Please read this installation manual completely before installing the
product. Installation work must be performed in accordance with the
national wiring standards by authorized personnel only.
Please retain this installation manual for future reference after reading
it thoroughly.
Hydro Kit Wall mounted (medium temperature)
Original instruction (R32)
16Transporting the Unit
16Selection of the best location
20 INSTALLATION OF INDOOR UNIT
20Conditions where Indoor Unit is Installed
23 PIPING AND WIRING FOR INDOOR UNIT
23Water Piping and Water Circuit Connection
26Water pump Capacity
26Pressure Drop
28Typical Installation Example
31Water cycle (For R32)
33Water Quality
33Frost protection
34Preparation for Piping
35Electrical Wiring
36Wiring Connection
39Connecting Cables
40 ACCESSORIES INSTALLATION
40Before Installation
40Thermostat
44DHW Tank
47DHW Tank Kit
49Solar Thermal Kit
50Dry Contact
52External Controller - Setting up programmable digital input operation
53Remote Temperature Sensor
55Solar pump
56Wi-fi Modem
572Way Valve
583Way Valve(A)
593Way Valve(B)
60Final check
61 SYSTEM SET-UP
61DIP Switch Setting
66 SERVICE SETTING
66How to enter service setting
66Service setting
67Service contact
68Model information
69RMC version lnformation
70Open source license
71Installer setting
733 Minutes Delay
74Select Temperature Sensor
75Dry Contact Mode
76Pump test run
77Air cooling set temp.
78Water cooling set temp.
79Air heating set temp.
80Water heating set temp.
81DHW set temp.
82Water supply off temp. during cooling
84Heater priority
85DHW time setting
86TH on/off Variable, heating air
87TH on/off Variable, heating water
88TH on/off Variable, cooling air
89TH on/off Variable, cooling water
90Heating temp. setting
91Cooling temp. setting
92Pump setting in heating
93Pump setting. in cooling
94Forced operation
95CN_CC
96Pump frequency setting (RPM)
97Pump Capacity
98CN_EXT
99Anti-freezing Temperature
100Pump Prerun/Overrun
101Solar Thermal System
103Current flow rate
104Data logging
105Password Initialization
106Troubleshooting
TABLE OF CONTENTS
3
ENGLISH
SAFETY INSTRUCTIONS
4
ENGLISH
SAFETY INSTRUCTIONS
Read the precautions in this
manual carefully before
operating the unit.
This symbol indicates that
the Operation Manual should
be read carefully.
The following safety guidelines are intended to prevent
unforeseen risks or damage from unsafe or incorrect operation
of the appliance. The guidelines are separated into ‘WARNING’
and ‘CAUTION’ as described below.
This symbol is displayed to indicate matters and
!
operations that can cause risk. Read the part with this
symbol carefully and follow the instructions in order to
avoid risk.
WARNING
!
This indicates that the failure to follow the instructions can
cause serious injury or death.
This appliance is filled with
flammable refrigerant (R32)
This symbol indicates that a
service personnel should be
handling this equipment with
reference to the Installation
Manual.
CAUTION
!
This indicates that the failure to follow the instructions can
cause the minor injury or damage to the product.
WARNING
!
Installation
• Compliance with national gas regulations shall be observed.
• Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
- There is risk of fire or electric shock.
SAFETY INSTRUCTIONS
• For electrical work, contact the dealer, seller, a qualified
electrician, or an Authorized Service Center.
- There is risk of fire or electric shock.
• Always ground the unit.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric
shock.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the
case edges and the fins on the condenser and evaporator.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
5
ENGLISH
• Do not install, remove, or reinstall the unit by yourself
(customer).
- There is risk of fire, electric shock, explosion, or injury.
• For antifreeze, always contact the dealer or an authorized
service center.
- Almost the antifreeze is a toxic product.
• For installation, always contact the dealer or an Authorized
Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the unit on a defective installation stand.
- It may cause injury, accident, or damage to the unit.
• Do not turn on the breaker or power under condition that front
panel, cabinet, top cover, control box cover are removed or
opened.
- Otherwise, it may cause fire, electric shock, explosion or
death.
SAFETY INSTRUCTIONS
6
ENGLISH
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the unit could fall with it, causing
property damage, unit failure, and personal injury.
• Do not install the unit outdoor.
- It may cause damage to the unit.
• Use a vacuum pump or inert (nitrogen) gas when doing
leakage test or purging air. Do not compress air or oxygen and
do not use flammable gases.
- There is the risk of death, injury, fire or explosion.
• The appliance shall be stored in a well-ventilated area where
the room size corresponds to the room area as specified for
operation. (for R32)
• Ducts connected to an appliance shall not contain an ignition
source. (for R32)
• The appliance shall be stored in a room without continuously
operating ignition sources (for example: open flames, an
operating gas appliance or an operating electric heater.)
• Means for disconnection must be incorporated in the fixed
wiring in accordance with the wiring rules.
• This equipment shall be provided with a supply conductor
complying with the national regulation.
• Have all electric work done by a licensed electrician according
to "Electric Facility Engineering Standard" and "Interior Wire
Regulations" and the instructions given in this manual and
always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric
shock.
• Keep any required ventilation openings clear of obstruction.
• Mechanical connections shall be accessible for maintenance
purposes.
SAFETY INSTRUCTIONS
• To prevent the mixing of different types of refrigerants, be
sure to check the type of refrigerant used in the outdoor unit.
• When mechanical connectors are reused indoors, sealing parts
shall be renewed. (for R32)
• When flared joints are reused indoors, the flare part shall be refabricated. (for R32)
Operation
• Do not let the air conditioner run for a long time when the
humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Take care to ensure that power cable could not be pulled out
or damaged during operation.
- There is risk of fire or electric shock.
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
7
ENGLISH
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch (operate) the unit with wet hands.
- There is risk of fire or electric shock.
• Do not place a heater or other appliances near the power
cable.
- There is risk of fire or electric shock.
• Do not allow water to run into electric parts.
- There is risk of fire, failure of the unit, or electric shock.
• Do not store or use flammable gas or combustibles near the
unit.
- There is risk of fire or failure of unit.
• Do not use the product in a tightly closed space for a long
time.
- Oxygen deficiency could occur.
SAFETY INSTRUCTIONS
8
ENGLISH
• When flammable gas leaks, turn off the gas and open a
window for ventilation before turning the unit on.
- There is risk of explosion or fire.
• If strange sounds, or smell or smoke comes from unit, turn the
breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If
possible, remove the unit from the window before the
hurricane arrives.
- There is risk of property damage, failure of unit, or electric
shock.
• Do not open the front cover of the unit while operation. (Do
not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or unit failure.
• When the unit is soaked (flooded or submerged), contact an
Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Ventilate the unit from time to time when operating it together
with a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the unit.
- There is risk of electric shock.
• Take care to ensure that nobody could step on or fall onto the
unit.
- This could result in personal injury and unit damage.
• For installation, always contact the dealer or an Authorized
Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• If the unit is not used for long time, we strongly recommend
not to switch off the power supply to the unit.
- There is risk of water freezing.
SAFETY INSTRUCTIONS
• Periodic ( more than once/year ) cleaning of the dust or salt
particles stuck on the heat exchanger by using water.
• Do not use means to accelerate the defrosting process or to
clean, other than those recommended by the manufacturer.
• Do not pierce or burn refrigerant cycle part.
• Be aware that refrigerants may not contain an odour.
CAUTION
!
Installation
• Always check for gas (refrigerant) leakage after installation or
repair of unit.
- Low refrigerant levels may cause failure of unit.
• Keep level even when installing the unit.
- To avoid vibration or water leakage.
• Use two or more people to lift and transport the unit.
- Avoid personal injury.
9
ENGLISH
•
Any person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an
industry accredited assessment authority, which authorises
their competence to handle refrigerants safely in accordance
with an industry recognised assessment specification. (for R32)
• The appliance shall be stored so as to prevent mechanical
damage from occurring.
• If anyone other than a licensed Professional installs, repairs, or
alters LG Electronics Air Conditioning Products, the warranty is
voided.
- All costs associated with repair are then the full responsibility
of the owner.
• Do not install the product where it will be exposed to sea wind
(salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly
on the condenser and evaporator fins, could cause product
malfunction or inefficient operation.
SAFETY INSTRUCTIONS
10
ENGLISH
• Refrigerant tubing shall be protected or enclosed to avoid
damage.
• Flexible refrigerant connectors (such as connecting lines
between the indoor and outdoor unit) that may be displaced
during normal operations shall be protected against mechanical
damage.
• The installation of pipe-work shall be kept to a minimum.
• Pipe-work shall be protected from physical damage.
• A brazed, welded, or mechanical connection shall be made
before opening the valves to permit refrigerant to flow
between the refrigerating system parts.
• Dismantling the unit, treatment of the refrigerant oil and
eventual parts should be done in accordance with local and
national standards.
• Do not install the unit in potentially explosive atmospheres.
Operation
• Do not lay on the cooled floor for long time when the unit is in
cooling operation.
- This could harm to your health.
• Do not use the unit for special purposes, such as preserving
foods, works of art, etc.
- There is risk of damage or loss of property.
• Use a soft cloth to clean. Do not use harsh detergents,
solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic
parts of the unit.
• Do not step on or put anything on the unit.
- There is risk of personal injury and failure of unit.
• Use a firm stool or ladder when cleaning or maintaining the
unit.
- Be careful and avoid personal injury.
SAFETY INSTRUCTIONS
• Servicing shall only be performed as recommended by the
equipment manufacturer. Maintenance and repair requiring the
assistance of other skilled personnel shall be carried out under
the supervision of the person competent in the use of
flammable refrigerants. (for R32)
• Do not unplug the power supply plug of Hydro Kit when
stopping Hydro Kit operation. Always turn Hydro Kit off, using
the wired remote controller.
- A plate heat exchanger burst may happen because of
disconnection of communication between Hydro Kit and the
outdoor unit.
11
ENGLISH
INSTALLATION PART
12
ENGLISH
INSTALLATION PART
Thank you for choosing LG Electronics Air-to-Water Heat Pump
Before starting installation, please make it sure that all parts are found inside the product box.
INDOOR UNIT BOX
ItemImage
Indoor unit
Owner's / Installation manual
Shut-off valve
Installation Sheet
Hydro Kit
GENERAL INFORMATION
GENERAL INFORMATION
13
ENGLISH
With advanced inverter technology,
Hydro Kit
is suitable for applications like under floor heating,
and hot water generation. By Interfacing to various accessories user can customize the range of
the application.
Model Information
Model name and related information
Model Name
Refrigerant
R321Ø
Indoor Unit
PhaseCapacity (kW)
5.6
7.1
9.0
Built-In Electric
Heater(kW)
6 (3+3)
Power Source
(Electric Heater)
220-240 V~
50 Hz
Power
Source (Unit)
220-240 V~
50 Hz
Accessories
To extend the functionality of
"accessories".
They are classified by "accessories" and "3rd party accessories" according to the manufacturer.
Accessories are presented LG Electronics, and 3rd party accessories are presented by related
manufacturers.
Hydro Kit
, there are various external auxiliary apparatus called as
GENERAL INFORMATION
14
ENGLISH
Accessories supported by LG Electronics
ItemPurposeModel
DHW Tank KitTo operate with DHW tank
Remote Air
Sensor
Dry Contact
Solar Thermal KitTo operate with solar heating system PHLLA(Limit temperature : 96 °C)
DHW TankTo generate and store hot water
Thermistor for
DHW Tank
Drain PanTo prevent drain water dropPHDPB
Central Controller
Wi-Fi Modem
Extension wire
Cover Plate
To control by air temperaturePQRSTA0
To receive on & off external signalPDRYCB500
Dry Contact For ThermostatPDRYCB300
To control hot water temperature of
DHW tank
Multiple installed products into one
central control
To enable remote system operation
from smartphone
To connect remote controller with
Indoor PCB for communication
To relocate remote controller from
indoor unit
PHLTA : 1Ø
PHLTC : 3Ø
PHS02060310 : 200 liter, Single Heating Coil,
1Ø 230 V 50 Hz 3 kW Electric Heater
PHS02060320 : 200 liter, Double Heating Coil,
1Ø 230 V 50 Hz 3 kW Electric Heater
PHS03060310 : 300 liter, Single Heating Coil,
1Ø 230 V 50 Hz 3 kW Electric Heater
PHS03060320 : 300 liter, Double Heating Coil,
1Ø 230 V 50 Hz 3 kW Electric Heater
PHRSTA0
PWFMDD200
PZCWRC1
PDC-HK10
Accessories supported by 3rd party Companies
ItemPurposeSpecification
Solar Heating System
ThermostatTo control by air temperature
3rdParty Controller
3way valve and actuator
2way valve and actuator To control water flow for Fan Coil Unit
To generate auxiliary heating energy
for water tank
To connect external controller using
modbus protocol
(A) : To control water flow for hot
water heating or floor heating / To
control water flow when installing
3rd party boiler
(B) : To control close/open mode of
solar circuit
GENERAL INFORMATION
• Solar collector
• 3way valve(B)
Heating-Only type (230 V AC)
Cooling/Heating type (230 V AC with
Mode selection switch)
3 wire, SPDT (Single Pole Double Throw)
type, 230 V AC
2 wire,NO(Normal Open) or NC(Normal
Closed) type, 230 V AC
15
ENGLISH
INSTALLATION
16
ENGLISH
INSTALLATION
Transporting the Unit
CAUTION
!
Be very careful while carrying the unit.
• Do not have only one person carry the unit if it is more than 20 kg (44.1 lbs).
• PP bands are used to pack some products. Do not use them as a mean for transportation
because they are dangerous.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise
plastic packaging bag may suffocate children to death.
• When carrying the unit, be sure to support it at 6-points. Carrying and lifting the unit with 4point support may make it unstable, resulting in a fall.
Selection of the best location
Select space for installing the unit, which will meet the following conditions:
The place where the unit shall be installed inside.
The place shall easily bear a load exceeding four times of the unit weight.
The place where the unit shall be leveled.
The place shall allow easy water drainage.
The place where the unit shall be connected to the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where there should not be any heat source or steam near the unit.
INSTALLATION
Minimum floor area(for R32)
- The appliance shall be installed, operated and stored in a room with a floor area larger than the
minimum area.
- Use the graph of table to determine the minimum area.
If this product is installed in the a room smaller than minimum floor area, there shall be
continuously operated mechanical ventilation system or natural ventilation openings.
Natural ventilation
[Room A]
→ ≥ 50 % of Anv
[Room B]
min
≥ 1.5 m
Unit
→ ≥ 100 % of Anv
min
The floor area of “Room A + Room B” is considered as floor area instead of “Room A” for
min
complying with minimum floor area “A
” if :
- Openings are permanent openings which cannot be closed.
- Room A shall be larger than 0.64 m
2
Bottom opening:
- The area of any openings above 300 mm from the floor shall not be considered in determining
compliance with Anv
- At least 50 % of the required opening area Anv
min
.
min
shall be below 200 mm from the floor.
- The bottom of the lowest openings shall not be higher than 100 mm from the floor.
- If the openings starts from the floor, the height must be higher than 20 mm.
Top opening:
- The total size of the top opening shall not be less than 50 % of minimum opening area for
min
Anv
and shall be at least 1.5 m above the floor.
min
- Anv
: the minimum opening for natural ventilation
m (kg)A
min
1.22451.2
1.473.5
1.698.8
1.8124.1
2.0149.4
2.2174.7
2.4200.0
2.6225.3
2.8250.6
3.0275.9
(cm2)
m (kg)A
3.2301.2
3.4326.5
3.6351.8
3.8377.1
4.0402.4
4.2427.7
4.4453.0
4.6478.3
4.8503.6
5.0528.9
min
(cm2)
INSTALLATION
Mechanical ventilation
If there is a mechanical ventilation system that satisfies with minimum air flow, a product can be
installed in the room smaller than the minimum floor area.
• The room shall comply with machinery room’s requirements of ISO 5149.
m (kg)A
min
(m2)
< 1.224-
1.2241.43
1.31.61
1.41.87
1.52.15
1.62.44
1.72.76
1.83.09
1.93.44
23.81
2.14.20
2.24.61
2.35.04
2.45.49
2.55.96
2.66.44
2.76.95
19
ENGLISH
INSTALLATION OF INDOOR UNIT
20
ENGLISH
INSTALLATION OF INDOOR UNIT
The indoor unit of
and refrigerant pipe from the outdoor unit are accessible at the same time.
In this chapter conditions for installation place is described. In addition, considerations when
installing accessories or 3rd party accessories are described, too.
Conditions where Indoor Unit is Installed
Specific conditions are required for installation place such as service space, wall mounting, water
pipe length and height, total volume of water, adjusting expansion vessel, and water quality.
General Considerations
Followings are should be considered before the installation of the indoor unit.
- The installation place should be free from outdoor weather conditions such as rain, snow, wind,
frost, etc.
- Choose the place where is water-resistant or good drainage.
- Service space should be secured.
- No flammable materials around the indoor unit.
- Mice can not be appeared to prevent entering the indoor unit or attacking wires.
- Do not place anything in front of the indoor unit to ensure air circulation around the indoor unit.
- Do not locate anything under the indoor unit to be free from unexpected water out.
- In case of water pressure increasing to 3 bar, water drainage should be treated when water is
drained by safety valve.
Hydro Kit
is installed inside where terminal of under floor water pipe cycle
Service Space
- Ensure that the spaces indicated by arrows around bottom,
side, and top side.
- Wider spaces are preferred for easy maintenance and piping.
- If minimum service space is not secured, air circulation can
be troubled and internal parts of the indoor unit can be
damaged by overheating.
NOTE
• The default setting of the product is for heating only.
To use the cooling system together, DIP S / W 4
should be turned ON and additional drain pan
accessory should be installed.
200
1 300
Minimum service space
(unit : mm)
250
200
INSTALLATION OF INDOOR UNIT
Bottom screws
Upper screw
Mounting to Wall
Step 1. Disconnect the remote control case from the front panel and disconnect the remote
control cable.
CAUTION
!
After installation is completed, return the remote control to its original state.
NOTE
Use a flat-blade screwdriver or a coin to remove the remote control case.
Step 2. After releasing five screws, detach front cover from the indoor unit. While detaching the
front cover, grab the left and right sides of the front cover. Then pull into upward
direction.
21
ENGLISH
Step 3. Attach "Installation Sheet" to the wall and mark the location of bolts.
This sheet helps to find correct location to the bolts.
CAUTION
!
The sheet should be attached level. If not, the supporting plate and the indoor unit will not
be mounted correctly.
INSTALLATION OF INDOOR UNIT
22
ENGLISH
Step 4. Detach the Installation sheet. Screw bolts at the hole marks on the wall.
When screwing bolts, use M8 ~ M11 anchor bolts to secure hanging the indoor unit.
NOTE
Self drilling screw can be used as alternatives of M8 ~ M11 anchor bolts. But M8 ~ M11
anchor bolts are more preferred.
Step 5. Hang the indoor unit at the supporting plate.
PIPING AND WIRING FOR INDOOR UNIT
PIPING AND WIRING FOR INDOOR UNIT
Procedures about water piping and electric wiring at the indoor unit are described in this chapter.
Water piping and water circuit connection, water charging, pipe insulations will be shown for
water piping procedures. For wiring, terminal block connection, connecting with the outdoor
unit, electric heater wiring will be introduced. Accessories connection, such as sanitary water
tank, thermostat, 3way or 2way valves, etc will be dealt in separated chapter.
Water Piping and Water Circuit Connection
CAUTION
!
General Considerations
Followings are should be considered before beginning water circuit connection.
- Service space should be secured.
- Water pipes and connections should be cleaned using water.
- Space for installing external water pump should be provided if internal water pump capacity
is not enough for installation field.
- Never connect electric power while proceeding water charging.
Water Piping and Water Circuit Connection
Definition of terms are as follow :
- Water piping : Installing pipes where water is flowing inside the pipe.
- Water circuit connecting : Making connection between the product and water pipes or between
pipes and pipes. Connecting valves or elbows are, for example, in this category.
23
ENGLISH
While installing water pipes, followings should be considered :
- While inserting or putting water pipes, close the end of the pipe with pipe cap to avoid dust
entering.
- When cutting or welding the pipe, always be careful that inner section of the pipe should not be
defective. For example, no weldments or no burrs are found inside the pipe.
- Drain piping should be provided in case of water discharge by the operation of the safety valve.
This situation can be happened when the internal pressure is over 3.0 bar and water inside the
indoor unit will be discharged to drain hose.
While connecting water pipes, followings should be considered.
- Pipe fittings (e.g. L-shape elbow, T-shape tee, diameter reducer, etc) should be tightened
strongly to be free from water leakage.
- Connected sections should be leakage-proof treatment by applying tefron tape, rubber bushing,
sealant solution, etc.
- Appropriate tools and tooling methods should be applied to prevent mechanical breakage of the
connections.
- Operation time of flow control valve(e.g. 3way valve or 2way valve) should be less than 90
seconds.
- Drain hose should be connected with drain piping.
24
ENGLISH
PIPING AND WIRING FOR INDOOR UNIT
WARNING
!
Installing shut-off valve
• While assembling two shut-off valves, that are found inside ‘AWHP Installation Kit
(AET69364401)’, pop sound will be heard when valve is open or close by rotating handles.
It is normal condition because the sound is due to leakage of charged nitrogen gas inside
the valve. The nitrogen gas is applied to secure quality assurance.
• Before starting water charging, these two shut-off valves should be assembled with water
inlet and outlet pipe of the indoor unit.
Water condensation on the floor
While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
While cooling operation, cold water may not flow to the radiator. If cold water enters to the
radiator, dew generation on the surface of the radiator can be occurred.
Drainage treatment
While cooling operation, condensed dew can drop down to the bottom of the indoor unit. In
this case, prepare drainage treatment (for example, vessel to contain condensed dew) to
avoid water drop.
PIPING AND WIRING FOR INDOOR UNIT
Water Charging
For water charging, please follow below procedures.
Step 1. Open all valves of whole water circuit. Supplied water should be charged not only inside
the indoor unit, but also in the under floor water circuit, sanitary water tank circuit, FCU
water circuit, and any other water circuits controlled by the product.
Step 2. Connect supply water into drain valve and fill valve located at the side of the shut-off
valve.
CAUTION
!
No water-leakage permitted at the drain and fill
valve. Leakage-proof treatment which is
described in previous section should be applied.
Water OutWater In
Step 3. Start to supply water. While supplying water, following should be kept.
- Pressure of supplying water should be 2.0 bar approximately.
- For supplying water pressure, time to be taken from 0 bar to 2.0 bar should be more
than 1 minute. Sudden water supply can yield water drain through safety valve.
- Fully open the cap of air vent to assure air purging. If air is exist inside the water circuit,
then performance degrade, noise at the water pipe, mechanical damage at the surface
of electric heater coil.
Step 4. Stop water supplying when the pressure gauge located in front of the control panel
indicates 2.0 bar.
Step 5. Close drain valve and fill valve. Then wait for 20~30 seconds to observe water pressure
being stabilized.
Step 6. If following conditions are satisfactory, then go to step 7(pipe insulation). Otherwise, go
to step 3.
- Pressure gauge indicates 2.0 bar. Note that sometimes pressure in decreased after step
5 due to water charging inside expansion vessel.
- No air purging sound is heard or no water drop are popping out from air vent.
25
ENGLISH
Pipe Insulation
Purpose of water pipe insulation is :
- To prevent heat loss to external environment
- To prevent dew generation on the surface of the pipe in cooling operation
PIPING AND WIRING FOR INDOOR UNIT
26
ENGLISH
Water pump Capacity
The water pump use variable type which is capable to change flow rate, so it may be required to
change default water pump capacity in case of noise by water flow. In most case, however, it is
strongly recommended to set capacity as
Rated flow-rate
.
NOTE
• To secure enough water flow rate, do not set water pump capacity as Minimum.
It can lead unexpected flow rate error CH14.
Pressure Drop
NOTE
When installing the product, install additional pump in consideration of the pressure loss and
pump performance.
If flow-rate is low, overloading of product can occur.
Performance test based on standard ISO 9906 with pre-pressure 2.0bar and liquid temperature
20 °C.
27
ENGLISH
WARNING
!
Selecting a water flowrate outside the curves can cause damage to or malfunction of the
unit.
PIPING AND WIRING FOR INDOOR UNIT
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loop
Fan coil unit
Radiator
M / F
High TemperatureRoom Thermostat(Field supply)
2way valve (Field supply)By-pass valve(Field supply)Low Temperature
Magnetic Filter (Recommended)
Shut-off valve
M / F
28
ENGLISH
Typical Installation Example
CAUTION
!
If
Hydro Kit
operated together. If entering water temperature of
will stop operation to prevent mechanical damage of the product. For detailed electric wiring
and water piping, please contact authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual figures,
installer should optimize the installation scene according to the installation conditions.
CASE 1: Connecting Heat Emitters for Heating and Cooling
is installed with pre-existing boiler, the boiler and
Hydro Kit
(Under floor loop, Fan Coil Unit, and Radiator)
Hydro Kit
is above 50 °C, the system
should not be
NOTE
• 2way valve
- It is important to install 2way valve to prevent dew condensation on the floor and radiator
while cooling mode.
- 2way valve should be installed at the supply side of the collector.
• By-pass valve
- To secure enough water flow rate, by-pass valve should be installed at the collector.
- By-pass valve should guarantee minimum water flow rate in any case. Minimum water
flow rate is described in water pump characteristics curve.
CASE 2: Connecting DHW Tank
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loopFan coil unit
Hot water
City water
Radiator
M / F
DHWDHW
tanktank
DHW
tank
High Temperature
Room Thermostat(Field supply)
2way valve
(Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Shut-off valve
Magnetic Filter (Recommended)
M / F
DHW
tank
NOTE
PIPING AND WIRING FOR INDOOR UNIT
29
ENGLISH
• DHW tank
- It should be equipped with internal electric heater to generate sufficient heat energy in
very cold season.
- DHW : Domestic Hot Water
PIPING AND WIRING FOR INDOOR UNIT
Solar heat source
OutdoorIndoor
Outdoor Unit
Indoor Unit
Floor heating loopFan coil unit
Hot water
City water
Radiator
M / F
DHWDHW
tanktank
DHW
tank
High Temperature
Room Thermostat(Field supply)
2way valve (Field supply)
3way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Shut-off valve
Pump(Field supply)
Magnetic Filter (Recommended)
M / F
DHW
tank
30
ENGLISH
CASE 3: Connecting Solar thermal system
NOTE
• DHW tank
- It should be equipped with internal electric heater to generate sufficient heat energy in
very cold season.
- DHW : Domestic Hot Water
• Pump
- Maximum power consumption of pump should be less than 0.25 kW.
Loading...
+ 81 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.