Pass & Seymour
Surface
Mounting
Screw Hole
Ceiling
Coverage Side View
High Bay • Line Voltage • Passive Infrared • Occupancy Sensor for Dry Locations
Grande hauteur • Tension secteur • Infrarouge passif • Détecteur de présence pour environnement sec
Montaje alto • Voltaje de línea • Infrarrojo pasivo • Sensor de ocupación para lugares secos
No: 341018 – 9/12 Rev. B U.S. Patents: 5640113, 5804991
Catalog Number(s) • Numéro(s) de Catalogue • Les Numéros de Catalogue: PSHB120277Lx
Country of Origin: Made in Taiwan • Pays d’origine: Fabriqué à Taïwan • País de origen: Hecho en Taiwán
Installation Instructions • Instrucciones de Instalación • Notice d’Installation
®
CAUTION
PSHB120277L3
Turn power off at the circuit breaker before installing
sensor.
SPECIFICATIONS
Voltages .............................................120/277VAC, 60Hz
Load Requirements
@ 120VAC, 60Hz ...........0-800W ballast or tungsten
@ 277VAC, 60Hz ............................0-1200W ballast
@ 120VAC .......................................................1/6 hp
LENS
Hallway L1 ........ 40 ft. mounting height, 60 ft. x 20 ft.
L2 ..................20 ft. mounting height, 40 ft. diameter
PSHB120277L1
L3 ..................40 ft. mounting height, 60 ft. diameter
PSHB120277L2
DESCRIPTION AND OPERATION
The PSHB120277Lx occupancy sensors are designed for automatic lighting control in warehouse high bay dry
location applications. All models contain a passive infrared sensor (PIR). The PSHB120277Lx series sensors are
modular and are made up of a Power Module and a Lens. The coverage area is determined by the lens module.
There are three different lenses available. See the Coverage section for more information.
All models in the PSHB120277Lx series use a set of DIP switches to set the time delay and PIR sensitivity, as
explained below.
COVERAGE
Coverage patterns, density and range, are determined by the type of Lens attached to the PSHB120277Lx.
PSHB120277L1
The L1 Lens offers linear patterns best suited for high bay aisleway applications. The Fresnel lens is designed to
detect walking motion when mounted at or around 40’. In optimal conditions, the lens has a 60’ linear detection
range.
Ceiling Side View
0
10
20
30
40
30 20 10 0102
10
0
10
20
0
40 30 20 10 010203040
Top View L1
20 ft
PSHB120277L2
The L2 Lens offers 360° coverage and is best suited for open area and aisleway coverage in high bay applications.
The L2 is a multi-cell, multi-tier Fresnel lens offering a high density coverage pattern that spreads over a 40’
diameter area at a height of 20’.
Ceiling Side View
5
10
15
20
151820 15 18 20
039636912 12
20
10
0
10
20
Top View L2
40 ft
20 10 01020
PSHB120277L3
Similar to the L2 Lens, the L3 offers 360° coverage, and is best suited for open areas and aisleways in high bay
applications. The L3 is a multi-cell, multi-tier Fresnel lens offering a high density coverage pattern.The L3
is designed for mounting at heights between 30’ to 40’, with a coverage area up to 60’ in diameter when mounted
at 40’.
10
20
30
40
Ceiling
03612273436122734 20 20
Side View Top View L3
34
27
20
12
6
3
0
3
6
12
20
27
34
20
20
036 12 27 3436122734
0663 3
68 ft
INSTALLATION
Turn the power off at the circuit breaker before installing the sensor.
1. Determine the mounting location appropriate to the features of the power module and the coverage area. Careful
consideration must be given to sensor placement. Avoid placing the sensor where the edge of the xture,
shelving or other obstructions may block the sensor’s line of sight. Mount the sensor below the edge of the xture
and away from the uorescent lamps so that the heat from the lamps does not affect the sensor.
2. Make sure that you have the appropriate accessories for the sensor mounting conguration. (See Mounting
Options.)
3. Assemble any necessary mounting accessories and attach them to the power module, making sure that the
ying leads from the power module are accessible.
4. Connect the line voltage and load wires to the sensor leads as shown in the Wiring Diagram for the unit’s
application.
• Do not allow bare wire to show.
• Make sure all connections are secure.
5. Restore power from the circuit breaker.
CAUTION
WIRING
Neutral
Hot
Black
White
Red
Load
PSHB120277Lx
MOUNTING OPTIONS
The PSHB120277Lx can be attached to the xture or junction box using the back box and chase nipple or directly
to the xture surface via the two screw holes provided in the Power Module (see Surface mounting below). The
Extender Module (PSHBEM) allows attaching the sensor to the side of the xture in a number of congurations
using provided chase nipples.
Back box mounting requires a standard 1/2” knockout for the chase nipple. The Power Module mounts to the back
box with a bayonet type tting requiring a slight twist of the units to separate them or lock them into place. The box
comes ready for side mounting. It can be modied for rear mounting as follows:
1. Pop out the cap in the rear knockout.
2. Un-snap the chase nipple from the side mount and snap into the rear mounting hole.
3. Use the cap to close the side mount hole.
AVERTISSEMENT
Coupez l’alimentation du disjoncteur avant
d’installer le détecteur.
SPÉCIFICATIONS
Voltages .........................................120/277 V c.a., 60 Hz
Conditions de charge
à 120 V c.a., 60 Hz ........0-800 W ballast ou tungstène
à 277 V c.a., 60 Hz ...........................0-1200 W Ballast
à 120 V c.a. .........................................................1/6 hp
LENTILLE
L1 pour couloir ....... Hauteur de montage de 12,19 m,
18,28 m x 6,09 m.
L2 ............................. Hauteur de montage de 6,09 m,
diamètre de 12,19 m.
L3 ...........................Hauteur de montage de 12,19 m,
diamètre de 18,28 m.
PRECAUCIÓN
Desconecte la alimentación del disyuntor antes de
instalar el sensor.
ESPECIFICACIONES
Voltajes ...........................................120/277 V CA, 60 Hz
Requerimientos de carga
A 120 V CA, 60 Hz .......0 a 800 W balasto o tungsteno
A 277 V CA, 60 Hz ......................Balasto de 0-1200 W
A 120 V CA..........................................................1/6 hp
LENTE
Hallway L1 ...... Altura de montaje de 12 m (40 pies),
18 m x 6 m (60 pies x 20 pies)
L2 ..................... Altura de montaje de 6 m (20 pies),
diámetro de 12 m (40 pies)
L3 ................... Altura de montaje de 12 m (40 pies),
diámetro de 18 m (60 pies)
4. The chase nipple provided can be pushed into a standard 1/2” knockout in a metal xture [max of 1 mm (0.04”)
thick metal] without the need for the included internal nut. The nut can be used for added security if necessary.
The PSHBEM extender module allows threading the wires through its chase nipples and into the xture for
connection. The two sides of the PSHBEM are then snapped together to protect the wires. The short chase nipple
is designed to snap into the PSHBEM connection box while the longer chase nipple snaps into any metal xture or
connection box with a standard knockout. The caps on the PSHBEM can be removed in various congurations to
allow moving the chase nipples and adjusting the height of the sensor on the xture.
Using the back box and PSHBEM Extender Module
PSHBEM
Extender
Module
PSHBLx
Lens
Back
Box
or
E
S
O
L
C
O
P
E
N
Alignment Guides
Surface mounting requires holes in the xture to pass wires
and attach two #6-32 screws through the surface mounting
screw holes on the component side of the Power Module as shown.
Light Level
Adjustment
Trimpot
Surface
Mounting
Detection
Indicator LED
PIR Sensor
ADJUSTMENTS
Sensor factory pre-sets are as follows (default settings are bold):
Factory Switch Settings
1 2 3 4 5 6 7 8 9 10
ON OFF OFF OFF OFF ON ON OFF OFF OFF
PIR Sensitivity (switches 1 & 2) ....................... Medium 85%
Time Delay (switches 3-7) ............................... 15 Minutes
Overrides (switches 8-10) ............................... See table below for each model.
N/A = not applicable, no effect.
PIR Sensitivity (Switches 1-2)
The factory setting of 85% is suitable for most applications, but it may be necessary to adjust the PIR sensitivity
if there is any environmental interference causing false triggers or if sensitivity needs to be increased for your
particular application. Use DIP switches 1 & 2 to adjust sensitivity.
Switch 1 2 PIR SENSITIVITY
OFF OFF 100% (HIGH)
ON OFF 85% (NORMAL)
OFF ON 75% (MEDIUM )
ON ON 60% (LOW)
Time Delay (Switches 3-7)
Use DIP switches 3 to 7 to adjust the time delay.
Switch 3 4 5 6 7 TIME DELAY
ON ON ON ON ON 15 seconds
OFF ON ON ON ON 5 minutes
OFF OFF ON ON ON 10 minutes
OFF OFF OFF ON ON 15 minutes
OFF OFF OFF OFF ON 20 minutes
OFF OFF OFF OFF OFF 30 minutes
PIR Override (Switches 8-10)
Overrides can disable control features of the PSHB120277Lx power module. The table below describes the override
functions of each PSHB120277Lx model.
IMPORTANT START-UP INFORMATION
A 60-second start-up period occurs during initial installation and after a power failure of 5 minutes or more. After
applying power to the sensor wait at least 60 seconds for the sensor to begin detecting occupancy and the load to
turn ON. It may turn ON during the start-up period, depending on the state of the relay when power was off.
• If the sensor detects occupancy during the start-up, when the load turns ON it stays ON as long as the sensor
continues to detect motion, plus the Time Delay.
• If no occupancy is detected during the 60-second start-up, the load may come on anyway during the start-up.
If no occupancy is detected by the time the start-up is complete, the relay opens and the load turns OFF.
MODEL/SWITCH # 8 9 10 FUNCTIONALITY LOAD EFFECT
PSHB120277Lx
PIR sensor, 1 load relay
OFF N/A N/A Occupancy control enabled Controlled by Occupancy
ON N/A N/A Override PIR Load always ON
TROUBLESHOOTING
If you suspect improper operation, review the Start-Up information. After start-up, the sensor will open or close the
relay to correspond to the occupancy status of the area. When power to the sensor is lost, the relay(s) close, turning
on the load if the load still has power.
To quickly test the unit, set the time delay to minimum. Wait for the start-up period to end. Move out of the sensor’s
view. Lights should turn OFF after 15 seconds. Move into the sensor’s view. The sensor’s Red LED should blink and
the lights should turn ON.
Red LED on power module does not blink:
Check sensor wire connections. Verify the neutral wire is tightly secured.
Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least one minute, then
a) Turn OFF power to the sensor.
b) The relay(s) will close.
c) Turn ON power to the sensor.
d) The load should come ON. If not, continue with step 2.
2. Check power connections to the light xture.
3. Check all sensor wire connections. Verify the load wire is tightly secured.
Lights will not turn OFF:
03612273436122734 20 20
0
Ceiling
Coverage Side View
1. If there is no motion from people or equipment in the sensor’s view but the red LED blinks, look for any nearby
source of infrared energy (heat) in motion, such as turbulent air from a heating or cooling supply, or other
sources such as heat from the uorescent lamps in the xture.
• Mount the sensor so that it’s lens is below the edge of the xture and does not directly view the lamps.
• Divert the air supply away from the sensor, or move the sensor.
2. Verify time delay set in switches 3-7. The time delay can be set from 15 seconds to 30 minutes. Ensure that the
time delay is set to the desired delay and that there is no movement within the sensor’s view for that time period.
3. Check PIR and Light Level Override DIP switch settings. If all control functions are overridden the load stays ON.
4. Check sensor wire connections. Verify load and neutral wires are secure.
INSTRUCTIONS EN FRANÇAIS
ORDERING INFORMATION
Catalog # Description
A complete high bay line voltage occupancy sensor consists of:
PSHB120277L1 High Bay Sensor 120/277 VAC with coverage 60' x 20' @ 40' mounting height.
PSHB120277L2 High Bay Sensor 120/277 VAC with coverage 40' diameter @ 20' mounting height.
PSHB120277L3 High Bay Sensor 120/277 VAC with coverage 60' diameter @ 40' mounting height.
PSHBEM Extender module with 2 chase nipples and nuts –
1 short (0.88") for connection to plastic, 1 long (1.24") for connection to metal
All units are White.
WARRANTY INFORMATION
Legrand/Pass & Seymour warranties its products to be free of defects in materials and workmanship for a
period of ve (5) years. There are no obligations or liabilities on the part of Legrand/Pass & Seymour for
consequential damages arising out of, or in connection with, the use or performance of this product or other indirect
damages with respect to loss of property, revenue or prot, or cost of removal, installation or reinstallation.
DESCRIPTION ET FONCTIONNEMENT
Les détecteurs de présence PSHB120277Lx sont conçus pour le contrôle de l’éclairage automatique pour des
applications en environnement sec et des entrepôts de grande hauteur. Tous les modèles comprennent un
détecteur à infrarouge passif (PIR). Les détecteurs série PSHB120277Lx sont modulaires et constitués d’un module
d’alimentation et d’une lentille. La zone de couverture est déterminée par le module de lentille. Trois différents types
de lentilles sont disponibles. Voir la section Couverture pour plus d’informations.
Tous les modèles de la série PSHB120277Lx utilisent un ensemble d’interrupteurs DIP pour régler la temporisation
et la sensibilité PIR comme indiqué ci-dessous.
COUVERTURE
Les schémas de couverture, la densité et la plage sont déterminés par le type de lentille xée sur le
PSHB120277Lx.
PSHB120277L1
La lentille L1 propose des schémas linéaires qui conviennent davantage aux couloirs de grande hauteur. La lentille
Fresnel est conçue pour détecter les mouvements de marche lorsqu’elle est montée à environ 12,19 m. Dans des
conditions optimales, la lentille dispose d’une plage de détection linéaire de 18,28 m.
Plafond Vue latérale
0
10
20
30
40
30 20 10 0102
20
10
0
10
20
0
40 30 20 10 010203040
Vue supérieure L1
20 ft
PSHB120277L2
La lentille L2 propose une couverture à 360° et convient davantage aux endroits ouverts et aux voies de passage
de grande hauteur. La L2 est une lentille Fresnel multi-cellules et multi-niveaux qui offre un schéma de couverture
haute densité couvrant une zone de plus de 12,19 m de diamètre à une hauteur de 6,09 m.
Plafond Vue latérale
5
10
15
20
151820 15 18 20
039636912 12
Vue supérieure L2
20
10
0
10
20
20 10 01020
40 ft
PSHB120277L3
Tout comme la lentille L2, la L3 propose une couverture à 360° et convient davantage aux endroits ouverts et
aux voies de passage de grande hauteur. La L3 est une lentille Fresnel multi-cellules et multi-niveaux qui offre un
schéma de couverture haute densité. La L3 est conçue pour un montage à des hauteurs entre 9,14 m et 12,19 m,
avec une zone de couverture allant jusqu’à 18,28 m de diamètre lorsqu’elle est montée à 12,19 m.
Plafond
10
20
30
40
Vue latérale Vue supérieure L3
27
20
12
6
3
0
3
6
12
20
27
34
20
20
036 12 27 3436122734
0663 3
68 ft
INSTALLATION
Coupez l’alimentation du disjoncteur avant d’installer le détecteur.
1. Déterminez l’emplacement de montage approprié selon les fonctions du module d’alimentation et la zone de
couverture. Prenez bien en considération le positionnement du détecteur. Évitez de placer le détecteur sur les
bords de l’appareil, d’une étagère ou autre obstacle susceptibles de bloquer le champ de vision du détecteur.
Montez le détecteur en dessous du bord de l’appareil et à l’écart des lampes uorescentes de façon à ce que la
chaleur des lampes n’affecte pas le détecteur.
2. Assurez-vous de disposer des accessoires appropriés pour la conguration de montage du détecteur. (voir
Options de montage.)
3. Assemblez tous les accessoires de montage nécessaires et xez-les sur le module d’alimentation, en vous
assurant que les connecteurs volants du module d’alimentation sont accessibles.
4. Branchez la tension secteur et les câbles de charge sur les connecteurs du détecteur comme indiqué dans le
Schéma de câblage applicable à l’unité.
• Ne laissez pas de ls nus apparents.
• Assurez-vous que tous les branchements sont sécurisés.
5. Rétablissez l’alimentation du disjoncteur.
AVERTISSEMENT
CÂBLAGE
OPTIONS DE MONTAGE
Le PSHB120277Lx peut être xé sur l’appareil ou la boîte de jonction à l’aide de la boîte électrique et du mamelon
de traversée ou directement sur la surface de l’appareil à l’aide des deux orices pour vis fournis sur le module
d’alimentation (voir Montage en surface ci-dessous). Le module d’extension (PSHBEM) permet de xer le détecteur
sur le côté de l’appareil dans un certain nombre de congurations à l’aide des mamelons de traversée fournis.
Le montage de la boîte électrique nécessite une entrée défonçable standard de 1,27 cm pour le mamelon de
traversée. Le module d’alimentation se monte sur la boîte électrique à l’aide d’une pièce de type à baïonnette en
tournant légèrement les unités pour les détacher ou les verrouiller en position. La boîte est livrée prête pour le
montage latéral. Elle peut être modiée pour un montage arrière de la manière suivante :
1. Sortez l’embout dans l’entrée défonçable arrière.
2. Déclipsez le mamelon de traversée du montage latéral et clipsez-le dans l’orice de montage arrière.
3. Utilisez l’embout pour fermer l’orice de montage latéral.
4. Le mamelon de traversée fourni peut être poussé dans une entrée défonçable standard de 1,27 cm dans un
appareil en métal [épaisseur de métal de 1 mm max.] sans avoir recours à un écrou interne. L’écrou peut être
utilisé pour plus de sécurité si nécessaire.
Le module d’extension PSHBEM permet d’introduire les câbles à travers les mamelons de traversée et dans
l’appareil pour le branchement. Les deux côtés du PSHBEM se clipsent ensuite ensemble pour protéger les
câbles. Le mamelon de traversée court est conçu pour se clipser dans la boîte de raccordement PSHBEM tandis
que le mamelon de traversée plus long se clipse dans n’importe quel appareil en métal ou boîte de raccordement
dotée d’une entrée défonçable standard. Les embouts présents sur le PSHBEM sont amovibles dans différentes
congurations pour permettre le déplacement des mamelons de traversée et le réglage de hauteur du détecteur sur
l’appareil.
Utilisation de la boîte électrique et du module d’extension PSHBEM
Le montage en surface requiert des orices dans l’appareil pour
passer les câbles et xer deux vis n° 6-32 à travers les orices
de vis de montage de surface sur le côté du composant du module
d’alimentation comme indiqué.
RÉGLAGES
Les paramètres d’usine du détecteur sont les suivants (les paramètres par défaut sont en gras) :
Réglages d’usine des interrupteurs
1 2 3 4 5 6 7 8 9 10
MARCHE OFF OFF OFF OFF MARCHE MARCHE OFF OFF OFF
Sensibilité PIR (interrupteurs 1 et 2)................ Moyen 85 %
Temporisation (interrupteurs 3 à 7).................. 15 minutes
Dérogations (interrupteurs 8 à 10) .................. Voir le tableau ci-dessous pour chaque modèle.
N/A = non applicable, sans effet.
Sensibilité PIR (interrupteurs 1 et 2)
Le réglage en usine de 85 % convient pour la plupart des applications. Cependant, il peut s’avérer nécessaire de
régler la sensibilité PIR si une interférence environnementale provoque des déclenchements intempestifs ou si
la sensibilité doit être augmentée pour une application donnée. Utilisez les interrupteurs DIP 1 et 2 pour régler la
sensibilité.
Interrupteur 1 2 SENSIBILITÉ PIR
OFF OFF 100 % (ÉLEVÉ)
MARCHE OFF 85 % (NORMAL)
OFF MARCHE 75 % (MOYEN)
MARCHE MARCHE 60 % (FAIBLE)
Temporisation (interrupteurs 3 à 7)
Utilisez les interrupteurs DIP 3 à 7 pour régler la temporisation.
Interrupteur 3 4 5 6 7 TEMPORISATION
MARCHE MARCHE MARCHE MARCHE MARCHE 15 secondes
OFF MARCHE MARCHE MARCHE MARCHE 5 minutes
OFF OFF MARCHE MARCHE MARCHE 10 minutes
OFF OFF OFF MARCHE MARCHE 15 minutes
OFF OFF OFF OFF MARCHE 20 minutes
OFF OFF OFF OFF OFF 30 minutes
Dérogation PIR (interrupteurs 8 à 10)
La dérogation peut désactiver les fonctions de contrôle du module d’alimentation PSHB120277Lx. Le tableau
ci-dessous décrit les fonctions de dérogation de chaque modèle PSHB120277Lx.
INFORMATIONS DE DÉMARRAGE IMPORTANTES
Une période de démarrage de 60 secondes intervient au cours de l’installation initiale et après une coupure de
courant de 5 minutes ou plus. Après avoir mis le détecteur sous tension, attendez au moins 60 secondes pour que
le détecteur commence à détecter une présence et que la charge se mette en MARCHE. Elle peut se mettre en
MARCHE pendant la phase de démarrage, en fonction de l’état du relais lorsque l’alimentation était coupée.
• Si le détecteur détecte une présence pendant le démarrage, lorsque la charge se met en MARCHE, cette
dernière reste en MARCHE aussi longtemps que le détecteur continue de détecter des mouvements, en tenant
également compte de la temporisation.
• Si aucune présence n’est détectée pendant les 60 secondes du démarrage, la charge peut se mettre en
MARCHE à n’importe quel moment pendant le démarrage. Si aucune présence n’est détectée à la n du
démarrage, le relais s’ouvre et la charge se met à l’ARRÊT.
MODÈLE/N°
D’INTERRUPTEUR 8 9 10 FONCTIONNALITÉ EFFET DE CHARGE
PSHB120277LX
Détecteur PIR, 1 relais de charge
OFF N/A N/A
MARCHE N/A N/A Dérogation PIR Charge toujours en MARCHE.
Contrôle de présence
activé
Contrôlé par la présence.
DÉPANNAGE
Si vous pensez que le module ne fonctionne pas correctement, consultez les informations de Démarrage. Après
le démarrage, le détecteur ouvrira ou fermera le relais pour s’aligner sur l’état de présence sur la zone. Lorsque
l’alimentation du détecteur est coupée, le(s) relais se ferme, mettant ainsi la charge en MARCHE si cette dernière
est toujours alimentée.
Pour tester rapidement l’unité, réglez la temporisation au minimum. Attendez que la période de démarrage se
termine. Écartez-vous du champ de vision du détecteur. La lumière doit normalement s’éteindre au bout de
15 secondes. Placez-vous dans le champ de vision du détecteur. La DEL rouge du détecteur doit clignoter et
l’éclairage doit s’allumer.