Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by
authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
4-WAY CEILING CASSETTE
Original instruction
[Representative] LG Electronics Inc. EU Representative :
LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro,
Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
www.lg.com
P/NO : MFL67855527
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
MODEL DESIGNATION
Serial number
Indoor Unit / Outdoor Units
D
etailed product type only
for M- series models
AQ : Wall mounted Libero-R
SQ : Wall mounted Libero-E
AH* : ARTC OOL
A
S : Wall mounted /
ARTCOOL mirror
J : Wall mounted
A : ARTCO OL
T : Ceiling Cassette
B, M : Ceiling Concealed Duct
V : Ceiling Suspended & floor
Q : Console
P : Floor Standing
M : Indoor units only for
Multi systems
U : Indoor units only for
Single A systems
C : Common Indoor Unit for
Multi and Single CAC
N : Indoor Unit
U : Outdoor Unit
2
ENGLISH
MODEL DESIGNATION
Product information
- Product Name : Air conditioner
- Model Name :
- Additional Information : serial number is
refer to the barcode on the product.
- Max allowable pressure High side :
4.2 Mpa / Low side : 2.4 Mpa
- Refrigerant : R410A
Airborne Noise Emission
The A-weighted sound pressure emitted by
this product is below 70 dB.
** The noise level can vary depending on the
site.
The figures quoted are emission level and are
not necessarily safe working levels.
Whilst there is a correlation between the
emission and exposure levels, this cannot be
used reliably to determine whether or not
further precautions are required.
Factor that influence the actual level of
exposure of the workforce include the
characteristics of the work room and the other
sources of noise, i.e. the number of
equipment and other adjacent processes and
the length of time for which an operator
exposed to the noise. Also, the permissible
exposure level can vary from country to
country.
This information, however, will enable the
user of the equipment to make a better
evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas
concentration where immediate measures can
be taken without hurting human body when
refrigerant leaks in the air. The limiting
concentration shall be described in the unit of
3
kg/m
(Freon gas weight per unit air volume)
for facilitating calculation
Limiting concentration: 0.44kg/m3(R410A)
Calculate refrigerant concentration
n
Refrigerant
concentration
(kg/m3)
Total amount of replenished
refrigerant in refrigerant facility (kg)
=
Capacity of smallest room where
indoor unit is installed (m3)
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
3
ENGLISH
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE
APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
!
It can result in serious injury or death when the directions are
ignored
CAUTION
!
It can result in minor injury or product damage when the directions are ignored
WARNING
!
• Installation or repairs made by unqualified persons can result
in hazards to you and others.
• Installation MUST conform with local building codes or, in the
absence of local codes, with the Nation Electrical Code NFPA
70/ANSI C1-1003 or current edition and Canadian Electrical
Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use
by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage,
personal injury and/or death.
Installation
• Always perform grounding. - Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is
damaged. - Otherwise, it may cause a fire or electrical shock.
IMPORTANT SAFETY INSTRUCTIONS
• For installation of the product, always contact the service center or a professional installation agency. - Otherwise, it may
cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and
the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service
panel of the outdoor unit are not attached securely, it could
result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and electrical
shock.
• Do not keep or use flammable gases or combustibles near
the air conditioner. - Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not
damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will
cause a fire or electrical shock.
• Do not install the product at a place that there is concern of
falling down. - Otherwise, it may result in personal injury.
• Use caution when unpacking and installing. - Sharp edges
may cause injury.
5
ENGLISH
Operation
• Do not share the outlet with other appliances. - It will cause
an electric shock or a fire due to heat generation.
• Do not use the damaged power cord. - Otherwise, it may
cause a fire or electrical shock.
• Do not modify or extend the power cord randomly. Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during
operation. - Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes
from it. - Otherwise, it may cause electrical shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
IMPORTANT SAFETY INSTRUCTIONS
6
ENGLISH
• Take the power plug out if necessary, holding the head of the
plug and do not touch it with wet hands. - Otherwise, it may
cause a fire or electrical shock.
• Do not use the power cord near the heating tools. Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during
operation. - Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it
may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out. - It may cause
electric shock and damage.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through dropping of the
unit or falling down.
• Do not place a heavy object on the power cord. - Otherwise, it
may cause a fire or electrical shock.
• When the product is submerged into water, always contact
the service center. - Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. Otherwise, children may be seriously injured due to falling
down.
• Use a vacuum pump or inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or oxygen, and do
not use flammable gases. Otherwise, it may cause fire or
explosion. - There is the risk of death, injury, fire or explosion.
• Do not turn on the breaker or power under condition that front
panel, cabinet, top cover, control box cover are removed or
opened. - Otherwise, it may cause fire, electric shock, explosion or death.
CAUTION
!
Installation
• Install the drain hose to ensure that drain can be securely
IMPORTANT SAFETY INSTRUCTIONS
done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of
product. - Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product. - Otherwise, it
may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong
detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. Otherwise, it may cause the failure of appliance or an accident.
7
ENGLISH
TABLE OF CONTENTS
8
ENGLISH
TABLE OF CONTENTS
2MODEL DESIGNATION
9INSTALLATION PLACES
10THE INDOOR UNIT
INSTALLATION
11Indoor Unit Drain Piping
12Wiring Connection
14REMOTE CONTROLLER
INSTALLATION
16Wired remote controller installation
17INSTALLATION OF DEC-
ORATIVE
PANEL(ACCESSORY)
19TEST RUNNING
20OPTIONAL OPERATION
20Installer Setting -Test Run Mode
21Installer Setting - Setting Address of
Central Control
22Installer Setting -Thermistor
23Installer Setting -Ceiling Height
Selection
24Installer Setting-Group Setting
25Installer Setting-Dry Contact Mode
Setting
26Installer Setting-Celsius / Fahrenheit
Switching
27Installer Setting -Optional Function
Setting
28Installer Setting - Remote controller
Mode Lock
29HOW TO SET E.S.P?
INSTALLATION PLACES
Unit : mm
Ceiling
Ceiling Board
Ceiling Board
300 or more
Above 250
1000 or less
1000
or more
500 or
more
500 or
more
300 or less
Floor
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
Annexedsheet
Or
Packingcorrugated
cardboardonthe
bottom
INSTALLATION PLACES
- There should not be any heat source or steam near the unit.
- There should not be any obstacles to prevent the air circulation.
- A place where air circulation in the room will be good.
- A place where drainage can be easily obtained.
- A place where noise prevention is taken into consideration.
- Do not install the unit near the door way.
- Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
- The indoor unit must keep the maintenance space.
9
ENGLISH
* Please use an annexed sheet or the corru-
gated cardboard on the bottom of packing
as installation sheet.
* When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife
etc as a picture below.
THE INDOOR UNIT INSTALLATION
Level gauge
C
eiling
Ceiling board
Levelgauge
Ceiling
Ceilingboard
Unit:mm
Unit:mm
875(Ceiling opening)
787(Hanging bolt)
684
(Hanging bolt)
671
875(Ceiling opening)
840 Unit size
840 Unit size
TQ/TR Series
TP/TN/TM Series
585~660
517
461
517
585~660
523
570
570
319
Use the ventilation fan
for smoke-collecting
hood wi th sufficie nt
capacity.
Cooking table
Air conditioner
Take enough
distance
10
ENGLISH
THE INDOOR UNIT INSTALLATION
!
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level
gauge.
• During the installation, care should be
taken not to damage electric wires.
!
Avoid the following installation location.
1 Such places as restaurants and kitchen
where considerable amount of oil steam
and flour is generated. These may cause
heat exchange efficiency reduction, or
water drops, drain pump mal-function. In
these cases, take the following actions;
- Make sure that ventilation fan is enough
- Ensure enough distance from the cook-
CAUTION
NOTE
to cover all noxious gases from this
place.
ing room to install the air conditioner in
such a place where it may not suck oily
steam.
- Select and mark the position for fixing bolts
and piping hole.
- Decide the position for fixing bolts slightly
tilted to the drain direction after considering
the direction of drain hose.
- Drill the hole for anchor bolt on the wall.
2 Avoid installng air conditioner in such
places where cooking oil or iron powder is
generated.
3 Avoid places where inflammable gas is
generated.
4 Avoid place where noxious gas is generat-
ed.
5 Avoid places near high frequency genera-
tors.
THE INDOOR UNIT INSTALLATION
Set screw of
paper model (4 pieces)
Paper model
for installation
Ceiling
board
150mm
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board
along the outer edge of the
paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
Keep the length of 15~18mm
between the air conditioner
bottom surface and the ceiling
surface
Adjust the
same height
Wall
Indoor
Outdoor
5~7mm
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
The following parts is option.
① Hanging Bolt - W 3/8 or M10
② Nut - W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 70 hole-core drill.
CAUTION
!
Tighten the nut and bolt to prevent unit
falling.
Indoor Unit Drain Piping
- Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
- During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
- The outside diameter of the drain connection
on the indoor unit is 32mm.
11
ENGLISH
Piping material: Polyvinyl chloride pipe VP25 and pipe fittings
- Be sure to execute heat insulation on the
drain piping.
- Install the drain raising pipes at a right
angle to the indoor unit and no more than
300mm from the unit.
THE INDOOR UNIT INSTALLATION
Upwardroutingnotallowed
Indoor unit
700 or less
1 -1.5m
Clamp metal(attached)Drain hose(attached)
Drain raising pipe
300mm or less300mm or less300mm or less
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Indoor
unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant
piping
Remote
controller
cord
1
1
Connection
cord
between the
indoor unit and
the outdoor
unit
Control box cover
(On which the
Electric Wiring
Connection is put)
1/50~1/100 slope
Hanger
distance
Hanger Bracket
Max 700mm
Flexible drain hose
Insulation
Metal
clamp
Max 300mm
1~15m
12
ENGLISH
Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
Drain test
The air conditioner uses a drain pump to drain
water.
Use the following procedure to test the drain
pump operation:
- Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
- Feed water to the flexible drain hose and
check the piping for leakage.
- Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
- When the test is complete, connect the flexible drain hose to the drain port on the indoor
unit.
HEAT INSULATION
- Use the heat insulation material for the
refrigerant piping which has an excellent
heat-resistance (over 120°C).
- Precautions in high humidity circumstance:
This air conditioner has been tested according to the "KS Standard Conditions with Mist"
and confirmed that there is not any default.
However, if it is operated for a long time in
high humid atmosphere (dew point temperature: more than 23°C), water drops are liable
to fall. In this case, add heat insulation material according to the following procedure:
- Heat insulation material to be prepared...
Adiabatic EPDM or NBR with thickness 10 to
20mm.
- Stick glass wool on all air conditioners that
are located in ceiling atmosphere.
CAUTION
!
The supplied flexible drain hose should not
be curved, neither screwed. The curved or
screwed hose may cause a leakage of
water.
Wiring Connection
- Open the control box cover and connect the
Remote controller cord and Indoor power
wires.
- Remove the control box cover for electrical
connection between the indoor and outdoor
unit. (Remove screws ¿)
The connecting cable connected to the
indoor and outdoor unit should be complied with the following specifications
(This equipment shall be provided with a
cord set complying with the national regulation).
If the supply cord is damaged, it must be
replaced by a special cord or assembly
available from the manufacturer of its
service agent.
Precautions when laying power
wiring
Use round pressure terminals for connections
to the power terminal block.
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the
power wiring may cause abnormal heat.)
- When connecting wiring which is the same
thickness, do as shown in the figure below.
CAUTION
!
The Power cord connected to the unit
should be selected according to the following specifications.
- For wiring, use the designated power wire
and connect firmly, then secure to prevent
outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening
the terinal screws. A screwdriver with a
small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may
break them.
REMOTE CONTROLLER INSTALLATION
1
2
3
2
3
<Wire guide grooves>
14
ENGLISH
REMOTE CONTROLLER INSTALLATION
Please fix tightly using provided screw after placing remote controller setup
board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends.
Please set up remote controller board fit to the reclamation box if there is a reclamation box.
- Install the product so as not to make a gap with the wall side and to prevent shaking after the
installation.
Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing
remote controller cable guide groove.
* Remove guide groove with long nose.
① Reclamation to the surface of the wall
② Upper part guide groove
③ Right part guide groove
REMOTE CONTROLLER INSTALLATION
W
all
Side
W
all
Side
Wall
Side
Wall
Side
<Connecting order>
<Separating order>
Please check if connector is normally connected.
Connecting cable
Indoor
Unit side
WallSide
Wall
Side
WallSide
WallSide
<Connectingorder>
<Separatingorder>
Please fix remote controller upper part
into the setup board attached to the surface of the wall, as the picture below, and
then, connect with setup board by pressing lower part.
- Please connect not to make a gap at the remote
controller and setup board’s upper and lower, right
and left part.
- Before assembly with the installation board, arrange
the Cable not to interfere with circuit parts.
When separating remote controller from
setup board, as the picture below, after
inserting into the lower separating hole
using screw driver and then, spinning
clockwise, remote controller is separated.
- There are two separating holes. Please individually
separate one at a time.
- Please be careful not to damage the inside
components when separating.
Please connect indoor unit and remote controller using connection cable.
15
ENGLISH
Please use extension cable if the distance between wired remote controller
and indoor unit is more than 10m.
CAUTION
!
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in
the temperature sensor.)
Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the
remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
REMOTE CONTROLLER INSTALLATION
5feet
(1.5meters)
Direct
Sun ray contact area
no
no
no
yes
16
ENGLISH
Wired remote controller installation
Since the room temperature sensor is in the remote controller, the remote controller box should
be installed in a place away from direct sunlight, high humidity and direct supply of cold air to
maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor
in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the
remote controller LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
Front
grille
Front grille
Coner
cover
Front grille
Conercover
Hook
clip
Hook
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
17
ENGLISH
The decorative panel has its installation
direction.
Before installing the decorative panel,
always remove the paper template.
1 Remove the packing and take out air inlet
grille from front panel.
2 Remove the Corner covers of the panel.
4 Insert two screws on diagonal corners of
panel. Do not tighten the bolts completely.
(The fixing screws are included in the
indoor unit box.)
Check the alignment of panel with the ceiling. Height can be adjusted using hanging
bolts as shown in picture. Insert the other
two screws and tighten all screws completely.
3 Fit the panel on the unit by inserting hooks
as shown in picture.
5 Fit the corner covers.
INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
Screw
Screw
CN-VANE 1,2
CN-DISPLAY
Screw
CN-VANE1,2
CN-DISPLAY
Screw
CN-VANE1,2
CN-DISPLAY
Air conditioner
unit
Decorative panel
Fit the insulator (this part) and
be careful for cool air leakage
Good example
Ceiling
board
Ceiling
board
Decorative
panel
Air
Cool air leakage
(no good)
Bad example
Air conditioner unit
18
ENGLISH
6 Open two screws of control panel cover.
7 Connect one display connector and two
vane control connectors of front panel to
indoor unit PCB.
The position marking on PCB is as:
Display connector : CN-DISPLAY
Vane control connector: CN-VANE 1,2
9 Install the air inlet grille and Filter on the
panel.
CAUTION
!
Install certainly the decorative panel.
Cool air leakage causes sweating.
Water drops fall.
8 Close the cover for control box.
TEST RUNNING
Thermometer
TEST RUNNING
19
ENGLISH
PRECAUTIONS IN TEST RUN
- The initial power supply must provide at least
90% of the rated voltage.
Otherwise, the air conditioner should not be
operated.
CAUTION
!
• For test run, carry out the cooling operation firstly even during heating season.
If heating operation is carried out firstly,
it leads to the trouble of compressor.
Then attention must be paid.
• Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes
later automatically)
- To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN
INSTALLATION IS COMPLETED
- After completing work, be sure to measure
and record trial run properties, and store
measured data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow
out temperature, wind velocity, wind volume, voltage, current, presence of abnormal
vibration and noise, operating pressure, piping temperature, compressive pressure.
- As to the structure and appearance, check
following items.
* Is the circulation of air adequate?
* Is the draining smooth?
* Is the heat insulation complete
(refrigerant and drain piping)?
* Is there any leakage of refrigerant?
* Is the remote controller switch operated?
* Is there any faulty wiring?
* Are not terminal screws loosened?
Connection of power supply
- Connect the power supply cord to the independent power supply.
Circuit breaker is required.
- Operate the unit for 15 minutes or more.
Evaluation of the performance
- Measure the temperature of the intake and
discharge air.
- Ensure the difference between the intake
temperature and the discharge one is more
than 8°C (Cooling) or reversely (Heating).
M4......118N.cm{12kgf.cm}
M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm}
M8......588N.cm{60kgf.cm}
OPTIONAL OPERATION
Press button to start.
3
During the test run, pressing the below
button will exit the test run.
If pressing button long for 3 seconds, it
enters into remote controller setter setup
mode.
- If pressing once shortly, it enters into user
setup mode. Please press more than 3
seconds for sure.
- Please cancel the right and left of wind
direction for RAC product.
1
Setup figure '01' blinks at the lower part of
indication window.
2
Function Code Set
20
ENGLISH
OPTIONAL OPERATION
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
OPTIONAL OPERATION
Set Group No. by pressing
button.(0~F)
3
Move to Indoor No. setting option
by pressing button.
4
Set Indoor No. by pressing
button.
5
Press button to save.
6
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup
mode if there is no button input for 25
seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
7
If entering into address setup mode by using
button, it indicates as picture below.
2
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
Function Code
Group No
I
ndoor No.
Installer Setting - Setting Address of Central Control
It's the function to use for connecting central control.
Please refer to central controller manual for the details
21
ENGLISH
OPTIONAL OPERATION
Function CodeThermistor setting
Set Thermistor value by pressing
button. (01: Remote Controller,
02: Indoor, 03: 2TH)
3
Press button to save.
4
5
If moving to room temperature perception sensor
selection menu by pressing button, it
indicates as picture below.
2
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup
mode if there is no button input for 25
seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
22
ENGLISH
Installer Setting -Thermistor
<Thermistor Table>
Temperature sensor selectionFunction
01Remote controllerOperation in remote controller temperature sensor
02Indoor unitOperation in indoor unit temperature sensor
Cooling
032TH
Heating
* The function of 2TH has different operation characteristics according to the product.
Operation of higher temperature by comparing indoor unit's and wired
remote controller’s temperature.
(There are products that operate at a lower temperature.)
Operation of lower temperature by comparing indoor unit's and wired
remote controller's temperature.
OPTIONAL OPERATION
Function Code Thermistor setting
Select ceiling height value by pressing
button. (01:Low, 02:Standard,
03:High, 04Very high)
3
Press button to save.
4
5
If moving to ceiling height selection menu by
pressing button, it indicates as picture below.
2
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup
mode if there is no button input for 25
seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
Installer Setting -Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceilingheight (only cassette model)
23
ENGLISH
<Ceiling Height Selection Table>
Ceiling Height LevelDescription
01LowDecrease the indoor airflow rate 1 step from standard level
02Standard Set the indoor airflow rate as standard level
03High Increase indoor airflow rate 1 step from standard level
04Super highIncrease indoor airflow rate 2 steps from standard level
* Ceiling height setting is available only for some products.
* Ceiling height of ‘Super high’ function may not exist depending on the indoor unit.
* Refer to the product manual for more details.
OPTIONAL OPERATION
Function CodeMaster/Slave value
Select Master/ Slave by pressing
button.
(00: Slave, 01: Master)
3
Press button to save.
4
If pressing button long for 3 seconds, it
enters into remote controller setter setup
mode.
- If pressing once shortly, it enters into
user setup mode. Please press more than
3 seconds for sure.
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup mode
if there is no button input for 25 seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
1
If pressing button repeatedly, it moves to
master/slave selection menu as picture below.
2
5
24
ENGLISH
Installer Setting-Group Setting
It is a function for settings in group control, or 2-remote controller control.
Remote controller Function
Master
Slave
* Refer to the 'group control' part for details
- When controlling in groups, basic operation settings, airflow strength weak/medium/strong,
lock setting of the remote controller, time settings, and other functions may be restricted.
Indoor unit operates based on master remote controller at group control.
(Master is set when delivering from the warehouse.)
Setup all remote controllers except one master remote controller to slave
at group control
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
If pressing button repeatedly, it moves to
remote controller dry contact mode setup menu
as picture below.
2
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup
mode if there is no button input for 25
seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
5
Installer Setting-Dry Contact Mode Setting
Dry contact function is the function that is possible to use only when dry contact equipment is
separately purchased/setup.
25
ENGLISH
What is Dry Contact?
Like hotel card key and body perception sensor, it is the signal of the point of contact when using
air-conditioner by interlocking.
- Please refer to dry contact manual for more details.
OPTIONAL OPERATION
Function Codeconversion mode value
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode.
Please press more than 3 seconds for
sure.
1
Press button to exit or system
will automatically exit after 25
seconds without any input.
5
Repeat pressing button to select
Function code 12.
Ex) Fahrengeit Setting
2
Select Temperature unit mode by pressing button.
(00: Celsius, 01: Fahrenheit)
3
Press button to save or release.
4
26
ENGLISH
Installer Setting-Celsius / Fahrenheit Switching
This function is used for switching the display between Celsius and Fahrenheit.
(Optimized only for U.S.A)
h Whenever press button in Fahrenheit mode, the temperature will increase/drop 2
degrees.
OPTIONAL OPERATION
Function Code Existing condition
Select existing condition of
each mode by pressing
button.
(00: not installed,
01 : installed)
3
Press button to save.
4
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
If pressing button repeatedly, it moves to the
selected option function code as picture below.
2
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of setup
mode if there is no button input for 25
seconds.
❈ When exiting without pressing set button, the
manipulated value is not reflected.
5
Function
Plasma purification
Electric heater
Dehumidifier
Elevation grill
Ventilation kit
Auxiliary heater
Code
20
21
22
23
24
25
Installer Setting -Optional Function Setting
Setting feature for indoor unit when air cleaning / heater / humidifier / Up/down grill / Ventilation
KIT / Auxiliary Heater is newly installed, or installed unit is removed.
27
ENGLISH
OPTIONAL OPERATION
codeDescription
42:00
42:01
42:02
Doesn’t limit operation mode setting.
User can setting to cooling mode only.
User can setting to heating mode only.
Press and hold button for
more than 3 seconds to enter the
installer settings mode.
1
Press button to exit.
5
Move to the installer code number 42 in the
menu using button.
2
Select the remote control master/slave
using button.
3
Press button to save the setting.
4
Code value for mode
lock setting
Set value
28
ENGLISH
Installer Setting - Remote controller Mode Lock
This function is used to limit ‘operation-mode’ selection setting.
h It can limit only wired remote controller button. other controllers can change operation mode.
(for example wireless remote controller and central controller)
HOW TO SET E.S.P?
If entering into ESP setup mode by using
button, it indicates as the picture below.
2
Select ESP fan step by pressing
button. (01: very low, 02: low, 03:
medium, 04: high, 05: power)
3
Move to ESP value setting by pressing
button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is the
smallest and 255 is the biggest.)
5
Function code,
ESP code
ESP value
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
Function CodeESP value
ESP step
HOW TO SET E.S.P?
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
29
ENGLISH
- When setting ESP value on the product without very weak wind or power wind function, it may
not work.
HOW TO SET E.S.P?
Function code,
ESP code
ESP value
Press button to save.
7
Select ESP fan step again by using
button and setup ESP value, as No. 4 and 5,
that corresponds each wind flow
6
Press button to exit.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
8
30
ENGLISH
- Please be careful not to change the ESP value for each fan step.
- It does not work to setup ESP value for very low/power step for some products.
- ESP value is available for specific range belongs to the product.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.