<![endif]>ENGLISH
INSTALLATION MANUAL
AIR CONDITIONER
•Please read this installation manual completely before installing the product.
•Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
•Please retain this installation manual for future reference after reading it thoroughly.your set and retain it for future reference.
MODELS : ARWB Series
http://www.lghvac.com
www.lg.com
P/NO : MFL68100306
2
<![if ! IE]> <![endif]>ENGLISH |
TIPS FOR SAVING ENERGY |
|
|
|
Here are some tips that will help you minimize the power consumption |
|
when you use the air conditioner. You can use your air conditioner |
|
more efficiently by referring to the instructions below: |
|
|
•Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
•Block sunlight with blinds or curtains while you are operating the air conditioner.
•Keep doors or windows closed tightly while you are operating the air conditioner.
•Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
•Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
•Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
! WARNING
It can result in serious injury or death when the directions are ignored
! CAUTION
It can result in minor injury or product damage when the directions are ignored
! WARNING
•Installation or repairs made by unqualified persons can result in hazards to you and othersInstallation of all field wiring and components MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code 70 and the National Building Con-struction and Safety Code or Canadian Electrical code and National Building Code of Canada.
•Installation or repairs made by unqualified persons can result in hazards to you and others.
•The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
•Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
•Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
-If the power source capacity is inadequate or electric work is performed improperly, electric shock or fire may result.
•Ask the dealer or an authorized technician to install the air conditioner.
-Improper installation by the user may result in water leakage, electric shock, or fire.
•Always ground the product.
-There is risk of fire or electric shock.
•Always intstall a dedicated circuit and breaker.
-Improper wiring or installation may cause fire or electric shock.
•For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
-There is risk of fire, electric shock, explosion, or injury.
•Do not install, remove, or re-install the unit by yourself (customer).
-There is risk of fire, electric shock, explosion, or injury.
•Do not store or use flammable gas or combustibles near the air conditioner.
-There is risk of fire or failure of product.
•Use the correctly rated breaker or fuse.
-There is risk of fire or electric shock.
•Do not install the unit at the outdoors.
-Otherwise it may cause fire, electric shock and trouble.
•Do not install the product on a defective installation stand.
-It may cause injury, accident, or damage to the product.
•Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
-There is the risk of death, injury, fire or explosion.
•When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
-If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
•Do not reconstruct to change the settings of the protection devices.
-If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
•Ventilate before operating air conditioner when gas leaked out.
-It may cause explosion, fire, and burn.
•Securely install the cover of control box and the panel.
-If the cover and panel are not installed securely, dust or water may enter the outside unit and fire or electric shock may result.
•If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
-Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
•Do not damage or use an unspecified power cord.
-There is risk of fire, electric shock, explosion, or injury.
•Use a dedicated outlet for this appliance.
-There is risk of fire or electrical shock.
•Be cautious that water could not enter the product.
-There is risk of fire, electric shock, or product damage.
•Do not touch the power switch with wet hands.
-There is risk of fire, electric shock, explosion, or injury.
•When the product is soaked (flooded or submerged), contact an Authorized Service Center.
-There is risk of fire or electric shock.
•Be cautious not to touch the sharp edges when installing.
-It may cause injury.
•Take care to ensure that nobody could step on or fall onto the outside unit .
-This could result in personal injury and product damage.
•Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
-There is risk of physical injury, electric shock, or product failure.
! CAUTION
Installation
•Always check for gas (refrigerant) leakage after installation or repair of product.
-Low refrigerant levels may cause failure of product.
•Do not install the product where the noise or hot air from the outside unit could damage the neighborhoods.
-It may cause a problem for your neighbors.
•Keep level even when installing the product.
-To avoid vibration or water leakage.
•Do not install the unit where combustible gas may leak.
-If the gas leaks and accumulates around the unit, an explosion may result.
•Use power cables of sufficient current carrying capacity and rating.
-Cables that are too small may leak, generate heat, and cause a fire.
•Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
-There is risk of damage or loss of property.
•When installting the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Operation
•Do not use the air conditioner in special environments.
-Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
•Do not block the inlet or outlet.
-It may cause failure of appliance or accident.
•Make the connections securely so that the outside force of the cable may not be applied to the terminals.
-Inadequate connection and fastening may generate heat and cause a fire.
•Be sure the installation area does not deteriorate with age.
-If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or personal injury.
•Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
-A bad connection may cause water leakage.
•Be very careful about product transportation.
-Only one person should not carry the product if it weighs more than 20 kg.
-Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
-Do not touch the heat exchanger fins. Doing so may cut your fingers.
-When transporting the outside unit , suspending it at the specified positions on the unit base. Also support the outside unit at four points so that it cannot slip sideways.
•Safely dispose of the packing materials.
-Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
•Turn on the power at least 6 hours before starting operation.
-Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
•Do not touch any of the refrigerant piping during and after operation.
-It can cause a burn or frostbite.
•Do not operate the air conditioner with the panels or guards removed.
-Rotating, hot, or high-voltage parts can cause injuries.
•Do not directly turn off the main power switch after stopping operation.
-Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
•Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
•Use a firm stool or ladder when cleaning or maintaining the air conditioner.
-Be careful and avoid personal injury.
3
TABLE OF CONTENTS
2TIPS FOR SAVING ENERGY
2IMPORTANT SAFETY INSTRUCTIONS
4INSTALLATION PROCESS
4OUTSIDE UNITS INFORMATION
6ALTERNATIVE REFRIGERANT R410A
6SELECT THE BEST LOCATION
8INSTALLATION SPACE
8WATER CONTROL
9LIFTING METHOD
9INSTALLATION
12 REFRIGERANT PIPING INSTALLATION
15 DEVICE PROTECTION UNIT
15INSTALLATION OF WATER PIPE
16PIPE CONNECTIONS BETWEEN INDOOR AND OUTSIDE UNIT
24 ELECTRICAL WIRING
31 HR UNIT PCB
38 TEST RUN
42CAUTION FOR REFRIGERANT LEAK
43COOLING TOWER APPLIED METHOD
43 WATER SOLENOID VALVE CONTROL
<![endif]>ENGLISH
4
<![if ! IE]> <![endif]>ENGLISH |
INSTALLATION PROCESS |
||
Determination of division work |
Indicate clearly who will be responsible for switch setting. |
||
|
Preparation of contract drawings |
Make connection clearly between outside, indoor, |
||
remote controller and option. |
|||
|
|
||
|
|
|
Sleeve and insert work
Installation of indoor unit
Refrigerant piping work
Drain pipe work
Duct work
Heat insulation work
Electrical work
(connection circuits and drive circuits)
Take account of gradient
Outside unit foundation work
of drain piping
The foundation must be level even
Check model name to
make sure the fitting Installation of outside unit is made correctly
Avoid short circuits and ensure sufficient space is allowed for service
Special attention to dryness, cleanness and tightness
Adjust to downward gradient
Make sure airflow is sufficient
Make sure no gaps are left where the insulating materials are joined
Multiple core cable must not be used. (suitable cable should be selected)
Airtight test
Vacuum drying
Additional charge of refrigerant
Fit facing panels
Automatic addressing of indoor unit
Test run adjustment
Transfer to customer with explanation
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm2) there must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Refer to automatic addressing flowchart
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Explain the use of the system as clearly as possible to your customer an make sure all relevant documentation is in order
!CAUTION
•The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
•The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8Mpa(551.1psi).
•Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
OUTSIDE UNITS INFORMATION
!CAUTION
•Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
•A combination operation over 100% cause to reduce each indoor unit capacity.
Combination Ratio(50~200%)
Outside Unit Number |
Connection Ratio |
Single outside unit s |
200% |
Double outside unit s |
160% |
More than Triple outside unit s |
130% |
Notes: * We can guarantee the operation only within 130% Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below.
•If the operation of indoor unit is more than 130%, low airflow operation is recommended in all the indoor units.
•If the operation of indoor unit is more than 130%, additional refrigerant is needed according to the Aheadquarter guidance.
•Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Power Supply : 3Ø, 460V, 60Hz
Model Name : ARWB***DAS4
Unit |
|
|
|
|
|
1 Unit |
|
||
|
|
|
|
|
|
|
|
|
|
System Capacity |
|
HP |
8 |
|
|
10 |
12 |
||
|
TON |
6 |
|
|
|
8 |
10 |
||
|
|
|
|
|
|||||
Model |
Combination Unit |
ARWB072DAS4 |
|
|
ARWB096DAS4 |
ARWB121DAS4 |
|||
|
|
|
|
|
|
|
|
|
|
Independent Unit |
ARWB072DAS4 |
|
|
ARWB096DAS4 |
ARWB121DAS4 |
||||
|
|
|
|||||||
Refrigerant Precharged Amount |
kg |
5.8 |
|
|
5.8 |
5.8 |
|||
lbs |
12.8 |
|
|
12.8 |
12.8 |
||||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Maximum Connectable Number of Indoor Units |
13 |
|
|
16 |
20 |
||||
Net Weight |
|
kg |
127 x 1 |
|
|
127 x 1 |
127 x 1 |
||
|
|
|
|
|
|
|
|
|
|
|
lbs |
280 x 1 |
|
|
280 x 1 |
280 x 1 |
|||
|
|
|
|
||||||
Dimensions(WxHxD) |
mm |
755 × 997 × 500 |
|
|
755 × 997 × 500 |
755 × 997 × 500 |
|||
inch |
(29-23/32 x 39-1/4 x |
|
(29-23/32 x 39-1/4 x |
(29-23/32 x 39-1/4 x |
|||||
|
|
19-11/16) x 1 |
|
|
19-11/16) x 1 |
19-11/16) x 1 |
|||
|
|
|
|
|
|||||
|
Liquid Pipes |
mm(inch) |
9.52(3/8) |
|
|
9.52(3/8) |
12.7(1/2) |
||
Refrigerant |
|
|
|
|
|
|
|
|
|
Low Pressure |
|
|
|
|
|
|
|
|
|
Connecting |
mm(inch) |
22.7(7/8) |
|
|
22.7(7/8) |
25.4(1) |
|||
Pipes |
Gas Pipes |
|
|
|
|
|
|
|
|
High Pressure |
mm(inch) |
19.05(3/4) |
|
|
19.05(3/4) |
19.05(3/4) |
|||
|
|
|
|||||||
|
Gas Pipes |
|
|
|
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
||||
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
||||
Pipes |
|
|
|
|
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
PT20(3/4)(external thread) |
||||
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
10°C ~ 45°C |
|
|
10°C ~ 45°C |
10°C ~ 45°C |
||
Temp. range of |
|
(50°F ~ 113°F) |
|
|
(50°F ~ 113°F) |
(50°F ~ 113°F) |
|||
Circulation water |
Heating |
|
-5°C ~ 45°C |
|
|
-5°C ~ 45°C |
-5°C ~ 45°C |
||
|
|
|
(23°F ~ 113°F) |
|
|
(23°F ~ 113°F) |
(23°F ~ 113°F) |
||
|
|
|
|
|
|
|
|
|
|
Unit |
|
|
|
|
|
1 Unit |
|
||
System Capacity |
|
HP |
14 |
|
|
|
|
|
18 |
|
TON |
12 |
|
|
|
|
|
14 |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|||
Model |
Combination Unit |
ARWB144DAS4 |
|
|
ARWB168DAS4 |
||||
Independent Unit |
ARWB144DAS4 |
|
|
ARWB168DAS4 |
|||||
|
|
|
|||||||
Refrigerant Precharged Amount |
kg |
3 |
|
|
|
|
|
3 |
|
|
|
|
|
|
|
|
|
||
lbs |
6.6 |
|
|
|
|
|
6.6 |
||
|
|
|
|
|
|
|
|||
Maximum Connectable Number of Indoor Units |
23 |
|
|
|
|
|
29 |
||
|
|
|
|
|
|
|
|
|
|
Net Weight |
|
kg |
140 x 1 |
|
|
|
|
140 x 1 |
|
|
lbs |
309 x 1 |
|
|
|
|
309 x 1 |
||
|
|
|
|
|
|
||||
Dimensions(WxHxD) |
mm |
755 × 997 × 500 |
|
|
755 × 997 × 500 |
||||
|
|
|
|
|
|
|
|
||
inch |
(29-23/32 x 39-1/4 x 19-11/16) x 1 |
|
(29-23/32 x 39-1/4 x 19-11/16) x 1 |
||||||
|
|
|
|||||||
|
Liquid Pipes |
mm(inch) |
12.7(1/2) |
|
|
|
|
|
12.7(1/2) |
Refrigerant |
Low Pressure |
mm(inch) |
28.58(1-1/8) |
|
|
|
|
28.58(1-1/8) |
|
Connecting |
|
|
|
|
|||||
Gas Pipes |
|
|
|
|
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
19.05(3/4) |
|
|
|
|
|
19.05(3/4) |
|
|
|
|
|
|
||||
|
Gas Pipes |
|
|
|
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
||||
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
||||
Pipes |
|
|
|
|
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
|||||
|
|
||||||||
Temp. range of |
Cooling |
|
10°C ~ 45°C(50°F ~ 113°F) |
|
10°C ~ 45°C(50°F ~ 113°F) |
||||
Circulation water |
Heating |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
-5°C ~ 45°C(23°F ~ 113°F) |
||||
|
|
|
|
|
|
|
|
||
Unit |
|
|
|
|
|
1 Unit / 2 Unit |
|
||
System Capacity |
|
HP |
20 |
|
|
|
|
|
24 |
|
|
|
|
|
|
|
|
|
|
|
TON |
16 |
|
|
|
|
|
20 |
|
|
|
|
|
|
|
|
|||
|
Combination Unit |
ARWB192DAS4 |
|
|
ARWB240DAS4 |
||||
|
|
|
|
|
|
|
|||
Model |
Independent Unit |
ARWB192DAS4 |
|
|
ARWB144DAS4 |
||||
|
|
|
|
|
|
ARWB096DAS4 |
|||
|
|
|
|
|
|
|
|
||
Refrigerant Precharged Amount |
kg |
3 |
|
|
|
|
|
3.0+5.8 |
|
|
|
|
|
|
|
|
|
||
lbs |
6.6 |
|
|
|
|
|
6.6+12.8 |
||
|
|
|
|
|
|
|
|||
Maximum Connectable Number of Indoor Units |
32 |
|
|
|
|
|
39 |
||
Net Weight |
|
kg |
140 x 1 |
|
|
|
(140 x 1) + (127 x 1) |
||
|
|
|
|
|
|
|
|
|
|
|
lbs |
309 x 1 |
|
|
|
(309 x 1) + (280 x 1) |
|||
|
|
|
|
|
|||||
Dimensions(WxHxD) |
mm |
755 × 997 × 500 |
|
|
(755 × 997 × 500) x 2 |
||||
|
|
|
|
|
|
|
|
||
inch |
(29-23/32 x 39-1/4 x 19-11/16) x 1 |
|
(29-23/32 x 39-1/4 x 19-11/16) x 2 |
||||||
|
|
|
|||||||
|
Liquid Pipes |
mm(inch) |
12.7(1/2) |
|
|
|
|
|
19.05(3/4) |
Refrigerant |
Low Pressure |
mm(inch) |
28.58(1-1/8) |
|
|
|
|
34.9(1-3/8) |
|
Connecting |
|
|
|
|
|||||
Gas Pipes |
|
|
|
|
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
19.05(3/4) |
|
|
|
|
|
28.58(1-1/8) |
|
|
|
|
|
|
||||
|
Gas Pipes |
|
|
|
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
||||
|
|
|
|
|
|
|
|
|
|
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
||||
Pipes |
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
||||
Temp. range of |
Cooling |
|
10°C ~ 45°C(50°F ~ 113°F) |
|
10°C ~ 45°C(50°F ~ 113°F) |
||||
Circulation water |
Heating |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
-5°C ~ 45°C(23°F ~ 113°F) |
||||
|
|
|
|
|
|
|
|
|
|
Unit |
|
|
|
|
|
2 Unit |
|
|
||
System Capacity |
|
HP |
28 |
|
34 |
|
38 |
|||
|
|
|
|
|
|
|
|
|
||
|
TON |
24 |
|
28 |
|
32 |
||||
|
|
|
|
|||||||
|
Combination Unit |
|
ARWN288DAS4 |
|
ARWN336DAS4 |
|
ARWN384DAS4 |
|||
Model |
Independent Unit |
|
ARWN168DAS4 |
|
ARWN168DAS4 |
|
ARWN192DAS4 |
|||
|
|
|
|
|
|
|
|
|||
|
|
ARWN121DAS4 |
|
ARWN168DAS4 |
|
ARWN192DAS4 |
||||
|
|
|
|
|
|
|||||
Refrigerant Precharged Amount |
kg |
3.0 + 5.8 |
|
3.0+3.0 |
|
3.0+3.0 |
||||
lbs |
6.6+12.8 |
|
6.6+6.6 |
|
6.6+6.6 |
|||||
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
Maximum Connectable Number of Indoor Units |
45 |
|
55 |
|
61 |
|||||
Net Weight |
|
kg |
|
(140 x 1) + (127 x 1) |
|
140 x2 |
|
140 x2 |
||
|
|
|
|
|
|
|
|
|
||
|
lbs |
|
(309 x 1) + (280 x 1) |
|
309 x2 |
|
309 x2 |
|||
|
|
|
|
|
||||||
Dimensions(WxHxD) |
mm |
|
(755 × 997 × 500) x 2 |
|
(755 × 997 × 500) x 2 |
(755 × 997 × 500) x 2 |
||||
inch |
|
29-23/32 x 39-1/4 x |
|
(29-23/32 x 39-1/4 x |
29-23/32 x 39-1/4 x |
|||||
|
|
|
19-11/16) x 2 |
|
19-11/16) x 2 |
|
19-11/16) x 2 |
|||
|
|
|
|
|
|
|||||
|
Liquid Pipes |
mm(inch) |
19.05(3/4) |
|
19.05(3/4) |
|
19.05(3/4) |
|||
Refrigerant |
|
|
|
|
|
|
|
|
|
|
Low Pressure |
|
|
|
|
|
|
|
|
||
Connecting |
mm(inch) |
34.9(1-3/8) |
|
34.9(1-3/8) |
|
41.3(1-5/8) |
||||
Pipes |
Gas Pipes |
|
|
|
|
|
|
|
|
|
High Pressure |
mm(inch) |
28.58(1-1/8) |
|
28.58(1-1/8) |
|
34.9(1-3/8) |
||||
|
|
|
||||||||
|
Gas Pipes |
|
|
|
|
|
|
|
|
|
Water |
Inlet |
mm(inch) |
|
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
||||
|
|
|
|
|
|
|
|
|
||
Connecting |
Outlet |
mm(inch) |
|
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
||||
Pipes |
|
|||||||||
|
|
|
|
|
|
|
|
|
||
|
Drain Outlet |
mm(inch) |
|
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
PT20(3/4)(external thread) |
|||
|
|
|
|
|
|
|
|
|
|
|
|
Cooling |
|
|
10°C ~ 45°C |
|
10°C ~ 45°C |
|
10°C ~ 45°C |
||
Temp. range of |
|
|
(50°F ~ 113°F) |
|
(50°F ~ 113°F) |
|
(50°F ~ 113°F) |
|||
Circulation water |
Heating |
|
|
-5°C ~ 45°C |
|
-5°C ~ 45°C |
|
-5°C ~ 45°C |
||
|
|
|
|
(23°F ~ 113°F) |
|
(23°F ~ 113°F) |
|
(23°F ~ 113°F) |
||
|
|
|
|
|
|
|
|
|
|
|
Unit |
|
|
|
|
|
3 Unit |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
System Capacity |
|
HP |
|
46 |
|
|
|
|
54 |
|
|
TON |
|
40 |
|
|
|
|
48 |
||
|
|
|
|
|
|
|
||||
|
Combination Unit |
|
ARWN480DAS4 |
|
ARWN576DAS4 |
|||||
|
|
|
|
|
|
|
||||
Model |
|
|
|
ARWN192DAS4 |
|
ARWN192DAS4 |
||||
Independent Unit |
|
ARWN144DAS4 |
|
ARWN192DAS4 |
||||||
|
|
|
||||||||
|
|
|
|
ARWN144DAS4 |
|
ARWN192DAS4 |
||||
|
|
|
|
|
|
|
|
|
||
Refrigerant Precharged Amount |
kg |
|
3.0+3.0+3.0 |
|
|
|
3.0+3.0+3.0 |
|||
lbs |
|
6.6+6.6+6.6 |
|
|
|
6.6+6.6+6.6 |
||||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
||
Maximum Connectable Number of Indoor Units |
|
64 |
|
|
|
|
64 |
|||
Net Weight |
|
kg |
|
140 x3 |
|
|
|
140 x3 |
||
|
lbs |
|
309 x3 |
|
|
|
309 x3 |
|||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|||||
Dimensions(WxHxD) |
mm |
|
(755 × 997 × 500) x 3 |
(755 × 997 × 500) x 3 |
||||||
inch |
|
(29-23/32 x 39-1/4 x 19-11/16) x 3 |
(29-23/32 x 39-1/4 x 19-11/16) x 3 |
|||||||
|
|
|
||||||||
|
Liquid Pipes |
mm(inch) |
|
19.05(3/4) |
|
|
|
|
19.05(3/4) |
|
Refrigerant |
|
|
|
|
|
|
|
|
|
|
Low Pressure |
mm(inch) |
|
41.3(1-5/8) |
|
|
|
|
41.3(1-5/8) |
||
Connecting |
|
|
|
|
|
|||||
Gas Pipes |
|
|
|
|
|
|
|
|
||
Pipes |
High Pressure |
mm(inch) |
|
34.9(1-3/8) |
|
|
|
|
34.9(1-3/8) |
|
|
|
|
|
|
|
|||||
|
Gas Pipes |
|
|
|
|
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT 40+PT40(1-1/2)(Internal thread) |
PT 40+PT40(1-1/2)(Internal thread) |
||||||
|
|
|
|
|
|
|
|
|
||
Connecting |
Outlet |
mm(inch) |
PT 40+PT40(1-1/2)(Internal thread) |
PT 40+PT40(1-1/2)(Internal thread) |
||||||
Pipes |
||||||||||
|
|
|
|
|
|
|
|
|
||
|
Drain Outlet |
mm(inch) |
|
PT20(3/4)(external thread) |
PT20(3/4)(external thread) |
|||||
Temp. range of |
Cooling |
|
|
10°C ~ 45°C(50°F ~ 113°F) |
10°C ~ 45°C(50°F ~ 113°F) |
|||||
Circulation water |
Heating |
|
|
-5°C ~ 45°C(23°F ~ 113°F) |
-5°C ~ 45°C(23°F ~ 113°F) |
5
Power Supply : 3Ø, 208/230V, 60Hz
Model Name : ARWB***BAS4
Unit |
|
|
|
1 Unit |
|
System Capacity |
|
HP |
8 |
|
10 |
|
TON |
6 |
|
8 |
|
|
|
|
|||
|
|
|
|
|
|
Model |
Combination Unit |
ARWB072BAS4 |
|
ARWB096BAS4 |
|
Independent Unit |
ARWB072BAS4 |
|
ARWB096BAS4 |
||
|
|
||||
|
|
|
|
|
|
Refrigerant Precharged Amount |
kg |
5.8 |
|
5.8 |
|
lbs |
12.8 |
|
12.8 |
||
|
|
|
|||
Maximum Connectable Number of Indoor Units |
13 |
|
16 |
||
|
|
|
|
|
|
Net Weight |
|
kg |
127x1 |
|
127x1 |
|
lbs |
280x1 |
|
280x1 |
|
|
|
|
|||
Dimensions(WxHxD) |
mm |
755x997x500 |
|
755x997x500 |
|
|
|
|
|
||
inch |
(29-23/32x39-1/4x |
|
(29-23/32x39-1/4x |
||
|
|
19-11/16)x1 |
|
19-11/16)x1 |
|
|
|
|
|
||
|
Liquid Pipes |
mm(inch) |
9.52(3/8) |
|
9.52(3/8) |
Refrigerant |
|
|
|
|
|
Low Pressure |
|
|
|
|
|
Connecting |
mm(inch) |
22.7(7/8) |
|
22.7(7/8) |
|
Pipes |
Gas Pipes |
|
|
|
|
High Pressure |
mm(inch) |
19.05(3/4) |
|
19.05(3/4) |
|
|
|
||||
|
Gas Pipes |
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
Pipes |
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
|
|
|
||||
|
Cooling |
|
10°C ~ 45°C |
|
10°C ~ 45°C |
Temp. range of |
|
(50°F ~ 113°F) |
|
(50°F ~ 113°F) |
|
Circulation water |
Heating |
|
-5°C ~ 45°C |
|
-5°C ~ 45°C |
|
|
|
(23°F ~ 113°F) |
|
(23°F ~ 113°F) |
|
|
|
|
|
|
Unit |
|
|
|
1 Unit |
|
System Capacity |
|
HP |
12 |
|
14 |
|
|
|
|
|
|
|
TON |
10 |
|
12 |
|
|
|
|
|||
Model |
Combination Unit |
ARWB121BAS4 |
|
ARWB144BAS4 |
|
Independent Unit |
ARWB121BAS4 |
|
ARWB144BAS4 |
||
|
|
||||
|
|
|
|
|
|
Refrigerant Precharged Amount |
kg |
5.8 |
|
5.8 |
|
lbs |
12.8 |
|
12.8 |
||
|
|
|
|||
Maximum Connectable Number of Indoor Units |
20 |
|
23 |
||
|
|
|
|
|
|
Net Weight |
|
kg |
127x1 |
|
127x1 |
|
lbs |
280x1 |
|
280x1 |
|
|
|
|
|||
|
|
|
|
|
|
Dimensions(WxHxD) |
mm |
755x997x500 |
|
755x997x500 |
|
inch |
(29-23/32x39-1/4x19-11/16)x1 |
|
(29-23/32x39-1/4x19-11/16)x1 |
||
|
|
|
|||
|
Liquid Pipes |
mm(inch) |
12.7(1/2) |
|
12.7(1/2) |
Refrigerant |
|
|
|
|
|
Low Pressure |
mm(inch) |
25.4(1) |
|
28.58(1-1/8) |
|
Connecting |
|
||||
Gas Pipes |
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
19.05(3/4) |
|
19.05(3/4) |
|
|
||||
|
Gas Pipes |
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
|
|
|
|
|
|
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
Pipes |
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
|
|
||||
Temp. range of |
Cooling |
|
10°C ~ 45°C(50°F ~ 113°F) |
|
10°C ~ 45°C(50°F ~ 113°F) |
Circulation water |
Heating |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
|
|
|
|
|
Unit |
|
|
|
2 Unit |
|
System Capacity |
|
HP |
18 |
|
20 |
|
|
|
|
|
|
|
TON |
14 |
|
16 |
|
|
|
|
|||
|
Combination Unit |
ARWB168BAS4 |
|
ARWB192BAS4 |
|
Model |
Independent Unit |
ARWB096BAS4 |
|
ARWB121BAS4 |
|
|
|
|
|
||
|
ARWB072BAS4 |
|
ARWB072BAS4 |
||
|
|
|
|
||
Refrigerant Precharged Amount |
kg |
5.8+5.8 |
|
5.8+5.8 |
|
|
|
|
|
||
lbs |
12.8+12.8 |
|
12.8+12.8 |
||
|
|
|
|||
Maximum Connectable Number of Indoor Units |
29 |
|
32 |
||
Net Weight |
|
kg |
127x2 |
|
127x2 |
|
|
|
|
|
|
|
lbs |
280x2 |
|
280x2 |
|
|
|
|
|||
Dimensions(WxHxD) |
mm |
(755x997x500)x2 |
|
(755x997x500)x2 |
|
inch |
(29-23/32x39-1/4x19-11/16)x2 |
|
(29-23/32x39-1/4x19-11/16)x2 |
||
|
|
|
|||
|
|
|
|
|
|
|
Liquid Pipes |
mm(inch) |
12.7(1/2) |
|
12.7(1/2) |
Refrigerant |
Low Pressure |
mm(inch) |
28.58(1-1/8) |
|
28.58(1-1/8) |
Connecting |
|
||||
Gas Pipes |
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
19.05(3/4) |
|
19.05(3/4) |
|
|
||||
|
Gas Pipes |
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
|
PT40(1-1/2)(Internal thread) |
Pipes |
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
|
PT20(3/4)(external thread) |
|
|
|
||||
Temp. range of |
Cooling |
|
10°C ~ 45°C(50°F ~ 113°F) |
|
10°C ~ 45°C(50°F ~ 113°F) |
Circulation water |
Heating |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
-5°C ~ 45°C(23°F ~ 113°F) |
|
|
|
|
|
|
<![endif]>ENGLISH
6
<![if ! IE]> <![endif]>ENGLISH |
|
|
|
|
|
|
|
Unit |
|
|
2 Unit |
||
|
System Capacity |
|
HP |
22 |
28 |
|
|
|
|
|
|
||
|
|
TON |
18 |
24 |
||
|
|
|
||||
|
|
Combination Unit |
ARWB216BAS4 |
ARWB288BAS4 |
||
|
Model |
Independent Unit |
ARWB144BAS4 |
ARWB144BAS4 |
||
|
|
|
|
|||
|
|
ARWB072BAS4 |
ARWB144BAS4 |
|||
|
|
|
|
|||
|
|
Refrigerant Precharged Amount |
kg |
5.8+5.8 |
5.8+5.8 |
|
|
|
lbs |
12.8+12.8 |
12.8+12.8 |
||
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
Maximum Connectable Number of Indoor Units |
35 |
45 |
||
|
|
Net Weight |
|
kg |
127x2 |
127x2 |
|
|
|
|
|
|
|
|
|
|
lbs |
280x2 |
280x2 |
|
|
|
|
|
|||
|
|
Dimensions(WxHxD) |
mm |
(755x997x500)x2 |
(755x997x500)x2 |
|
|
|
inch |
(29-23/32x39-1/4x19-11/16)x2 |
(29-23/32x39-1/4x19-11/16)x2 |
||
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Liquid Pipes |
mm(inch) |
19.05(3/4) |
19.05(3/4) |
|
|
Refrigerant |
Low Pressure |
mm(inch) |
34.9(1-3/8) |
34.9(1-3/8) |
|
|
Connecting |
||||
|
|
Gas Pipes |
|
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
28.58(1-1/8)) |
28.58(1-1/8)) |
|
|
|
||||
|
|
|
Gas Pipes |
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
|
|
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
|
|
Pipes |
|
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
PT20(3/4)(external thread) |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
Cooling |
|
10°C ~ 45°C |
10°C ~ 45°C |
|
|
Temp. range of |
|
(50°F ~ 113°F) |
(50°F ~ 113°F) |
|
|
|
Circulation water |
Heating |
|
-5°C ~ 45°C |
-5°C ~ 45°C |
|
|
|
|
|
(23°F ~ 113°F) |
(23°F ~ 113°F) |
|
|
|
|
|
|
|
|
|
Unit |
|
|
3 Unit |
|
|
|
System Capacity |
|
HP |
36 |
42 |
|
|
|
TON |
30 |
36 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Combination Unit |
ARWB360BAS4 |
ARWB432BAS4 |
|
|
|
Model |
|
|
ARWB144BAS4 |
ARWB144BAS4 |
|
|
Independent Unit |
|
|
||
|
|
ARWB144BAS4 |
ARWB144BAS4 |
|||
|
|
|
||||
|
|
|
|
|
ARWB072BAS4 |
ARWB144BAS4 |
|
|
Refrigerant Precharged Amount |
kg |
5.8+5.8+5.8 |
5.8+5.8+5.8 |
|
|
|
|
|
|
||
|
|
lbs |
12.8+12.8+12.8 |
12.8+12.8+12.8 |
||
|
|
|
|
|||
|
|
Maximum Connectable Number of Indoor Units |
58 |
64 |
||
|
|
Net Weight |
|
kg |
127x3 |
127x3 |
|
|
|
|
|
|
|
|
|
|
lbs |
280x3 |
280x3 |
|
|
|
|
|
|||
|
|
Dimensions(WxHxD) |
mm |
(755x997x500)x3 |
(755x997x500)x3 |
|
|
|
|
|
|
||
|
|
inch |
(29-23/32x39-1/4x19-11/16)x3 |
(29-23/32x39-1/4x19-11/16)x3 |
||
|
|
|
|
|||
|
|
|
Liquid Pipes |
mm(inch) |
19.05(3/4) |
19.05(3/4) |
|
|
Refrigerant |
Low Pressure |
mm(inch) |
41.3(1-5/8) |
41.3(1-5/8) |
|
|
Connecting |
||||
|
|
Gas Pipes |
|
|
|
|
|
|
Pipes |
High Pressure |
mm(inch) |
34.9(1-3/8) |
34.9(1-3/8) |
|
|
|
||||
|
|
|
Gas Pipes |
|
|
|
|
|
Water |
Inlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
|
|
Connecting |
Outlet |
mm(inch) |
PT40(1-1/2)(Internal thread) |
PT40(1-1/2)(Internal thread) |
|
|
Pipes |
|
|
|
|
|
|
Drain Outlet |
mm(inch) |
PT20(3/4)(external thread) |
PT20(3/4)(external thread) |
|
|
|
|
||||
|
|
Temp. range of |
Cooling |
|
10°C ~ 45°C(50°F ~ 113°F) |
10°C ~ 45°C(50°F ~ 113°F) |
|
|
Circulation water |
Heating |
|
-5°C ~ 45°C(23°F ~ 113°F) |
-5°C ~ 45°C(23°F ~ 113°F) |
|
|
|
|
|
|
|
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
These days the developed countries have approved it as the environ- ment-friendly refrigerant and encouraged to use it widely to prevent environment pollution.
!CAUTION
•The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8Mpa(551.1psi).
•Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
•Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
•For high-pressure refrigerant, any unapproved pipe must not be used.
•Do not heat pipes more than necessary to prevent them from softening.
•Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
SELECT THE BEST LOCATION
Select space for installing outside unit , which will meet the following conditions:
•With strength which bears weight of unit
•With space for air passage and service work
Don't install the unit at the space where generation, inflow, stagnation, and leak of combustible gas is expected.
•Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
•Location with no leakage of combustible gas
•Recommend the outside unit to be installed within 0~40°C(32~104°F).
•Location with installation or service work space (Refer to required space)
•Do not use the outside unit under any special environment where oil, steam and sulfuric gas exist.
•Install in a separate machine room not exposed to external air
-Establish an anti-freeze plan for the water supply when the product is stopped during the winter.
-Install the product so that the noise from the machine room is not transferred outsides
•The floor of the machine room must be water proof.
•Drainage must be installed in the machine room to process the water drainage.
•Install a floor slope to make the drainage smooth.
•Avoid installing the outside unit in the location with following conditions.
•Location where corrosive gas such as acidic gas is generated. (It may cause the refrigerant leakage by corrosion of the pipe.)
•Location where electromagnetic waves happen.
(It may cause the abnormal operation by control parts disorder.)
•Location to be able to leak the combustible gas
•Location with carbon fiber or combustible dust.
•Location with the combustible material like thinner or gasoline. (It may cause a fire by leaking the gas near the product.)
!CAUTION
•Do not install Multi V water outdoors. Always install indoor like machine room.
•Inverter product may generate electric noise. Keep the body from computer, stereo etc. at enough distance. Specially leave space from indoor remote controller to shoes electric devices at the above 3m in weak electric wave area. Insert the power cable and other wire into separate conduit.
Select installation location of the HR unit suitable for following conditions
-Avoid a place where rain may enter since the HR unit is for indoor.
-Sufficient service space must be obtained.
-Refrigerant pipe must not exceed limited length.
-Avoid a place subject to a strong radiation heat from other heat source.
-Avoid a place where oil spattering, vapor spray or high frequency electric noise is expected.
-Install the unit at a place in which it is not affected by operation noise. (Installation within cell such as meeting room etc. may disturb business due to noise.)
-Place where refrigerant piping, drain piping and electrical wiring works are easy.
481(18-15/16)
7
<![if ! IE]> <![endif]>345(13-19/32) |
1 |
2 |
3 |
<![endif]>450(17-23/32)
Inspection door (servicing space)
450(17-23/32)
<![if ! IE]> <![endif]>218(8-19/32) |
|
<![if ! IE]> <![endif]>182(7-5/32) |
174(6-27/32) |
453(17-27/32) |
174(6-27/32) |
100(3-15/16) more |
(Serviceing space) |
300(11-13/16) |
300(11-13/16) |
more |
more |
|
7 |
100(3-15/16) more |
<![if ! IE]> <![endif]>ENGLISH |
(Serviceing space) |
|
300(11-13/16) |
|
450(17-23/32) |
more |
more |
(Servicing space)
124(4-7/8) 1/32)-128(5 6
61(2-13/32) 419(16-1/2)
(Servicing space)
4 |
5 |
|
<![if ! IE]> <![endif]>60(2-3/8) |
137(5-13/32) |
|
|
<![if ! IE]> <![endif]>30(13/16)- |
|
|
|
(unit: mm(inch)) |
|
|
|
|
|
|
No. |
Part Name |
Description |
||
|
|
|||
PRHR031A/PRHR041A |
PRHR021A |
|||
|
|
|||
|
|
|
|
|
1 |
Low pressure |
Ø28.58(1-1/8) Brazing con- |
Ø22.2(7/8) Brazing connec- |
|
Gas pipe con- |
||||
nection |
tion |
|||
|
nection port |
|||
|
|
|
||
|
High pressure |
Ø22.2(7/8) Brazing connec- |
Ø19.05(3/4) Brazing con- |
|
2 |
Gas pipe con- |
|||
tion |
nection |
|||
|
nection port |
|||
|
|
|
||
|
|
Ø15.88(5/8) Brazing con- |
|
|
3 |
Liquid pipe con- |
nection (PRHR041A) |
Ø9.52(3/8) Brazing connec- |
|
nection port |
Ø12.7(1/2) Brazing connec- |
tion |
||
|
|
tion (PRHR031A) |
|
|
|
|
|
|
|
|
Indoor unit Gas |
Ø15.88(5/8) Brazing con- |
Ø15.88(5/8) Brazing con- |
|
4 |
pipe connection |
|||
nection |
nection |
|||
|
port |
|
|
|
|
Indoor unit Liq- |
Ø9.52(3/8) Brazing connec- |
Ø9.52(3/8) Brazing connec- |
|
5 |
uid pipe connec- |
|||
tion |
tion |
|||
|
tion port |
|
|
|
6 |
Control box |
- |
- |
|
|
|
|
|
|
7 |
Hanger metal |
M10 or M8 |
M10 or M8 |
|
|
|
|
|
!NOTE
•Be sure to install the inspection door at the control box side.
•If reducers are used, servicing space must be increased equal to reducer's dimension.
(Servicing space) |
(Servicing space) |
8
<![if ! IE]> <![endif]>ENGLISH |
INSTALLATION SPACE |
|
|
|
Individual Installation |
|
During the installation of the unit, consider service, inlet, and outlet |
|
acquire the minimum space as shown in the figures below. |
: Service area
|
<![if ! IE]> <![endif]>20 |
<![if ! IE]> <![endif]>(25/32) |
|
Product |
<![if ! IE]> <![endif]>500(19-11/16) |
Water pipe |
(Outside unit) |
|
|
||
installation |
|
|
|
|
|
space |
|
<![if ! IE]> <![endif]>600(23-5/8) |
|
Service area |
|
|
(Front) |
|
|
|
|
|
350(13-25/32) |
|
20(25/32) |
755(29-23/32) 100(3-15/16) |
|
|
<Top View> |
|
(Unit: mm(inch))
|
<![if ! IE]> <![endif]>100(3-15/16) |
|
|
<![if ! IE]> <![endif]>997(39-1/4) |
|
H-Beam Support |
<![if ! IE]> <![endif]>100(3-15/16) |
|
<Front View> |
||
|
Collective / Continuous Installation
Space required for collective installation and continuous installation as shown below considering passage for air and people.
: Service area
|
|
|
(Unit: mm(inch)) |
|
|
|
|
|
<![if ! IE]> <![endif]>11/16)-500(19 (25/32) |
|
|
|
|
<![if ! IE]> <![endif]>20 |
Product |
Product |
Product |
Product |
|
(Outside unit) |
(Outside unit) |
(Outside unit) |
(Outside unit) |
|
|
Service area |
Service area |
Service area |
Service area |
<![if ! IE]> <![endif]>-5/8) |
|
<![if ! IE]> <![endif]>600(23 |
||||
|
(Front) |
(Front) |
(Front) |
(Front) |
|
|
|
|
|
|
|
|
350(13-25/32) |
350(13-25/32) |
350(13-25/32) |
350(13-25/32) |
|
20 |
755(29-23/32) |
100(3-15/16) 755(29-23/32) |
100(3-15/16) 755(29-23/32) |
100(3-15/16) 755(29-23/32) |
100(3-15/16) |
(25/32) |
|
<Top view> |
|
|
|
|
|
|
|
|
*In case of the water pipe passing side product, please make sufficient service place to avoid occurring between water pipe and product side.
Two Layer Installation
Space required for two layer installation as shown below considering passage for air and people.
:
Service area
(Unit: mm(inch))
100(3-15/16) |
997(39-1/4) |
100(3-15/16) |
100(3-15/16) |
997(39-1/4)
100(3-15/16)
H-Beam Support
<Front View>
WATER CONTROL
Water control
•Keep the water temperature between 10~45°C(50~113°F). Other it may cause the breakdown.
-Standard water supply temperature is 30°C(86°F) for Cooling and 20°C(68°F) for heating.
•Properly control the water velocity. Otherwise it may cause the noise, pipe vibration or pipe contraction, expansion according to the temperature. Use the same water pipe size connected with the product or more.
•Refer to the water source pipe diameter and water velocity table below. As the water velocity is fast, air bubble will increase.
Diameter [mm(inch)] |
Velocity range (m/s) |
|
|
< 50(1-31/32) |
0.6 ~ 1.2 |
|
|
50(1-31/32) ~ 100(5-7/8) |
1.2 ~ 2.1 |
|
|
100100(5-7/8) < |
2.1 ~ 2.7 |
|
|
•Be careful of the water purity control. Otherwise it may cause the breakdown due to water pipe corrosion.
(Refer to 'Standard Table for Water Purity Control')
•In case the water temperature is above 40°C(104°F), it is good to prevent the corrosion by adding the anticorrosive agent.
•Install the pipe, valve and gauge sensor in the space where it is easy to maintain. Install the water valve in the low position for drain, if required.
•Be careful not to let air in. If so, the water velocity will be unstable in the circulation, pump efficiency will also decrease and may cause the piping vibration. Therefore, install the air purge where it may generate the air.
•Choose the following anti freezing methods. Otherwise, it will be dangerous for the pipe to break in the winter.
-Circulate the water with the pump before dropping the temperature.
-Keep the normal temperature by boiler.
-When the cooling tower is not operated for a long time, drain the water in the cooling tower.
-Use an anti-freeze. (For using an anti freeze, change the DIP switch on main PCB in outside unit.)
-Refer to the additive amount about freezing temperature as in the table given below.
Anti freeze type |
Minimum temperature for anti freezing [°C(°F)] |
||||||
|
|
|
|
|
|
||
0 |
-5(23) |
-10(14) |
-15(5) |
-20(-4) |
-25(-13) |
||
|
|||||||
|
|
|
|
|
|
|
|
Ethylene glycol (%) |
0 |
12 |
20 |
30 |
- |
- |
|
|
|
|
|
|
|
|
|
Propylene glycol (%) |
0 |
17 |
25 |
33 |
- |
- |
|
|
|
|
|
|
|
|
|
Methanol (%) |
0 |
6 |
12 |
16 |
24 |
30 |
|
|
|
|
|
|
|
|
•In addition to anti freeze, it may cause the change of the pressure in the water system and the low performance of the product.
•Make sure to use the closed cooling type tower.
When applying the open type cooling tower, use a 2nd heat exchanger to make the water supply system a closed type system.
Standard table for water purity control
The water may contain many foreign substances and hence may influence the performance and lifetime of the product due to the corrosion of the condenser and water pipe. (Use water source that complies with the below standard table for water purity control.)
If you use water supply other than the tap water to supply the water for the cooling tower, you must do a water quality inspection.
•If you use the closed cooling tower, the water quality must be controlled in accordance with the following standard table.
If you do not control the water quality in accordance with the following standard water quality table, it can cause performance deterioration to the air conditioner and severe problem to the product
Items |
Closed type |
|
Effect |
||
|
Circulating water |
Supplemented water |
Corrosion |
|
Scale |
|
Basic Item |
|
|
|
|
pH(25C) |
7.0~8.0 |
7.0~8.0 |
O |
|
O |
Conductivity[25C](mS/m) |
Below 30 |
Below 30 |
O |
|
O |
Chlorine ion(mg CI-/l) |
Below 50 |
Below 50 |
O |
|
- |
Sulfuric acid ion(mg SO24-/l) |
Below 50 |
Below 50 |
O |
|
O |
Acid demand[pH 4.8] (mg SiO2/l) |
Below 50 |
Below 50 |
- |
|
O |
Total hardness(mg SiO2/l) |
Below 70 |
Below 70 |
- |
|
O |
Ca hardness(mg CaCO3/l) |
Below 50 |
Below 50 |
- |
|
O |
Ion silica(mg SiO2/l) |
Below 30 |
Below 30 |
- |
|
O |
|
Reference Item |
|
|
|
|
Fe(mg Fe/l) |
Below 1.0 |
Below 0.3 |
O |
|
O |
Copper(mg Cu/l) |
Below 1.0 |
Below 0.1 |
O |
|
- |
Sulfuric acid ion(mg S2/l) |
Must not be detected |
Must not be detected |
O |
|
- |
+ |
Below 0.3 |
Below 0.1 |
O |
|
- |
Ammonium ion(mg NH4/l) |
|
||||
Residual chlorine(mg Cl/l) |
Below 0.25 |
Below 0.3 |
O |
|
- |
Free carbon dioxide(mg CO2/l) |
Below 0.4 |
Below 4.0 |
O |
|
- |
Stability index |
- |
- |
O |
|
O |
Reference
•The "O" mark for corrosion and scale means that there is possibility of occurrence.
•When the water temperature is 40°C(104°F) or above or when uncoated iron is exposed to the water, it can result in corrosion. Therefore adding anti-corrosion agent or removing the air can be very effective.
•In case of using the closed type cooling tower, the cooling water and supplementing water must satisfy the water quality criteria of closed type system in the table.
•Supplementing water and supplied water must be supplied with tap water, industrial water and underground water excluding filtered water, neutral water, soft water etc.
•15 items in the table are general causes of corrosion and scale.
LIFTING METHOD
-When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at the front and rear.
-Always lift the unit with ropes attached at fours points so that impact is not applied to the unit.
-Attach the ropes to the unit at an angle of 40° or less
Sub line
A 40° or less
B Rope supporter
! CAUTION
Be very careful while carrying the product.
•Do not have only one person carry product if it is more than 20 kg(44lbs).
•PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
•Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
•When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
•Use 2 belts of at least 8m(26.2ft) long.
•Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
•Hoist the unit making sure it is being lifted at its center of gravity.
9
INSTALLATION |
<![if ! IE]> <![endif]>ENGLISH |
|
|
• Install at places where it can endure the weight and vibration/noise |
|
of the outside unit . |
|
• The outside unit supports at the bottom shall have width of at least |
|
100mm(3-15/16inch) under the Unit’s legs before being fixed. |
|
|
|
• The outside unit supports should have minimum height of 200mm |
|
(7-7/8inch). |
|
• Anchor bolts must be inserted at least 75mm(2-15/16 inch). |
|
|
100mm |
|
least |
inch) |
|
At |
|
|
|
-15/16 |
|
(3 |
|
|
100mm |
|
least |
inch) |
|
At |
|
|
|
-15/16 |
|
(3 |
|
|
100mm |
|
least |
inch) |
|
At |
|
|
|
-15/16 |
|
(3 |
|
|
100mm |
|
||
|
|
|||
least |
) |
|||
inch |
||||
At |
|
|||
|
-15/16 |
|
||
(3 |
|
|
The location of the Anchor bolts
Unit: mm(inch)
|
|
755(29-23/32) |
|
|
62(2-7/16) |
631(24-27/32) |
62(2-7/16) |
<![if ! IE]> <![endif]>500(19-11/16) |
<![if ! IE]> <![endif]>472(18-37/64) |
|
|
The location of anchor bolt
Foundation for Installation
•Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
•Use the H-beam support as a base support
•Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm(7-7/8inch)).
At least 200mm (7-7/8inch)
10
<![if ! IE]> <![endif]>ENGLISH |
The corner part must be fixed firmly. Otherwise, the support for the |
||||
|
|||||
|
installation may be bent. |
|
|
|
|
|
Get and use M10 Anchor bolt. |
|
|
|
|
|
Put Cushion Pad between the outside unit |
and ground support for |
|||
|
the vibration protection in wide area. |
|
|
|
|
|
Space for pipes and wiring (Pipes and wirings for bottom side) |
||||
|
H-beam support |
|
|
|
|
|
Concrete support |
|
|
|
Unit: mm(inch) |
|
<![if ! IE]> <![endif]>100(3-15/16) |
<![if ! IE]> <![endif]>75(2-61/64) |
<![if ! IE]> <![endif]>200(7-7/8) |
<![if ! IE]> <![endif]>75(2-61/64) |
<![if ! IE]> <![endif]>200(7-7/8) |
!WARNING
•Install where it can sufficiently support the weight of the outside unit .
If the support strength is not enough, the outside unit may drop and hurt people.
•Install where the outside unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outside unit may fall and hurt people.
•Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the water flowing out of the outside unit in operation), and the passages of the pipe and wiring, when making the ground support.
•Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.
!CAUTION
•Be sure to remove the Pallet(Wood Support) of the bottom side of the outside unit Base Pan before fixing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
•Be sure to remove the Pallet(Wood Support) of the bottom side of the outside unit before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.
Pallet(Wood Support)
- Remove before Installation
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
-Use the accessory piping kit or the pipes purchased locally.
-Measure the distance between the indoor and the outside unit .
-Cut the pipes a little longer than measured distance.
-Cut the cable 1.5m(4.92ft) longer than the pipe length.
|
|
Pipe |
Copper |
|
Reamer |
|
Slanted Uneven Rough |
|
tube |
90 |
|
|
|
Point down |
Burrs removal
-Completely remove all burrs from the cut cross section of pipe/tube.
-Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
|
Handle |
Bar |
Bar |
"A" |
Yoke |
|
Cone |
Copper pipe
Clamp handle
Red arrow mark
Flaring work
- Carry out flaring work using flaring tool as shown below.
Indoor unit |
Pipe [mm(inch)] |
"A" [mm(inch)] |
||
[kW(Btu/h)] |
Gas |
Liquid |
Gas |
Liquid |
|
|
|
|
|
<5.6 (19,100) |
12.7(1/2) |
6.35(1/4) |
0.5~0.8 (0.02~0.03) |
0~0.5 (0~0.02) |
|
|
|
|
|
<16.0 (54,600) |
15.88(5/8) |
9.52(3/8) |
0.8~1.0 (0.03~0.04) |
0.5~0.8 (0.02~0.03) |
<22.4 (76,400) |
19.05(3/4) |
9.52(3/8) |
1.0~1.3 (0.04~0.05) |
0.5~0.8 (0.02~0.03) |
|
|
|
|
|
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Check
-Compare the flared work with figure below.
-If flare is noted to be defective, cut off the flared section and do flaring work again.
Smooth all round
Inside is shining without scratches.
= Improper flaring =
Inclined Surface Cracked Uneven
damaged thickness
Even length all round
Flare shape and flare nut tightening torque
Precautions when connecting pipes
-See the following table for flare part machining dimensions.
-When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
-See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
-After all the piping has been connected, use nitrogen to perform a gas leak check.
pipe size |
Tightening Torque |
A [mm(inch)] |
Flare shape |
|||
[mm(inch)] |
N·m(lbs ·ft) |
|||||
|
|
|
|
|||
Ø9.52(3/8) |
38±4(28±3.0) |
12.8(0.5)~13.2(0.52) |
90 2 |
|
|
|
|
|
|
||||
|
|
|
A |
45 |
2 |
|
Ø12.7(1/2) |
55±6(41±4.4) |
16.2(0.64)~16.6(0.65) |
|
|
||
|
|
|
||||
|
|
|
|
R=0.4~0.8 |
||
Ø15.88(5/8) |
75±7(55±5.2) |
19.3(0.76)~19.7(0.78 |
|
|
|
!CAUTION
•Always use a charge hose for service port connection.
•After tightening the cap, check that no refrigerant leaks are present.
•When loosening a flare nut, always use two wrenches in combination, When connecting the piping,
always use a spanner and torque wrench
in combination to tighten the flare nut.
Union
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Opening shutoff valve
1Remove the cap and turn the valve counter clockwise with the wrench.
2Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shut off |
|
Tightening torque N·m(lbs ·ft)(Turn clockwise to close) |
|||||
|
|
|
|
|
|
|
|
Shaft(valve body) |
|
|
|
Gas line pip- |
|||
valve size |
Cap |
Service |
|
||||
[mm(inch)] |
Closed |
Opened |
Hexagonal |
(Valve lid) |
port |
Flare nut |
ing attached |
|
wrench |
|
|
|
to unit |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ø6.35 |
|
|
|
|
|
16±2 |
|
(1/4) |
6.0 ±0.6 |
|
|
17.6±2.0 |
|
(12±1.5) |
|
|
|
|
|
|
|
||
Ø9.52 |
(4.4±0.4) |
|
4mm |
(13.0±1.5) |
|
38±4 |
|
|
|
|
|
|
|||
(3/8) |
|
|
(0.16inch) |
|
|
(28±3.0) |
|
|
|
|
|
|
|
|
|
Ø12.7 |
10.0 ±1.0 |
|
|
20.0±2.0 |
|
55±6( |
- |
(1/2) |
(7.4±0.7) |
|
|
(14.8±1.5) |
|
41±4.4) |
|
|
|
|
|
||||
|
|
5.0 ±0.0 |
|
|
12.7±2 |
|
|
Ø15.88 |
12.0 ±1.2 |
|
|
75±7 |
|
||
(5/8) |
(8.9±0.9) |
(3.7±0.4) |
5mm |
|
(9.4±1.5) |
(55±5.1) |
|
|
|
|
|
|
|
|
|
Ø19.05 |
14.0 ±1.4 |
|
(0.24inch) |
|
|
110±10 |
|
|
|
|
|
|
|||
(3/4) |
(10.3±1.0) |
|
|
25.0±2.5 |
|
(81.1±7.4) |
|
|
|
|
|
|
|
|
|
Ø22.2 |
|
|
|
(18.4±1.8) |
|
|
|
|
|
|
|
|
|
|
|
(7/8) |
30.0 ±3.0 |
|
8mm |
|
|
- |
25±3.0 |
|
|
|
|
||||
Ø25.4 |
(22.1±2.2) |
|
(0.31inch) |
|
|
(18.5±2.2) |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
(1.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat insulation
1Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 248°F).
2Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 73.4°F), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
-Heat insulation material to be prepared... EPDM (Ethylene Propylene Diene Methylene)-over 248°F the heat-resistance temperature.
-Add the insulation over 10mm(0.39 inch) thickness at high humidity environment.
Fastening band (accessory)
Refrigerant piping
Indoor unit
Thermal insulator (accessory)
11
Plumbing materials and storage methods |
<![if ! IE]> <![endif]>ENGLISH |
|
|
Pipe must be able to obtain the specified thickness and should be |
|
used with low impurities. |
|
Also when handling storage, pipe must be careful to prevent a frac- |
|
ture, deformity and wound. |
|
Should not be mixed with contaminations such as dust, moisture. |
|
|
|
Refrigerant piping on three principles
|
Drying |
Cleanliness |
Airtight |
|
|
|
|
|
|
|
Should be no moisture |
No dust inside. |
There is no refrigerant |
|
|
inside |
leakage |
||
|
|
|||
|
|
|
|
|
Items |
Moisture |
Dust |
Leakage |
|
|
||||
|
|
|
||
|
|
|
|
|
|
- Significant hydroly- |
- Degradation of re- |
- Gas shortages |
|
|
sis of refrigerant oil |
frigerant oil |
- Degradation of re- |
|
|
- Degradation of re- |
|
||
|
- Poor insulation of |
frigerant oil |
||
|
frigerant oil |
|||
|
the compressor |
- Poor insulation of |
||
Cause |
- Poor insula’tion of |
|||
|
||||
- Do not cold and |
the compressor |
|||
failure |
the compressor |
|||
warm |
- Do not cold and |
|||
|
- Do not cold and |
|||
|
|
|||
|
warm |
- Clogging of EEV, |
warm |
|
|
- Clogging of EEV, |
Capillary |
|
|
|
Capillary |
|
|
|
|
|
|
|
|
|
- No moisture in the pipe |
- No dust in the pipe. |
- Airtightness test |
|
|
- Until the connec- |
- Until the connec- |
should be. |
|
|
- Brazing operations |
|||
|
tion is completed, |
tion is completed, |
||
|
the plumbing pipe |
the plumbing pipe |
to comply with |
|
|
entrance should be |
entrance should be |
standards. |
|
|
strictly controlled. |
strictly controlled. |
- Flare to comply |
|
|
|
|
||
|
- Stop plumbing at |
- Pipe entrance |
with standards. |
|
Coun- |
rainy day. |
should be taken |
- Flange connections |
|
|
side or bottom. |
|||
- Pipe entrance |
to comply with |
|||
termea- |
should be taken |
- When removal burr |
standards. |
|
sure |
side or bottom. |
after cutting pipe, |
|
|
|
- When removal burr |
pipe entrance |
|
|
|
should be taken |
|
||
|
after cutting pipe, pipe |
|
||
|
entrance should be |
down. |
|
|
|
- Pipe entrance |
|
||
|
taken down. |
|
||
|
- Pipe entrance |
should be fitted cap |
|
|
|
when pass through |
|
||
|
should be fitted cap |
|
||
|
the walls. |
|
||
|
when pass through |
|
||
|
|
|
||
|
the walls. |
|
|
|
|
|
|
|
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor.
In order to avoid this problem, Welding should be done after replacing air by nitrogen gas.
When welding plumbing pipe, the work is required.
Welding Point
Oxide scale
Note) should not block the outlet side. When the internal pressure in pipe is abo ve the atmospheric pressure, pinhole is o ccurred and it is a leakage cause.
|
Regulator |
|
|
|
|
|
Nitrogen gas Pressure |
|
|
0.02Mpa (2.9psi) less |
|
Taping |
Auxiliary valve |
(Should not contain air)
<![endif]>Nitrogen
12
<![if ! IE]> <![endif]>ENGLISH |
|
|
|
|
|
|
|
! |
CAUTION |
|
|
|
|
|
|
|
|
|
1 |
Always use the nitrogen.(not use oxygen, carbon dioxide, and a |
|||
|
|
|
Chevron gas): Please use the following nitrogen pressure |
||
|
|
|
0.02Mpa (2.9psi) Oxygen – Promotes oxidative degradation of re- |
||
|
|
|
frigerant oil. Because it is flammable, it is strictly prohibited to |
||
|
|
|
use Carbon dioxide – Degrade the drying characteristics of gas |
||
|
|
|
|||
|
|
|
Chevron Gas – Toxic gas occurs when exposed to direct flame. |
||
|
2 |
Always use a pressure reducing valve. |
|||
|
3 |
Please do not use commercially available antioxidant. |
|||
|
|
|
The residual material seems to be the oxide scale is ob- |
||
|
|
|
served. In fact, due to the organic acids generated by oxida- |
||
|
|
|
tion of the alcohol contained in the anti-oxidants, ants nest |
||
|
|
|
corrosion occurs. (causes of organic acid alcohol + copper |
||
|
|
|
+ water + temperature) |
REFRIGERANT PIPING INSTALLATION
Pipe joint (auxiliary parts): Securely perform brazing with a nitrogen blow into the service port.(Releasing pressure : 0.02 MPa(2.9psi) or less)
Cap: Remove caps and operate valve, etc. After operation, always reattach caps (tightening torque of valve cap: 25Nm (250kg-cm) or more). (Don't remove the internal part of the port)
Service port: Make the refrigerant pipe vacuum and charge it using the service port. Always reattach caps after completing work (tightening torque of service cap: 14Nm (140kg-cm) or more).
Liquid pipe
Gas pipe
Elbow joint (field supply)
Remove the front panel before pipe connection
Must check the pipe (liquid pipe, low pressure gas pipe, high pressure gas pipe) before pipe connection
LiquidLiquidpipepipe
LowGaspressurepipegas pipe
High pressure gas pipe |
! WARNING
Always use extreme care to prevent the refrigerant gas (R410A) from leakage while using fire or flame. If the refrigerant gas comes in contact with the flame from any source, such as a gas stove, it breaks down and generates a poisonous gas which can cause gas poisoning. Never perform brazing in an unventilated room. Always conduct an inspection for gas leakage after installation of the refrigerant piping has been completed.
Cautions in pipe connection/valve operation
Open status when both the pipe and the valve are
in a straight line.
Cut both the pipe and the valve with a cutter to suit the length
[Don't cut the length of less than 70mm(2-3/4”)]
CLOSE OPEN
Connection of Outside units
Outside units |
Model Low Pressure Gas Pipe |
Liquid Pipe |
High Pressure Gas Pipe |
|
|
|
|
416(16-3/8) |
|
|
|
331(13-1/32) |
|
|
|
I.D34.9(1-3/8) |
|
|
|
|
I.D31.8(1-1/4) |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
I.D31.8(1-1/4) |
I.D28.58(1-1/8) |
I.D25.4(1) |
|
|||||||||
|
|
|
|
408(16-1/16) |
|
|
|
314(12-3/8) |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
A |
B |
|
I.D.28.58(1-1/8) |
I.D.28.58(1-1/8) |
|
|
I.D.15.88(5/8) |
I.D.15.88(5/8) |
|
|
|
|
|
|
|
|
|
I.D31.8(1-1/4) |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
I.D28.58(1-1/8) |
|
|
|
111 |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
I.D28.58(1-1/8) |
I.D25.4(1) |
||||||||
(Master) |
(Slave1) |
|
I.D.31.8(1-1/4) |
|
I.D.22.2(7/8) |
111(4-3/8) |
I.D.19.05(3/4) |
I.D.12.7(1/2) |
|
83(3-9/32) |
|
|
|
|
|
|
|
|
|
(4-3/8) |
|||
|
|
|
I.D.34.9(1-3/8) |
|
|
|
I.D.9.52(3/8) |
|
|
|
|
453(17-27/32) |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
491(19-9/32) |
|
|
|
|
|
||
2 Unit |
|
A ARCNN21 |
I.D.38.1(1-1/2) |
O.D28.58(1-1/8) |
|
|
|
|
I.D.12.7(1/2) |
I.D12.7(1/2) |
|
O.D12.7(1/2) |
I.D9.52(3/8) |
|
|
O.D25.4(1) |
I.D22.2(7/8) |
|
|||||
|
|
|
|
|
I.D.28.58(1-1/8) |
|
|
|
I.D.15.88(5/8) |
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
I.D.41.3(1-5/8) |
O.D.34.9(1-3/8) |
|
I.D22.2(7/8) |
I.D.22.2(7/8) |
O.D.19.05(3/4) |
O.D15.88(5/8) |
|
|
I.D9.52(3/8) |
|
70(2-3/4) |
|
|
|
80(3-5/32) |
|
|
|||
|
|
|
|
|
|
|
I.D19.05 |
|
|
|
|
|
|
O.D25.4(1) |
I.D22.2(7/8) |
I.D19.05(3/4) |
|
I.D15.88(5/8) |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
O.D19.05(3/4) |
|
I.D12.7(1/2) |
|||||
|
|
|
130(5-1/8) |
|
|
(3/4) |
|
|
|
|
|
|
|
|
|
X2 |
|
|
|
|
|
|
|
|
|
|
120(4-23/32) |
|
|
70(2-3/4) |
110(4-11/32) |
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
120(4-23/32) |
|
|
|
110(4-11/32) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
I.D34.9(1-3/8) |
|
|
|
|
I.D34.9(1-3/8) |
|
|
||
A |
B |
C |
|
406(16) |
|
|
|
334(13-5/32) |
|
|
|
|
I.D41.3(1-5/8) |
I.D38.1(1-1/2) |
I.D28.58(1-1/8) |
|
|||||||
|
353(13-29/32) |
|
|
|
281(11-1/16) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
(Master) |
(Slave1) |
(Slave2) |
|
|
|
|
|
|
|
|
|
|
|
|
I.D38.1(1-1/2) |
|
|
I.D28.58(1-1/8) |
125(4-29/32) |
||||
3 Unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
I.D34.9(1-3/8) |
I.D22.2(7/8) |
|
||||
|
ARCNN31 |
I.D38.1(1-1/2) |
I.D34.9(1-1/8) |
I.D.34.9(1-3/8) |
111(4-3/8) |
I.D.22.2(7/8) |
O.D.19.05(3/4) |
O.D.19.05(3/4) |
|
83(3-9/32) |
|
|
471(18-17/32) |
|
|
|
|
|
|||||
|
I.D.41.3(1-5/8) |
|
|
|
|
|
|
|
|
|
|
517(20-11/32) |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
I.D19.05(3/4) |
I.D15.88(5/8) |
|
I.D41.3(1-5/8) |
I.D38.1(1-1/2) |
|
|||||
|
|
|
|
|
|
|
|
|
|
I.D.15.88(5/8) |
I.D.12.7(1/2) |
O.D22.2(7/8) |
|
|
O.D38.1(1-1/2) |
O.D34.9(1-3/8) |
I.D41.3(1-5/8) |
||||||
|
|
|
I.D.41.3(1-5/8) |
I.D.28.58(1-1/8) |
I.D.15.88(5/8) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
O.D28.58(1-1/8) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
O.D.34.9(1-3/8) |
|
I.D22.2(7/8) |
O.D.19.05(3/4) |
I.D.12.7(1/2) |
O.D12.7(1/2) |
I.D9.52(3/8) |
I.D6.35(1/4) |
120(4-23/32) |
|
90(3-17/32) |
130(5-1/8) |
|
|||||||
|
|
|
|
|
|
|
I.D19.05 |
|
X 2 |
|
|
|
|
|
|
I.D12.7(1/2) |
|
|
|
I.D22.2(7/8) |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
O.D15.88(5/8) |
|
|
O.D28.58(1-1/8) |
|
|||||||
|
|
|
|
|
|
|
(3/4) |
110(4-11/32) |
110(4-11/32) |
|
|
|
|
|
|
|
|
|
I.D19.05 |
|
|||
|
|
|
|
125(4-29/32) |
120(4-23/32) |
|
|
|
|
|
|
|
|
|
|
70(2-3/4) |
|
|
120(4-23/32) |
(3/4) |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Install the branch pipe between outside units so that the outlet pipe is parallel to the surface.
Y branch
A |
Within +/- 10 |
|
|
B |
|
A To outside unit |
Viewed from point A |
|
in direction of arrow |
||
|
||
B To branch piping or indoor unit |
||
Facing |
Facing |
|
downwards |
upwards |
! WARNING
After completing work, securely tighten both service ports and caps so that gas does not leak.
Within ± 3° Within ± 3°
! CAUTION
When installing the branch pipe vertically between the outside units, the refrigerant can be uneven between the outside units, leading to compressor burn and reduced capacity.
Ball Valve |
Elbow |
Ball Valve(Gas Pipe) |
Liquid pipe |
(Liquid Pipe) |
|
Gas pipe |
|
|
|
|
Installation procedure for HR unit
1.Using an insert-hole-in- anchor, hang the hanging bolt.
2.Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as shown in the figure in the bottom, and fit the main unit to hang on the hanger metal.
3.After checking with a level that the unit is level, tighten the hexagon nut.
* The tilt of the unit should be within ±5° in front/back and left/right.
4.This unit should be installed suspended from ceiling and side A should always be
facing up.
5.Insulate not used pipes completely as shown in the figure.
Six-sided Nut |
|
|
(M10 or M8) |
A |
|
Hanger metal |
||
|
||
Flat washer |
|
|
(M10) |
Insulation |
|
Hanging bolt |
|
|
(M10 or M8) |
|
13
Type of HR Unit |
<![if ! IE]> <![endif]>ENGLISH |
|
|
Select an HR unit according to the number of the indoor units to be in- |
|
stalled. HR units are classified into 3 types by the number of con- |
|
nectable indoor units. |
|
Ex) Installation of 6 indoor units |
|
Consists of HR unit for 4 branches and HR unit for 2 branches. |
|
1 |
2 |
1 |
2 |
3 |
PRHR021(2 branches) PRHR031(3 branches)
1 2 3 4
PRHR041(4 branches)
Installation of Outside Unit, HR Unit, Indoor Unit
Refrigerant Pipe
3 pipes are connected to the HR unit from the outside unit, classified into liquid pipe, low pressure gas pipe and high pressure gas pipe depending on status of refrigerant passing through the pipe.
You must connect 3 pipes from outside unit to HR unit.
For connection between indoor unit and HR unit, you must connect both liquid pipe and gas pipe from the HR unit to the indoor unit. In this case, connect them to the indoor unit starting from No.1 connection port of the HR unit (the port number is displayed on ports of the HR unit). Use auxiliary flare as annexed parts in connection to the indoor unit.
Gas pipe
Liquid pipe
HR Unit |
Liquid pipe |
|||
Low pressure |
|
|
|
|
|
|
|
|
|
Gas pipe |
|
3 |
4 |
|
1 |
2 |
|
Gas pipe
High pressure Gas pipe
Liquid pipe
! CAUTION
Whenever connecting the indoor units with the HR unit, install the indoor units in numerical order from No.1.
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X), No.1, 3, 4 (X), No.2, 3, 4 (X).
! WARNING
Before brazing work, remove gas in the HR Unit by cutting the three pipes in the small circles on the figure.
If not, it may cause injuries.
Remove the caps before connecting pipes.
Joint Method of HR Unit (Big Duct : ARNU76GB8-,
ARNU96GB8-)
Joint Method is required when B5/B8 chassis is installed. In Joint Method, two neighboring outlets of one HR unit are linked by Y branch pipe and connected to one indoor unit.
|
|
|
|
|
|
|
1st HR Unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2nd HR Unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
|
1 |
2 |
3 |
4 |
|
B8 |
|
BG |
|
|
BH |
|
B8 |
|
|
(96k) (28k) |
|
|
(21k) |
(76k) |
|
|
|||
Liquid pipe |
|
|
|
|
|
|
|
|
|
Low pressure gas pipe |
|
|
|
|
|
|
1 |
2 |
3 4 |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
High pressure gas pipe |
|
|
|
|
|
|
|
|
|
Remove caps on |
|
|
Gas pipe Ø15.88 (5/8) |
|
|
||||
The brazing part. |
|
|
Liquid pipe Ø9.52 (3/8) |
|
|
||||
|
|
|
|
|
Brazing Type |
|
|
|
|
|
|
|
|
|
|
|
Unit : mm(inch) |
||
HR unit |
|
|
PRHR021A |
PRHR031A |
|
PRHR041A |
|||
Low pressure gas pipe |
Ø22.2(7/8) |
Ø28.58(1-1/8) |
|
Ø28.58(1-1/8) |
|||||
High pressure gas pipe |
Ø19.05(3/4) |
Ø22.2(7/8) |
|
Ø22.2(7/8) |
|||||
Liquid pipe |
|
Ø9.52(3/8) |
Ø12.7(1/2) |
|
Ø15.88(5/8) |
Liquid pipe
Low pressure gas pipe
Low pressure gas pipe
High pressure gas pipe
(Brazing Type)
Gas pipe Ø15.88 (5/8)
Liquid pipe Ø9.52 (3/8)
Brazing Type
14
<![if ! IE]> <![endif]>ENGLISH |
Installation of Zoning Control |
|
|
|
|
||
|
Some indoor unit can be connected to one port of HR unit. |
||
|
HR unit |
HR unit |
|
|
Zoning control group 1 |
sealing |
Zoning control group 2 |
|
|
||
|
(Max. 8 Indoor Units) |
|
(Max. 8 Indoor Units) |
|
Changeover under control |
Auto changeover |
Changeover under control |
! WARNING
•A branch pipe of HR unit allows up to 14.5kW(48kBtu/h) based on cooling capacity of the indoor unit. (up to 14.5kW(48kBtu/h) for max installation)
•The maximum total capacity of indoor units connected to a PRHR041 HR unit is 58kW(192kBtu/h).
•The maximum number of indoor units connected to a PRHR041 HR unit are 32 indoor units. (The Maximum indoor units per a branch pipe of HR unit are 8 indoor units)
•There is not operate “Auto-changeover” & “Mode override” function in the zoning group.
•When there are operating indoor units on cooling(heating) mode, another indoor units aren’t changed on heating(cooling) mode in the zoning group.
[Reducers for indoor unit and HR unit]
(Unit : mm)
Gas pipe
Models |
Liquid pipe |
|
|
|
|
Low pressure |
||||||
|
|
|
|
High pressure |
||||||||
Indoor unit |
|
|
|
|
|
– |
|
|
|
|
|
|
reducer |
|
|
|
|
|
|
|
|
|
|
|
|
OD9.52(3/8) |
Ø6.35(1/4) |
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
OD15.88(5/8) |
Ø12.7(1/2) |
||
PRHR021A |
|
|
|
OD19.05(3/4) |
|
Ø15.88(5/8) |
Ø12.7(1/2) |
OD22.2(7/8) |
Ø19.05(3/4) |
Ø15.88(5/8) |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OD9.52(3/8) |
Ø6.35(1/4) |
|
|
|
|
|
|
|
|
||
|
|
|
|
OD12.7(1/2) |
Ø9.52(3/8) |
OD15.88(5/8) |
Ø12.7(1/2) |
|||||
HR unit |
|
|
|
|
|
|
|
|
|
|
|
|
reducer |
|
|
|
|
|
|
|
|
|
|
|
|
PRHR031A/ |
|
|
|
OD22.2(7/8) |
Ø19.05(3/4) |
Ø15.88(5/8) |
OD28.58(1-1/8) |
|
Ø22.2(7/8) |
Ø19.05(3/4) |
||
|
|
|
|
|
|
|
|
|
||||
PRHR041A |
OD15.88(5/8) |
Ø12.7(1/2) |
Ø9.52(3/8) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
OD15.88(5/8) |
Ø12.7(1/2) |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
OD19.05(3/4) |
Ø15.88(5/8) |
CAUTION
1Use the following materials for refrigerant piping.
•Material: Seamless phosphorous deoxidized copper pipe
•Wall thickness : Comply with the relevant local and national regu-
lations for the designed pressure 3.8MPa(551.14psi). We recommend the following table as the minimum wall thickness.
Outer diameter |
6.35 |
9.52 |
12.7 |
15.88 |
19.05 |
22.2 |
25.4 |
28.58 |
31.8 |
34.9 |
38.1 |
41.3 |
44.45 |
53.98 |
[mm(inch)] |
(1/4) |
(3/8) |
(1/2) |
(5/8) |
(3/4) |
(7/8) |
(1) |
(1-1/8) |
(1-1/4) |
(1-3/8) |
(1-1/2) |
(1-5/8) |
(1-3/4) |
(2-1/8) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum thickness |
0.8 |
0.8 |
0.8 |
0.99 |
0.99 |
0.99 |
0.99 |
0.99 |
1.1 |
1.21 |
1.35 |
1.43 |
1.55 |
2.1 |
[mm(inch)] |
(1/32) |
(1/32) |
(1/32) |
(5/128) |
(5/128) |
(5/128) |
(5/128) |
(5/128) |
(3/64) |
(3/64) |
(7/128) |
(7/128) |
(1/16) |
(11/128) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
3Use care to prevent dust, water or other contaminants from entering the piping during installation.
4Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5Always use the branch piping set shown below, which are sold separately.
Y branch |
|
Header |
|
|
|
|
|
||
4 branch |
7 branch |
10 branch |
||
|
||||
|
|
|
|
|
ARBLB01621, ARBLB03321, |
ARBL054 |
ARBL057 |
ARBL1010 |
|
ARBLB07121, ARBLB14521, |
|
|
|
|
ARBL104 |
ARBL107 |
ARBL2010 |
||
ARBLB23220 |
||||
|
|
|
|
6If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut the connecting section and then use an adapter for connecting different diameters to connect the piping.
7Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8A second branch cannot be made after a header. (These are shown by .)
A
A
B
To Outside Unit
Sealed Piping
9The Multi V water will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always properly charge the unit. When servicing, always check the notes concerning both the piping length and the amount of additional refrigerant.
10Never perform a pump down. This will not only damage the compressor but also deteriorate the performance.
11Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
12.Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling performance, drip of condensate and other such problems.
13.When connecting the refrigerant piping, make sure the service valves of the Outside Unit is completely closed (the factory setting) and do not operate it until the refrigerant piping for the Outside and Indoor Units has been connected, a refrigerant leakage test has been performed and the evacuation process has been completed.