LG AMNQ12GL2A0 INSTALLATION MANUAL

www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ceilling Concealed Duct Original instruction
INSTALLATION MANUAL
ENGLISH
*MFL67448535*
Rev. : 00(06T18)
Copyright © 2016 - 2018 LG Electronics Inc. All Rights Reserved.
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi­tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
ENGLISH
TIPS FOR SAVING ENERGY
2
TIPS FOR SAVING ENERGY
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes, with the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal­function, property damage, personal injury and/or death.
Installation
• Always perform grounding. - Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged. - Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation agency. - Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
- If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. - No installation may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. - Otherwise, it may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
- It may cause injury or an accident.
• Do not disassemble or repair the product randomly. - It will cause a fire or electrical shock.
• Do not install the product at a place that there is concern of falling down. - Otherwise, it may result in personal injury.
• Use caution when unpacking and installing. - Sharp edges may cause injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it may cause fire, electric shock, explosion or death.
Operation
• Do not share the outlet with other appliances. - It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord. - Otherwise, it may cause a fire or electrical shock.
!
!
!
• Do not modify or extend the power cord randomly. - Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation. - Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it. - Otherwise, it may cause electri­cal shock or a fire.
• Keep the flames away. - Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet hands. - Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools. - Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. - Otherwise, it may electri­cal shock and failure.
• Do not allow water to run into electrical parts. - Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out. - It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter. - They are sharp and may cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. - It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord. - Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center. - Otherwise, it may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. - Otherwise, children may be seriously injured due to falling down.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done. - Otherwise, it may cause water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors. - Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. - Otherwise, it may cause the failure of product.
• Keep level parallel in installing the product. - Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. - Otherwise, it may do harm to your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. - The appearance of the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. - Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. - Otherwise, it may cause the failure of appli­ance or an accident.
!
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
5
2 TIPS FOR SAVING
ENERGY
3 IMPORTANT SAFETY
INSTRUCTIONS
6 INTRODUCTION
7 INSTALLATION OF
INDOOR
7 Selection of the best location
8 Ceiling dimension and hanging bolt
location
9 Indoor Unit Installation
9 Wiring Connection
10 Part name and functions
11 Indoor Unit Drain Piping
12 Drain test
12 Heat insulation
13 REMOTE CONTROLLER
INSTALLATION
15 Wired remote controller installation
16 OPTIONAL OPERATION
16 Installer Setting -Test Run Mode
17 Installer Setting - Setting Address of
Central Control
18 Installer Setting -Thermistor
19 Installer Setting-Group Setting
20 Installer Setting-Dry Contact Mode
Setting
21 Installer Setting -Celsius / Fahrenheit
24 HOW TO SET E.S.P?
TABLE OF CONTENTS
TABLE OF CONTENTS
Switching
22 Installer Setting -Optional Function
Setting
23 Installer Setting -Remote controller
Mode Lock
24 Installer Setting -E.S.P.
26 Installer Setting -Static Pressure Step
Setting
28 DIP SWITCH SETTING
6
ENGLISH
INTRODUCTION
Air outlet vents
Air filters
Control box
Air intake vents
TEMP
FAN SPEED
OPER MODE
Wired Remote Controller
INTRODUCTION
Top view
Side view
Unit: mm(inch)
eiling
B
INSTALLATION OF INDOOR
INSTALLATION OF INDOOR
7
ENGLISH
Selection of the best location
Install the air conditioner in the location that satisfies the following conditions.
- The place shall easily bear a load exceeding four times the indoor unit’s weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall easily connect with the out­door unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good.
- There should not be any heat source or steam near the unit.
Unit: mm(inch)
600
Inspection hole
(600 x 600)
Air outlet
Control box
600
Capacity (kBtu/h) A B
9 800 800
12 / 18 800 1000
24 800 1200
A(Min)
B(Min)
(Unit: mm)
C
* Suitable dimension "H" is necessary to get a
slope to drain as shown in the figure
Confirm the positional relationship between the unit and suspension bolts.
- Installation the ceiling opening to clean the filter or service under the product.
Service Space
A
Air outlet
H=20 or more
8
E
Drainage hole
ENGLISH
INSTALLATION OF INDOOR
Ceiling dimension and hanging bolt location
Install the unit above the ceiling correctly.
CASE 1
osition of suspension Bolt
P
- Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
G
C
D
J A
B
I
F
H
CASE 2
- Install the unit leaning to a drainage hole side as a figure for easy water drainage.
osition of console Bolt
P
- A place where the unit will be leveled and that can support the weight of the unit.
- A place where the unit can withstand its vi­bration.
- A place where service can be easily per­formed.
M10 Nut
M10 SP. washer
M10 washer
M10 washer
M10 SP. washer
M10 Nut
X 4
X 4
X 4
X 4
X 4
X 4
(Local supply)
(Local supply)
(Unit:mm)
Dimension
Capacity (kBtu/h)
12/18 933 972 628 700 36 190 20 860 155 900
A B C D E F G H I J
9 733 772 628 700 36 190 20 660 155 700
24 11331172 628 700 36 190 20 1060 155 1100
INSTALLATION OF INDOOR
ENGLISH
9
Wiring Connection
Connect the wires to the terminals on the control board individually according to the out­door unit connection.
- Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set an­chor firmly.
- Secure the installation plates onto the sus­pension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension bolts
CAUTION
Tighten the nut and bolt to prevent unit falling.
!
CAUTION
The Power cord connected to the unit should be selected according to the fol­lowing specifications. (Cable type CV ap­proved by IEC 60502-1)
!
Terminal Block
Indoor
Terminal Block
Indoor
1(L) 2(N) 3
Outdoor unitIndoor unit
Terminal Block outdoor
1(L) 2(N) 3
20mm
GN/YL
NORMAL CROSS-SECTIONAL AREA 2.5mm
2
WARNING
Make sure that the screws of the termi­nal are free from looseness.
!
Indoor Unit Installation
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
10
INSTALLATION OF INDOOR
ENGLISH
Caution for gradient of unit and drain piping
Lay the drain hose with a downward inclina­tion so water will drain out.
- Always lay the drain with downward inclina­tion (1/50 to 1/100). Prevent any upward flow or reverse flow in any part.
- 5mm or thicker formed thermal insulator shall always be provided for the drain pipe.
Ceiling
Ceiling
1/100~1/50
Drainage hole
CORRECT
INCORRECT
Drainage hole
• Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
• Minimum thickness of the insulation for the connecting pipe shall be 5 mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
CAUTION
!
Drainage holeMake sure to be closed.
Unit
Drainage pipe (Local supply)
Thermal insulator
(Local supply)
- Low static duct type in case of suction from bottom side.
- In case of suction from bottom size, bend the Panel rear and screw with cabinet case.
Air outlet
Air Filter
Panel Rear
Air outlet
Air Filter
Panel Rear
Air outlet
Air Filter
Panel Rear