Legrand OS300S User Manual

OS300S
120/277VAC
PIR Wall Switch
SPECIFICATIONS
Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . .120/277VAC, 50/60Hz
@120VAC . . . . . . . . . . . . . . . . . . .0-800W tungsten or ballast
@277VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0-1200W ballast
Load Type Compatibility . . . . . . . . . .incandescent, fluorescent,
magnetic or electronic ballast
Time Delay Adjustment . . . . . . . . . . . . . . . . . . .5 to 30 minutes,
user-selectable or automatic
Sensitivity Adjustment . . . . . . . . . . . . . . . . . . . . . . . .High or 50%
Alerts . . . . . . . . . . . . . . . .Selectable Audible and/or Light Flash
Horsepower Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/6 HP
Installation Instructions
US Patents: 4,787,722
Syracuse, NY 13221
4,874,962
800.223.4185
UNIT DESCRIPTION AND OPERATION
The OS300S is a passive infrared wall switch that turns lighting ON and OFF based on occupancy and ambient light levels. SmartSet™ technology allows the sensor to be installed without any adjustments. This technology allows the sensor to automatically adjust to the usage patterns in the space. Alternate operating modes, selected by DIP switch settings, can be combined to create the ideal custom control.
Turning The Lights On
Auto On Mode The OS300S will turn lights ON and OFF automatically
Manual On Mode Occupants must turn ON the lights by pressing the
Button Override The lights can be turned ON or OFF by pressing the
Time Delays
The OS300S time delay holds the lights ON until no motion is detected for a time period of 5 seconds to 30 minutes, at which point it turns the lights OFF. The sensor can automatically select the time delay, or the user can choose a fixed delay.
SmartSet™ Time Records typical occupancy patterns. Using this history Delays (which is constantly updated), it chooses an optimal
Fixed Time Delay DIP switch selections provide fixed time delays of 5,
based on occupancy. If the lights are turned OFF manually, automatic-ON operation will not be reenabled until no motion is detected for five minutes. This feature prevents lights from accidentally being turned ON after they were deliberately turned OFF.
Auto-ON/OFF button. The sensor will then keep the lights ON until no motion is detected for the selected time delay period. There is a 30 second reset delay. If motion is detected during this time, the sensor will turn the lights back ON automatically. After the reset delay time has elapsed, the Auto-ON/OFF button must be pressed to turn the lights ON.
Auto ON/OFF button, regardless of the operating mode.
time delay from 7 minutes (when space is usually vacant) up to 30 minutes (for times that show heavy usage). SmartSet behavior starts immediately, and is refined continually as history is collected.
10, 15, 20, 25 or 30 minutes.
Call 800.223.4185 for Technical Support
Walk-Through Use for rooms that have frequent walk-through traffic Mode (ie. room that accepts mail deliveries). The OS300S
Test Mode To test the sensor, a short time delay of 5 seconds is
turns the lights OFF three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay applies.
set as the default (SmartSet/Test). Test Mode cancels automatically after five minutes, or if a fixed time delay is selected. To restart the Test Mode, change the time delay switch setting to any fixed amount and then return it to the SmartSet/Test setting.
Light Level Control
Light Level Control Lights are held OFF, even when the controlled area is Enabled occupied, as long as the ambient light level is greater
than a chosen threshold level. The light level can be set with the overhead lights ON or OFF.
Sensitivity Adjustment
The OS300S constantly monitors the controlled environment and automatically adjusts to avoid common ambient conditions that can cause false detections, while providing maximum coverage.
High Default setting. Suitable for most applications.
Low Reduces sensitivity by approximately 50%. Useful in
cases where the sensor is detecting movement outside of the desired area (also consider masking the lens) and where heat sources cause unnecessary activation.
Alerts
The OS300S can provide alerts as a warning before the lights turn OFF.
Light Flash Alert Lights will flash OFF for one second, one minute
Audible Alerts Sensor will “chirp” twice, at one minute and at
Dual Alerts When both Light Flash Alerts and Audible Alerts are
No Alerts No warning will be provided.
before they will be turned OFF by the sensor.
30 seconds before turn-OFF. A distinct alert will sound 10 seconds before the lights go OFF.
selected, the Audible Alert at one minute remaining is replaced by the Light Flash Alert.