Tabelle 11.6: Accessories for PC configuration / IO-Link / fieldbus connection............................. 115
Leuze electronicODS…/ODK… 9 / 96B5
General information
TRI
TOF
1General information
1.1Explanation of symbols
The symbols used in this technical description are explained below.
Attention
This symbol precedes text messages which must strictly be observed. Failure to comply with
this information results in injuries to personnel or damage to the equipment.
Attention Laser Radiation
This symbol warns of possible danger caused by hazardous laser radiation.
Notice
This symbol indicates text passages containing important information.
Notice
According to their measurement principle, this manual also refers to the sensors in
brief as triangulation sensors and as time-of-flight sensors and partly distinguishes
them in the text by means of different colors:
•= triangulation sensors
•= time-of-flight sensors
1.2Important terms
Absolute measurement accuracy
Shows the possible divergence of the measurement value from the anticipated value
through changes in the environmental conditions during the measuring process.
Accuracy is increased under constant environmental conditions.
Response time
The time period required to obtain stable measurements after change of the reflectivity behavior. In the case of sensors with the time-of-flight measurement principle, the
response time equals the measurement time.
6ODS…/ODK… 9 / 96BLeuze electronic
General information
TRI
TOF
Resolution
The smallest possible distance change of the measurement object, which causes a
definite change in the output signal. For sensors with triangulation measurement principle, the short range resolution exceeds that at distant range. Objects at short range
can be measured with higher accuracy.
Warmup time
Time the sensor needs in order to reach the operating temperature. The warmup time
is around 20min (depending on the sensor type). An optimal measurement is only
possible after the end of the warmup time.
Output resolution
The output resolution describes how the measurement values are presented on the
display and digital interfaces. The output resolution (0.01mm, 0.1 mm or 1mm) is set
for each sensor type and cannot be changed.
Delay before start-up
The delay before start-up indicates the point in time when the first valid measurement
can be obtained after switching on.
Insensitivity towards ambient light
Indicates the insensitivity of the measurement result towards ambient light. Sensors
with triangulation measurement principle () also measure reliably with external
light interference of 5kLux (ODS… 96B) or 30 kLux (ODSL 9), while the typical light
intensity in the workplaces is only about 1kLux. Sensors with time-of-flight measure-
ment principle () feature a significantly higher immunity against external light
interference of about 100kLux. The immunity against external light interference of triangulation sensors may be improved significantly via the Ambient Light Suppres-sion mode (abt. 30kLux).
Light switching / Dark switching
Indicates the behavior of the switching output when an object is inside the taught/configured switching distance. At light switching, the switching output is active (high), at
dark switching inactive.
Integration time
The integration time for triangulation sensors is comparable to the exposure time for
photographic cameras. It is automatically adjusted to the intensity of the reflected light
and thus depends on the reflectance factor of the measurement object. It is inversely
proportional to the measurement frequency. Triangulation sensors by
Leuze electronic automatically adjust themselves for optimum integration time.
Measurement time
The measurement time indicates the time difference between 2 consecutive
measurements. For triangulation sensors, the measurement time changes as a result
of the adaptation of the integration time in correspondence with the reflectance and
the measurement distance.
Leuze electronicODS…/ODK… 9 / 96B7
TNT 35/7-24V
General information
TOF
TRI
Diffuse reflection
Return and/or degree of reflection of the radiated light. Please observe the
reflectance values in the respective specifications (90% is white, 6% is black). In the
case of sensors with the time-of-flight measurement principle, the measurement
range depends on the reflectance.
Time of Flight
Distance measurement procedures that determines the distance of an object via the
propagation time of a light pulse emitted by the sensor's transmitter that is reflected
by the object and received by the sensor's receiver. For large operating ranges, high
immunity against light interference and low influence of gloss and structures on the
measurement value.
Triangulation
Distance measuring procedure, which determines the distance of an object by the
incidence angle of the light reflected from the object. For short to medium operating
ranges, fast measurement rate, high accuracy.
Repeatability
Measuring distance change with repeated measurement at the same output signal
(observe the same peripheral conditions as with resolution).
1.3Declaration of conformity
The optical distance sensors of the ODS…/ODK… series have been manufactured observing current European standards and guidelines.
Notice
A corresponding Declaration of Conformity can be requested from the manufacturer.
The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen,
possesses a certified quality assurance system in accordance with ISO 9001.
8ODS…/ODK… 9 / 96BLeuze electronic
2Safety
This sensor was developed, manufactured and tested in accordance with the applicable
safety standards. It corresponds to the state of the art.
2.1Proper use
The ODS… distance sensors are optical electronic sensors for the optical, contactless
measurement of distance to objects.
Areas of application
The optical distance sensors of the ODS… series have been designed for the following
areas of application:
• distance measurement
• contour determination
• thickness measurement
• positioning
• filling level measurement
• diameter determination
• sag determination and much more.
CAUTION
Operate in accordance with intended use.
Only operate the device in accordance with its intended use.
The protection of personnel and the device cannot be guaranteed if the device is operated in a manner not corresponding to its intended use.
Leuze electronic GmbH + Co. KG is not liable for damages caused by improper use.
Read the technical description before commissioning the device.
Knowledge of this technical description is an element of proper use.
Safety
TNT 35/7-24V
NOTICE
Comply with conditions and regulations!
Observe the locally applicable legal regulations and the rules of the employer's liability
insurance association.
OPERATION NOTICE IN ACCORDANCE WITH UL CERTIFICATION:
CAUTION – Use of controls or adjustments or performance of procedures other than
those specified herein may result in hazardous light exposure.
ATTENTION ! Si d'autres dispositifs d'alignement que ceux préconisés ici sont utilisés ou s'il est procédé autrement qu'indiqué, cela peut entraîner une exposition à
des rayonnements et un danger pour les personnes.
Leuze electronicODS…/ODK… 9 / 96B9
Safety
Attention
For UL applications, use is only permitted in class 2 circuits in accordance with the NEC (National Electric Code).
2.2Foreseeable misuse
Any use other than that defined under the "Approved purpose" or which goes beyond that
use is considered improper use.
In particular, use of the device is not permitted in the following cases:
• Rooms with explosive atmospheres
• in circuits which are relevant to safety
• Operation for medical purposes
NOTICE
Do not modify or otherwise interfere with the device.
Do not carry out modifications or otherwise interfere with the device.
The device must not be tampered with and must not be changed in any way.
The device must not be opened. There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
2.3Competent persons
Connection, mounting, commissioning and adjustment of the device must only be carried
out by competent persons.
Prerequisites for competent persons:
• They have a suitable technical education.
• They are familiar with the rules and regulations for occupational safety and safety at
work.
• They are familiar with the technical description of the device.
• They have been instructed by the responsible person on the mounting and operation
of the device.
Certified electricians
Electrical work must be carried out by a certified electrician.
Due to their technical training, knowledge and experience as well as their familiarity with
relevant standards and regulations, certified electricians are able to perform work on electrical systems and independently detect possible hazards.
In Germany, certified electricians must fulfill the requirements of accident-prevention regulations BGV A3 (e.g. electrician foreman). In other countries, there are respective regulations that must be observed.
10ODS…/ODK… 9 / 96BLeuze electronic
2.4Disclaimer
Leuze electronic GmbH + Co. KG is not liable in the following cases:
• The device is not being used properly.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Changes (e.g., constructional) are made to the device.
2.5Laser safety notices – Laser class 1
Valid for:ODSL 9/…C1…
ODSL 96BM/…C1…
ATTENTION, LASER RADIATION – LASER CLASS 1
The device satisfies the requirements of IEC 60825-1:2007 (EN 60825-1:2007) safety
regulations for a product in laser class 1 as well as the U.S. 21 CFR 1040.10 regulations
with deviations corresponding to "Laser Notice No. 50" from June 24th, 2007.
Adhere to the applicable legal and local regulations regarding protection from laser
beams.
The device must not be tampered with and must not be changed in any way.
There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
Safety
Valid for:ODSIL 96BM/…
ATTENTION, VISIBLE AND INVISIBLE
LASER RADIATION – LASER CLASS 1
The device satisfies the requirements of IEC 60825-1:2007 (EN 60825-1:2007) safety
regulations for a product in laser class 1 as well as the U.S. 21 CFR 1040.10 regulations
with deviations corresponding to "Laser Notice No. 50" from June 24th, 2007.
Adhere to the applicable legal and local regulations regarding protection from laser
beams.
The device must not be tampered with and must not be changed in any way.
There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
Leuze electronicODS…/ODK… 9 / 96B11
TNT 35/7-24V
Safety
2.6Laser safety notices – Laser class 2
Valid for:ODSL 9/… without indicator …C1… in type designation
Never look directly into the beam!
The device satisfies the requirements of IEC 60825-1:2007 (EN 60825-1:2007) safety
regulations for a product in laser class 2 as well as the U.S. 21 CFR 1040.10 regulations
with deviations corresponding to "Laser Notice No. 50" from June 24th, 2007.
Never look directly into the laser beam or in the direction of reflecting laser beams!
If you look into the beam path over a longer time period, there is a risk of injury to the
retina.
Do not point the laser beam of the device at persons!
Intercept the laser beam with an opaque, non-reflective object if the laser beam is
accidentally directed towards a person.
When mounting and aligning the device, avoid reflections of the laser beam off reflec-
tive surfaces!
CAUTION! Use of controls or adjustments or performance of procedures other than
specified herein may result in hazardous light exposure.
Adhere to the applicable legal and local regulations regarding protection from laser
beams.
The device must not be tampered with and must not be changed in any way.
There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
ODSL 96BM/… without indicator …C1… in type designation
ODSLR 96BM/… without indicator …C1… in type designation
ODKL 96BM/… without indicator …C1… in type designation
ATTENTION, LASER RADIATION – LASER CLASS 2
NOTICE
Affix laser information and warning signs!
Laser information and warning signs are affixed to the device (see figure 2.1). In addition,
self-adhesive laser information and warning signs (stick-on labels) are supplied in several
languages (see figure 2.2 and figure 2.3).
Affix the laser information sheet with the language appropriate for the place of use to
the device.
When using the device in the US, use the stick-on label with the "Complies with
21 CFR 1040.10" notice.
Affix the laser information and warning signs near the device if no signs are attached
to the device (e.g. because the device is too small) or if the attached laser information
and warning signs are concealed due to the installation position.
Affix the laser information and warning signs so that they are legible without exposing
the reader to the laser radiation of the device or other optical radiation.
12ODS…/ODK… 9 / 96BLeuze electronic
ODSL(R) 96B with triangulation measurement
TRI
ODSL 9
A Laser exit opening
B Laser warning sign
A
B
A
B
ODSL/ODKL 96B with time-of-flight measurement principle
Potencia máx. (peak):
Duración del impulso:
Longitud de onda:
RADIAÇÃO LASER
NÃO OLHAR FIXAMENTE O FEIXE
EQUIPAMENTO LASER CLASSE 2
EN 60825-1:2007
Potência máx. (peak):
Período de pulso:
Comprimento de onda:
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
IEC 60825-1:2007
Complies with 21 CFR 1040.10
Maximum Output (peak):
Pulse duration:
Wavelength:
䉏⏘戟⺓
▎䦃展⏘㧮
伊䉏⏘ℶ❐
GB7247.1-2012
㦏⮶戢⒉᧤⽿⋋᧥
厘⑁㖐兼㢅梃
㽱栎
248 mW
6,5
n
s
658 nm
248 mW
6,5 ns
658 nm
248 mW
6.5 ns
658 nm
248 mW
6,5 ns
658 nm
248 mW
6,5 ns
658 nm
248 mW
6,5 ns
658 nm
248 mW
6.5 ns
658 nm
248 mW
6.5 ns
658 nm
50108905-04
TOF
Safety
Bild 2.3:Laser warning and information signs – supplied stick-on labels
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B15
The different sensor types
TRI
3The different sensor types
3.1ODSL 9 with triangulation measurement
The ODSL 9 is an optical distance sensor that operates according to the triangulation
measurement principle. Advantages of the ODSL 9:
• For short to medium operating ranges
• High measurement rate
• Very high accuracy
• Measurement against diffusely reflective objects
• Low temperature influence on the measurement value
Overview of sensor features
• Plastic housing with protection class IP 67
• Dimensions 50mm x 50mm x 21mm
• Visible red-light laser
• Operating ranges up to 650mm
• Measurement time 2ms
• Yellow LC display (backlit) for measurement value display and sensor configuration
• Configuration via PC software and programming unit
• 2 short-stroke keys for menu navigation
• 2 device LEDs
16ODS…/ODK… 9 / 96BLeuze electronic
The different sensor types
TRI
TOF
3.2ODS… 96B with triangulation measurement
The ODSL 96B is an optical distance sensor that operates according to the triangulation
measurement principle. Advantages of the ODS… 96B with triangulation measurement principle:
• For short to medium operating ranges
• High measurement rate
• High accuracy
• Measurement against diffusely reflective objects
• Low temperature influence on the measurement value
Overview of sensor features
• Metal housing with protection class IP 67, IP 69K
• Dimensions 90 mm x 70 mm x 30 mm
• Device models with red-light LED, infrared LED and visible red-light laser
• Operating ranges up to 2000mm (range specification in the type designation)
• Minimum measurement time 1ms
• OLED display for measurement value display and sensor configuration
• Configuration via PC software and programming unit
• Labeled key pad with 2 buttons for menu navigation
• 2 device LEDs each at the sensor front and back
3.3ODSL/ODKL/ODSIL 96B with time-of-flight measurement
The ODSL/ODKL/ODSIL 96B is an optical distance sensor that operates according to the
time-of-flight measurement principle. Advantages of the time-of-flight measurement principle:
• For large ranges
• High immunity against light interference
• Low influence of gloss and structures on the measurement value
• Measurement against diffusely reflective objects (ODSL/ODSIL 96B) or reflective
tapes (ODKL 96B)
• Wide area of application
Overview of sensor features
• Metal housing with protection class IP 67, IP 69K
• Dimensions 90 mm x 70 mm x 30 mm
• Device models with infrared-light laser and visible red-light laser
• Operating ranges up to 10m diffuse or 25m against high gain foil
(no range specification in the type designation)
• Minimum measurement time 1.4ms
• OLED display for measurement value display and sensor configuration
• Configuration via PC software and programming unit
• Labeled key pad with 2 buttons for menu navigation
• 2 device LEDs each at the sensor front and back
Leuze electronicODS…/ODK… 9 / 96B17
TNT 35/7-24V
Description ODSL 9
LC display
128 x 32 pixels
2 short-stroke keys
LED
status displays
4Description ODSL 9
4.1General description
The ODSL 9 is a distance sensor with an extensive area of application. The devices are
available as a laser version with analog output or serial output as well as with 1 to 2 switching
outputs. The distance measuring device operates on the triangulation principle and uses a
CMOS line for evaluating.
Through automatic adjustment of the integration time (exposure time) to the intensity of the
objects' reflected light, a high degree of independence from the reflectivity properties of the
measurement object is achieved.
An integrated RISC controller facilitates brief measurement times while at the same time
providing highly precise measurement values. The high-performance hardware is also able
to preprocess measurement data directly in the sensor.
The standard measurement range lies between 50 … 450mm. One model for greater
ranges covers the measurement range from 50 … 650mm. Both models have an output
resolution of 0.1 mm. Higher resolution models are available with a measurement range of
50 … 100mm or 50 … 200mm. Its output resolution is 0.01mm.
Two short-stroke keys and a backlit LC display are integrated into the device. They allow the
ODSL 9 to be configured via a graphical menu. During measurement operation, the display
shows the current measurement value. The sensor can be protected against unauthorized
operation by password protection.
The configuration software available from www.leuze.com
products by means of a PC and visualization of the ODSL 9's measurement values. Moreover,
stored parameter sets can be duplicated in other distance sensors. The connection is made
via the configuration adapter, which is available as an accessory (UPG10).
allows configuration of the ODSL 9
18ODS…/ODK… 9 / 96BLeuze electronic
Bild 4.1: Indicator and operating elements of the ODSL 9
Accessories
The configuration software as well as a UPG 10 configuration adapter are available for configuring the ODSL 9 from a PC.
Mounting systems and connection cables in various lengths and configurations round off the
accessories.
Details can be found in chapter 11.
4.2Typical areas of application for the ODSL 9
Typical areas of application for the ODSL 9 are:
• Positioning of actuators and robots
• Height and width measurement as well as determination of diameter
• Quality assurance in assembly lines
• Contour measurement of moving objects
Laser light spot:1mm x 1 mm
Application examples
Description ODSL 9
Bild 4.2: Application example: wood width measurement with the ODSL 9
Leuze electronicODS…/ODK… 9 / 96B19
TNT 35/7-24V
Description ODSL 9
Bild 4.3: Application example: installation check with the ODSL 9
Notice
For mounting instructions please refer to chapter 6.2.
20ODS…/ODK… 9 / 96BLeuze electronic
4.3ODSL 9 variants
TRI
TRI
TOF
Model variations
The ODSL 9 is available as a laser distance sensor (red light) . Measurement ranges:
50… 100 mm with absolute measurement accuracy ±0.5%, resolution 0.01mm
50… 200mm with absolute measurement accuracy ±0.5… ±1.0%, resolution 0.01… 0.1 mm
50… 450 mm with absolute measurement accuracy ±1.0%, resolution 0.1mm
50… 650 mm with absolute measurement accuracy ±1.0%, resolution 0.1 … 0.5mm
4.3.1Type code
Use the following table to determine the equipment features of your ODSL 9.
Description ODSL 9
OD S L 9/ V 6.C1 -450 -S12
Connection typeS12M12 connector
Operating range in
mm ()
Laser class
Switching output
Measurement data
output
Light sourceLlaser
Target objectSmeasurement against diffusely reflective objects
10050 … 100 mm, High Res., resolution 0.01mm
20050 … 200 mm, resolution 0.01 … 0.1mm
45050 … 450 mm, resolution 0.1mm
65050 … 650 mm, resolution 0.1 … 0.5mm
.C1laser class 1
N/Alaser class 2
61 push/pull output
662 push/pull outputs
Canalog current output
Vanalog voltage output
LIO-Link interface
D2serial RS 232 interface
D3serial RS 485 interface
ODoptical distance sensor
Notice
According to their measurement principle, this manual also refers to the sensors in
brief as triangulation sensors and as time-of-flight sensors and partly distinguishes
them in the text by means of different colors:
AArea not definedStarting at abt. 650mm or
BLinearity not defined
CMeasurement range
DObject present
ENo object detected
1000mm, "No Signal" is
displayed and a value of 0V or
0mA is output at the analog
output.
FMeasurement distance
Bild 4.4: Behavior of the ODSL 9 analog output (factory setting)
22ODS…/ODK… 9 / 96BLeuze electronic
Description ODSL 9
Response of the analog output
The ODSL 9 M/C or M/V has an analog output with linear behavior inside of the respective
measurement range. There is a departure from linearity above and below the linear area. If
a signal is present, output values above the maximum (> 20mA or > 10V) or below the
minimum (< 4mA or < 1V) specified for the measurement range can still be detected.
For ODSL 9 models with voltage output, it is also possible to set the voltage range of the
output.
The analog output can be easily configured using the LC display or via software. In order to
achieve the highest resolution possible, the range of the analog output should be set as
small as the application allows. The characteristic output curve can be configured with a
positive or negative gradient. For this purpose, both distance values Position Min. Val.
and Position Max. Val. for the minimum and maximum analog output value are set
accordingly, see figure 4.4.
Alternatively, the analog output can also be taught via pin 2 (see chapter "Teach-in of the
switching outputs/characteristic output curve (time control)").
Behavior of the switching output
In addition, a switching output is also available with the ODSL 9 M/C and M/V. The position
within the measuring range at which the switching output becomes active can be set arbitrarily via a teach line or via configuration. In addition to the switching point, it is also possible
to set the switching hysteresis and switching behavior (light/dark switching) using the shortstroke keys or the configuration software.
Teach-in of the characteristic output curve
In addition to edge-controlled teach-in of the switching outputs (slope control), the
ODSL 9 with analog output can also be used to perform a time-controlled teach-in of swit-ching output and characteristic output curve (time control) via the teach line. Both teach
events are described in chapter 7.3.
Leuze electronicODS…/ODK… 9 / 96B23
TNT 35/7-24V
Description ODSL 9
4.5ODSL 9/L with IO-Link interface
The sensors are equipped with an IO-Link interface for measurement data output. The
sensor cyclically transfers a data packet of 2 bytes at a baud rate of 38.4 k (COM2,
Frame 2.2, Vers. 1.0) to the IO-Link master module. The sensor has no switching output; the
SIO mode is not supported.
The process data and parameters are described in the IODD (IO-Link Device Description).
You can download the IODD on the Internet from www.leuze.com
The ODSL 9/L… can be configured on the PC with a generic IODD interpreter. To do this,
the PC is connected to the PC via an IO-Link master.
4.5.1IO-Link process and service data
IO-Link process data
Output data device
A15 A14 A13 A12 A11 A10 A9A8A7A6A5A4A3A2A1A0
MSB
16 bit measurement value:distance
1 bit output resolution:0.01mm/0.1 mm (type dependent)
Signal too weak:65535
Laser error: 65533
16 bit measurement value
.
Data bit
LSB
IO-Link service data
Sensors with IO-Link interface can be configured and diagnosed via the service data.
Measure mode parameter
With this parameter, a measure mode can be activated for adapting to the application task.
There are four measurement modes (Standard, Precision, Speed and Light Suppres-
sion) to choose from.
Measure filter parameter
With this parameter, a measurement value filter can be activated for adapting to the application task. Three options are available (Off, Averaging and Center Value).
Notice
Detailed information on the parameters can be found in chapter 7.
24ODS…/ODK… 9 / 96BLeuze electronic
Description ODSL 9
4.5.2IO-Link system commands and diagnostics (observation)
System commands
Laser transmitter activation
This system command switches on the laser transmitter.
Laser transmitter deactivation
This system command switches off the laser transmitter.
If the sensor is deactivated, then the most recently determined measurement value is frozen.
The state of the laser can be monitored in the sensor state.
Setting to factory setting
This system command restores the factory settings of the sensor.
Diagnostics (observation)
Signal too weak [process value 65535] or laser error [process value 65533]
Reception signal is not sufficient: Either no object is in the measurement range or the signal
from the object is too low for measurement. A displayed laser error indicates a laser-light
source malfunction.
Signal warning
Low reception signal: The object is not detected reliably, e.g. because the signal from the
object is very weak.
Laser activation
Status information on whether the laser transmitter is activated or deactivated.
Measurement range sensor
Status information on whether an object is located in the measurement range of the sensor.
Notice
If parameters are changed on the device via the display and keyboard, it is not signaled to
the master. When there is an explicit query by the master, however, the changed value is
available.
Notice
Detailed information about the IO-Link service data and the IODD can be found at
www.leuze.com
Leuze electronicODS…/ODK… 9 / 96B25
.
TNT 35/7-24V
Description ODSL 9
4.6ODSL 9/D with serial interface
The ODSL 9/D… sensors are equipped with one switching output and one serial interface,
which is implemented either as an RS 232 interface (ODSL 9/D2…) or as an RS 485 interface (ODSL 9/D3…).
The transmission rate can be set to between 9,600 and 57,600 baud.
Serial transmission is performed with 1 start bit, 8 data bits and 1 stop bit without parity.
For the transmission of the measurement values, 4 different transmission modes may be
configured (see figure 4.5):
• ASCII measurement value
(6 bytes)
• 14-bit measurement value
(2 bytes, ODS 96 compatible)
• 16-bit measurement value
(3 bytes, ODSL 30 compatible)
• Remote control operation
4.6.1Measurement value output for various transmission types
Object distanceMeasurement value output
No evaluable receive signal65535 (signal too weak)
< Measurement range
Within measurement range
> Measurement range
Device error65333 (laser error)
Distance value
(undefined linearity)
Distance value
linear
Distance value
(undefined linearity)
26ODS…/ODK… 9 / 96BLeuze electronic
707070
0001
xx1 0
7070
Measurement value = 16 bit
output resolution 0.01mm/0.1 mm (type dependent)
1. Low Byte (bit 0 = 0, bit 1 = 0)
Measurement value = 14 bit
output resolution 0.01mm/0.1 mm (type dependent)
Measurement value ASCII transmission
Transmission format: MMMMM<CR>
MMMMM= 5-digit measurement value in 0.1 mm (for 0.1 mm output resolution)
or= 5-digit measurement value in 0.01mm (for 0.01mm output resolution)
<CR>= ASCII character "Carriage Return" (x0D)
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0 (LSB)
bit 11
bit 10
bit 9
bit 8
bit 7
bit 6
don’t care
don’t care
bit 15 (MSB)
bit 14
bit 13
bit 12
2. Middle Byte (bit 0 = 1, bit 1 = 0) 3. High Byte (bit 0 = 0, bit 1 = 1)
1. Low Byte (bit 0 = 0)2. High Byte (bit 0 = 1)
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0 (LSB)
bit 13 (MSB)
bit 12
bit 11
bit 10
bit 9
bit 8
bit 7
Remote control operation
ASCII transfer of the measurement value on request
4 digits (4 bytes) or 5 digits (5 bytes).
0
1
Description ODSL 9
Bild 4.5: Serial transmission formats ODSL 9
Leuze electronicODS…/ODK… 9 / 96B27
TNT 35/7-24V
Description ODSL 9
4.6.2Commands for remote control operation
For remote-control operation (Serial -> Com Function -> Remote control), a device
address can be set between 0 and 14 (Serial -> Node Address).
In this operating mode, the ODSL 9/D only responds to commands from the control. The
following control commands are available:
Measurement value query, 4 digits:
Byte no.Response
0 12345678
CommandSensor
Sensor
response
address
0x00
through
0x0E
"
"
*
(0x2A)
––––––––
ASCII addressASCII distance measurement value
tensones1'000's100'stensones
Measurement value query, 5 digits:
Byte no.Response
0 1 2 345678
Command
Sensor
response
(0x2A)
(0x2A)
ASCII
"
address
"
*
"0…9",
"A…D"
ASCII
"
address
"
*
"0…9",
"A…D"
"M"
"#"
(0x4D)
(0x23)
ASCII distance measurement value
10'000's 1'000's 100'stensones
–––––
Execute referencing function:
Byte no.Response
Command
Sensor
response
0 1 2 345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"R"
(0x52)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Detailed information on referencing can be found in chapter 7.8.2
"#"
(0x23)
State
–
"#"
(0x23)
time
max.
15ms
time
max.
15ms
time
max.
2s
Execute preset measurement:
Command
Sensor
response
Byte no.Response
0 1 2 345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"P"
(0x52)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
time
max.
2s
28ODS…/ODK… 9 / 96BLeuze electronic
Description ODSL 9
Detailed information on Preset/Offset can be found in chapter 7.8.1
Activate sensor:
Byte no.Response
Command
Sensor
response
0 1 2345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"A"
(0x41)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Deactivate sensor:
Byte no.Response
Command
Sensor
response
0 1 2345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"D"
(0x44)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Status byte (bitwise processing):
Bit numberMeaning
7 (MSB)
0 (LSB)
always = 0 (reserved)
1 = other error (e.g. no measurement possible or referencing / preset not successful), 0 = OK
6
always = 1
5
always = 0 (reserved)
4
always = 0 (reserved)
3
1 = sensor deactivated, 0 = sensor activated
2
1 = no signal or signal too low, 0 = signal OK
1
1 = laser interference, 0 = Laser OK
time
max.
15ms
time
max.
15ms
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B29
Description ODSL 9
+24 V
15 kΩ
470 Ω
1,5 kΩ
A (Tx+)
B (Tx-)
4.6.3Termination of the data lines of the ODSL 9/D3…
The ODSL 9/D3… features a combined transmitter and receiver component that can
transmit serial data according to the RS 485 and RS 422 standard (see TIA/EIA-485-A or
DIN66259, Part 3).
These standards define some basic rules that should be followed in order to achieve the
most reliable data transmission:
• The data lines A and B (which correspond to the ODSL 9 pins Tx+ and Tx-) are connected to an intrinsic impedance of Z
• The end of the data line (and the beginning in case of RS 485) is terminated using a
120Ω resistor. The ODSL 9/D3… does not have an internal bus termination.
• The RS 485 bus participants are wired in an in-line bus topology, i.e., the data line is
fed from one bus participant to the next. Cable stubs are to be avoided or to be kept
as short as possible.
• The RS 485 specification assumes an inactive potential difference of U
between the data lines. A bus termination in the form of a voltage divider should be
implemented in order to maintain this level. Usually, it is connected to the RS 485
coupling module of the PLC.
The RS 485 specification permits transmission rates in the megabit range for up to
32 participants. The ODSL 9/D3… is designed for a data transmission rate of typically
9600 baud (9600 … 57600 baud may be configured). In practice, this means that the strict
requirements regarding the bus termination and the cabling are "softened" for a few bus
participants.
However, it is important to maintain the bus idle levels (U
module does not include a bus termination with voltage divider, the following circuit may be
used.
≈ 120Ω via a 2-wire twisted pair cable.
0
≥ 200mV
AB
≥ 200mV). If the PLC coupling
AB
30ODS…/ODK… 9 / 96BLeuze electronic
Bild 4.6: Voltage divider for the RS 485 bus termination
The RS 422 connection does not require a bus termination for cable lengths up to about
20m and data transmission rates less than 9600 Baud.
Further information:
• RS 422: Electrical Specification acc. to DIN 66259, Part 3
• ISO 8482: Abstract
Specifies the physical medium characteristics for twisted pair multipoint interconnections in either 2-wire or 4-wire network topology, a binary and bi-directional signal
transfer, the electrical and mechanical design of the endpoint system branch cables
and the common trunk cable which may be up to 1200m in length, the component
measurements of the integrated type generators and receivers within the endpoint
system, the applicable data signaling rate up to 12.5Mbit/s.
4.6.4Operation on the fieldbus and the Ethernet
ODSL 9/D2 sensors… with an RS 232 serial interface can be connected with MA 2xxi
modular interfacing units to the following fieldbus and Ethernet types:
•PROFIBUSDP–> MA 204i
• Ethernet TCP/IP–>MA 208i
• CANopen–>MA 235i
• EtherCAT–>MA 238i
•PROFINET-IO–> MA 248i
• DeviceNet–>MA 255i
• EtherNet/IP–>MA 258i
To do this, the modular interfacing unit is connected to the sensor via a connection cable.
To operate the distance sensors, rotary switch S4 of the modular interfacing unit must be set
to switch position B.
Further details can be found in the technical descriptions of the modular interfacing units.
Description ODSL 9
Notice
The default settings of the ODS serial interface have to be adjusted. Further information on
configuration of the interface can be found in the technical description of the corresponding
device.
Specifications for the serial interface
COM function:ASCII
Baud rate:38400 baud
The ODSL 9/D2… is to be operated in the "Precision" measure mode. The mode is set
through the display menu via
chapter 7.2.6).
Leuze electronicODS…/ODK… 9 / 96B31
Application -> Measure mode -> Precision (see
TNT 35/7-24V
Description ODSL 9
+U
B
2nd switching output
1st switching output
Measurement
distance [mm]
Max. 100mm:50100
Max. 450mm:50450
Max. 650mm:50650
4.7ODSL 9/66 with two switching outputs
Bild 4.7: Behavior of the switching outputs ODSL 9/66
The two switching outputs of the ODSL 9/66 work independently of each other. Upper and
lower switching points as well as hysteresis can be set separately for both switching outputs
via the LC display or the configuration software.
Via the teach input, either the upper or the lower measurement range limit can be taught for
both switching outputs or, alternatively, the center of the switching range. A common teach
line is available for both switching outputs. An exact description of the teach event can be
found in chapter 7.3.
32ODS…/ODK… 9 / 96BLeuze electronic
Description ODS… 96B/ODK… 96B
TRI
TOF
TRI
TOF
5Description ODS… 96B/ODK… 96B
5.1General description
The ODS… 96B/ODK… 96B is a distance sensor with a large area of application. The
devices are available as LED or laser version with analog or serial output. Two different
measurement principles are applied:
Measurement principle: Triangulation
When using the triangulation measuring procedure, the distance of an object is determined
via the angle of incidence of the light reflected by the object. For the actual measurement, a
linear CMOS array is used. The measurement principle is suitable for medium operating
ranges and permits a fast measurement rate and high accuracy.
Through automatic adjustment of the integration time (exposure time) to the intensity of the
objects' reflected light, a high degree of independence from the reflectivity properties of the
measurement object is achieved. In case of low reflectivity (dark objects) a longer measurement time results. The sensor sets the measurement time automatically.
The measurement range extends from 60 - 2,000 mm (depending on sensor model).
Measurement principle: time-of-flight
In the time-of-flight measurement procedure, the distance of an object is determined via the
propagation time of a light pulse emitted by the sensor's transmitter that is reflected by the
object and received by the sensor's receiver. The measurement principle is suitable for large
operating ranges with simultaneous immunity to light interference and a low influence of
gloss and structures on the measurement value. The measurement time can be adjusted via
the configuration software or via membrane keyboard and OLED display. It remains fixed.
The measurement range extends from 300 - 25,000mm (depending on sensor model).
Notice
The type designation indicates which measurement principle your sensor uses:
• Sensors with triangulation measurement principle include an operating range
specification in the type designation. Example: ODSL 96B M/C6-2000-S12.
• Sensors with time-of-flight measurement principle do not include an operating
range specification in the type designation. Example: ODSL 96B M/C6-S12.
According to their measurement principle, the sensors are in the following also referred to in brief as triangulation sensors and as time-of-flight sensors and are partly
distinguished in the text by means of different colors:
•= triangulation sensors
•= time-of-flight sensors
Leuze electronicODS…/ODK… 9 / 96B33
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
LED
Status displays
OLED display
128 x 32 pixels
Key pad with
2 buttons
LED
status displays
All device models feature an integrated RISC controller for brief measurement times with
simultaneous high precision measurement values. The high-performance hardware is also
able to preprocess measurement data directly in the sensor.
A key pad and an OLED display are integrated into the device, which allow the ODS… 96B/
ODK… 96B to be configured via a graphical menu. During measurement operation, the
display shows the current measurement value. A lockable cover on the back of the
ODS… 96B/ODK… 96B and password protection safeguard the sensor against unauthorized operation.
The configuration software available from www.leuze.com
ODS… 96B/ODK… 96B sensors with a PC and visualization of the measured values. Moreover, stored parameter sets can be duplicated in other distance sensors. The connection is
made via the configuration adapter, which is available as an accessory (UPG10).
allows configuration of the
Bild 5.1: Display and operational controls ODS… 96B/ODK… 96B
Accessories
A configuration software as well as a UPG 10 configuration adapter are available for configuring the ODS… 96B/ODK… 96B from a PC.
The housing dimensions of the ODS… 96B/ODK… 96B distance sensors are identical to
those of the sensors of the 96 series from Leuze electronic. In particular, the mounting
accessories of the 96 series can be used for the ODS… 96B/ODK… 96B.
For ODKL 96B sensors, a special high-gain reflective tape is available.
Mounting systems and connection cables in various lengths and configurations round off the
accessories.
Details can be found in chapter 11.
34ODS…/ODK… 9 / 96BLeuze electronic
Description ODS… 96B/ODK… 96B
TRI
5.2Typical areas of application for the ODS… 96B/ODK… 96B
Due to the high number of sensor models and light spot geometries, the ODS… 96B/
ODK… 96B is suitable for nearly all areas of application.
Notice
For mounting instructions please refer to chapter 6.2.
ODS 96B with infrared or red-light LED, measurement range 100 … 1400mm ():
• Measurement on large surface objects, e.g., bulk material, material on drums, sheet
material
• brightVision
LED light spot:15mm x 15 mm
Output resolution:0.1mm
Application example
®
– very bright light spot with LED red light
TNT 35/7-24V
Bild 5.2: Application example: fill level measurement with ODS 96B (TRI)
Leuze electronicODS…/ODK… 9 / 96B35
Description ODS… 96B/ODK… 96B
TRI
ODSL 96B with laser, measurement range 60 … 2000mm ():
• Measurement in millisecond cycles for large operating ranges
• Stable and precise measurement values, even at varying temperatures and object
variations
ODSL 96B "S" with laser, measurement range 150 … 800mm ():
• Small laser light spot for the precise measurement onto small objects, metallic surfaces or objects with color structures
Laser light spot:1mm x 1 mm
Output resolution:0.1mm
Application example
Bild 5.4: Application example: robot arm positioning with ODSL 96B "S" (TRI)
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B37
Description ODS… 96B/ODK… 96B
TRI
ODSL 96B "XL" with laser, measurement range 150 … 1200 mm ():
• Elongated light spot for precise measurement on perforated or porous objects
(e.g., corrugated cardboard), and on objects that are not precisely aligned
Characteristic output curve of the triangulation laser model
AArea not definedStarting at abt. 1500mm or
BLinearity not defined
CMeasurement range
DObject present
ENo object detected
3000mm, "No Signal" is
displayed and a value of 0V or
0mA is output at the analog
output.
FMeasurement distance
Bild 5.9: Behavior of the analog output on the triangulation laser model (factory setting)
44ODS…/ODK… 9 / 96BLeuze electronic
Description ODS… 96B/ODK… 96B
TOF
0 abt. 200 30025000 26500 abt. 30000
0 abt. 200
300
60006300abt. 10000
U [V]
abt. 10.5
10
1
0
I [mA]
abt. 21
20
4
1
Laser+ refl. tape:
Laser:
Characteristic output curve of the time-of-flight laser model
Leuze electronicODS…/ODK… 9 / 96B45
AArea not definedStarting at abt. 10,000mm or
BLinearity not defined
CMeasurement range
DObject present
ENo object detected
30,000mm, "No Signal" is
displayed and a value of 0V or
0mA is output at the analog
output.
FMeasurement distance
Bild 5.10:Behavior of analog output of the time-of-flight laser model (factory setting)
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
TRI
TOF
TRI
TOF
Response of the analog output
The ODS… 96B/ODK… 96B M/C or M/V has an analog output with linear behavior inside of
the respective measurement range. There is a departure from linearity above and below the
linear area. If a signal is present, output values above the maximum (> 20 mA or > 10V) or
below the minimum (< 4mA or < 1 V) specified for the measurement range can still be
detected.
For the models with voltage output, it is also possible to set the voltage range of the output.
The analog output can be easily configured using the OLED display or via software. In order
to achieve the highest resolution possible, the range of the analog output should be set as
small as the application allows. The characteristic output curve can be configured with a
positive or negative gradient. For this purpose, the two distance values
Position Min. Val. and Position Max. Val. are set appropriately for the minimum and
maximum analog output values, see figure 5.8, figure 5.9 and figure 5.10.
Alternatively, the analog output can also be taught via pin 2 (see chapter 7.3 "Configuration
example - lower switching point").
Behavior of the switching output
In addition, a switching output is also available with the ODS… 96B/ODK… 96B M/C and M/
V. The position within the measuring range at which the switching output becomes active
can be set arbitrarily via a teach line or via configuration. In addition to the switching point,
it is also possible to set the switching hysteresis and switching behavior (light/dark switching)
using the key pad or the configuration software.
Teach-in of the characteristic output curve
There are different teach methods depending on the device model ( or ):
•:
In addition to edge-controlled teach-in of the switching outputs (slope control), the
ODS… 96B with analog output can also be used to perform a time-controlled teach-in of switching output and characteristic output curve (time control) via the teach
line. Both teach events are described in chapter 7.4.2.
•:
For the ODS… 96B with time-of-flight measurement principle, there is only a timecontrolled teach model. The time intervals for the individual teach functions are,
however, considerably different to those of the triangulation sensors. This teach event
is described in chapter 7.4.3.
46ODS…/ODK… 9 / 96BLeuze electronic
Description ODS… 96B/ODK… 96B
5.5ODS… 96B/ODK… 96B M/L with IO-Link interface
The sensors are equipped with an IO-Link interface for measurement data output. The
sensor cyclically transfers a data packet of 2 bytes at a baud rate of 38.4 k (COM2,
Frame 2.2, Vers. 1.0) to the IO-Link master module. The sensor has no switching output; the
SIO mode is not supported.
The process data and parameters are described in the IODD (IO-Link Device Description).
You can download the IODD on the Internet from www.leuze.com.
The ODS… 96B/ODK… 96B M/L can be configured on the PC with a generic IODD
interpreter. To do this, the PC is connected to the PC via an IO-Link master.
5.5.1IO-Link process and service data
IO-Link process data
Output data device
Data bit
A15 A14 A13 A12 A11 A10 A9A8A7A6A5A4A3A2A1A0
MSB
16 bit measurement value:distance
1 bit output resolution:1mm
Signal too weak:65535
Signal error: 65534
Laser error: 65533
16 bit measurement value
LSB
IO-Link service data
Sensors with IO-Link interface can be configured and diagnosed via the service data.
Measure mode parameter
With this parameter, a measure mode can be activated for adapting to the application task.
There are four measurement modes (Standard, Precision, Speed and Light Suppres-
sion) to choose from.
Measure filter parameter
With this parameter, a measurement value filter can be activated for adapting to the application task. Three options are available (Off, Averaging and Center Value).
Notice
Detailed information on the parameters can be found in chapter 7.
Leuze electronicODS…/ODK… 9 / 96B47
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
5.5.2IO-Link system commands and diagnostics (observation)
System commands
Laser transmitter activation
This system command switches on the laser transmitter.
Laser transmitter deactivation
This system command switches off the laser transmitter.
If the sensor is deactivated, then the most recently determined measurement value is frozen.
The state of the laser can be monitored in the sensor state.
Setting to factory setting
This system command restores the factory settings of the sensor.
Diagnostics (observation)
Signal too weak [process value 65535], signal error [process value 65534] or laser
error [process value 65533]
Reception signal is not sufficient: either no object is in the measurement range or the signal
from the object is too low for measurement. A permanently displayed signal error indicates
that the sensor has a defect. A displayed laser error indicates a laser-light source malfunction.
Signal warning
Low reception signal: the object is not detected reliably, e.g. because the signal from the
object is very weak.
Laser activation
Status information on whether the laser transmitter is activated or deactivated.
Measurement range sensor
Status information on whether an object is located in the measurement range of the sensor.
Notice
If parameters are changed on the device via the display and keyboard, it is not signaled to
the master. When there is an explicit query by the master, however, the changed value is
available.
Notice
Detailed information about the IO-Link service data and the IODD can be found at
www.leuze.com
48ODS…/ODK… 9 / 96BLeuze electronic
.
Description ODS… 96B/ODK… 96B
5.6ODS… 96B/ODK… 96B M/D with serial interface
The sensors are equipped with one switching output and one serial interface, which is implemented either as an RS 232 interface or as an RS 485 interface. The transmission rate can
be set to between 9,600 and 57,600 baud.
Serial transmission is performed with 1 start bit, 8 data bits and 1 stop bit without parity.
For the transmission of the measurement values, 4 different transmission modes may be
configured (see figure 4.5):
• ASCII measurement value
(6 bytes)
• 14-bit measurement value
(2 bytes, ODS 96 compatible)
• 16-bit measurement value
(3 bytes, ODSL 30 compatible)
• Remote control operation
5.6.1Measurement value output for various transmission types
Object distanceMeasurement value output
No evaluable receive signal65535 (signal too weak)
< Measurement range
Within measurement range
> Measurement range
Device error
Distance value
(undefined linearity)
Distance value
linear
Distance value
(undefined linearity)
65334 (signal error)
65333 (laser error)
Leuze electronicODS…/ODK… 9 / 96B49
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
7070
0
1
Measurement value = 16 bit
output resolution 0.1mm/1 mm (type dependent)
1. Low Byte (bit 0 = 0, bit 1 = 0)
Measurement value = 14 bit
output resolution 0.1mm/1 mm (type dependent)
Measurement value ASCII transmission
Transmission format: MMMMM<CR>
MMMMM= 5-digit measurement value in mm (for 1 mm output resolution)
or= 5-digit measurement value in 0.01mm (for 0.1mm output resolution)
<CR>= ASCII character "Carriage Return" (x0D)
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0 (LSB)
bit 11
bit 10
bit 9
bit 8
bit 7
bit 6
don’t care
don’t care
bit 15 (MSB)
bit 14
bit 13
bit 12
2. Middle Byte (bit 0 = 1, bit 1 = 0) 3. High Byte (bit 0 = 0, bit 1 = 1)
1. Low Byte (bit 0 = 0)2. High Byte (bit 0 = 1)
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0 (LSB)
bit 13 (MSB)
bit 12
bit 11
bit 10
bit 9
bit 8
bit 7
Remote control operation
ASCII transfer of the measurement value on request
4 digits (4 bytes) or 5 digits (5 bytes).
707070
0001
xx1 0
Bild 5.11:ODS… 96B/ODK…96B M/D serial transmission formats
5.6.2Commands for remote control operation
For remote-control operation (Serial -> Com Function -> Remote control), a device
address can be set between 0 and 14 (Serial -> Node Address).
In this operating mode, the ODS 96B M/D only responds to commands from the control. The
following control commands are available:
50ODS…/ODK… 9 / 96BLeuze electronic
Measurement value query, 4 digits:
TRI
Description ODS… 96B/ODK… 96B
Byte no.Response
CommandSensor
Sensor
response
0 12345678
address
0x00
through
0x0E
"
*
(0x2A)
––––––––
ASCII addressASCII distance measurement value
"
tensones1'000's100'stensones
Measurement value query, 5 digits:
Byte no.Response
0 1 2 345678
Command
(0x2A)
Sensor
response
(0x2A)
Execute the referencing function (only for
Command
(0x2A)
Sensor
response
(0x2A)
ASCII
"
address
"
*
"0…9",
"A…D"
ASCII
"
address
"
*
"0…9",
"A…D"
"M"
"#"
(0x4D)
(0x23)
ASCII distance measurement value
10'000's 1'000's 100'stensones
–––––
):
Byte no.Response
0 1 2 345678
ASCII
"
address
"
*
"0…9",
"A…D"
ASCII
"
address
"
*
"0…9",
"A…D"
"R"
(0x52)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Detailed information on referencing can be found in chapter 7.8.2
"#"
(0x23)
State
–
"#"
(0x23)
time
max.
15ms
time
max.
15ms
time
max.
2s
Execute preset measurement:
Command
Sensor
response
Byte no.Response
0 1 2 345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"P"
(0x52)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
time
max.
2s
Detailed information on Preset/Offset can be found in chapter 7.8.1
Leuze electronicODS…/ODK… 9 / 96B51
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
Activate sensor:
Byte no.Response
Command
Sensor
response
0 1 2345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"A"
(0x41)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Deactivate sensor:
Byte no.Response
Command
Sensor
response
0 1 2345678
ASCII
"
*
(0x2A)
"
*
(0x2A)
address
"
"0…9",
"A…D"
ASCII
address
"
"0…9",
"A…D"
"D"
(0x44)
State
"#"
(0x23)
"#"
(0x23)
–––––
–––––
Status byte (bitwise processing):
Bit numberMeaning
7 (MSB)
0 (LSB)
always = 0 (reserved)
1 = other error (e.g. no measurement possible or referencing / preset not successful), 0 = OK
6
always = 1
5
always = 0 (reserved)
4
always = 0 (reserved)
3
1 = sensor deactivated, 0 = sensor activated
2
1 = no signal or signal too low, 0 = signal OK
1
1 = laser interference, 0 = laser OK
time
max.
15ms
time
max.
15ms
52ODS…/ODK… 9 / 96BLeuze electronic
Description ODS… 96B/ODK… 96B
+24 V
15 kΩ
470 Ω
1,5 kΩ
A (Tx+)
B (Tx-)
5.6.3Termination of the data lines of the OD… 96B/D3…
The OD… 96B/D3… features a combined transmitter and receiver component that can
transmit serial data according to the RS 485 and RS 422 standard (see TIA/EIA-485-A or
DIN66259, Part 3).
These standards define some basic rules that should be followed in order to achieve the
most reliable data transmission:
• The data lines A and B (which correspond to the OD… 96B pins Tx+ and Tx-) are
connected to an intrinsic impedance of Z
• The end of the data line (and the beginning in case of RS 485) is terminated using a
120Ω resistor. The OD… 96B/D3… does not have an internal bus termination.
• The RS 485 bus participants are wired in an in-line bus topology, i.e., the data line is
fed from one bus participant to the next. Cable stubs are to be avoided or to be kept
as short as possible.
• The RS 485 specification assumes an inactive potential difference of U
between the data lines. A bus termination in the form of a voltage divider should be
implemented in order to maintain this level. Usually, it is connected to the RS 485
coupling module of the PLC.
The RS 485 specification permits transmission rates in the megabit range for up to
32 participants. The OD… 96B/D3… is designed for a data transmission rate of typically
9600 baud (9600 … 57600 baud may be configured). In practice, this means that the strict
requirements regarding the bus termination and the cabling are "softened" for a few bus
participants.
However, it is important to maintain the bus idle levels (U
module does not include a bus termination with voltage divider, the following circuit may be
used.
≈ 120Ω via a 2-wire twisted pair cable.
0
AB
≥ 200mV
AB
≥ 200mV). If the PLC coupling
Bild 5.12:Voltage divider for the RS 485 bus termination
Leuze electronicODS…/ODK… 9 / 96B53
The RS 422 connection does not require a bus termination for cable lengths up to about
20m and data transmission rates less than 9600 Baud.
TNT 35/7-24V
Description ODS… 96B/ODK… 96B
Further information:
• RS 422: Electrical Specification acc. to DIN 66259, Part 3
• ISO 8482: Abstract
Specifies the physical medium characteristics for twisted pair multipoint interconnections in either 2-wire or 4-wire network topology, a binary and bi-directional signal
transfer, the electrical and mechanical design of the endpoint system branch cables
and the common trunk cable which may be up to 1200m in length, the component
measurements of the integrated type generators and receivers within the endpoint
system, the applicable data signaling rate up to 12.5Mbit/s.
5.6.4Operation on the fieldbus and the Ethernet
OD… 96B/D2… sensors with an RS 232 serial interface can be connected with MA 2xxi
modular interfacing units to the following fieldbus and Ethernet types:
•PROFIBUSDP–> MA 204i
• Ethernet TCP/IP–>MA 208i
• CANopen–>MA 235i
•EtherCAT–> MA 238i
•PROFINET-IO–> MA 248i
• DeviceNet–>MA 255i
• EtherNet/IP–>MA 258i
To do this, the modular interfacing unit is connected to the sensor via a connection cable.
To operate the distance sensors, rotary switch S4 of the modular interfacing unit must be set
to switch position B.
Further details can be found in the technical descriptions of the modular interfacing units.
Notice
The default settings of the ODS serial interface have to be adjusted. Further information on
configuration of the interface can be found in the technical description of the corresponding
device.
Specifications for the serial interface
COM function:ASCII
Baud rate:38400 baud
The OD… 96B/D2… is to be operated in the "Precision" measure mode. The mode is set
through the display menu via
chapter 7.2.6).
54ODS…/ODK… 9 / 96BLeuze electronic
Application -> Measure mode -> Precision (see
Description ODS… 96B/ODK… 96B
+U
B
2nd switching output
1st switching output
Measurement
distance [mm]
Lower limit of meas. rangeUpper limit of meas. range
5.7ODS… 96B/ODK…96B M/66 with two switching outputs
Bild 5.13:Behavior of the switching outputs ODS… 96B/ODK… 96B M/66
The two switching outputs of the ODS… 96B/ODK… 96B M/66 operate independently of
each other. Upper and lower switching points as well as hysteresis can be set separately for
both switching outputs via the OLED display or the configuration software.
Via the teach input, either the upper or the lower measurement range limit can be taught for
both switching outputs or, alternatively, the center of the switching range. A common teach
line is available for both switching outputs. An exact description of the teach event can be
found in chapter 7.3.
Leuze electronicODS…/ODK… 9 / 96B55
TNT 35/7-24V
Installation
TRI
6Installation
6.1Storage and transport
Attention!
When transporting or storing, package the sensor so that it is protected against collision and
humidity. Optimum protection is achieved when using the original packaging. Heed the required environmental conditions specified in the technical data.
Unpacking
Check the packaging for any damage. If damage is found, notify the post office or ship-
ping agent as well as the supplier.
Check the delivery contents using your order and the delivery papers:
• Delivered quantity
• Device variant and model as indicated on the nameplate
• Laser warning signs
• Technical description
The name plate provides information as to what type of distance sensor your device is.
Save the original packaging for later storage or shipping.
If you have any questions concerning your shipment, please contact your supplier or your
local Leuze electronic sales office.
Observe the applicable local regulations when disposing of the packaging materials.
6.2Mounting
Mounting systems are available which have to be ordered separately at Leuze electronic.
The order number can be found in chapter 11.3 and chapter 11.4. Apart from this, the drilledthrough holes are suitable for the individual mounting of the ODS, depending on the area in
which it is to be used.
Installation
To avoid errors while the object enters the measurement beam, correct entry direction of the
objects has to be observed for sensors with triangulation principle (). The following
graphics show instructions on the installation:
56ODS…/ODK… 9 / 96BLeuze electronic
Installation
Only for !
TRI
Only for !
TRI
and !
TRI
TOF
Preferred direction of entry of the objects when using triangulation sensors
Bild 6.1: Preferred direction of entry of the objects when using triangulation sensors
Preferred mounting of triangulation sensors for structured surfaces
Bild 6.2: Preferred mounting of triangulation sensors for structured surfaces
View through a chase
Bild 6.3: View through a chase
If the distance sensors have to be installed behind a cover, the chase has to have at least
the size of the optical glass cover. Otherwise, a correct measurement is not possible or can
not be guaranteed.
Leuze electronicODS…/ODK… 9 / 96B57
TNT 35/7-24V
Installation
reflecting surface
Only for !
TRI
Alignment to measurement objects with reflecting surfaces
Bild 6.4: Alignment to measurement objects with reflecting surfaces
If the measurement object to be detected has a reflecting surface, a measurement may not
be possible depending on the angle in which the light is reflected by the measurement
object's surface. The directly reflected part of the transmitted light beam must not be incident
on the receiver of the distance sensor. Adjust the angle between the sensor and the
measurement object such that the sensor can reliably detect the measurement object.
58ODS…/ODK… 9 / 96BLeuze electronic
7Operation
LED
status displays
OLED display
128 x 32 pixels
screw-down
cover
LED
status displays
ODSL 9
ODS…/ODK… 96B
LED
status displays
LC display
128 x 32 pixels
2 short-stroke keys:
upper key=
lower key=
key pad with
2 buttons
cover opened
7.1Indicator and operating elements
Operation
Bild 7.1: Indicator and operating elements
The device LEDs display the operating state. For the ODS… 96B/ODK… 96B, the device
LEDs have an identical function on the front and back of the distance sensor. During
Leuze electronicODS…/ODK… 9 / 96B59
measurement operation, the dot matrix display shows the distance measurement value.
TNT 35/7-24V
Operation
7.1.1LED status displays
LEDStateDisplay during sensor operation
continuous lightready
green
yellow
Tabelle 7.1: LED function indicator
During teach-in, the LED indicator deviates from the information shown in Table 7.1 and
varies depending on the selected teach mode. Detailed information on this topic can be
found in chapter 7.3.
7.1.2Control buttons
The LC display and control buttons of the ODSL 9 are always accessible. The OLED display
and key pad of the ODS… 96B/ODK… 96B are protected by a screw-down cover.
Notice
For the ODS… 96B/ODK… 96B, safety class II at a rated voltage of 250V AC is only ensured
with the cover closed.
flashinginterference
offno supply voltage
continuous lightobject inside teach-in measurement range
offobject outside teach-in measurement range
The ODS is operated using the and
Notice
button on sensors of the ODSIL design (TOF sensors with infrared laser) ser-
The
ves to switch on/off the red alignment laser.
Notice
The control buttons of the ODSL 9 are not labeled:
• The upper key corresponds to the
• The lower key corresponds to the
60ODS…/ODK… 9 / 96BLeuze electronic
buttons, which are located next to the display.
button of the ODS… 96B/ODK… 96B.
button of the ODS… 96B/ODK… 96B.
7.1.3Displays
255mm
255mm
low
No Signal
X
255mm
255mm
255mm
X
255mm
+
0
255mm
+
R
The display changes depending on the current operating mode. There are the following two
display modes:
•Measure mode
• Menu display
The menu display is accessed by pressing one of the two control buttons.
Operation via the menu is described in chapter 7.2.
After switching on the supply voltage +U
the green LED illuminates continuously, the distance sensor is in measure mode.
In measure mode, the current measurement value is displayed in the
display, e.g. 255mm.
Notice
After a warmup time of 20 min., the device has reached the operating temperature required
for an optimum measurement.
Status displays in measure mode
In case of a weak reception signal, "Low" appears in the display.
If no object is detected or if the signal is too weak, "No Signal" appears
in the display.
If the current measurement value of sensors with analog output exceeds the range for the
analog output, an arrow appears on the right next to the measurement value.
An arrow pointing downward indicates that the current measurement
value is lower than the lower limit of the analog output.
An arrow pointing upward indicates that the current measurement value
is larger than the upper limit of the analog output.
Operation
and following error-free initialization of the device,
B
If the laser has been deactivated, then "
If a distance calibration has been performed, then "+O" or "+R" appear in the display.
The "+O" display appears if an offset or preset was activated.
The "+R" display appears if the referencing function has been activated.
Leuze electronicODS…/ODK… 9 / 96B61
X
" appears in the display
TNT 35/7-24V
Operation
255mm
255mm
Signal Error
Input
Output Q1
Q1 Upper Sw. Pt
Q1 Upper Sw. Pt.
0250 mm
Q1 Hysteresis
1 016 mm
Q1 Hysteresis
0010 mm
Q1 Hysteresis
0010 mm
Q1 Hysteresis
0010 mm
Errors at the Q1/Q2 switching outputs are indicated as follows.
Lightning bolt icon with an underlying point:
short-circuit at switching output Q1 or configuration adapter UPG10
connected, but PC not connected.
Lightning bolt icon with underlying bar:
short-circuit at switching output Q2.
A wrench icon with the text "Signal Error" indicates a signal error. A
permanently displayed signal error indicates that the sensor has a
defect.
7.1.4Operation/navigation
In menu display, the display has two lines. The and buttons both have different functions depending on the operating situation. These functions are represented via icons on the
right edge of the display – i.e. to the immediate left of the buttons.
The following situations can occur:
Menu navigation
selects the next menu item (Output Q1)
switches to the submenu shown with inverted colors (Input)
selects the next menu item (Q1 Upper Sw. Pt)
returns to the next higher menu (). At the top menu level, the
menu can be exited here (
edge indicates the current menu level:
Menu Exit). The number of bars at the left
Selecting values or selection parameters for editing
selects the next menu item ( -> Q1 Lower Sw. Pt)
selects edit mode for Q1 Upper Sw. Pt
Editing value parameters
changes the value of the first digit (1)
selects the second digit (0) for editing
changes the edit mode;
saves the new value (0010)
changes the edit mode,
selects the first digit (0) for renewed editing. If an impermissible
value was entered, the "new entry" icon initially appears and the checkmark is not available for selection.
changes the edit mode,
rejects the new value (1016 remains saved)
62ODS…/ODK… 9 / 96BLeuze electronic
appears
appears
or appears
Editing selection parameters
Input Polarity
Active Low 0V
Input Polarity
Active High +24V
Input Polarity
Active High +24V
Input Polarity
Active High +24V
FactorySettings
Execute
displays the next option for input polarity (Active High +24V)
returns to the input menu and retains Active Low 0V
shows the next option for input polarity (Active Low 0V)
selects the new value Active High +24V and displays the confir-
mation menu:
changes the edit mode;
saves the new value (Active High +24V)
Operation
changes the edit mode;
saved)
7.1.5Reset to factory settings
Press the
ODK… to the state upon delivery from the factory.
Press the
All settings made previously are permanently lost. Press , and the
ODS…/ODK… returns to measurement operation without resetting the
parameters.
You can also use the menu or the configuration software to reset to factory settings (see
chapter 7.2.7).
button while switching on the device to reset the configuration of the ODS…/
button again to reset all parameters to the factory settings.
rejects the new value (Active Low 0V remains
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B63
Operation
TRI
TRI
TOF
TRI
7.2Configuration / menu structure
7.2.1Input
The Input menu only appears if your sensor has a binary input. The function of the input at
pin 2 is set in the Input menu.
Level 1Level 2Level 3Explanation / NotesDefault
Input
Output Q1
Input Mode
Teach Time Ctrl.
Input Mode
Teach Time Ctrl.
Input Polarity
Active High +24V
Input Polarity
Active High +24V
Output Q1
Output Q2
Input Mode
Tabelle 7.2: Input menu
Input Mode
Teach Time Ctrl.
Input Mode
Teach Slope Ctrl.
Input Mode
Teach
Input Mode
Trigger
Input Mode
Activation
Input Mode
Preset
Input Mode
Dist. Referencing
Input Polarity
Active High +24V
Input Polarity
Active Low 0V
Defines how the input at pin 2 behaves when UB is applied. Only one of
the 4 or 6 options can be selected
with
.
Teaching analog output and switching output, see chapter 7.4.2, only
Only teaches switching output, see
chapter 7.4.2, only
Teaching analog output and switching output, see chapter 7.4.3, only
Triggers a measurement value output
(edge controlled), see chapter 7.5
Switches on the laser beam (level
controlled)
Preset via teach-in, see
chapter 7.8.1
Referencing via teach-in, see
chapter 7.8.2, only
Defines the polarity of the input
signal for Input Mode
Input activated at +24V
Input activated at 0V
X
s
X
64ODS…/ODK… 9 / 96BLeuze electronic
7.2.2Output Q1
Hysteresis
Measurement distance
ON
OFF
Lower
switching point
Upper
switching point
Hysteresis
ON
OFF
Light switching
Dark switching
The Output Q1 menu only appears if your sensor has a binary output Q1. It is used to set
the switching behavior of switching output Q1.
Operation
Level 1Level 2Level 3Explanation / NotesDefault
Output Q1
Analog Output
Q1 Upper Sw. Point
0600 mm
+ for
changing the values
Adjusts the switching
behavior of output Q1
Upper switching point
Q1 Lower Sw. Point
0200 mm
+ for
changing the values
Lower switching point
Q1 hysteresis
0050 mm
+ for
changing the values
Hysteresis
Q1 Light/Dark
Dark Switching
Q1 Light/Dark
Dark Switching
Q1 Light/Dark
Dark Switching
Q1 Light/Dark
Light Switching
Dark switching
Light switching
Tabelle 7.3: Menu Output Q1
1)You can determine the values for your sensor using the type key on page 21 and the appropriate
data in chapter 10.1. For ODSL 96B sensors with time-of-flight measurement principle, the
assured measurement range 300 … 6,000mm applies (6 … 90 % diffuse reflection).
The adjustable parameters have the following meaning:
• Light switching: If an object is located between the upper and lower switching point,
the switching output is active (high).
• Dark switching: If an object is located between the upper and lower switching point,
the switching output is not active (low).
• Hysteresis: Expansion of the switching range for switching off. For switching on, the
set switching points remain always valid.
Upper limit of meas.
1)
range/2
Lower limit of meas.
1)
range
10x minimum
sensor resolution
X
1)
TNT 35/7-24V
Bild 7.2: Behavior of the switching outputs
Leuze electronicODS…/ODK… 9 / 96B65
Operation
7.2.3Output Q2
The Output Q2 menu only appears if your sensor has a binary output Q2. It is used to set
the switching behavior of switching output Q2. The adjustable parameters correspond to
those of output Q1.
Level 1Level 2Level 3Explanation / NotesDefault
Output Q2
Analog Output
Q2 Upper Sw. Point
0600 mm
+ for
changing the values
Adjusts the switching
behavior of output Q2
Upper switching point
Q2 Lower Sw. Point
0200 mm
+ for
changing the values
Lower switching point
Q2 Hysteresis
0050 mm
+ for
changing the values
Hysteresis
Q2 Light/Dark
Dark Switching
Q2 Light/Dark
Dark Switching
Q1 Light/Dark
Dark Switching
Q1 Light/Dark
Light Switching
Dark switching
Light switching
Analog Output
Serial
Q1 Upper Sw. Point
Tabelle 7.4: Menu Output Q2
1)You can determine the values for your sensor using the type key on page 21 and the appropriate
data in chapter 10.1. For ODSL 96B sensors with time-of-flight measurement principle, the
assured measurement range 300 … 6,000mm applies (6 … 90% diffuse reflection).
Upper limit of
meas. range/2
Lower limit of
meas. range
10x minimum sensor resolution
1)
1)
1)
X
66ODS…/ODK… 9 / 96BLeuze electronic
7.2.4Analog Output
The Analog Output - menu only appears if your sensor has an analog output. It is used to
adjust the characteristic output curve of the analog output.
Operation
Level 1Level 2Level 3Explanation / NotesDefault
Analog Output
Serial
Position Max. Val.
2000 mm
+ for
changing the values
Position Min. Val.
2000 mm
+ for
changing the values
Analog Range
1 - 10 V
Analog Range
1 - 10 V
Analog Range
1 - 10 V
Analog Range
0 - 10 V
Analog Range
1 - 5 V
Analog Range
0 - 5 V
Serial
Application
Position Max. Val.
Sets the behavior of the
analog output
Distance measurement
value for maximum voltage / maximum current
Distance measurement
value for minimum voltage
/ minimum current
Analog Range only
appears for sensors with
voltage output.
X
The function sets the vol-
tage range of the analog
voltage output.
Sensors with current output are permanently set to
4…20mA.
The Analog Range menu
item does not appear for
these sensors.
Tabelle 7.5: Analog Output menu
1)You can determine the values for your sensor using the type key on page 21 and the appropriate
data in chapter 10.1. For ODSL 96B sensors with time-of-flight measurement principle, the
assured measurement range 300 … 6,000mm applies (6 … 90 % diffuse reflection).
For sensors with voltage output, select the voltage range of the analog output. Then set the
distance which corresponds to the lower range limit (0V, 1V or 4 mA) at the analog output
and the distance which corresponds to the upper range limit (5V or 10V or 20 mA). This lets
you spread the characteristic output curve according to your requirements.
It is also possible to invert the working range of the analog output, i.e., the selected value of
the lower range limit is larger than that of the upper range limit. This creates a descending
characteristic output curve.
Upper limit of
meas. range
Lower limit of
meas. range
1)
1)
TNT 35/7-24V
Notice
The adjustable working ranges are dependent on the selected device type and must lie within the sensor's measurement range. The check to determine whether the entered values
are plausible and valid is performed after the upper and lower limits are entered. Invalid values cannot be saved. You can either change the entered value (
without saving (
).
) or cancel the entry
Leuze electronicODS…/ODK… 9 / 96B67
Operation
7.2.5Serial
The Serial - menu only appears if your sensor has a serial interface. It is used to adjust the
serial interface parameters.
Level 1Level 2Level 3Explanation / NotesDefault
Serial
Application
COM Function
ASCII
COM Function
ASCII
Baud rate
9600 Bd
Baud rate
9600 Bd
Node Address
01
Application
Settings
Com Function
Tabelle 7.6: Serial menu
COM Function
ASCII
COM Function
14 bit
COM Function
16 bit
COM Function
Remote Control
Baud rate
9600 Bd
Baud rate
19200 Bd
Baud rate
38400 Bd
Baud rate
57600 Bd
+ for
changing the values
Sets the transmission parameters
of the serial output
Sets the format of the measurement
value output, see chapter 4.6.
Measurement value output corresponding to the device resolu-
tion, see figure 4.5
2-byte transmission, compatible
with ODS 96, see figure 4.5
3-byte transmission, compatible
with ODSL 30, see figure 4.5
Remote control operation of the
ODS 96B via remote commands,
see chapter 4.6.2
Adjusts the transmission rate of the
serial interface
9600 Bd
19200 Bd
38400 Bd
57600 Bd
Address under which the ODS 96B
is addressed
X
X
68ODS…/ODK… 9 / 96BLeuze electronic
7.2.6Application
TRI
TOF
In the Application menu, the measurement function of the sensor can be optimized for the
given application. Several measure modes, measurement filters and a distance calibration
are available for this purpose. Details on the function can be found in chapter 7.6 to
chapter 7.8.
Level 1Level 2Level 3Explanation / NotesDefault
Application
Settings
Measure Mode
Standard
Measure Mode
Standard
Measure Filter
Off
Measure Filter
Off
Tabelle 7.7: Application menu
Measure Mode
Standard
Measure Mode
Precision
Measure Mode
Speed
Measure Mode
Light Suppression
Measure Filter
Off
Measure Filter
Averaging
Measure Filter
Center Value
Measure Filter
Peak
Measure Filter
Range
Sets the measure mode.
See chapter 7.6.
Standard mode
Precision mode
Fast measurement
Extraneous light suppression 1)
Filters the measurement
results.
See chapter 7.7.
Off
Floating average calculation
Median
Filters individual measure-
ment jumps
Measurement value output
only within the limit values set
for Range Upper Pos. and
Range Lower Pos.
2)
2)
Operation
X
X
X
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B69
Operation
Level 1Level 2Level 3Explanation / NotesDefault
Measurem. Count
10
Measurem. Count
10
Measurem. Count
10
Measurem. Count
20
Measurem. Count
30
Measurem. Count
40
Measurem. Count
50
Measurem. Count
07
Sets the number of measurement values which are read in
for the Average and Center Value filters.
For Center Value: selection
in steps of 10:
10 measurement values
20 measurement values
30 measurement values
40 measurement values
50 measurement values
For Averaging: Set from
1…99
+ for changing the
values
Filter Depth
Coarse
Filter Depth
Coarse
Filter Depth
Coarse
Filter Depth
Medium
Filter Depth
Fine
Sets the filter depth for the
Center Value measurement
filter. Prevents falsification of
the average value by "outliers".
A small number of extreme
values are not taken into
account.
Some extreme values are not
taken into account.
A large number of extreme
values are not taken into
account.
Peak Window
Medium
Peak Window
Medium
Peak Window
Medium
Peak Window
Fine
For the Peak measurement filter, sets the minimum deviation
of the measurement values
from the previous measurement value
Medium change in measure-
ment value
Small change in measurement
value
2)
Range Upper Pos.
2000 mm
Upper limit for the Range
measurement filter
2)
Tabelle 7.7: Application menu
X
01
X
X
Upper limit
of meas.
range
70ODS…/ODK… 9 / 96BLeuze electronic
Operation
TRI
TRI
TRI
TRI
Level 1Level 2Level 3Explanation / NotesDefault
Range Lower Pos.
0200 mm
Lower limit for the Range
measurement filter.
2)
Distance Correct.
Off
Distance Correct.
Off
Distance Correct.
Off
Distance Correct.
Offset/Preset
Distance Correct.
Referencing
Enables the correction of the
measurement value by a fixed
2)
value.
Measurement value unchan-
ged.
Offset / Preset, see
chapter 7.8.1
Via referencing, see
chapter 7.8.2, for only
Offset
+500 mm
+ for
changing the values
Setting the offset value in
[mm], see chapter 7.8.1
Preset Position
+300 mm
+ for
changing the values
Setting the preset value
in [mm], see chapter 7.8.1
Pres.-Offs. Calc.
No
Pres.-Offs. Calc.
No
Pres.-Offs. Calc.
No
Pres.-Offs. Calc.
Execute
Calculation of the preset/offset value. To do this,
Distance Correct. -> Offset/Preset must first be
activated.
For further information, see
chapter 7.8.1
2)
Ref. Position
+300 mm
+ for
changing the values
Nominal position of the reference object, see chapter 7.8.2
(for only)
Execute the referencing function. This requires
Distance Correct. ->
Referencing to be activated
in advance (for only).
For further information, see
chapter 7.8.2
Settings
Menu Exit
Ref. Calculation
No
Measure Mode
Ref. Calculation
No
Ref. Calculation
Execute
Tabelle 7.7: Application menu
1) Only for ODSL 96B M/C6.C1S-1500-S12 5012 and ODSL 96B M/V6.C1S-1500-S12 ().
2) Sensors with an IO-Link interface do not have this menu item available.
2)
2)
Lower limit
of meas.
range
X
0mm
Upper limit
of
measure-
ment
range
/ 2
Upper limit
of
measure-
ment
range
/ 2
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B71
Operation
7.2.7Settings
In the Settings - menu, information on the ODS can be called up and set in the display.
Level 1Level 2Level 3Explanation / NotesDefault
Settings
Menu Exit
Tabelle 7.8: Settings menu
Language
English
Language
English
Display
On
Display
On
Factory Settings
Inactive
Factory Settings
Inactive
Password Check
Inactive
Password Check
Inactive
Language
English
Language
Deutsch
Language
Francais
Language
Espanol
Language
Italiano
Display
On
Display
Off
Display
Auto
Factory Settings
Inactive
Factory Settings
Execute
Password Check
Inactive
Password Check
Activated
Setting of the display language
Display language English
Display language German
Display language French
Display language Spanish
Display language Italian
Display settings
Always on with maximum
brightness
Off; is switched back on after
keyboard actuation
Display set to full brightness after
keyboard actuation for abt. 1min.,
dimmed thereafter
Reset to factory settings
The ODS 96B is not reset to factory
settings
The ODS 96B is reset to factory
settings
Blocks access to the menu with the
permanent password "165"
Not active
Active
X
X
X
72ODS…/ODK… 9 / 96BLeuze electronic
Operation
Level 1Level 2Level 3Explanation / NotesDefault
Menu Exit
Input
Info
Display
Part No.
50106594
Serial No.
01403000490
Software
V01.10
Part No.
Returns information regarding the
device
Leuze - Part No., see chapter 11.2
Serial number
Software version
Tabelle 7.8: Settings menu
Leuze electronicODS…/ODK… 9 / 96B73
TNT 35/7-24V
Operation
Input
Output Q1
Output Q1
Output
Q1 Upper Sw. Pt.
0250 mm
Q1 Lower Sw. Pt.
1016 mm
Q1 Lower Sw. Pt.
1 016 mm
Q1 Lower Sw. Pt.
0016 mm
Q1 Lower Sw. Pt.
0100 mm
Q1 Lower Sw. Pt.
0100 mm
Q1 Upper Sw. Pt
Output Q2
Analog Output
Menu Exit
Input
225 mm
7.3Configuration example - lower switching point
To illustrate menu operation, we will explain how to set the lower switching point of switching
output Q1 to 100mm as an example
In the measure mode, press a button (once or twice) until the menu
appears.
Press ; Output Q1 appears in the top menu line.
Press
Press again; Q1 Lower Sw. Pt. appears in the upper menu line.
Press
ching point value is displayed with inverted colors.
Press as many times as necessary to set the desired value 0.
Accept the value by pressing
digits.
After pressing
of the display. The
accepted. This behavior of the
(re-edit value) and a (eject value) then appear in succession.
Once you have completed the setting, accept the value by pressing
colors, and the new value, saved in non-volatile memory, is displayed.
Repeatedly press until appears in the upper menu line.
Press
Repeatedly press until Menu Exit appears in the upper menu
line.
Press
ration.
Notice
The selectable or editable values are shown with inverted text colors (black on light-blue
background).
If no button is pressed in the configuration menu within 120s, the brightness is then reduced.
If no button is pressed in the 60 s after that, the device automatically returns to measure mode.
The device can be protected against unintentional changes to the configuration by activating
the password function (see table 7.8 on page 72). The password is always set to "165".
to select Output Q1.
to set the lower switching point. The first digit of the swit-
; repeat the procedure for all other
for the 4th time, a appears in the lower right part
indicates that the next time
button can be changed by repeatedly pressing . A
; now, Q1 Lower Sw. Pt. is again displayed with inverted
to access the next-higher menu level.
to exit the menu and return to normal measurement ope-
is pressed, the set value will be
74ODS…/ODK… 9 / 96BLeuze electronic
7.4Teach-in
Teach point
600100
Teach point
600100
Teach point
600100
Switching points and characteristic output curves can also be set through teach-in without
using the software. The following instructions require that you have familiarized yourself with
the operation of the ODS using the control buttons and the display.
7.4.1Setting the teach point
The settings made via the menu or software for the two values Q1 Upper Sw. Point and
Q1 Lower Sw. Point determine the point which is to be taught (applies in an analogous way
for Q2). In the following examples, we will consider an ODS 96B with 100 … 600mm
measurement range.
Q1 Lower Sw. Point > 100 mm AND Q1 Upper Sw. Point < 600 mm
If both switching points are set to a value ≠ Lower limit of measurement range or Upper
limit of measurement range using the menu or software, the difference between the two
values defines a switching range. The teach point is the center of the switching range.
Example:
• Q1 Lower Sw. Point = 400mm
• Q1 Upper Sw. Point = 500mm
• yields a switching range of 100mm
The teach point lies in the middle of the switching range.
If a distance of e.g. 300mm is now taught, the Q1 switches on at 250mm and back off at 350mm.
Q1 Lower Sw. Point = 100 mm AND Q1 Upper Sw. Point < 600 mm
If the lower switching point is set to the Lower limit of measurement range using the
menu or software, the upper switching point is taught.
Example:
• Q1 Lower Sw. Point = 100mm
• Q1 Upper Sw. Point = 357mm
The teach point defines the upper switching point. If a
distance of e.g. 300mm is now taught, the Q1 switches
on at 100mm and back off at 300mm.
Operation
TNT 35/7-24V
Q1 Lower Sw. Point > 100 mm AND Q1 Upper Sw. Point = 600 mm
If the upper switching point is set to the Upper limit of measurement range using the
menu or software, the lower switching point is taught.
Example:
• Q1 Lower Sw. Point = 225mm
• Q1 Upper Sw. Point = 600mm
The teach point defines the lower switching point. If a
distance of e.g. 300mm is now taught, the Q1 switches on
at 300mm and back off at 600mm.
Leuze electronicODS…/ODK… 9 / 96B75
Operation
TRI
7.4.2Teach-in for triangulation sensors
Teach-in of the switching outputs (slope control)
In this teach mode, the teach event is performed in the same way as with the ODS 96.
On the OLED display, activate menu item:
Input -> Input Mode -> Teach slope control
Position the measurement object at the desired distance.
Activate the "teach in" input (pin 2) for at least 100 ms (by applying +U
ding on the setting for Input Polarity, see chapter 7.2.1).
The yellow and green LEDs flash simultaneously during this process.
After that, connect the teach input to GND.
You have now taught in the 1st switching output.
If your device has another switching output which you would like to teach:
Position the measurement object at the second desired distance.
Reactivate the "teach in" input (pin 2) for ≥ 2s.
The yellow and green LEDs flash alternately during this process.
After that, connect the teach input to GND.
You have now taught in the 2nd switching output.
The taught switching points are dependent on the settings for the upper and lower switching
point, see "Setting the teach point" on page 75.
or GND, depen-
B
Teach-in of the switching outputs/characteristic output curve (time control)
In addition to the edge controlled teach-in of the switching output, it is also possible to
perform a level-controlled teach-in of switching output and output characteristic curve via the
teach line for ODS… 96B devices with analog output. The following steps are necessary for
the level-controlled teach-in:
If you have changed the factory setting for teaching under Input Mode:
On the OLED display, activate menu item:
Input -> Input Mode -> Teach time control
Position the measurement object at the desired teach distance.
Notice
Please note that the teach distance must lie within the measurement range.
The duration of the activation of the teach input determines the teach step according to the
table shown below. The teach event is indicated by the flashing of the LEDs and on the
display.
76ODS…/ODK… 9 / 96BLeuze electronic
or GND, depending on the setting
B
Operation
Teach functionDuration of
Switching output Q1
Teach point, see chapter 7.4.1
Distance value for start of measurement range =
1V / 4 mA at analog output (pin 5)
Distance value for end of measurement range =
10V / 20 mA at analog output (pin 5)
Table 7.9:LED indicator while teaching the characteristic output curve (time control)
At the end of the given teach event:
Reconnect the teach input to GND.
The menu entries can be used to check that the teach values are properly accepted and to
make any changes.
If the teach event is not successful, the following remedy is possible:
• Repeat teach event or
• Disconnect sensor from voltage to restore the old values.
Notice
If the measurement range start is taught to a distance greater than the measurement range
end, a declining characteristic output curve is automatically set.
Second switching output for Time Control
Sensors with two switching outputs can also be taught in Time Control mode. The LEDs indicate the respective teach step as follows:
• green and yellow LEDs flash simultaneously:Teach switching output Q1
• green LED is on continuously, yellow LED flashes: Teach switching output Q2
teach signal
2 … 4sflash synchronously
4…6s
6 … 8sflashing
Green
LED
continuous
light
Yellow
LED
flashing
continuous
light
Leuze electronicODS…/ODK… 9 / 96B77
TNT 35/7-24V
Operation
TOF
7.4.3Teach-in for time-of-flight sensors
Teach-in of the switching outputs/characteristic output curve
The following steps are required for time-controlled teach-in of TOF sensors:
If you have changed the factory setting for teaching under Input Mode:
On the display, activate menu item:
Input -> Input Mode -> Teach
Position the measurement object at the desired distance.
Activate the "teach in" input (pin 2) (by applying +U
for Input Polarity, see chapter 7.2.1).
The duration of the activation of the teach input determines the teach step according to the
table shown below.
Teach functionDuration T of teach
Switching output Q1
Teach point, see chapter 7.4.1
Switching output Q2 (devices with 2 switching outputs)
Teach point, see chapter 7.4.1
Distance value for start of measurement range =
1V or 4mA at analog output (pin 5)
Distance value for end of measurement range =
10V or 20mA at analog output (pin 5)
Table 7.10: Teach function in correspondence with the duration of the teach signal
The menu entries can be used to check that the teach values are properly accepted and to
make any changes.
or GND, depending on the setting
B
signal
20 … 80ms
120 … 180ms
220 … 280ms
320 … 380ms
T
Active High +24V
Inactive Low 0V
Bild 7.3: Teach signal curve for time-of-flight sensors
Notice
If the inactive level is permanently applied to the teach input, the teach input is locked.
If the menu is set to Input -> Input Mode -> Input polarity -> Active Low +0V, inverted
input signals are used for teaching.
78ODS…/ODK… 9 / 96BLeuze electronic
t
7.5Trigger
TRI
TOF
No continuous measurement occurs while in Input Mode -> Trigger.
An ascending edge at the "teach in" input (pin 2) triggers a single measurement; the
measurement value is present at the output until the next trigger event. This applies for
ODS-models with analog output and serial output.
In this way it is possible to precisely perform individual measurements for the trigger signal
in combination with a photoelectric sensor even in dynamic situations.
7.6Measurement modes
In the Application menu, you can set 3 or 4 different measurement modes. The effect on
the measurement behavior of the ODS depends on the device:
Triangulation sensors
• Standard: Standard setting
• Precision: High accuracy, abt. 95% slower
• Speed: Fast measurement, abt. 30% faster
• Light Suppression: Higher insensitivity towards ambient light
The following table provides an overview of the effects of the individual parameters on the
measurement function.
Tabelle 7.12: Effects of the measurement modes for time-of-flight sensors
Leuze electronicODS…/ODK… 9 / 96B79
TNT 35/7-24V
Operation
7.7Measure filter
In the Application menu, you can set 5 different measurement filters. This affects the
measurement behavior of the ODS as follows:
• Off: No filtering of the measurement values.
• Averaging: A sliding average is calculated and output from the last 2 … 99 measurement values (set the number with Measurem. Count). If the measurement value
changes abruptly, the output value moves linearly over the course of n measurements
from the old measurement value to the new measurement value. Thus, the time for
measurement value updating is not affected by the number of measurements; the
response time for distance changes becomes slower.
• Center Value: Filter out extreme values - the average value is calculated from every
10 … 50 single measurements. The number of single measurements to be used is
selected with Measurem. Count (10, 20, 30, 40 or 50). The setting made under
Filter Depth specifies whether only the most extreme (Coarse), medium (Medium)
or minor deviations (Fine) should be filtered out.
• Peak
• Range
1)
: Filters out jumps in measurement values. Measurement values are only
passed on if the difference to the last measurement value is not too large. Following a
change in distance, the values are not output until the distance value has quieted
back down. The setting under Peak Window is used to specify whether only medium
(Medium) measurement jumps are to be filtered out or if smaller (Fine) jumps are to
be filtered as well.
1)
: The measurement value output is limited to the range which is defined with
Range Lower Pos. and Range Upper Pos., located down further in the menu.
Example with Range Lower Pos. = 300mm and Range Upper Pos. = 400mm:
• for distances < 300mm, 300 mm is output as measurement value
• between 300mm and 400mm, the actual measurement value is output
• for distances > 400mm , 400 mm is output as measurement value.
Notice
For Center Value, the time for measurement value updating increases considerably!
The following table provides an overview of the effects of the individual parameters on the
measurement function.
1) Sensors with an IO-Link interface do not have this menu item available.
80ODS…/ODK… 9 / 96BLeuze electronic
7.8Distance calibration
Using the Distance Correct. 1) menu item, it is possible to influence the measured
distance value.
Notice
Offset and Preset are used for correcting the measurement value by a fixed amount. Referencing, on the other hand, increases the accuracy of measurements in the distance range
near the taught reference distance. To obtain the most exact measurement accuracy possible, referencing should be performed as close to the measurement as possible. Execution
of the referencing function via the teach input is ideally suited for this.
7.8.1Preset or Offset
Deviations which occur while mounting the ODS can be compensated for by the Offset 1) or
1)
Preset
Notice
If calculation of the offset results in negative measurement values, zero is output at the
interface and on the display.
parameter:
•For Offset, a fixed value and sign are specified.
•For Preset, a nominal measurement value is specified; a measurement is then perfor-
med using an object located at the desired nominal distance. The Offset parameter
mentioned above is changed as a result of this measurement.
Operation
Setting the offset
1)
Configuration is performed using the key pad and display:
Select:
Application -> Distance Correct. -> Offset/Preset
Then enter the offset value:
Application -> Offset
The set offset value is added to the measured distance value of the sensor.
Example:
Measurement value of the ODS 96B:1500 mm
Input:Offset: -100 mm
Output on the display and at the interface: 1400mm
1) Sensors with an IO-Link interface do not have this menu item available.
Leuze electronicODS…/ODK… 9 / 96B81
TNT 35/7-24V
Operation
Setting the preset
1)
Configuration is performed using the key pad and display:
Select:
Application -> Distance Correct. -> Offset/Preset
Then enter the preset value:
Application -> Preset Position
Position an object at the desired preset distance.
Perform a preset measurement:
Application -> Pres.-Offs. Calc. -> Execute
The offset value is automatically calculated from the measurement value and nominal
measurement value (preset value) and entered as the offset in the configuration.
Example:
Input:Preset value: 1400mm,
Object dist. 1300mm in front of ODSL 96B: Preset Calculation ...active, trigger measurement
with Execute, an offset of +100mm is automatically
stored
Object distance 1300mm:Output on display and at interface: 1400mm
Object distance 1400mm:Output on display and at interface: 1500mm
Notice
Deactivating Offset / Preset
1)
If the Preset or Dist. Referencing function is activated in the Input menu, then first
activate another function in the Input menu: Teach Time Ctrl., Teach Slope Crtl.,
Teach, Trigger or Activation. Afterwards, the offset correction can be deactivated by
setting the offset value to zero or by selecting a different mode under Distance Correct.
In the latter case, when the "Offset/Preset" mode is reselected, the most recently set offset
and preset values are again available.
1) Sensors with an IO-Link interface do not have this menu item available.
82ODS…/ODK… 9 / 96BLeuze electronic
7.8.2Referencing for triangulation sensors
TRI
TOF
ODS triangulation sensors have a referencing function for the internal calibration of the
sensor.
Notice
The referencing function is not available for time-of-flight sensors ( ).
By carrying out the integrated reference measurement function before a measurement, the
sensor's accuracy can be improved by having the ODS also measure the environmental
conditions during reference measurement. The corrective value determined here is used if
referencing is activated.
Select:
Application -> Distance Correct. -> Referencing
Then enter the reference value:
Application -> Ref. Position
Before referencing, position an object in front of the ODS at the desired reference dis-
tance.
Perform a reference operation:
• Using a command: In remote control mode, see chapter 4.6.2
• Using teach-in: To do this, use the menu or software to activate the
Input -> Input Mode -> Dist. Referencing function.
Then each time the teach input (pin 2) is activated, referencing is performed.
• Using a menu command: Use the menu or software to set
Application -> Distance Correct. -> Referencing, and then execute the
Application -> Ref. Calculation -> Execute menu command.
This starts a one-time referencing operation.
The referencing correction is deactivated by selecting a different mode under
Distance Correct. (Off or Offset/Preset). When the Referencing mode is again
selected, the most recently set reference distance is again available. If re-referencing is not
performed, the old corrective values may result in incorrect measurement values.
Operation
Notice
In particular, the referencing function should be performed for changing environmental conditions. In addition, you should perform referencing prior to all measurements which have
elevated accuracy requirements.
While executing the referencing function (duration abt. 2s), no measurements are possible;
the reference object must remain still during this period!
Notice
For the ODS… 9/96B, referencing is a selective calibration on a target located at a specified
reference distance. The entire measurement system is not referenced as it is with the
ODSL 30.
7.8.3Teach-in of Offset and Preset via the binary input
Activate the desired function through the Input menu:
Leuze electronicODS…/ODK… 9 / 96B83
TNT 35/7-24V
Operation
TRI
TRI
TOF
Input Mode -> Preset or Distance Referencing (only)
Before distance calibration, position an object in front of the sensor at the desired dis-
Distance calibration with triangulation sensors
Activate the "teach in" input (pin 2) (by applying +UB or GND, depending on the setting
The duration of the activation of the teach input determines the teach step according to the
table shown below. The teach event is indicated by the flashing of the LEDs and on the
display.
tance.
for Input Polarity, see chapter 7.2.1).
Teach functionDuration of teach
signal
Preset or Distance Referencing2 … 4 sflash synchronously
Table 7.14: Distance calibration via binary input with triangulation sensors
Green
LED
Yellow
LED
Distance calibration for time-of-flight sensors
Activate the "teach in" input (pin 2) (by applying +UB or GND, depending on the setting
for Input Polarity, see chapter 7.2.1).
The duration of the activation of the teach input determines the teach step according to the
table shown below.
Teach functionDuration of teach signal
Preset20 … 80ms
Table 7.15: Distance calibration via binary input with time-of-flight sensors
84ODS…/ODK… 9 / 96BLeuze electronic
8Configuration software
Distance sensor
UPG 10
To the PC
Connection cable to the
power supply unit
General description
The configuration software make it possible to operate all ODSL 9, ODS... 96B/ODK 96 B,
with the exception of the sensors with an IO-Link interface.
For sensors with IO-Link, please observe the notes in chapter 4.5 and chapter 5.5.
The configuration software can be used together with a connected distance sensor to create
device configurations.
Without a connected distance sensor the program works in the Demo mode.
You can download the software on the Internet from www.leuze.com
8.1Connecting to a PC
The distance sensor is connected to a PC via the UPG 10 configuration adapter. The
adapter is simply inserted between the sensor and the connection cable. The UPG 10 is
connected to the PC via the serial interface cable that ships with the UPG 10.
Configuration software
.
Leuze electronicODS…/ODK… 9 / 96B85
Bild 8.1: Connecting the distance sensor via the UPG 10 configuration adapter
TNT 35/7-24V
Configuration software
8.2Installing the configuration software
Requirements for the installation of the configuration software:
• Pentium
• At least 64 MB free main memory (RAM)
• Hard disk with at least 30 MB free memory
• RS 232 interface for sensor configuration
•Microsoft
Installation
You can download the configuration software on the Internet from www.leuze.com. The software is located under the Download tab of the selected distance sensor.
Copy the file into a suitable folder on your storage drive and unpack the zip file.
Start the installation by double-clicking on the "setup.exe" file. Administrator privileges
are necessary for this purpose.
®
or faster Intel® processor (or compatible models, e.g. AMD®)
®
Windows 98/NT/2000/XP/7
8.3Starting the program
After successful installation and restart of the computer, the configuration software is ready
to use.
Select the ODS configuration software icon from the program group.
If no sensor is connected, the software boots in demo mode.
Notice
The ODS configuration software automatically finds the UPG 10 on the serial ports COM1
to COM10. If a non-supported COM port, e.g. COM11, is assigned during the automatic
installation of the serial driver, then a COM port supported by the software must be assigned
to operate the UPG 10.
You can adapt the COM port setting as follows:
In the operating system, assign the value 1 to the system variable
"devmgr_show_nonpresent_devices" (System control -> System -> Advanced
system settings -> Environmental variable).
86ODS…/ODK… 9 / 96BLeuze electronic
Configuration software
Bild 8.2: System variable "devmgr_show_nonpresent_devices"
Open the device manager and in the "View" menu select the menu item "Show sup-
pressed devices" (System control -> Device manager -> View). Now, under "Connections", all interfaces (including unconnected ones) are shown to which a COM port has
been assigned.
Assign a serial port, COM1 to COM10, to the COM port to which the UPG 10 is con-
nected (Select COM port -> Properties -> Connection settings-> Advanced -> COM
connection number).
Bild 8.3: COM port properties - connection settings "Advanced"
Leuze electronicODS…/ODK… 9 / 96B87
TNT 35/7-24V
Configuration software
8.4ODS configuration software main window
After selecting a device type and confirming with OK, the following window appears:
Bild 8.4: ODS configuration software - main window
The menu bar of the ODS configuration software offers the following functions
• File -> Exit program
• Options -> Language and interface selection. German and English are the available
languages. Under Interface, you must select the COM port to which the distance sensor is connected. The necessary communication parameters are automatically set for
the interface.
88ODS…/ODK… 9 / 96BLeuze electronic
Configuration software
Additional functions can be executed in the main window:
• Start measurement and Stop measurement are used to graphically represent the
measurement values in the main window.
Bild 8.5:ODS configuration software - measurement
•Use Print to send the currently detected measurement curve to the default Windows
printer.
• Save measured values saves the current measurement values in a text file
• Parameterization opens the configuration window, see next chapter
Leuze electronicODS…/ODK… 9 / 96B89
TNT 35/7-24V
Configuration software
8.5Configuration window
The individual menu items are self-explanatory and correspond to the menus of the display
in the distance sensor. Explanations of the possible settings can be found in chapter 7.2.
The command buttons at the bottom of the screen have the following functions:
Load parameters
Loads a saved configuration from the hard disk.
Save parameters
Saves a created configuration on the hard disk.
Factory Settings
Resets the connected distance sensor to factory settings.
Read parameters from ODS
Reads and displays the configuration of the connected ODS 96B.
Write parameters to ODS
Saves the current configuration in the non-volatile parameter memory of the ODS 96B
Quit parameterization
Ends the program
Notice
Leuze electronic can only deliver distance sensors with default settings. You as customer
are responsible for correct storage of your changed data sets. Back-up your device configuration on data carriers.
1) Luminosity coefficient 6 … 90%, complete measurement range, "Standard" operating mode, at 20°C,
medium range U
2) After an operating time of 20 min., the device has reached the operating temperature required for an optimal measurement.
3) Same object, identical environmental conditions, measurement object ≥ 50 x 50mm²
4) Typ. ± 0.02 %/K
5) For UL applications: only for use in "Class 2" electrical circuits according to NEC
6) These sensors shall be used with UL Listed Cable assemblies rated 30 V, 0.5 A min,
in the field installation, or equivalent (categories: CYJV/CYJV7 or PVVA/PVVA7)
5) 6)
YesYesYesYesYes
, measurement object ≥50x50mm²
B
92ODS…/ODK… 9 / 96BLeuze electronic
9.2Electrical data, installation data
Specifications ODSL 9
ODSL 9/ C…ODSL 9/ V…ODSL 9/ D…
Electrical data
Operating voltage U
Residual ripple≤ 15% of U
Bias current≤180mA
Switching outputs
1)
B
2)
1 push/pull output, teachable2 push/pull
18 … 30V DC (incl. residual ripple)
ODSL 9/(C)66…
B
ODSL 9/L…
outputs,
partially
teachable
Signal voltage high/low≥ (UB- 2V) / ≤ 2V
Analog outputcurrent
4 … 20mA,
R
≤ 500Ohm
Output currentmax. 100 mA for each push/pull output
–21
IEC 60825-1:2007,
21 CFR 1040.10 with
Laser Notice No. 50)
Light spot diameterabt. 15 mm
at 600mm distance
divergent min.
2mm x 6mm
divergent, 1mm x 1mm
at 800mm distance ("S")
at 2000mm distance
divergent, 1mm x 1mm
at 800mm distance ("S")
divergent, 15mm x 4mm
at 800mm distance
("XL")
Error limits
Absolute measurement
accuracy
2)
1)
± 1.5%60 … 150mm:
±3mm
±1.5%
150 … 2000mm:
Repeatability
3)
B/W detection thresholds
±0.5%±0.5%±0.5%
≤ 1%≤ 1%≤ 1%
±1.5%
(6%/90 %)
Tem pe ra tu re
yes
4)
yes
4)
yes
4)
compensation
Timing
Measurement time 1 … 5 ms
1)
1…5ms
Response time≤ 15 ms≤ 15ms≤ 180ms
1)
12 … 60ms
1) 5)
1)
Delay before start-up≤ 300ms≤ 300ms≤ 300ms
Certifications
UL508, C22.2No.14-13
6)7)
yesyesno
TNT 35/7-24V
Leuze electronicODS…/ODK… 9 / 96B97
Specifications ODS… 96B/ODK… 96B
1) Luminosity coefficient 6 … 90%, complete measurement range, "Standard" operating mode, at 20°C,
medium range U
2) After an operating time of 20 min., the device has reached the operating temperature required for an optimal
measurement.
3) Same object, measurement object ≥ 50 x 50mm²
4) Typ. ± 0.02 %/K
5) Measurement time in factory setting (ambient light measure mode), operation in other measure modes is
not recommended
6) For UL applications: only for use in "Class 2" electrical circuits according to NEC
7) These sensors shall be used with UL Listed Cable assemblies rated 30 V, 0.5 A min,
in the field installation, or equivalent (categories: CYJV/CYJV7 or PVVA/PVVA7)
, measurement object ³50x50mm²
B
98ODS…/ODK… 9 / 96BLeuze electronic
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.