LG CV-H186BLB0, CV-H246BLB0 Service Manual

Page 1
Room Air Conditioner
(Con vertible T ype)
SERVICE MANUAL
MODEL: CV-H186BLB0
CV-H246BLB0 (Applied to new Refrigerant R-407C)
Page 2
Functions.................................................................................................................................3
Product Specifications (Cooling & Heating).........................................................................5
Dimensions..............................................................................................................................6
Refrigeration Cycle Diagram..................................................................................................8
Wiring Diagram........................................................................................................................9
Operation Details ..................................................................................................................10
Display Function ...................................................................................................................18
Self-diagnosis Function........................................................................................................18
Installation .............................................................................................................................19
Operation ...............................................................................................................................36
Disassembly of the parts (Indoor Unit)...............................................................................38
Cycle.......................................................................................................................................42
Cycle Troubleshooting Guide...............................................................................................45
Electronic Parts Troubleshooting Guide.............................................................................46
Electronic control device......................................................................................................50
Schematic Diagram...............................................................................................................51
Exploded View and Replacement Parts List.......................................................................52
–2–
Page 3
Functions
• Room temperature sensor. (Thermistor)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low, Chaos
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode or Hot Start Mode (only Heating Model)
--- Lights up during compressor running (only Cooling Model)
• Intermittent operation of fan at low speed.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing up and down, right and left (not on all models) automatically.
• The setting temperature, indoor fan speed and desired operation made are automatically set by fuzzy rule.
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
• Both the indoor and outdoor fan stops during deicing.
• Hot start after deice ends.
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C.
Deice (defrost) control (Heating)
Hot-start Control (Heating)
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Auto Operation
–3–
Page 4
–4–
Soft Dry Operation Mode.( )
Remote Controller
Operation ON/OFF
Reset
Operation Mode Selection
Fan Speed Selection
Room Temperature Display
Temperature Setting
Setting the Time or Timer
Timer Selection
Timer Setting
Timer Cancel
Sleep Operation
Airflow Direction Control
(Cooling
model only)
(Heating
model only)
TEMPERATURE
LOW HIGH
(Low) (Med) (High) (CHAOS)
Cooling Operation Mode.( )
Heating Operation Mode.( )
Auto Operation Mode.( )
Fan Operation Mode
ON OFF
SET
CANCEL
: High:39°C °Í LOW:11°C
: OFF, ON, OFF °Í ON
: Cancel Sleep Mode, Timer ON or Timer OFF.
: 1, 2, 3, 4, 5, 6, 7hr, Off Timer
: Fan Operates without cooling.
Cooling Heating
Down to 18°C Up to 30°C
Down to 16°C Up to 30°C
Page 5
Product Specifications
–5–
Model Name
Item Unit
Cooling Capacity Btu/h(kcal/h) Heating Capacity Btu/h(kcal/h) Moisture Removal /h Power Source
ø
, V, Hz Indoor Outdoor
Input Cooling
Heating
Running Current Cooling
Heating
E.E.R.(Cooling) Btu/h-W C.O.P.(Heating) w/w
Indoor Outdoor Indoor Outdoor
Refrigerant (R-410A) g Airflow Direction Control (Up & Down) Remocon Type
Liquid
Gas
Sleeping Operation Drain Hose Connecting Wire Main Power Cable Time Delay Safety Function Air Circulation Soft Dry Fan Speed (Indoor) Timer Self-Diagnosis Auto-Restart
Air Circulation m3/min
W
A
Dimensions (W x H x D)
Net. Weight
mm
kg
Service Valve & Connecting Tube
CV-H186BLB0 CV-H246BLB0
19,000(4,788) 23,300(6,048) 19,000(4,788) 23,300(6,048)
2.5 3.5 3ø, 220-240V~, 50Hz
13.5 15 45 50
2,050 2,600 2,000 2,550
9.0 11.8
8.8 11.6
9.27 8.96
2.78 2.76
1,200 x 205 615
870 x 655 320
30 59
1,500 1,650
O
L.C.D Wiress
1/4"(6.35)
1/2"(12.7) 5/8"(15.88)
O O
0.75mm
2
2.0mm
2
2.5mm
2
O O O
3 (Hi, Med, Low)
24Hrs
O O
Page 6
Dimensions
(1) Indoor Unit
250mm
36mm
36mm
1076mm
1200mm
205mm
615mm
392mm
265mm
468mm
R
63mm
38mm
175mm
(Installation Plate)
(Rear Side)
–6–
Page 7
(2) Outdoor Unit
Gas side 3-way valve
Liquid side 3-way valve
W
L6L7 L8 L9
L4
L11
L10
D
L1
L2
L5
L3
MODEL
DIM
W mm 870
H mm 655
D mm 320 L1 mm 370 L2 mm 25 L3 mm 340 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54
L10 mm 74.5 L11 mm 79
–7–
CV-H186BLB0 CV-H246BLB0
Page 8
8
Refrigeration Cycle Diagram
• CV-H186BLB0
• CV-H246BLB0
For installation over rated distance, 30g of refrigerant should be added for each meter. ex) If 18K or 24K Model is installed at a distance of 15m, 300g of refrigerant should be added.
(15-7.5) x 30g = 225g
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGER
HEAT EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
CAPILLARY TUBE
COOLING HEATING
REVERSING VALVE
Pipe size(Diameter:ø) Piping length(m) Elevation(m)
MODEL
Gas Liquid Rated Max Rated Max
CV-H186BLB0 1/2" 1/4" 7.5 15 5 8 CV-H246BLB0 5/8" 1/4" 7.5 20 5 8
Page 9
9
Wiring Diagram
(1) Indoor Unit
CV-H186BLB0, CV-H246BLB0
3854A20125GWIRING DIAGRAM
CAPACITOR
MOTOR
BR
OR RD BL BK
CN - FAN
TRANS ­FORMER
THERMISTOR
CN-TH
STEP
MOTOR
STEP
MOTOR
CN-DISP
DISPLAY PCB
ASSY
MAIN PCB
ASSY
CN-UP/DOWN 1,2
CN - TRANS
RY-L RY-M RY-H
FUSE
T3.15A
RY-COMP
CN-4WAY
RY-4WAY
RY-FAN
POWER
INPUT
TO OUTDOOR UNIT
TERMINAL
BLOCK
YL
GN/YL
GN/YL
GN/YL
1(L) 2(N) 3 4 5 6 7 8
BR
BL
BLBKWH
RD
DOOR S/W 1,2
OUTDOOR WIRING DIAGRAM
COMP
R
S
BL
WH
BL
BRBKBK
GN/YL
CAPACITOR
CAPACITOR
REVERSING
VALVE
RD BR
RD BK
OR
TB1
YL OR OR BK
BK
BK
BK BL
WH
C
FAN
MOTOR
TO INDOOR UNIT
TERMINAL
BLOCK
3854A20128P
34
5
6
7
PIPE TH
TNS
NO
L1
L2
L3 L4
D.P
NC NO NC
pipe TH
TB2
1 2 3 4
5 6 7 8 9
Low Ambient PCB
FUSE T3.15A
TRIAC
(2) Outdoor Unit
CV-H186BLB0, CV-H246BLB0
Page 10
Operation Details
(1) The function of main control
1. Time Delay Safety Control
3min…The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle. (Protection of compressor)
5sec…Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
30sec… The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off. While compressor is running, it takes 3~5 seconds to switch.
2. Airflow Direction Control
This function is to swing the louver up and down automatically and to set it at the desired position.
The procedure is as the following.
1st ; Press the ON/OFF Button to operate the product. 2nd ; Press the Airflow Direction Control Button to swing the louver up and down automatically. 3nd ; Repress the Airflow Direction Control Button to set the louver as the desired position.
MODE0
1
2
3
4
5
6
7
135°
Cooling
MODE
MODE
MODE
MODE
MODE
MODE
MODE
9
MODE
(CLOSE)
OPEN
135°
12°
Cooling
HeatingHeatingHeating
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
OPEN
135°
12°
Cooling
Heating
Heating
Heating
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
–10–
For Heating Model
Airflow direction control figure when installed on the floor.
Airflow direction control figure when installed under the ceiling.
Page 11
3. Cooling Mode Operation
When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following
4. Cooling or Heating Mode with Sleep Mode Auto Operation
When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the
operation diagram is as following.
Cooling Mode with the Sleep Mode
The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Heating Mode with the Sleep Mode. (Heating model only)
The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.
COMP. ON (SET TEMP.+0.5°C)
COMP. OFF (SET TEMP. -0.5°C)
More than More than
3 minutes 3 minutes
INDOOR FAN Low Low Low Low Low COMPRESSOR ON OFF ON OFF ON
30 minutes 30 minutes
1°C
1°C
–11–
Setting Temp. +3°C (Compressor OFF)
Setting Temp. (Compressor ON)
Indoor Fan Med. Med. Med. Med. Med. Med. Compressor ON OFF ON OFF ON OFF
Intake Air temp.
COMP. ON (SET TEMP.+0.5°C)
COMP. OFF (SET TEMP. -0.5°C)
More than More than 3 minutes 3 minutes
Selecting Selecting Selecting fan speed fan speed fan speed
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN Low Low
Page 12
5. Auto Operation
The operation procedure is as following. (Cooling & Heating Model)
If initial mode is decided, that mode is continued without the room temperature changing.
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
Auto Operation for Cooling.
–12–
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode Indoor fan speed are automatically decided by Fuzzy rule. Setting temperature
Intake-air
temperature
Operation Mode Heating Soft Dry Cooling
Operation Condition Intake-air Temperature Setting temperature Fan speed Air Direction Control
Over 26°C25°C Over 24°C~below 26°C Intake air -1°C Over 22°C~below 24°C Intake air -0.5°C Over 20°C~below 22°C intake air temperture
below 20°C20°C
Over 20°C~below 30°C Fuzzy control
below 20°C20°C
over 30°C30°C
below 21°C
below
24°C
~
Over 24°C
Over
21°C
When Auto Operation initial start
When pressing room temp­erature setting button during Auto Operation
Controlled
by Fuzzy logic
In this mode, when pressing the verti­cal air diretion con­trol. Button, louvers moves to 1/f rhythm (refer to page 17)
Intake-Air temp
Setting Temp. +0.5°C (Compressor OFF)
Setting Temp.-0.5°C (Compressor ON)
Indoor Fan Compressor
ON ONOFF OFF
Fuzzy Speed
Page 13
Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
Auto Operation for Heating. (Heating model only)
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, louver moves as following cycle.
–13–
Intake Air temp. below 20°C over 20°…~below 21°C
Setting temp. 20°C Intake air temp. +0.5°C
21.5°C
20°C
20°C
Intake-Air temp.
Setting temp.
20.5°C
21°C
MODE0
MODE1
MODE2
MODE3
MODE4
MODE5
MODE6
MODE9
(CLOSED)
End
Start
Page 14
6. Natural wind by CHAOS logic
–14–
For more fresh feeling than other fan speed mode, press the indoor fan Speed Selector and set to CHAOS mode. In this mode, the wind blows like natural breeze by auto­matically changing fan speed according to the CHAOS logic.
Intake Air temp.
OUTDOOR FAN/COMP.
INDOOR FAN
: Setting fan speed : LOW
Cooling on temp.
(Setting temp.+0.5)
Setting CHAOS Natural wind
Setting temp.
Cooling off temp.
(Setting temp.-0.5)
: CHAOS Natural wind
: COMP ON : COMP OFF
GRAPH of Natural wind by the CHAOS logis (During Cooling operation)
Intake Air temp.
30sec
OUTDOOR FAN/COMP.
INDOOR FAN
: Setting fan speed : LOW
Heating off temp.
(Setting temp.+3.0)
Setting CHAOS Natural wind
Heating on temp.
(Setting temp.)
: CHAOS Natural wind
: COMP ON : COMP OFF
GRAPH of Natural wind by the CHAOS logis (During Heating operation)
LOW OR STOP
Page 15
15
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
For Heating Model
INDOOR FAN
4-WAY VALVE
ON
ON ON
OFF OFF
OFF OFF
ON ON
ON ON
26°C
28°C
Indoor piping temp.
Intake Air temp.
Setting temp. +3.0˚C
(Compressor OFF)
Setting temp.
(Compressor ON)
minimum
1min.
minimum
3min.
Fan
Stops
Low
Fan
Low Fan Low Fan Fan StopSelected Fan
Selected
Fan
Low Fan
Selected
Fan
minimum
3min.
minimum
30sec.
minimum
1min.
OUTDOOR FAN
COMPRESSOR
8. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 28°….
During heating operation, if piping temperatures falls below 26°C fan stops.
The operation diagram is as following.
PIPING TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
ON
26°C
: Selected Fan : Low Fan : Fan Stop
28°C
Page 16
16
9. Deice Control
Deicing operation is controlled by timer and sensing the outdoor piping temperature.
The first deicing star ts only when the outdoor pipe temperature falls below -6°C after 30 minutes passed from
starting of heating operation.
Deicing ends after 5 minutes passed from starting of deice operation or when the outdoor pipe temperature rises over 12°C even if before 6 minutes.
The second deicing starts only when the outdoor pipe temperture falls below -6°C after 30 minutes passed from ending of the first deicing.
More than 30 minutes
of heating operation
Within
6 minutes
DeicingDeicing
ON OFF ON ON
ON
ON OFF OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6°C
DEICE ON
12°C
DEICE OFF
The outdoor
piping Temp.
ON
More than 30 minutes
of heating operation
HOT-
START
ON
OFF
ON
INDOOR FAN Low Fan Low Fan
Intake Air temp.
Setting temp. +1.0˚C
(Compressor ON)
Setting temp. -0.5˚C
(Compressor OFF)
Setting temp.
2min.58sec. 2min.58sec.
10min. 10min.7min.
Within 7min.
CoolingCooling
OUTDOOR FAN
COMPRESSOR
Selected
Fan
Selected
Fan
ON
ON
ON
ON
OFF
OFF
OFF
OFFONON
OFF
OFF
ONONOFF
OFFONON
OFF
OFF
10. Soft Dry Operation
During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor OFF temperature is the setting temperature minus 0.5°C.
When the room temperature rises over the compressor ON temperature, the operation mode is switched to the cooling mode.
When the room temperature falls between the compressor ON temperature and OFF temper ature, the operation mode is switched to the Soft Dry Operation. In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room temperature falls below compressor OFF temperature, Compressor OFF.
In micom dehumidify mode, control of fan speed is as following.
Page 17
12. Protection of the evaporator pipe from frosting
If the temperature of the indoor coil is below -2°C after 7 minutes from starting the compressor, the
compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor and the temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoperated. Indoor fan operates at low speed (comp. OFF) or at selected speed (comp. ON)
13. Inlet grille open
Once the inlet grille is opened during operation of the unit, the unit automatically stops operation and the lamps will be turned-off. But memorized functions are still available. When the inlet grille is closed again, the unit become waiting state for operation. From then, the unit can be operated by forced operation button or Start/Stop button of remote controller.
14. Test Operation
When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan regardless of room temperature and resets in 18 min.
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
15. Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance should be on the automatically operates in the mode on the memory.
Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)
If no input by the remote controller or no switching of the slide switch within 7 hr after the appliance operates by the Auto Restarting operation, the appliance is forced to stop at the moment of 7-hr elapse.
–17–
11. Forced operation
If you lose wireless remote controller, you can operate the unit with forced operation switch.
The standard conditions are as following.
Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to
intake Air temperature.
Heat pump Model
Room Temp°24
°C
21°C °¥Room Temp°¬24
°C
Room Temp °¥21
°C
Operation Mode Cooling Soft Dry Heating
FAN Speed High Soft Dry Rule High
Setting Temp. 22°C Air Intake Temperature 24°C
R
Forced Operation Button
Press the Forced Operation Button.
Press the Forced Operation Button once again to stop operation.
Page 18
18
Note)
For normal operation after checking by test mode, you should press SW1 nine times for resetting or reconnect the power cord.
Self-diagnosis Function
1. Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below -2°C after 7 mins from starting the compressor, the compressor and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
2. Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
1. Heating Model
Display Function
Coolling, Soft Dry, Fan, Heating
Timer Mode
Sleep Mode
Hot-start, Deice
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Deice Indicator
Coolling, Soft Dry, Fan, Heating
Timer Mode
Sleep Mode
Outdoor Unit Operating
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Outdoor Unit Operation
Page 19
–19–
1. Selection of the best location
1) Indoor unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consider­ation.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
2) Outdoor unit
• If an awning is built over the unit to prevent direct sun­light or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
1. Installation of Indoor, Outdoor Unit
More than
20cm
More than eye-level
More than
20cm
R
R
More than
20cm
More than
20cm
(Ceiling installation)
(Floor/Wall installation)
More than 10cm
More than 10cm
More than 70cm
Indoor unit
Outdoor unit
B
A
MODEL
18K BTU
1/2" 1/4" 7.5 15
24K BTU
5/8" 1/4"
7.
520
GAS LIQUID
58 30 58 30
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
Rated Rated
Max. Max.
If 18K or 24K Model is installed at a distance of 15m, 225g of refrigerant
should be added .........................................................(15-7.5) x 30g
Installation
Page 20
20
2. Indoor unit installation
Before Installing, prepare Installation Plates
'Installation Plates' are attached at the bottom of indoor unit. Detach them by removing each 3 screws at both sides.
Detach 'Side Plate (R,L)' by removing each 2 screws on both sides.
Pull the upper right and left side of 'Inlet Grille' to the front, and it will stop at slightly tilted position.
Unhook the 'Inlet hanger' from the 'Hanger screw' on the both left and right side.
Detach the 'Inlet Grille' from the Indoor Unit.
1) Installation on the ceiling
Measure and mark the position for the Suspen­sion bolts and the piping hole.
Drill the hole for anchor nut on the ceiling.
Before secure the Installation Plates, select the bent direction of the Installion Plate to the inside or the outside according to the installation circumstances.
Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
R
1076
Suspension
bolt
Center-line for the
piping hole
265
1236
265
Install Plate
1)
2)
R
5~7mm
Indoor Outdoor
WALL
Side Plate
Inlet Grille
Inlet hanger
Hanger
screw
Page 21
21
Insert the nuts and washer onto the suspension bolts
for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the anchor-nuts firmly.
Secure the Installation plates onto the Suspension
bolts (adjust level roughly.) using nuts, washers and spring washers.
Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates.
Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
Move the hooks on the unit to the upper slot of Installation Plates. Then the unit will be declined to the bottomside so as to drain well.
Washer
Nut
Suspension
bolts
Ceiling
Anchor nut
Suspension
bolts
Spring washer
max.
12mm
Washer
Nut
1)
2)
Suspension
bolt
Installation plate
Adjust a level
R
Level gauge
Lower slot
R
R
Upper slot
Page 22
–22–
Drain hose
Ceiling
Ceiling
Ceiling
Front of view
Side of view
1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 7mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
CAUTION
The unit must be horizontal or declined to the drain hose connected when finished installation.
The unit must be declined to the bottomside of the unit when finished installation.
Page 23
–23–
R
R
R
1
2
Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 28, 31.
R
Inlet hanger
Hook
Cabinet Bottom
Secure the unit to the Installation Plates with four M8 bolts and washers.
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.
Fit the projection hooks of the side plates to the 'Side
Panel' and the 'Front Panel' by lifting it.
Fasten the screws.
Page 24
–24–
1076
more than
260
265
Washer
Nut
Wall
Anchor nut
Spring washer
Wall
5~7mm
Less than
12mm
1236
Indoor Outdoor
2) Installation on the Wall
Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor nut on the wall.
Drill the piping hole on the wall slightly tilted to the out- door side using a ø70 hole-core drill.
Secure the 'Install Plate' onto the wall with four anchor
bolts, washers and spring washers.
Before secure the Install Plates, select the bent direc­tion of the 'Install Plate' to the inside or outside accord­ing to the installation circumstances.
Page 25
–25–
Install the Indoor unit onto Installation Plate.
Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate.
Secure the unit to the Installation Plate with four M8 bolts and washers.
Hook up the Inlet Grille Hook to the cabinet.
Hang the Inlet Hanger to the screw.
Fit the projection hooks of the side plates to the 'Side
Panel' and the 'Front Panel' by lifting it.
Fasten the screws.
R
2
1
Before working, refer to "Connecting pipe and cable to Indoor Unit" on page 29, 31.
Inner slot
Page 26
26
3) Installation on the floor
Installation of Mount Bracket.
Select and mark the position for Mount Brackets and the piping hole.
Drill the hole for the anchor nut on the wall.
Drill the piping hole using a ø70 hole-core drill.
Secure the Mount Brackets on the wall with four M4
screws.
Install the indoor unit onto the Mount Brackets.
Engage the slot at the back of the unit with Mount Bracket.
Drill the piping hole with 70mm dia, hole core drill.
Piping hole should be slightly slant to the outdoor side.
After Installing, reassemble detached parts.
Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the Hanger Screw.
Assemble the 'Side Plates(R,L)' with 2 screws on both left and right side.
Floor mount
bracket
Slot
Floor mount bracket
Install plate
Slot
Piping hole
Wall
5~7mm
Indoor Outdoor
more than 760mm
From the left wall
From the right wall
448mm
more than 840mm
Wall
Page 27
27
2. Piping and Drainage of Indoor Unit
2-1. Preparation of Piping
1. Cut the pipes and the cable.
Use the accessory piping kit or the pipes pur­chased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured dis­tance.
Cut the cable 1.5m longer than the length of the pipe.
2. Remove burrs.
Remove burrs from cut edges of pipes.
Turn the pipe end toward down to avoid the metal
powder entering the pipe.
Caution: If burrs are not removed, they may cause a gas leak­age.
3. Flaring the pipes.
Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. (When the flare nuts are removed from the indoor unit.) Some gas may leak, as some gas is charged to prevent the inside of the pipe from rusting.
Fit the copper pipe end into the Bar of flare tool about 0~1.0mm higher.
(See illustration)
Flare the pipe ends.
Carr y out flaring work using dedicated flaring tool
for R-410A.
4. Tape the flaring portion to protect it from the dust or damages.
90
Slanted Rough
Pipe cutter
Pipe
Reamer
Point down
"A"
Bar
Bar
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Copper pipe
Inclined Cracked Uneven
thickness
Surface
damaged
= Improper flaring =
When properly flared, the internal surface of the flare will evenly shine and be of even thickness. After the flare part comes into contact with the connec­tors, carefully check the flare finish.
"A"; ø15.88 mm (5/8")
1.0 mm
ø12.7 mm (1/2")
0.5 mm
ø9.52 mm (3/8")
0.5 mm
ø6.35 mm (1/4")
0.5 mm
Page 28
28
2-2. Installation on the ceiling
1)
Connecting the pipes to the indoor unit
The pipe can be connected to right side, bottom or back of the unit.
1. For the Right Side Piping
After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet. Drain hose should be go through under the Hose Bracket as shown in figure .
Hang the drain hose on the hose hanger and fix it to the hole of the hose bracket with a screw.
2. For the Bottom Side Piping
Remove the knock-out on the bottomside of Inlet Grille
Align the center of the pipings and sufficiently tighten
the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Hang the drain hose on the hose hanger and fix it to
the hole of cabinet bottom with a screw.
2) Connecting the Drain Hose
The drain hose can be connected to not only the
right side but also left side of the unit.
If the drain hose is connected to the left side, it
should go through the cabinet bottom.
Hang the drain hose on the hose hanger and fix it to the hole of cabinet bottom with a screw.
R
R
R
Drain Hose
Drain Hose
Piping
Hose
Bracket
1
3
4
5
2
Hose Hanger
Hose Hanger
Hose Hanger
BOTTOM
Page 29
29
2-3.
Installation on the wall or floor
1) Connecting the pipes to the indoor unit
1. For the Right Rear Piping
Remove the knock-out at the back side of the cabinet.
After bending an end of the connecting tube, align the
center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Tape the Drain Hose to the pipings to avoid coming
off the drain-outlet.
2. For the Right Side Piping
After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
Tape the Drain Hose to the pipings to avoid coming
off the drain-outlet.
3.
For the Right Bottom Piping
Align the center of the pipings and sufficiently tighten the flare nut with fingers.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
Connect the Drain Hose insulated to the drain outlet.
2)
Connecting the Drain Hose
The drain hose can be connected to not only right side but also left side of the unit.
Taping Drain Hose
Piping
Piping
Drain Hose Connecting
Cable
Drain Hose
Piping
Drain Hose
REAR
BOTTOM
Taping
Taping
Page 30
30
1) Connecting the pipes to the Outdoor unit
1. Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on the wrench.
1) Checking the Drainage
1. Remove the Air Filter.
To remove air filter, take hold of tab and pull
slightly upwards.
2. Check the drainage.
Spray one or two glasses of water upon the
evaporator.
Ensure that water flows drain hose of indoor unit
without any leakage.
3. Connecting Pipes to the Outdoor Unit
4. Checking the Drainage
R
Liquid side piping (Smaller Dia.)
Gas side piping (Bigger Dia.)
Torque wrench
Outdoor unit
R
Pipe Size Torque
Liquid Side
1/4" 1.8kg·m 3/8" 4.2kg·m
Gas Side
1/2" 5.5kg·m 5/8" 6.6kg·m
Page 31
31
1) Connecting cables to the Indoor Unit
1) Remove the Air guide - L by loosening 2 screws after removing the Inlet grille from the Indoor unit.
2) Connect the wires to the ter minals on the con­trol board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
R
AIR GUIDE-L
INDOOR UNIT
Control
Panel
1
2
Clamp
Terminals on the indoor unit
POWER
INPUT
GN/YL
POWER
INPUT
GN/YL
Terminals on the indoor unit
1(L) 2(N)
34
Terminals on the outdoor unit
34
Terminals on the outdoor unit
34
567
1(L) 2(N)
3456 78
Cooling & Heating type
Cooling only type
NORMAL CROSS­SECTIONAL AREA
2.5mm2(24K)
2.0mm2(18K)
NORMAL CROSS­SECTIONAL AREA
2.5mm
2
(24K)
2.0mm2(18K)
NORMAL CROSS­SECTIONAL AREA
0.75mm
2
The power cord connected to the indoor unit should be complied with the following specifications (Type H05VV-F(Indoor) approved by HAR or SAA).
The power connecting cable
connected between the indoor and outdoor unit should be complied with the following specifications (Type H07RN-F approved by HAR or SAA).
The connecting cable connected between the indoor and outdoor unit should be complied with the following specifications (Type H07RN-F approved by HAR or SAA).
CAUTION
Ø8.0mm
Ø10.0mm
Ø8.0mm
Ø10.0mm
Ø6mm
5. Connecting Cables between Indoor Unit and Outdoor Unit
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2cable(thinner cable) on the clamp and tighten it with a plastic clamp to the oth­er boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of live pin on the power plug should be over 1.8m.
Page 32
32
3) Connecting the cable to Outdoor Unit
1. Remove the Cover control from the unit by loosening a screw. Connect the wires to the terminals on the control board individually as following.
2. Secure the cable onto the control board with the hold­er (clamper).
3. Refix the cover control to the original position with the screw.
4. Use a recongnized circuit breaker 20A(18K, 24K) between the power source and the unit. A disconnec­tion device to adequately disconnect all supply lines must be fitted.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of contr ol box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
Proper starting power is not given to the compressor.
10) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor unit
Terminal block
Connecting cable
Cover control
Holder for connecting cable
Over 5mm
Holder for power supply cord
Power supply cord
Page 33
33
4) Form the pipings
1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings)
If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
2. Tape the Pipings, drain hose and Connecting Cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
2. Tape the Pipings and Connecting cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.
4. Fix the pipings onto the wall by saddle or equivalent.
In case of the Outdoor unit being installed below position of the Indoor unit.
In case of the Outdoor Unit being installed above position of the Indoor Unit.
Trap is required to prevent water from entering into electrical parts.
Seal a small opening around the pipings with gum type sealer.
Taping
Drain hose
Pipings Connecting
cable
Plastic Band
Power supply cord
Seal a small opening around the pipings with gum type sealer.
Trap
Page 34
34
6. Air Purging of the Pipes and Indoor Unit
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor.
1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below -76cmHg.
5. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench.
6. Tighten the valve stem nuts of the 2-way valve and 3-way valve.
7. Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m)
Indoor unit
Outdoor unit
Liquid side
CLOSEOPEN
Vaccum pump
Gas side
Closed
Closed
2-way valve/
3-way valve
3-way
valve
Page 35
35
7. Test running
R
Thermometer
2) Evaluation of the performance
1. Measure the temperature of the intake and dis-
charge air.
2. Ensure the difference between the intake temper-
ature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
3)
Selection of the slide switch according to installation method (Heating model only)
1. In case the indoor unit is installed on the floor,
please change the side switch which is on the Main PCB Assembly to the 'BOTTOM' state.
2. In case the indoor unit is installed under the ceil-
ing, please change the slide switch which is on the Main PCB Assembly to the ' CEILING' state.
The initial state of the slide switch is set for the bottom installation.
1) Connection of power supply
1. Connect the power supply cord to the inde-
pendent power supply.
Circuit breaker is required.
2. Prepare the remote control.
Insert two batteries provided. Remove the battery cover from the remote con­troller.
Slide the cover according to the arrow direction. Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equiva­lent.)
Be sure that the (+) and (-) directions are cor­rect.
Be sure that both batteries are new. Re-attach the cover.
Slide it back into position.
3. Operate the unit for fifteen minutes or more.
Page 36
36
Operation
(1) Name and Function-Remote controller
1) Cooling Model
Signal transmitter.
Transmits the signals to the room air conditioner.
Remote Controller
ON OFF
SET
CANCEL
1
2
7
8
9 10 11
4 5 6
3
OPERATION DISPLAY
Displays the operation conditions.
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
AIR FLOW DIRECTION START/STOP BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heat­ing (turns indoor fan on/off).
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
RESET BUTTON
Used prior to resetting time or after replacing batteries.
123
4
5
6
7
8
9
10
11
Page 37
37
2) Heat Pump Model
Signal transmitter.
Transmits the signals to the room air conditioner.
Remote Controller
ON OFF
SET
CANCEL
1
2
7
8 9
10
11
4
5
6
3
OPERATION DISPLAY
Displays the operation conditions.
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
AIR FLOW DIRECTION START/STOP BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heat­ing (turns indoor fan on/off).
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
RESET BUTTON
Used prior to resetting time or after replacing batteries.
123
4
5
6
7
8
9
10
11
Page 38
–38–
Disassembly of the parts (Indoor unit)
Warning :
Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.
1. Remove the air filter.
• Pull the inlet grille slightly toward you.
• Pull out the air filter. (2 pieces)
2. Remove the girlle fr om chassis
• Remove the screws securing the side plate and push to the bottom-side.
• Unhook the hanger from the hanger screw at the left and the right side.
• Pick out the inlet grille.
3. Remove the lower air guide
• Remove a screw of both side fixing "barrier air­guide".
• Remove the screws of both sides of the lower air­guide.
• Remove the lower air-guide toward “arrow mark” by turning upwards as shown in figure.
R
RRR
1
3
4
2
Hanger
Screw
Hanger
Inlet Grille
Barrier Air guide
Lower Air guide
Page 39
39
4. Remove air guide upper, crossflow fan and motor.
Remove the screws of both sides and center securing the upper air-guide.
Remove 2 screws fastening the bracket of door switch.
Remove a bearing assembly by removing a screw and the bearing cover.
Remove 4 screws securing the motor cover.
Loosen the screw securing the crossflow fan to
the fan motor shaft. (do not remove)
Remove the crossflow fan by sliding it out from the shaft of fan motor.
5. Remove the control box Assembly.
Disconnect the step motor connector, fan motor connector, display PCB connector, thermistor connector and door switch connector from the main PCB.
If necessary, disconnect power supply cord and connecting cable from the terminal block and remove the cord clamp screw.
Remove 2 screws securing the control box and pick out the control box carefully.
R
R
R
Motor
Cover
Bearing
Cover
Bearing
Door
Switch
Page 40
40
6. Remove the front panel.
Remove the screws of both sides fixing the front panel.
Push the upper side of front panel strongly to pull out the front panel from the inner hook of diffuser frame.
Pull down the front panel carefully not so as to harm the display PCB wires and thermistor wires.
7. Remove the diffuser assembly.
Remove the screws of both side of diffuser assembly. (4 pieces)
Push the upper side of cabinet strongly to pull out the inner hook of diffuser frame from the cabinet hole.
Take up the diffuser frame carefully not so as to harm the display PCB wires and the step motor wires.
8. Remove display PCB assembly.
Remove the screws at the both side of display cover.
If necessary, disconnect the display PCB connector from PCB assembly.
Remove 2 screws of PCB assembly.
R
R
Diffuser frame
Front
Panel
Diffuser
frame
Front
Panel
Hook
Diffuser
frame
Cabinet
Hook
Display Cover
Page 41
9. Remove the vane-upper, vane-lower and step motor.
Remove 2 screws securing the step motor assembly and pull it out from the vanes carefully.
Unhook the vanes from the vane supporter and remove the upper vane and lower vane by pulling the center of vanes with care.
10. Remove the drain pan assembly.
Remove the both side of screws. (4 pieces)
Pull out the drain pan assembly.
Be careful not to harm to the EPS packing of
drain pan and the tubings of evaporator.
11. Remove the evaporator.
Remove the screws of both sides securing the EVA barrier-R/L on the side cabinet.
Remove the screws which fasten the barrier on the evaporator and take out the barrier assembly.
Remove the evaporator assembly by sliding toward arrow mark. (As shown in figure)
–41–
EVA. Barrier-L
EVA. Barrier-R
Side Cabinet
Lower Vane
Upper Vane
Vane Supporter
Step Motor
Page 42
42
Cycle
1. Installation (Connecting the piping between indoor and outdoor unit)
• Installation
(1) Connect the piping between the indoor and
outdoor unit firmly.
– Incorrect connection may cause the leakage and
incomplete vacuuming.
(2) Attach the charging hose (manifold gage) to the
service port.
– Charging hose is necessary to check the pressure
and to inject N2 for leakage test.
– The valve of charging hose must be closed before
being connected.
(3) Inject the 100~300g N
2 through the charging hose
opening the valve.
(4) Check the joint part using a gas detector or soapy
water for leakage.
– On checking, the service valve of main service port
must be closed, this test is only for checking whether pipe connection is OK or not.
(5) If there is no leakage, discharge N
2 in piping
completely into tank for retrieving.
Completely discharge is needed for vacuuming. If leakage is found, please fasten the joint more
tightly.
(6) After closing the valve of charging hose,
disconnect the tank and connect the vacuum pump to charging hose and open the valve again for vacuuming.
(7) Turn on the vacuum pump until the pressure drops
below 0 kg/cm
2
.
(8) After vacuuming, disconnect the vacuum pump and
open the spindle of service port (liquid-side) slightly for 30 sec and then open the spindle of service port (gas side) with hexagonal wrench.
(9) Open the liquid side completely first and then the
gas side fully in order.
Lo
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
2(3)-Way valve
3-Way valve
Gas cylinder
R-407C
Page 43
43
2. Disconnection (on moving)
• Disconnection
(1) Attach the charging hose (manifold gage) to
the service port.
– Connect the manifold gage once to the service
port not stopping. Stopping in the middle of process may cause the leakage.
(2) Purge the air in hose into special device such
as retrieving tank opening the valve of charging- hose (gas side) slightly and then close it tightly.
(3) Operate the air conditioner for 10~15 min until
cycle is stabilized.
(4) Close the spindle of service port (liquid side-
high pressure) and wait till pressure of gas side (low pressure) drops below 0 kgf/cm2.
(5) After the needle of gage indicates below
0 kgf/cm2, close the valve of gas side quickly and turn off the power.
(6) Disconnect the piping between indoor and
outdoor unit and then put on service cap to the service port.
Lo
Outdoor unit
Indoor unit
Liquid side
Gas side
Closed
Closed
2(3)-Way valve
3-Way valve
Retrieving Tank
Page 44
44
3. Gas Charging
(After Evacuation)
• Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-
connected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can be charged in liquid state.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the
specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping partway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Lo
Charging cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2(3)-Way valve
3-Way valve
OPEN
Open
Check valve
(1)
Page 45
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the rated
current
Temp. difference : over 8°C
Operating Current
All amount of refrigerant leaked out Check refrigeration cycle
Refrigerant leakege Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
NOTICE :
1. The suction pressure is usually 8.5~9.5 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)
Defective compressor Current is low Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation
Insufficient amount of Current is low
Lower Higher refrigerant (Leakage)
Clogging Current is low
High
Higher
–45–
Page 46
Electronic Parts Troubleshooting Guide
: The unit does not operate.
Possible Trouble 1
–46–
YES
YES
YES
NO
YES
Is the input voltage
of transformer AC220V?
Is the input voltage
of IC01D DC14V?
Check the FUSE and the wiring diagram Check the RY-COMP PIN 3 and CN-4WAY PIN 1
Is the output voltage
of IC01D DC12V?
Is the PIN 29 of
Micom DC5V?
Exchange Micom
YES
NO
Check the main P.C.B pattern
NO
NO
Exchange D01D-D05D
NO
YES
Exchange the transformer
Is shorted the
transformer output?
NO
YES
Is the output voltage
of IC02D DC5V?
NO
Is the PIN 55,64 of
Micom DC5V?
YES
Exchange IC01D
Exchange IC02D
NO
Check the 5V P.C.B pattern
Is the output voltage
of transformer about AC14V?
Exchange IC01A
Page 47
47
Possible Trouble 2
: The indoor fan does not operate.
NO
NO
YES
NO
Is it DRY mode?
Is it the HOT
mode?
Is IC02M operated
normally?
Check the fan motor and connector. (CN-FAN)
YES
Is the each S.S.R
any problem?
YES
NO
YES
Adjust set temperature
Does the temperature
set all right?
NO
Adjust set temperature
Does the temperature
set all right?
NO
YES
YES
Exchange
IC02M
Exchange S.S.R
Page 48
48
Possible Trouble 3
: Up/Down Air direction louver does not operate.
Possible Trouble 4
: Remote controller does not operate.
YES
NO
YES
Is IC01M operated
normally?
Is the PIN 1 of
CN-UP/DOWN DC12V?
Check the step motor and connector (CN-UP/DOWN 1,2)
Check the main P.C.B DC12V pattern
NO
Exchange
IC01M
NO
YES
YES
YES
Is the battery consumed
much?
Is the PIN 8 of CN-DISP
DC5V?
Is the connection of
CN-DISP all right?
Exchange receiver ass'y
Connect CN-DISP exactly
NO
NO
Exchange the battery
Check the main P.C.B DC5V pattern
Page 49
49
Possible Trouble 5
: Ineffective Heating
Possible Trouble 6
: The unit does not operate by forced operation switch.
YES
YES
NO
Is 4way-valve operated?
Check the RY-4WAY and 4way-valve
Exchange IC02M
NO
Check RY-4WAY
NO
YES
Is the F/OP key
any problem?
Check P.C.B pattern check
Exchange F/OP key
Is IC02M operated
normally?
Page 50
50
Electronic control device
(1) MAIN P.C.B ASM (CV-H186BLB0, CV-H246BLB0)
(2) DISPLAY P.C.B ASM (P/No.: 6871AQ3263A)
Page 51
Schematic Diagram
51
Page 52
Exploded View and Replacement Parts List
1. Indoor Unit
–52–
130911
263230
35211A
342800
359010
152302
330870
354211
352115
261704
137213
W0CZZ
166000
346811
268712237900
235450
146811
159911
159911
352150
267110
137213
135314
Page 53
–53–
130911 CABINET ASSY 3091AP2533A 3091AP2533A 135314 GRILLE ASSY, INLET SUB 5237A10002K 5237A10002K 137213 PANEL ASSY, SIDE 3720AP2767P 3720AP2767P 137213 PWB(PCB) ASSY, MAIN 6871A20042H 6871A20042H 146811 MOTOR ASSY, STEP 4681AR2727G 4681AR2727G 152302 FILTER(MECH), A/C 5230AP7093A 5230AP7093A 159911 VANE ASSY, HORIZONTAL 5991AP2867B 5991AP2867B 159911 VANE ASSY 5991AP7334C 5991AP7334C 166000 SWITCH, PUSH 6600AP2059B 6600AP2059B 235450 DISPLAY ASSY (MECH) 3545AP7224A 3545AP7224A 237900 WINDOW, DISPLAY 3790AP7080A 3790AP7080A 261704 TRANSFORMER, POWER 6171AQ3198E 6171AQ3198E 263230 THERMISTOR ASSY 6323AQ2333Y 6323AQ2333Y 267110 REMOTE CONTROLLER ASSY 6711A20010K 6711A20010K 268712 PWB(PCB) ASSY, DISPLAY 6871AQ3263A 6871AQ3263A 330870 DRAIN PAN ASSY 3087AP7233A 3087AP7233A 342800 BEARING 3H02821B 3H02821B 346811 MOTOR ASSY, INDOOR 4681AP2306G 4681AP2306E 352115 TUBE ASSY, EVA-IN 5211AP2810J 5211AP2810J 35211A TUBE ASSY, SUCTION INDOOR 5211AP2813B 5211AP2813A 352150 HOSE ASSY, DRAIN 5251AP2460B 5251AP2460B 354211 EVAPORATOR ASSY 5421AP2812A 5421AP2812A 359010 FAN ASSY, CROSS FLOW 5901AR2351E 5901AR2351E W0CZZ CAPACITOR 3H00671A 3H00671A 738280 MANUAL, OWNERS 3828A20147D 3828A20147D 738281 MANUAL, SERVICE 3828A20059X 3828A20059X
Parts List (Heat Pump Models)
LOCATION
DESCRIPTION
PART No.
NO.
REMARK
CV-H186BLB0 CV-H246BLB0
Page 54
2. Outdoor Unit
–54–
435512
554030
552201
437212
552201
W0CZZ-2
268711
263230
435511
W6640
668713 W0CZZ-3
552202
566000
552203
552203
430410
552570
554160
561410
447910
W0CZZ-1
546810
559010
437210
Page 55
55
Parts List (Heat Pump Models)
LOCATION
DESCRIPTION
PART No.
NO.
REMARK
349480 ORIFICE 4948AP2527A 4948AP2527A 435311 GRILLE, DISCHARGE 3530A20007B 3530A20007B 435512 COVER ASSY, TOP(OUTDOOR) 3H03266K 3H03266K 437210 PANEL ASSY, FRONT 3721A20005Q 3721A20005Q 437212 PANEL ASSY, REAR 3720AP0003D 3720AP0003D 546810 MOTOR ASSY, OUTDOOR 4681A20013T 4681A20013X 552111 TUBE ASSY, CAPILLARY 5211A10039T 5211A30331R
552202 VALVE, REVERSING 3A02027A 3A02027A 552203-1 VALVE, SERVICE 2H01890D 2A00392E 552203-2 VALVE, SERVICE 2H02479F 2H02479F
554031 CONDENSER ASSY, BENT 5403A20022F 5403A20022F
554160 COMPRESSOR SET 2520UWFP2AA 2520UWJP2BA
559010 FAN ASSY, PROPELLER 1A00195B 1A00195B
561410 COIL ASSY, REVERSING VALVE 3A02028Y 3A02028Y
649950 CONTROL BOX ASSY, OUTDOOR 4995A20027M 4995A20027N W0CZZ-1 CAPACITOR, DRAWING 3A00988B 6120AR2094T W0CZZ-2 CAPACITOR, DRAWING 2A00986D 2A00986D
CV-H186BLB0 CV-H246BLB0
Page 56
P/No.: 3828A20059X
June, 2003
Printed in Korea
Loading...