Lenze 8240 User Manual

Page 1
ED B8220 UE-V020
Show/Hide Bookmarks
!NIh
Operating Instructions
Global Drive
Frequency Inverters 8220/8240 HVAC Series
HVACandPumpDrives Power Range 0.37 - 110 kW
Page 2
qЬЙлЙ lйЙк~нбеЦ fелнкмЕнбзел ~кЙ о~дбЗ Сзк нЬЙ UOuu ЕзенкзддЙкл зС нЬЙ оЙклбзелW
Show/Hide Bookmarks
33.822X- E- 0x. 3x. -V020 (8221 - 8227)
33.824X- E- 1x. 3x. -V020 (8241 - 8246)
Type
Design: B = Module C = Cold Plate E = Enclosure IP20
Hardware level and index
Software level and index
Variante
Explanation
bЗбнбзе зСW MNLMPLNVVV NMLOMMO
кЙоблЙЗ
Page 3

Contents

Show/Hide Bookmarks
1 Preface and general information 1-1..........................
NKN ^Дзмн нЬЙлЙ lйЙк~нбеЦ fелнкмЕнбзел KKK NJNKKKKKKKKKKKKKKKKKKKKKKKKKKKK
NKNKN qЙкгбездзЦу млЙЗ NJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK NKNKO `Ь~еЦЙл бе нЬЙлЙ lйЙк~нбеЦ fелнкмЕнбзел NJNKKKKKKKKKKKKKKKKK
NKO pЕзйЙ зС ЗЙдбоЙку NJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
NKP iЙЦ~д кЙЦмд~нбзел NJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
2 Safety information 2-1.......................................
OKN dЙеЙк~д л~СЙну беСзкг~нбзе OJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
OKO i~узмн зС нЬЙ л~СЙну беСзкг~нбзе OJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
OKP oЙлбЗм~д Ь~т~кЗл OJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
3 Technical data 3-1...........................................
PKN dЙеЙк~д З~н~L~ййдбЕ~нбзе ЕзеЗбнбзел PJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKO o~нЙЗ З~н~ ElйЙк~нбзе пбнЬ NOM B зоЙкдз~ЗF PJOKKKKKKKKKKKKKKKKKKKKKK
PKOKN lйЙк~нбеЦ ЕзеЗбнбзел PJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKOKO qóéÉë UOON íç UOOQ PJPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKOKP qóéÉë UOOR íç UOOT PJQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKOKQ qóéÉë UOQN íç UOQP PJRKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKOKR qóéÉë UOQQ íç UOQS PJSKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKP o~нЙЗ З~н~ ElйЙк~нбзе пбнЬ NRM B зоЙкдз~ЗF PJTKKKKKKKKKKKKKKKKKKKKKK
PKPKN qóéÉë UOON íç UOOQ PJTKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKPKO qóéÉë UOOR íç UOOT PJUKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKPKP qóéÉë UOQN íç UOQP PJVKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKPKQ qóéÉë UOQQ íç UOQS PJNMKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKQ cмлЙл ~еЗ Е~ДдЙ ЕкзллJлЙЕнбзел PJNNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKQKN lйЙк~нбзе зС ЕзенкзддЙкл бе ~ riJ~ййкзоЙЗ лулнЙг PJNNKKKKKKKKK PKQKO pбеЦдЙ ЗкбоЙл пбнЬ NOM B зоЙкдз~З PJNNKKKKKKKKKKKKKKKKKKKKKK PKQKP pбеЦдЙ ЗкбоЙл пбнЬ NRM B зоЙкдз~З PJNOKKKKKKKKKKKKKKKKKKKKKK
PKR ^е~дзЦ йдмЦJбе гзЗмдЙ PJNPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKRKN cЙ~нмкЙл PJNPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKS aбгЙелбзел PJNQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
PKSKN `зенкзддЙк ЗбгЙелбзел PJNQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK PKSKO ^е~дзЦ йдмЦJбе гзЗмдЙ PJNQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
UOOuhäáã~_^NMMO
i
Page 4
Contents
Show/Hide Bookmarks
4 Installation 4-1..............................................
QKN jÉÅÜ~åáÅ~ä áåëí~ää~íáçå QJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
QKNKN fгйзкн~ен езнЙл QJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK QKNKO pн~еЗ~кЗ ~ллЙгДду пбнЬ СбсбеЦ Дк~ЕвЙнл QJOKKKKKKKKKKKKKKKKKK QKNKP ^ллЙгДду зС ~е~дзЦ йдмЦJбе гзЗмдЙ QJPKKKKKKKKKKKKKKKKKKKKK
QKO bдЙЕнкбЕ~д белн~дд~нбзе QJQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
QKOKN fгйзкн~ен езнЙл QJQKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK QKOKO mзпЙк ЕзееЙЕнбзел QJRKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
QKOKOKN j~бел ЕзееЙЕнбзе QJRKKKKKKKKKKKKKKKKKKKKKKKKK QKOKOKO jзнзк ЕзееЙЕнбзе QJSKKKKKKKKKKKKKKKKKKKKKKKKK QKOKOKP `зееЙЕнбзе Зб~Цк~г QJVKKKKKKKKKKKKKKKKKKKKKKK
QKOKP `зенкзд ЕзееЙЕнбзел QJNMKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
QKOKPKN `зенкзд Е~ДдЙл QJNMKKKKKKKKKKKKKKKKKKKKKKKKKKKK QKOKPKO ^ллбЦегЙен зС нЬЙ Езенкзд нЙкгбе~дл QJNNKKKKKKKKKK QKOKPKP `зееЙЕнбзе Зб~Цк~гл QJNOKKKKKKKKKKKKKKKKKKKKKK QKOKPKQ `зееЙЕнбзе Зб~Цк~гл зС ~е~дзЦ йдмЦJбе гзЗмдЙл QJNP
QKP fелн~дд~нбзе зС ~ `bJнуйбЕ~д ЗкбоЙ лулнЙг QJNQKKKKKKKKKKKKKKKKKKKKKKKKKK
5 Commissioning 5-1..........................................
RKN _ЙСзкЙ узм лпбнЕЬ зе RJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
RKO pЬзкн лЙнJмй EС~Ензку лЙннбеЦF RJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
RKOKN pпбнЕЬJзе лЙимЙеЕЙ RJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK RKOKO c~Ензку лЙнн б еЦ зС нЬЙ гзлн бгйзкн~ен ЗкбоЙ й~к~гЙнЙкл RJOKKKKK
RKP ^З~йн г~ЕЬбеЙ З~н~ RJPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
RKPKN aЙнЙкгбеЙ лйЙЙЗ к~еЦЙ EС
ÇãáåIÑÇã~ñ
RKPKO ^ЗамлнгЙен зС ~ЕЕЙдЙк~нбзе ~еЗ ЗЙЕЙдЙк~нбзе нбгЙл Eq RKPKP pЙннбеЦ зС нЬЙ ЕмккЙен дбгбн Ef
ã~ñ
RKQ lйнбгбл~нбзе зС нЬЙ зйЙк~нбеЦ ЕЬ~к~ЕнЙкблнбЕ зС нЬЙ ЗкбоЙ RJSKKKKKKKKKKKKK
RKQKN pЙдЙЕн нЬЙ Езенкзд гзЗЙ RJSKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK RKQKO lйнбгбл~нбзе зС зйЙк~нбеЦ гзЗЙл RJUKKKKKKKKKKKKKKKKKKKKKKK
RKQKOKN lйнбгбл~нбзе з С sLС ЕЬ~к~ЕнЙкблнбЕ Езенкзд
пбнЬ Езелн~ен s
ãáå
RKQKOKO lйнбгбл~нбзе зС гзнзкJЕмккЙен Езенкзд RJNMKKKKKKKK
RKR lйЙк~нбзе пбнЬ нЬЙ mfaJЕзенкзддЙк RJNNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
RKRKN pн~еЗ~кЗбл~нбзе зС йкзЕЙлл о~дмЙ RJNOKKKKKKKKKKKKKKKKKKKKKKK
RKS ^ййдбЕ~нбзе Йс~гйдЙл RJNPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
RKSKN ^бк ЕзеЗбнбзебеЦ RJNPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK RKSKO mмгй ~ййдбЕ~нбзе пбнЬ йкЙллмкЙ Езенкзд RJNSKKKKKKKKKKKKKKKKKK RKSKP mмгй ~ййдбЕ~нбзе пбнЬ дЙоЙд Езенкзд RJNUKKKKKKKKKKKKKKKKKKKKK
RKT páÖå~äJÑäçï ÅÜ~êíë RJOMKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
FRJPKKKKKKKKKKKKKKKKKKKK
FRJQKK
áêIqáÑ
FRJRKKKKKKKKKKKKKKKKKKKKKKKK
Дззлн RJUKKKKKKKKKKKKKKKKKKK
ii
UOOuhäáã~_^NMMO
Page 5
Contents
Show/Hide Bookmarks
6 During operation 6-1........................................
7 Configuration 7-1...........................................
TKN _~ëáÅë TJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
TKO `çÇÉ í~ÄäÉ TJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
8 Troubleshooting and fault elimination 8-1.....................
UKN qкзмДдЙлЬззнбеЦ UJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
UKNKN aблйд~у ~н нЬЙ ЕзенкзддЙк UJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK UKNKO aблйд~у ~н нЬЙ зйЙк~нбеЦ гзЗмдЙ UJNKKKKKKKKKKKKKKKKKKKKKKKK UKNKP j~дзйЙк~нбзе зС нЬЙ ЗкбоЙ UJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
UKO c~мдн ~е~дулбл млбеЦ нЬЙ Ьблнзку ДмССЙк UJOKKKKKKKKKKKKKKKKKKKKKKKKKKKK
UKP c~мдн беЗбЕ~нбзел UJPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
UKQ oЙлЙн зС С~мдн беЗбЕ~нбзел UJRKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
9 Accessories (Overview) 9-1..................................
VKN ^ЕЕЙллзкбЙл Сзк ~дд нуйЙл VJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
VKO pçÑíï~êÉ VJNKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
VKP qуйЙJлйЙЕбСбЕ ~ЕЕЙллзкбЙл VJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
VKPKN qóéÉë UOOu VJOKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK VKPKO qóéÉë UOQu VJPKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKKK
10 Index 10-1...................................................
UOOuhäáã~_^NMMO
iii
Page 6
Contents
Show/Hide Bookmarks
iv
UOOuhäáã~_^NMMO
Page 7
Preface and general information
Show/Hide Bookmarks

1 Preface and general information

1.1 About these Operating Instructions ...
D qЬЙлЙ lйЙк~нбеЦ fелнкмЕнбзел ЬЙдй узм нз ЕзееЙЕн ~еЗ лЙн мй нЬЙ UOuu
СкЙимЙеЕу беоЙкнЙкK qЬЙу Езен~бе л~СЙну беСзкг~нбзе пЬбЕЬ гмлн ДЙ зДлЙкоЙЗK
D ^дд йЙклзел пЬз пзкв зе ~еЗ пбнЬ UOuu СкЙимЙеЕу беоЙкнЙкл гмлн Ь~оЙ нЬЙ
lйЙк~нбеЦ fелнкмЕнбзел ~о~бд~ДдЙ ~еЗ зДлЙкоЙ ~дд кЙдЙо~ен езнЙл ~еЗ белнкмЕнбзелK
D qЬЙ lйЙк~нбеЦ fелнкмЕнбзел гмлн ~дп~ул ДЙ бе ~ ЕзгйдЙнЙ ~еЗ йЙкСЙЕнду
êÉ~Ç~ÄäÉ ëí~íÉK
1.1.1 Terminology used
Term In the following text used for 82XX Any frequency inverter of the series 8210, 8220, 8240 Controller 82XX frequency inverter Drive system Drive systems with 82XX frequency inverters and other Lenze drive components
1.1.2 Changes in these Operating Instructions
Material No. Edition Important Contents
398946 15/11/1997 1. edition
01/04/1998 2. edition D Chapter 3
D Chapter 5.5 D Editorial update
01/03/1999 3. edition D Chapter 5.6.4: cancelled
454071 10/2002 replaces 398946 D Change of company name
D Chapter 5.1 D Chapter 8.3

1.2 Scope of delivery

Scope of delivery Important
D 1 82XX frequency inverter D 1 Operating Instructions D 1 accessory kit (components for the
mechanical and electric installation)
After receipt of the delivery, check immediately whether the scope of supply matches with the accompanying papers. Lenze does not accept any liability for deficiencies claimed subsequently. Claim
D visible transport damage immediately to the forwarder. D visible deficiencies/incompleteness immediately to your Lenze
representative.
UOOuhäáã~_^NMMO
1-1
Page 8
Preface and general information
g
p
Show/Hide Bookmarks

1.3 Legal regulations

Labelling
Application as directed
Nameplate CE mark Manufacturer
Lenze controllers are unambiguously designated by the content of the nameplate.
Conforms to the EC Low Voltage Directive
Lenze Drive Systems GmbH Postfach 10 13 52 D-31763 Hameln
82XX frequency inverter
D must only be operated under the conditions prescribed in these Instructions. D are components
- used for open and closed loop control of variable speed drives withasynchronous standard motors, reluctance motors, PM-synchronous motors with asynchronous damping cage.
- used for installation into a machine.
- used for assembly together with other components to form a machine.
D are electric units for the installation into control cabinets or similar enclosed operating housing. D comply with the requirements of the Low-Voltage Directive. D are not machines for the purpose of the Machinery Directive. D are not to be used as domestic appliances, but only for industrial purposes.
Drive systems with 82XX frequency inverters
D comply with the EMC Directive if they are installed according to the guidelines of CE-typical drive systems. D can be used
- on public and non-public mains.
- in industrial as well as residential and commercial premises.
D The user is responsible for the compliance of his application with the EC directives.
Any other use shall be deemed inappropriate!
Liability D The information, data and notes in these Operating Instructions met the state of the art at the time of printing.
Claims referring to drive systems which have already been supplied cannot be derived from the information, illustrations, and descriptions given in these Operating Instructions.
D The specifications, processes, and circuitry described in these Operating Instructions are for guidance only and
must be adapted to your own specific application. Lenze does not take responsibility for the suitability of the process and circuit proposals.
D The indications given in these Operating Instructions describe the features of the product without warranting them. D Lenze does not accept any liability for damage and operating interference caused by:
- disregarding these Instructions
- unauthorized modifications to the controller
- operating errors
- improper working on and with the controller
Warranty D Warranty conditions: see Sales and Delivery Conditions of Lenze Drive Systems GmbH.
D Warranty claims must be made immediately after detecting defects or faults. D The warranty is void in all cases where liability claims cannot be made.
Disposal
Material recycle dispose
Metal D - Plastic D - Printed-board assemblies - D
1-2
UOOuhäáã~_^NMMO
Page 9

2 Safety information

Show/Hide Bookmarks

2.1 General safety information

Safety and application notes for controllers
EнзW iзпJsздн~ЦЙ aбкЙЕнбоЙ TPLOPLbb`F
Safety information
1. General
During operation, drive controllers may have, according to their type of protection, live, bare, in some cases also movable or rotating parts as well a s hot surfaces. Non-authorized removal of the required cover, inappropriate use, incorrect installation or operation, creates the risk of severe injury to persons or damage to material assets. Further information can be obtained from the documentation. All operations concerning transport, installation, and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or DIN VDE 0110 and national regulations for the prevention of accidents must be observed). According to this basic safety information qualified skilled personnel are persons who are familiar with the erection, assembly, commissioning, and operation of the product and who have the qualifications necessary for their occupation.
2. Application as directed
Drive controllers are components which are designed for installation in electrical systems or machinery. When installing in machines, commissioning of the drive controllers (i.e. the starting of operation as directed) is prohibited until it is proven that the machine corresponds to the regulations of the EC Directive 89/392/EEC (Machinery Directive); EN 60204 must be observed. Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC Directive (89/336/EEC). The drive controllers meet the requirements of the Low Voltage Directive 73/23/EEC. The harmonized standards of the prEN 50178/ DIN VDE 0160 series together with EN 60439-1/DIN VDE 0660 part 500 and EN 60146/DIN VDE 0558 are applicable to drive controllers. The technical data and information on the connection conditions must be obtained from the nameplate and the documentation and must be observed in all cases.
3. Transport, storage
Notes on transport, storage and appropriate handling must be observed.
Climatic conditions must be observed according to prEN 50178.
4. Erection
The devices must be erected and cooled according to the regulations of the corresponding documentation. The drive controllers must be protected from inappropriate loads. Particularly during transport and handling, components must not be bent and/or isolating distances must not be changed. Touching of electronic components and contacts must be avoided. Drive controllers contain electrostatically sensitive components which can easily be damaged by inappropriate handling. Electrical components must not be damaged or destroyed mechanically (health risks are possible!).
5. Electrical connection
When working on live drive controllers, the valid national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE connection). More detailed information is included in the documentation. Notes c oncerning the installation in compliance with EMC - such as screening, grounding, arrangement of filters and laying of cables - are included in the documentation of the drive controllers. These notes must also be observed in all cases for drive controllers with the CE mark.The compliance with the required limit values demanded by the EMC legislation is the responsibility of the manufacturer of the system or machine.
6. Operation
Systems where drive controllers are installed must be equipped, if necessary, with additional monitoring and protective devices according to the valid safety regulations, e.g. law on technical tools, regulations for the prevention of accidents, etc. Modifications of the drive controllers by the operating software are allowed. After disconnecting the drive controllers from the supply voltage, live parts of the controller and power connections must not be touched immediately, because of possibly charged capacitors. For this, observe the corresponding labels on the drive controllers. During operation, all covers and doors must be closed.
7. Maintenance and servicing
The manufacturer’s documentation must be observed.
This safety information must be kept!
The product-specific safety and application notes in these Operating Instructions must also be observed!
UOOuhäáã~_^NMMO
2-1
Page 10
Safety information
Show/Hide Bookmarks

2.2 Layout of the safety information

D ^дд л~СЙну езнЙл Ь~оЙ ~ мебСзкг д~узмнW
J qЬЙ бЕзе ЕЬ~к~ЕнЙкбтЙл нЬЙ нуйЙ зС З~еЦЙкK J qЬЙ лбЦе~д пзкЗ ЕЬ~к~ЕнЙкбтЙл нЬЙ лЙоЙкбну зС З~еЦЙкK J qЬЙ езнЙ ЗЙлЕкбДЙл нЬЙ З~еЦЙк ~еЗ лмЦЦЙлнл Ьзп нз ~озбЗ нЬЙ З~еЦЙкK
Signal word
kçíÉ
Icons used Signal words
Warning of danger to persons
Warning of hazardous electrical voltage
Danger! Warns of impending danger.
Consequences if disregarded: Death or very severe injuries.
Warning of a general danger
Warning of damage to material
Other notes Note! This note designates general, useful notes.
Warning! Warns of potential, very hazardous situations.
Possible consequences if disregarded: Death or very severe injuries.
Caution! Warns of potential, hazardous situations.
Possible consequences if disregarded: Light or minor injuries.
Stop! Warns of potential damage to material .
Possible consequences if disregarded: Damage of the controller/drive system or its environment
If you obser ve it, handling of the controller/drive system is made easier.

2.3 Residual hazards

Operator’s safety After mains disconnections, the power terminals U, V, W and +UG,-UGremain live for at least three
Protection of devices Cyclic connection and disconnection of the controller supply voltage at L1, L2, L3 or +UG,-UGmay
Overspeeds Drive systems can reach dangerous overspeeds (e. g. setting of inappropriately high field frequencies):
minutes.
D Before working on the controller, check that no voltage is applied to the power terminals.
overload the internal input current load:
D Allow at least 3 minutes between disconnection and reconnection.
D The controllers do not offer any protection against these operating conditions. Use additional
components for this.
.
2-2
UOOuhäáã~_^NMMO
Page 11
Technical Data
p
Show/Hide Bookmarks

3 Technical data

3.1 General data/application conditions

Field Values Vibration resistance Germanischer Lloyd, general conditions Humidity class Humidity class F without condensation (average relative humidity 85 %) Permissible temperature
ranges
Permissible installation height h
Degree of pollution VDE 0110 part 2 pollution degree 2 Noise emission Requirements acc. to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Noise immunity
Insulation strength Overvoltage category III according to VDE 0110 Packaging to DIN 4180 Types 824X
Type of protection
Approvals
during transport of the controller: -25 °C ¼ +70 °C during storage of the controller: -25 °C ¼ +55 °C during operation of the controller: 0 °C ¼ +40 °C
+40 °C ¼ +50 °C
h 1000m amsl 1000 m a.m.s.l. < h 4000 m a.m.s.l.
Limit value class A to EN 55011 (industrial area) with mains filter Limit value class B to EN 55022 (residential area) with mains filter and installation into control cabinet
Limit values maintained usig mains filter Requirements according to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements Standard Severities
ESD EN61000-4-2 3, i.e. 8 kV with air discharge
RF interference(enclosure) EN61000-4-3 3, i.e. 10 V/m; 27¼1000 MHz Burst EN61000-4-4 3/4,i.e.2kV/5kHz Surge
(Surge on mains cable)
Types 822X
EN 61000-4-5 3, i.e. 1.2/50 μs,
Dust packaging Transport packaging
IP20 NEMA 1: Protection against contact
IP 41 on the heat-sink side with thermal separation in push-through technique
CE: Low-Voltage Directive a nd
UL 508: UL 508C:
without power derating with power derating
without power derating with power derating
6 kV with contact discharge
1 kV phase-phase, 2 kV phase-PE
Electromagnetic Compatibility Industrial Control Equipment
Power Conversion Equipment
UOOuhäáã~_^NMMO
3-1
Page 12
Technical Data
Show/Hide Bookmarks

3.2 Rated data (Operation with 120 % overload)

3.2.1 Operating conditions
D ^ййдбЕ~нбзелW
J mмгйл пбнЬ лим~кЙ ЕЬ~к~ЕнЙкблнбЕ ~еЗ С~ел
D léÉê~íáçå çåäó ïáíÜ
J г~бел СбднЙк зк г~бел ЕЬзвЙK J ~ г~бел оздн~ЦЙ зС P ^` L QMM s L RM eтLSM eтK
D ^З~йн г~белJлбЗЙ ~ЕЕЙллзкбЙл нз нЬЙ беЕкЙ~лЙЗ г~бел ЕмккЙенW
J cзк СмлЙл ~еЗ Е~ДдЙ ЕкзллJлЙЕнбзел лЙЙ ЕЬ~йнЙк PKQKO J cзк З~н~ зС знЬЙк ЕзгйзеЙенл лЙЙ Т^ЕЕЙллзкбЙлТK
D ^мнзг~нбЕ ЕЬзййЙк СкЙимЙеЕу кЙЗмЕнбзе нз Q вeт бС нЬЙ змнймн ЕмккЙен
беЗбЕ~нЙЗ бл ЙсЕЙЙЗЙЗK
3-2
UOOuhäáã~_^NMMO
Page 13
3.2.2 Types 8221 to 8224
p(p
)
p
)
60s
2
)
g
p
Show/Hide Bookmarks
Technical Data
120 % overload Type 8221 8222 8223
Order no. EVF8221-E-
Mains voltage V
V020
[V] 320 V - 0%V
rated
EVF8222-E-
V020
440 V + 0%; 45 Hz - 65 Hz 0%
rated
4)
EVF8223-E-
V020
8224
EVF8224-E-
V020
Alternative DC supply VDC[V] 460 V - 0% VDC≤ 620 V + 0% Mains current with mains filter/mains choke I
[A] 39.0 50.0 60.0 97.0
mains
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V Motor power (4 pole ASM)
off 4kHz/8kHz*
Output power U, V, W off 4 kHz/8 kHz*
Output power +UG,-U Output
current
4kHz* I 8kHz* I
G
12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current for
4kHz* I 8kHz* I 12 kHz* I
2
16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Motor voltage
3)
1)
P
[kW] 22 30 37.5 55
rated
P
[hp] 30 40 50 74
rated
S
rated4
S
rated8
[kVA] [kVA]
29.8
22.2
39.5
32.6
46.4
41.6
PDC[kW] 10.2 4.0 0 5.1
[A] 43 56 66 100
rated4
[A] 32 47 59 89
rated8
[A] 27 40 50 62
rated12
[A] 24 35 44 54
rated16
[A] 32 47 59 89
rated4
[A] 29 43 47
rated8
[A] 25 37 44 54
rated12
[A] 21 30 35 46
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 48 70.5 89 134 [A] 48 70.5 89 134
[A] 40 59 75 92
[A] 36 53 66 81 [A] 48 70.5 89 134 [A] 43 64 70
[A] 38 56 66 81
[A] 31 46 53 69
VM[V] 0-3×V
/0Hz¼ 50Hz, if required up to 480Hz
mains
5)
5)
74.8
61.7
59
88
Power loss (Operation with INx) Pv[W] 640 810 810 1350 Power derating [%/K]
[%/m]
Field frequency
Resolution absolute 0.02 Hz Digital setpoint selection Accuracy 0.05 Hz Analog setpoint selection
Linearity 0.5 % (max. selected signal level: 5 V or 10 V) Temperature
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5 %/1000m
40 °C<T
amb
0 ¼ 40 °C: +0.4 %
<50°C: 2.5%/K
sensitivity Offset 0%
Weight m[kg] 15 15 15 33,5
5)
5)
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% INx.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Max. permissible ambient temperature during operation +35 °C
5)
must only be operated with C144 = -1- (automatic chopper frequency reduction at J
=-5°C). Ensure not to
max
exceed the currents.
* Chopper frequency of the inverter
UOOuhäáã~_^NMMO
3-3
Page 14
Technical Data
p(p
)
p
p
2
)
g
p
Show/Hide Bookmarks
3.2.3 Types 8225 to 8227
V020
4)
8226 8227
EVF8226-E-
V020
440 V + 0% ;
rated
EVF8227-E-
V020
120 % overload Type 8225
Order no. EVF8225-E-
Mains voltage V
[V] 320 V - 0% V
rated
45 Hz ¼ 65 Hz 0% Alternative DC supply VDC[V] 460 V - 0% VDC≤ 620 V + 0% Mains current
I
with mains filter/mains choke
mains
[A]
119 144 185
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V Motor power (4 pole ASM)
off 4kHz/8kHz*
Output power U, V, W off 4 kHz/8 kHz*
Output power +UG,-U Output
current
G
4kHz* I 8kHz* I 12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current for 60s
4kHz* I 8kHz* I 12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Motor voltage
3)
1)
P
[kW] 75 90 110
rated
P
[hp] 100 120 148
rated
S S
rated4 rated8
[kVA] [kVA]
91.5
76.2
110
103.9
PDC[kW] 0 28.1 40.8
[A] 135 159 205
rated4
[A] 110 150 171
rated8
[A] 88 120 126
rated12
[A] 77 105 108
rated16
[A] 110 150 159
rated4
[A] 76
rated8
[A] 66 82 90
rated12
[A] 60 67 72
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 165 225 270 [A] 165 225 221
[A] 114 156 164
[A] 100 136 140 [A] 165 225 238 [A] 114
[A] 85 107 117
[A] 78 87 94
VM[V] 0-3×V
5)
5)
/0Hz¼ 50Hz, if required up to 480Hz
mains
92
138
5)
5)
142
124.7
100
150
Power loss (Operation with INx) Pv[W] 1470 2100 2400 Power derating [%/K]
[%/m]
Field frequency
Resolution absolute 0.02 Hz Digital setpoint selection Accuracy 0.05 Hz Analog setpoint selection
Linearity 0.5 % (max. selected signal level: 5 V or 10 V)
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5 %/1000m
40 °C<T
<50°C: 2.5%/K
amb
Temperature sensitivity 0 ¼ 40 °C: +0.4 % Offset 0%
Weight m[kg] 36.5 59 59
4)
5)
5)
5)
5)
3-4
UOOuhäáã~_^NMMO
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% INx.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Max. permissible ambient temperature during operation +35 °C
5)
must only be operated with C144 = -1- (automatic chopper frequency reduction at J
=-5°C). Ensure not to
max
exceed the currents.
* Chopper frequency of the inverter
Page 15
Technical Data
p(p
)
p
p
2
)
g
p
Show/Hide Bookmarks
3.2.4 Types 8241 to 8243
120 % overload Type 8241 8242 8243
Order no. EVF8241-E-
V020
Mains voltage V
[V] 320V 0% V
rated
Alternative DC supply VDC[V] 460V 0% VDC≤ 620V 0% Mains current
with mains filter/mains choke
I
[A] 1.7 2.8 5.0
mains
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V Motor power (4 pole ASM)
off 4kHz/8kHz*
Output power U, V, W off 4 kHz/8 kHz*
Output power +UG,-U Output
current
G
4kHz* I 8kHz* I 12kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current for 60s
4kHz* I 8kHz* I 12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Motor voltage
3)
1)
P
[kW] 0.55 1.1 2.2
rated
P
[hp] 0.75 1.5 2.9
rated
S
rated4
S
rated8
[kVA] [kVA]
1.3
1.0
PDC[kW] 1.9 0.7 0
[A] 1.8 3.0 5.5
rated4
[A] 1.5 2.5 3.9
rated8
[A] 1.35 2.2 3.5
rated12
[A] 1.2 2.0 3.1
rated16
[A] 1.5 2.5 3.9
rated4
[A] 1.3 2.2 2.9
rated8
[A] 1.3 2.1 3.4
rated12
[A] 1.1 1.8 2.9
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 2.25 3.6 6.6 [A] 2.2 3.7 5.8
[A] 2.0 3.3 5.2
[A] 1.8 3.0 4.7 [A] 2.3 3.8 5.8 [A] 2.0 3.2 5.0
[A] 1.9 3.2 5.1
[A] 1.6 2.7 4.3
VM[V] 0-3×V
mains
Power loss (Operation with INx) Pv[W] 50 65 115 Power derating [%/K]
Field frequency
[%/m] Resolution absolute 0.02 Hz Digital setpoint selection Accuracy 0.05 Hz Analog setpoint selection
Linearity 0.5 % (max. selected signal level: 5 V or 10 V)
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5 %/1000m
Temperature sensitivity 0 ¼ 40 °C: +0.4 % Offset 0%
Weight m[kg] 3.5 3.5 5.0
EVF8242-E-
V020
440 V 0% ;
rated
EVF8243-E-
V020
45Hz ¼ 65Hz 0%
2.1
1.7
/0Hz¼ 50Hz, if required up to 480Hz
40 °C<T
<50°C: 2.5%/K
amb
3.8
2.7
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% INx.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
* Chopper frequency of the inverter
UOOuhäáã~_^NMMO
3-5
Page 16
Technical Data
p(p
)
p
p
2
)
g
p
Show/Hide Bookmarks
3.2.5 Types 8244 to 8246
120 % overload Type 8244 8245 8246
Order no. EVF8244-E-
V020
Mains voltage V
[V] 320V 0% V
rated
Alternative DC supply VDC[V] 460V 0% VDC≤ 620V 0% Mains current
I
with mains filter/mains choke
mains
[A]
8.8 15.0 20.5
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V Motor power (4 pole ASM)
off 4kHz/8kHz*
Output power U, V, W off 4 kHz/8 kHz*
Output power +UG,-U Output
current
G
4kHz* I 8kHz* I 12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current for 60s
4kHz* I 8kHz* I 12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Motor voltage
3)
1)
P
[kW] 4.4 7.5 11.0
rated
P
[hp] 5.4 10.0 15.0
rated
S
rated4
S
rated8
[kVA] [kVA]
6.5
4.8
PDC[kW] 2.0 0 0
[A] 9.2 16.0 23.5
rated4
[A] 7.0 13.0 23.5
rated8
[A] 6.3 11.7 20.0
rated12
[A] 5.6 10.4 16.5
rated16
[A] 7.0 13.0 23.5
rated4
[A] 6.0 11.1 20.0
rated8
[A] 6.1 11.3 19.4
rated12
[A] 5.2 9.7 15.2
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 11.0 19.5 35.3 [A] 10.5 19.5 35.0
[A] 9.5 17.5 30.0
[A] 8.4 15.6 24.6 [A] 10.5 19.5 35.5 [A] 7.8 14.5 22.9
[A] 9.1 16.5 29.0
[A] 7.8 14.5 22.9
VM[V] 0-3×V
mains
Power loss (Operation with INx) Pv[W] 165 260 360 Power derating [%/K]
[%/m]
Field frequency
Resolution absolute 0.02 Hz Digital setpoint selection Accuracy 0.05 Hz Analog setpoint selection
Linearity 0.5 % (max. selected signal level: 5 V or 10 V)
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5 %/1000m
40 °C<T
Temperature sensitivity 0 ¼ 40 °C: +0.4 % Offset 0%
Weight m[kg] 5.0 7.5 7.5
EVF8245-E-
V020
440 V 0% ;
rated
EVF8246-E-
V020
45Hz ¼ 65Hz 0%
11.1
9.0
16.3
16.3
/0Hz¼ 50Hz, if required up to 480Hz
<50°C: 2.5%/K
amb
3-6
UOOuhäáã~_^NMMO
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% INx.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
* Chopper frequency of the inverter
Page 17
Technical Data
p(p
)
p
forfü
r
60s
)
Show/Hide Bookmarks

3.3 Rated data (Operation with 150 % overload)

lйЙк~нбзе йЙкгбннЙЗ пбнЬ ~ г~бел оздн~ЦЙ зС
P^` L QMM s J QUMs LRM eòLSM eò
3.3.1 Types 8221 to 8224
150 % overload Type 8221 8222 8223 8224
Mains voltage V Alternative DC supply VDC[V] 460 V - 0% VDC≤740 V + 0%
Mains current with mains filter/mains choke without mains filter/mains choke
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ; 460 V V
740 V
DC
Motor power (4 pole ASM) off 4kHz/8kHz*
Output power U, V, W off 4 kHz/8 kHz*
Output power +UG,-U Output
current
4kHz* I 8kHz* I
1)
G
12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current
60s
4kHz* I 8kHz* I 12 kHz* I
2)
16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Power loss (Operation with INx) Pv[W] 430 640 810 1100
[V] 320 V - 0% V
rated
I
mains
I
mains
[A] [A]
29.0
43.5
528 V + 0% ; 45 Hz ¼ 65 Hz 0%
rated
42.0
--
55.0
--
80.0
400 V 480 V 400 V 480 V 400 V 480 V 400 V 480 V
P
[kW] 15 18.5 22 30 30 37 45 55
rated
P
[hp] 20 25 30 40 40 49.5 60 74
rated
S
[kVA] 22.2 26.6 32.6 39.1 41.6 49.9 61.7 73.9
rated8
PDC[kW] 10.2 11.8 4.0 4.6 0 0 5.1 5.9
[A] 32 32 47 47 59 56 89 84
rated4
[A] 32 32 47 47 59 56 89 84
rated8
[A] 27 25 40 37 50 47 62 67
rated12
[A] 24 22 35 33 44 41 54 58
rated16
[A] 32 30,5 47 45 59 56 89 84
rated4
[A] 29 27 43 41 47
rated8
[A] 25 24 37 35 44 38 54 48
rated12
[A] 21 19 30 28 35 30 46 39
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 48 48 70.5 70.5 89 84 134 126 [A] 48 48 70.5 70.5 89 84 134 126
[A] 40 38 59 56 75 70 92 87
[A] 36 33 53 49 66 61 81 75 [A] 48 46 70.5 66,5 89 56 134 126 [A] 43 41 64 61 70
[A] 38 36 56 53 66 57 81 75
[A] 31 29 46 42 53 45 69 63
3)
3)
44
65
3)
3)
59
88
3)
3)
--
3)
55
3)
82
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% I
3)
must only be operated with C144 = -1- (automatic chopper frequency reduction at J
.
Nx
=+5°C). Ensure not to
max
exceed the currents.
* Chopper frequency of the inverter
For all other data see chapter 3.2.2.
UOOuhäáã~_^NMMO
3-7
Page 18
Technical Data
p(p
)
p
forfü
r
60s
)
Show/Hide Bookmarks
3.3.2 Types 8225 to 8227
150 % overload Type 8225 8226 8227
Mains voltage V Alternative DC supply VDC[V] 460 V - 0% VDC≤740 V + 0%
Mains current with mains filter/mains choke without mains filter/mains choke
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ; 460 V V
740 V
DC
Motor power (4 pole ASM) at 4 kHz/8 kHz*
Output power U, V, W at 4kHz/8 kHz*
Output power +UG,-U Output
current
4kHz* I 8kHz* I
1)
G
12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current
60s
4kHz* I 8kHz* I 12 kHz* I
2)
16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Power loss (Operation with INx) Pv[W] 1470 1960 2400
[V] 320 V - 0% V
rated
I
[A]
mains
[A]
I
mains
100
--
528 V + 0% ; 45 Hz ¼ 65 Hz 0%
rated
135
--
165
400 V 480 V 400 V 480 V 400 V 480 V
P
[kW] 55 75 75 90 90 110
rated
P
[hp] 74 100 100 120 120 148
rated
S
[kVA] 76.2 91.4 103.9 124 124.7 149
rated8
PDC[kW] 0 0 28.1 32.4 40.8 47.1
[A] 110 105 150 142 180 171
rated4
[A] 110 105 150 142 171 162
rated8
[A] 88 83 120 112 126 117
rated12
[A] 77 72 105 98 108 99
rated16
[A] 110 104 150 141 159
rated4
[A] 76
rated8
[A] 66 60 82 75 90 81
rated12
[A] 60 55 67 60 72 63
rated16
rated max4
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 165 157 225 213 270 256 [A] 165 157 225 213 221 211
[A] 114 108 156 147 164 153
[A] 100 94 136 128 140 130 [A] 165 156 225 212 238 [A] 114
[A] 85 78 107 98 117 106
[A] 78 72 87 78 94 83
3)
3)
71
107
3)
3)
92
138
3)
3)
86
169
3)
3)
3)
3)
100
3)
3) 1413)
150
--
3)
149
3)
94
3)
223
3-8
UOOuhäáã~_^NMMO
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% I
3)
must only be operated with C144 = -1- (automatic chopper frequency reduction at J
.
Nx
=+5°C). Ensure not to
max
exceed the currents.
* Chopper frequency of the inverter
For all other data see chapter 3.2.3.
Page 19
Technical Data
p(p
)
p
forfü
r
60s
)
Show/Hide Bookmarks
3.3.3 Types 8241 to 8243
150 % overload Type 8241 8242 8243
Mains voltage V Alternative DC supply VDC[V] 460 V - 0% VDC≤ 740 V + 0%
Mains current with mains filter/mains choke without mains filter/mains choke
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ; 460 V V
740 V
DC
Motor power (4 pole ASM) at 4 kHz/8 kHz*
Output power U, V, W at 4kHz/8 kHz*
Output power +UG,-U Output
current
4kHz* I 8kHz* I
1)
G
12kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current
60s
4kHz* I 8kHz* I 12 kHz* I
2)
16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Power loss (Operation with INx) Pv[W] 50 65 100
[V] 320 V - 0% Vrated 528 V + 0% ; 45 Hz 065 Hz ”0%
rated
I
mains
I
mains
[A] [A]
1.5
2.1
2.5
3.5
3.9
5.5
400 V 480 V 400 V 480 V 400 V 480 V
P
[kW] 0.37 0.37 0.75 0.75 1.5 1.5
rated
P
[hp] 0.5 0.5 1.0 1.0 2.0 2.0
rated
S
[kVA] 1.0 1.2 1.7 2.1 2.7 3.2
rated8
PDC[kW] 1.9 2.3 0.7 0.9 0 0
[A] 1.5 1.5 2.5 2.5 3.9 3.9
rated8
[A] 1.5 1.5 2.5 2.5 3.9 3.9
rated8
[A] 1.35 1.35 2.2 2.2 3.5 3.5
rated12
[A] 1.2 1.2 2.0 2.0 3.1 3.1
rated16
[A] 1.5 1.5 2.5 2.4 3.9 3.7
rated4
[A] 1.3 1.3 2.2 2.1 2.9 2.8
rated8
[A] 1.3 1.3 2.1 2.1 3.4 3.4
rated12
[A] 1.1 1.1 1.8 1.8 2.9 2.9
rated16
rated max8
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 2.2 2.25 3.7 3.75 5.8 5.85
[A] 2.2 2.25 3.7 3.75 5.8 5.85
[A] 2.0 2.0 3.3 3.3 5.2 5.2
[A] 1.8 1.8 3.0 3.0 4.7 4.7 [A] 2.3 2.2 3.8 3.6 5.8 5.5 [A] 2.0 1.8 3.2 3.0 5.0 4.7
[A] 1.9 1.9 3.2 3.2 5.1 5.1
[A] 1.6 1.6 2.7 2.7 4.3 4.3
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% I
.
Nx
* Chopper frequency of the inverter
For all other data see chapter 3.2.4.
UOOuhäáã~_^NMMO
3-9
Page 20
Technical Data
p(p
)
p
forfü
r
60s
)
Show/Hide Bookmarks
3.3.4 Types 8244 to 8246
150 % overload Type 8244 8245 8246
Mains voltage V Alternative DC supply VDC[V] 460 V - 0% VDC≤ 740 V + 0%
Mains current with mains filter/mains choke without mains filter/mains choke
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ VDC≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ; 460 V V
740 V
DC
Motor power (4 pole ASM) at 4 kHz/8 kHz*
Output power U, V, W at 4kHz/8 kHz*
Output power +UG,-U Output
current
4kHz* I 8kHz* I
1)
G
12 kHz* I 16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Max. output current
60s
4kHz* I 8kHz* I 12 kHz* I
2)
16 kHz* I noise optimized 4 kHz* I noise optimized 8 kHz* I noise optimized 12 kHz* I noise optimized 16 kHz* I
Power loss (Operation with INx) Pv[W] 150 210 360
[V] 320 V - 0% Vrated 528 V + 0% ; 45 Hz 065 Hz ”0%
rated
I
mains
I
mains
[A] [A]
7.0
12.0
-
16.8
20.5
400 V 480 V 400 V 480 V 400 V 480 V
P
[kW] 3.0 3.0 5.5 5.5 11.0 11.0
rated
P
[hp] 4.0 4.0 7.5 7.5 15.0 15.0
rated
S
[kVA] 4.8 5.8 9.0 10.8 16.3 10.8
rated8
PDC[kW] 2.0 2.5 0 0 0 0
[A] 7.0 7.0 13.0 13.0 23.5 23.5
rated4
[A] 7.0 7.0 13.0 13.0 23.5 23.5
rated8
[A] 6.3 6.3 11.7 11.7 20.0 19.1
rated12
[A] 5.6 5.6 10.4 10.4 16.5 15.7
rated16
[A] 7.0 6.6 13.0 12.3 23.5 22.1
rated4
[A] 6.0 5.6 11.1 10.4 20.0 18.8
rated8
[A] 6.1 6.1 11.3 11.3 19.4 18.4
rated12
[A] 5.2 5.2 9.7 9.7 15.2 14.6
rated16
rated max8
rated max8
rated max12
rated max16
rated max4
rated max8
rated max12
rated max16
[A] 10.5 10.5 19.5 19.5 35.0 33.5 [A] 10.5 10.5 19.5 19.5 35.0 33.5
[A] 9.5 9.5 17.5 17.5 30.0 28.7
[A] 8.4 8.4 15.6 15.6 24.6 23.6 [A] 10.5 8.4 19.5 15.6 35.5 28.2 [A] 7.8 7.8 14.5 14.5 22.9 21.8
[A] 9.1 9.1 16.5 16.5 29.0 27.6
[A] 7.8 7.8 14.5 14.5 22.9 21.8
-
3-10
UOOuhäáã~_^NMMO
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and 2 minutes base load with 75% I
.
Nx
* Chopper frequency of the inverter
For all other data see chapter 3.2.5.
Page 21
Technical Data
y
p
Show/Hide Bookmarks

3.4 Fuses and cable cross-sections

3.4.1 Operation of controllers in a UL-approved system
D rлЙ зеду riJ~ййкзоЙЗ СмлЙл ~еЗ СмлЙ ЬздЗЙклW
J RMM s нз SMM s бе нЬЙ г~бел беймн E^`I cN KKK cPFK J TMM s бе нЬЙ оздн~ЦЙ a` Дмл Ea`I cQLcRFK J ^Енбо~нбзе ЕЬ~к~ЕнЙкблнбЕ ТeТ зк ТhRТ
D lеду млЙ riJ~ййкзоЙЗ Е~ДдЙл
3.4.2 Single drives with 120 % overload
qЬЙ н~ДдЙ о~дмЙл ~кЙ о~дбЗ Сзк нЬЙ зйЙк~нбзе зС UOuu ЕзенкзддЙкл ~л лбеЦдЙ ЗкбоЙл пбнЬ ~ г~нЕЬбеЦ гзнзк ~еЗ NRM B зоЙкдз~З бе ймгй ~еЗ С~е ЗкбоЙлK
Type
Fuse F1, F2, F3 E.l.c.b. Cable cross-section VDE UL VDE mm
8221 M 50A 50A -- 16 5 8222 M 63A 63A -- 25 3 8223 M 80A 80A -- 25 3 8224 M 125A 125A -- 70 2/0 8225 M 160A 175A -- 95 3/0 8226 M 160A 175A -- 95 3/0 8227 M 200A 200A -- 120 4/0 8241 M6A 5A B6A 1 17 8242 M6A 5A B6A 1 17 8243 M 10A 10A B 10A 1.5 15 8244 M 10A 10A B 10A 1.5 15 8245 M 20A 20A B 20A 4 11 8246 M 32A 25A B 32A 6 10
1)
Observe national and regional regulations (e. g. VDE/EVU)!
Mains input L1, L2, L3, PE/motor connection U, V, W, PE
Operation with mains filter/choke only
2
1)
AWG
UOOuhäáã~_^NMMO
3-11
Page 22
Technical Data
y
p
Show/Hide Bookmarks
3.4.3 Single drives with 150 % overload
qЬЙ н~ДдЙ о~дмЙл ~кЙ о~дбЗ Сзк нЬЙ зйЙк~нбзе зС UOuu ЕзенкзддЙкл ~л лбеЦдЙ ЗкбоЙл пбнЬ ~ г~нЕЬбеЦ гзнзк ~еЗ NRM B зоЙкдз~ЗK
Type
Operation without mains filter/mains choke Operation with mains filter/mains choke
Fuse F1, F2, F3
VDE UL VDE mm
8221 63A -- -- 16 5 M 35A 35A -- 10 7 8222 -- -- -- -- -- M 50A 50A -- 16 5 8223 -- -- -- -- -- M 80A 80A -- 25 3 8224 -- -- -- -- -- M 100A 100A -- 50 0 8225 -- -- -- -- -- M 125A 125A -- 70 2/0 8226 -- -- -- -- -- M 160A 175A -- 95 3/0 8227 -- -- -- -- -- M 200A 200A -- 120 4/0 8241 M6A 5A B6A 1 17 M6A 5A B6A 1 17 8242 M6A 5A B6A 1 17 M6A 5A B6A 1 17 8243 M 10A 10A B 10A 1.5 15 M 10A 10A B 10A 1.5 15 8244 -- -- -- -- -- M 10A 10A B 10A 1.5 15 8245 M 25A 25A B 25A 6 10 M 20A 20A B 20A 4 11 8246 -- -- -- -- -- M 32A 25A B 32A 6 10
1)
E.l.c.b. Cable cross-section1)Fuse
Observe national and regional regulations (e. g. VDE/EVU)!
Mains input L1, L2, L3, PE/motor connection U, V, W, PE
F1, F2, F3
2
AWG VDE UL VDE mm
E.l.c.b. Cable cross-section
2
AWG
1)
3-12
UOOuhäáã~_^NMMO
Page 23

3.5 Analog plug- in module

Show/Hide Bookmarks
3.5.1 Features
qЬЙ ~е~дзЦ й дмЦJбе гзЗмдЙ йкзобЗЙл ~ лЙЕзеЗ ~е~дзЦ беймнK fн ЕзеоЙкнл ~е ~е~дзЦ беймн лбЦе~д EM KKK NM s зЗЙк M KKK OM г^F бенз ~ ЗбЦбн~д лбЦе~д EймдлЙ СкЙимЙеЕу M KKK NM вeтI дЙоЙдW M KKK Ps ilt ~еЗ NO KKK PMs efdeFK
cзк зйЙк~нбзе пбнЬ Q KKK OM г^I нЬЙ СзддзпбеЦ ЕзЗЙл гмлн ДЙ ЕЬ~еЦЙЗW
`QOS Z NOMB `QOT Z JNOKRB
cзк СмкнЬЙк беСзкг~нбзеI йдЙ~лЙ лЙЙ нЬЙ `зЗЙ q~ДдЙ K
fеоЙкнЙкл зС нЬЙ UONMI UOOM ~еЗ UOQM лЙкбЙл пЬбЕЬ ~кЙ ЙимбййЙЗ пбнЬ ~е ~е~дзЦ йдмЦJбе гзЗмдЙ Е~е ДЙ млЙЗ Сзк нЬЙ СзддзпбеЦ йкзЕЙлл ЕзенкзддЙк ~ййдбЕ~нбзелW
D mкЙллмкЙ Езенкзд
Technical Data
D qЙгйЙк~нмкЙ зк оздмгЙ Езенкзд
D pЙнйзбен лмгг~нбзе
D pйЙЙЗ зк З~еЕЙкJйзлбнбзе Езенкзд
qз зйЙк~нЙ нЬЙ ~е~дзЦ йдмЦJбе гзЗмдЙI нЬЙ нЙкгбе~д ЕзеСбЦмк~нбзе `MMT Ь~л нз ДЙ лЙн нз JOUJ KKK JQRJ зк JQUJ KKK JRNJK
Note!
lеду беоЙкнЙкл зС нЬЙ UONMI UOOM ~еЗ UOQM лЙкбЙл Сзк es^` ~еЗ ймгй ~ййдбЕ~нбзел Е~е ДЙ ЙимбййЙЗ пбнЬ ~е ~ е~дзЦ йдмЦJбе гзЗмдЙ ДЙЕ~млЙ нЬЙу йкзобЗЙ нЬЙ кЙимбкЙЗ лзСнп~кЙK
fеоЙкнЙкл пбнЬ йдмЦJбе гзЗмдЙ ~кЙ лмДаЙЕн нз нЬЙ нЙЕЬебЕ~д З~н~ ~еЗ ~ййдбЕ~нбзе ЕзеЗбнбзел зС ЕзенкзддЙклK
UOOuhäáã~_^NMMO
3-13
Page 24
Technical Data
Show/Hide Bookmarks

3.6 Dimensions

3.6.1 Controller dimensions
qЬЙ ЕзенкзддЙк ЗбгЙелбзел ЗЙйЙеЗ зе нЬЙ гЙЕЬ~ебЕ~д белн~дд~нбзе EлЙЙ ЕЬ~йнЙк QKNFK
3.6.2 Analog plug-in module
2 0
2 8 E 1 E 2
3 , 9 0 c m
E 3 E 4
3 9
4 , 0 0 c m
4 , 8 0 c m
cfd PJN aбгЙелбзел зС ~е~дзЦ йдмЦJбе гзЗмдЙ
0 - 1 0 V
0 - 2 0 m A
âPRKMNQM
3-14
UOOuhäáã~_^NMMO
Page 25

4 Installation

Show/Hide Bookmarks

4.1 Mechanical installation

4.1.1 Important notes
D rлЙ нЬЙ ЕзенкзддЙкл зеду ~л ДмбднJбе ЗЙобЕЙл>
D fС нЬЙ ЕзздбеЦ ~бк Езен~бел йзддмн~енл EЗмлнI СдмССI ЦкЙ~лЙI ~ЦЦкЙллбоЙ Ц~лЙлFW
J н~вЙ лмбн~ДдЙ йкЙоЙенбоЙ гЙ~лмкЙл I ЙKЦK лЙй~к~нЙ ~бк ЗмЕнI белн~дд~нбзе зС
СбднЙклI кЙЦмд~к Е дЙ~ебеЦI ЙнЕK
D lДлЙкоЙ СкЙЙ лй~ЕЙ>
J vзм Е~е белн~дд лЙоЙк~д ЕзенкзддЙкл еЙсн нз Й~ЕЬ знЬЙк пбнЬзмн СкЙЙ лй~ЕЙ бе ~
Езенкзд Е~ДбеЙнK J bелмкЙ мебгйЙЗЙЗ оЙенбд~нбзе зС ЕзздбеЦ ~бк ~еЗ змндЙн зС ЙсЬ~млн ~бк> J ^ддзп ~ СкЙЙ лй~ЕЙ зС NMM гг ~н нЬЙ нзй ~еЗ ~н нЬЙ ДзннзгK
Installation
D aз езн ЙсЕЙЙЗ нЬЙ ~гДбЙен нЙгйЙк~нмкЙ йЙкгбллбДдЙ ЗмкбеЦ зйЙк~нбзе EлЙЙ
ÅÜ~éíÉêK PKNF
D tбнЬ Езенбезмл злЕбдд~нбзел зк обДк~нбзелW
J `ЬЙЕв пЬЙнЬЙк лЬзЕв ~ДлзкДЙкл ~кЙ еЙЕЙлл~куK
Possible mounting positions
D fе оЙкнбЕ~д йзлбнбзе ~н нЬЙ Д~Ев зС нЬЙ Езенкзд Е~ДбеЙнI нЙкгбе~дл йзбен нз нЬЙ
СкзенW J tбнЬ ~нн~ЕЬЙЗ СбсбеЦ Дк~ЕвЙнлK J qЬЙкг~дду лЙй~к~нЙЗ пбнЬ ЙснЙке~д ЬЙ~н лбев EТймлЬJнЬкзмЦЬ нЙЕЬездзЦуТFK
UOOuhäáã~_^NMMO
4-1
Page 26
Installation
Show/Hide Bookmarks
4.1.2 Standard assembly with fixing brackets
Assembly preparation s for 822X EëÉÉ cfd QJNF
To assemble and install the controller it is necessary to remove the unit cover. The accessory kit inside the controller contains the parts required for the assembly and installation.
1.Loosen screws (x).
2.Swing cover to the top and detach.
3.Bolt the fixing brackets onto the housing.
3 )
 N 
hPRKMNPN
cfd QJN aбгЙелбзел J лн~еЗ~кЗ ~ллЙгДду
3)
With attachable fieldbus or I/O module: Observe assembly depth and assembly space required for connection cables
[mm] 8221 / 8222 / 8223 250 402 350 22 206 370 24 250 230 6.5 24 11 8224 340 580 510 28.5 283 532 38 285 265 11 24 18 8225 340 672 591 28.5 283 624 38 285 265 11 28 18 8226 / 8227 450 748.5 680 30.5 389 702 38 285 265 11 28 18 8241 / 8242 78 384 350 39 - 365 - 250 230 6.5 30 - 8243 / 8244 97 384 350 48,5 - 365 - 250 230 6.5 30 - 8245 / 8246 135 384 350 21.5 92 365 - 250 230 6.5 30 -
a b b1 c c1 d d1 e
3)
e1 g k m
4-2
UOOuhäáã~_^NMMO
Page 27
4.1.3 Assembly of analog plug-in module
Show/Hide Bookmarks
F r o n t v i e w S i d e v i e w
Installation
8 2 7 9
hPRKMNQNd_
cfd QJO ^е~дзЦ йдмЦJбе гзЗмдЙ ЗбкЙЕнду гзменЙЗ зенз нЬЙ ЕзенкзддЙк
Assembly
D qЬЙ ~е~дзЦ йдмЦJбе гзЗмдЙ бл йдмЦЦЙЗ зенз нЬЙ кбЦЬн нЙкгбе~д лнкбй
EнЙкгбе~дл OM KKK PVFK
D qЬЙ мебн кЙимбкЙл QM гг гзкЙ ~ллЙгДду ЗЙйнЬK
Step What to do
1. Remove the socket connector possibly attached to terminals 20 ... 39.
2. Connect the analog plug-in terminal to the terminals 20 ... 39.
3. Plug the socket connector in the terminals strip of the analog plug-in module (the plug-in modules
4. Connect the analog input to the terminals E1 and 39 of the socket connector.
serves as intermediate adapter).
UOOuhäáã~_^NMMO
4-3
Page 28
Installation
Show/Hide Bookmarks

4.2 Electrical installation

4.2.1 Important notes
D mдЙ~лЙ зДлЙкоЙ нЬЙ нкбййбеЦ ЕЬ~к~ЕнЙкблнбЕ зС нЬЙ ЙKoKЕKДI бС ~ййдбЙЗK
D bелмкЙ ~ййкзйкб~нЙ ~Енбо~нбзе пЬЙе млбеЦ ЕмккЙенJзйЙк~нЙЗ ЙKдKЕKДлK
D cзк беСзкг~нбзе зе нЬЙ белн~дд~нбзе ~ЕЕзкЗбеЦ нз bj` лЙЙ ЕЬ~йнЙк QKPK
D mкбзк нз ~ллЙгДду ~еЗ лЙкобЕЙ зйЙк~нбзелI нЬЙ йЙклзееЙд гмлн ДЙ СкЙЙ зС
ЙдЙЕнкзлн~нбЕ ЕЬ~кЦЙK
D rемлЙЗ Езенкзд беймнл ~еЗ змнймнл лЬзмдЗ ДЙ ЕзоЙкЙЗ пбнЬ йдмЦлK
D fе Е~лЙ зС ЕзеЗЙел~нбзеI ЕзееЙЕн нЬЙ ЕзенкзддЙк нз нЬЙ г~бел оздн~ЦЙ зеду
~СнЙк нЬЙ облбДдЙ ЬмгбЗбну Ь~л Йо~йзк~нЙЗK
D mдЙ~лЙ зДлЙкоЙ нЬЙ кЙлнкбЕбнзел зС Й~ЕЬ г~бел нуйЙ>
Mains Operation of the controller Notes
With grounded neutral No restrictions Observe controller ratings With isolated neutral
(IT mains)
With grounded phase Operation only possible with one
DC supply via +UG/-UG DCvoltagemustbesymmetricaltoPE Controller will be destroyed when grounding
Operation with recommended mains filtersisnotpossible
variant
D Mains filter will be destroyed if ”earth fault”
occurs.
D Contact Lenze.
Contact Lenze
Gconductor or -UGconductor.
+U
4-4
UOOuhäáã~_^NMMO
Page 29
4.2.2 Power connections
Show/Hide Bookmarks
4.2.2.1 Mains connection
Types 8221 to 8227 Types 8241 to 8246
Installation
+UG
PE
L2
L1
Correct screen connection with screened cables:
D Connect the screen with the conductive mounting plate
using a suitable clamp.
D To improve the screen connection: Connect screen
additionally at the stud PE next to the power connections.
-UG
L3
hPRKMMVV
iN iO iP
Connect screen correctly (required parts in the accessory kit):
D Screw the screen plate onto the fixing brackets ➁. D Fix screen using cable lugs. Do not use the screen for
strain relief!
D To improve the screen connection: Connect screen
additionally at the stud PE next to the power connections.
cfd QJP mкзйзл~д Сзк г~бел ЕзееЙЕнбзе UOOuLUOQu
D `зееЙЕн нЬЙ г~бел Е~ДдЙл пбнЬ нЬЙ лЕкЙп нЙкгбе~дл iNI iOI iPK
J qбЦЬнЙебеЦ нзкимЙл
Terminals
Type 8221 - 8223 4 Nm (35 lbin) 8224 - 8225 7 Nm (62 lbin) 8226 - 8227 12 Nm (106.2 lbin) 8241 - 8246 0.5 ... 0.6 Nm (4.4 ... 5.3 lbin) 3.4 Nm (30 lbin)
L1, L2, L3, +UG, -UG PE connection
JrdHrd
mb
hPRKMNNO
UOOuhäáã~_^NMMO
4-5
Page 30
Installation
Show/Hide Bookmarks
4.2.2.2 Motor connection
_ЙЕ~млЙ зС нЬЙ bj` л~СЙну пЙ кЙЕзггЙеЗ нЬЙ млЙ зС лЕкЙЙеЙЗ гзнзк Е~ДдЙл зедуK
Types 8221/8222/8223
PE
T1
T2
Types 8224/8225
PE
T1
T2
UVW
UV
Correct screen connection with screened cables:
D Fix the screen of the motor cables and, if
necessary, thermal contacts by means of butt joints.Do not use the screen for strain relief!
D To improve the screen connection: Connect
screens additionally at the stud PE next to the motor connections.
hPRKMMUN
D Strain relief by using cable binders ➀. D Correct screen connection with screened cables:
W
- Connect the screen of the motor cables to the screen sheet using a cable clamp and screws
M5 x 12 ➁.
- Connect the screen of the thermal at the stud PE next to the motor connections with a
M5 X 12
surface as large as possible.
hPRKMKMNPU
Types 8226/8227
PE
T1
U
T2
V
W
D Strain relief by using cable clamps and screws
D Correct screen connection with screened cables:
M4 X 12
M5 X 12
 
hPRKMNPV
cfd QJQ mкзйзл~д Сзк нЬЙ гзнзк ЕзееЙЕнбзе пбнЬ UOOu
M4 x 12 ➂.
- Additional strain relief/fixing can be achieved
by using cable binders ➀.
- Connect the screen of the motor cables to the screen sheet using a cable clamp and screws
M5 x 12 ➁.
- Connect the screen of the thermal at the stud PE next to the motor connections with a surface as large as possible.
4-6
UOOuhäáã~_^NMMO
Page 31
Types 824X
Show/Hide Bookmarks
Connect screen correctly (required parts in the accessory kit):
D Screw the screen plate onto the fixing brackets ➁. D Fix the screen of the motor cables and, if necessary, thermal
contacts by means of butt joints. Do not use the screen for strain relief!
D To improve the screen connection: Connect screens
W
U
V
UVW
T1 T2
PE
additionally at the stud PE next to the motor connections.
cfd QJR mкзйзл~д Сзк нЬЙ гзнзк ЕзееЙЕнбзе пбнЬ UOQu
D `зееЙЕн нЬЙ гзнзк Е~ДдЙл нз нЬЙ лЕкЙп нЙкгбе~дл rI sI tK
Installation
J lДлЙкоЙ ЕзккЙЕн йздЙ ЕзееЙЕнбзеK J qбЦЬнЙебеЦ нзкимЙл
Terminals
Screen/
strain relief
Type
U, V, W PE connection
8221 - 8223 4 Nm (35 lbin) -
8224 - 8225 7 Nm (62 lbin) 3.4 Nm (30 lbin)
8226 - 8227 12 Nm (106.2 lbin)
8241 - 8246
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
3.4 Nm
(30 lbin)
M4: 1.7 Nm (15 lbin) M5: 3.4 Nm (30 lbin)
-
D pпбнЕЬбеЦ зе нЬЙ гзнзк лбЗЙ зС нЬЙ ЕзенкзддЙк бл йЙкгбннЙЗ
J Сзк л~СЙну лпбнЕЬ зСС EЙгЙкЦЙеЕу лпбнЕЬ зССFK J ЗмкбеЦ зйЙк~нбзе меЗЙк дз~ЗK
T1, T2
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
UOOuhäáã~_^NMMO
4-7
Page 32
Installation
Show/Hide Bookmarks
D qЬЙ гзнзк Е~ДдЙ лЬзмдЗ ДЙ ~л лЬзкн ~л йзллбДдЙ ДЙЕ~млЙ зС нЬЙ й злбнбоЙ
ЙССЙЕн зе нЬЙ ЗкбоЙ ЕЬ~к~ЕнЙкблнбЕK J qЬЙ н~ДдЙ EлЙЙ ДЙдзпF лЬзпл нЬЙ кЙд~нбзе ДЙнпЙЙе нЬЙ гзнзк Е~ДдЙ дЙеЦнЬ
~еЗ нЬЙ йзллбДду кЙимбкЙЗ змнймн СбднЙклK
J cзк Цкзмй ЗкбоЙл EлЙоЙк~д гзнзкл ЕзееЙЕнЙЗ нз зеЙ ЕзенкзддЙкF бн бл
еЙЕЙлл~ку нз Е~дЕмд~нЙ нЬЙ кЙлмднбеЦ Е~ДдЙ дЙеЦнЬ д
f
= pмг зС ~дд гзнзк Е~ДдЙ дЙеЦнЬл kзK зС гзнзк Е~ДдЙл
êÉë
J qЬЙ ЕзгйзеЙенл лн~нЙЗ бе нЬЙ н~ДдЙ EлЙЙ ДЙдзпF ~кЙ о~дбЗ Сзк ЕЬзййЙк
СкЙимЙеимбЙл U вeт E`MNU Z JMJI JNJFK tЬЙе млбеЦ ЕзенкзддЙкл пбнЬ ЕЬзййЙк СкЙимЙеЕбЙл [ U вeтI ЗбССЙкЙен гЙ~лмкЙл г~у ДЙ кЙимбкЙЗK mдЙ~лЙ Езен~Ен iЙетЙK
J tЬЙе млбеЦ мелЕкЙЙеЙЗ гзнзк Е~ДдЙлI нЬЙ З~н~ беЗбЕ~нЙЗ бе нЬЙ н~ДдЙ EлЙЙ
ДЙдзпF ~кЙ о~дбЗ Сзк ЗзмДдЙ гзнзк Е~ДдЙ дЙеЦнЬлK
J mдЙ~лЙ Езен~Ен iЙетЙ пЬЙе нЬЙ ~ДлздмнЙ зк кЙлмднбеЦ гзнзкJЕ~ДдЙ дЙеЦнЬл
~êÉ [ OMM ãK
W
êÉë
Type Output filters additionally required in the motor cable
0 50m 100m 200m
8221/8222 Motor filter/motor choke 8223/8224/8225
8226/8227 8241/8242/8243
8244/8245/8246
None
None Motor filter/motor choke Sine filter
None
motor choke
(Contact Lenze)
4-8
UOOuhäáã~_^NMMO
Page 33
4.2.2.3 Connection diagram
Show/Hide Bookmarks
L1
L2
L3
N
PE
K10
RB
J
K10
PE
RB
K10
Z1
PE
F1 F2 F3
L1
L2 L3
Installation
PE
+UG
-UG
RB1
RB2
+UG
PE
-UG
Z3
PE
Z2
-X1
PE
UV
W
M
3~
cfd QJS UOOuLUOQu йзпЙк ЕзееЙЕнбзел
F1, F2, F3 Fuses K10 Mains contactor Z1 Mains choke/mains filter, see Accessoires
Types 8222-8227, 8244/8246 - operation only with assigned mains choke/mains filter
Z2 Motor filter/sine filter, see Accessories Z3 Brake chopper/brake module, see Accessories RB Brake resistor, see Accessories
J
RB
Temperature monitoring - brake resistor
X1 Terminal strip in control cabinet
822X 824X
PE
hPQKMMTR
UOOuhäáã~_^NMMO
4-9
Page 34
Installation
Show/Hide Bookmarks
4.2.3 Control connections
4.2.3.1 Control cables
D tЙ кЙЕзггЙеЗ нЬЙ мебд~нЙк~д лЕкЙЙебеЦ зС ~дд Е~ДдЙл Сзк ~е~дзЦ лбЦе~дл нз
~озбЗ лбЦе~д ЗблнзкнбзеK
D `зееЙЕн нЬЙ лЕкЙЙел зС нЬЙ Езенкзд Е~ДдЙл ~л СзддзплW
J UOOuI UOQu
tбнЬ нЬЙ ЕзддЙЕнбоЙ лЕкЙЙе лЬЙЙн зе нЬЙ Скзен гЙн~д лмкС~ЕЙ EлЕкЙп дЙеЦнЬ г~сKNO ггFK
hPRKMMON
D fС нЬЙ Езенкзд Е~ДдЙл ~кЙ бенЙккмйнЙЗ EнЙкгбе~д лнкбйлI кЙд~улFI нЬЙ лЕкЙЙел гмлн
ДЙ кЙЕзееЙЕнЙЗ зоЙк нЬЙ лЬзкнЙлн йзллбДдЙ Зблн~еЕЙK
D `зеееЙЕн нЬЙ СбсбеЦ лЕкЙп зС нЬЙ лЙнйзбен йзнЙенбзгЙнЙк нз mbK
D fС йзллбДдЙI лЙй~к~нЙ нЬЙ гзебнзкбеЦ Е~ДдЙл Скзг нЬЙ гзнзк Е~ДдЙK
4-10
UOOuhäáã~_^NMMO
Page 35
4.2.3.2 Assignment of the control terminals
t
g
Vol
t
100
k
p
q
y
p
p
Show/Hide Bookmarks
Protection againstcontac
The control terminals have a basic isolation (double insulating distance). The protection against contact is ensured without any additional measures.
Protection against polarity reversal
The protection against polarity reversal prevents from the wrong connection of the internal control inputs. It is however possible to overcome the protection against polarity reversal by applying great force. The controller cannot be enabled then.
Motor temperature monitoring
The connections of the motor-temperature monitoring (T1, T2) are next to the connection terminals U, V, W.
62 7 8 9 K11 K12 K14
K21 K22 K24
20 28 E1 E2 E3 E4 39
hPRKMMOT
cfd QJT mзлбнбзе зС нЬЙ Езенкзд нЙкгбе~дл
Installation
Analog inputs
Analog output Digital
inputs
Monitoring
Termin a l Use
(Factory setting is printed in bold)
7 GND 1 8 Setpoint input,
9 Supply for setpoint potentiometer 5.2V / 6mA 62 Analog output, referenc e: terminal 7
20 Voltage supply for digital inputs
28 Controller enable HIGH E4 CW rotation/
E3 DC-injection brake HIGH E2 E1 39 GND 2 (reference for external voltages) T1 Motore-temperature monitoring
T2 Motore-temperature monitoring
reference: Termina l 7
(0 to 10V)
0 ... 6V (changes possible under C108)
15 V/20 mA
CCW rotation (CW/CCW)
JOG frequencies Binary code 20Hz, 30Hz, 40Hz
(PTC thermistor/thermal contact)
(PTC thermistor/thermal contact)
6 4 2
Jumper
5 3 1
Level Data
5-6
0to20mA
5-6
4to20mA
3-4
0to5V
1-2
0to10V
0... 10 V / 2mAResolution:10bit
CW: LOW CCW: HIGH
Resolution:10bit Linearity error: ±0.5 % Temperature fault: 0.3 % (0...+40 °C) Input resistance
age signal:>
Current signal: 250
HIGH: 12 V ... 30 V LOW: 0V...3V
If not used: set parameter C119 = -0-!
Relay output K1
Relay output K2
Termin a l Use
(Factory setting is printed in bold)
K11 Relay output normally-closed contact
(TRIP)
K12 Relay mid-position contact K14 Relay output normally-open contact
(TRIP)
K21 Relay output normally-closed contact
(Ready for operation)
K22 Relay mid-position contact 250 V AC / 3,0A or
K24 Relay output normally-open contact
(Ready for operation)
Relay position (switched) Data
opened
closed
opened 250 V AC / 3,0A or
closed 250 V AC / 3,0A or
24 V AC / 3,0 A or 60 V DC / 0.5 A
60 V DC / 0.5A
60 V DC / 0.5A
60 V DC / 0.5A
UOOuhäáã~_^NMMO
4-11
Page 36
Installation
Show/Hide Bookmarks
4.2.3.3 Connection diagrams
82XX
GND 2
GND 1
Vref
3k3
5,2V
>100k
62
78
PE
9
R ³ 1k
K11 K12
K14
K1
Vcc
2028E1E2E3 E4
3k
3k3k
3k3k
39
hPRKMMTTJP
cfd QJU `зенкзд ЕзееЙЕнбзелW pмййду пбнЬ бенЙке~д Езенкзд оздн~ЦЙ
82XX
GND 2
PE
GND 1
3k3
>100k
62 789
Vref
5,2V
K11 K12 K14
K1
3k
Vcc
20 28 E1 E2 E3 E4 39
3k
3k3k3k
-
12...30V
+
K21
K21
K22
K22
K24
K2
T1 T2
PTC
Sx
K2
K24
T1 T2
PTC
4-12
UOOuhäáã~_^NMMO
R ³ 1k
hPRKMMTTJQ
cfd QJV `зенкзд ЕзееЙЕнбзелW bснЙке~д оздн~ЦЙ лмййду EHNO s KKK HPM sF
GND1 Reference for internal voltages GND2 Reference for external voltages
GND1 and GND2 have a potential isolation inside the unit.
Sx
Page 37
Installation
V
Show/Hide Bookmarks
4.2.3.4 Connection diagrams of analog plug-in modules
Connection
8 2 2 X / 8 2 4 X
G N D 1
6 2 7 8 9 K 1 1 K 1 2 K 1 4 2 0 2 8 E 1 E 2 E 3 E 4 3 9
V C C 1 5 5 %
3 K
8 2 7 9
2 0 2 8 E 1 E 2 E 3 E 4 3 9
R
G N D 2
Voltage supply for the 8279 plug-in module:
D Plug the module on the controller. D Bridge terminals 7 and 39.
Note:
With this type of wiring there are 2 or more wires connected to one terminal.To avoid this, provide an external connection facility.
0 . . . 1 0 V
hPRKMNQOJN
cfd QJNM `зенкзд ЕзееЙЕнбзелW pмййду пбнЬ бенЙке~д Езенкзд оздн~ЦЙ
Danger!
8 2 2 X / 8 2 4 X
G N D 1
6 2 7 8 9 K 1 1 K 1 2 K 1 4 2 0 2 8 E 1 E 2 E 3 E 4 3 9
V C C 1 5 5 %
G N D 2
There is no mains isolation between external supply and unit mass. There is no double mains isolation between the mains and the terminals. Therefore, the unit is not electrically isolated, i.e. not protected against contact.
Connection
Voltage supply for the 8279 plug-in module:
D Plug the module on the controller.
8 2 7 9
2 0 2 8 E 1 E 2 E 3 E 4 3 9
R
G N D
D Bridge terminals 7 and 39.
Note
With this type of wiring there are 2 or more wires connected to
0 . . . 1 0 V
1 2 . . . 3 0
hPRKMNQOJO
one terminal.To avoid this, provide an external connection facility.
cfd QJNN `зенкзд ЕзееЙЕнбзелW pмййду пбнЬ ЙснЙке~д Езенкзд оздн~ЦЙ EHNO KKK HPM sF
GND1 Reference for internal voltages GND2 Reference for external voltages
GND1 and GND2 have a potential isolation inside the unit.
UOOuhäáã~_^NMMO
4-13
Page 38
Installation
Show/Hide Bookmarks
4.3 Installation of a CE-typical drive system
General notes
- If you observe the following measure you can be sure that the drive system will not cause any EMC problems, i.e. comply with the EMC Directive when running the machine.
- If devices which do not comply with the CE requirement concerning noise immunity EN 50082-2 are operated close to the controller, these devices may be interfered electromagnetically by the controllers.
Assembly D Connect controller, mains choke, and mains filter to the grounded mounting plate with a wire of large a
cross-section as possible:
- Mounting plates with conductive surfaces (zinc-coated, stainless steel) allow permanent contact.
- Varnished boards should not be used for installation in accordance with EMC
D If you use several mounting plates:
- Connect as much surface as possible of the mounting plates (e.g. with copper bands).
D Ensure the separation of motor cable and signal or mains cable. D Do not use the same terminal strip for mains input and motor output. D Cable guides as close as possible to the reference potential.Unguided cables have the same effect as aerials.
Filters D Use mains filters or RFI filters and mains chokes which are assigned to the controller:
- RFI filters reduce impermissible high-frequency interference to a permissible value.
- Mains chokes reduce low-frequency interferences which depend on the motor cable and its length.
- Mains filters combine the functions of mains choke and RFI filter.
Screening D Connect the screen of the motor cable with the controller
- to the screen connection of the controller.
- additionally to the mounting plate with a surface as large as possible.
- Recommendation: For the connection, use ground clamps on bare metal mounting surfaces.
D If contactors, motor-protecting switches or terminals are located in the motor cable:
- Connect the screens of the connected cables also to the mounting plate, with a surface as large as possible.
D Connect the screen to PE, with a surface as large as possible.
- Metal glands at the motor terminal box ensure a connection of the screen and the motor housing.
D If the mains cable between mains filter and controller is longer than 300 mm:
- Screen mains cables.
- Connect the screen of the mains cable direc tly to the inverter and to the mains filter and connect it to the mounting plate with as large a surface as possible.
D Use of a brake chopper:
- Connect the screen of the brake resistor cable directly to the mounting plate, at the brake chopper and the brake resistor with as large a surface as possible.
- Connect the screen of the cable between controller and brake chopper directly to the mounting plate, at the inverter and the brake chopper with a surface as large as possible.
D Screen the control cables:
- Connect both screen ends of the digital control cables.
- Connect one screen end of the analog co ntrol cables.
- Always connect the screens to the screen connection at the controller over the shortest possible distance.
D Application of the controllers 821X/822X/824X in residential areas:
- Use an additional screen damping ³ 10 dB to limit the radio interference. This is usually achieved by installation in enclosed and grounded control cabinets made of metal.
Grounding D Ground all metallically conductive components (controller, mains filter, motor filter, mains choke) using suitable
cables connected to a central point (PE bar).
D Maintain the minimum cross-sections prescribed in the safety regulations:
- For EMC, not the cable cross-section is important, but the surface and the contact with a cross-section as large as possible, i.e. large surface.
4-14
UOOuhäáã~_^NMMO
Page 39
Installation
Show/Hide Bookmarks
M a i n s
P E
P E
R B
P E S
P E S P E S
P E
R B 1 R B 2 + U G
- U G
Z 3
n
n
n
F 1
n
K 1 0
Z 1
+ U G
P E
n
P E S
P E S
L x
P E
8 2 X X
- U G
G N D 1
V r e f
7 8 9
U
V
W
P E
6 2
P E S
P E S
K 1 1
K 1 2 K 1 4
K 1
V c c
2 0
2 8
E 1
G N D 2
E 4 3 9
E 2
E 3
P E S
P E S
P E
P E S
Z 2
- X 1
P E S
M
P E
cfd QJNO bс~гйдЙ Сзк ~е белн~дд~нбзе бе ~ЕЕзкЗ~еЕЙ пбнЬ нЬЙ bj` кЙЦмд~нбзелW
F1 Fuse K10 Mains contactor Z1 Mains filter ”A” or ”B”, see Accessories Z2 Motor filter/sine filter, see Accessories Z3 Brake module/brake chopper, see Accessories
-X1 Terminal strip in control cabinet RB Brake resistor PES HF screen because auf PE connection with a surface as large as possible (see chapter ”Screening”) n Number of phases
P E
3 ~
hPRKMMUOÄ
UOOuhäáã~_^NMMO
4-15
Page 40
Installation
Show/Hide Bookmarks
4-16
UOOuhäáã~_^NMMO
Page 41

5 Commissioning

Show/Hide Bookmarks
qЬЙ ЕзенкзддЙкл ~кЙ С~ЕнзкуJлЙн нз ЗкбоЙ ~ ЕзккЙлйзеЗбеЦ СзмкJйздЙ лн~еЗ~кЗ ~луеЕЬкзезмл гзнзкK cмкнЬЙк лЙннбеЦл ~кЙ езн еЙЕЙлл~куK
D OPMLQMM sI RM eò
D OSRLQSM sI SM eò
D OUMLQUM sI SM eò
lеду ~ СЙп лЙннбеЦл об~ нЬЙ UOMN __ зйЙк~нбеЦ гзЗмдЙ зк ~ СбЙдЗДмл гзЗмдЙ ~кЙ еЙЕЙлл~ку нз ~З~йн у змк ЗкбоЙ нз узмк ~ййдбЕ~нбзеK qЬЙ лнЙйл кЙимбкЙЗ ~кЙ лмгг~кбтЙЗ бе ЕЬ~йнЙк RKP ~еЗ бе ЕЬ~йнЙк RKQK

5.1 Before you switch on

mкбзк нз бебнб~д лпбнЕЬJзе зС нЬЙ ЕзенкзддЙкI ЕЬЙЕв нЬЙ пбкбеЦ Сзк ЕзгйдЙнЙеЙллI лЬзкнJЕбкЕмбнI ~еЗ Й~кнЬ С~мднW
Commissioning
D mзпЙк ЕзееЙЕнбзеW
J sб~ iNI iO ~еЗ iP J ^днЙке~нбоЙду об~ нЙкгбе~дл HrdI Jrd Ea`JЦкзмй ЗкбоЙF
D `зенкзд нЙкгбе~длW
J oЙСЙкЙеЕЙ йзнЙенб~д Сзк нЬЙ Езенкзд нЙкгбе~дл бл нЙкгбе~д PVK J `зенкзддЙк Йе~ДдЙW нЙкгбе~д OU J pЙдЙЕнбзе зС ЗбкЙЕнбзе зС кзн~нбзеW нЙкгбе~д bP зк bQ J bснЙке~д лЙнйзбен лЙдЙЕнбзеW нЙкгбе~дл TI U J `ЬЙЕв амгйЙк йзлбнбзе> c~Ензку лЙннбеЦW M J NM s EлЙЙ нЬЙ н~ДдЙ бе
ÅÜ~éíÉê QKOKPKOFK
J aмкбеЦ зйЙк~нбзе пбнЬ ~е бенЙке~д оздн~ЦЙ лмййду об~ нЙкгбе~д OMI ДкбЗЙ нЬЙ
нЙкгбе~дл T ~еЗ PVK
D fе Е~лЙ зС ЕзеЗЙел~нбзе ЕзееЙЕн нЬЙ Е зенкзддЙк нз г~бел оздн~ЦЙ зеду ~СнЙк нЬЙ
облбДдЙ ЬмгбЗбну Ь~л Йо~йзк~нЙЗK
j~бен~бе нЬЙ лпбнЕЬJзе лЙимЙеЕЙ>
UOOuhäáã~_^NMMO
5-1
Page 42
Commissioning
p
g
p
d
t
i
p
que,
torqu
e
control
control
V
min
boost,see
Show/Hide Bookmarks

5.2 Short set-up (factory setting)

5.2.1 Switch-on sequence
Step
1.Switch on mains voltage
2.Select the direction of rotation. D CW rotation:
- Apply a LOW signal to terminal E4 (0...+3V).
D CCW rotation:
- Apply a HIGH signal to terminal E4 ( +12...+30V).
3.Select the setpoint. Apply a voltage 0...+10 V to terminal 8.
4.Enable the controller . Apply a HIGH signal (+12...+30V) to terminal 28.
5.The drive is now operating according to factory setting.
5.2.2 Factory setting of the most important drive parameters
Setting Code Factory setting Adaption to
Operating mode C001 -0- Setpoint selection via terminal 8
Control v ia terminals Parameter setting via 8201BB
Terminal configuration C007 -0- E4 E3 E2 E1
CW/CCWDC brakeJOG1/2/3
Machine data Chapter 5.3 ff. Speed range
Acceleration and
ecelera
times Current limit
values Drive performance Chapter 5.4 ff.
Current,
,
tor power
characteristic
Min. field frequency C010 0.00 Hz Max. Field frequency C011 50.00 Hz
Acceleration time C012 5.00 s
on
Deceleration time C013 5.00 s
Motor mode C022 150 % Generator mode C023 80 %
Operating mode C014 -4- Motor-current control
V/f rated frequency C015 50.00 Hz
V
setting C016 0,00 %
min
Slip compensation C021 0,0 %
the application
Seecodetable, chapter 7.2
Seecodetable, chapter 7.2
Chapter 5.3.1
Chapter 5.3.2
Chapter 5.3.3
Motor-current control chapter 5.4.2.2
V/f characteristic control
D with constant
boost, see
V
min
chapter
5.4.2.1
5-2
UOOuhäáã~_^NMMO
Page 43

5.3 Adapt machine data

Show/Hide Bookmarks
Commissioning
5.3.1 Determine speed range (f
Code Name
Possible settings
dmin,fdmax)
IMPORTANT
Lenze Selection Info
C010 Minimum field
0.00 0.00 {0.02Hz} 480.00
frequency
C011 Maximum field
50.00 7.50 {0.02Hz} 480.00
frequency
Function The speed range required for the application can be selected here by determing the field
and f
frequencies f
D f
dmin
D f
dmax
dmin
corresponds to the speed at 0 % speed setpoint selection.
corresponds to the speed at 100 % speed setpoint selection.
dmax
:
Adjustment Relation between field frequency and synchronous motor speed:
SM
Ñ
Çã~ñ
å
=
êëóå
é
n f
synchronous motor speed [min-1]
rsyn
Max. field frequency [Hz]
dmax
p Number of pole pairs
Example: 4 pole asynchronous motor:
dmax
=50Hz
p = 2, f
Important D With the setting of f
D When selecting the setpoint by means of JOG values, f D f
is and internal standardization variable:
dmax
dmin>fdmax
the field frequency is limited to f
RM SM
å
êëóå
=
O
dmax
= NRMM ãáå
ÓN
.
dmax
acts as limitation.
- Use the LECOM interface only for important modifications, when the controller is inhibited.
D Observe the maximum speed of the motor! D f
is only effective under the following conditions:
dmin
- With analog setpoint selection.
- With the motor potentiometer function ”DOWN”.
Special features
D With field frequencies f
> 300Hz:
d
- Avoid chopper frequencies < 8 kHz.
D With C500 and C501, you can relate the display value of f
fd
C011 (fdmax)
C010 (fdmin)
0 % 100 %
dmin
and f
toaprocessvalue.
dmax
hPRKMMSO
UOOuhäáã~_^NMMO
5-3
Page 44
Commissioning
Show/Hide Bookmarks
5.3.2 Adjustment of acceleration and deceleration times (Tir,Tif)
Code Name
Possible settings Lenze Selection Info
C012 Acceleration time 5.00 0.00 {0.02s} 1300.00 T C013 Deceleration time 5.00 0.00 {0.02s} 1300.00 T
ir
if
Function The accleration and deceleration times determine the time required by the drive to follow a setpoint
change.
Adjustment
D The acceleration and deceleration times refer to a change of the field frequency from 0 Hz to the
max. field frequency set under C011.
D Calculate the times T
and tifare the times required for the change between fd1and fd2:
-t
ir
Ñ
qáê= íáê⋅
Çã~ñ
ÑÇO− Ñ
and Tif, which must be set under C012 and C013.
ir
Ñ
ÇN
qáÑ= íáÑ⋅
Çã~ñ
ÑÇO− Ñ
ÇN
Important Under unfavourable operating conditions, too short acceleration and deceleration times can lead to
the deactivation of the controller under overload with the indication of TRIP OC5. In these events, the acceleration and deceleration times should be set short enough so that the drive can follow the speed profile without reaching I
f /Hz
d
f
dmax
f
d2
f
d1
0
t
ir
T
ir
of the controller.
max
t
if
T
if
t
hPRKMMSP
5-4
UOOuhäáã~_^NMMO
Page 45
Commissioning
Show/Hide Bookmarks
5.3.3 Setting of the current limit (I
Code Name
C022 I
C023 I
Function The controllers are equipped with a current-limit control which determines the dynamic response
Adjustment The acceleration and decleration time should be set short enough so that the drive can follow the
Drive characteristic when reaching the limit value
limit
max
motor mode
limit
max
generator mode
Possible settings Lenze Selection Info
150 30 {1 %} 150
80 30 {1 %} 150
under load. The measured load is compared with the limit values set under C022 for motor load and under C023 for generator load. If the current-limit values are exceeded, the controller will change its dynamic response.
speed profile without reaching I
D During acceleration:
- Expansion of the acceleration ramp.
D During deceleration:
- Expansion of the deceleration ramp.
D When the load increases at constant speed:
- When the motor-current limit value is reached: Reduction of the field frequency to 0.
- When the generator-current limit value is reached:
Increase the field frequency to the maximum frequency (C011).
- Stop the field-frequency change if the load falls below the limit value.
max
)
max
of the controller.
IMPORTANT
Important
D In the generator mode the current can only be controlled correctly when you connect a brake unit
or in group drive with energy exchange.
D For operation with chopper frequencies > 8 kHz, the current limit values should be set to the
currents ”I . (Derating with higher chopper frequencies)
for 60 s” indicated in the rated data (see chapter 3.3
max
UOOuhäáã~_^NMMO
5-5
Page 46
Commissioning
N
Show/Hide Bookmarks
5.4 Optimisation of the operating characteristic of the drive
_у гЙ~ел зС нЬЙ СзддзпбеЦ лЙннбеЦл узм Е~е беСдмЙеЕЙ нЬЙ ЕмккЙенI нзкимЙ ~еЗ йзпЙк ЕЬ~к~ЕнЙкблнбЕ зк нЬЙ ЕзееЙЕнЙЗ гзнзкK
vзм Е~е ЕЬззлЙ ДЙнпЙЙе нЬЙ Езенкзд гзЗЙл ТгзнзкJЕмккЙен ЕзенкздТ ~еЗ ТsLСJЕЬ~к~ЕнЙкблнбЕ ЕзенкздТK fе ЕЬ~йнЙк RKQKN узм пбдд СбеЗ лзгЙ гзкЙ беСзкг~нбзе нз ЬЙдй узм пбнЬ нЬЙ лЙдЙЕнбзеK
5.4.1 Select the control mode
Code Name
Possible settings Lenze Selection Info
C014¿ Operating mode -4- -2- Linear characteristic V~fdwith constant V
boost.
2
-3- Square characteristic V~f boost
V
min
with constant
d
-4- Motor-current control
Function D Under C014 you can set the control mode and the voltage characteristic.
D The V/f-characteristic control with auto boost enables a low-loss operation of single drives with
standard three-phase AC motors with load-dependent V
D The motor-current control enables a ”Sensorless Speed Control”. Compared with the V/f
min
boost.
characteristic control, the drive can operate with a considerable higher torque and consumes less current during idle running.
C014 = -2­Linear characteristic
V o u t
1 0 0 %
V
m i n
0
0 1
f
d
f
d N
C014 = -3­Square-law characteristic (e. g. for pumps, fans)
V o u t
1 0 0 %
V
m i n
0
0
f
d
1
f
d
Control modes of the
min
voltage characteristic
hPRKMMSRd_
5-6
UOOuhäáã~_^NMMO
Page 47
Commissioning
Show/Hide Bookmarks
Help for decision Motor cable
screened ≤50 m
unscreened ≤100 m
C014
Single drives
With constant load -4- -2- -2- ­With changing loads -4- -2- -2- ­With heavy start conditions -4- -2- -2- ­High-dynamic positioning and feed drives -2- - -2- ­Lifts and hoists -4- -2-/-4- -2- ­Pumps and fan drives -3- -2- -3- -2­Three-phase reluctance motors -2- - -2- ­Three-phase sliding rotor motors -2- - -2- ­Three phase motors with assigned frequency-voltage
characteristic Group drives (depending on the resulting motor-cable
length) same motors and loads -4- -2- -2- ­different motors and/or changing loads -2- - -2-
recommended alternatively recommended alternatively
-2- - -2- -
ä
= á⋅ N+ äO+  + äáF
êÉë
screened > 50 m
unscreened > 100 m
UOOuhäáã~_^NMMO
5-7
Page 48
Commissioning
Show/Hide Bookmarks
5.4.2 Optimisation of operating modes
5.4.2.1 Optimisation of V/f characteristic control with constant V
boost
min
Codes required
Code Name
C015
V/f rated frequency 50.00 7.50 {0.02Hz} 960.00
C016
V
setting 0.00 0.00 {0.02 %} 40.00
min
C021
Slip compensation 0.0 -50.0 {0.1 %} 50.0
Adjustment
1.If necessary, select V/f characteristic (C014).
2.Select V/f-rated frequency (C015).
V o u t V o u t
1 0 0 %
Possible settings Lenze Selection Info
D The V/f-rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.
D An internal mains voltage compensation compensates deviations in the mains during operation.
They therefore do not have to be considered for the setting of C015.
Adjustment
Calculate the frequency to be set under C105:
`MNRxeòz =
C014 = -2­Linear characteristic
QMMs
s
к~нЙЗ гзнзк
o~нЙЗ гзнзк СкЙимЙеЕу xeтz
xsz
C014 = -3­Square-law characteristic (e. g. for pumps, fans)
1 0 0 %
IMPORTANT
5-8
UOOuhäáã~_^NMMO
V
m i n
0
0 1
V
m i n
f
d
f
d N
0
0
1
f
d
f
d N
hPRKMMSR
Page 49
Commissioning
p
p
Show/Hide Bookmarks
3.Set the Vmin boost (C016). D Load independent boost of the motor voltage for field frequenc ies below the rated V/f
frequency.You can thus optimize the torque performance of the inverter drive.
D It is absolutely necessary to adapt the asynchronous motor used, since otherwise, the motor can
be destroyed by overtemperatue:
Adjustment
Please note the thermal characteristic of the connected motor under small field frequencies:
D Usually, standard asynchronous motors with insulation class B can be operated for a short time
with rated current and frequencies between 0Hz ≤ f
D Please ask the motor manufacturer for the exact setting values for the motor current.
A Operate the motor when no load is applied with a slip frequency of f
7,5 kW: fd≈5Hz
-P
Mot
-P
>7,5 kW: fd≈2Hz
Mot
B Increase V
until you reach the following motor current:
min
25Hz.
d
:
d
- Motor in short-term operation at 0Hz fd≤ 25Hz:
with self-ventilated motors: I with forced ventilated motors: I
motor motor
0.8 II
rated motor
rated motor
- Motor in permanent operation at 0Hz fd≤ 25Hz:
0.8 ¡ I
motor motor
I
rated motor
rated motor
s Slip constant (C021)
synchronous motor speed [min-1]
n
rsyn
rated speed to motor nameplate [min-1]
n
r
rated frequency to motor nameplate [Hz]
f
dr
4.Set slip compensation (C021).
with self-ventilated motors I with forced ventilated motors: I
Rough setting by means of the motor data:
å
å
ê
êëóå
ë =
å
êëóå
NMMB
å
êëóå
SM
Ñ
Çê
=
é
p Number of pole pairs
Precise setting:
Change C021 under constant load until the speed is near the synchronous speed. If C021 is set to too high values, the drive may become instable (overcompensation).
Important The change from V/f-characteristic control to motor-current control should only be made when the
controller is inhibited.
UOOuhäáã~_^NMMO
5-9
Page 50
Commissioning
t
h
i
twh
t
(
)
p
p
Show/Hide Bookmarks
5.4.2.2 Optimisation of motor-current control
Codes required
Code Name
Possible settings
IMPORTANT
Lenze Selection Info
C015
V/f rated frequency 50.00 7.50 {0.02Hz} 960.00
C021
Slip compensation 0 -50.0 {0.1 %} 50.0
C088 Rated motor current * 0.0 ... 2.0 ¡ rated output current
C091 Motor cos j * 0.4 {0.1} 1.0
* depends on
eun
Input only necessary
en motors no
adapted.
Setting sequence D Drives with matching 4 pole standard motors 230/400 V in star connection do not need to be
adapted.After having started the drive, the controller itself detects all further motor data.
D The following drives can be optimized by entering the nameplate data ”rated motor current” and
”cos j” under C088 or C091:
- Motor one power class smaller than the motor assigned to the controller.
- Motor one or two power classes smaller than the motor assigned to the controller.
-Driveswith2,6,8,10and12polestandardmotors.
- Drives with special motors.
D With the slip compensation C021, you can optimize the ”sensorless speed control” for your
application.
1.If nece ssary,
(factory setting)
select C014 = -4-.
2.Select V/f-rated frequency (C015).
Motor voltage
Motor connection
C015
220/380 V Y 52,6 Hz 230/400 V, 265/460 V, 280/480 V Y 50 Hz 220/380 V, 230/400 V, 265/460 V, 280/480 V D 87 Hz 380/660 V D 52,6 Hz 400/690 V D 50 Hz
5-10
3.If nec essary, enter the motor data of unadapted motors (C088, C091).
4.Set slip compensation (C021):
Important
UOOuhäáã~_^NMMO
Rough setting by means of the motor data:
ë =
å
êëóå
êëóå
=
NMMB
å
êëóå
SM
Ñ
Çê
é
s Slip constant (C021) n n f
synchronous motor speed [min-1]
rsyn
rated speed to motor nameplate [min-1]
r
rated frequency to motor nameplate [Hz]
dr
å
å
ê
p Number of pole pairs
Precise setting:
Change C021 under constant load until the speed is near the synchronous speed. If C021 is set to too high values, the drive may become instable (overcompensation).
D The change from V/f-characteristic control to motor-current control should only be carried out
when the controller is inhibited.
D The idle current of the motor (magnetizing current) must not exceed the rated current of the
controller.
D With very small friction values it is possible that an angle offset of up to 180° occurs when
enabling the controller.
Page 51

5.5 Operation with the PID-controller

Show/Hide Bookmarks
qЬЙ СзддзпбеЦ Езенкздл Е~е ДЙ бгйдЙгЙенЙЗ пбнЬ нЬЙ бенЙке~д йкзЕЙлл ЕзенкзддЙкW
D mкЙллмкЙ
D qЙгйЙк~нмкЙ
D cäçï
D eмгбЗбну
D péÉÉÇ
D a~еЕЙкJйзлбнбзеK
Settings
Configuration Set C005 -6- or -7- for controlled operation with a PID controller. Setpoint The setpoint can be set via terminal 8 or terminal E1. The terminal not used for
Terminal E1
setpoint selection is used for the feedback.
D If you use the ”analog plug-in module 8279” terminal E1 will be used as
2nd analog input (0 ... 10 V / 0/4 ... 20 mA).
D If you do not use the ”analog plug-in module 8279”, terminal E1 can be used as
digital input. Pulse frequency 0 ... 10 kHz with level:
0 ... 3V = LOW
12... 30V = HIGH
Commissioning
qЬЙ ЕзЗЙл `MTM нз `MTO ~кЙ ЙлйЙЕб~дду Сзк й~к~гЙнЙк лЙннбеЦ зС нЬЙ mfa ЕзенкзддЙк EлЙЙ `зЗЙ н~ДдЙ
).
fе ~ЗЗбнбзеI нЬЙ беСдмЙеЕЙ зС нЬЙ mfa ЕзенкзддЙк Е~е ДЙ лЙн меЗЙк `MTQK rеЗЙк `OPU узм Е~е лЙдЙЕн пЬЙнЬЙк узм п~ен ~ лЙнйзбен йкЙЕзенкзд зк езнK qЬбл бл оЙку ~Зо~ен~ЦЙзмл Сзк ~ййдбЕ~нбзел бе пЬбЕЬ нЬЙ лЙнйзбен лбЦе~д бл ЗбкЙЕнду йкзйзкнбзе~д нз нЬЙ ЗкбоЙ лйЙЙЗK qЬмл бн бл йзллбДдЙ нз дбгбн нЬЙ беСдмЙеЕЙ зС нЬЙ mfa ЕзенкзддЙкI лмЕЬ нЬ~н зеду нЬЙ г~сбгмг ЙсйЙЕн~ДдЙ лдбй зС нЬЙ г~ЕЬбеЙ пбдд ДЙ ЕзгйЙел~нЙЗK
qЬЙ ~Енм~д о~дмЙ зС нЬЙ mfa ЕзенкзддЙк бл Зблйд~уЙЗ меЗЙк `MRNK qЬЙ mfa ЕзенкзддЙк лЙнйзбен бл Зблйд~уЙЗ бе `MQS зк `MQVK qЬЙ Езенкзд к~еЦЙ Е~е ДЙ дбгбнЙЗ Ду ~ЗамлнбеЦ нЬЙ ~е~дзЦ беймнл E`MOSI `MOT Сзк нЙкгбе~д UX `QOSI `QOT Сзк нЙкгK bN пбнЬ йдмЦJбе гзЗмдЙ UOTVFK qЬбл Е~е ДЙ млЙЗI Сзк белн~еЕЙ бе йкЙллмкЙ ЕзенкздлI нз ЗЙнЙкгбеЙ нЬЙ йкЙллмкЙ лЙнйзбенK
qЬЙ fJЕзгйзеЙен зС нЬЙ ЕзенкзддЙк Е~е ДЙ кЙлЙн пЬЙе кЙ~ЗбеЦ нЬЙ n
нЬкЙлЬздЗ
ãáå
E`MNTF нз лмййкЙлл нЬЙ бебнб~д ЕзеЗбнбзел ДЙЕ~млЙ зС нЬЙ гбллбеЦ ~Енм~д о~дмЙK
UOOuhäáã~_^NMMO
5-11
Page 52
Commissioning
l
icat
iondat
b
l
Show/Hide Bookmarks
5.5.1 Standardisation of process value
UONuLUOOu лЙннбеЦ к~еЦЙLUOQuW
Code Name Possible settings IMPORTANT
Lenze Selection Info
C500* Display factor
app numerator
C501* Display factor for
process varia denominator
2000 1 {1} 25000
um
10 1 {1} 25000
e
Function Adaption of the field-frequency related parameters C010, C011, C017, C019, C037, C038, C039,
C050,C051 and C181 to a process value to be controlled, e.g. pressure, temperature, flow rate, humidity or speed. By this, an absolute or relative display or selection of a process value can be implemented.
Adjustment
The display value CXXX is calculated from:
CXXX =
C011
200
C500 C501
Example Relative or absolute selection and display of a speed setpoint
= 5 bar, fdmax =50Hz:
P
soll
a) Relative standardisation in %
50
100, 0 (%) =
200
4000
10
(e. g. C500=4000; C501=10)
b) Absolute standardisation in physical units
50
5, 00(bar) =
200
200
10
(e. g. C500=200; C501=10)
5-12
UOOuhäáã~_^NMMO
Page 53

5.6 Application examples

Show/Hide Bookmarks
5.6.1 Air conditioning
Cold
water
Mist
collector
Heat
exchanger
Hot
water
Water
treatment
Commissioning
-
Water
V-belt
M
3
v
u
w
DDC
Speed set-value
8210/20/40 with operating unit
STP
PRG
L
SH
RUN
L
3
E
7
8
injection
Speed set-value
39
DDC
STP
PRG
SH
Circulation
pump
RUN
*
2
Z
Unit 1
M
7
u
3
wv
*
2
Z
1
2
G
3
G
V
U
Unit 2
8
2
G
3
G
V
U
W
L
L
L
-U
+U
W
*
1
Z
1
L1L2L
L
L
L
-U
+U
*
1
Z
1
K
1
F
3
hPRKMNQPd_
cfd RJN ^ййдбЕ~нбзе Йс~гйдЙ зС ~е ~бк ЕзеЗбнбзебеЦ лулнЙг
* Z1 Mains filter required for radio interference level A or B. * Z2 Motor filter required for motor cables: screened as from 50 m, unscreened as from 100 m.
Sine filter required for motor cables: screend as from 100 m, unscreened as from 200 m.
Screen all signal and motor cables. Please observe the corresponding installation instruction in chapter 4.2 and 4.3.
UOOuhäáã~_^NMMO
5-13
Page 54
Commissioning
Show/Hide Bookmarks
Ta sk ( FI G 5 - 1):
qЬЙ ~бк ЕзеЗбнбзе зС ~ ЗЙй~кнгЙен лнзкЙ бл нз ДЙ ЕзенкзддЙЗ ~ЕЕзкЗбеЦ нз нЬЙ емгДЙк зС йЙклзел йкЙлЙенKqЬЙ С~ел гмлн ЕбкЕмд~нЙ ~е ~гзмен зС ~бк нЬ~н ЕзккЙлйзеЗл нз нЬЙ емгДЙк зС йЙзйдЙ EЗ~н~I Сзк белн~еЕЙI йкзобЗЙЗ Ду ~ йЙклзе ЕзменбеЦ мебнFK
Functions used
D Belt monitoring D Mains failure detection
- Controlled deceleration and stopping of the drive after mains failure
D Flying restart circuit on coasting motor D Removal of mechanical resonances D Smoothstart/stopwithSramps
`зЗЙ лЙннбеЦл J мебн NW
Code Name Possible settings
C001
Operating mode -0- -0- Setpoint selec tion via term. 8
C2001
C005
Configuration -0- -0- Operation with open-loop control via terminal 8
C2005
C008
Function relay K1 -1- -14- Apparent motor current (C054) < Current threshold C156
C2008
C014
Operating mode -0- -3- Square characteristic V~f
C2014
C142
Start condition -1- -3- Automatic start, if term. 28 HIGH, flying-restart circuit
C2142
C156 Current threshold 0 50 % C182 t C625 Locked frequency 1 480.00 30.00Hz Removal of mechanical resonances C628 Bandwidth of skip frequencies,
f
C988 DC-bus voltage threshold for
DC-bus voltage control
RFG S shape 0.00 0.50 s Smooth start / stop
integration
skip
(the parameters selected must be adapted to the machine data)
Lenze Selection
0.00 10.00 %
0 81 % Controlled deceleration and stopping after mains failure by
Motor deceleration after mains failure
(jumper setting see chapter 4.2.3.2) Control via term. parameter settingwith 8201BB
and acceleration finished (Belt monitoring)
2
with constant V
d
active
changing the parameter set
min
boost
5-14
UOOuhäáã~_^NMMO
m~к~гЙнЙк лЙн ЕЬ~еЦЙзоЙк Ду ЕзенкзддбеЦ нЬЙ a` Дмл
PAR 1 PAR 2 (Code = C2XXX)
C007=2 C105 = 0.5 s
C2007 = 0 C2105 = 5.00 s
kзнЙW qЙкгбе~д P гмлн ~дп~ул Ь~оЙ ilt дЙоЙд Em^oOW kзкг~д зйЙк~нбзеX m^oNW npmF
Page 55
Commissioning
Show/Hide Bookmarks
`зЗЙ лЙннбеЦл J мебн OW
Code Name Possible settings
Lenze Selection Info
C001 Operating mode -0- -0- Setpoint selection via term. 8. Control via
C005 Configuration -0- -0- Operation with open-loop control via terminal 8 C014 Operating mode -0- -3- Square characteristic V~f
According to the information given in both tables (code setting for unit 1 and 2):
1. All other parameters are based on the factory setting.
2. Set the rated motor data (depends on the motor used) under C088 (rated motor current) and C091 (motor cos φ).
terminals. Parameter setting via 8201BB
2
with constant
boost
V
min
d
UOOuhäáã~_^NMMO
5-15
Page 56
Commissioning
Show/Hide Bookmarks
5.6.2 Pump application with pressure control
P u m p
P r e s s u r e s e n s o r
0 - 1 0 V , 0 / 4 - 2 0 m A
p
-
+
A c t .
p r e s s u r e v a l u e
M
3
v
u
D i s p l a y w i t h
a n a l o g i n p u t
P r e s s u r e
s e t - v a l u e
e . g . f r o m P L C
o r e x t e r n a l T e r m i n a l
U p
R F R
D o w n
2 8
E
2 0
2 1 0 2
1E3E2
M / R
J O G
4
E
w
X 1
*
2
Z
3
L
2
L
1
*
1
Z
1
K
1
F
L
L e n z e 8 2 1 0 / 2 0 / 4 0 f r e q u e n c y i n v e r t e r
789
L
6 2
K 1 4
K 1 2
K 1 1
5-16
UOOuhäáã~_^NMMO
F a u l t m e s s a g e
e . g . P L C
hPRKUOhMMO
cfd RJO ^ййдбЕ~нбзе зС ~ ймгй пбнЬ йкЙллмкЙ Езенкзд
* Z1 Mains filter required for radio interference level A or B.
Mains choke see chapter 3 Rated Data
* Z2 Motor filter required for motor cables: screened as from 50 m, unscreened as from 100 m.
Sine filter required for motor cables: screend as from 100 m, unscreened as from 200 m.
Screen all signal and motor cables. Please observe the corresponding installation instruction in chapter 4.2 and 4.3.
Page 57
Commissioning
Show/Hide Bookmarks
Ta sk ( FI G 5 - 2):
^ ЕЙенкбСмЦ~д ймгй бл млЙЗ нз ЙелмкЙ Езелн~ен йкЙллмкЙ бе ~ йбйЙдбеЙ лулнЙг EЙKЦK Сзк п~нЙк лмййду зС кЙлбЗЙенб~д ~еЗ беЗмлнкб~д йкЙгблЙлFK
qЬЙ ~ййдбЕ~нбзе ЗзЙл езн зеду кЙимбкЙ кЙгзнЙ Езенкзд Скзг ~ ЕЙенк~д зйЙк~нбеЦ й~еЙд Дмн ~длз лЙннбеЦ йзллбДбдбнбЙл ~н лбнЙK qЬЙ йкЙллмкЙ бл нз ДЙ кЙЗмЕЙЗ нз ~ СбсЙЗ о~дмЙ ЗмкбеЦ нбгЙл пЬЙе зеду СЙп п~нЙк бл кЙимбкЙЗK _у гзебнзкбеЦ нЬЙ ~Енм~д йкЙллмкЙ бн бл ~длз йзллбДдЙ нз ЗЙнЙЕн Дмклн йбйЙлK
cмеЕнбзел млЙЗ
D fенЙке~д mfa ЕзенкзддЙк Сзк йкЙллмкЙ ЕзенкздK
J oЙЦмд~к ЕзенкздI лЙнйзбен лЙдЙЕнбзе об~ СбЙдЗДмл пбнЬ СЙЙЗД~Ев об~ ~е~дзЦ
ЕЬ~ееЙд нЙкгбе~д UK
D kЙнпзквбеЦ об~ СбЙдЗДмл EЙKЦK йдмЦJзе гзЗмдЙ ONMOFK
D j~ем~д L oЙгзнЙ ЕЬ~еЦЙзоЙк EjJLJoFK
J `Ь~еЦЙ ДЙнпЙЙе лЙнйзбен лЙдЙЕнбзе об~ СбЙдЗДмл ~еЗ г~ем~д
гзгЙен~куJЕзен~Ен лпбнЕЬ EнЙкгбе~д bN Z ЗзпеI нЙкгбе~д bO Z мйFK
D pЙдЙЕнбзе зС ~ йкзЕЙлл лЙнJо~дмЙ EЙKЦK йкЙллмкЙ лЙнJо~дмЙF об~ gld о~дмЙ зС
нЬЙ беоЙкнЙкK
D bдЙЕнкбЕ~д ЕзенкзддЙк беЬбДбнK
`зЗЙ лЙннбеЦлW
Code Name Possible settings IMPORTANT
Lenze Selection
C001 Operating mode -0- -3- Setpoint selection (control, parameter setting)
C005 Configuration -0- -7- Operation with closed-loop control, with
C007 Terminal configuration -0- -26- Motor potentiometer (UP/DOWN), JOG1, M/R C037 JOG value 1 20.00 16.67Hz Fixed reduction to 1/3 of the rated pressure. C051 Actual PID controller value Only display of act.
C070 Gain
PID controller
C071 Integral action time PID controller 100 100 ms Adapt to process
C072 Differential component PID
controller C074 Influence PID controller 0.0 100% C238 Frequency precontrol -1- -0- No precontrol
1.00 1.00 Adapt to process
0.0 0.0 Adapt to process
via LECOM
analog feedback via terminal 8
pressure
All other parameters are based on the factory setting.
Set the rated motor data (depends on the motor used) under C088 (rated motor current) and C091 (motor cos φ).
The pressure setpoint cannot only be selected via a fieldbus but also via the operating unit 8201BB (installation up to 10m
distance possible) or an alalog input signal (with module 8279).
For standardisation of the process value see chapter 5.5.1.
UOOuhäáã~_^NMMO
5-17
Page 58
Commissioning
g
Show/Hide Bookmarks
5.6.3 Pump application with level control
water
Outgoin
Water tank
+
-
Level sensor
0-10 V, 0/4-20 mA
Delivery pump
Incoming
water
M
3
v
u
w
X1
Water level set-value
0 -10V, 0/4 - 20mA
*
2
Z
1
39
L
STP
PRG
SH
RUN
E
8279
G
3
G
V
U
W
7
8
-U
+U
L
L
*
1
Z
1
2
L
1
K
1
F
cfd RJP ^ййдбЕ~нбзе зС ~ ймгй пбнЬ дЙоЙд Езенкзд
* Z1 Mains filter required for radio interference level A or B. * Z2 Motor filter required for motor cables: screened as from 50 m, unscreened as from 100 m.
Sine filter required for motor cables: screend as from 100 m, unscreened as from 200 m.
Screen all signal and motor cables. Please observe the corresponding installation instructions in c hapter 4.2 und 4.3.
3
L
2
L
1
L
hPRKUOhMMP
5-18
UOOuhäáã~_^NMMO
Page 59
Commissioning
Show/Hide Bookmarks
Ta sk ( FI G 5 - 3):
fе ~ н~ев нЬЙ п~нЙк бл нз ДЙ ЬЙдЗ ~н ~ Езелн~ен дЙоЙдK qЬЙ лйЙЙЗ зС нЬЙ ймгй гмлн ДЙ ЕзенкзддЙЗ ЗЙйЙеЗбеЦ зе нЬЙ ~гзмен зС п~нЙк ЗЙдбоЙкЙЗK
cмеЕнбзел млЙЗ
D fенЙке~д mfa ЕзенкзддЙк Сзк дЙоЙд ЕзенкздK
J kзкг~д ЕзенкздI ~е~дзЦ лЙнйзбен лЙдЙЕнбзе об~ нЙкгбе~д U пбнЬ СЙЙЗД~Ев об~
~е~дзЦ беймн bN пбнЬ йдмЦJбе гзЗмдЙ UOTVK
`зЗЙ лЙннбеЦлW
Code Name Possible settings IMPORTANT
Lenze Selection
C005 Configuration -0- -6- Operation with closed-loop control; setpoint
C070 Gain
PID controller
C071 Integral action time PID
controller
C072 Differential component
PID controller C074 Influence PID controller 0.0 100% C238 Frequency precontrol -1- -0- No precontrol C239 Frequency setting range -0- -1- Unipolar Direction of rotation
1.00 1.00 Adapt to process
100 100 ms Adapt to process
0.0 0.0 Adapt to process
via terminal 8 with digital frequency feedback via terminal E1
cannot be changed via process controller
All other parameters are based on the factory setting. Set the rated motor data (depends on the motor used) under C088 (rated motor current) and C091 (motor cos φ).
UOOuhäáã~_^NMMO
5-19
Page 60
Commissioning
y
Show/Hide Bookmarks

5.7 Signal-flow charts

O u t p u t
f r e q u e n c
L U , O U
¬
S t o p
t
R a m p f u n c t i o n g e n e r a t o r
C 0 1 3
C 1 0 5
C 0 1 2
R e s e t
®
D C b r a k e
C t r l . e n a b l e ,
f d m a x
- f d m a x A u t o D C b r a k e t h r e s h d d
C 1 8 2
R F G S s h a p e
T i S s h a p e
. . .
A n a l o g s e t p o i n t
u n i p o l a r ( f d m i n . . f d m a x )
f d m a x
C 0 1 0
1
1
C 0 3 4
C 0 4 6
K e y p a d , L E C O M , m o t o r p o t e n t i o m e t e r f u n c t i o n
- 1 - , - 3 - . - 1 2 -
d m i n
f
M a s t e r c u r r e n t
0 . . . 2 0 m A /
4 . . . 2 0 m A
S k i p f r e q u e n c i e s
0
K e y p a d ,
L E C O M
- 0 -
- 1 - . . . - 3 -
J O G - s e t p o i n t
f d m a x
C 0 3 7
C 0 3 8
C 6 2 5 t o C 6 2 8
D i r e c t i o n o f r o t a t i o n
E 3 E 4
L E C O M
- 0 ­1
E n a b l e
J O G -
s e t p o i n t
E 3 E 4
E 1 E 2
C 0 3 9
3 J O G -
s e t p o i n t
E 1 E 2
- 1 -
- 1
f r e e
d i g i t a l i m p u l s
D i g i t a l i m p u l s
1 , 0 * f d m a x
5-20
UOOuhäáã~_^NMMO
D
S 1 / 4
A
8
7
X 1
2 5 0 R
cfd RJQ mкзЕЙлл ~еЗ лйЙЙЗ ЕзенкзддЙк Сзк `MMR Z M
hPRKMNQTd_
Page 61
Commissioning
Show/Hide Bookmarks
E 1 E 2 E 3 E 4
F r e e d i g i t a l
i n p u t s
Q m i n - t h r e s h d d
Q m i n
C 0 5 0
d m a x
d m a x
f r e q u e n c y
O u t p u t -
f
- f
Q m i n
C o n f i g u r a t i o n
- 6 - , - 7 -
- 1 - . . . . - 5 -
A u t o D C b r a k e
R a m p f u n c t i o n g e n e r a t o r
R e s e t
D C b r a k e
C t r l . e n a b l e
K e y p a d , L E C O M
F r e q u e n c e
p r e c o n t r o l
S t o p , a u t o D C b r a k e ,
I m a x
P I D - c o n t r o l l e r
I n f l u e n c e
P I D - c o n t r o l l e r
1
- 1
P I D - c o n t r o l l e r
o u t p u t
R e s e t I c o m p o n e n t
C 0 1 7
0
. - 7 -
1
0
C 0 0 8
E 1 E 2 E 3 E 4
i n p u t s
F r e e d i g i t a l
R e s e t
S k i p f r e q u e n c i e s
R F G S s h a p e
T i S s h a p e
D i r e c t i o n o f r o t a t i o n
D i s p l a y a d d . s e t - v a l u e
E 1 E 2 E 3 E 4
I n f l u e n c e 0
C t r l . e n a b l e
D C b r a k e
L U , O U
D i s p l a y a c t u a l v a l u e
D i g i t a l i n p u t s
S p e e d l i m i t a t i o n w i t h
t o r q u e c o n t r o l
C 0 0 5 = 5
K e y p a d ,
L E C O M
E n a b l e
J O G v a l u e
E 1 E 2 E 3 E 4
F r e e d i g i t a l
i n p u t s
M o t o r p o t e n t i o m e t e r f u n c t i o n
K e y p a d , L E C O M ,
C 0 0 5 = - 5 - M o t o r c u r r e n t c o n t r o l ( C 0 1 4 = - 4 - )
C 0 0 5 = - 4 - T o r q u e s e t - v a l u e ,
C 0 0 5 = - 3 - T o r q u e l i m i t a t i o n ,
0
1 , 5 * I N u n i t
M o t o r p o t e n t i o m e t e r f u n c t i o n
K e y p a d , L E C O M ,
A n a l o g s e t - v a l u e
u n i p o l a r ( f d m i n . . f d m a x )
C o n f i g u r a t i o n
J O G - s e t - v a l u e - 1 - . . . - 3 -
C o n f i g u r a t i o n
C o n f i g u r a t i o n
C o n f i g u r a t i o n
8
7
X 1
s e t - v a l u e
3 J O G -
G a i n
0 . . . 2 0 m A
4 . . . 2 0 m A
M a s t e r c u r r e n t
i n v e r s e s e t v a l u e
G a i n
O f f s e t
O f f s e t
S t a n d a r d i s a t i o n
S 1 / 4
f r e q u e n c y i n p u t
2 5 0 R
u d u l e
e r m i n a l
p l u g o n
cfd RJR mкзЕЙлл ~еЗ лйЙЙЗ ЕзенкзддЙк Сзк `MMR Z N KKK T
hPRKMNPQ~d_
UOOuhäáã~_^NMMO
5-21
Page 62
Commissioning
Show/Hide Bookmarks
5-22
UOOuhäáã~_^NMMO
Page 63

6 During operation

Show/Hide Bookmarks
D oЙйд~ЕЙ ЗЙСЙЕнбоЙ СмлЙл пбнЬ нЬЙ йкЙлЕкбДЙЗ нуйЙ зеду пЬЙе ез оздн~ЦЙ бл
~ййдбЙЗK qЬЙкЙ ~кЙ ез СмлЙл бе нЬЙ ЕзенкзддЙкK
D `уЕдбЕ г~бел лпбнЕЬбеЦW
J aз езн лпбнЕЬ зе нЬЙ ЕзенкзддЙк гзкЙ нЬ~е ЙоЙку P гбемнЙлI знЬЙкпблЙ нЬЙ
бенЙке~д бебнб~дJЕмккЙен дбгбн~нбзе Е~е ДЙ зоЙкдз~ЗЙЗK
D pпбнЕЬбеЦ зе нЬЙ гзнзк лбЗЙW
J mЙкгбллбДдЙ Сзк ЙгЙкЦЙеЕу лпбнЕЬJзССK J jзебнзкбеЦ гЙлл~ЦЙл Е~е ДЙ ~Енбо~нЙЗ пЬЙе лпбнЕЬбеЦ нЬЙ гзнзк пЬЙе нЬЙ
ЕзенкзддЙк бл Йе~ДдЙЗK
D aЙйЙеЗбеЦ зе нЬЙ ЕзенкзддЙк лЙннбеЦлI нЬЙ ЕзееЙЕнЙЗ гзнзк Е~е ДЙ
зоЙкЬЙ~нЙЗW J cзк белн~еЕЙI дзеЦЙк a`JДк~вбеЦ зйЙк~нбзелK J iзеЦЙк зйЙк~нбзе зС лЙдСJоЙенбд~нЙЗ гзнзкл ~н дзп лйЙЙЗK
During operation
D qЬЙ ЕзенкзддЙкл ЦЙеЙк~нЙ ~е змнймн СкЙимЙеЕу зС мй нз QUM eт пЬЙе лЙннбеЦ бн
ЕзккЙлйзеЗбеЦдуW J fС ~е бе~ййкзйкб~нЙ гзнзк бл ЕзееЙЕнЙЗI ~ Ь~т~кЗзмл зоЙклйЙЙЗ г~у зЕЕмкK
D fС узм млЙ нЬЙ СмеЕнбзе `tL``t EлЙдЙЕнбзе зС нЬЙ ЗбкЙЕнбзе зС кзн~нбзеF пбнЬ
нЬЙ ЕзеСбЦмк~нбзе `MMT Z JMJ нз JNPJW J qЬЙ ЗкбоЙ Е~е кЙоЙклЙ нЬЙ ЗбкЙЕнбзе зС кзн~нбзе бе нЬЙ ЙоЙен зС ~
ЕзенкздJоздн~ЦЙ С~бдмкЙ зк ~ Е~ДдЙ ДкЙ~вK
D fС узм млЙ нЬЙ СмеЕнбзе ТcдубеЦJкЙлн~кн ЕбкЕмбнТ E`NQO Z JOJI JPJF пбнЬ г~ЕЬбеЙл
пбнЬ дзп беЙкнб~ нзкимЙ ~еЗ СкбЕнбзеW J qЬЙ гзнзк Е~е лн~кн Сзк ~ лЬзкн нбгЙ зк кЙоЙклЙ нЬЙ ЗбкЙЕнбзе зС кзн~нбзе Сзк ~
лЬзкн нбгЙ ~СнЙк Йе~ДдбеЦ нЬЙ ЕзенкзддЙк пЬЙе нЬЙ гзнзк бл бе лн~еЗлнбддK
D qЬЙ ЕзенкзддЙкл UOOuLUOQu Ь~оЙ ~ нЙгйЙк~нмкЙJЗЙйЙеЗЙен С~е ЕбкЕмбнW
J qЬЙ С~ел ~кЙ зеду ~Енбо~нЙЗ пЬЙе нЬЙ ЬЙ~н лбев нЙгйЙк~нмкЙI пЬбЕЬ бл ~
СбсЙЗ С~Ензку лЙннбеЦI бл ЙсЕЙЙЗЙЗK
UOOuhäáã~_^NMMO
6-1
Page 64
During operation
Show/Hide Bookmarks
6-2
UOOuhäáã~_^NMMO
Page 65

7 Configuration

Show/Hide Bookmarks

7.1 Basics

D qЬЙ ЕзеСбЦмк~нбзе зС нЬЙ ЕзенкзддЙк бл млЙЗ нз ~З~йн нЬЙ ЗкбоЙ нз узмк
~ййдбЕ~нбзелK
D cзк нЬблI узм Ь~оЙ нЬЙ СзддзпбеЦ СмеЕнбзел ~о~бд~ДдЙW
J lйЙк~нбеЦ СмеЕнбзел J `зенкзд СмеЕнбзе J aблйд~у СмеЕнбзел J jзебнзкбеЦ СмеЕнбзел
D qЬЙ йзллбДдЙ СмеЕнбзе лЙннбеЦл ~кЙ зкЦ~ебтЙЗ бе ЕзЗЙлW
J `зЗЙл ~кЙ емгЙкбЕ~дду лзкнЙЗI лн~кнбеЦ Скзг нЬЙ ЕзЗЙ пбнЬ нЬЙ лг~ддЙлн
емгДЙк нз нЬЙ зеЙ пбнЬ нЬЙ ЬбЦЬЙлн емгДЙкK ^дд ЕзЗЙл лн~кн пбнЬ ~ Т`ТK J qЬЙу ~кЙ дблнЙЗ бе нЬЙ ЕзЗЙ н~ДдЙK J b~ЕЬ ЕзЗЙ йкзобЗЙл й~к~гЙнЙкл пЬбЕЬ Е~е ДЙ млЙЗ нз ~Замлн ~еЗ зйнбгбтЙ
узмк ЗкбоЙK
Configuration
D qЬЙ ЕзеСбЦмк~нбзе зС нЬЙ ЕзенкзддЙк Е~е ДЙ ЙенЙкЙЗ Ду гЙ~ел зС нЬЙ вЙуй~З зС
нЬЙ UOMN__ зйЙк~нбеЦ гзЗмдЙ зк Ду гЙ~ел зС ~ СбЙдЗДмл об~ нЬЙ лЙкб~д бенЙкС~ЕЙK
J qЬЙ зйЙк~нбеЦ гзЗмдЙ ~еЗ СбЙдЗДмл гзЗмдЙл ~кЙ ~о~бд~ДдЙ ~л ~ЕЕЙллзкбЙлK
D qЬЙ ЕЬ~еЦбеЦ зС й~к~гЙнЙкл Ду гЙ~ел зС нЬЙ зйЙк~нбеЦ гзЗмдЙ зк СбЙдЗДмл
гзЗмдЙл бл ЗЙлЕкбДЙЗ J бе нЬЙ lйЙк~нбеЦ fелнкмЕнбзел зС нЬЙ гзЗмдЙлK J бе нЬЙ j~ем~дK
D ^дд СмеЕнбзел зС нЬЙ ЕзенкзддЙк ~кЙ ЗЙлЕкбДЙЗ лЬзкнду бе нЬЙ ЕзЗЙ н~ДдЙK
Note!
qЬЙ СмеЕнбзел ~кЙ ЗЙлЕкбДЙЗ бе ЗЙн~бд бе нЬЙ j~ем~дK
UOOuhäáã~_^NMMO
7-1
Page 66
Configuration
Show/Hide Bookmarks

7.2 Code table

How to read the code table:
Column Abbreviation Meaning
Code C013 Code C013
D The parameter of the code can be different in PAR1 and PAR2. D The parameter value is accepted immediately (ONLINE).
C009* D The parameter value of the code is always the same in PAR1 and PAR2, but is
C001¿ D The parameter value of the code will be accepted after pressing SH+PRG. [C002] D The parameter value of the code will be accepted after pressing SH+PRG but
Name
Lenze Factory setting of the code
* The column ”Important” contains further information
Selection 1{1%}99Min. value {Steps/Unit} Max. Value Info - Meaning of the code IMPORTANT - Additional, important explanation of the code
always displayed in PAR1.
only if the c ontroller is inhibited.
Name of the code.
820X
Unit-specific setting possibilites (here for 820X). Without unit designation the code is valid for all unit types.
Code Name Possible settings IMPORTANT
Lenze Selection Info
C001¿ Operating mode -0- -0- Setpoint selection via term. 8
[C002]* Parameter set -0- -0- Function executed
Control v ia terminals Parameter setting via 8201BB
-1- Setpoint selection via 8201BB or via LECOM Control v ia terminals Parameter setting via 8201BB
-2- Setpoint selection via term. 8 Control v ia terminals Parameter setting via LECOM
-3- Setpoint selection via LECOM Control via LECOM Parameter setting via LECOM
-1- Overwrite PAR1 with factory setting
-2- Overwrite PAR2 with factory setting
-3- Overwrite PAR1 and PAR2 with the data of the operating module
-4- Overwrite PAR1 with the data of the operating module
-5- Overwrite PAR2 with the data of the operating module
-6- Transmit PAR1 and PAR2 to the operating module
-7- Overwrite PAR1, PAR2 and the unit-dependent data (C016, C036, C088, C091) with the data of the operating module.
7-2
UOOuhäáã~_^NMMO
Page 67
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
Name
C003¿ Save parameter
set
-1- -0- Data will not be saved on EEPROM; all data will be lost when switching off the mains
-1- Data will be saved on EEPROM; setting when switching on the mains
C004¿ Switch-on display -0- -0- Field frequency f
d
-1- Unit load
-2- Motor current
C005¿ Configuration -0- -0- Operation with open-loop control via
terminal 8
-1- Operation with open-loop control via terminal 8 with setpoint summation via frequency input E1
-2- Operation with open-loop control via frequency input E1 with setpoint summation via terminal 8
-3- Operation with open-loop control via frequency input E1 with torque limitation via terminal 8
-4- Torque selection via terminal 8 with speed limitation via f
dmax
(C011)
-5- Torque selection via terminal 8 with speed limitation via frequency input E1
-6- Operation with closed-loop control; setpoint via terminal 8 with digital frequency feedback via terminal E1
-7- Operation with closed-loop control, setpoint via frequency input E1 with analog feedback via terminal 8
C007¿ Te r m i n a l
configuration
-0- E4 E3 E2 E1
-0- CW/CCW DC brake JOG1/2/3
-1- CW/CCW PAR JOG1/2/3
-2- CW/CCW QSP JOG1/2/3
-3- CW/CCW PAR DC brake JOG1
-4- CW/CCW QSP PAR JOG1
-5- CW/CCW DC brake Trip set JOG1
-6- CW/CCW PAR Trip set JOG1
-7- CW/CCW PAR DC brake Trip set
-8- CW/CCW QSP PAR Trip set
-9- CW/CCW QSP Trip set JOG1
-10- CW/CCW Trip set UP DOWN
InfoSelectionLenze
-0- only valid for C010, C011, C012, C013, C037, C038, C105, C181 and C182
Selections -4- and
-5- are only permitted for motor-current control
(C014=4)andwith activated flying
restart circuit (C142 = 2, 3).
D CW =
CW rotation
D CCW =
CCW rotation
D DC brake =
DC injection brake
D PAR =
Change of
parameter sets
D JOG =
JOG frequency
D QSP =
Quick stop
UOOuhäáã~_^NMMO
7-3
Page 68
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
(continued)
C007¿
Name
Termina l configuration
-0- E4 E3 E2 E1
-11- CW/CCW DC brake UP DOWN
-12- CW/CCW PAR UP DOWN
-13- CW/CCW QSP UP DOWN
-14- CCW/QSP CW/QSP DC brake JOG1
-15- CCW/QSP CW/QSP PAR JOG1
-16- CCW/QSP CW/QSP JOG1/2/3
-17- CCW/QSP CW/QSP PAR DC brake
-18- CCW/QSP CW/QSP PAR Trip set
-19- CCW/QSP CW/QSP DC brake Trip set
-20- CCW/QSP CW/QSP Trip set JOG1
-21- CCW/QSP CW/QSP UP DOWN
-22- CCW/QSP CW/QSP UP JOG1
-23- M/R CW/CCW UP DOWN
-24- M/R PAR UP DOWN
-25- M/R DC brake UP DOWN
-26- M/R JOG1 UP DOWN
-27- M/RTrip set UP DOWN
-28- JOG1/2/3 I-OFF D/F
-29- JOG1 DC brake I-OFF D/F
-30- JOG1 QSP I-OFF D/F
-31- DC brake QSP I-OFF D/F
-32- Trip set QSP I-OFF D/F
-33- QSPPAR I-OFF D/F
-34- CW/QSPCCW/QSP I-OFF D/F
-35- JOG1/2/3 PAR D/F
-36- DC brake QSP PAR D/F
-37- JOG1 QSP PAR D/F
-38- JOG1 PAR Trip set D/F
-39- JOG1/2/3 Trip set D/F
-40- JOG1 QSP Trip set D/F
-41- JOG1 DC brake Trip set D/F
-42- QSP DC brake Trip set D/F
-43- CW/CCW QSP Trip set D/F
-44- UP DOWN PAR D/F
-45- CW/CCW QSP PAR D/F
-46- M/R PAR QSP JOG1
-47- CW/QSP CCW/QSP M/R JOG1
-48- INFL_0 DC brake I-OFF D/F
-49- INFL_0 JOG1 QSP D/F
-50- INFL_0 JOG1 I-OFF D/F
-51- DC brake PAR I-OFF D/F
InfoSelectionLenze
D Tri p - S e t =
External fault
D UP/DOWN =
Motor potentiometer functions
D M/R =
Manual/Remote changeover
D I-OFF =
Reset I-component of the PID controller
D D/F =
Digital frequency input 0 - 10 kHz
D INFL_0 =
Set influence of the PID controller to 0
When changing between the parameter sets via terminal, the corresponding terminal must be assignedwithPARin both parameter sets.
7-4
UOOuhäáã~_^NMMO
Page 69
Configuration
V
min
boost
316kHzreducedpowerlos
s
C021Slip0,0-5
0.0{0.1%}50.0
*whenC01
4=2,3
p
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
Name
InfoSelectionLenze
C008¿ Function relay K1 -1- -0- Ready for operation
-1- TRIP fault message
-2- Motor is running
-3- Motor is running / CW rotation
-4- Motor is running / CCW rotation
min
d
or IMP
=0
max
-10 °C)
-5- Field frequency f
-6- f
-7- Q
-8- I
dset
min
max
reached
reached
reached
-9- Overtemperature (J
-10- TRIP or Q
822X/824X -11- PTC warning
-12- Apparent motor current (C054) < threshold C156
-13- Apparent motor current (C054) < threshold C156 and f
d>Qmin
threshold (C017)
-14- Apparent motor current (C054) < threshold C156 and input of ramp function generator = output of ramp function generator
822X/824X -15- Warning motor phase failure
-16- fd(C050) < f
dmin
(C010)
C009* Device address 1 1 {1} 99 Only for LECOM
applications
C010 Minimum field
0.00 0.00 {0.02Hz} 480.00
frequency
C011 Maximum field
50.00 7.50 {0.02Hz} 480.00
frequency C012 Acceleration time 5.00 0.00 {0.02s} 1300.00 C013 Deceleration time 5.00 0.00 {0.02s} 1300.00
C014¿ Operating mode
-2- Linear characteristic V~fdwith constant boost
V
-3- Square characteristic V~f
min
boost
V
min
2
with constant
d
-4- -4- Motor-current control C015 V/f rated frequency 50.00 7.50 {0.02Hz} 960.00 C016 V C017 Threshold Q
setting 0.00 0.00 {0.2 %} 40.0 depends on the unit
min
min
0.00 0.00 {0.02Hz} 480.00
C018¿ Chopper frequency -1- -0- 4kHz reduced power loss
-1- 8kHz,reduced power loss
-2- 12kHz reduced power loss
-3- 16kHz reduced power loss
-4- 4kHz reduced noise emission
-5- 8kHz reduced noise emission
-6- 12 kHz reduced noise emission
-7- 16 kHz reduced noise emission
C019 Threshold auto DC
0.10 0.00 {0.02Hz} 5.00
brake
compensation
-
0.0 0.0 {0.1 %} 20.0 *whenC014=4
*
* depends on the unit
C022 I
max
limit
150 30 {1 %} 150
motor mode
UOOuhäáã~_^NMMO
7-5
Page 70
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
C035*¿ Selection DC brake -0- -0- Selection of brake voltage under C036
Name
InfoSelectionLenze
C023 I
C026* Offset adjustment
C027* Scaling factor of
C034¿ Master current -0- -0- 0 to 20mA /
C036 Voltage for DC
C037 JOG value 1 20.00 -480.00 {0.02Hz} 480.00 C038 JOG value 2 30.00 -480.00 {0.02Hz} 480.00 C039 JOG value 3 40.00 -480.00 {0.02Hz} 480.00 C040 Controller enable * -0- Controller inhibited
C043 TRIP reset * -0- No current fault
C046 Frequency setpoint * -480.00 {0.02 %} 480.00 * see Operating
C047* Torque setpoint
C049* Additional setpoint Only display
C050* Output frequency Only display C051* Actual PID
C052* Motor voltage Only display C053* DC-bus voltage Only display C054* Motor current Only display C056* Unit load Only display C061* Heat sink
C070 Gain
C071 Integral action time
C072 Differential
C074 Influence PID
limit
max
generator mode
analog input
analog input
brake
limit value
I
max
controller value
temperature
PID controller
PID controller
component PID controller
controller
80 30 {1 %} 150 The current-limit
0.00 -10.00 {0.01 V} 10.00
100.0 -200.0 {0.1 %} 200.0
0to5V/0to10V
-1- 4 to 20mA
-1- Selection of brake current under C036
* 0 {0.02 %} 150 * depends on the unit
-1- Controller enabled
-1- Current fault
1.00 0.00 {0.01} 300.00 0.0 = P-component
100 10ms 9999s 9999s = I-componen
0.0 0.0 {0.1} 5.0 0.0 = D-component
0.0 0.0 {0.1 %} 100.0
controller for operation in generator mode is notactiveat30%.
* see Operating Instructions 2102
* see Operating Instructions 2102
Instructions 2102 Only display
D C005=4,5
- Torque setpoint
D C005 =
1, 2, 3, 6, 7
limit
-I
max
value (C022)
D Only when
C005=1,2
Only display
Only display
inactive
tinactive
inactive
7-6
UOOuhäáã~_^NMMO
Page 71
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
Name
InfoSelectionLenze
C077* Gain
C078* Integral action time
C079
C088 Rated motor
C091 Motor cos j *
C093*
C099* Software version 82 3x (Software 3x) Only display
C105 Deceleration time
C106 Holding time for
C108* Gain (C111) 128 0 {1} 255
controller
I
max
I
controller
max
Oscillation damping
822X/824X 5 0 {1} 80
current
Type Only display
QSP
autom. DC injection brake
0.25 0.00 {0.01} 1.00
65 12 {1 ms} 9990
* 0 {1 A} 480
0.0 ... 2.0
0.4 {0.1} 1.0
821X 821X 822X 822X 824X 824X
5.00 0.00 {0.02s} 1300.00
0.02 0.00 {0.01s} 999.00
¡ rated output current
* depends on the unit
* depends on the unit
* depends on the unit
UOOuhäáã~_^NMMO
7-7
Page 72
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
Name
C111¿ Monitor signal -0-
822X/824X -20- PTC warning
822X/824X -24- Warning motor phase failure
C114¿ Signal level
-0- E4 E3 E2 E1
digital inputs
InfoSelectionLenze
-0- Field frequency
-1- Unit load
-2- Motor current
-3- DC-bus voltage
-4- Motor power
-5- Motor voltage
-6- Analog output 1/f
(1/C050)
d
-7- Field frequency of f
dmin
(C010) ... f
dmax
(C011)
-8- Actual PID controller value
-9- Ready for operation
-10- TRIP fault message
-11- Motor is running
-12- Motor is running / CW rotation
-13- Motor is running / CCW rotation
-14- Field frequency f
-15- f
-16- Q
-17- I
dsoll
min
max
reached reached
reached
-18- Overtemperature (Â
-19- Setting of TRIP, Q
d
=0
min
max
or Imp
-10°)
-21- Apparent motor current (C054) < current threshold (C156)
-22- Apparent motor current (C054) < current threshold (C156) and
threshold
f
d>Qmin
-23- Apparent motor current (C054) < threshold (C156) and input of ramp function generator = output of ramp function generator
-25- fd(C050) < f
dmin
(C010)
-0-0000
-1-0001
-2-0010
-3-0011
-4-0100
-5-0101
-6-0110
-7-0111
-8-1000
-9-1001
-10- 1 0 1 0
-11- 1 0 1 1
-12- 1 1 0 0
-13- 1 1 0 1
-14- 1 1 1 0
-15- 1 1 1 1
Selection -9- ... -25­corresponds to the relay output functions C008 and C117:
D LOW=0V D HIGH=10V
0: Ex is not inverted 1: Ex is inverted
7-8
UOOuhäáã~_^NMMO
Page 73
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
C125¿* LECOM baud rate -0- -0- 9600 baud
Name
C115¿ Priority mask
digital inputs
C117¿
Function relay K2
822X/824X -11- PTC warning
822X/824X -15- Warning motor phase failure
C119¿ Function PTC
822X/824X
2
C120
I
¡t switch off
822X/824X 0 0 {1 %} 100
-0- E4 E3 E2 E1
-0-0000
-1-0001
-2-0010
-3-0011
-4-0100
-5-0101
-6-0110
-7-0111
-8-1000
-9-1001
-10- 1 0 1 0
-11- 1 0 1 1
-12- 1 1 0 0
-13- 1 1 0 1
-14- 1 1 1 0
-15- 1 1 1 1
-0- -0- Ready for operation
-1- TRIP fault message
-2- Motor is running
-3- Motor is running / CW rotation
-4- Motor is running / CCW rotation
min
d
or IMP
=0
max
-10 °C)
-5- Field frequency f
-6- f
-7- Q
-8- I
dset
min
max
reached
reached
reached
-9- Overtemperature (J
-10- TRIP or Q
-12- Apparent motor current (C054) < threshold C156
-13- Apparent motor current (C054) < threshold C156 and f
d>Qmin
threshold (C017)
-14- Apparent motor current (C054) < threshold C156 and input of ramp function generator = output of ramp function generator
-16- fd(C050) < f
dmin
(C010)
-0- -0- PTC input not active
-1- PTC input active, TRIP and pulse inhibit will be set
-2- PTC input active, warning
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
-4- 19200 baud
InfoSelectionLenze
0: Function Ex depends on C001
1: Function Ex is independent of C001
D Ctrl. inhibit and
TRIP reset always have first priority.
D With -0- also TRIP
set and QSP have priority.
Only for LECOM applications
UOOuhäáã~_^NMMO
7-9
Page 74
Configuration
reduction-1-A
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
C196*¿ Input condition
Name
InfoSelectionLenze
C126* Selection of
communication errors
C127 Selection
Setpoint selection
C135* Control word see Operating
C141* Standardized
setpoint
C142¿ Start condition -1- -0- Automatic start inhibited, flying-restart
C144¿ Chopper-frequenc
y
C150* Status word see Operating
C156* Current threshold 0 0 {1 %} 150 C161* Current fault Only display C162* Last fault Only display C163* Last but one fault Only display C164* Last but two fault Only display
C170¿ TRIP-reset
selection
C171 Delay for
Auto-TRIP-Reset
C178* Operating time Only display C179* Mains switch-on
time
C181* Setpoint PID
controller
C182* Integration time
ramp function generator S-shape
autom. DC injection brake
-0- -0- No TRIP when stopping the communication
-0- -0- Absolute setpoint selection in Hz via C046
-1- -0- No chopper-frequency lowering
0.00 0.00 {0.01s} 60.00
0.00 -480.00 {0.02 Hz} 480.00 Only when C181
0.00 0.00 {0.01 s} 50.00 D C182 = 0.00
-0- -0- DC brake active at C050 < C019
in the process channel
-1- TRIP (-CEO-) when stopping the communication in the process channel
or process channel
-1- Standardized setpoint selection via C141 (0 ... 100 %) or process channel (± 16384 = f
-100.00 {0.01 %} 100.00 Only for bus
circuit not active
-1- Automatic start, if term. 28 HIGH, flying-restart circuit not active
-2- Automatic start inhibited, flying-restart circuit active
-3- Automatic start, if term. 28 HIGH, flying-restart circuit active
utomaticchopper-frequencylowering
when J
max
-0- TRIP-reset by pressing the STP key or LOW signal at ctrl. enable
-1- Auto-TRIP reset
-1- DC brake active at C050 < C019 and setpoint < C019
dmax
-10°C
(C011))
Only for bus operation
Only for bus operation
Instructions 2102
operation OnlywhenC127=1
active
Instructions 2102
Only display
0active
- Linear ramp function generator
D C182 > 0.00
- Ramp function generator S shape with
time = C182
T
i
7-10
UOOuhäáã~_^NMMO
Page 75
Configuration
d
byt
h
LenzeService!
l
icat
iondat
b
l
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
C377*¿ Gain Zk-voltage
C425¿* Adjustment of
C597*¿
Name
C200 Software EKZ
C238¿ Frequency
precontrol
C239¿ Frequency setting
range C304 Password1 C305 Password2 C306 Contents of the
address C307 Address
detection
822X/824X
C395 LW O R D process
input data C396 LW O R D process
output data
digital frequency
C426* Gain adjustment
frequency input E1
C427* Offset adjustment
frequency input E1
C500* Display factor
app
numerator
C501* Display factor for
process varia
denominator
Activation of
motor-phase
failure detection
822X/824X -0- -0- Inactive
C599*
Current limit value
motor-phase
failure detection
822X/824X 5 1{1%}50 C625* Frequency 1 480.00 0.00 {0.02 Hz} 480.00 C626* Frequency 2 480.00 0.00 {0.02 Hz} 480.00 C627* Frequency 3 480.00 0.00 {0.02 Hz} 480.00
-1- -0- No precontrol
-1- With setpoint precontrol
-0- -0- Bipolar
-1- Unipolar
-2- Dig.- Reso- Scann- Max.­freq. lution ing freq.
-0- 100 Hz 1/200 1 s 300 Hz
-1- 1 kHz 1/200 100 ms 3 kHz
-2- 10 kHz 1/200 10 ms 10 kHz
-3- 10 kHz 1/1000 50 ms 10 kHz
-4- 10 kHz 1/10000 500 ms 10 kH z
100 -200.0 {0.1 %} 200.0
0.0 -12.5 {0.1 %} 12.5
2000 1 {1} 25000
um
10 1 {1} 25000
e
-1- TRIP
-2- Warning
InfoSelectionLenze
Should only be change Lenze Service!
Only for bus operation
Only for bus operation
When using the analog input module 8279 for the frequency input E1:
D Set C425 to 2, 3
or 4
e
UOOuhäáã~_^NMMO
7-11
Page 76
Configuration
Show/Hide Bookmarks
Code IMPORTANTPossible settingsName
Code IMPORTANT
Name
C628* Bandwidth of
frequencies
C988* DC-bus voltage
threshold for DC-bus voltage control
InfoSelectionLenze
0.00 0.00 {0.01 %} 100.00
0 0 {1 %} 200 D C988=0%
- No parameter set changeover via DC-bus voltage
D C988 = 1 ... 200%
- Parameter set changeover via DC-bus voltage active
PPPPaaaarrrraaaammmmeeeetttteeeerrrrsssseeeetttt cccchhhhaaaannnnggggeeeeoooovvvveeeerrrrvvvviiiiaaaa tttteeeerrrrmmmmiiiinnnnaaaalllloooorrrrLLLLEEEECCCCOOOOMMMMiiiissss nnnnoooottttppppoooossssssssiiiibbbblllleeeewwwwhhhheeeennnn CCCC999988888888>>>>0000!!!!
7-12
UOOuhäáã~_^NMMO
Page 77
Troubleshooting and fault elimination
p
g
Show/Hide Bookmarks

8 Troubleshooting and fault elimination

vзм Е~е кЙЕзЦебтЙ бггЙЗб~нЙду пЬЙнЬЙк ~ С~мдн Ь~л зЕЕмкЙЗ Ду Зблйд~у ЙдЙгЙенл зк лн~нмл беСзкг~нбзе EЕЬ~йнЙк UKNFK
qЬЙ С~мднл Е~е ДЙ ~е~дулЙЗ Ду млбеЦ нЬЙ Ьблнзку ДмССЙк EЕЬ~йнЙк UKOF ~еЗ нЬЙ дблн бе ЕЬ~йнЙк UKPK qЬбл дблн ЬЙдйл узм нз Йдбгбе~нЙ нЬЙ С~мднлK

8.1 Troubleshooting

8.1.1 Display at the controller
aмкбеЦ зйЙк~нбзе пбнЬзмн зйЙк~нбеЦ гзЗмдЙ нпз iba ~н нЬЙ мебн Скзен беЗбЕ~нЙ нЬЙ зйЙк~нбеЦ лн~нмлK
LED Operating status green red
on off Controller enabled on on Mains switched on, automatic start inhibited (AS_LC) blinking off Controller inhibited off blinki ng every second Fault message, check under C161 off blinking every 0.4 seconds Undervoltage switch-off off off Programming mode
8.1.2 Display at the operating module
pн~нмл беЗбЕ~нбзел бе нЬЙ Зблйд~у беЗбЕ~нЙ нЬЙ ЕзенкзддЙк лн~нмлK
Display Meaning
OV Overvoltage UV Undervoltage IMAX Set current limit exceeded TEMP Heat sink temperature near switch-off
UOOuhäáã~_^NMMO
8-1
Page 78
Troubleshooting and fault elimination
f
higherlocation.
t
heh
ist
f
f
t
b
Show/Hide Bookmarks
8.1.3 Maloperation of the drive
Maloperation Possible causes Motor does not rotate D DC-bus voltage too low
Motor does not rotate smoothly
Current consumption of motor too high
(Red LED is blinking every 0.4 seconds; message LU is displayed)
D Controller inhibited
(green LED is blinking, display of the operating module: OFF, STOP or AS_LC)
D Setpoint = 0 D DC braking active D Quick-stop function active D JOG setpoint activated and JOG frequency = 0 D Fault message is displayed (see chapter 8.3 ) D Mechanical motor brake is not released
D Defective motor cable D Maximum current C022 and C023 too low D Motor underexcited or overexcited (check parameter setting)
D Setting of C016 too high D Setting of C015 too low D C088 and C091 are not adapted to the motor data.

8.2 Fault analysis using the history buffer

qЬЙ Ьблнзку ДмССЙк бл млЙЗ нз нк~ЕЙ С~мднлK qЬЙ С~мдн гЙлл~ЦЙл ~кЙ лнзкЙЗ бе нЬЙ Ьблнзку ДмССЙк бе нЬЙ зкЗЙк зС нЬЙбк зЕЕмккЙеЕЙK
qЬЙ гЙгзку дзЕ~нбзел Е~е ДЙ кЙнкбЙоЙЗ об~ нЬЙ ЕзЗЙлK
Structure of the history buffer Code C0168 Entry Note
C161 Memory location 1 Active fault
C162 Memory location 2 Last fault
C163 Memory location 3 Last but one fault
C164 Memory location 4 Last but two fault
If the fault is no longer active or has been acknowledged:
D The contents o
the memory locations 1-3 will be saved in a
”higher” location.
D The contents of the memory location 4 will be eliminated from
orybu
er andcanno
D Memory location 1 will be deleted (= no active fault).
ereadanylonger.
8-2
UOOuhäáã~_^NMMO
Page 79
Troubleshooting and fault elimination
Show/Hide Bookmarks

8.3 Fault indications

Display Fault Cause Remedy
--- No fault - ­EEr External fault (TRIP-Set) A digital input assigned to the TRIP-Set
function has been activated H05 Internal fault Contact Lenze LP1 Motor phase failure D Failure of one or several motor phases
D Motor current too low
LU Undervoltage DC-bus voltage too low D Check mains voltage
OC1 Short circuit
Short circuit Find out cause of short circuit; check cable
Excessive capacitive charging current of
the motor cable OC2 Earth fault
Grounded motor phase Check motor; check cable
Excessive capacitive charging current of
the motor cable OC3 Overload inverter during
Acceleration time too short (C012) D Increase acceleration time
acceleration or short circuit
Defective motor cable Check wiring
Interturn fault in the motor Check motor OC4 Overload controller during
Deceleration time too short (C013) D Increase deceleration time
deceleration
OC5 I x t overload Frequent and too long acceleration
processes with overcurrent OC6 Overload motor
Motor is thermally overloaded, for
instance, because of
D impermissible continuous current D Check drive selection
D frequent or too long acceleration
processes
OH Heat sink temperature is
higher than the value set in the controller
Ambient temperature
> +40 °C or +50 °C
T
amb
Heat sink very dirty Clean heat sink
Incorrect mounting position Change mounting position OH3 PTC monitoring (TRIP)
Motor too hot bec ause of exc essive
current or frequent and too long
acceleration
PTC not connected Connect PTC or switch-off monitoring
OH4 Overtemperature unit Inside unit too hot D Reduce controller load
OH51 PTC monitoring (Warning)
Motor too hot because of excessive
current or frequent and too long
acceleration
PTC not connected Connect PTC or switch-off monitoring
Check external encoder
Check motor cables, check V connect motor with corresponding power or adapt motor under C599.
D Check supply module
Use motor cable which is shorter or of lower capacitance
Use motor cable which is shorter or of lower capacitance
D Check drive selection
D Check the selection of the brake resistor or
connect the brake chopper
Check drive dimensioning
D Check the setting under C120
D Allow controller to cool and ensure ventilation D Check the ambient temperature in the control
cabinet
Check drive dimensioning
(C0585=3)
D Improve cooling D Check fan in the controller
Check drive dimensioning
(C0585=3)
min
setting,
UOOuhäáã~_^NMMO
8-3
Page 80
Troubleshooting and fault elimination
g
y
g
Show/Hide Bookmarks
Display RemedyCauseFault
OV Overvoltage
Pr Faulty parameter transfer
via the operating module
Pr1 Faulty PAR1 transfer via the
operating module
Pr2 Faulty PAR2 transfer via the
operating module
rSt Faulty auto-TRIP reset More than 8 fault messages in 10
Mains voltage too high Check voltage supply Feedback operation
Braking operation
Earth leakage on the motor side Check motor cable and motor for earth fault
PAR1 and PAR2 are defective.
PAR1 is defective.
PAR2 is defective.
minutes
D Increase deceleration times. D For operation with brake choppers:
- Check the selection and connection of the brake resistor
- Increase the deceleration times
(disconnect motor from inverter) It is absolutely necessary to repeat the data
transfer or load the factory setting before enabling the controller.
Depends on the fault message
8-4
UOOuhäáã~_^NMMO
Page 81
Troubleshooting and fault elimination
Show/Hide Bookmarks

8.4 Reset of fault indications

TRIP
^СнЙк Йдбгбе~нбеЦ нЬЙ С~мднI нЬЙ ймдлЙ беЬбДбн пбдд зеду ДЙ кЙлЙн ~СнЙк нЬЙ ~ЕвезпдЙЗЦЙгЙен зС qofmK
Note!
fС нЬЙ qofm лзмкЕЙ бл лнбдд ~ЕнбоЙI нЬЙ qofm Е~еезн ДЙ кЙлЙнK
Code Name Possible settings IMPORTANT
Lenze Selection Info
C170¿ TRIP-reset selection -0- TRIP-reset by pressing the STP key
C171 Delay for
Auto-TRIP-Reset
0.00 0.00 {0.01s} 60.00
or a LOW signal at ctrl. enable
-1- Auto-TRIP reset
Function You can select whether the fault is to be reset automatically or manually.
Activation C170 = -0-:
D Manual TRIP-reset D STP key D LOW signal at terminal 28
C170 = -1-:
Auto-TRIP reset resets all faults after the time set under C171.
Important
D Mains switching always resets TRIP. D With more than 8 Auto-TRIP resets within 10 minutes, the controller sets TRIP and indicates rST.
UOOuhäáã~_^NMMO
8-5
Page 82
Troubleshooting and fault elimination
Show/Hide Bookmarks
8-6
UOOuhäáã~_^NMMO
Page 83

9 Accessories (Overview)

Show/Hide Bookmarks

9.1 Accessories for all types

Name Order number
8201BB operating module EMZ8201BB Diagnosis terminal (2.5 m cable) EMZ8272BB-V001 Diagnosis terminal (5.0 m cable) EMZ8272BB-V002 Diagnosis terminal (10 m cable) EMZ8272BB-V003 Digital display EPD203 Setpoint potentiometer ERPD0001k0001W Rotary button for potentiometer ERZ0001 Scale for potentiometer ERZ0002 RS232/485 fieldbus module EMF2102IB-V001 RS485 fieldbus module EMF2102IB-V002 Level converter for RS485 EMF2101IB PC system cable RS232/485 EWL0020 Optical fibre fieldbus module EMF2102IB-V003 Optical fibre adaptor for PLC 0...40m EMF2125IB Supply unit for optical fibre adaptor 2125 EJ0013 InterBus-S module EMF2111IB PROFIBUS module EMF2131IB System bus module (CAN) EMF2171IB System bus module (CAN) with addressing EMF2172IB PTC module EMZ8274IB I/O module EMZ8275IB Monitor module EMZ8276IB Bipolar setpoint module EMZ8278IB Analog module EMZ8279IB
Accessories

9.2 Software

Name Order number
PC program for Global Drive controllers ESP-GDC 1
UOOuhäáã~_^NMMO
9-1
Page 84
Accessories
Show/Hide Bookmarks

9.3 Type-specific accessories

9.3.1 Types 822X
Name Order number
8221 8222 8223 8224
Mains filter type A EZN3A0110A030 EZN3A0080A042 EZN3A0060H054 Mains filter type B EZN3B0110A030 EZN3B0080A042 EZN3B0060H054 Mains choke ELN3-088H035 ELN3-0075H045 ELN3-0055H055 ELN3-0038H085 Motor filter ELM3-004H055 ELM3-004H055 on request on request Sine filter on request on request on request on request Brake module EMB9351-E EMB9351-E EMB9351-E EMB9351-E Brake chopper EMB9352-E EMB9352-E EMB9352-E EMB9352-E (2 x ) Brake resistor ERBD033R02k0 ERBD022R03k0 ERBD018R03k0 ERBD022R03k0 (2 x ) Thermal separation
(”Push-through technique”)
DC-bus fuse EFSCC0500AYJ EFSCC0800AYJ EFSCC1000AYJ EFSCC0800AYJ (2 x) Fuse holder EFH20004 EFH20004 EFH20004 EFH20004 (2 x )
EJ0011 EJ0011 EJ0011 EJ0011
Name Order number
8225 8226 8227
Mains filter type A Mains filter type B Mains choke ELN3-0027H105 ELN3-0022H130 ELN3-0017H170 Motor filter on request on request on request Sine filter on request on request on request Brake module EMB9351-E EMB9351-E EMB9351-E Brake chopper EMB9352-E (2 x ) EMB9352-E (3 x) EMB9352-E (3 x) Brake resistor ERBD018R03k0 (2 x) ERBD022R03k0 (3 x) ERBD018R03k0 (3 x) Thermal separation
(”Push-through technique”)
DC-bus fuse EFSCC1000AYJ (2 x) EFSCC0800AYJ (3 x) EFSCC1000AYJ (3 x) Fuse holder EFH20004 (2 x ) EFH20004 (3 x) EFH20004 (3 x)
9-2
UOOuhäáã~_^NMMO
Page 85
9.3.2 Types 824X
Show/Hide Bookmarks
Name Order number
E.l.c.b. EFA3B06A EFA3B06A EFA3B10A EFA3B10A Fuse EFSM-0060AWE EFSM-0060AWE EFSM-0100AWE EFSM-0100AWE Fuse holder EFH10001 EFH10001 EFH10001 EFH10001 Mains filter type A EZN3A2400H002 EZN3A1500H003 EZN3A0900H004 EZN3A0500H007 Mains filter type B EZN3B2400H002 EZN3B1500H003 EZN3B0900H004 EZN3B0500H007 Motor filter ELM3-030H004 ELM3-030H004 ELM3-014H010 ELM3-014H010 Sine filter EZS3-002A001 EZS3-004A001 EZS3-006A001 EZS3-010A001 Brake module EMB9351-E EMB9351-E EMB9351-E EMB9351-E Brake chopper EMB9352-E EMB9352-E EMB9352-E EMB9352-E Brake resistor ERBD180R 300W ERBD180R300W ERBD082R600W ERBD068R800W Thermal separation
(”Push-through technique”)
DC-bus fuse EFSCC0060AYJ EFSCC0060AYJ EFSCC0080AYJ EFSCC0120AYJ Fuse holder EFH20004 EFH20004 EFH20004 EFH20004
Accessories
8241 8242 8243 8244
EJ0036 EJ0036 EJ0037 EJ0037
Name Order number
8245 8246
E.l.c.b. EFA3B13A EFA3B20A Fuse EFSM-0160AWE EFSM-0200AWE Fuse holder EFH10001 EFH10001 Mains filter type A EZN3A0300H013 EZN3B0300H013 Mains filter type B EZN3B0300H013 ELN3-0160H012 Motor filter ELM3-014H010 EZN3A0150H024 Sine filter EZS3-009A002 EZN3B0150H024 Brake module EMB9351-E EMB9351-E Brake chopper EMB9352-E EMB9352-E Brake resistor ERBD047R01k2 ERBD047R01k2 Thermal separation
(”Push-through technique”)
DC-bus fuse EFSCC0200AYJ EFSCC0400AYJ Fuse holder EFH20004 EFH20004
EJ0038 EJ0038
UOOuhäáã~_^NMMO
9-3
Page 86
Accessories
Show/Hide Bookmarks
9-4
UOOuhäáã~_^NMMO
Page 87

10 Index

Show/Hide Bookmarks
Index
A
^ЕЕЙдЙк~нбзе нбгЙлI RJQ
^З~йн нЬЙ гзнзкI RJS
^е~дзЦ йдмЦJбе гзЗмдЙ
^ллЙгДдуI QJP
cЙ~нмкЙлI PJNP
qЙЕЬебЕ~д З~н~I PJNP
^ййдбЕ~нбзеI ~л ЗбкЙЕнЙЗI NJO
^ййдбЕ~нбзе ЕзеЗбнбзелI OJN
^ййдбЕ~нбзе Йс~гйдЙлI RJNP
^бк ЕзеЗбнбзебеЦI RJNP
mмгй ~ййдбЕ~нбзе пбнЬ дЙоЙд ЕзенкздI RJNU
mмгй ~ййдбЕ~нбзе пбнЬ йкЙллмкЙ ЕзенкздI RJNS
^ййдбЕ~нбзел ~л ЗбкЙЕнЙЗI NJO
^ййкзо~длI OJN
^ллЙгДду
^е~дзЦ йдмЦJбе гзЗмдЙI QJP
tбнЬ СбсбеЦ Дк~ЕвЙнл
qóéÉë UOOuI Q JO qóéÉë UOQuI Q JO
^мнзJqofm кЙлЙнI UJR
C
`~ДдЙ ЕкзллJлЙЕнбзелI pбеЦдЙ ЗкбоЙлI PJNN
NOM B зоЙкдз~ЗI PJNN NRM B зоЙкдз~ЗI PJNO
`çÇÉ í~ÄäÉI TJO
fеСзкг~нбзезенЬЙI TJO
`зггбллбзебеЦI RJN `зеСбЦмк~нбзеI TJN
^ЕЕЙдЙк~нбзе ~еЗ ЗЙЕЙдЙк~нбзе нбгЙлI RJQ _~лбЕ беСзкг~нбзеI TJN `зЗЙ н~ДдЙI TJO `мккЙенJдбгбн о~дмЙлI RJR j~сбгмг СбЙдЗ СкЙимЙеЕуI RJP jбебгмг СбЙдЗ СкЙимЙеЕуI RJP
`зееЙЕнбзе
^е~дзЦ йдмЦJбе гзЗмдЙI QJNP `зенкздI `зееЙЕнбзе Зб~Цк~гI QJNO `зенкзд Е~ДдЙлI QJNM j~белI QJR jзнзкI QJS mзпЙк I `бкЕмбн Зб~Цк~гI QJV qЙгйЙк~нмкЙ гзебнзкбеЦI QJNN
`зееЙЕнбзе Зб~Цк~г
^е~дзЦ йдмЦJбе гзЗмдЙI QJNP `зенкзд ЕзееЙЕнбзелI QJNO mзпЙк ЕзееЙЕнбзеI QJV
`зееЙЕнбзелI mзпЙкI QJR `зенкзд Е~ДдЙлI QJNM `зенкзд ЕзееЙЕнбзелI QJNM `зенкзд гзЗЙI йЙкгбллбДдЙI RJS `зенкзд нЙкгбе~длI QJNN
mкзнЙЕнбзе ~Ц~белн йзд~кбну кЙоЙкл~дI QJNN pмкоЙуI QJNN qЙкгбе~д ~ллбЦегЙенI QJNN
`зенкзддЙкI NJN
^ййдбЕ~нбзе ~л ЗбкЙЕнЙЗI NJO i~ДЙддбеЦI NJO
`мккЙенJдбгбн о~дмЙлI RJR
UOOuhäáã~_^NMMO
10-1
Page 88
Index
Show/Hide Bookmarks
D
aЙЕЙдЙк~нбзе нбгЙлI RJQ
aЙСбебнбзел зС нЙкгбездзЦу млЙЗI NJN
aЙЦкЙЙ зС йзддмнбзеI OJN
aÉê~íáåÖI RJR
aбгЙелбзел
UOOu пбнЬ СбсбеЦ Дк~ЕвЙнлI QJO
UOQu пбнЬ СбсбеЦ Дк~ЕвЙнлI QJO
^е~дзЦ йдмЦJбе гзЗмдЙI PJNQ
`зенкзддЙкI PJNQ
aáëéä~ó
ibaJI UJN
léÉê~íáåÖ ëí~íìëI UJN
F
c~Ензку лЙннбеЦ
fгйзкн~ен ЗкбоЙ й~к~гЙнЙклI RJO pЬзкн лЙнJмйI R JO pпбнЕЬJзе лЙимЙеЕЙI RJO
c~елI ^ййдбЕ~нбзе зС UOuuI PJO c~мдн ~е~дулблI UJO c~мдн гЙлл~ЦЙлI UJP
oÉëÉíI UJR
cбЙдЗ СкЙимЙеЕу
j~сбгмгI RJP jбебгмгI RJP
cкЙимЙеЕу беоЙкнЙкK pÉÉ `зенкзддЙк cмлЙл
бе riJ~ййкзоЙЗ лулнЙглI PJNN pбеЦдЙ ЗкбоЙлI PJNN
NOM B зоЙкдз~ЗI PJNN NRM B зоЙкдз~ЗI PJNO
G
dÉåÉê~ä Ç~í~I OJN
aкбоЙ й~к~гЙнЙклI c~Ензку лЙннбеЦI R JO
aкбоЙ лулнЙгI NJN
E
bдЙЕнкбЕ~д белн~дд~нбзеI QJQ
fгйзкн~ен езнЙлI QJQ
bj`
^ллЙгДдуI QJNQ
`bJнуйбЕ~д ЗкбоЙ лулнЙгI fелн~дд~нбзеI QJNQ
cбднЙклI QJNQ
dкзмеЗбеЦI QJNQ
fåëí~ää~íáçåI QJNQ
pЕкЙЙебеЦI QJNQ
H
eблнзку ДмССЙкI UJO
pнкмЕнмкЙI UJO
eмгбЗбну Ед~ллI OJN
I
fебнб~д лпбнЕЬJзеI RJN fеймнл
^å~äçÖI QJNN aáÖáí~äI QJNN
fåëí~ää~íáçåI QJN
`bJнуйбЕ~д ЗкбоЙ лулнЙгI QJNQ
^ллЙгДдуI QJNQ cбднЙклI QJNQ dкзмеЗбеЦI QJNQ
pЕкЙЙебеЦI QJNQ bдЙЕнкбЕ~дI QJQ jЙЕЬ~ебЕ~дI QJN
fелн~дд~нбзе ЬЙбЦЬнI OJN fелмд~нбзе лнкЙеЦнЬI OJN
J
bеЕдзлмкЙI OJN
10-2
UOOuhäáã~_^NMMO
gмгйЙкI ^е~дзЦ лЙнйзбен лЙдЙЕнбз еI QJNN
Page 89
Index
Show/Hide Bookmarks
L
i~ДЙддбеЦI `зенкзддЙкI NJO
ibaI UJN
iЙЦ~д кЙЦмд~нбзелI NJO
iб~ДбдбнуI NJO
M
j~бел ЕзееЙЕнбзеI QJR
j~белJоздн~ЦЙ ЕзгйЙел~нбзеI RJU
j~дзйЙк~нбзе зС нЬЙ ЗкбоЙI UJO
j~емС~ЕнмкЙкI NJO
jÉÅÜ~åáÅ~ä áå ëí~ää~íáçåI QJN
jÉëë~ÖÉëI c~ìäíI UJP
jзебнзк змнймнI QJNN
jзебнзкбеЦI jзнзк нЙгйЙк~нмкЙI QJNN
jçíçêI ^Ç~éíI RJS
jзнзк Е~ДдЙI pЕкЙЙебеЦI QJS
jзнзк ЕзееЙЕнбзеI QJS
qóéÉë UOOuI Q JS qóéÉë UOQuI Q JT
P
m~Åâ~ÖáåÖI OJN
mfa ЕзенкзддЙкI RJNN
mзпЙк ЕзееЙЕнбзелI QJR
mкзнЙЕнбзе ~Ц~б е лн Езен~ЕнI QJNN
mкзнЙЕнбзе ~Ц~белн йзд~кбну кЙоЙкл~дI QJNN
mмгйлI ^ййдбЕ~нбзе зС UOuuI PJO
R
o~íÉÇ Ç~í~
qóéÉë UOONJUOOQ
NOM B зоЙкдз~ЗI PJP NRM B зоЙкдз~ЗI PJT
qóéÉë UOORJUOOT
NOM B зоЙкдз~ЗI PJQ NRM B зоЙкдз~ЗI PJU
qóéÉë UOQNJUOQP
NOM B зоЙкдз~ЗI PJR NRM B зоЙкдз~ЗI PJV
qóéÉë UOQQJUOQS
NOM B зоЙкдз~ЗI PJS NRM B зоЙкдз~ЗI PJNM
oЙд~у змнймнI QJNN
oÉëÉíI c~ìäí ãÉëë~ÖÉI UJR
oЙлбЗм~д Ь~т~кЗлI OJO
jзнзк нЙгйЙк~нмкЙ гзебнзкбеЦI QJNN
jзменбеЦ йзлбнбзелI qуйЙл UOOuLUOQuI QJN
N
kзблЙ ЙггбллбзеI OJN
kзблЙ бггмебнуI OJN
O
lйЙк~нбеЦ гзЗмдЙI c~мдн Зблйд~уI UJN
léÉê~íáåÖ ëí~íìëI aá ëéä~óI UJN
lйЙк~нбзеI pн~нмл Зблйд~уI UJN
lйЙк~нзкЫл л~СЙнуI OJO
lмнймнлI ^е~дзЦI QJNN
lоЙклйЙЙЗлI OJO
S
p~СЙну беСзкг~нбзеI OJN
Сзк ЕзенкзддЙкл нз iзпJsздн~ЦЙ aбкЙЕнбоЙI OJN i~узмнI OJO
p~СЙну езнЙлI i~узмн
lнЬЙк езнЙлI OJO t~кебеЦ зС З~г~ЦЙ нз г~нЙкб~дI OJO t~кебеЦзСЗ~еЦЙкнзйЙклзелI OJO
pЕзйЙ зС ЗЙдбоЙкуI NJN
pЕкЙЙебеЦ
bj`I QJNQ jçíçê Å~ÄäÉI QJS
pÜçêí ëÉíJìéI RJO
páÖå~äJÑäçï ÅÜ~êíëI RJOM
pпбнЕЬJзеI fебнб~дI RJN
pпбнЕЬJзе лЙимЙеЕЙI c~Ензку лЙннбеЦI RJO
UOOuhäáã~_^NMMO
10-3
Page 90
Index
Show/Hide Bookmarks
T
qЙЕЬебЕ~д З~н~I OJN
^е~дзЦ йдмЦJбе гзЗмдЙI PJNP
cЙ~нмкЙлI PJNP
dЙеЙк~д З~н~L~ййдбЕ~нбзе ЕзеЗбнбзелI OJN
qЙгйЙк~нмкЙ гзебнзкбеЦI QJNN
qЙгйЙк~нмкЙ к~еЦЙлI OJN
qк~елйзкнI лнзк~ЦЙI OJN
qofmI UJR
qкзмДдЙлЬззнбеЦI UJN
aблйд~у ~н нЬЙ зйЙк~нбеЦ гзЗмдЙ I UJN c~мдн ~е~дулбл млбеЦ нЬЙ Ьблнзку ДмССЙк I UJO c~мдн беЗбЕ~нбзеI UJP ibaI UJN j~дзйЙк~нбзе зС нЬЙ ЗкбоЙI UJO oЙлЙн зС С~мдн беЗбЕ~нбзелI UJR qofmI UJR
U
rебн йкзнЙЕнбзеI OJO
V
sбДк~нбзе кЙлблн~еЕЙI OJN
W
t~êê~åíóI NJO
t~лнЙ Зблйзл~дI NJO
10-4
UOOuhäáã~_^NMMO
Page 91
Index
Show/Hide Bookmarks
UOOuhäáã~_^NMMO
10-5
Page 92
Index
Show/Hide Bookmarks
10-6
UOOuhäáã~_^NMMO
Loading...