Lenze 8201, 8203, 8202, 8204 Operating Instructions Manual

Page 1
EDB8200UE 00398283
Operating Instruct ions
G l obal D rive
Frequency inverters 8200 series
Typ
Id.-NR
Serien-Nr.
Eingang1
Eingang2
Lenze
Postfach 101352 ,31763 HAMELN
K35.0110-3
Page 2
TheseOperatingInstructionsarevalidforthe82XX controllersoftheversions:
33.820X- E- 1x. 1x (8201 - 8204)
33.8202- E- 1x. 1x -V002 reduced assemblydepth(8202)
Type
Design: B= Module C= ColdPlate E= Enclosure IP20
H ardware level and index
Software level and index
Variant
E x planation
Correspondsto the German editionof 16/06/1997 Edition of: 02/10/1997
Page 3
Contents
820XBA1097 i
1 Preface and general inform ation 1- 1...........................
1.1 About theseOperating Instructions . .. 1-1.......................
1.1.1 Terminologyused 1-1...............................
1.1.2 Whatisnew? 1-2..................................
1.2 Scope of delivery 1-2.....................................
1.3 Legal regulations 1-3.....................................
2 Safety information 2- 1......................................
2.1 General safety information 2-1...............................
2.2 Layout of the safety information 2-3...........................
2.3 R esidual hazards 2-4.....................................
3 Technical data 3- 1.........................................
3.1 General data/application conditions 3-1.........................
3.2 R ated data (O peration with 150 % overload) 3-2...................
3.2.1 Types 8201 to8204 3-2.............................
3.3 F uses and cable cross-sections 3-4...........................
3.3.1 Single driveswith150 % overload 3-4....................
3.4 Dimensions 3-4.........................................
4 Installation 4-1............................................
4.1 Mechanical installation 4-1.................................
4.1.1 Importantnotes 4-1.................................
4.1.2 St andard assembly with fixingrails or fi xing angles 4-3.........
4.1.2.1 Types8201 to8204 4-3......................
4.1.2.2 Type 8202-V002 (reducedassemblydepth) 4-4.......
4.1.3 DIN-rail assembly 4-5...............................
4.2 Electricalinstallation 4-6...................................
4.2.1 Importantnotes 4-6.................................
4.2.2 Power connections 4-7..............................
4.2.2.1 Mainsconnection 4-7........................
4.2.2.2 Motor connection 4-7........................
4.2.2.3 Connectiondiagram 4-9.......................
4.2.3 Controlconnections 4-10..............................
4.2.3.1 Controlcables 4-10...........................
4.2.3.2 Assignment of thecontrol terminals 4-10............
4.2.3.3 Connectiondiagrams 4-12......................
4.3 Installationof a CE-typical drive system 4-13......................
Page 4
Contents
ii 820XBA1097
5 Commissioning 5-1.........................................
5.1 Before you switch on 5-1..................................
5.2 Short set-up (Factorysetting) 5-2.............................
5.2.1 Switch-onsequence 5-2.............................
5.2.2 Factory setting of the most important drive parameters 5-3......
5.3 Adapt machine data 5-4...................................
5.3.1 Determinespeedrange (fdmin, f dmax) 5-4.................
5.3.2 Adjustment of acceleration and deceleration times (Tir , T if) 5-6..
5.3.3 Settingofthecurrent limit(Imax) 5-7.....................
5.4 Optimisation of the operating characteristic of the drive 5-8...........
5.4.1 Select the control mode 5-8...........................
5.4.1.1 OptimisationofV/f-characteristiccontrolwithautoboost......
5-11
5.4.1.2 Optimisation of V/ f- characteristic control 5-13.........
6 During operation 6-1.......................................
7 Configura t ion 7-1..........................................
7.1 Basics 7-1............................................
7.2 Code table 7-2.........................................
8 Troubleshooting and fault elim ina t ion 8-1.......................
8.1 Troubleshooting 8-1......................................
8.1.1 Display at the controller 8-1...........................
8.1.2 Display at the oper ating module 8-1.....................
8.1.3 Maloperation of the drive 8-2..........................
8.2 F ault analysis using the history buffer 8-2.......................
8.3 F ault indications 8-3......................................
8.4 R eset of fault indications 8-5................................
9 Accessories (Overview ) 9-1..................................
9.1 Accessoriesfor alltypes 9-1................................
9.2 Software 9-2...........................................
9.3 Type-specific accessories 9-2...............................
10 Inde x 9-3................................................
Page 5
Preface and gener al inf orm ation
820XBA1097 1-1
1 Preface and general information
1.1 About these Operating Instructions ...
-
TheseOperating Instructions help you to connect and set up the 82X Xfrequency inverter. Theycontain safety information which must be observed.
-
All persons who work on and with 82X Xfrequency inverters must have the Operating Instructionsavailable and observe all relevant notes and instructions.
-
TheOperating Instructions must always be inacompleteand perfectly readable state.
1.1.1 Terminology used
Term In the following text used for 82XX Anyfrequencyinverter of theseries8200, 8210, 8220, 8240 Controller 82XXfrequency inverter Drive system Drive systems with 82 XXfrequencyinvertersandother Lenze drive
components
Page 6
1-2 820XBA1097
1.1.2 What is new?
Material no.
Edition of Important Content
375134 05/10/1994 8200/8210 Short Instructions 375190 13/02/1995 8200/8210 Operating Instructions 398283 02/10/1997 replaces 375134
replaces 375190
-
Contentsonlyfor8200
-
Complete revision of the contents
-
Completeeditorial revision
1.2 Scope of delivery
Scope of delivery Important
-
1 82XX frequencyinverter
-
1 Operating Instructions
-
1 accessory kit (componentsf or the mechanical and electric installation)
After receipt of the delivery, check immediately whether the scope of supply matches with the accompanying papers. Lenze doesnot accept anyliabilityfor deficiencies claimed subsequently.
Claim
-
visible transport damage immediatelyto the forwarder.
-
visible deficiencies/incompleteness immediatelyto your Lenze representative.
Page 7
Preface and gener al inf orm ation
820XBA1097 1-3
1.3 Legal regulations
Labelling
Nameplate CE mark Manufacturer
Labelling
Conforms to the ECLow V oltage Directive
Lenze GmbH & CoKG Postfach101352 D- 31763 Hameln
Application as directed
82XX frequency inverter
-
must only be operatedunder theconditionsprescribed in theseInstructions.
-
are components
- used for open and closed loop control of variable speed drives withasynchronous standard motors, reluctance motors, PM-synchronousmotorswith asynchronousdamping cage.
- usedfor installati on into a machine.
- used for assembly together with other components to form a machine.
-
are electric units for theinstallation into control cabinetsor similar enclosed operating housing.
-
comply with the requirements of theLow-Voltage Directive.
-
are not machines for the purpose of the Machinery Directive.
-
are not to be used as domestic appliances, but only for industrial purposes.
Drive systems with 82XX frequency inverters
-
comply with the EMCDirective if theyare installed according tothe guidelines of CE-typical drive systems.
-
canbeused
- on public and non-public mains.
- in industrial as well as residential and commercial premises.
-
The user is responsible for thecomplianceof his application with the ECdirectives.
Any other use shall be deemed inappropriate!
Page 8
1-4 820XBA1097
Liability
-
The information, data and notes in these Operating Instructions met the state of the art at the time of printing. Claims referring to drive systems which have already been supplied cannot be derived from theinformation, illustrations, and descriptions given in t hese Operating Instructions.
-
Thespecifications, processes, and circuitrydescribed in these Operating Instructions are for guidance only and must be adapted to your own specific application. Lenze does not take responsibilityfor the suitability of the processand circuit proposals.
-
Theindicationsgiven in these Operating Instructions describethe featuresof theproduct without warranting them.
-
Lenzedoesnot accept anyliabilityfor damage and operatinginterference causedby:
- disregarding theseInstructions
- unauthorized modifications to thecontroller
- operat i ng errors
- improperworking onand with the controller
Warranty
-
Warrantyconditions: see Sales and Delivery Conditions of Lenze GmbH& Co KG.
-
Warrantyclaims must be madeimmediatelyafter detecting defects or faults.
-
The warrantyis voidin all caseswhereliabilityclaimscannotbe made.
Disposal
Material recycle dispose
Disposa
l
Metal
-
-
Plastic
-
-
Printed-board assemblies -
-
Page 9
Safety information
820XBA1097 2-1
2 Safety information
2.1 General safety information
Safety and application notes for controllers
(to: Low-VoltageDirective 73/23/ EEC)
1. General
During operation, drivecontrollers may have, according to their type of protection, live, bare, in some cases also movable or rotating parts as well as hot surfaces.
Non-authorized removal of the required cover, inappropriate use, incorrect installation or operation, creates the risk of sev ere injury to persons or damage to material assets.
Further information can be obtained from the documentation.
All operations concerningtranspo rt, installation, and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 364 andCENELEC HD 384 or DIN VDE 0100 and IEC report 664 or DIN VDE 0110 and national regulationsfortheprevention of accidents must be observed).
According to this basic safetyinformationqualified skilledpersonnel arepersons who arefamiliarwith the erection, assembly, commissioning, and operation of the product and who havethe qualifications necessaryfor their occupation.
2. Applicat ion as directed
Drive controllers are components which are designed for installation in electrical systems or machinery.
When installing in machines, commissioning of the drive controllers (i.e. the starting of operation as directed) is prohibited until it isproven that themachine corresponds
totheregulationsoftheECDirective 89/392/EEC (Machinery Directive); EN60204 must beobserved. Commissioning (i.e. starting of operation as directed) is onlyallowed when t here is compliancewith t he EMC Directive(89/336/EEC). The drivecontrollers meet the requirements of the Low V oltage Directive 73/23/EE C. The harmonizedstandards oftheprEN50178/ DIN VDE0160 seriestogetherwith EN60439- 1/DIN VDE0660 part 500 andEN60146/DIN VDE0558 areapplicableto drive controllers. Thetechnical data and information on the connection conditions must be obtained from the nameplate and the documentation and must be observed in all cases.
3. Transport, storage
Noteson transport, storageand appropriate handling must be observed.
Climatic conditionsmust be observed according to
prEN50178.
4. Erection
The devices must be erected and cooled according to the regulations of the corresponding documentation. The drivecontrollers must be protectedfrom inappropriate loads. Particularlyduring transport and handling, components must not be bent and/or isolating distances must not be changed. Touching of electronic components and contacts must be avoided. Drive controllerscontainelectrostat icallysensitive components which can easily be damaged by
Page 10
Safety information
2-2 820XBA1097
inappropriate handling. E lectrical components must not be damaged or destroyed mechanically(health risks are possible!).
5. Electrica l connection
When working on live drive controllers, the valid national regulations for the prevention of accidents (e.g. VBG4) must be observed.
Theelectrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PEconnection). More detailed information is included in the documentation.
Notes concerning the installation in compliance with EMC - such asscreening, grounding, arrangement of filtersand laying of cables - are included in the documentation of the drivecontrollers. Thesenotes must also be observ ed in all cases for drivecontrollers with the CEmark. The compliance with therequired limit values demanded bythe EMClegislation is the responsibilityof the manufacturerof the systemor machine.
6. Operation
Sy stems where drive controllers are installed must be equipped, if necessary, with additionalmonitoring and protectivedevices according to thevalid safety regulations, e.g. law on technical tools, regulationsfor the preventionof accidents, etc. Modifications of the drivecontrollersby the operating software are allowed.
After disconnectingthe drivecontrollers from the supply voltage, liveparts of the controller and power connections must not be touched immediately, because of possibly charged capacitors. For this, observe the corresponding labelson the drive controllers. During operation, all covers and doors must be closed.
7. Maintenance and servicing
Themanufacturer’s documentation must be observed.
This safety information must be kept!
The product-specific safety and application notes in these Operating Instructions must also be observed!
Page 11
Safety information
820XBA1097 2-3
2.2 Layout of the safetyinformation
-
All safety notes have a uniform layout:
- The icon characterizesthetype of danger.
- The signal word characterizes the severity of danger.
- The note describes thedanger and suggests how to avoid the danger.
Signal word
Note
Icons used Signal words
Warning of danger to persons
Warning of hazardous electrical voltage
Danger! Warns of impending dangeU.
Consequences if disregarded: Death or very severe injuries.
Warning of a general danger
Warning! Warns of potential, very hazardous situations.
Possible consequences if disregarded: Death or very severe injuries.
Caution! Warns of potential, hazardous situations.
Possible consequences if disregarded: Light or minor injuries.
Warning of damage to material
Stop! Warns of potential damage to material .
Possible consequences if disregarded: Damageof t he controller/drive system or its
environment
.
Other notes Note! T his note designates general, useful notes.
If youobserveit, handling of the controller/drive system is made easier.
Page 12
Safety information
2-4 820XBA1097
2.3 Residual hazards
Operator’s safety After mains disconnections, thepower terminals U, V, Wand +UG,-UGremainlivefor at
least three minutes.
-
Beforeworking on the controller, check that no voltageis applied tothe power terminals.
Prot ection of devices
Cyclic connection and disconnection of the controller supplyvoltage at L1, L2, L3 or +UG,
-U
G
may overloadthe internal input current load:
-
Allow at least3 minutes between disconnection and reconnection.
Overspeeds Drive systems can reach dangerous overspeeds (e. g. setting of inappropriately high field
frequencies):
-
The controllers do not offer any protection against these operating conditions. Use additional components for this.
Page 13
Technical Dat a
820XBA1097 3-1
3Technicaldata
3.1 General data/application conditions
Field Values Vibra tion resistance Germanischer Lloyd, general conditions Humidity class Humidity class F without condensation (average relative humidity 85 %) Permissible
during transport of thecontroller: -25C¤+70C
Permissible
temperature ranges
during storage of the controller: -25C¤+55C during operation of the controller: 0C¤+40C
+40
C¤
+50C
without power derating with power derating
Permissible instal lation height h
h$1000 m.a.m.s.l 1000 m a.m.s.l
h$
4000 m a.m.s.l
without power derating with power derating
Degree of pollution VDE 0110 part2 pollutiondegree2 Noise emission Requirementsacc. to EN50081-2, EN50082-1, IEC22G- WG4 (Cv) 21
Limit valueclass A to EN55011 (industrial area)with mains filter Limit valueclass B to EN55022 (residential area)withmains filter andinstallation into
control cabinet
Noise immunity
Limit values maintained usig mains filter Requirementsaccording to EN50082- 2, IEC22G-WG4 (Cv)21
Requirements Standard Severities
ESD EN61000-4- 2 3, i. e. 8 kVwith air discharge
6 kVwith contact discharge R Finterference(enclosure) EN61000-4- 3 3, i.e. 10 V/m;27¤1000 MHz Burst EN61000-4- 4 3/4, i.e.2 kV/5 kHz Surge
(Surge on mains cable)
EN61000- 4- 5 3,i.e.1.2/50³s,
1 kV phase-phase,
2 kV phase-PE
Insulation strength Ov ervoltage categoryIII according to V D E0110 Packaging (DIN
4180)
Dust packaging
Type of protection IP20
NEMA 1: Protection against contact
Approvals CE: Low Voltage Directive
Electromagnetic compatibility
Page 14
Technical Data
3-2 820XBA1097
3.2 Rat ed data (Operation w ith 150 % ove rload)
3.2.1 Types 8201 to 8204
150 % overload Type 8201 8202 8203 8204
Order no. EVF8201-E EVF8202-E EVF8203-E EVF8204-E
Variant ”reduced assembly
Type 8202-V002
Variantreducedassembly
depth”
Order no. EVF8202-E-V002
Mainsvoltage V
rated
[V] 190Vá0%$V
rated
$
260Vá0% ; 45Hz¤65Hzá0%
AlternativeDCsupply VDC[V] 270Vá0%$V
DC
$
360Vá0%
Mains current
4)
with mains filter/mains choke without mains filter/mains choke
I
mains
[A]
4.2
5.0
7.5
9.0
12.5
15.0
17.0
-
Data for mains operation with 1 AC/ 230 V / 50 Hz/60 Hz; 270$V
DC
$
275V
Motor power (4 pole ASM)
P
rated
[kW] 0.37 0.75 1.5 2.2
Motorpower(4poleASM
)
at 9.2 kHz*
P
rated
[hp] 0.5 1.0 2.0 2.9
Output power U, V, W at 9.2 kHz*
S
N9.2
[kVA] 1.0 1.5 2.7 3.6
Output power +UG,-U
G
1)
PDC[kW] 0.0 0.0 0.0 0.0
Output current I
rated
[A] 2.6 4.0 7.0 9.5
Max. output current for 60s
2)
I
Nmax
[A] 3.9 6.0 10.5 14.2
Motor voltage
3)
VM[V] 0-3V
mains
/0Hz¤50Hz, if required upto240Hz
Power loss (O peration with IN) Pv[W] 30 50 70 100
Page 15
Technical Data
820XBA1097 3-3
150 % overload 8204820382028201Type
EVF8204-EEVF8203- EEVF8202-EEVF8201- EOrder no.
Variant ” reduced a ssembly depth”
8202-V002TypeVariant ” reduced assembly
depth”
EVF8202- E- V002Order no.
Power derating [%/K]
[%/m]
40C< T
amb
<50C: 2,5%/K
1000 m a.m.s.l.
h$
4000 m a.m.s.l.: 5%/1000 m
Field
Resolution Absolute 0.05Hz
Field
frequency
Digital setpoint selection
Accuracy
á
0.05 Hz
Analog setpoint
Linearity
á
0.5 % (max. selected signal level, 5V or 10V)
Analogsetpoin
t
selection
Temperature sensitivity
0¤40C: +0.4 %
Offset
á
0.3 %
Weight m[kg] 1.0 1.3
Variant 1.0
2.2 2.2
1)
This power can be additionally obtained when operating a matching motor
2)
Thecurrentsapplytoa periodicalloadcyclewith1 minute overcurrentwith thecurrentmentioned here and 2 minutes base load with 75% I
Nrated
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of themains v oltage
4)
Observ etheN-conduction load when having a symmetrical mains distribution! (Seeelectrical installation)
* Cho pper frequencyof the inverter
Page 16
Technical Dat a
3-4 820XBA1097
3.3 Fuses and cable cross-sections
3.3.1 Single drives with 150 % overload
The table values are valid for the operation of 82X Xcontrollers as singledrives with a mat ching motor and 150 % overload.
Type
MainsinputL1,N,PE/motorconnectionU,V,W,PE
Typ
e
Operationwithoutmainsfilter/ mains choke Operation with mains filter/mains choke
Fuse F1, F2, F3
E.l.c.b. Cable
cross-section
1)
Fuse F1, F2, F3
E.l.c.b. Cable
cross-section
1)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG
8201 M 10A - C10A 1.5 15 M 10A - C10A 1.5 15 8202 M 15A - C16A 2.5 13 M 15A - C16A 2.5
[1.5]
13 [15]
8203 M 20A - C20A 4 11 M 15A - C16A 2.5
[1.5]
13 [15]
8204 - - - - - M 20A - C20A 4
[2.5]
11 [13]
V alues in square brackets are valid for motor connection
1)
Observe national and regional regulations (e. g. VDE/EVU)!
3.4 Dimensions
The controller dimensions depend on the mechanical installation ( see chapter 4.1) .
Page 17
Installa t ion
820XBA1097 4-1
4 Installation
4.1 Mechanical installation
4.1.1 Important notes
-
Use the controllers only as built-in devices!
-
If the cooling air contains pollutants (dust, fluff, grease, aggressivegases):
- take suitable preventive measures , e.g. separate air duct, installation of filters, regular cleaning, etc.
-
Observe free space!
- Youcan installseveral controllers next to eachother without free spac e inacontrolcabinet.
- Ensureunimpeded ventilation of cooling air and outlet of exhaust air!
- Allow afreespaceof 100mmat thetop and atthebottom.
-
Do not exceed the ambient temperature permissible during operation ( see chapter . 3.1)
-
With continous oscillations or vibrations:
- Check whether shock absorbers arenecessary.
Page 18
Installat ion
4-2 820XBA1097
Possible mounting positions
-
Invertical position at theback of the control cabinet, terminals pointto thefront:
- Withattached fixing rails.
- With special fixing unit on oneor two DINrails.
-
Turned by 90( flat assembly on the backside of the control cabinet) :
- Insert theattached fixing rail into the guides at the heat sink.
-
Horizontally with an additional fan.
-
Ona pivoting framefor assemblydepths< 198 mm:
- Thereforeeasy handling and installation of the front interfaces possible.
Page 19
Installa t ion
820XBA1097 4-3
4.1.2 Standard assembly with fixing rails or fixing angles
4.1.2.1 Types 8201 to 8204
g
Typ
Id.-NR
Fert. -Nr
Serien-Nr.
Eingang1
Eingang2
Lenze
Postfach101352,31763HAMEL N
c
k
a
e
db
1)
2)
3)
K35.0074
FIG 4-1 Dimensions 8201 - 8204: Standard assembly
1)
Fixing rail for sideassembly
2)
Observe the free space required for the connection cables
3)
With attachable fieldbus or I/Omodule: Observ eassembly depth and assembly space required for connectioncables
[mm]
a b c d e
3)
g k
8201 64 210 29 190 158 6.5 30 8202 64 210 29 190 198 6.5 30 8202- V002 64 210 29 190 158 6.5 30 8203 / 8204 83 283 38 263 211 6.5 30
Page 20
Installat ion
4-4 820XBA1097
4.1.2.2 Type 8202-V002 (reduced assembly depth)
This variant is equipped with a heat sink with a smaller surface. Observe the following points to comply with the technical data:
-
Assembly on an unpainted, metallic assembly board.
-
Area > 0.15 m2.
-
Sheet thickness at least 2 mm.
Page 21
Installa t ion
820XBA1097 4-5
4.1.3 DIN-rail assembly
Typ
Id.-NR
Fert.-Nr
Se rien-N r.
Eingang1
Eingang2
Lenze
Postfach101352,31763HAMELN
a
e
b
c1
2)
3)
c2
c3
1)
1)
K35.0071
FIG 4-2 Dimensions 8201 - 8204: DIN-rail assembly
1)
8201/8202: Assemblyona DINrail(middle) oron twoDINrails (top andbottom)possible 8203 - 8204: Assemblyontwo DINrails
2)
Observe the free space required for the connection cables
3)
With attachable fieldbus or I/Omodule: Observ eassembly depth and assembly space required for connectioncables
[mm]
a b c1 c2 c3 e
3)
8201 64 188 16 98 149 173 8202 64 188 16 98 149 213 8203 / 8204 83 258 16 - 149 237
Page 22
Installat ion
4-6 820XBA1097
4.2 Electrical installation
4.2.1 Important notes
-
Ensure appropriate activation when using current-operated e.l.c.b.s.
-
Forinformation ontheinstallationaccordingto EMCsee chapter 4.3
-
Prior to assembly and service operations, the personnel must be free of electrostatic charge.
-
Unused controlinputs and outputs should be covered with plugs.
-
Incaseof condensation, connect the controller to the mains voltage only after the visible humidity has evaporated.
-
Please observe the restricitons of each mains type!
Mains Operation of the controller Notes
With grounded neutral Norestrictions O bserve controller ratings
Operation ofseveral820X controllers connected toa mains 3AC/N/PEandsymmetrical distribution to the three outer conductors excepted
-
Observe the load of the shared N-conductor.
- r.m.s. current,seechapter 3.2
-
Possiblyenlarge thecross-section of the N-conductor.
With isolated neutral (IT mains)
Operation with recommended mainsfiltersisnotpossible
-
Mainsfilter will be destroyed if
”earthfault” occurs.
-
Contact Lenze.
With grounded phase Operation onlypossible with one
variant
Contact Lenze
DCsupply via +UG/-UG DCvoltagemustbesymmetrical
toPE
Co ntroller will be destroyed when grounding +U
G-Leiter or -UG-Leiter
Page 23
Installa t ion
820XBA1097 4-7
4.2.2 Power connections
4.2.2.1 Mains connection
-
Connect themainscableswiththescrew terminals L1, L2, L3.
- Tightening torques
Terminals
Type
L1, L2, L3, +UG, -UG PE connection
8201 - 8204 0.5 ... 0.6 Nm (4.4... 5.3 lbin) 3.4 Nm(30lbin)
4.2.2.2 Motor connection
Because of the EMC safety we recommend the use of screened motor cables only.
Screen connection
-
820X: Onthe front FAST-ONconnec tor.
-
Connect themotorcablesto thescrew terminals U, V,W anschließen.
- Observecorrect pole connection.
- Tightening torques
Terminals
Type
U, V, W PEconnection
Screen/
strain relief
T1, T2
8201 ­8204
0.5 ... 0. 6 Nm
(4.4 ... 5.3 lbin)
3.4 Nm
(30 lbin)
- -
-
Switching on the motor side of the controller is permitted
- forsafetyswitch off (emergenc y switch off).
- d uringoperation under load.
Page 24
Installat ion
4-8 820XBA1097
-
Themotorcableshouldbeasshortaspossiblebecauseof thepositiveeffectonthedrivecharacteristic.
- FIG 4-3 shows the relation between motor-cable length and the possible required output filters.
- Forgroup drives (several motorsconnected t o one controller)it is necessary to calculate the resulting cable length l
res
:
IresSum of all motor cable lengthsôNo.ofmotorcables
¯
- When using unscreened motor cables, the data indicated in F I G4-3 arevalid for the double motor-cable length.
- Please contact Lenze when the absolute or resulting motor-cablelengthsar e> 200 m.
Type Permissible control mode C014 8201 8202
-0-,-1-,-2-,-3--2-,-3
-
8203
-0-,-1-
,
-2-,-3-
-2-,-3--2-,-3
-
+ motor filter/
-2-,-3-
+ sine filter
8204
-2-,-3-+motorfilter/+sinefilter
0 15 25 50 100 200
Motor-cablelength (resulting) ,screened in m
FIG4-3 Output filters additionallyrequired inthemotorcable
Page 25
Installa t ion
820XBA1097 4-9
4.2.2.3 Connection diagram
L1
UVW
+UG
-UG
M
3~
PE
RB1 RB2
+UG
-UG
K10
K10
RB
L1
PE
8201... 8204
Z3
N
K10
-X1
N/L2
F1 F2*
PE
Z1
PE
PE
PE
PE
Z2
ϑ
R
B
K10*
K35.0135
F1 Fuse F2* Fuse only for supply with 2AC/ PE/
190-260V K10 Mains contactor K10* Mains contactor only for supply
with 2AC / PE/ 190-260V Z1 Mains filter/mains choke, see
Accessories Z2 Motor filter/sinefilter, see
Accessories Z3 Brakechopper/brake module, see
Accessories R B Brake resistor, see Accessories
J
RB
Temperature monitoring - brake
resistor X1 Terminal strip in control cabinet
8204 operation only with assigned mains choke/mains filter
FI G4-4 820Xpower connections
Page 26
Installat ion
4-10 820XBA1097
4.2.3 Control connections
4.2.3.1 Control cables
-
We recommend the unilateral screening of all cables for analogsignals to avoid signald istortion.
-
Connect the screens of the control cables as follows:
-820X: On the front FAST-ON connector.
-
If the control cables are interrupted (terminal strips, relays) , the screens must be reconnected over the shortest possible distance.
-
Connnect the fixing screw of the setpoint potentiometer to PE.
4.2.3.2 Assignment of the control terminals
K35.0026
62 7 8 9 K11 K12 K14
20 28 E1 E2 E3 E4 39
FIG 4-5 Positionof the control terminals
Page 27
Installa t ion
820XBA1097 4-11
Terminal Use
(Factory setting is printed in bold)
Level Data
Analog
7 GND 1
inputs
8 Setpoint input,
reference: Terminal 7
(0 to 10V)
6 4 2
5
3
1
5-6 5-6 3-4
1-2
0to20mA 4to20mA 0to5V 0to10V
Resolution: 9 bit Linearity fault:
0.5 %
Temperature fault:0.3 % (0 ...+40
C)
Input resistance
Jumper
Voltagesignal:>100k
C urrent signal: 250
9 Supply for setpoint potentiometer 5.2V/ 6mA
Analog output
62 Analog output, reference: terminal 7
(Fiel d frequency)
0...6 V/ 2mAResolution: 8 bit
Digital inputs
20 Voltage supply for digital inputs
12 V/20 mA
input
s
28 Controller enable HIGH
HIGH:12V...30V
E4 CW rotation/
CCW rotation (CW/CCW)
CW: LOW CCW: HIGH
HIGH:12V...30
V
LOW : 0 V... 3 V
E3 DC-injection brake HIG H E2
JOG frequencies
Binarycode
E1
JOGfrequencie
s
20Hz, 30Hz, 40Hz
Binarycod
e
39 GN D2 (reference for external voltages)
Terminal Use
(Factory setting is printed in bold)
Relay position (switched)
Data
Relay output
K11 Rela youtput normally-closed contact
(TRIP)
opened
24 VAC/ 3,0 Aor 60 VDC/ 0.5 A
outpu
t
K1
K22 Relaymid-positioncontact
60VDC/0.5
A
K24 Rela youtput normally-open contact
(TRIP)
closed
Page 28
Installat ion
4-12 820XBA1097
4.2.3.3 Connection diagrams
62
78
9
K11 K12
K14
3k
3k3k
3k3k
Vcc
GND 2
K1
GND 1
5,2V
Vref
3k3
>100k
82XX
R ≥ 1k
2028E1E2E3 E4
39
PE
K35.0077-3
FIG 4-6 Controlconnections: Supply with internalcontrol voltage
62 789
K11 K12 K14
3k
3k3k3k
3k
Vcc
GND 2
GND 1
5,2V
Vref
3k3
>100k
12...30V
82XX
R ≥ 1k
+
-
20 28 E1 E2 E3 E4 39
PE
K1
K35.0077-4
FIG 4-7 Controlconnections: External voltage supply (+12 V... +30 V)
G N D1 Reference for internal voltages G N D2 Reference for external voltages
G N D 1 and GN D 2 havea potential isolation inside the unit.
Page 29
Installa t ion
820XBA1097 4-13
4.3 Installation of a CE-typical drive system
General notes
-
The user is responsible for the compliance of his application with the EC directives.
- If youobserve the following measure you can be sure that thedrive system will not causeany EMC problems, i.e. complywith theEMCDirective when running the machine.
- If devices which do notcomplywiththeCErequirementconcerningnoiseimmunityEN 50082- 2 areoperated closeto the controller,thesedevicesmaybe interfered electromagneticallybythe controllers.
Assembly
-
Connect controller, mains choke, and mains filter to the grounded mounting platewith a wire of largea cross-section as possible:
- Mountingplates with conductive surfaces (zinc-coated, stainlesssteel) allow permanent contact.
- Varnished boards should not be used for installation in accordance with EMC
-
If youuse several mounting plates:
- Conne ct as much surfaceas possible of the mounting plates(e.g. with copper bands).
-
E nsure the separation of motor cable and signal or mains cable.
-
Donot use the same terminal strip for mains input and motor output.
-
Cable guides as close as possible to the reference potential. Unguided cables havethe same effect as aerials.
Filters
-
Use mains filters or RFIfilters and mains chokes which are assigned to thecontroller:
- RFI filters reduce impermissible high-frequency interference to a permissible value.
- Mains chokes reduce low-frequency interferences which depend on the motor cable and its length.
- Mains filters combine the functions of mains choke and R FI filter.
Page 30
Installat ion
4-14 820XBA1097
Screening-Connect the screen of the motor cable with the controller
- tothe screen connection of the controller.
- additionallyto themounting platewith a surfaceaslargeas possible.
- Re co mmendation: For the connection, use ground clampson bare metal mounting surfaces.
-
If contactors, motor-protecting switches or terminals are located in the motor cable:
- Connect the screens of theconnected cables also to the mounting plate, with a surfaceas large as possible.
-
Connect the screen to PE, with a surface as large as possible.
- Metal glands at the motor terminal boxensure a connection of the screen and the motor housing.
-
If the mains cable between mains filter and controller is longer than 300 mm:
- Screen mains cables.
- Connect the screen of themains cable directlytothe inverter and to the mains filter and connect it to the mounting platewith as largea surfaceaspossible.
-
Use of a brake chopper:
- Connect the screen of thebrake resistor cabledirectlyto the mounting plate, at the brake chopper and the brake resistor with as large a surfaceas possible.
- Connect the screen of thecable between controller and brake chopper directlyto the mounting plate, at the inverter and the brake chopper with a surface as large as possible.
-
Screen the control cables:
- Connect both screen ends of the digital control cables.
- Connect one screen end of the analog control cables.
- Alwaysconnect thescreens to the screenconnection at thecontroller over theshortest possible distance.
-
Application ofthecontrollers 821X/822X/ 824Xinresidentialareas:
- Use an additional screen damping
10 dB to limit the radiointerference. Thisis usually
achievedby installation in enclosed and grounded control cabinetsmade of metal.
Grounding-Ground all conductivemetal components (controller, mains filter, motor filter,mains choke)using
suitable cables connected to a central point (PEbar).
-
Maintain the minimum cross-sections prescribed in the safety regulations:
- For EMC, not the cable cross-section isimportant, but the surface and the contact with a cross-section as large as possible, i.e. large surface.
Page 31
Installa t ion
820XBA1097 4-15
Lx
UVW
M
3~
PE
RB1 RB2+UG
-UG
RB
Netz
PE
82XX
K10
Z3
Z2
PE
PE
Z1
PE
n
PE
789
GND 1
GND 2
PE
Vref
Vcc
-UG
+UG
F1
-X1
n
n
n
n
K1
62
K11
K12 K14
2028E1
E2
E3
E4 39
PES
PES
PES
PES PES
PES
PES
PES
PES
PE
PE
n
n
PES
PES
K35.0082
FIG4-8 Exampleforaninstallation in accordancewiththeEMCregulations:
F1 Fuse K10 Mains contactor Z1 Mainsfilter ”A” or ”B”, see Accessories
Z2 Motorfilter/sine filter, seeAccessories Z3 Brake module/brake chopper, see Accessories
-X1 Terminalstrip in controlcabinet R B Brake resistor PES HFscreen because of aPEconnectionwith a surfaceas large as possible
(see ”Screening” in this chapter)
n Number of phases
Page 32
Installat ion
4-16 820XBA1097
Page 33
Commissioning
820XBA1097 5-1
5 Commissioning
The controllers are factory-set to drive a corresponding four-pole standard motor with 230/400V, 50Hz. Further settings are not necessary.
Onlyafewsettingsviathe8201 BB operatingmoduleorafieldbus module arenecessary to adapt your driveto your application. The steps required are summarized in chapter 5.3 and in chapter 5.4.
5.1 Before you switch on
Prior to i nitial switch-on of the controller, check the wiring for completeness,short-c ircuit,and earthfault:
-
Power connection:
- ViaterminalsL1/N - 820X.
- Alternatively via terminals +UG, -UG (DC-group drive)
-
Control terminals:
- Reference potential for the control terminals is terminal 39.
- Controller enable: terminal 28
- Selection of directio n ofrotation: terminal E3 or E4
- External setpoint selection: terminals 8, 9
- Checkjumperposition! Factpr settomg: 0 - 10V (see page 4-10).
- During operation with an internal voltage supply via terminal 20, brid e theterminals 7 and 39.
Page 34
Commissioning
5-2 820XBA1097
-
Incaseof condensation connect thecontrollerto mains voltage only after the visible humidity has evaporated.
-
The plug-inpower terminalsof the 820Xcontroller must only be connected or disconnected when no voltage is applied.
Maintain the switch-on sequence!
5.2 Short set- up (Factory setting)
5.2.1 Switch-on sequence
Step
1.Switchon mains voltage
2.Select the direction of rotation.
-
CW rotation:
- Applya LOWsignal to terminalE4 (0...+3V).
-
CCW rotation:
- Applya HI GH signal to terminal E4 (+12...+30V).
3.Select the setpoint. Applya voltage0...+10 Vto terminal 8.
4.E nable the controller . Applya HIGHsignal (+12...+30 V)to terminal 2 8 .
5.Thedrive is now operating accordingto factory setting.
Page 35
Commissioning
820XBA1097 5-3
5.2.2 Fact ory setting of the most imp ortant drive parameters
Setting Code Factory setting Adaption to
the application
Operating mode C001 -0- Setpoint selection viat erminal 8
Control viaterminals Parameter settingvia 8201BB
See code table, chapter 7.2
Terminal configuration C007 -0- E4 E3 E2 E1
CW/CCWDC injection brakeJOG1/2/3
See code table, chapter 7.2
Machine data Chapter 5.3 ff. Speed range
Min. field frequency C010 0.0 Hz
Chapter 5.3 .1
Max. field frequency
C011 50.0 Hz
Acceleration and
Accelerationtime C012 5.0 s
Chapter 5.3 .2
and
deceleration times
Deceleration time C013 5.0 s
Current limit values
Motormode C022 150 %
Chapter 5.3 .3
value
s
Generator mode C023 80 %
Drive performance Chapter 5.4 ff. Current,
torque,
Operating mode C014 -0- Linear characteristic Vfdwithauto
boost
V/f characteristic
power
characteristic
V/f rated frequency C015 50.0 Hz
control
-
withauto boost, see
V
min
setting C016 type
dependent
chapter
5.4.1.1
-
with V
min
Slip compensation C021 0%
withV
min
boost, see chapter
5.4.1.2
Page 36
Commissioning
5-4 820XBA1097
5.3 Adapt machine data
5.3.1 Determine speed range (f
dmin,fdmax)
Code Name
Possible settings
IMPORTANT
Lenze Selection Info
C010 Minimum field
frequency
0.0 0.0 {0.1Hz} 480.0
C011 Maximum field
frequency
50.0 30.0 {0.1Hz} 480.0
Function Thespeed rangerequired for theapplicationcan be selected here by determing the
field frequencies f
dmin
and f
dmax
:
-
f
dmin
corresponds to the speed at 0 % speed setpoint selection.
-
f
dmax
corresponds to the speed at 100 % speed setpoint selection.
Adjustment Relation between field frequencyand synchronous motor speed:
n
rsyn
f
dmax
ô
60
p
n
rsyn
synchronous motor speed [min-1]
f
dmax
max. field frequency[Hz]
p numberof pole pairs
E x ample: 4 pole asynchronous motor:
p=2,f
dmax
=50Hz
n
rsyn
50ô60
2
1500min
–1
Page 37
Commissioning
820XBA1097 5-5
Important
-
With the setting of f
dmin>fdmax
the field frequency is limited to f
dmax
.
-
When selecting the setpoint by means of JOGvalues, f
dmax
acts as limitation.
-
f
dmax
is an internal standardization variable:
- Use the LECOM interfaceonlyfor important modifications, when t he controller is inhibited.
-
Observe the maximum motor speed!
-
f
dmin
is only effectiveunder the following conditions:
- With analog setpoint selection.
- With the motor potentiometer function ”DOWN”.
Special features
-
With field frequencies fd>240Hz:
- Theovercurrentswitch-offcan be activated.
fd
C011 (fdmax)
C010 (fdmin)
0 % 100 %
K35.0062
Page 38
Commissioning
5-6 820XBA1097
5.3.2 Adjustment of acceleration and deceleration times (T
ir
,Tif)
Code Name Possible settings IMPORTANT
Lenze Selection Info
C012 Acceleration time 5.0 0.0 {0.1s} 999.0 T
ir
C013 Deceleration time 5.0 0.0 {0.1s} 999.0 T
if
Function Theaccleration and deceleration timesdetermine thetime required by the drive to
follow a setpoint change.
Adjustment
-
Theacceleration and deceleration times refer to a change of the field frequency from 0 Hzto themax. field frequencyset under C 011.
-
C alculate thetimes Tirand Tif, which must be set under C012 andC013.
-t
ir
and tifare the times required for thechange between fd1and fd2:
T
ir
t
ir
ô
f
dmax
f
d2
f
d1
T
if
t
if
ô
f
dmax
f
d2
f
d1
Important U nder unfavourable operating conditions, too short acceleration and deceleration
times can lead to the deactivationof the controller under overloadwith theindication of TRI POC5. In these events, the acceleration and deceleration times should be set short enough so that the drive can follow the speed profile without reaching I
max
of the
controller.
Special features
Theslopecanbeset between 0.095Hz/ s and 780Hz/s.
f /Hz
d
f
dmax
d2
f
f
d1
0
t
ir
t
if
T
ir
T
if
t
K35.0063
Page 39
Commissioning
820XBA1097 5-7
5.3.3 Setting of the current limit (I
max
)
Code Name Possibl e settings IMPORTANT
Lenze Selection Info
C022 I
max
limit
motor m ode
150 30 {1 %} 150
C023 I
max
limit
generator mode
80 30 {1%} 110
Function Thecontrollers are equipped with a current-limit control which determinesthe
dynamic responseunder load. Themeasured load is comparedwith the limit values set under C022 for motor load and under C023 for generator load.If the current-limit values are exceeded, the controller will change its dynamic response.
Adjustment The acceleration and decleration time should be set short enough so that the drive can
follow the speed profile without reaching I
max
of the controller.
Drive characteristic when reaching the limit value
-
During acceleration:
- Expansion of the acceleration ramp.
-
During deceleration:
- Expansion of the deceleration ramp.
-
When the load increases at constant speed:
- When themotor-current limit value is reached: Reductionof thefield frequencyto 10H z.
- When thegenerator-current limit value is reached:
Increasethe field frequencyto the maximum frequency(C011).
- Stop thefield-frequency change if the load falls below thelimit value.
Page 40
Commissioning
5-8 820XBA1097
5.4 Optimisation of the operating characteristic of the drive
By means of the following settings you can influence the current, torque and power characteristic or the connected motor.
You can choose between the control modes ”V/f-characteristic
control with auto boost” and ”V/f-characteristic control with constant V
min
boost”. In chapter 5.4.1 you will find some more
information to help you with the selection.
5.4.1 Select the control mode
Code Name Possible settings IMPORTANT
Lenze Selection Info
C014§Operating mode -0- -0- Linear characteristic Vfdwith
auto boost
-1- Square characteristic V
f
d
2
with auto boost
-2- Linear characteristic V
fdwith
constant V
min
boost
-3- Square characteristic V
f
d
2
with constant V
min
boost
Control modesofthe voltage characteristic
Function
-
Under C014 youcan set the control modeand the voltage characteristic.
-
TheV/f-characteristic control with auto boost enables a low-loss operation of single driveswith standard three-phase ACmotors with load-dependent V
min
boost.
Page 41
Commissioning
820XBA1097 5-9
C014 = - 0­Linear characteristic
C014 = - 1­Square-law characteristic (e. g. for pumps,
fans)
K35.0064
100%
0
01
f
d
f
dN
V
min
0
01
f
d
f
dN
V
min
Vout
100%
Vout
A u to b o o s t
A u to b o o s t
C014 = - 2­Linear characteristic
C014 = - 3­Square-law characteristic (e. g. for pumps, fans)
K35.0065
100%
0
01
f
d
f
dN
V
min
0
0
1
f
d
f
d
N
V
min
V out
100%
V out
Page 42
Commissioning
5-10 820XBA1097
Help f or decision Motor cable
screened$25 m
unscreened
$
50 m
screened > 25 m
unscreened > 5 0 m
C014
Single drives
recommended alternatively recommended alternatively
Withconstant load -0- -2- -2- ­With changing loads -0- -2- -2- ­Withheavy start conditions -0- -2- -2- ­Highdynamic posotioning and feed drives -0- - -2- ­Lifts and hoists -0- -2- -2- ­Pumps and fan drives -1- -3- -3- -2­Three-phase reluctance motors -2- - -2- ­Three-phase sliding rotor motors -2- - -2- ­Three-phase motorswith assigned
frequency-voltage characteristic
-2- - -2- -
Group drives (depending on the resulting motor-cable length)
l
res
i
¯
ô
(l
1
l
2
ööö
li)
Simitas motors and loads -2- - -2- ­Different motors and/or changingloads -2- - -2- -
Page 43
Commissioning
820XBA1097 5-11
5.4.1.1 Optimisation of V/f-characteristic control with auto boost
Codes required
Code Name Possibl e settings IMPORTANT
Lenze Selection Info
C015
V/ f-rated frequency
50.0 30.0 {0.1Hz} 960.0
C016
V
min
setting * 0{1%}40 * type dependent
C021
Slip compensation
0 0{1%}12
Setting sequence
1.If necessary, select V/f characteristic (C014).
2. Select V/ f- rated frequency(C015).
-
TheV/f-rated frequencydetermines the slope of the V/f characteristic and has considerable influence on the current, torque and power performance of the motor.
-
An internal mains voltage compensation compensates deviations in the mains during operation. Theytherefore do not haveto be considered for the setting of C015.
Adjustment
Calculatethe frequencyto be set under C015 C015[Hz]
230V
V
ratedmotor
[V]
ô
rated motor frequency[Hz ]
C014 = - 0­Linear characteristic
C014 = - 1­Square-law characteristic (e. g. for pumps, fans)
K35.0064
100%
0
01
f
d
f
dN
V
min
0
01
f
d
f
dN
V
min
Vout
100%
Vout
A u to b o o s t
A u to b o o s t
Page 44
Commissioning
5-12 820XBA1097
3.Set theVmin boost (C016).
Loa d-dependentboost of the motor voltage in thefield-frequencyrangebelow the V/f-rated frequency. C016 acts as gain factor of the auto-boost function.
Adjustment
Ingeneral, an adjustment is not necessary. An optimisation canbe advantageous:
For drives with very high starting torques:
A Operate the motor under load. B Select the frequencysetpoint. C Increase V
min
until the required motor current (torque) occurs.
Too high settings of V
min
can lead to a positive-feedback effect which activates the
TRIP”Overcurrent” (OCx).
For drives wi th square load torques (fans, pumps):
A Operate the motor under load. B Select the frequencysetpoint. C Adapt V
min
until themotor isrunning steadilyand smoothly over thewhole fre­quencyrange. Too high settings of V
min
can activate the TRIP”Overcurrent” (OC x )and lead to an
extensivemotor temperature.
For drives with special motors:
A Operate the motor under load. B Select the frequencysetpoint. C Increase V
min
until the required motor current (torque) occurs.
Too high settings of V
min
can lead to a positive-feedback effect which activates the
TRIP ”Overcurrent” (OCx).
D Check thecurrent consumption during idle-running when no load is applied
4.Set slip compensation
Rough setting by means of the motor data:
4.Setslipcompensation
(C021).
s
n
rsyn
n
r
n
rsyn
ô
100%
n
rsyn
f
dr
ô
60
p
s Slip constant (C021) n
rsyn
synchronous motor speed [min-1]
n
r
rated speed to motor nameplate [min-1]
f
dr
rated frequency tomotornameplate [Hz]
p Number of pole pairs
Precise setting:
C hange C021 under constant load until the speed is near thesynchronous speed. If C021 is set to too high values, the drive maybecome instable (overcompensation).
Page 45
Commissioning
820XBA1097 5-13
5.4.1.2 Optimisation of V/f-characteristic control
Codes required
Code Name Possibl e settings IMPORTANT
Lenze Selection Info
C015
V/ f-rated frequency
50.0 30.0 {0.1Hz} 960.0
C016
V
min
setting * 0{1%}40 * type dependent
C021
Slip compensation
0 0{1%}12
Setting sequence
1.If necessary, select V/f characteristic (C014).
2. Select V/ f- rated frequency(C015).
-
TheV/f-rated frequencydetermines the slope of the V/f characteristic and has considerable influence on the current, torque and power performance of the motor.
-
An internal mains voltage compensation compensates deviations in the mains during operation. Theytherefore do not haveto be considered for the setting of C015.
Adjustment
Calculatethe frequencyto be set under C015 C015[Hz]
230V
V
ratedmotor
[V]
ô
rated motor frequency [Hz]
C014 = - 2­Linear characteristic
C014 = - 3­Square-law characteristic (e. g. for pumps, fans)
K35.0065
100%
0
01
f
d
f
dN
V
min
0
0
1
f
d
f
d
N
V
min
V out
100%
V out
Page 46
Commissioning
5-14 820XBA1097
3.Set theVmin boost (C016).
-
Load-independentboost of the motor voltagefor field frequencies below the U/f-rated frequency. You can thus optimizethe torque performance of theinverter drive.
-
It is absolutely necessary to adapt the asynchronous motor used, since otherwise, the motor can be destroyed byovertemperatue:
Adjustment
Please note the thermal characteristic of theconnected motor under small field frequencies:
-
Usually, standard asynchronous motors with insulation classB can be operated for a short time with rated current and frequencies between 0Hz
$
f
d
$
25Hz.
-
Please ask the motor manufacturer for the exact setting values for the motor current.
A Operate the motor in idle running with a slip frequencyof f
d
:
-P
mot
$
7.5 kW: f
d
5Hz
-P
mot
7.5 kW: f
d
2Hz
B Increase V
min
until you reachthe following motor current:
- Motor in short-term operation at 0Hz
$
f
d
$
25Hz:
with self-ventilated motors: I
motor
$
I
N motor
with forced-ventilated motors: I
motor
$
I
Nmotor
- Motor in permanent operation at 0Hz$f
d
$
25Hz:
with self-ventilated motors I
motor
$
0.8kI
N motor
with forced-ventilated motors: I
motor
$
I
Nmotor
4.Set slip compensation
Rough setting by means of the motor data:
4.Setslipcompensation
(C021).
s
n
rsyn
n
r
n
rsyn
ô
100%
n
rsyn
f
dr
ô
60
p
s Slip constant (C 021) n
rsyn
synchronous motor speed [min-1]
n
r
rated speed to motornameplate[min-1]
f
dr
rated frequencytomotor nameplate [Hz]
p Number of pole pairs
Precise setting:
C hange C021 under constant load until the speed is near thesynchronous speed. If C021 is set to too high values, the drive maybecome instable (overcompensation).
Page 47
During operation
820XBA1097 6-1
6 During operation
-
Replace defective fuses with the prescribed type only when no voltage is applied. Thereare no fuses in the controller .
-
Cyclic mains switching:
- Do not switch on thecontroller morethan every3 minut es, otherwise the internal initial-current limitation can be overloaded.
-
Switching on the motor side:
- Permissible for emergency switch-off.
- Monitoringmessages canbe activated whenswitching the motorwhenthecontrollerisenabled.
-
Theplug-in connection terminals of the 820Xcontrollers must only be connected or disconnected when no voltage is applied.
-
Depending on the controller settings, the connected motor can beoverheated:
- For instance, longer DC-braking operations.
- Longer operationof self-ventilated motors atlow speed.
-
Thecontrollers generate an output frequency of up to 480 Hz when setting it correspondingly:
- If an inappropriate motor is connected, a hazardous overspeed may occur.
- With frequencies>240 Hz,820Xc o ntrollerscanactivate the over-curre n t switch-off.
Page 48
During operation
6-2 820XBA1097
-
If youuse thefunctionCW/CCW(selectionof the direction of rotation)withtheconfiguration C007 = -0- t o -13-:
- Thedrivecanreversethedirectionofrotationintheevent ofa control-voltage failureor a cable b reak.
-
If youuse thefunction”Flying-restartcircuit” (C142 = -2-, -3- ) with machines with low inertia torque and friction:
- The motor can start for a short time or reverse the direction of rotation for a short time after enabling the controller when the motor is in standstill.
Page 49
Configuration
820XBA1097 7-1
7 Configuration
7.1 Basics
-
The configurationof the c ontroller is used to adap t t he drive to your applications.
-
F or this, you have the following functions available:
- Operating functions
- Cont rol function
- Display functions
- Monitoringfunctions
-
Thepossible function settings areorganized in codes:
- Codes are numerically sorted, starting from the code with the smallest number to the one with the highest number. All codes start w itha”C”.
- They are listed in the code table.
- Each code provides parameters which can be used to adjust and optimize your drive.
-
The configurationof the c ontroller canb e entered by means of the keypad of the8201BB operating moduleor bymeans ofafieldbusviatheserialinterface.
- The operating module and fieldbus modules are available as accessories.
-
The changing of parameters by means of the operating moduleor fieldbusmodules is described
- in the Operating Instructions of the modules.
- in the Manual.
-
Allfunctions of the controllerare described shortly in the code table. Adetailed description can be obtained from the Manual.
Page 50
Configuration
7-2 820XBA1097
7.2 Code table
How to read the code table:
Column Abbreviation Meaning
Code C013 CodeC013
-
The parameter of the code can be different in P A R1 and PAR2.
-
The parameter value is accepted immediately(ON LINE) .
C009*
-
The parameter value of the code is always the same in PAR1andPAR2,butisalwaysdisplayedinPAR1.
C001
§
-
The parameter value of the code will be accepted after pressing SH+PRG.
[C002]
-
The parameter value of the code will be accepted after pressing SH+PRGbut only if the controller is inhibited.
Name
820X
Name of the code. Unit- specific settingpossibilites (here for 820X). Without unit designation the code is valid for all unit types.
Lenze Factory setting of the code
* The column ”Important” contains furtherinformation
Selection 1{1%}99Minimum value {smallest step/unit} maximum value Info - Meaning of the code IMPOR TANT - Additional, important explanations of the code
Page 51
Configuration
820XBA1097 7-3
Code Name
Possible set tings
IMPORTANT
CodeNam
e
Lenze Selection Info
IMPORTANT
C001§Operating mode -0- -0- Setpoint selection via term. 8
Control viaterminals Parameter settingvia 8201BB
-1- Setpoint selection via 8201BB or via LE C OM Control viaterminals Parameter settingvia 8201BB
-2- Setpoint selection via term. 8 Control viaterminals Parameter settingviaLECOM
-3- Setpoint selection via LECOM Control via LE COM Parameter settingviaLECOM
[C002]*Parameter set -0- Function executed
-1- Overwrite PAR1 withfactorysetting
-2- Overwrite PAR2 withfactorysetting
-3 - Overwrite PAR1 and PAR2 with the data of the operating module
-4- Overwrite PAR1 withthedataof the operating module
-5- Overwrite PAR2 withthedataof the operating module
-6- Transmit PAR1 and PAR2 to the operating module
C004§Switch-on
display
-0- -0- Fieldfrequencyf
d
-1- Controller load
-2- Motor current
Page 52
Configuration
7-4 820XBA1097
Code IMPORTANTPossible set tingsNameCode IMPORTANT
InfoSelectionLenze
Name
[C007]*Term inal
configuration
-0- E4 E3 E2 E1
-0- CW/CCWD Cbrake JOG 1/2/3
-1- CW/CCWPAR JOG1/2/3
-2- CW/CCWQSP JOG1/2/3
-3- CW/CCWPAR DCbrake JOG1
-4- CW/CCWQSP PAR JOG1
-5- CW/CCWD Cbrake Trip set JOG1
-6- CW/CCWPAR Tripset JOG1
-7- CW/CCWPAR DCbrake Trip set
-8- CW/CCWQSP PAR Trip set
-9- CW/CCWQSP Tripset JOG1
-10- CW/CCWTripset UP DOWN
-11- CW/CCWDC brake UP DOWN
-12- CW/CCWPAR UP DOWN
-13- CW/CCWQSP UP DOWN
-14- CCW/QSPCW/QSPDC brake JOG1
-15- CCW/QSPCW/QSP PAR JOG1
-16- CCW/QSPCW/QSPJOG1/2/3
-17- CCW/QSPCW/QSP PAR
DC brake
-18- CCW/QSPCW/QSP PAR Tripset
-19- CCW/QSPCW/QSPDC brake Tripset
-20- CCW/QSPCW/QSPTrip set JOG1
-21- CCW/QSPCW/QSP UP DOWN
-22- CCW/QSPCW/QSP UP JOG1
-
CW = CW rotation
-
CCW = CCW rotation
-
DC brake = DC injection brake
-
PAR =
Changeof parameter sets
-
JOG= JOG frequency
-
QSP = Quick stop
-
Trip-Set = External fault
-
UP/DOWN = Motor potentiomet er functions
C008§Functionrelay
K1
-1- -0- Ready for operation
-1- TRIPfault message
-2- Motor is running
-3- Motor is running / CWrotation
-4- Motor is running / CCW rotation
-5- Field frequencyf
d
=0
-6- f
dset
reached
-7- Q
min
reached
-8- I
max
reached
-9- Overtemperature (
J
max
-10C)
-10- TRIPorQ
min
or IMP
Page 53
Configuration
820XBA1097 7-5
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C009* Deviceaddress 1 1{1} 99 Only for
LE COM applications
C010 Minimumfield
frequency
0.0 0.0 {0.1Hz} 480.0
C011 Maximum field
frequency
820X 50.0 30.0 {0.1Hz} 480.0 821X 50.0 7.5 {0.1Hz} 480.0
30.0 {0.1Hz} 480.0
(Software2x) (Software1x)
822X/824X 50.0 7.5 {0.1Hz} 480.0
C012 Acceleration
time
5.0 0.0 {0.1s} 999.0
C013 Deceleration
time
5.0 0.0 {0.1s} 999.0
C014§Operating mode
820X -0- -0- Linear characteristic Vfdwithauto
boost
-1- Square characteristic V
f
d
2
withauto
boost
-2- Linear characteristic Vfdwithconstant V
min
boost
-3- Square characteristic V
f
d
2
with
constant V
min
boost
821X/822X
/ 824X
-4- -4- Motor-current control
C015
V/ f-rated frequency
820X 50.0 30.0 {0.1Hz} 960.0 821X 50.0 7.5 {0.1Hz} 960.0
30.0 {0.1Hz} 960.0
(Software2x) (Software1x)
822X/824X 50.0 7.5 {0.1Hz} 960.0
Page 54
Configuration
7-6 820XBA1097
Code IMPORTANTPossible set tingsNameCode IMPORT ANT
InfoSelectionLenze
Name
C016
V
min
setting
C01
6
820X * 0{1%} 40 * depends on
the unit
821X/822X
/824X
0 0{1%} 40
C017 Threshold Q
min
0.0 0.0 {0.1Hz} 480.0
C018
§
Chopper frequency
§
821X/822X/824X-1- -0- 4 kHz
-1- 8kHz
-2- 12kHz
-3- 16kHz
-4- 12 kHznoise optimized
-5- 16 kHznoise optimized
C019
Threshold auto DC brake
821X/822X/824X0.1 0.1 {0.1Hz} 5.0
C021
Slip compensation
820X 0 0{1%} 12 821X 0 0{1%} 20
0{1%} 12
(Software2 x) (Software1 x)
822X/824X 0 0{1%} 20
C022 I
max
limit motor
mode
150 30 {1 %} 150
C023 I
max
limit
generator mode
80 30 {1 %} 110
C034§Master current -0- - 0- 0 to20mA /
0to5V/0to10V
-1- 4 to 20mA
C036 V oltage for DC
brake
* 0{1%} 40 * depends on
the unit
C037 JOGvalue1 20 0 {1Hz} 480
Page 55
Configuration
820XBA1097 7-7
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C038 JOGvalue 2 30 0 {1Hz} 480 C039 JOGvalue 3 40 0 {1Hz} 480
C050* Output
frequency
Only display
C052* Motor voltage Only display C054* Motor current Only display C056* Controller load Only display C061* Heat sink
temperature
Only display
C079
Oscillation damping
Is not transferred when transferring
822X/824X 5 0{1} 80
t
r
a
n
s
f
e
r
r
i
n
g
parameters via the operating module.
C088 R ated motor
current
821X/822X/824
X
*
0.0 ... 1.2krated output current
* depends on the unit
C091 Motor cos
j
821X/822X/824
X
*
0.4 {0.1} 1.0
* depends on the unit
C093*
Type Only display
820X 820X 821X 821X
822X/824X 822X
Page 56
Configuration
7-8 820XBA1097
Code IMPORTANTPossible set tingsNameCode IMPORT ANT
InfoSelectionLenze
Name
C099*
Software version Onlydisplay
820X 82 1x(Software 1x) 821X 82 2x(Software 2x)
82 1x(Software1x)
822X/824X 82 1x(Software1x)
C105 Deceleration
time quick stop
821X/822X/824
X
5.00 0.00 {0.01s} 999.00
C106
Holding time for autom. DC injection brake
820X 0.00 0.00 {0.01s} 50.00
821X/822X
824X
0.02 0.00 {0.01s} 999.00
C108*
Gain(C111)
820X 220 0 {1} 255 821X 128 0 {1} 255
822X/824X 128 0 {1} 255
C111
§
Monitor signal -0- -0- Field frequency
-1- Controller load
-2- Motor current
-3- DC-bus voltage
Page 57
Configuration
820XBA1097 7-9
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoSelectionLenze
Name
C117§Functionrelay
K2
822X/824X
-0- -0- Readyfor operation
-1- TRIPfault message
-2- Motor isrunning
-3- Motor isrunning / CWrotation
-4- Motor isrunning / CCW rotation
-5- Field frequency f
d
=0
-6- f
dSet
reached
-7- Q
min
reached
-8- I
max
reached
-9- Overtemperature (
J
max
-10C)
-10- TRIPorQ
min
or IMP
-11- PTC warning
C119§FunctionPTC
822X/824X
-0- -0- PTC input inactive
-1- PTCinput active, TRIPand IMP (pulse inhibit) are set
-2- PTCinput active, warning
C120
I
2
k
t switchoff
822X/824X 0 0{1%} 100
C125
§
*
LE COM baud rate
-0- -0- 9600 baud
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
-4- 19200 baud
Only for LE COM applications
C142§Start condition -1- -0- Automatic start inhibited, flying-restart
circuit inactive
-1- Automatic start, if term. 28 HIGH, flying-restart circuit not active
-2- Automatic start inhibited, flying-restart circuit active
-3- Automatic start, if term. 28 HIGH, flying-restart circuit active
Page 58
Configuration
7-10 820XBA1097
Code IMPORTANTPossible set tingsNameCode IMPORT ANT
InfoSelectionLenze
Name
C144
§
Chopper-frequency reduction
§
821X/822X/824X-1- -0- Nochopper-frequency reduction
-1- Automatic chopper-frequency lowering when
J
max
-10C
C161* Current fault Onlydisplay C162* Last fault Onlydisplay C163* Last but one
fault
Onlydisplay
C164* Last but two
fault
Onlydisplay
C170§TRIP-reset
selection
-0- TRIP-resetby pressingthe STPkeyor LOWsignal at ctrl. enable
-1- Auto-TRI P-Reset
C171 Delay for
Auto-TRIP-Reset
0 0{1s} 60
C178* O perating time Only display C179* Mainsswitch-on
time
Onlydisplay
C377 Gain Zk-voltage
detection
822X/824X
Should only be changed by the Lenze Service!
C500*
Display factor application datum numerator
821X/822X/824X2000 1 {1} 25000
C501*
Display factor forprocess variable denominator
821X/822X/824X10 1 {1} 25000
Page 59
Troubleshootin g and fault el imination
820XBA1097 8-1
8 Troubleshooting and fault elimination
-
Faults are immediately indicated via the display or status information ( chapter 8.1) .
-
The fault can be analysed by using the history buffer ( chapter
8.2)and thelist inc hapter8.3. The list helps youwith the elimination of faults.
8.1 Troubleshooting
8.1.1 Display at the controller
During operationwithout an operatingmodule, theoperating state ofthe c ontroller isdisplayed on two LEDsatthe front of theunit.
LED Operating status green red
on off C ontroller enabled on on Mains switched on and automatic start inhibited (AS_LC) blinking off Controller inhibited off blinking everysecond Fault message, check under C161 off blinking every0.4 seconds Undervoltageswitch-off off off Programmingmode
8.1.2 Display at the operating module
Status indications in the display indicate the controller status.
Display Meaning
OV Overvoltage UV Undervoltage IMAX Set current limit exceeded TEMP Heat sink temperature near switch-off
Page 60
Troubleshooting and fault elimination
8-2 820XBA1097
8.1.3 Maloperationofthedrive
Maloperation Possiblecauses Motordoesnotrotate
-
DC-busvoltagetoolow (redLEDisblinkingevery0.4s;messageLUisdisplayed)
-
Controllerinhibited (greenLEDisblinking,displayoftheoperatingmodule:OFF, STOPorAS_LC)
-
Setpoint=0
-
DCbrakingactive
-
Quick-stopfunctionactive
-
JOGsetpointactivatedandJOGfrequency=0
-
Faultisindicated(seechapter8.3)
-
Mechanicalmotorbrakeisnotreleased
Motordoesnotrotate smoothly
-
Defectivemotorcable
-
MaximumcurrentC022andC023toolow
-
Motorunderexcitedoroverexcited(checkparametersetting)
Currentconsumptionof motortoohigh
-
SettingofC016toohigh
-
SettingofC015toolow
-
C088andC091arenotadaptedtothemotordata.
8.2Faultanalysisusingthehistorybuffer
Thehistorybufferisusedtotracefaults.Thefaultmessagesare storedinthehistorybufferintheorderoftheiroccurrence.
Thehistorybufferhas4memorylocationswhichcanbeaddressed viacodes.
Structureofthehistorybuffer
Code C0168 Entry Note
C161 Memorylocations1 Activefault
Ifthefaultisnolongeractiveorhasbeen acknowledged:
C162 Memorylocation2 Lastfault
acknowledged:
-
Thecontentsofthememorylocations1-3willbe savedinahigherlocation.
C163 Memorylocation3 Lastbutonefault
savedinahigherlocation.
-
Thecontentsofthememorylocation4willbe eliminatedfromthehistorybufferandcannotbe
C164 Memorylocation4
Lastbuttwofault
Thecontentsofthememorylocation4willbe eliminatedfromthehistorybufferandcannotbe readanylonger.
-
Memorylocation1willbedeleted(=noactivefault).
Page 61
Troubleshootin g and fault el imination
820XBA1097 8-3
8.3 Fault indications
Display Fault Cause Remedy
--- No fault - ­EEr E x ternal fault (TR I P-Set) Adigital input assigned to the
TRIP-Set function has been activated
Check external encoder
H05 Internal fault Contact Lenze LU Undervoltage DC-bus voltage too low
-
Check mains voltage
-
C heck supplymodule
OC1 Short circuit
Short circuit Find out cause of short circuit; check
cable
Excessivecapacitive charging current of the motor cable
U semotor cable which is shorter or of lower capacitance
OC2 Earth fault
Grounded motor phase Check motor; check cable
OC2Earthfault
Excessivecapacitive charging current of the motor cable
U semotor cable which is shorter or of lower capacitance
OC3 Ov erload inverter during
acceleration or short
Acceleration t ime tooshort (C012)
-
Increase acceleration time
-
Check driveselection
accelerationorshortcircui
t
Defective motor cable Check wiring Interturn fault in the motor C heck motor
OC4 Overload controllerduring
deceleration
Deceleration time tooshort (C013)
-
Increase deceleration time
-
Check theselection of thebrake resistoror connect the brake chopper
OC5 Ixtoverload
Fre quent and toolong acceleration processes with overcurrent
Check drive dimensioning
Permanent overload with I
motor
>1.05xI
Nx
OC6 Ov erload motor
Motor is thermally overloaded, for instance, because of
-
impermissible continuous current
-
Check driveselection
-
frequent or too long acceleration processes
-
C heck thesetting under C120
Page 62
Troubleshooting and fault elimination
8-4 820XBA1097
Display RemedyCauseFault
OH Heatsinktemperatureis
higherthanthevalueset inthecontroller
Ambienttemperature T
amb
>+40Cor+50C
-
Allowcontrollertocoolandensure ventilation
-
Checktheambienttemperaturein
thecontrolcabinet Heatsinkverydirty Cleanheatsink Incorrectmountingposition Changemountingposition
OH3 PTCmonitoring
Motortoohotbecauseof excessivecurrentorfrequentand toolongacceleration
Checkdrivedimensioning
PTCnotconnected ConnectPTCorswitchoffmonitoring
(C0585=3)
OH4 Overtemperatureunit Insideunittoohot
-
Reducecontrollerload
-
Improvecooling
-
Checkfaninthecontroller
OU Overvoltage
Mainsvoltagetoohigh Checkvoltagesupply
OU Overvoltage
Feedbackoperation Brakingoperation
-
Increasedecelerationtimes.
-
Foroperationwithbrakechoppers:
-Checktheselectionand connectionofthebrakeresistor
-Increasethedecelerationtimes
Earthleakageonthemotorside Checkmotorcableandmotorforearth
fault(disconnectmotorfrominverter)
OUE Overvoltage Mainsovervoltagelongerthan5s Checkmainsvoltage rSt Faultyauto-TRIPreset Morethan8faultmessagesin
10minutes
Dependsonthefaultmessage
Pr Faultyparametertransfer
viatheoperatingmodule
PAR1andPAR2aredefective.
Itisabsolutelynecessarytorepeatthe datatransferorloadthefactory settingbeforeenablingthecontroller.
Pr1 FaultyPAR1transfervia
theoperatingmodule
PAR1isdefective.
datatransferorloadthefactory settingbeforeenablingthecontroller.
Pr2 FaultyPAR2transfervia
theoperatingmodule
PAR2isdefective.
Page 63
Troubleshootin g and fault eli mination
820XBA1097 8-5
8.4 Reset of fault indications
TRIP
Aftereliminating thefault, the pulse inhibit willonlyberesetafterthe acknowledgement of TR I P.
Note!
Ifthe TRIPsource is still active, the TRIPcannot be reset.
Code Name
Possible set tings
IMPORTANT
Lenze Selection Info
C170§TRIP-reset
selection
-0- TRIP -reset by pressing the STP keyor a LO Wsignal at ctrl. enable
-1- Auto-TRIPreset
C171 Deceleration for
Auto-TRIP reset
0 0{1s}60
Page 64
Troubleshooting and fault elimination
8-6 820XBA1097
Function Youcanselectwhethertheactivefaultistoberesetautomaticallyormanually.
Auto-Tripresetdoesnotresetallfaultsautomatically.
Activation C170=-0-:
-
ManualTRIP-reset
-
STPkey
-
LOWsignalatterminal28
C170=-1-:
Auto-TripresetresetsthefollowingfaultmessagesafterthetimesetunderC171:
-OC3(overloadduringacceleration)
-OC4(overloadduringdeceleration)
-OC5(overload)
-OC6(I
ktswitch-off)
-OH(overtemperature)
-OUE(overvoltageinDCbus)
Important MainsswitchingalwaysresetsTRIP.
Withmorethan8auto-tripresetswithin10minutes,thecontrollersetsTRIPand indicatesrST(numeratorexceeded).
Page 65
Accessori es
820XBA1097 9-1
9 Accessories (Overview)
9.1 Accessories for all types
Name Order number
8201BBoperating module EMZ8201BB Diagno sisterminal (2.5 m cable) EMZ8272BB- V001 Diagno sisterminal (5.0 m cable) EMZ8272BB- V002 Diagno sisterminal (10 m cable) EMZ8272BB-V003 Digital display EPD203 Setpoint potentiometer ERPD0001k0001W Rotarybuttonfor potentiometer ERZ0001 Scale for potentiometer ERZ0002 RS232/485 fieldbusmodule EMF2102IB-V001 RS485 fieldbus module EMF2102IB- V002 Level converter for RS485 EMF2101IB PCsystem cable RS232/485 EWL0020 Optical fibre fieldbus module EMF2102IB- V003 Optical fibre adaptor for PLC0...40m EMF2125IB Supplyunit for opticalfibre adaptor 2125 EJ0013 InterBus-Smodule EMF2111IB PROFIBUSmodule EMF2131IB System bus module(CAN) EMF2171IB System bus module(CAN)with addressing EMF2172IB PTCmodule EMZ8274IB I/Omodule EMZ8275IB Monitor module EMZ8276IB Bipolarsetpoint module EMZ8278IB
Page 66
A ccessories
9-2 820XBA1097
9.2 Softw are
Name Order number
PCprogram for Global Drive controllers ESP-GDC1
9.3 Type- specific accessories
Name Order numbe r
8201 8202 8203 8204
E.l.c.b. EFA1C10A EFA1C16A EFA1C20A EFA1C20A Fuse EFSM- 0100ASB EFSM-0150ASB EFSM- 0200ASC EFSM- 0200ASC Fuse holder EFH30001 EFH30001 EFH30001 EFH30001 Mainsfilter type“A” EZN2-004A001 EZN2-008A001 EZN2- 013A001 EZN2- 017A001
Mainschoke ELN1-0900H005 ELN1-0500H009 ELN1-0350H014 ELN1- 0160H017 RFIfilter for operation: With mains choke EZF1-006A002 EZF1-009A002 EZF1-018A002 EZF1-018A002 Without mains choke EZF1-006A002 EZF1-009A002 EZF1- 018A002 inadmissible Motorfilter ELM3-030H003 ELM3-020H004 ELM3-010H010 ELM3-014H010 Sine filter EZS3- 003A001 EZS3-004A002 EZS3-007A001 EZS3-010A001 Brake module EMB8251-E EMB8251-E EMB8251-E EMB8251-E Swivelwall assembly EJ0001 EJ0001 EJ0001 EJ0001 DIN-rail assembly EJ0002 EJ0002 EJ0002 EJ0002 Fan for flat assembly EJ0003 EJ0003 EJ0003 EJ0003 Current-limiting module EMZ8201AB EMZ8201AB EMZ8203AB EMZ8203AB DC-bus fuse EFSM- 0060AWE EFSM- 0060AWE EFSM- 0100AWE EFSM-0160AWE Fuse holder EFH10001 EFH10001 EFH10001 EFH10001
Page 67
Index
820XBA1097 9-3
10 Index
A
Accelerationtimes,5-6 Adapt the motor, 5-8 Application, as directed, 1 -3 Application conditions, 2-1 Applications as directed, 1-3 Approvals, 2-1 Assembly
Variant reduced assembly depth, Type 8202-V002, 4-4 Withfixing rail, Types 820X, 4-3
Auto-TR I Preset, 8-5
C
Cable cross-sections, Singledrives,3-4
150 % overload, 3-4
Code table, 7 -2
Information on the, 7-2
Commissioning, 5 -1 Configuration, 7-1
Acceleration and deceleration times, 5-6 Basic information, 7-1 Codetable, 7-2 Current limit value, 5-7 Maximum field frequency, 5-4 Minimum field frequency,5-4
Connection
Control, Connection diagram, 4-12 Control cables, 4-10 Mains, 4-7 Motor, 4-7 Power,Circuit diagram, 4-9
Connection diagram
Control connections, 4-12 Power connection, 4-9
Connections, Power, 4-7 Controlcables, 4- 10 Control connections, 4-10 Control mode, permissible, 4-8, 5-8 Control terminals, 4-10
Overview, 4-10 Terminal assignment, 4-10
Controller, 1-1
Application as directed, 1-3 Labelling, 1-3
Cur rent limit , 5-7
Page 68
Index
9- 4 820XBA1097
D
Deceleration times, 5-6 Definitions of terminology used, 1-1 Degree of pollution, 2-1 Dimensions
8202-V002 reduced assemblydepth, 4-4 820Xwithfixingrail,4- 3 Controller, 3-4
Display
LED-, 8-1 Operating status, 8-1
Disposal, 1-4 Driveparameters, Factory setting, 5-3 Drive system, 1-1
E
Electrical installation, 4-6
Important notes, 4-6
EMC
Assembly, 4-13 CE-typical drive system, Installation, 4-13 Filters, 4-13 Grounding, 4-14 Installation, 4-13 Screening, 4-14
E nclosure, 2-1
F
Factory setting
Important drive parameters, 5-3 Short set-up, 5-2 Switch-on sequence, 5-2
Fault analysis, 8-2 Fault message s, 8-3
Reset, 8-5
Field frequency
Maximum, 5- 4 Minimum, 5-4
Frequency inverter. Siehe Controller Fuses, Single drives, 3-4
150 % overload, 3-4
G
G eneral data, 2-1
H
Historybuffer, 8-2
Structure, 8-2
Humidity class, 2-1
I
Initial switch-on, 5-1 Inputs
Analog, 4-11 Digital, 4-11
Installation,4-1
CE-typical drive system, 4-13
Assembly, 4-13 Filters, 4-13 Grounding, 4-14
Screening, 4-14 Electrical,4 -6 Mechanische, 4-1
Inst allation height, 2-1 Insulation strength, 2-1
Page 69
Index
820XBA1097 9-5
J
Jumper, Analog setpoint selection, 4-11
L
Labelling, Contr oller, 1 -3 LE D , 8-1 Legal regulations, 1-3 Liability, 1-4
M
Mains c onnection, 4-7 Mains-voltagecompensation, 5-11, 5- 13 Maloperation of the drive, 8-2 Manufacturer, 1-3 Mechanicalinstallat ion, 4-1 Messages, Fault, 8-3 Monitor output, 4-11 Motor, Adapt, 5-8 Motor cable, Screening, 4-7 Motor connec tion,4-7 Mounting positions,Types820X, 4-2
N
Noise emmission, 2- 1 Noise immunity, 2-1
O
Operating module, Fault display, 8-1 Operating status, Display, 8-1
Operation, Status display , 8-1 Operator’s safety, 2-4
Outputs, Analog, 4-11 Ov erspeeds, 2-4
P
Packaging, 2-1 Power connections, 4-7
R
Rated data, Types8201- 8204, 150 % overload, 3-2
Relayoutput, 4-11 Reset, Fault message, 8-5 Residualhazards, 2-4
S
Safety information, 2-1
for controllers to Low-Voltage Directive, 2-1 Layout, 2-3
Safety notes, Layout
Other notes, 2-3 Warning of damage to material, 2-3 Warning of danger to persons, 2-3
Scope of delivery , 1-2 Screening
EMC,4- 14 Motor cable, 4-7
Short set-up, 5-2 Switc h-on, Initial, 5-1 Switch-onsequence,Fact orysetting, 5-2
Page 70
Index
9- 6 820XBA1097
T
Technical data, 2-1
General data/application conditions, 2-1
Temperature ranges, 2-1 Transport, storage, 2-1 TRIP, 8-5 Troubleshooting, 8-1
Display at the operating module , 8-1 Fault analysisusing the history buffer , 8-2 Fault indication, 8-3 LED, 8-1 Maloperation of the drive, 8-2 Reset of fault indications, 8-5 TRIP, 8-5
U
U nit protection, 2-4
V
Variant, V002,4-4 Vibration resistance, 2-1 Vmin setting, Drives with special motors,
5-12
W
Warranty, 1- 4
Loading...