRANS
CN-FAN
The connecting
wire of CN-
DC/DC, and
Indoor and Out-
door Unit
Blue Black Brown Red
Phenomena
Page 63
Service Manual 63
Cycle Troubleshooting Guide
9. Voltage of Connectors according to Indoor Fan Speed
4
3
2
1
1
1 2 3 4
INDOOR
FAN
MOTOR
INDOOR PWB ASSY
Connecting wires
between Indoor
and Outdoor
Indoor
Connecting Terminal
Outdoor
Connecting Terminal
Input Power
TAB-N
RY-COMP-A
RY-COMP-B
CN-DC/DC
BL BK BR RD
BL
BK
BR
RD
+-
12
32
42
12
32
42
12
32
42
OUTDOO
R CN-DC/DC
INDOOR
CN-DC/DC
INDOOR
CN-MOTOR
No. of pins
MODELS
CONNELTORS
S-Hi Hi Med Low Off
34.0 32.0 27.8 24.1
34.0 32.0 27.8 24.1
34.0 32.0 27.8 24.1
0.0
5.0 5.0 5.0 5.0 5.0
0~5 0~5 0~5 0~5 5.0
0~12 0~12 0~12 0~12 0~12
17.0 17.0 17.0 17.0 17.0
0.0
0~12 0~12 0~12 0~12 0~12
17.0 17.0 17.0 17.0 17.0
0.0
18K
DC Voltage(±10%)
34 34
Page 64
64 Room Air Conditioner
Electronic Control Device
PWB ASSY SVC PART LIST
1 18K Cooling Model 6871A20387J 12K 20K 27K 12K OPEN OPEN\
NO MODEL P/No.
OPTIONAL FUNCTION
OR1H OR2H OR3H OR4H OR5H OR6H
OJ1H, OJ2H, : SHORT
TOP VIEW
BOTTOM VIEW
Electronic Control Device
MAIN PWB ASSY(Indoor Unit)
Page 65
Electronic Control Device
TOP VIEW
BOTTOM VIEW
MAIN PWB ASSY(Outdoor Unit)
Page 66
66 Room Air Conditioner
Electronic Control Device
• TOP VIEW
• BOTTOM VIEW
DISPLAY PWB ASSEMBLY
Page 67
Service Manual 67
Schematic Diagram
OUTDOOR
48
46
47
44
42
43
40
38
39
41
36
35
34
33
37
45
15
1
2
2
1
23
18
16
17
19 20
21 22
28
24 25 26
27
29
30
31.
32
SLEEP
TIMER
ON/OFF
DEFROST
LED1
LED3
LED4
LED2
58
7
11
13
14
12
10
9
8
63
3
5
6
4
1
2
64
62 61 60 59
53
57 56 55 54
51
52
50 49
1
CN-HVB(BL)
3
2
HVB ASSY
132
12V
R93 10K
RXE250
POLY SW1
CN-MOTOR1(WH)
AVret
AVdd1 AVss
HVB PIN2
HVB
HVB PIN1
receiver
220
10V
IC01D
IC02D
103
C06D
7805
470uF
25V
C05D
+
O
50V
I
104
C04D
470uF
25V
O
C03D
+
7812
CN-12V(WH)
CN-CON(WH)
1111
C03L
3223 3
2
2
3
C04L
25V
RECEIVER
DISPLAY
Vcc
0.01
DC 5V
TEST
KEY
GND
Vout
1111
33
22
33
22
88 8 8
DC5V
L3
DC12V
10
13
12
11
CN-D1
7
8910
456
CN-D1(WH)
10
121311
11
12
1313
12
11
1010
10
777
10988
9
10
8
9
6544
5
6
5
6
4
DC12V
2200uF
35V
C01D
50V
C02D
104
I
+
MOTOR1
FG1
FAN
INDOOR
4321
4321
RXD
FG2
TXD
10K
R96
10K
R97
DC 5V
R95
2
-
+
10K
3
8
KA393
IC9-1
1
4
DC12V
R27H 20K
R28H 20K
12V
5V
5V
220
10V
C02L
10K
R12H
OJ01H
OJ02H
FG1
5
103
C13H
R11H
1K
50V
C03M
103
5V
678
DC 5V
R81A 1K
103
C81A
103
C91
4.7K
R92 10K
KA393
IC9-2
R90 1K
7
R91
6
5
+
-
R81 1K
103
C81
4
Q
SCD
321
FG
5V
S-Hi
OR6H
Hi
OR5H
Med
OR4H
103
C01M
2 2
STEPPING MOTOR
CN-D3
44
5
6
7
567
2
3
2
3
11
4
5
7
6
4
5
7
6
2
3
1
2
3
1
YL
2
3
PK BL
1
2
3
1
1
BL
4
OR
RD
5
1
4
5
STEPPING MOTOR
5
RD
OR
3
YL
PK
4
5
3
4
44 44
CN-D2
123
9
8
7
6
5
CN-D2(WH)
3211
2
3
123
999
5
6
7
8
5
6
7
8
6
5
7
8
3
2
1
SUB PCB ASM
CN-D1(WH)
1
2
3
1
2
3
1
2
3
12V
103
IC02M
KID65004AF
KID65004AF
IC01M
8
9
5V
R01G 220
R04G 220
R03G 220
R02G 220
R07G 220
R06G 220
R05G 220
5V
13
14
16
15
4
3
1
2
10
11
12
7
6
5
6
11
HVB
15
2
16
1
14
12
13
3
5
4
12V
9
10
8
7
0IMCRNE002M
uPD780023AGC
VssO
Vdd0
C02M
bdc
efg
a
Vss1
RESET
AVdd
X2X1INT1
INTO
CN-UD(BL)
1
1
YL
4
5
BL PK
5 4
3 2
OR RD
3 2
STEPPING MOTOR
5V
CN-TH1(WH)
1
~
+
MOTOR2
CN-MOTOR2(YL)
2
INDOOR
24
FAN
3
FG2
43
1
1
63V
C07D
100uF
C01A
25V
0.01
104,50V
750
~
POLY SW2
RXE250
C92
1/4W
DC12V
R99
CN-DC/DC(BL)
33
44
1
2
1
2
R21H~R26H
R26H
F1
OR1HOR2H
Low
OR3H
F2
R22H
R24H
R25H
R23H
R21H
E2 1K
E3 1K
12.1K 1%
5V
214
3
214
3
R05H
10K
KIA7036P
KSC7536
5V
R02H
1%
1%
R04H
6.2K
12.1K
R02A 20K
3
5V
2
3.6V
1
IC01A
324
HVB PIN2
HVB PIN1
ROOM-TH
PIPE-TH
3
1
2
4
5
421
3
312
4
5
CN-LR1(WH)
CN-LR2(WH)
C01L
680pF
PKM13EPP-4002
CST-8.00MTW
5V
1M
R01B
TXD
RXD
OSC01B
50V
5.1K
R01L
1K
R01E
BZ01E
R02E 20
5V
receiver
1K
R02L
8
7
4
5
6
9
12
11
10
13
IC03M
KID65004AF
1
2
3
16
15
14
12V
L / R 2
STEP MOTOR
4
5
RD
312
BL PK
OR
YL
L / R 1
STEP MOTOR
OR
5
4
RD
YL
PK
4
3BL1
OR
STEPPING MOTOR
4
1
BLPK
3
2
YL
4
1
3
2
STEPPING MOTOR
3
PK
5
RD
BL
1
2
4
YL
OR
RD
5
3
5
1
2
4
5
CN-D8
CN-D5
CN-D6
CN-D7
Schematic Diagram
Indoor Unit
Page 68
68 Room Air Conditioner
Schematic Diagram
Outdoor Unit
Page 69
Exploded View and Replacement Parts List
249951
268711-2
147581
135311-2
146811
135500-2
146811
352380-2
352380-1
131410
147581
135311-1
567480
135500-1
135311-3
147581
354210
352150
35211B
349490
330870
135500-3
267110
152302
346810-1
359012-1
346810-2
359012-2
146811
135316
352116
352115
268711-1
135313
159830
Exploded View and Replacement Parts List
Indoor Unit
Service Manual 69
Page 70
Exploded View and Replacement Parts List
Parts List(indoor)
LOCATION
No.
131410 CHASSIS ASSEMBLY 3141A20008J R
135311-1 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A20124K R
135311-2 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A20124J R
135311-3 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A20125G R
135316 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A10334J R
135500-1 COVER 3550A20512B R
135500-2 COVER 3550A20120B R
135500-3 COVER 3550A20121B R
146811 MOTOR ASSEMBLY,STEP 4681A20055A R
147581 LOUVER,HORIZONTAL 4758A20033A R
147582 LOUVER,VERTICAL 4758A20034A R
152302 FILTER(MECH),A/C 5230A10011A R
159830 AIR CLEANER ASSEMBLY 5983A20006P R
249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20825A R
263230 THERMISTOR ASSEMBLY 6323A20004N R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20083R R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20462D R
268714 PWB(PCB) ASSEMBLY,MAIN 6871A20387J R
330870 DRAIN PAN ASSEMBLY 3087A20013B R
346810-1 MOTOR ASSEMBLY,INDOOR 4681A20047C R
346810-2 MOTOR ASSEMBLY,INDOOR 4681A20047D R
349490 ORIFICE ASSEMBLY 4949A20002C R
352115 TUBE ASSEMBLY,EVAPORATOR IN 5211A20302C R
352116 TUBE ASSEMBLY,EVAPORATOR OUT 5211A20301F R
35211B TUBE ASSEMBLY,TUBING 5211A30038X R
352150 HOSE ASSY,DRAIN 5251AR1222R R
352380-1 AIR GUIDE 5238A10009A R
352380-2 AIR GUIDE 5238A10010A R
354210 EVAPORATOR ASSEMBLY,FIRST 5421A20104C R
359012-1 FAN,TURBO 5900A00004A R
359012-2 FAN,TURBO 5900A00005A R
135313 GRILLE ASSEMBLY, INLET 3531A10270T R
DESCRIPTION
LAN181CNW(ASNC183VML3)
LA180CPF(ASNC183UML3)
PAR T N o.
REMARKS
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
70 Room Air Conditioner
Page 71
2. Outdoor unit(18K)
435512
437210
559010
546810
55211G
554031
437212
435511
447910
552202
561410
567502-1
552116
566000
430410
649950
263230-1
263230-2
668711
W0CZZ-2
W0CZZ-1
552203-2
552203-1
554160-1
554160-2
567502-2
550140
550140
263230
Exploded View and Replacement Parts List
Service Manual 71
Page 72
Exploded View and Replacement Parts List
Parts List(outdoor)
LOCATION
No.
552203-1 VALVE,SERVICE 2H02479B R
552203-2 VALVE,SERVICE 5220A20006A R
554031 CONDENSER ASSY,BENT 5403A20058B R
554160-1 COMPRESSOR SET 2520UGJK2AA R
554160-2 COMPRESSOR SET 2520UGAK2AA R
559010 FAN ASSY, PROPOLLER 1A00195B R
567502-1 O.L.P 6750U-L039A R
567502-2 O.L.P 6750U-L058A R
649950 CONTROL BOX ASSY, OUTDOOR 4995A20383W R
668711 PWB(PCB) ASSY, MAIN(OUTDOOR) 6871A10184E R
W0CZZ-1 CAPACITOR, DRAWING 3A00988B R
W0CZZ-2 CAPACITOR, DRAWING 6120AR2194D R
430410 BASE ASSY, OUTDOOR 3041AP2741G R
435511 COVER ASSY, CONTROL(OUTDOOR) 3551AR7184T R
437210 PANEL ASSY, FRONT (OUTDOOR) 3721A20005H R
437212 PANEL ASSY, REAR (OUTDOOR) 3720AP0003D R
550140-2 ISOLATOR, COMP 4H00637A R
546810 MOTOR ASSY, OUTDOOR 4681A20013N R
566000 SWITCH,PRESSURE 6600L000013 R
435512 COVER ASSY, TOP(OUTDOOR) 3H03266P R
55211G TUBE ASSEMBLY, CONDENSER OUT 5211A25034C R
552200 VALVE, EXPANSION BODY 5220A90003B R
561411 COIL ASSEMBLY, EXPANSION 6141A20032A R
435301 GRILLE, DISCHARGE 3530A20007B R
447910 BARRIER ASSEMBLY OUTDOOR 4791A30004K R
263230-1 THERMISTOR ASSEMBLY 6323A20002L R
263230-2 THERMISTOR ASSEMBLY 6323A20016A R
DESCRIPTION
LAU181CNW(ASUC183VML3)
LA180CPO(ASUC183VML3)
PART No .
REMARKS
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
72 Room Air Conditioner
Page 73
P/No.: 3828A20065Y
Printed in Korea
Loading...