LG CT24R INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL
AIR CONDITIONER
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands [Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
MFL67855536
Rev.02_040319
Copyright © 2016 - 2019 LG Electronics Inc. All Rights Reserved.
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
CEILING CASSETTE Original instruction
www.lg.com
РУССКИЙ ЯЗЫК
ENGLISH
УКРАÏНСЬКА
ITALIANO ESPAÑOL
ҚАЗАҚ ТІЛІ
БЕЛАРУСКАЯ МОВА
FRANÇAIS DEUTSCH
OʻZBEK TILI
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
2
ENGLISH
MODEL DESIGNATION
MODEL DESIGNATION
Product information
- Product Name : Air conditioner
- Model Name :
SQSM N B 015
- Additional Information : serial number is refer to the barcode on the product.
- Max allowable pressure High side :
4.2 MPa / 4.32 MPa (it can be different by model)
- Max allowable pressure Low side :
2.4 MPa
- Refrigerant : R32 / R410A
Serial number
Chassis name
Indoor Unit / Outdoor Units
N : Indoor Unit U : Outdoor Unit
Detailed product type only for M- series models
AQ : Wall mounted Libero-R SQ : Wall mounted Libero-E AH* : ARTCOOL AW* : ART COOL Mirror AH : Ceiling Cassette AHL : Ceiling Concealed Duct (Low Static) R : Refrigerant R32/R410A PC : Standard plus (S)
Detailed product type for U- / C- series models
L : Low Static H : High COP C : Econo R : Refrigerant R32 / R410A
Nominal Capacity
Ex) 7 000 Btu/h Class '07', 18 000 Btu/h Class '18'
Product type
S : Wall mounted / ARTCOOL mirror J : Wall mounted A : ARTCOOL T : Ceiling Cassette B, M : Ceiling Concealed Duct V : Ceiling Suspended & floor Q : Console P : Floor Standing
Connectable Outdoor unit type
M : Indoor units only for
Multi systems
U : Indoor units only for
Single A systems
C : Common Indoor Unit for
Multi and Single CAC
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels.
Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required.
Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country.
This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m3(Freon gas weight per unit air volume) for facilitating calculation
Limiting concentration: 0.44 kg/m3(R410A)
n Calculate refrigerant concentration
Refrigerant
concentration
(kg/m3)
Total amount of replenished refrigerant in refrigerant facility (kg)
=
Capacity of smallest room where indoor unit is installed (m3)
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
3
ENGLISH
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
The following symbols are displayed on indoor and outdoor units.
Read the precautions in this manual carefully before operating the unit.
This symbol indicates that the Operation Manual should be read carefully.
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product.
WARNING
!
It can result in serious injury or death when the directions are ignored.
CAUTION
!
It can result in minor injury or product damage when the directions are ignored.
WARNING
!
This appliance is filled with flammable refrigerant (R32)
This symbol indicates that a service personnel should be handling this equipment with reference to the Installation Manual.
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
• Compliance with national gas regulations shall be observed.
Installation
• Always perform grounding.
- Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation agency.
- Otherwise, it may cause a fire, electrical shock, explosion or injury.
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of
the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board.
- No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner.
- Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down.
- Otherwise, it may result in personal injury.
• Use caution when unpacking and installing.
- Sharp edges may cause injury.
• The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
• Two or more people must lift and transport the product. Avoid personal injury.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• Do not pierce or burn refrigerant cycle part.
• Be aware that refrigerants may not contain an odour.
• Keep any required ventilation openings clear of obstruction.
• The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.(for R32)
• Refrigerant tubing shall be protected or enclosed to avoid damage.
• Flexible refrigerant connectors (such as connecting lines between the indoor and outdoor unit) that may be displaced during normal operations shall be protected against mechanical damage.
IMPORTANT SAFETY INSTRUCTIONS
6
ENGLISH
• A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.
• Mechanical connections shall be accessible for maintenance purposes.
• The appliance shall be installed in accordance with national wiring regulations.
Operation
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep the flames away.
- Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation.
- Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter.
- They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling down.
IMPORTANT SAFETY INSTRUCTIONS
7
ENGLISH
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit.
- Otherwise, children may be seriously injured due to falling down.
• Use a vacuum pump or inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or oxygen, and do not use flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
• Turn off all devices that cause fire when the refrigerant leaks., ventilate the room (example : opening window or using ventilation unit), and contact with dealer who you purchased the unit.
• The installation of pipe-work shall be kept to a minimum.
• When mechanical connectors are reused indoors, sealing parts shall be renewed.(for R32)
• When flared joints are reused indoors, the flare part shall be re­fabricated.(for R32)
CAUTION
!
Installation
• Install the drain hose to ensure that drain can be securely done.
- Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
- Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product.
- Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product.
- Otherwise, it may cause vibration or water leakage.
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an
IMPORTANT SAFETY INSTRUCTIONS
8
ENGLISH
industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.(for R32)
• Wear adequate personal protection equipment (PPE) when installing, maintaining or servicing the product.
• Pipe-work shall be protected from physical damage.
Operation
• Avoid excessive cooling and perform ventilation sometimes.
- Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
- The appearance of the air conditioner may deteriorate, change color,
or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles.
- Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet.
- Otherwise, it may cause the failure of appliance or an accident.
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. (for R32)
• Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
TABLE OF CONTENTS
TABLE OF CONTENTS
2 MODEL DESIGNATION
3 TIPS FOR SAVING ENERGY
4 IMPORTANT SAFETY INSTRUCTIONS
10 INSTALLATION PLACES
12 THE INDOOR UNIT INSTALLATION
13 Indoor Unit Drain Piping 14 Wiring Connection 16 Flaring Work
19 REMOTE CONTROLLER INSTALLATION
21 Wired remote controller installation
22 INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
9
ENGLISH
24 TEST RUNNING
25 OPTIONAL OPERATION
25 Installer Setting - Test Run Mode 26 Installer Setting - Setting Address of Central Control 27 Installer Setting - Thermistor 28 Installer Setting - Ceiling Height Selection 29 Installer Setting - Group Setting 30 Installer Setting -Dry Contact Mode Setting 31 Installer Setting - Celsius / Fahrenheit Switching 32 Installer Setting - Optional Function Setting 33 Installer Setting - Remote controller Mode Lock
34 HOW TO SET E.S.P?
INSTALLATION PLACES
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
10
ENGLISH
INSTALLATION PLACES
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
10 or
Ceiling
Ceiling Board
more
Ceiling Board
500 or more
* Please use an annexed sheet or the
corrugated cardboard on the bottom of packing as installation sheet.
500 or
1 000
or more
Chassis
H
Floor
more
H
TU 3 300
TQ/TR/TP 3 600
TN/TM 4 200
* When using the bottom sheet, please use it
after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.
Unit : mm
300 or less
At least 1 800
H or less
INSTALLATION PLACES
11
ENGLISH
Minimum floor area
(for R32)
- The appliance shall be installed, operated and stored in a room with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
Amin (m2)
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant charge + additional refrigerant amount
- Amin : minimum area for installation
600
500
400
300
200
100
0
Floor location
m (kg) Amin (m
< 1.224
1.224
12.9
1.4 16.82
1.6 21.97
1.8 27.80 2 34.32
2.2 41.53
2.4 49.42
2.6 58.00
2.8 67.27 3 77.22
3.2 87.86
3.4 99.19
3.6 111.20
3.8 123.90 4 137.29
4.2 151.36
4.4 166.12
0 1.224 2 3 4 5 6 7 8
2
)
-
Floor location
m (kg) Amin (m
4.6 181.56
4.8 197.70 5 214.51
5.2 232.02
5.4 250.21
5.6 269.09
5.8 288.65 6 308.90
6.2 329.84
6.4 351.46
6.6 373.77
6.8 396.76 7 420.45
7.2 444.81
7.4 469.87
7.6 495.61
7.8 522.04
2
)
Wall mounted
m (kg) Amin (m
< 1.224
1.224
1.43
1.4 1.87
1.6 2.44
1.8 3.09 2 3.81
2.2 4.61
2.4 5.49
2.6 6.44
2.8 7.47 3 8.58
3.2 9.76
3.4 11.02
3.6 12.36
3.8 13.77 4 15.25
4.2 16.82
4.4 18.46
2
)
-
Wall mounted
m (kg) Amin (m
4.6 20.17
4.8 21.97 5 23.83
5.2 25.78
5.4 27.80
5.6 29.90
5.8 32.07 6 34.32
6.2 36.65
6.4 39.05
6.6 41.53
6.8 44.08 7 46.72
7.2 49.42
7.4 52.21
7.6 55.07
7.8 58.00
2
)
Ceiling Mounted
m (kg) Amin (m
< 1.224
1.224
0.956
1.4 1.25
1.6 1.63
1.8 2.07 2 2.55
2.2 3.09
2.4 3.68
2.6 4.31
2.8 5.00 3 5.74
3.2 6.54
3.4 7.38
3.6 8.27
3.8 9.22 4 10.21
4.2 11.26
4.4 12.36
2
)
-
Floor standing
Wall mounted
Ceiling mounted
m (kg)
Ceiling Mounted
m (kg) Amin (m
4.6 13.50
4.8 14.70 5 15.96
5.2 17.26
5.4 18.61
5.6 20.01
5.8 21.47 6 22.98
6.2 24.53
6.4 26.14
6.6 27.80
6.8 29.51 7 31.27
7.2 33.09
7.4 34.95
7.6 36.86
7.8 38.83
2
)
THE INDOOR UNIT INSTALLATION
12
ENGLISH
THE INDOOR UNIT INSTALLATION
TP/TN/TM Series
875(Ceiling opening)
787(Hanging bolt)
840 Unit size
671
523
Ceiling
840 Unit size
TQ/TR Series
585~660
517
570
570
319
Level gauge
Ceiling board
(Hanging bolt)
684
Unit:mm
517
875(Ceiling opening)
585~660
CAUTION
!
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
NOTE
!
Avoid the following installation location.
1
Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
-
Make sure that ventilation fan is enough to cover all noxious gases from this place.
- Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Air conditioner
1 065
965
448
Unit:mm
50
354
466
400 4040
600
306
461
TU Chassis
50
860
250
- Select and mark the position for fixing bolts and piping hole.
- Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
- Drill the hole for anchor bolt on the wall.
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
2 Avoid installng air conditioner in such
places where cooking oil or iron powder is generated.
3 Avoid places where inflammable gas is
generated.
4 Avoid place where noxious gas is
generated.
5 Avoid places near high frequency
generators.
THE INDOOR UNIT INSTALLATION
Ceiling board
Maintenance drain port
Upward routing not allowed
Pipe clamp
Indoor unit
Ceiling
Keep the length of the bolt from the bracket to 40 mm
Air Conditioner body
Keep the length of 15~18 mm between the air conditioner bottom surface and the ceiling surface
Paper model for installation
Keep the length of 20~22 mm between the air conditioner bottom surface and the ceiling surface
Paper model for installation
Set screw of paper model (4 pieces)
Open the ceiling board along the outer edge of the paper model
Ceiling
Air conditioner body
Set screw of paper model (4 pieces)
Open the ceiling board along the outer edge of the paper model
Ceiling board
Ceiling board
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Flat washer for M10 (accessory)
Flat washer for M10 (accessory)
Nut (W3/8 or M10)
The following parts is option.
Hanging Bolt - W 3/8 or M10Nut - W 3/8 or M10Spring Washer - M10Plate Washer - M10
4Way
Keep the length of the bolt from the bracket to 40 mm
1Way
Ceiling board
Adjust the same height
Ceiling board
Adjust the same height
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
13
150 mm
Ceiling board
70 mm
ENGLISH
CAUTION
!
Tighten the nut and bolt to prevent unit falling.
Wall
Indoor
Outdoor
5~7 mm
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
- During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
- The outside diameter of the drain connection on the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP­25 and pipe fittings
- Be sure to execute heat insulation on the drain piping.
- Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
THE INDOOR UNIT INSTALLATION
700 or less
1 -1.5 m
Clamp metal(attached) Drain hose(attached)
Drain raising pipe
300 mm or less300 mm or less300 mm or less
Remote controller cord
1
1
Connection cord between the indoor unit and the outdoor unit
Control box cover (On which the Electric Wiring Connection is put)
14
ENGLISH
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Drain test The air conditioner uses a drain pump to drain
water. Use the following procedure to test the drain pump operation:
- Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
- Feed water to the flexible drain hose and check the piping for leakage.
- Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
- When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Feed water
Drain Pump
Drain pan
Flexible drain hose (accessory)
Drain port
Drain hose connection Use the clip (accessory)
Main drain pipe
Glue the joint
HEAT INSULATION
- Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120 °C).
- Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23 °C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
Indoor unit
- Heat insulation material to be prepared... Adiabatic EPDM or NBR with thickness 10 to 20 mm.
- Stick glass wool on all air conditioners that are located in ceiling atmosphere.
Fastening band (accessory)
Refrigerant piping
Thermal insulator (accessory)
Wiring Connection
- Open the control box cover and connect the Remote controller cord and Indoor power wires.
- Remove the control box cover for electrical connection between the indoor and outdoor unit. (Remove screws )
- Use the cord clamper to fix the cord.
CAUTION
!
The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
Max 300 mm
Metal clamp
Insulation
Hanger
distance
Hanger Bracket
1~1.5 m
1/50~1/100 slope
Flexible drain hose
Max 700 mm
THE INDOOR UNIT INSTALLATION
NORMAL CROSS-SECTIONAL AREA 0.75 mm
2
20 mm
35±5 mm
GN/YL
10±3 mm
Power wire
Round pressure terminal
Connect same thickness
wiring to both sides.
It is forbidden to
connect two to one
side.
It is forbidden to
connect wiring of
different thicknesses.
15
ENGLISH
CAUTION
!
The connecting cable connected to the indoor and outdoor unit should
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
be complied with the following specifications (This equipment shall be provided with a cord set complying with the national regulation).
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
CAUTION
!
The Power cord connected to the unit should be selected according to the following specifications.
- For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
16
Pipe
Reamer
Point down
Flare nut
Copper tube
ENGLISH
THE INDOOR UNIT INSTALLATION
Flaring Work
Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
1 Use the piping kit accessory or the pipes
purchased locally.
2 Measure the distance between the indoor
and the outdoor unit.
3 Cut the pipes a little longer than measured
distance.
4 Cut the cable 1.5 m longer than the pipe
length.
Copper
pipe
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. While removing burrs put the end of the copper tube/pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing.
90 °
Slanted Uneven Rough
Putting nut on
- Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after finishing flare work)
Flaring work
1
Firmly hold copper pipe in a bar with the dimension shown in below table table below.
2 Carry out flaring work with the flaring tool.
Pipe diameter
Inch (mm)
Ø 1/4 (Ø 6.35) Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Ø 5/8 (Ø 15.88) Ø 3/4 (Ø 19.05)
Bar
<Wing nut type>
0.04~0.05 (1.1~1.3)
0.06~0.07 (1.5~1.7)
0.06~0.07 (1.6~1.8)
0.06~0.07 (1.6~1.8)
0.07~0.08 (1.9~2.1)
A inch (mm)
Wing nut type Clutch type
0~0.02 (0~0.5)
"A"
Copper pipe
<Clutch type>
CAUTION
!
Copper in contact with refrigerants shall be oxygen-free or de-oxidized, for example Cu-DHP as specified in EN 12735-1 and EN 12735-2.
CAUTION
!
• The installation of pipe-work shall be kept to a minimum.
• Flared joint shall be restricted to use with annealed pipe only, and to pipe sizes not exceeding a diameter of 20 mm outside diameter.
THE INDOOR UNIT INSTALLATION
17
ENGLISH
Check
1 Compare the flared work with the figure
by.
2 If a flared section is defective, cut it off
and do flaring work again.
Smooth all round
Even length
all round
Inside is shiny without scratches
= Improper flaring =
Inclined
Surface
Cracked Uneven
damaged
thickness
Connecting the installation pipe and drain hose to the indoor unit
1 Align the center of the pipes and
sufficiently tighten the flare nut by hand.
Indoor unit tubing Flare nut Pipes
2 Tighten the flare nut with a wrench.
Outside diameter
mm inch kgf.m Ø 6.35 1/4 1.8~2.5 Ø 9.52 3/8 3.4~4.2 Ø 12.7 1/2 5.5~6.5
Ø 15.88 5/8 6.3~8.2 Ø 19.05 3/4 9.9~12.1
Torque
CAUTION
!
(for R32)
• When mechanical connectors are reused indoors, sealing parts shall be renewed.
• When flared joints are reused indoors, the flare part shall be re-fabricated.
3 When needed to extend the drain hose of
indoor unit, assembly the drain pipe as shown on the drawing.
Drain pipe
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
Wrap the insulation material around the connecting portion
1 Overlap the connection pipe insulation
material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
Insulation material
Torque wrench
Indoor unit tubing
Open-end wrench (fixed)
Flare nut
Connection pipe
THE INDOOR UNIT INSTALLATION
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case Bad Case
* Tubing cutting line have to be upward.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
18
ENGLISH
2 Set the tubing cutting line upward.
Wrap the area which accommodates the rear piping housing section with vinyl tape.
3 Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient enough to cover where they fit into the rear piping housing section.
Wrap with vinyl tape
Pipe
Drain hose
Vinyl tape(wide)
REMOTE CONTROLLER INSTALLATION
1
2
3
2
3
<Wire guide grooves>
REMOTE CONTROLLER INSTALLATION
Please fix tightly using provided screw after placing remote controller setup board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
- Install the product so as not to make a gap with the wall side and to prevent shaking after the installation.
19
ENGLISH
Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller cable guide groove.
* Remove guide groove with long nose.
Reclamation to the surface of the wallUpper part guide grooveRight part guide groove
REMOTE CONTROLLER INSTALLATION
Wall Side
Wall Side
Wall Side
Wall
Side
<Connecting order>
<Separating order>
Please check if connector is normally connected.
Connecting cable
Indoor Unit side
20
ENGLISH
Please fix remote controller upper part into the setup board attached to the surface of the wall, as the picture below, and then, connect with setup board by pressing lower part.
- Please connect not to make a gap at the remote controller and setup board’s upper and lower, right and left part.
- Before assembly with the installation board, arrange the Cable not to interfere with circuit parts.
When separating remote controller from setup board, as the picture below, after inserting into the lower separating hole using screw driver and then, spinning clockwise, remote controller is separated.
- There are two separating holes. Please individually separate one at a time.
- Please be careful not to damage the inside components when separating.
Please connect indoor unit and remote controller using connection cable.
Please use extension cable if the distance between wired remote controller and indoor unit is more than 10 m.
CAUTION
!
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50 m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
REMOTE CONTROLLER INSTALLATION
no
Wired remote controller installation
Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5 ft(1.5 m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
Direct
Sun ray contact area
yes
no
21
ENGLISH
no
5 feet
(1.5 meters)
no
no
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
Separate the link from the front grill
Coner cover
Hook clip
Hook
22
ENGLISH
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
The decorative panel has its installation direction. Before installing the decorative panel, always remove the paper template.
1 Remove the packing and take out air inlet
grille from front panel.
3 Fit the panel on the unit by inserting hooks
as shown in picture.
4 Insert two screws on diagonal corners of
panel. Do not tighten the bolts completely. (The fixing screws are included in the indoor unit box.) Check the alignment of panel with the ceiling. Height can be adjusted using hanging bolts as shown in picture. Insert the other two screws and tighten all screws completely.
2 Remove the Corner covers of the panel.
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
Screw
Installing the grill link on the panel body
Inserting the edge into the panel body
Closing the door lock
Check the left, right and central sections
CN_VANE 1,2
CN_DISPLAY
23
ENGLISH
5 Fit the corner covers.
6 Open two screws of control panel cover.
7 Connect one display connector and two
vane control connectors of front panel to indoor unit PCB. The position marking on PCB is as: Display connector : CN_DISPLAY Vane control connector: CN_VANE 1,2
9 Install the air inlet grille and Filter on the
panel.
- After inserting the edge of the grill into the panel body, close the door lock and press on the left, right, and center sections.
8 Close the cover for control box.
24
Air conditioner unit
Decorative panel
Fit the insulator (this part) and be careful for cool air leakage
Good example
Ceiling
board
Ceiling
board
Decorative panel
Air
Cool air leakage
(no good)
Bad example
Air conditioner unit
ENGLISH
TEST RUNNING
CAUTION
!
Install certainly the decorative panel. Cool air leakage causes sweating. Water drops fall.
TEST RUNNING
PRECAUTIONS IN TEST RUN
- The initial power supply must provide at least 90 % of the rated voltage. Otherwise, the air conditioner should not be operated.
CAUTION
!
• For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
• Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later automatically)
- To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETED
- After completing work, be sure to measure and record trial run properties, and store measured data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure.
- As to the structure and appearance, check following items.
* Is the circulation of air adequate? * Is the draining smooth? * Is the heat insulation complete
(refrigerant and drain piping)? * Is there any leakage of refrigerant? * Is the remote controller switch operated? * Is there any faulty wiring? * Are not terminal screws loosened?
M4......118 N.cm{12 kgf.cm}
M5......196 N.cm{20 kgf.cm}
M6......245 N.cm{25 kgf.cm}
M8......588 N.cm{60 kgf.cm}
Connection of power supply
- Connect the power supply cord to the independent power supply. Circuit breaker is required.
- Operate the unit for 15 minutes or more.
Evaluation of the performance
- Measure the temperature of the intake and discharge air.
- Ensure the difference between the intake temperature and the discharge one is more than 8 °C (Cooling) or reversely (Heating).
Thermometer
OPTIONAL OPERATION
Installer Setting - Test Run Mode
After installing the product, you must run a Test Run mode. For details related to this operation, refer to the product manual.
If pressing button long for 3 seconds, it
1
enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
- Please cancel the right and left of wind direction for RAC product.
Function Code Set
Setup figure '01' blinks at the lower part of
2
indication window.
OPTIONAL OPERATION
25
ENGLISH
Press button to start.
3
During the test run, pressing the below
4
button will exit the test run.
- Select operation, temperature up/down, wind flow control, wind direction, start/stop button.
OPTIONAL OPERATION
26
ENGLISH
Installer Setting - Setting Address of Central Control
It's the function to use for connecting central control. Please refer to central controller manual for the details
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more than 3 seconds for sure.
If entering into address setup mode by using
2
button, it indicates as picture below.
Set Group No. by pressing
3
button.(0~F)
Indoor No.
Group No
Function Code
Move to Indoor No. setting option
4
by pressing button.
Set Indoor No. by pressing
5
button.
Press button to save.
6
Pressing button will exit settings mode.
7
After setup, it automatically gets out of setup
mode if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
Installer Setting - Thermistor
OPTIONAL OPERATION
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If moving to room temperature perception sensor
2
selection menu by pressing button, it indicates as picture below.
Set Thermistor value by pressing
3
button. (01: Remote Controller, 02: Indoor, 03: 2TH)
27
ENGLISH
Function Code Thermistor setting
Press button to save.
4
Pressing button will exit settings mode. After setup, it automatically gets out of setup
5
mode if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
<Thermistor Table>
Temperature sensor selection Function 01 Remote controller Operation in remote controller temperature sensor 02 Indoor unit Operation in indoor unit temperature sensor
03 2 TH
Cooling
Heating
* The function of 2 TH has different operation characteristics according to the product.
Operation of higher temperature by comparing indoor unit's and wired remote controller’s temperature. (There are products that operate at a lower temperature.)
Operation of lower temperature by comparing indoor unit's and wired remote controller's temperature.
OPTIONAL OPERATION
28
ENGLISH
Installer Setting - Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceilingheight (only cassette model)
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If moving to ceiling height selection menu by
2
pressing button, it indicates as picture below.
Select ceiling height value by pressing
3
button. (01:Low, 02:Standard, 03:High, 04:Very high)
Function Code Thermistor setting
Press button to save.
4
Pressing button will exit settings mode. After setup, it automatically gets out of setup
5
mode if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
<Ceiling Height Selection Table>
Ceiling Height Level Description
01 Low Decrease the indoor airflow rate 1 step from standard level 02 Standard Set the indoor airflow rate as standard level 03 High Increase indoor airflow rate 1 step from standard level 04 Super high Increase indoor airflow rate 2 steps from standard level
* Ceiling height setting is available only for some products. * Ceiling height of ‘Super high’ function may not exist depending on the indoor unit. * Refer to the product manual for more details.
OPTIONAL OPERATION
Installer Setting - Group Setting
It is a function for settings in group control, or 2-remote controller control.
If pressing button long for 3 seconds, it
1
enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to
2
master/slave selection menu as picture below.
Select Master/ Slave by pressing
3
button. (00: Slave, 01: Master)
Function Code Master/Slave value
29
ENGLISH
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of setup mode
if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
Remote controller Function
Master
Slave
* Refer to the 'group control' part for details.
- When controlling in groups, basic operation settings, airflow strength weak/medium/strong, lock setting of the remote controller, time settings, and other functions may be restricted.
Indoor unit operates based on master remote controller at group control. (Master is set when delivering from the warehouse.)
Setup all remote controllers except one master remote controller to slave at group control
OPTIONAL OPERATION
30
ENGLISH
Installer Setting - Dry Contact Mode Setting
Dry contact function is the function that is possible to use only when dry contact equipment is separately purchased/setup.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to
2
remote controller dry contact mode setup menu as picture below.
Select Dry contact setting by
3
pressing button. (00 : Automatic, 01 : manual)
Function Code Dry Contact
Press button to save.
setting value
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of setup
mode if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
What is Dry Contact?
Like hotel card key and body perception sensor, it is the signal of the point of contact when using air-conditioner by interlocking.
- Please refer to dry contact manual for more details.
OPTIONAL OPERATION
Function Code conversion mode value
If pressing button long for 3 seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
1
Press button to exit or system will automatically exit after 25 seconds without any input.
5
Repeat pressing button to select Function code 12.
Ex) Fahrengeit Setting
2
Select Temperature unit mode by pressing button.
(00: Celsius, 01: Fahrenheit)
3
Press button to save or release.
4
Installer Setting-Celsius / Fahrenheit Switching
This function is used for switching the display between Celsius and Fahrenheit. (Optimized only for U.S.A)
31
ENGLISH
h Whenever press button in Fahrenheit mode, the temperature will increase/drop 2
degrees.
OPTIONAL OPERATION
32
ENGLISH
Installer Setting - Optional Function Setting
Setting feature for indoor unit when air cleaning / heater / humidifier / Up/down grill / Ventilation KIT / Auxiliary Heater is newly installed, or installed unit is removed.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If pressing button repeatedly, it moves to the
2
selected option function code as picture below.
Function
Plasma purification
Electric heater
Dehumidifier Elevation grill Ventilation kit
Auxiliary heater
Select existing condition of
3
each mode by pressing button.
(00: not installed, 01 : installed)
Function Code Existing condition
Press button to save.
4
Pressing button will exit settings mode.
5
After setup, it automatically gets out of setup
mode if there is no button input for 25 seconds.
When exiting without pressing set button, the
manipulated value is not reflected.
Code
20 21 22 23 24 25
OPTIONAL OPERATION
Installer Setting - Remote controller Mode Lock
This function is used to limit ‘operation-mode’ selection setting.
Press and hold button for
1
more than 3 seconds to enter the installer settings mode.
Move to the installer code number 42 in the
2
menu using button.
Select the remote control master/slave
3
using button.
33
ENGLISH
Code value for mode
code Description 42:00 42:01 42:02
Press button to save the setting.
lock setting
Doesn’t limit operation mode setting. User can setting to cooling mode only. User can setting to heating mode only.
Set value
4
Press button to exit.
5
h It can limit only wired remote controller button. other controllers can change operation mode.
(for example wireless remote controller and central controller)
HOW TO SET E.S.P?
34
ENGLISH
HOW TO SET E.S.P?
This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
If entering into ESP setup mode by using
2
button, it indicates as the picture below.
Function Code ESP value
ESP step
Function code, ESP code
ESP value
- When setting ESP value on the product without very weak wind or power wind function, it may not work.
Select ESP fan step by pressing
3
button. (01: very low, 02: low, 03: medium, 04: high, 05: power)
Move to ESP value setting by pressing
4
button. (It is 000 when delivering from the warehouse.)
Press button to setup ESP value.
5
(It is possible to setup ESP value from 1 to 255, and 1 is the smallest and 255 is the biggest.)
HOW TO SET E.S.P?
Function code, ESP code
ESP value
Press button to save.
7
Select ESP fan step again by using button and setup ESP value, as No. 4 and 5, that corresponds each wind flow
6
Press button to exit. After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
8
- Please be careful not to change the ESP value for each fan step.
- It does not work to setup ESP value for very low/power step for some products.
- ESP value is available for specific range belongs to the product.
35
ENGLISH
36
ENGLISH
A C
[
[
P I s P
C O
Loading...